Spec 2
Spec 2
Spec 2
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. This Section includes the following hangers and supports for HVAC system:
1. Steel pipe hangers and supports.
2. Trapeze pipe hangers.
3. Metal framing systems.
4. Thermal-hanger shield inserts.
5. Fastener systems.
6. Pipe stands.
7. Equipment supports.
1.02 DEFINITIONS
A. MSS: Manufacturers Standardization Society for The Valve and Fittings Industry Inc.
1.03 REFERENCES
E. NFPA 13
B. Design supports for multiple pipes, including pipe stands, capable of supporting
combined weight of supported systems, system contents, and test water.
D. Design seismic-restraint hangers and supports for piping and equipment and obtain
approval from authorities having jurisdiction.
A. The need for a seismic restraint system shall be determined by establishing the
Seismic Design Category of the project based on the provisions of IBC 2009. This
shall be done by considering the Occupancy Category and Site Class of the project
along with the Component Importance Factor of individual elements of the HVAC
piping systems.
B. Provide a seismic bracing system to restrain piping from excessive motion when
subjected to horizontal seismic forces, to prevent damage to adjacent equipment and
building structure. Bracing shall permit thermal expansion of pipe and ensure that
vibration isolators are not short-circuited.
C. Design of the seismic bracing system shall be provided by the manufacturer based on
as-built drawings and approved by the Engineer.
1.06 SUBMITTALS
B. Compliance statement must include response to all the points under Quality
Assurance.
C. Product technical literature for each type of hanger / support and seismic restraint.
D. Shop drawings for multiple piping supports and trapeze hangers. Include design
calculations and indicate size and characteristics of components and fabrication
details.
A. Pipe hangers and supports shall be in accordance with MSS SP58 (Pipe Hangers and
Supports – Materials, Design and Manufacture).
C. For installations where the hangers and supports are expected to be exposed to harsh
corrosive conditions, such as areas with high relative humidity or high salt content in
the air, these shall be hot dip galvanized, according to ASTM A123.
D. Design and preparation of Shop Drawings and calculations for each multiple pipe
support, trapeze and pipe anchor shall be done by a qualified engineer.
F. All gasket used as separation between pipe and hangers shall be manufactured from
EPDM only. Third party test certificates shall be furnished to establish the grade of
elastomer.
G. Each hanger and support shall have the manufacturer’s name, part number and
country of manufacture engraved on it.
H. All hangers and supports shall be manufactured at an ISO 9001, ISO 14001 and ISO
18001 certified facility. Manufacturer’s ISO certificates, clearly stating Pipe Supports
within the scope of registration, shall be furnished.
I. Country of Origin certificate shall accompany supplies, indicating the actual place of
manufacture of goods.
J. Pipe hangers and supports for all piping services shall be from the same manufacturer.
N. Specified field fabricated items shall be made from quality structural steel. All holes
required shall be drilled and not gas cut. Give two (2) coats of primer and one coat of
zinc rich paint prior to installation.
O. Cutting, welding or any such operation, which damages the finish, is not permitted on
galvanized or other factory finished surfaces.
P. All duct and pipe supports should be fabricated from hot dipped galvanized angles and
channels. The welding joints and the cut ends should be protected with zinc rich paint
before installed.
A. Deliver products to site, store and protect under provisions of Division1 General
requirements..
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 Subject to compliance with the requirements of the Contract Documents, products to
be provided shall be from the manufacturer having minimum five (5) years of
experience in the same product and approved by the Engineer.
A. Hangers for all services shall provide means of vertical pipe level adjustment after
installation.
C. Heavy-duty steel trapezes to support multiple pipes shall be designed for the
combined weight of pipe, water and adjacent fittings, and field fabricated from ASTM
A36 structural steel channel.
E. Hangers and supports shall be made from mild steel as standard. For severely
corrosive conditions, as determined by the Engineer, provide stainless steel (304 / 316
as required).
KEO/21-7387-0004 23 0529 / 4 Hangers and Supports for Piping and Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
F. Dielectric Protection – Steel pipe hangers and supports shall be furnished with fitted
EPDM gasketing when installed with any type of non-ferrous pipe. EPDM gasket with
Class 1 fire rating classification shall be provided where fire resistant lining is deemed
necessary by the project designer.
G. For insulated piping, rubber support inserts shall be provided at all pipe support
locations to prevent crushing of insulation. Rubber support inserts with Class 0 fire
rating classification shall be provided where fire resistant rubber support inserts are
deemed necessary by the project designer.
H. Hangers shall closely fit the outer diameter of plain or insulated pipe. Oversized
hangers shall not be accepted.
J. Hangers and supports shall be selected and installed to ensure thermal pipe
movement is axially guided into expansion devices and build up of pipe stress is
minimised.
K. Riser piping support system design shall ensure pipe is adequately anchored to resist
imposed loads and thrust. Risers shall be guided to prevent buckling, while permitting
axial pipe movement. Support system shall isolate the pipe thermally and acoustically
from building structure. Anchors and guides specially designed for riser piping shall be
installed.
L. Piping shall be braced to resist seismic forces as per the ‘Seismic Restraint
Requirements’ section.
M. Vibration isolators shall be provided at first five pipe hanger and support locations
adjacent to isolated rotating mechanical equipment, to minimise transmission of noise
and vibration to the building structure.
D. Ferrous piping up to 150 mm (6 inch) nom. Dia.: Adjustable galvanized steel clevis
completes with galvanized steel pipe covering shield for insulated piping.
A. Provide adjustable clevis hangers (MSS Type 1) for all individually suspended piping
where provision for thermal expansion and contraction is not required.
B. Clevis hangers shall have a solid steel bolt with threaded end as the cross rod. Cross
rod made from threaded rod or fully threaded bolt will not be accepted.
C. For insulated pipe where effective outer diameter does not correspond to a standard
pipe size, intermediate sizes of clevis hangers shall be provided to ensure a close fit.
Oversized hangers will not be accepted.
D. Clevis hangers used with any type of non-ferrous piping shall be additionally fitted with
EPDM gasket lining to prevent direct contact between dissimilar materials.
E. Provide U-Strap clamps (MSS Type 26) or U-Bolts (MSS Type 24), as directed by the
Engineer, for fixing pipe to channel where multiple pipes are supported on a trapeze
and provision for thermal expansion and contraction is not required.
F. U-Strap clamps shall have slotted mounting holes to facilitate alignment with holes
drilled in channel.
G. U-Bolts shall be supplied with two nuts. U-Bolts made from threaded rod shall not be
accepted.
H. For installation with non-ferrous pipe, U-Strap clamps shall be fitted with EPDM gasket
lining and U-Bolts shall be fitted with a full EPDM sleeve. Additionally, a rubber strip
shall be provided between the pipe and channel.
I. Provide roller supports or Teflon based slide assemblies - for all chilled or hot water
piping straight runs over 20m without changes in direction and for any other situation
where pipe requires to be allowed to move axially to prevent build up of stress.
1. The type of support provided shall be one of the following, as directed by the
Engineer : Pipe roller set (MSS Type 41)
2. Roller stand / roller chair (MSS Type 44)
3. Adjustable roller hanger (MSS Type 43)
4. Adjustable roller stand (MSS Type 46)
5. Clamp shoe slide assembly (MSS Type 35)
J. Complete roller supports, including the rolls, shall have a full steel construction.
K. Roller bolts shall be solid steel with threaded end. Use of threaded rod or fully threaded
bolt through the roll will not be accepted.
M. For trapeze mounted parallel pipes, the roller supports or slide assemblies shall be
mounted on the channel.
N. For non-ferrous pipe where provision is required for thermal expansion and
contraction, clamp shoe slide assemblies with fitted EPDM gasket lining shall be
provided.
O. For individually supported pipe above 80mm running close to the floor, where provision
for thermal expansion and contraction is not required, provide adjustable pipe
stanchion saddles (MSS Type 38) with vertical leveling arrangement and U-Bolt for
securing the pipe. The saddle shall be mounted on a floor stanchion comprising steel
base flange and welded pipe upright column.
P. For pipe 80mm or smaller, running close to the floor, provide a structural steel base
and fix pipe to channel using U-Strap clamps or U-Bolts, as directed by the Engineer.
A. Ferrous piping up to 150 mm (6 inch) nom. dia.: Adjustable pipe stanchion saddle
support complete with U-bolt, stand pipe with adjuster and floor flange, use galvanized
steel pipe covering shield for insulated piping.
B. Ferrous piping over 150 mm (6 inch) ND: Cast iron pipe roll with base and stand. RCC
/ structural steel pedestals shall be provided, as appropriate, to locate the base. Pipe
covering protection saddle shall be used for insulated piping.
A. The overall support system for all riser piping shall be implemented based on
manufacturer recommendations, which shall ensure riser piping is appropriately
anchored, guided and stabilized and expansion devices are permitted to function
properly.
B. Chilled water, hot water and condenser water riser piping above 100mm size shall be
installed with engineered all-directional acoustic pipe riser anchors and acoustic pipe
riser guides.
C. Acoustic anchors shall be capable of resisting all imposed loads and thrust acting at
the anchor location. They shall have a telescoping design incorporating a substantial
fabric reinforced neoprene element, to reduce structural transmission of noise from
piping and prevent formation of a thermal bridge at anchor location.
D. The anchors shall have a minimum seismic rating of 1g in all three axes. These shall
be attached to the pipe (one pair at each anchorage location) by means of an extended
double-bolt riser clamp, specifically designed for installation of acoustic anchors.
G. The guides shall have a minimum seismic rating of 1g in the horizontal plane.These
shall be attached to the pipe (one pair at each guide location) by means of an extended
double-bolt riser clamp, specifically designed for installation of acoustic guides.
H. Riser clamps (MSS Type 8) shall be provided at each floor to support steel riser pipe
which has not been installed with engineered acoustic riser anchors and guides.
I. For steel riser piping installed with acoustic anchors and guides, riser clamps shall be
provided for stabilization of pipe at all floors where riser guides are not present.
J. For insulated pipe where effective outer diameter does not correspond to a standard
pipe size, intermediate sizes of riser clamps shall be provided to ensure a close fit.
Oversized clamps will not be accepted.
K. Ferrous piping up to 150 mm (6 inch) nom. dia.: Galvanized steel riser clamps or offset
pipe clamp, use solid wood inserts (Ref. by: Elcen no. 216) for insulated piping. As
manufactured by: Elcen no. 39 and or 44 or approved equal.
L. Ferrous piping over 150 mm (6 inch) ND: Gusset plates with integral bearing plates
(minimum thickness equal to that of the pipe) welded to pipe and resting on cross
channels over heavy-duty vibration isolation pads (50 durometer). Cross channels
shall be offset to accommodate the piping insulation and the vapor barrier sealed
around the gusset plate with mastic sealant. `Z' cleats shall be welded on the cross
channels at the ends of the bearing plates to restrict movement.
A. Provide rubber support inserts made from moulded hard rubber at all hanger and
support locations of insulated pipework, to transmit pipe load without crushing the
insulation.
1. The rubber density shall not be less than 1000 kg/m3 and shall not exceed 1200
kg/m3.
2. The thickness of the inserts shall be same as the insulation, and vapour barrier
shall be continuous across the outside of the inserts.
3. Rubber support inserts shall be manufactured with sufficient width, material
control and moulding quality to bear imposed pipe loads.
4. Usage of steel inserts within the rubber will not be permitted under any
circumstance.
5. Rubber support inserts with Class 0 fire rating classification shall be provided
where fire resistant rubber support inserts are deemed necessary by the project
designer.
D. Pipe covering protection saddles (MSS Type 39) may be installed at support locations
of ferrous hot water piping, instead of rubber support inserts.
E. If pipe covering protection saddles are installed with insulated non-ferrous or chilled
water pipe, the surfaces in contact with the pipe shall be fitted with high compressive
strength fabric reinforced neoprene sleeves - to avoid forming a thermal bridge (in
case of steel chilled water pipe) and contact between dissimilar metals (in case of non-
ferrous pipe).
A. The selection, positioning and installation of seismic bracing shall be based on the
recommendations of the manufacturer, as approved by the Engineer.
B. Seismic restraint shall be provided by cable sway bracing kits, each comprising a pair
of complete assemblies with multi-strand stainless steel cable, fixing brackets,
stainless steel thimbles and wire clips.
C. Structural Steel: steel plates, shapes, and bars, black and galvanized.
B. Horizontal ferrous piping (insulated): Steel plate (minimum thickness as that of the
pipe and length equal to the diameter) welded to pipe, projecting beyond the insulation;
attached to structural steel framing by bolting or welding. Seal the vapor barrier around
the plate with mastic sealants.
C. Vertical ferrous piping (non-insulated): Steel hold down anchor clamp and base plate
attached to RCC / structural steel supports. Back weld clamp to pipe after installation.
D. Vertical ferrous piping (insulated): Same as the support of vertical insulated ferrous
piping over 150 mm (6 inches) nom. dia.; excluding the vibration isolation pad. Bolt
down / weld the bearing plate to the cross channel.
B. Ball hangers: Provide for allowing angular movement of the hanger rod, where
required.
C. Threaded rod couplers: Provide for joining two lengths of threaded hanger rods, where
required. Install back nuts on both sides of the coupler.
A. Concrete inserts: Provide malleable iron or galvanized steel concrete inserts complete
with adjustable insert nut, suitable for hanger rods of size 22 mm (7/8 inch) diameter
and under. Provide galvanized steel continuous concrete insert at Contractor's option.
B. Self-drilling type concrete inserts: Provide galvanized steel self drilling expansion type
concrete inserts for hanger rods up to 12 mm (1/2 inch) dia., at Contractor's option.
C. Support rails (cast-in type): Electro zinced steel sections with anchor lugs and filler
strip complete with hammer head nut or extension pieces.
D. Support rails (surface mounted type): Electro zinced steel sections with anchor lugs
and filler strip complete with hammer head nut or extension pieces. The rail shall be
single or double as appropriate.
2.014 FLASHING
B. Lead flashing: 24.5 kg/sq.M (5 lb/sq.ft.) sheet lead for waterproofing; 5 kg/sq.M (1
lb/sq.ft.) sheet lead for soundproofing.
D. Caps: Galvanized steel, 0.8 mm (22 gauge) minimum; 1.5 mm (16 gauge) at fire
resistant elements.
2.015 SLEEVES
A. Sleeves for pipes through fire rated and fire resistive floors and walls: Schedule 40
galvanized steel pipe sleeve; pack with 96 kg/cu.M (6 lbs/cu.ft.) density fiberglass and
caulk both ends with approved fire rated sealant. (UL listed)
B. Sleeves for pipes passing through non-fire rated beams, walls, footings and dry floors:
Schedule 40 galvanized steel pipe sleeve; pack with 96 kg/cu.M (6 lbs/cu.ft.) density
fiberglass and caulk both ends with approved type sealant (UL listed). For vertical
piping, extend sleeve 50 mm (2 inch) above the finish floor level.
C. Sleeves for ferrous pipes passing through external retaining walls: Cast iron or ductile
iron with integral puddle; pack with 96 kg/cu.M (6 lbs/cu.ft.) density fiberglass; caulk
internal side with approved sealant (UL listed); caulk external side with hemp yarn and
lead.
D. Sleeves for cast iron drain, waste and vent piping through wet floors: Provide PVC
pipe sleeve or wooden box to form the opening; remove this sleeve or box after curing
of the concrete. After completion of cast iron pipe installation, fill the opening with non-
shrinkable grout; trowel both sides of slab, smooth and level.
F. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule-40, galvanized, plain ends.
G. Cast Iron: Cast or fabricated “wall pipe” equivalent to ductile-iron pressure pipe, with
plain ends and integral water stop, unless otherwise indicated.
H. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange.
Include clamping ring and bolts and nuts for membrane flashing.
J. Molded PVC: Permanent, with nailing flange for attaching to wooden forms.
L. Molded PE: Reusable, PE, tapered-cup shaped and smooth-outer surface with nailing
flange for attaching to wooden forms.
2.016 ESCUTCHEONS
A. Provide set screw type escutcheons, size sufficient to completely cover exposed
penetrations. Prime coat finish where adjoining surface is to be field painted; baked
enamel white finish where adjoining surface is fiberboard. Chrome finish where
adjoining surface is tiled with ceramic, marble, etc.
KEO/21-7387-0004 23 0529 / 11 Hangers and Supports for Piping and Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
2.017 FINISH
A. All hangers support inserts, shields and saddles shall have galvanized finish.
B. Compact Pipe Stand: One-piece plastic unit with integral-rod-roller, pipe clamps, or
V-shaped cradle to support pipe, for roof installation without membrane penetration.
C. Low-Type, Single-Pipe Stand: One-piece stainless-steel base unit with plastic roller,
for roof installation without membrane penetration.
PART 3 - EXECUTION
3.01 GENERAL
A. Install hangers and supports to allow controlled thermal and seismic movement of
piping systems, to permit freedom of movement between pipe anchors, and to facilitate
action of expansion joints, expansion loops, expansion bends, and similar units.
B. Install hangers and supports complete with necessary inserts, bolts, rods, nuts,
washers, and other accessories.
C. Install hangers and supports so that piping live and dead loads and stresses from
movement will not be transmitted to connected equipment.
D. Install hangers and supports to provide indicated pipe slopes and so maximum pipe
deflections allowed by ASME B31.9, “Building Services Piping”, is not exceeded.
E. Field fabricate heavy-duty steel trapezes from ASTM A36 steel shapes, welded
according to AWS D-1.1.
I. Field fabricated anchors shall be entirely separate from pipe hangers and shall be of
heavy welded steel construction. The design shall ensure a thermal and acoustic
break is provided between the pipe and building structure. Anchor loads, locations,
method of fixing and design details shall be certified by a structural engineer and
submitted for review prior to commencement of works.
K. Install seismic cable bracing at an angle of 450 +/- 150 to the ceiling slab. The
installation shall permit thermal expansion and contraction of the pipe and not impede
the functioning of vibration isolators if present.
Steel Piping:
Support vertical steel pipe at least at every floor. See also section 2.3.
Copper Piping:
B. Comply with MSS SP-69 for pipe hanger selections and applications that are not
specified in piping system Sections.
C. Use hangers and supports with galvanized, metallic coatings for piping and equipment
that will not have field-applied finish.
J. Saddles and Shields: Unless otherwise indicated and except as specified in piping
system Sections, install the following types:
1. Steel Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids
with insulation that matches adjoining insulation.
2. Protection Shields (MSS Type 40): Of length recommended in writing by
manufacturer to prevent crushing insulation.
3. Thermal-Hanger Shield Inserts: For supporting insulated pipe.
K. Spring Hangers and Supports: Unless otherwise indicated and except as specified in
piping system Sections, install the following types:
1. Restraint-Control Devices (MSS Type 47): Where indicated to control piping
movement.
2. Spring Cushions (MSS Type 48): For light loads if vertical movement does not
exceed 1-1/4 inches (32 mm).
3. Spring-Cushion Roll Hangers (MSS Type 49): For equipping Type 41 roll
hanger with springs.
4. Spring Sway Braces (MSS Type 50): To retard sway, shock, vibration, or
thermal expansion in piping systems.
5. Variable-Spring Hangers (MSS Type 51): Preset to indicated load and limit
variability factor to 25 percent to absorb expansion and contraction of piping
system from hanger.
6. Variable-Spring Base Supports (MSS Type 52): Preset to indicated load and
limit variability factor to 25 percent to absorb expansion and contraction of
piping system from base support.
7. Variable-Spring Trapeze Hangers (MSS Type 53): Preset to indicated load and
limit variability factor to 25 percent to absorb expansion and contraction of
piping system from trapeze support.
8. Constant Supports: For critical piping stress and if necessary to avoid transfer
of stress from one support to another support, critical terminal, or connected
equipment. Include auxiliary stops for erection, hydrostatic test, and load-
adjustment capability. These supports include the following types:
a. Horizontal (MSS Type 54): Mounted horizontally.
L. Comply with MSS SP-69 for trapeze pipe hanger selections and applications that are
not specified in piping system Sections.
M. Comply with MFMA-102 for metal framing system selections and applications that are
not specified in piping system Sections.
A. Steel Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Install
hangers, supports, clamps, and attachments as required to properly support piping
from building structure.
B. Trapeze Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Arrange
for grouping of parallel runs of horizontal piping and support together on field-
fabricated trapeze pipe hangers.
1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe
size or install intermediate supports for smaller diameter pipes as specified
above for individual pipe hangers.
2. Field fabricate from ASTM A 36/A 36M, steel shapes selected for loads being
supported. Weld steel according to AWS D1.1.
C. Metal Framing System Installation: Arrange for grouping of parallel runs of piping and
support together on field-assembled metal framing systems.
G. Install hangers and supports complete with necessary inserts, bolts, rods, nuts,
washers, and other accessories.
KEO/21-7387-0004 23 0529 / 18 Hangers and Supports for Piping and Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
H. Equipment Support Installation: Fabricate from welded-structural-steel shapes.
I. Install hangers and supports to allow controlled thermal and seismic movement of
piping systems, to permit freedom of movement between pipe anchors, and to facilitate
action of expansion joints, expansion loops, expansion bends, and similar units.
J. Install lateral bracing with pipe hangers and supports to prevent swaying.
K. Install building attachments within concrete slabs or attach to structural steel. Install
additional attachments at concentrated loads, including valves, flanges, and strainers,
NPS 2-1/2 (DN 65) and larger and at changes in direction of piping. Install concrete
inserts before concrete is placed; fasten inserts to forms and install reinforcing bars
through openings at top of inserts.
L. Load Distribution: Install hangers and supports so piping live and dead loads and
stresses from movement will not be transmitted to connected equipment.
M. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and so
maximum pipe deflections allowed by ASME B31.1 (for power piping) and
ASME B31.9 (for building services piping) are not exceeded.
B. Grouting: Place grout under supports for equipment and make smooth bearing
surface.
A. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers and
equipment supports.
B. Fit exposed connections together to form hairline joints. Field weld connections that
cannot be shop welded because of shipping size limitations.
C. Field Welding: Comply with AWS D1.1 procedures for shielded metal arc welding,
appearance and quality of welds, and methods used in correcting welding work, and
with the following:
1. Use materials and methods that minimize distortion and develop strength and
corrosion resistance of base metals.
2. Obtain fusion without undercut or overlap.
3. Remove welding flux immediately.
4. Finish welds at exposed connections so no roughness shows after finishing and
contours of welded surfaces match adjacent contours.
3.07 ADJUSTING
B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches (40
mm).
3.08 PAINTING
A. Touch Up: Clean field welds and abraded areas of shop paint. Paint exposed areas
immediately after erecting hangers and supports. Use same materials as used for
shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted
surfaces.
1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils
(0.05 mm).
B. Touch Up: Cleaning and touchup painting of field welds, bolted connections, and
abraded areas of shop paint on miscellaneous metal are specified in Division 09
painting Sections. Section "High-Performance Coatings."
KEO/21-7387-0004 23 0529 / 20 Hangers and Supports for Piping and Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
galvanizing-repair paint to comply with ASTM A 780.
3.09 INSERTS
B. Provide inserts for suspending hangers from reinforced concrete slabs and sides of
reinforced concrete beams.
C. Provide hooked rod to concrete reinforcement section for inserts carrying pipe over
150 mm (6 inch) nom. dia.
D. Where concrete slabs form finished ceiling, provide inserts to be flush with slab soffit.
E. Where expansion type anchors are used, select type and quality to suit the concrete
into which it is to be installed.
A. Provide hanger or support assembly to take up the filled weight of piping for half spans
on either side plus 100 kgs, with minimum overall factor of safety of two.
B. Install hangers to provide minimum 12-mm (1/2-inch) space between finished covering
and adjacent work.
E. Where several pipes can be installed in parallel and at same elevation, provide
multiple or trapeze hangers.
G. Anchor piping at either side of flexible connections (at the system side only on
connections to equipment).
I. Piping buried in raft slabs or trenches shall be supported as detailed on the Contract
drawings. The support shall be capable of holding the pipe in position against buoyant
forces exerted during pouring of concrete.
K. Provide amply sized structural steel sections for multiple trapeze hangers, anchor
braces, supporting frames etc. Submit calculations where asked for.
L. Where special slab construction (like Omni slab) is used, install support rails anchored
to concrete portions for installing hangers.
N. Provide riser clamps at mid span for vertical piping up to and including 25 mm (1 inch)
nom. dia.
B. Where sleeves in concrete structural elements are omitted due to error, core the
required openings only after obtaining written permission of the Engineer. Provide
sleeves with puddle flanges resting on the concrete surface, and non-shrink grout to
fix the sleeve in position. Cutting of hole by chiseling is not permitted.
C. Project all sleeves in wet areas by at least 50 mm (2 inch) above the finish floor level.
D. Erect sleeves, puddle flanges etc. in the formwork, perpendicular to the wall face and
rigidly to resist displacement during pouring of concrete.
E. Ensure verticality of flange faces and alignment of bolt holes with connected
equipment (valves etc.).
F. Seal the openings around, so as to avoid leakage (and resultant honeycombing) and
undesirable formation of concrete.
H. Size sleeves large enough to allow for movement of pipe due to expansion or
contraction. Provide for continuous insulation wrapping.
B. Piping and ducting passing through weather or water proofed walls, floors, and roofs:
Provide flexible flashing and metal counter flashing as appropriate.
C. Sound control: Provide acoustical lead flashing around ducts and pipes, penetrating
equipment rooms, installed in accordance with manufacturer's instructions for sound
control.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
1.02 DEFINITIONS
1.03 REFERENCES
A. Wind-Restraint Loading:
KEO/21-7387-0004 23 0548 / 1 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
1. Basic Wind Speed: 100MPH
2. Building Classification Category: II
3. Minimum 10 lb/sq. ft. (48.8 kg/sq. m) multiplied by the maximum area of the
HVAC component projected on a vertical plane that is normal to the wind
direction, and 45 degrees either side of normal.
B. Seismic-Restraint Loading:
Site Class as Defined in the IBC: (Shall be defined from soil report; Project Specific.
Refer to Structural Drawings.
C. Seismic-Restraint Loading:
1. Site Classification based on UBC 1997 Seismic Zone 2A for buildings G+4 up to
9; Seismic Zone 2B for buildings 10 storeys and higher.
D. Final Seismic restraint loading shall be confirmed by the contractor based on AHJ.
1.05 SUBMITTALS
KEO/21-7387-0004 23 0548 / 2 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
3. Vibration Isolation Base Details: Detail overall dimensions, including anchorages
and attachments to structure and to supported equipment. Include auxiliary
motor slides and rails, base weights, equipment static loads, power transmission,
component misalignment, and cantilever loads.
4. Seismic- and Wind-Restraint Details:
a. Design Analysis: To support selection and arrangement of seismic and
wind restraints. Include calculations of combined tensile and shear loads.
b. Details: Indicate fabrication and arrangement. Detail attachments of
restraints to the restrained items and to the structure. Show attachment
locations, methods, and spacings. Identify components, list their
strengths, and indicate directions and values of forces transmitted to the
structure during seismic events. Indicate association with vibration
isolation devices.
c. Coordinate seismic-restraint and vibration isolation details with wind-
restraint details required for equipment mounted outdoors. Comply with
requirements in other Division 22 Sections for equipment mounted
outdoors.
d. Preapproval and Evaluation Documentation: By an evaluation service
member of ICC-ES an agency acceptable to authorities having
jurisdiction, showing maximum ratings of restraint items and the basis for
approval (tests or calculations). All restraining devices shall have a
preapproval number from OSHPD or some other recognized government
agency showing maximum restraint ratings
C. Coordination Drawings: Show coordination of seismic bracing for HVAC piping and
equipment with other systems and equipment in the vicinity, including other supports
and seismic restraints.
D. Welding certificates.
H. Operation and Maintenance Data: For air-mounting systems to include in operation and
maintenance manuals.
KEO/21-7387-0004 23 0548 / 3 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
D. Seismic-restraint devices shall have horizontal and vertical load testing and analysis and
shall bear anchorage preapproval OPA number from OSHPD, preapproval by ICC-ES,
or preapproval by another agency acceptable to authorities having jurisdiction, showing
maximum seismic-restraint ratings. Ratings based on independent testing are preferred
to ratings based on calculations. If preapproved ratings are not available, submittals
based on independent testing are preferred. Calculations (including combining shear
and tensile loads to support seismic-restraint designs must be signed and sealed by a
qualified professional engineer.
E. The contractor shall be responsible for seismic design for the project requirements of
AHJ.
F. Do not exceed the allowable noise level, 70 dBA measured at a distance of 1200 mm (4
feet) from source, by proper engineering of equipment assemblies.
A. Deliver products to site, store and protect under provisions of Division1 General
requirements.
PART 2 - PRODUCTS
2.02 GENERAL
A. All metal parts of vibration isolation units installed out of doors shall be hot dip
galvanised, cadmium plated, or neoprene coated after fabrication. Galvanising shall
meet ASTM salt spray test standards and Federal test standard No. 14.
B. Isolator types are scheduled to establish minimum standards. At the Contractor's option,
labour saving accessories can be an integral part of isolators supplied to provide initial
lift of equipment to operating height, hold piping at fixed elevations during installation
and initial system filling operations, and similar installation advantages. Accessories
must not degrade the vibration isolation system.
C. Static deflection of isolators shall be as shown on the schedule (refer to clause 3.010).
All static deflections stated are the minimum acceptable deflection for the mounts under
actual load. Isolators selected on the basis of rated deflection are not acceptable.
D. The isolation manufacturer shall be responsible for the structural design of steel beam
bases and concrete inertia bases to support mechanical equipment scheduled or
specified to receive a supplementary base. and shall be based on the actual operating
weights of the equipment as per manufacturer’s data.
A. Type "A" - INTEGRAL BASES: This type is generally applicable for packaged chillers,
pumps, Air Handling Units, Air conditioning Units etc. which are supplied with factory
fabricated rigid base which can be mounted directly on vibration isolators. Equipment
manufacturer's recommendations should be sought for the number, locations and
weight distribution to select and install vibration isolators.
B. Type "B" - STEEL STRUCTURAL BASES: This type is generally subdivided into closed
frame type (Type B1) and rails type (Type B2). These are steel bases fabricated either
as per the approved shop drawing or as per the equipment manufacturer's
recommendation. These are used for equipment not having a rigid base. The type B1
shall be used where the vibration isolators are located within the equipment base and
type B2 shall be used when the vibration isolators are outside the equipment and the
type B2 base acts as a cradle. The minimum depth shall be 4 inches.
C. TYPE "C" CONCRETE INTERTIAL BASES: This type generally consists of structural
steel, fabricated pouring form with reinforcing bars. The concrete shall be poured on
site. The minimum depth shall be 6 inches.
D. TYPE "D" - ROOF CURBS: This type is generally used for Roof top Air Handling Units
with direct cutting through roof slab under the units. These roof curbs shall be supplied
by the unit manufacturer. The manufacturer's recommendations should be sought for
the number, locations and weight distribution to select and install vibration isolators.
E. TYPE "E" - HOUSE KEEPING PADS: These are concrete bases used for all equipment
with or without moving parts and shall be suitable for taking up the static and dynamic
loads (if any). Size base to extend 10 cms beyond equipment base in all directions and
minimum10 cms above finished floor level. Roughen floor slab beneath base for bond
and or provide rebar dowels in floor slab. Locate anchor bolts (welded on to a rebar
framework to maintain spacing) with templates supplied by the equipment manufacturer.
Provide steel angle frame with anchorage lugs at the corners.
F. TYPE "F" - FLOATING CONCRETE BASE: This is similar to Type "E" (Housekeeping
pads) but isolated at the bottom and all the side by either pre-compressed glass fiber
pads or close cell Neoprene Isolation Board. The thickness of isolating pads varies from
25 to 100 mm (1 to 4 inch) depending on the application.
A. TYPE "1" - ISOLATING PADS: This type of vibration isolators shall be generally used
where the vibrating force is transmitted directly to ground or the vibrating force is very
small compared to the absorption capacity of the structural slab at higher levels.
KEO/21-7387-0004 23 0548 / 5 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
fabricating the pads shall be as recommended by the manufacturer. Pads should have a
Maximum Durometer of 40.
E. TYPE "2" - MOLDED NEOPRENE RUBBER MOUNTS: These shall be used where a
greater deflection is required than that for pads. The maximum deflection allowable is 12
mm (0.5 inch) on these rubber mounts. The normal shape of mount is conical with a
captive insert for attaching to equipment base.
F. TYPE "3" - FREE STANDING SPRING ISOLATORS: These shall be constructed with
open type stable spring and load plates at top and bottom with an adjustable bolt for
levelling. Neoprene rubber acoustical treatment shall be provided to prevent
transmission of very high frequency vibration and noise. The spring shall be so designed
that the horizontal stiffness is more than 75 % of vertical stiffness. The rated loads and
deflections for these springs shall allow additional 50 % travel to that of the rated
deflection before the springs are compressed solid, to accommodate any errors in actual
load distribution.
G. TYPE "4" - RESTRAINED SPRING ISOLATORS: These are similar to type "3", but with
additional restraints in the vertical direction. These isolators shall have hold down bolts
to limit vertical movement. The restraints should have adequate clearance so that they
are activated only when a temporary restraint is needed.
H. TYPE "5" - HOUSED SPRING ISOLATORS: These isolators are similar to type "4"
except that they consist of two telescoping houses. The contact surfaces of houses are
separated by resilient inserts such as Neoprene Sponge or equivalent material.
I. TYPE "6" - RUBBER HANGERS: These are similar to type "2" except that the conical
rubber mold is housed in a steel casing and have a through hole for the hanger rod. The
assembly should allow for 20 to 35 degrees angular movement for the hanging rod
without metal to metal contact.
J. TYPE "7" - SPRING HANGERS: These are similar to type "3" except that the spring is
mounted in a steel casing and used for suspension only. The assembly shall allow for
20 to 25 degrees angular movement for the hanging rod without metal to metal contact.
L. TYPE "9" - THRUST RESTRAINTS: These are similar to type "7", but installed in pairs
to counteract the thrust caused by air pressure.
M. TYPE "10" - AIR SPRINGS: These shall consist of constant dry air supplying equipment
and air bellows. These shall be used where 150 mm (6 inch) or greater deflection is
required and natural frequencies do not exceed 80 Hz.
KEO/21-7387-0004 23 0548 / 6 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
A. Pads: Arranged in single or multiple layers of sufficient stiffness for uniform loading over
pad area, molded with a nonslip pattern and galvanized-steel baseplates, and factory
cut to sizes that match requirements of supported equipment.
1. Resilient Material: Oil- and water-resistant neoprene rubber Two layers of 3/4"
(19mm) thick neoprene pad consisting of 2" (50mm) square waffle modules
separated horizontally by a 16 (1.5mm) gauge galvanized shim. Load distribution
plates shall be used as required.
KEO/21-7387-0004 23 0548 / 7 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
5. Lateral Stiffness: More than 80 percent of rated vertical stiffness.
6. Overload Capacity: Support 200 percent of rated load, fully compressed, without
deformation or failure.
F. Housed Spring Mounts: Housed spring isolator with integral seismic snubbers.
1. Housing: Ductile-iron or steel housing to provide all-directional seismic restraint.
2. Base: Factory drilled for bolting to structure.
3. Snubbers: Vertically adjustable to allow a maximum of 1/4-inch (6-mm) travel up
or down before contacting a resilient collar.
H. Spring Hangers: Combination coil-spring and elastomeric-insert hanger with spring and
insert in compression.
1. Frame: Steel, fabricated for connection to threaded hanger rods and to allow for
a maximum of 30 degrees of angular hanger-rod misalignment without binding or
reducing isolation efficiency.
2. Outside Spring Diameter: Not less than 80 percent of the compressed height of
the spring at rated load.
3. Minimum Additional Travel: 50 percent of the required deflection at rated load.
4. Lateral Stiffness: More than 80 percent of rated vertical stiffness.
5. Overload Capacity: Support 200 percent of rated load, fully compressed, without
deformation or failure.
6. Elastomeric Element: Molded, oil-resistant rubber or neoprene. Steel-washer-
reinforced cup to support spring and bushing projecting through bottom of frame.
7. Self-centering hanger rod cap to ensure concentricity between hanger rod and
support spring coil.
J. Pipe Riser Resilient Support: All-directional, acoustical pipe anchor consisting of 2 steel
tubes separated by a minimum of 1/2-inch- (13-mm-) thick neoprene. Include steel and
neoprene vertical-limit stops arranged to prevent vertical travel in both directions.
Design support for a maximum load on the isolation material of 500 psig (3.45 MPa) and
for equal resistance in all directions.
KEO/21-7387-0004 23 0548 / 8 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
K. Resilient Pipe Guides: Telescopic arrangement of 2 steel tubes or post and sleeve
arrangement separated by a minimum of 1/2-inch- (13-mm-) thick neoprene. Where
clearances are not readily visible, a factory-set guide height with a shear pin to allow
vertical motion due to pipe expansion and contraction shall be fitted. Shear pin shall be
removable and reinsertable to allow for selection of pipe movement. Guides shall be
capable of motion to meet location requirements.
A. This shall consist of a sleeve 25 mm (1-inch) larger all round than that of the penetrating
element and fabricated out of steel pipe or sheet metal as the condition warrants. The
sleeve length shall be 25 mm (1 inch) extra on both sides of the penetrated construction.
The annular space is filled with resilient material such as Neoprene sponge or type 1B
material and ends sealed with approved sealant compatible with the resilient material.
A. Flexible duct connections shall be fabricated from coated fabric (or loaded vinyl as
called for on the drawings). The clear space between connected parts shall be a
minimum of 75-mm (3-inch) and the connection shall have 38-mm (1 1/2-inch) minimum
of slack material.
B. UL Listed fire retardant, Neoprene coated (Silicon rubber for smoke extract duty /
Hypalon for outdoor use), woven, glass-fibre fabric of 750 gm/M2 (30 Oz/yard2) average
weight: tailored to suit requirements.
C. Pressure Rating: 500 Pa (2 inch WG) positive and 375 Pa (1.5 inch WG) negative.
E. Continuous Temperature Range: -40 C to 93 C (-40 F to 200 F) for normal air
moving equipment and 260 C (500 F) for smoke extraction units.
F. Galvanised steel edging strips, crimped on to the duct fabric shall be provided at the
ends of flexible connections to equipment / metal ducts.
A. Flexible pipe connections shall be fabricated of multiple plies of nylon cord, fabric, and
neoprene, vulcanised so as to become inseparable and homogeneous. Straight
connections shall be formed in a double sphere shape. Elbow connections shall have a
single sphere shape at the curve of the unit. Flexible connections shall be able to accept
compressive, elongative, transverse, and angular movements.
B. The flexible connections shall be selected and specially fitted, if necessary, to suit the
system temperature, pressure, and fluid type.
C. Use bellow type metal flexible connectors with braided steel wire armour when they are
located in outdoor areas where the type described above will be damaged due to sun
radiation.
KEO/21-7387-0004 23 0548 / 9 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
D. Connectors for pipe sizes 50 mm (2 inch) nom. dia. or smaller shall have threaded
female union couplings, made up of compatible material like cast iron for steel and
bronze for copper piping, on each end. Larger sizes shall be fitted with metallic flange
couplings.
E. Water Seal: Galvanized sheet metal with EPDM seals at corners, attached to upper
support frame, extending down past wood nailer of lower support assembly, and
counterflashed over roof materials.
B. Inertia Base: Factory-fabricated, welded, structural-steel bases and rails ready for
placement of cast-in-place concrete.
1. Design Requirements: Lowest possible mounting height with not less than 1-inch
(25-mm) clearance above the floor. Include equipment anchor bolts and auxiliary
motor slide bases or rails.
a. Include supports for suction and discharge elbows for pumps.
2. Structural Steel: Steel shapes, plates, and bars complying with
ASTM A 36/A 36M. Bases shall have shape to accommodate supported
equipment.
3. Support Brackets: Factory-welded steel brackets on frame for outrigger isolation
mountings and to provide for anchor bolts and equipment support.
4. Fabrication: Fabricate steel templates to hold equipment anchor-bolt sleeves
and anchors in place during placement of concrete. Obtain anchor-bolt
templates from supported equipment manufacturer.
KEO/21-7387-0004 23 0548 / 11 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
A. General Requirements for Restraint Components: Rated strengths, features, and
applications shall be as defined in reports by an evaluation service member of ICC-ES
or an agency acceptable to authorities having jurisdiction. All restraining devices shall
have a preapproval number from OSHPD or some other recognized government agency
showing maximum restraint ratings.
1. Structural Safety Factor: Allowable strength in tension, shear, and pullout force
of components shall be at least four times the maximum seismic forces to which
they will be subjected.
B. Snubbers: Factory fabricated using welded structural-steel shapes and plates, anchor
bolts, and replaceable resilient isolation washers and bushings.
1. Anchor bolts for attaching to concrete shall be seismic-rated, drill-in, and stud-
wedge or female-wedge type.
2. Resilient Isolation Washers and Bushings: Oil- and water-resistant neoprene.
3. Maximum 1/4-inch (6-mm) air gap, and minimum 1/4-inch- (6-mm-) thick resilient
cushion.
D. Restraint Cables: Seismic Cable Restraints shall consist of galvanized steel aircraft
cables sized to resist seismic loads with a minimum safety factor of two and arranged to
provide all-directional restraint. Cables must be pre-stretched to achieve a certified
minimum modulus of elasticity. ASTM A 603 Galvanized ASTM A 492 Stainless Steel
Cable end connections shall be steel assemblies that swivel to final installation angle
and utilize two clamping bolts to provide proper cable engagement. Cables must not be
allowed to bend across sharp edges. Cable assemblies shall have an Anchorage
Preapproval OPA Number from OSHPD in the State of California verifying the maximum
certified load ratings.
E. Hanger Rod Stiffener: Steel tube or steel slotted-support-system sleeve with internally
bolted connections Reinforcing steel angle clamped to hanger rod.
F. Bushings for Floor-Mounted Equipment Anchor Bolts: Neoprene bushings designed for
rigid equipment mountings and matched to type and size of anchor bolts and studs.
H. Resilient Isolation Washers and Bushings: One-piece, molded, oil- and water-resistant
neoprene, with a flat washer face.
J. Adhesive Anchor Bolts: Drilled-in and capsule anchor system containing polyvinyl or
urethane methacrylate-based resin and accelerator, or injected polymer or hybrid mortar
adhesive. Provide anchor bolts and hardware with zinc-coated steel for interior
KEO/21-7387-0004 23 0548 / 12 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
applications and stainless steel for exterior applications. Select anchor bolts with
strength required for anchor and as tested according to ASTM E 488.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine areas and equipment to receive vibration isolation and seismic- and wind-
control devices for compliance with requirements for installation tolerances and other
conditions affecting performance.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 APPLICATIONS
A. Multiple Pipe Supports: Secure pipes to trapeze member with clamps approved for
application by an evaluation service member of ICC-ES or an agency acceptable to
authorities having jurisdiction.
B. Hanger Rod Stiffeners: Install hanger rod stiffeners where indicated or scheduled on
Drawings to receive them and where required to prevent buckling of hanger rods due to
seismic forces.
B. Equipment Restraints:
KEO/21-7387-0004 23 0548 / 13 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
1. Install seismic snubbers on HVAC equipment mounted on vibration isolators.
Locate snubbers as close as possible to vibration isolators and bolt to equipment
base and supporting structure.
2. Install resilient bolt isolation washers on equipment anchor bolts where clearance
between anchor and adjacent surface exceeds 0.125 inch (3.2 mm).
3. Install seismic-restraint devices using methods approved by an evaluation
service member of ICC-ES or an agency acceptable to authorities having
jurisdiction providing required submittals for component.
C. Piping Restraints:
1. Comply with requirements in MSS SP-127.
2. Space lateral supports a maximum of 40 feet (12 m) o.c., and longitudinal
supports a maximum of 80 feet (24 m) o.c.
3. Brace a change of direction longer than 12 feet (3.7 m).
D. Install cables so they do not bend across edges of adjacent equipment or building
structure.
F. Install bushing assemblies for anchor bolts for floor-mounted equipment, arranged to
provide resilient media between anchor bolt and mounting hole in concrete base.
G. Install bushing assemblies for mounting bolts for wall-mounted equipment, arranged to
provide resilient media where equipment or equipment-mounting channels are attached
to wall.
I. Drilled-in Anchors:
1. Identify position of reinforcing steel and other embedded items prior to drilling
holes for anchors. Do not damage existing reinforcing or embedded items during
coring or drilling. Notify the structural engineer if reinforcing steel or other
embedded items are encountered during drilling. Locate and avoid prestressed
tendons, electrical and telecommunications conduit, and gas lines.
2. Do not drill holes in concrete or masonry until concrete, mortar, or grout has
achieved full design strength.
3. Wedge Anchors: Protect threads from damage during anchor installation.
Heavy-duty sleeve anchors shall be installed with sleeve fully engaged in the
structural element to which anchor is to be fastened.
4. Adhesive Anchors: Clean holes to remove loose material and drilling dust prior
to installation of adhesive. Place adhesive in holes proceeding from the bottom
of the hole and progressing toward the surface in such a manner as to avoid
introduction of air pockets in the adhesive.
5. Set anchors to manufacturer's recommended torque, using a torque wrench.
6. Install zinc-coated steel anchors for interior and stainless-steel anchors for
exterior applications.
KEO/21-7387-0004 23 0548 / 14 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
3.04 ACCOMMODATION OF DIFFERENTIAL SEISMIC MOTION
A. Install flexible connections in piping where they cross seismic joints, where adjacent
sections or branches are supported by different structural elements, and where the
connections terminate with connection to equipment that is anchored to a different
structural element from the one supporting the connections as they approach
equipment. Comply with requirements in Division 22 Section "Hydronic Piping" for
piping flexible connections.
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
3.06 ADJUSTING
B. Adjust limit stops on restrained spring isolators to mount equipment at normal operating
height. After equipment installation is complete, adjust limit stops so they are out of
contact during normal operation.
KEO/21-7387-0004 23 0548 / 15 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
E. Adjust restraints to permit free movement of equipment within normal mode of
operation.
3.07 DEMONSTRATION
3.08 APPLICATION
A. General
1. Refer to PART 2 - PRODUCTS of this specification for vibration isolation devices
identified on the schedule or specified herein.
B. Major Equipment
1. Unless otherwise shown or specified, all floor mounted major equipment shall be
set on concrete housekeeping pads as per recommendations of the
manufacturer. See schedule of mounting pads in this section.
2. Types and minimum static deflections of vibration isolation devices for major
equipment items shall be as scheduled on the drawings or specified here under.
3. Flexible duct connections shall be installed at all fan unit intakes, fan unit
discharges, and wherever else shown on the drawings.
4. Flexible pipe connections shall be installed at all pipe connections to vibration
isolated equipment in the positions shown on the drawings.
5. Electrical connections to vibration isolated equipment shall be flexible, as called
for in the electrical portion of the specification.
6. Snubbers or thrust restraints shall be installed on equipment as called for in the
schedule on the drawings or specified here under.
D. Piping
1. Provide flexible pipe connections in piping connected to vibration isolated
equipment, as called for and shown on drawings.
2. Anchor piping at the system side of the flexible connector.
3. All pipe/conduit penetrations of partitions, floor/ceiling/roof slabs must be sealed
airtight with acoustic sealant or mineral fibre and fire code compound.
E. Duct Work
1. Ducts within the specified limits which penetrate the building construction shall be
isolated from the building by using resilient penetration sleeve / seals.
2. Resilient lateral guides shall be used wherever lateral support of vertical duct
runs is required within the specified limits.
KEO/21-7387-0004 23 0548 / 16 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
3.09 INSTALLATION OF VIBRATION ISOLATION EQUIPMENT
A. General
1. Locations of all vibration isolation equipment shall be selected for ease of
inspection and adjustment as well as for proper operation.
2. Installation of vibration isolation equipment shall be in accordance with the
manufacturer's instructions.
B. Isolation Mounts
1. All vibration isolators shall be aligned squarely above or below mounting points of
the supported equipment.
2. Isolators for equipment with bases shall be located on the sides of the bases,
which are parallel to the equipment shaft unless this is not possible because of
physical constraints.
3. If a housekeeping pad is provided, the isolators shall bear on the housekeeping
pad and the isolator base plate shall rest entirely on the pad.
4. Hanger rods for vibration isolated support shall be connected to structural beams
or joists, not from the floor slab between beams and joists. Provide intermediate
support members as necessary.
5. Vibration isolation hanger elements shall be positioned as high as possible in the
hanger rod assembly, but not in contact with the building structure, and so that
the hanger housing may rotate a full 360 degrees about the rod axis without
contacting any object.
6. Parallel running pipes may be hung together on a trapeze, which is isolated from
the building. Isolator deflections must be the largest determined by the provisions
for pipe isolation. Do not mix isolated and non-isolated pipes on the same
trapeze.
7. No pipes or equipment shall be supported from other pipes or equipment.
8. Resiliently isolated pipes shall not contact the building construction or other
equipment.
9. The installed and operating heights of vibration isolators supporting any
equipment shall be identical. Limit stops shall be out of contact during normal
operation.
10. Adjust all leveling bolts and hanger rod bolts so that the isolated equipment is
level and in proper alignment with connecting ducts or pipes.
C. Bases
1. No equipment unit shall bear directly on vibration isolators unless its own frame
is suitably rigid to span between isolators and such direct support is approved by
the equipment manufacturer. This provision shall apply whether or not a base
frame is called for on the schedule. In the case that a base frame is required for
the unit because of the equipment manufacturer's requirements and is not
specifically called for on the equipment schedule, a base frame recommended by
the equipment manufacturer shall be provided.
2. Unless otherwise indicated, there is to be a minimum operating clearance of 38-
mm (1 1/2 inch) between inertia bases or steel frame bases and the floor
beneath the equipment. Position isolator mounting brackets and adjust isolators
so that the required clearance is maintained. The clearance space shall be
checked by the Contractor to ensure that no construction debris has been left to
short circuit or restrict the proper operation of the vibration isolation system.
KEO/21-7387-0004 23 0548 / 17 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
1. Sheet metal ducts or plenum openings shall be squarely aligned with the fan
discharge, fan intake, or adjacent duct section prior to installation of the flexible
connection, so that the clear length is approximately equal all the way around the
perimeter. Flexible duct connections shall not be installed until this provision is
met. The fan unit or adjacent duct section shall be able to move 25 mm (1 inch)
in any direction without causing metal to metal contact or stretching taut the
flexible connection.
F. Thrust Restraints
1. Snubbers shall be adjusted to clear the equipment base and to provide lateral
restraint during on / off cycling, but be out of contact during normal operation of
the equipment.
2. Thrust restraints shall be attached at the center line of thrust and symmetrically
on each of the units. Adjust the restraints to limit equipment movement to the
specified limit.
END OF SECTION
KEO/21-7387-0004 23 0548 / 18 Vibration And Seismic Controls For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
SECTION 23 0553
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 REFERENCES
A. Section Includes:
1. Equipment labels.
2. Warning signs and labels.
3. Pipe labels.
4. Duct labels.
5. Stencils.
6. Valve tags.
7. Warning tags.
1.03 SUBMITTALS
B. Samples: For color, letter style, and graphic representation required for each
identification material and device.
C. Equipment Label Schedule: Include a listing of all equipment to be labeled with the
proposed content for each label.
1.04 COORDINATION
B. Coordinate installation of identifying devices with locations of access panels and doors.
C. Install identifying devices before installing acoustical ceilings and similar concealment.
KEO/21-7387-0004 23 0553 / 1 Identification For Hvac Piping And Equipment
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 COLORS
B. Co-ordinate with all other, similarly identified services and agree on a schedule, which
avoids confusing repetitions.
C. Comply with prevailing governmental regulations, where appropriate, like for fuel / gas
piping.
A. All the labelling, warning signs etc. shall be in English and Arabic. All numbering shall be
in Indian numerals.
B. Lettering shall not be smaller than 10 mm x 6 mm in size. Use larger size letters as
appropriate.
C. Lettering on plastic and metal plates shall be etched, engraved, embossed or made
otherwise in a permanent manner (stencilling on prepared surfaces excluded).
A. Two ply self adhesive vinyl tapes applied around the pipes with 12-mm overlap. Use 15-
cm wide tapes of colors as schedule below:
1. Refrigerant Liquid Line White.
2. Refrigerant Suction Line Navy Blue.
3. Chilled Water Supply Navy Blue / White / Navy Blue.
4. Chilled Water Return Sky Blue / White / Sky Blue.
5. Condensate Brown / White / Brown.
B. Two ply self adhesive vinyl strip markers of size 5 x 15cm (minimum) with white arrows
on contrasting background shall be provided to indicate direction of flow in pipe.
2.05 STENCILS
A. Use clean cut stencils of appropriate size, for making identification wording . The paint
used shall be semi-gloss enamel.
A. Three ply, rigid plastic name plates with black engraved lettering on light contrasting
background shall be used for identifying electrical control panels, technical cupboards,
plant rooms, and equipment. Fix these labels by adhesives or by metal screws.
A. Three ply rigid plastic tags with black engraved lettering on light contrasting background
shall be used for identifying valves. Each tag shall be minimum four (4) cm diameter in
size and shall have a drilled hole for attaching to valves with corrosion resistant metallic
chain.
A. Use colored (as coded) continuously printed vinyl tapes at midway between the surface
and pipe crown. Each grid shall be minimum 15 cm wide. Use metal coated tapes for
non-metallic pipes.
A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving,
1/8 inch (3.2 mm) thick, and having predrilled holes for attachment hardware.
D. Maximum Temperature: Able to withstand temperatures up to 160 deg F (71 deg C).
E. Minimum Label Size: Length and width vary for required label content, but not less than
2-1/2 by 3/4 inch (64 by 19 mm).
F. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less
than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830
mm), and proportionately larger lettering for greater viewing distances. Include
secondary lettering two-thirds to three-fourths the size of principal lettering.
H. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
I. Label Content: Include caution and warning information, plus emergency notification
instructions.
C. Pipe Label Contents: Include identification of piping service using same designations or
abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.
1. Flow-Direction Arrows: Integral with piping system service lettering to
accommodate both directions, or as separate unit on each pipe label to indicate
flow direction.
2. Lettering Size: At least 1-1/2 inches (38 mm) high.
A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving,
1/8 inch (3.2 mm) thick, and having predrilled holes for attachment hardware.
D. Maximum Temperature: Able to withstand temperatures up to 160 deg F (71 deg C).
E. Minimum Label Size: Length and width vary for required label content, but not less than
2-1/2 by 3/4 inch (64 by 19 mm).
F. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less
than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830
mm), and proportionately larger lettering for greater viewing distances. Include
secondary lettering two-thirds to three-fourths the size of principal lettering.
H. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
I. Duct Label Contents: Include identification of duct service using same designations or
abbreviations as used on Drawings, duct size, and an arrow indicating flow direction.
1. Flow-Direction Arrows: Integral with duct system service lettering to
accommodate both directions, or as separate unit on each duct label to indicate
flow direction.
2. Lettering Size: At least 1-1/2 inches (38 mm) high.
A. Valve Tags: Stamped or engraved with 1/4-inch (6.4-mm) letters for piping system
abbreviation and 1/2-inch (13-mm) numbers.
1. Tag Material: Brass, 0.032-inch (0.8-mm) minimum thickness and having
predrilled or stamped holes for attachment hardware.
2. Fasteners: Brass wire-link or beaded chain; or S-hook.
B. Valve Schedules: For each piping system, on 8-1/2-by-11-inch (A4) bond paper.
Tabulate valve number, piping system, system abbreviation (as shown on valve tag),
location of valve (room or space), normal-operating position (open, closed, or
modulating), and variations for identification. Mark valves for emergency shutoff and
similar special uses.
1. Valve-tag schedule shall be included in operation and maintenance data.
3.01 PREPARATION
A. Clean piping and equipment surface of substances that could impair bond of
identification devices, including dirt, oil, grease, release agents, and incompatible
primers, paints, and encapsulants.
C. All equipment shall be numbered, and these numbers should be included in as built
drawings and manuals.
B. Locate pipe labels where piping is exposed or above accessible ceilings in finished
spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and
plenums; and exterior exposed locations as follows:
1. Near each valve and control device.
2. Near each branch connection, excluding short takeoffs for fixtures and terminal
units. Where flow pattern is not obvious, mark each pipe at branch.
3. Near penetrations through walls, floors, ceilings, and inaccessible enclosures.
4. At access doors, manholes, and similar access points that permit view of
concealed piping.
5. Near major equipment items and other points of origination and termination.
6. Spaced at maximum intervals of 50 feet (15 m) along each run. Reduce intervals
to 25 feet (7.6 m) in areas of congested piping and equipment.
7. On piping above removable acoustical ceilings. Omit intermediately spaced
labels.
B. Locate labels near points where ducts enter into concealed spaces and at maximum
intervals of 50 feet (15 m) in each space where ducts are exposed or concealed by
removable ceiling system.
A. Install tags on valves and control devices in piping systems, except check valves; valves
within factory-fabricated equipment units; faucets; convenience and lawn-watering hose
connections; and HVAC terminal devices and similar roughing-in connections of end-
use fixtures and units. List tagged valves in a valve schedule.
B. Valve-Tag Application Schedule: Tag valves according to size, shape, and color
scheme and with captions similar to those indicated in the following subparagraphs:
1. Valve-Tag Size and Shape:
a. Chilled Water: 1-1/2 inches (38 mm), round or square
b. Condenser Water: 1-1/2 inches (38 mm), round or square.
c. Refrigerant: 1-1/2 inches (38 mm), round or square
d. Hot Water: 1-1/2 inches (38 mm), round or square.
e. Gas: 1-1/2 inches (38 mm), round or square.
2. Valve-Tag Color:
a. Chilled Water: Green.
b. Condenser Water: Green.
c. Refrigerant: Black.
d. Hot Water: Green.
e. Gas: Yellow.
3. Letter Color:
a. Chilled Water: White.
b. Condenser Water: White.
c. Refrigerant: Orange.
d. Hot Water: White.
e. Gas: Black.
A. Write required message on, and attach warning tags to, equipment and other items
where required.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes Testing, Adjusting & Balancing (TAB) to produce design
objectives for the following:
1. Air Systems: All Air Systems and associated equipment and apparatus of
mechanical work
a. Constant-volume air systems.
2. Kitchen hood airflow balancing.
3. Space pressurization testing and adjusting.
4. Vibration measuring.
5. Sound level measuring.
6. Indoor-air quality measuring.
7. Verifying that automatic control devices are functioning properly.
8. Reporting results of activities and procedures specified in this Section.
9. Commercial Refrigeration Systems and associated equipment and apparatus of
mechanical work.
1.02 DEFINITIONS
A. Adjust: To regulate fluid flow rate and air patterns at the terminal equipment, such as to
reduce fan speed or adjust a damper.
D. Draft: A current of air, when referring to localized effect caused by one or more factors
of high air velocity, low ambient temperature, or direction of airflow, whereby more heat
is withdrawn from a person's skin than is normally dissipated.
I. Smoke-Control System: An engineered system that uses fans to produce airflow and
pressure differences across barriers to limit smoke movement.
J. Smoke-Control Zone: A space within a building that is enclosed by smoke barriers and
is a part of a zoned smoke-control system.
K. Static Head: The pressure due to the weight of the fluid above the point of
measurement. In a closed system, static head is equal on both sides of the pump.
L. Suction Head: The height of fluid surface above the centerline of the pump on the
suction side.
M. System Effect: A phenomenon that can create undesired or unpredicted conditions that
cause reduced capacities in all or part of a system.
P. Terminal: A point where the controlled medium, such as fluid or energy, enters or
leaves the distribution system.
R. Testing, Adjusting, and Balancing (TAB) Firm: The entity responsible for performing and
reporting TAB procedures.
A. Related work to be coordinated and used in conjunction with this specification includes
but is not restricted to:
1. Section 23 0800 – Commissioning of HVAC
1.04 REFERENCES
A. ASHRAE 111, Practices for Measurement, Testing, Adjusting, and Balancing of Building
Heating, Ventilation, Air-conditioning, and Refrigeration Systems.
J. BSRlA- Pre Commissioning of Pipe work Systems, 2nd Edition; Application Guide
112001.1
L. BSRlA- Achieving minimum outdoor air- commissioning and test procedures; application
Guide 1712000.
M. BSRlA- Guidance to the standard Specification for vibration testing of building services
installations; Facilities Management Specification 7.
1.05 SUBMITTALS
C. Strategies and Procedures Plan: Within 60 days from Contractor's Notice to Proceed
(TAB), submit 3 copies of TAB strategies and step-by-step procedures as specified in
Part 3 "Preparation" Article. Include a complete set of report forms intended for use on
this Project.
D. Submit test sheet formats, drawings, schemes etc. for approval prior to commencement
of work
E. Certified TAB Reports: Submit two copies of reports prepared, as specified in this
Section, on approved forms certified by TAB firm.
F. Sample Report Forms: Submit two sets of sample TAB report forms.
G. Include identification and types of instruments used and their most recent calibration
date with submission of final test report
A. TAB Firm Qualifications: Engage an independent, certified TAB firm with at least 8
years of successful testing, adjusting, and balancing experience on projects with testing
and balancing requirements similar to those required for this project
D. Certification of TAB Reports: Certify TAB field data reports. This certification includes
the following:
1. Review field data reports to validate accuracy of data and to prepare certified
TAB reports.
2. Certify that TAB team complied with approved TAB plan and the procedures
specified and referenced in this Specification.
E. TAB Report Forms: Use standard forms from AABC's "National Standards for Testing
and Balancing Heating, Ventilating, and Air Conditioning Systems."
A. Full Owner Occupancy: Owner will occupy the site and existing building during entire
TAB period. Cooperate with Owner during TAB operations to minimize conflicts with
Owner's operations.
B. Partial Owner Occupancy: Owner may occupy completed areas of building before
Substantial Completion. Cooperate with Owner during TAB operations to minimize
conflicts with Owner's operations.
1.08 COORDINATION
B. Notice: Provide seven days' advance notice for each test. Include scheduled test dates
and times.
C. Perform TAB after leakage and pressure tests on air and water distribution systems
have been satisfactorily completed.
1.09 WARRANTY
A. National Project Performance Guarantee: Provide a guarantee forms stating that TAB
firm comply and guarantee the following provisions:
1. The certified TAB firm has tested and balanced systems according to the
Contract Documents.
2. Systems are balanced to optimum performance capabilities within design and
installation limits.
PART 2 - PRODUCTS
2.01 MANUFACTURERES
A. Utilize test instruments and equipment for TAB work required, of type, precision, and
capacity as recommended by the AABC.
B. All equipment shall be properly calibrated with certification providing that recent
calibration has taken place.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine installed work and conditions under which testing is to be done to ensure that
work has been completed, cleaned and is operable. Do not proceed with TAB work
until unsatisfactory conditions have been corrected in manner acceptable to Tester
B. Examine the Contract Documents to become familiar with Project requirements and to
discover conditions in systems' designs that may preclude proper TAB of systems and
equipment.
1. Contract Documents are defined in the General and Supplementary Conditions
of Contract.
F. Examine equipment performance data including fan and pump curves. Relate
performance data to Project conditions and requirements, including system effects that
can create undesired or unpredicted conditions that cause reduced capacities in all or
part of a system. Calculate system effect factors to reduce performance ratings of
HVAC equipment when installed under conditions different from those presented when
the equipment was performance tested at the factory. To calculate system effects for air
systems, use tables and charts found in AMCA 201, "Fans and Systems," Sections 7
through 10; or in SMACNA's "HVAC Systems--Duct Design," Sections 5 and 6.
Compare this data with the design data and installed conditions.
G. Examine system and equipment installations to verify that they are complete and that
testing, cleaning, adjusting, and commissioning specified in individual Sections have
been performed.
I. Examine HVAC system and equipment installations to verify that indicated balancing
devices, such as test ports, gage cocks, thermometer wells, flow-control devices,
balancing valves and fittings, and manual volume dampers, are properly installed, and
that their locations are accessible and appropriate for effective balancing and for
efficient system and equipment operation.
J. Examine systems for functional deficiencies that cannot be corrected by adjusting and
balancing.
K. Examine HVAC equipment to ensure that clean filters have been installed, bearings are
greased, belts are aligned and tight, and equipment with functioning controls is ready for
operation.
L. Examine terminal units, such as variable-air-volume boxes, to verify that they are
accessible, and their controls are connected and functioning.
M. Examine plenum ceilings used for supply air to verify that they are airtight. Verify that
pipe penetrations and other holes are sealed.
P. Examine heat-transfer coils for correct piping connections and for clean and straight
fins.
Q. Examine system pumps to ensure absence of entrained air in the suction piping.
R. Examine equipment for installation and for properly operating safety interlocks and
controls.
3.02 PREPARATION
B. Provide instruments required for testing, adjusting, and balancing operations. Make
instruments available to Engineers Representative to facilitate spot checks during
testing. Retain possession of instruments and remove at completion of services.
C. Complete system readiness checks and prepare system readiness reports. Verify the
following:
1. Permanent electrical power wiring is complete.
2. Automatic temperature-control systems are operational.
3. Equipment and duct access doors are securely closed.
4. Balance, smoke, and fire dampers are open.
5. Isolating and balancing valves are open and control valves are operational.
6. Ceilings are installed in critical areas where air-pattern adjustments are required
and access to balancing devices is provided.
7. Windows and doors can be closed so indicated conditions for system operations
can be met.
KEO/21-7387-0004 23 0593 / 7 Testing, Adjusting And Balancing For Hvac
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
3.03 GENERAL PROCEDURES FOR TESTING AND BALANCING
A. Perform testing and balancing procedures on each system according to the procedures
contained in ASHRAE 111 and this Section.
B. Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the
minimum extent necessary to allow adequate performance of procedures. After testing
and balancing, close probe holes and patch insulation with new materials identical to
those removed. Restore vapor barrier and finish according to insulation Specifications
for this Project. Obtain prior engineer approval for the use of plastic plugs with retainers
may be used to patch drilled holes in ductwork and housings.
C. Mark equipment and balancing device settings with paint or other suitable, permanent
identification material, including damper-control positions, valve position indicators, fan-
speed-control levers, and similar controls and devices, to show final settings.
D. Take and report testing and balancing measurements metric (SI) units.
A. Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and
recommended testing procedures. Crosscheck the summation of required outlet
volumes with required fan volumes.
D. Determine the best locations in main and branch ducts for accurate duct airflow
measurements.
E. Check airflow patterns from the outside-air louvers and dampers and the return- and
exhaust-air dampers, through the supply-fan discharge and mixing dampers.
F. Locate start-stop and disconnect switches, electrical interlocks, and motor starters.
G. Verify that motor starters are equipped with properly sized thermal protection.
A. Adjust fans to deliver total indicated airflows within the maximum allowable fan speed
listed by fan manufacturer.
B. Adjust volume dampers for main duct, submain ducts, and major branch ducts to
indicated airflows within specified tolerances.
1. Measure static pressure at a point downstream from the balancing damper and
adjust volume dampers until the proper static pressure is achieved.
a. Where sufficient space in submain and branch ducts is unavailable for
Pitot-tube traverse measurements, measure airflow at terminal outlets and
inlets and calculate the total airflow for that zone.
2. Remeasure each submain and branch duct after all have been adjusted.
Continue to adjust submain and branch ducts to indicated airflows within
specified tolerances.
D. Adjust terminal outlets and inlets for each space to indicated airflows within specified
tolerances of indicated values. Make adjustments using volume dampers rather than
extractors and the dampers at air terminals.
1. Adjust each outlet in same room or space to within specified tolerances of
indicated quantities without generating noise levels above the limitations
prescribed by the Contract Documents.
KEO/21-7387-0004 23 0593 / 9 Testing, Adjusting And Balancing For Hvac
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
2. Adjust patterns of adjustable outlets for proper distribution without drafts.
A. Motors, 1/2 HP and Larger: Test at final balanced conditions and record the following
data:
1. Manufacturer, model, and serial numbers.
2. Motor horsepower rating.
3. Motor rpm.
4. Efficiency rating.
5. Nameplate and measured voltage, each phase.
6. Nameplate and measured amperage, each phase.
7. Starter thermal-protection-element rating.
A. During TAB, report the need for adjustment in temperature regulation within the
automatic temperature-control system.
B. Measure indoor wet- and dry-bulb temperatures every other hour for a period of two
successive eight-hour days, in each separately controlled zone, to prove correctness of
final temperature settings. Measure when the building or zone is occupied.
A. Measure, adjust, and record the airflow of each kitchen hood. For kitchen hoods
designed with integral makeup air, measure and adjust the exhaust and makeup airflow.
Measure airflow by duct Pitot-tube traverse. If a duct Pitot-tube traverse is not possible,
provide an explanation in the report of the reason(s) why and also the reason why the
method used was chosen.
1. Install welded test ports in the sides of the exhaust duct for the duct Pitot-tube
traverse. Install each test port with a threaded cap that is liquid tight.
C. Visually inspect the hood exhaust duct throughout its entire length in compliance with
authorities having jurisdiction. Begin at the hood connection and end at the point it
discharges outdoors. Report findings.
1. Check duct slopes as required.
2. Verify that duct access is installed as required.
3. Verify that point of termination is as required.
4. Verify that duct air velocity is within the range required.
5. Verify that duct is within a fire-rated enclosure.
D. Report deficiencies.
B. Measure, adjust, and record the pressurization of each room, each zone, and each
building by adjusting the supply, return, and exhaust airflows to achieve the indicated
conditions.
C. Measure space pressure differential where pressure is used as the design criteria, and
measure airflow differential where differential airflow is used as the design criteria for
space pressurization.
1. For pressure measurements, measure and record the pressure difference
between the intended spaces at the door with all doors in the space closed.
Record the high-pressure side, low-pressure side, and pressure difference
between each adjacent space.
2. For applications with cascading levels of space pressurization, begin in the most
critical space and work to the least critical space.
3. Test room pressurization first, then zones, and finish with building pressurization.
D. To achieve indicated pressurization, set the supply airflow to the indicated conditions
and adjust the exhaust and return airflow to achieve the indicated pressure or airflow
difference.
E. For spaces with pressurization being monitored and controlled automatically, observe
and adjust the controls to achieve the desired set point.
1. Compare the values of the measurements taken to the measured values of the
control system instruments and report findings.
2. Check the repeatability of the controls by successive tests designed to
temporarily alter the ability to achieve space pressurization. Test over
pressurization and under pressurization, and observe and report on the system's
ability to revert to the set point.
3. For spaces served by variable-air-volume supply and exhaust systems, measure
space pressurization at indicated airflow and minimum airflow conditions.
F. In spaces that employ multiple modes of operation, such as normal mode and
emergency mode or occupied mode and unoccupied mode, measure, adjust, and record
data for each operating mode.
G. Record indicated conditions and corresponding initial and final measurements. Report
deficiencies.
C. Perform vibration measurements when other building and outdoor vibration sources are
at a minimum level and will not influence measurements of equipment being tested.
1. Turn off equipment in the building that might interfere with testing.
2. Clear the space of people.
D. Perform vibration measurements after air and water balancing and equipment testing is
complete.
H. Measure and record equipment vibration, bearing vibration, equipment base vibration,
and building structure vibration. Record velocity and displacement readings in the
horizontal, vertical, and axial planes.
1. Pumps:
a. Pump Bearing: Drive end and opposite end.
b. Motor Bearing: Drive end and opposite end.
c. Pump Base: Top and side.
d. Building: Floor.
e. Piping: To and from the pump after flexible connections.
2. Fans and HVAC Equipment with Fans:
a. Fan Bearing: Drive end and opposite end.
b. Motor Bearing: Drive end and opposite end.
c. Equipment Casing: Top and side.
d. Equipment Base: Top and side.
e. Building: Floor.
f. Ductwork: To and from equipment after flexible connections.
g. Piping: To and from equipment after flexible connections.
3. Chillers and HVAC Equipment with Compressors:
a. Compressor Bearing: Drive end and opposite end.
b. Motor Bearing: Drive end and opposite end.
c. Equipment Casing: Top and side.
d. Equipment Base: Top and side.
e. Building: Floor.
f. Piping: To and from equipment after flexible connections.
I. For equipment with vibration isolation, take floor measurements with the vibration
isolation blocked solid to the floor and with the vibration isolation floating. Calculate and
report the differences.
B. Calibrate sound meters before each day of testing. Use a calibrator provided with the
sound meter complying with ANSI S1.40 and that has NIST certification.
C. Use a microphone that is suitable for the type of sound levels measured. For areas
where air velocities exceed 100 fpm (0.51 m/s), use a windscreen on the microphone.
D. Perform sound-level testing after air and water balancing and equipment testing are
complete.
F. Perform measurements when the space is not occupied and when the occupant noise
level from other spaces in the building and outside are at a minimum.
G. Clear the space of temporary sound sources so unrelated disturbances will not be
measured. Position testing personnel during measurements to achieve a direct line-of-
sight between the sound source and the sound-level meter.
H. Take sound measurements at a height approximately 48 inches (1200 mm) above the
floor and at least 36 inches (900 mm) from a wall, column, and other large surface
capable of altering the measurements.
I. Take sound measurements in dBA and in each of the 8 unweighted octave bands in the
frequency range of 63 to 8000 Hz.
J. Take sound measurements with the HVAC systems off to establish the background
sound levels and take sound measurements with the HVAC systems operating.
1. Calculate the difference between measurements. Apply a correction factor
depending on the difference and adjust measurements.
K. Perform sound testing at critical locations on Project for each of the space types; offices,
bedrooms, auditorium, classrooms, conference, spaces with NC 25 or lower,
mechanical rooms, etc. If testing multiple locations for each space type, select at least
one location that is near and at least one location that is remote from the predominant
sound source.
B. Observe and record the following conditions for each HVAC system:
1. The distance between the outside-air intake and the closest exhaust fan
discharge, cooling tower, flue termination, or vent termination.
2. Specified filters are installed. Check for leakage around filters.
3. Cooling coil drain pans have a positive slope to drain.
4. Cooling coil condensate drain trap maintains an air seal.
5. Evidence of water damage.
6. Insulation in contact with the supply, return, and outside air is dry and clean.
C. Measure and record indoor conditions served by each HVAC system. Make
measurements at multiple locations served by the system if required to satisfy the
following:
1. Most remote area.
2. One location per floor.
3. One location for every 5000 sq. ft. (500 sq. m).
D. Measure and record the following indoor conditions for each location two times at two-
hour intervals, and in accordance with ASHRAE 113:
1. Temperature.
2. Relative humidity.
3. Air velocity.
4. Concentration of carbon dioxide (ppm).
5. Concentration of carbon monoxide (ppm).
6. Nitrogen oxides (ppm).
7. Formaldehyde (ppm).
B. Check transmitter and controller locations and note conditions that would adversely
affect control functions.
C. Record controller settings and note variances between set points and actual
measurements.
D. Check the operation of limiting controllers (i.e., high- and low-temperature controllers).
E. Check free travel and proper operation of control devices such as damper and valve
operators.
F. Check the sequence of operation of control devices. Note air pressures and device
positions and correlate with airflow and water flow measurements. Note the speed of
response to input changes.
J. Record voltages of power supply and controller output. Determine whether the system
operates on a grounded or nongrounded power supply.
K. Note operation of electric actuators using spring return for proper fail-safe operations.
3.016 TOLERANCES
A. Set HVAC system airflow and water flow rates within the following tolerances:
1. Supply, Return, and Exhaust Fans and Equipment with Fans: Plus 5 to plus 10
percent.
2. Air Outlets and Inlets: 0 to minus 10 percent.
3. Heating-Water Flow Rate: 0 to minus 10 percent.
4. Cooling-Water Flow Rate: 0 to minus 5 percent.
3.017 REPORTING
B. Include a certification sheet in front of binder signed and sealed by the certified testing
and balancing engineer.
1. Include a list of instruments used for procedures, along with proof of calibration.
C. Final Report Contents: In addition to certified field report data, include the following:
1. Pump curves.
2. Fan curves.
3. Manufacturers' test data.
4. Field test reports prepared by system and equipment installers.
5. Other information relative to equipment performance, but do not include Shop
Drawings and Product Data.
E. System Diagrams: Include schematic layouts of air and hydronic distribution systems.
Present each system with single-line diagram and include the following:
1. Quantities of outside, supply, return, and exhaust airflows.
2. Water flow rates.
3. Duct, outlet, and inlet sizes.
4. Pipe and valve sizes and locations.
5. Terminal units.
6. Balancing stations.
7. Position of balancing devices.
F. Air-Handling Unit Test Reports: For air-handling units with coils, include the following:
1. Unit Data: Include the following:
a. Unit identification.
b. Location.
c. Make and type.
d. Model number and unit size.
e. Manufacturer's serial number.
f. Unit arrangement and class.
g. Discharge arrangement.
KEO/21-7387-0004 23 0593 / 17 Testing, Adjusting And Balancing For Hvac
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
h. Sheave make, size in inches (mm), and bore.
i. Sheave dimensions, center-to-center, and amount of adjustments in
inches (mm).
j. Number of belts, make, and size.
k. Number of filters, type, and size.
2. Motor Data:
a. Make and frame type and size.
b. Horsepower and rpm.
c. Volts, phase, and hertz.
d. Full-load amperage and service factor.
e. Sheave make, size in inches (mm), and bore.
f. Sheave dimensions, center-to-center, and amount of adjustments in
inches (mm).
3. Test Data (Indicated and Actual Values):
a. Total airflow rate in cfm (L/s).
b. Total system static pressure in inches wg (Pa).
c. Fan rpm.
d. Discharge static pressure in inches wg (Pa).
e. Filter static-pressure differential in inches wg (Pa).
f. Preheat coil static-pressure differential in inches wg (Pa).
g. Cooling coil static-pressure differential in inches wg (Pa).
h. Heating coil static-pressure differential in inches wg (Pa).
i. Outside airflow in cfm (L/s).
j. Return airflow in cfm (L/s).
k. Outside-air damper position.
l. Return-air damper position.
m. Damper position.
H. Electric-Coil Test Reports: For electric furnaces, duct coils, and electric coils installed in
central-station air-handling units, include the following:
1. Unit Data:
a. System identification.
b. Location.
c. Coil identification.
d. Capacity in Btuh (kW).
e. Number of stages.
f. Connected volts, phase, and hertz.
g. Rated amperage.
h. Airflow rate in cfm (L/s).
i. Face area in sq. ft. (sq. m).
j. Minimum face velocity in fpm (m/s).
2. Test Data (Indicated and Actual Values):
a. Heat output in Btuh (kW).
b. Airflow rate in cfm (L/s).
c. Air velocity in fpm (m/s).
d. Entering-air temperature in deg F (deg C).
e. Leaving-air temperature in deg F (deg C).
f. Voltage at each connection.
g. Amperage for each phase.
I. Fan Test Reports: For supply, return, and exhaust fans, include the following:
1. Fan Data:
a. System identification.
b. Location.
c. Make and type.
d. Model number and size.
e. Manufacturer's serial number.
f. Arrangement and class.
g. Sheave make, size in inches (mm), and bore.
h. Sheave dimensions, center-to-center, and amount of adjustments in
inches (mm).
2. Motor Data:
a. Make and frame type and size.
b. Horsepower and rpm.
c. Volts, phase, and hertz.
d. Full-load amperage and service factor.
e. Sheave make, size in inches (mm), and bore.
f. Sheave dimensions, center-to-center, and amount of adjustments in
inches (mm).
g. Number of belts, make, and size.
3. Test Data (Indicated and Actual Values):
a. Total airflow rate in cfm (L/s).
b. Total system static pressure in inches wg (Pa).
c. Fan rpm.
d. Discharge static pressure in inches wg (Pa).
e. Suction static pressure in inches wg (Pa).
KEO/21-7387-0004 23 0593 / 19 Testing, Adjusting And Balancing For Hvac
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
J. Round, Flat-Oval, and Rectangular Duct Traverse Reports: Include a diagram with a
grid representing the duct cross-section and record the following:
1. Report Data:
a. System and air-handling unit number.
b. Location and zone.
c. Traverse air temperature in deg F (deg C).
d. Duct static pressure in inches wg (Pa).
e. Duct size in inches (mm).
f. Duct area in sq. ft. (sq. m).
g. Indicated airflow rate in cfm (L/s).
h. Indicated velocity in fpm (m/s).
i. Actual airflow rate in cfm (L/s).
j. Actual average velocity in fpm (m/s).
k. Barometric pressure in psig (Pa).
K. Air-Terminal-Device Reports:
1. Unit Data:
a. System and air-handling unit identification.
b. Location and zone.
c. Test apparatus used.
d. Area served.
e. Air-terminal-device make.
f. Air-terminal-device number from system diagram.
g. Air-terminal-device type and model number.
h. Air-terminal-device size.
i. Air-terminal-device effective area in sq. ft. (sq. m).
2. Test Data (Indicated and Actual Values):
a. Airflow rate in cfm (L/s).
b. Air velocity in fpm (m/s).
c. Preliminary airflow rate as needed in cfm (L/s).
d. Preliminary velocity as needed in fpm (m/s).
e. Final airflow rate in cfm (L/s).
f. Final velocity in fpm (m/s).
g. Space temperature in deg F (deg C).
L. System-Coil Reports: For reheat coils and water coils of terminal units, include the
following:
1. Unit Data:
a. System and air-handling unit identification.
b. Location and zone.
c. Room or riser served.
d. Coil make and size.
e. Flowmeter type.
2. Test Data (Indicated and Actual Values):
a. Airflow rate in cfm (L/s).
b. Entering-water temperature in deg F (deg C).
c. Leaving-water temperature in deg F (deg C).
d. Water pressure drop in feet of head or psig (kPa).
e. Entering-air temperature in deg F (deg C).
f. Leaving-air temperature in deg F (deg C).
O. Sound Measurement Reports: Record sound measurements on octave band and dBA
test forms and on an NC or RC chart indicating the decibel level measured in each
3.019 INSPECTIONS
A. Initial Inspection:
1. After testing and balancing are complete, operate each system and randomly
check measurements to verify that the system is operating according to the final
test and balance readings documented in the Final Report.
2. Randomly check the following for each system:
a. Measure airflow of at least 10 percent of air outlets.
b. Measure water flow of at least 5 percent of terminals.
c. Measure room temperature at each thermostat/temperature sensor.
Compare the reading to the set point.
d. Measure sound levels at two locations.
e. Measure space pressure of at least 10 percent of locations.
f. Verify that balancing devices are marked with final balance position.
g. Note deviations to the Contract Documents in the Final Report.
B. Final Inspection:
1. After initial inspection is complete request that a final inspection be made. TAB
firm test and balance engineer shall conduct the inspection in the presence of
Owner / engineer.
2. Owner / Engineer can randomly select measurements documented in the final
report to be rechecked. The rechecking shall be limited to either minimum 15
percent of the total measurements recorded, or the extent of measurements that
can be accomplished in a normal 2 business days.
C. Reliability test for refrigeration / cooling plant and / or system shall take place between
1st of June and 30th of September and for heating plant and / or system between 16th
of November and 15th of February only.
D. During reliability tests, Contractor shall take spot readings as directed by the owner
representative to confirm that the system balance is maintained. Contractor shall
prepare and fill in log sheets recording test results and submit the same in a suitable
format, at the end of the test.
E. Completion certificates for HVAC system will be issued only after successful completion
of reliability tests.
A. Within 90 days of completing TAB, perform additional testing and balancing to verify that
balanced conditions are being maintained throughout and to correct unusual conditions.
B. Seasonal Periods: If initial TAB procedures were not performed during near-peak
summer and winter conditions, perform additional testing, inspecting, and adjusting
during near-peak summer and winter conditions.
END OF SECTION
HVAC INSULATION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The whole of the insulation work shall be carried out by an approved specialist insulation
Contractor. All allowances shall be included for arranging a specialist subcontract
accordingly and for informing the specialist Sub-contractor of all conditions relating to
the Contract and for coordinating his works with the remainder of the works.
B. All allowances shall be included for informing the specialist Sub-contractor of all details
of the building structure, program arrangements, and other relevant details at the time of
tender and for all necessary visits to site by the Sub-contractor or his workers.
D. In addition to complying with the relevant standards, all insulating material shall be free
from Asbestos and with low VOC.
E. Insulating materials shall be acceptable only if they are equal to or better than the
grades or classes of fire resistance as follows:
1. B.S. 476, Part 4, (Noncombustible grade.)
2. B.S. 476 Part 5 Class P, (Not easily ignitable.)
3. B.S. 476, Part 6, (Fire Propagation Index a maximum of 12.6.)
4. B.S. 476, Part 7, Class 1, (Surface spread of flame.)
5. B.S. 476 Part 9, (Production of emitted smoke shall not give more than 35%
obscuration of the light beam.)
F. All insulation finishes, and coverings shall be classified as Class 0 surface spread when
tested in accordance with B.S. 476, Part 6 & Part 7.
G. All adhesives, mastics, coatings, sealers and primers shall be classified as Class 1
surface spread when tested in accordance with B.S. 476, part 7, and shall have low
VOC content. They shall not in any way attack the insulation or the surface to which the
insulation is being applied and shall be suitable for the working temperatures.
A. Section Includes:
1. Insulation Materials:
a. Cellular glass/Fibre Glass
b. Flexible elastomeric/Elastomeric rubber
B. Related Sections:
1. Division 22 Section "Plumbing Insulation."
2. Division 23 Section "Metal Ducts" for duct liners.
1.03 SUBMITTALS
A. Product Data: For each type of product indicated. Include thermal conductivity,
thickness, and jackets (both factory and field applied, if any).
B. Shop Drawings:
1. Detail application of protective shields, saddles, and inserts at hangers for each
type of insulation and hanger.
2. Detail attachment and covering of heat tracing inside insulation.
3. Detail insulation application at pipe expansion joints for each type of insulation.
4. Detail insulation application at elbows, fittings, flanges, valves, and specialties for
each type of insulation.
5. Detail removable insulation at piping specialties, equipment connections, and
access panels.
6. Detail application of field-applied jackets.
7. Detail application at linkages of control devices.
8. Detail field application for each equipment type.
C. Samples: For each type of insulation and jacket indicated. Identify each Sample,
describing product and intended use.
1. Sample Sizes:
a. Submit samples of all types of insulation for approval. Submit pipe
insulation samples 300 mm long x 25 mm inside x 125 mm outside
diameter, and flat samples 300 mm x 300 mm x 25 mm, minimum size.
b. Submit with samples, the full technical brochures.
c. Where the specification calls for additional treatments, such as wrapping
and waterproofing, submit also a completed sample of similar size.
d. All samples after approval are to be retained on site to be a reference for
future work.
E. Material Test Reports: From a qualified testing agency acceptable to authorities having
jurisdiction indicating, interpreting, and certifying test results for compliance of insulation
materials, sealers, attachments, cements, and jackets, with requirements indicated.
Include dates of tests and test methods employed.
A. Installer Qualifications: Skilled mechanics who have successfully completed three (3)
years minimum experience.
C. Mockups: Before installing insulation, build mockups for each type of insulation and
finish listed below to demonstrate quality of insulation application and finishes. Build
mockups in the location indicated or, if not indicated, as directed by Architect. Use
materials indicated for the completed Work.
1. Piping Mockups:
a. One 10-foot (3-m) section of NPS 2 (DN 50) straight pipe.
b. One each of a 90-degree threaded, welded, and flanged elbow.
c. One each of a threaded, welded, and flanged tee fitting.
d. One NPS 2 (DN 50) or smaller valve, and one NPS 2-1/2 (DN 65) or
larger valve.
e. Four support hangers including hanger shield and insert.
f. One threaded strainer and one flanged strainer with removable portion of
insulation.
g. One threaded reducer and one welded reducer.
h. One pressure temperature tap.
i. One mechanical coupling.
2. Ductwork Mockups:
a. One 10-foot (3-m) section each of rectangular and round straight duct.
b. One each of a 90-degree mitered round and rectangular elbow, and one
each of a 90-degree radius round and rectangular elbow.
c. One rectangular branch takeoff and one round branch takeoff from a
rectangular duct. One round tee fitting.
d. One rectangular and round transition fitting.
e. Four support hangers for round and rectangular ductwork.
B. Protect insulation from moisture and dirt by inside storage and enclosure and polythene
wrapping in accordance with the manufacturer’s recommendation.
1.06 COORDINATION
A. Coordinate size and location of supports, hangers, and insulation shields specified in
Division 23 Section "Hangers and Supports for HVAC Piping and Equipment."
B. Coordinate clearance requirements with piping Installer for piping insulation application,
duct Installer for duct insulation application, and equipment Installer for equipment
insulation application. Before preparing piping and ductwork Shop Drawings, establish
and maintain clearance requirements for installation of insulation and field-applied
jackets and finishes and for space required for maintenance.
1.07 SCHEDULING
A. Submit maintenance data for each type of mechanical insulation. Include this data,
product data and certifications in the maintenance manual.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Insulating materials shall have thermal conductivity values not more than those listed as
follows:
--------------------------------------------------------------------------------------------------------------
MATERIAL TYPE THERMAL CONDUCTIVITY.
W/M/DEG.C
--------------------------------------------------------------------------------------------------------------
Mineral wool Sectional 0.04
Mineral wool Slabs 0.04
Fibre Glass All 0.034
Closed Cell All 0.035
(elastomeric foam)
Polyurethane Sectional 0.025
Styrofoam Rigid 0.026
Polyolefin All 0.032
---------------------------------------------------------------------------------------------------
All conductivity figures are rated at an average temperature of 23 deg C.The closed
cell elastomeric rubber insulation shall have following characteristics in addition to
clause above:
1. Water vapour permeability 0.09 ugm/Nh, BS 4370/2 (= 7000 to DIN 52615)
(OR) < 0.05 Perm-inch
2. Density 50 ±10 kg / m3 or 2.54Lb / ft3 to 3.75Lb / ft3
3. Closed cell content > 90%.
4. Corrosion risk assessment Din 1988 / 7 Certified.
5. Noise reduction Din 4109 up to 32 dB (A).
6. Thermal conductivity of 0.035 w/mk at 23°C mean temperature to BS
874 PART 2 – 86 (DIN 52613, 52612) or ASTM C518
B. Material shall be FM 4924 or UL 723 approved and carry a stamp on the facing.
C. The insulation thickness for pipes and ducts shall be verified by the specialist supplier/
manufacturer to confirm no condensation.
E. Products that come in contact with stainless steel shall have a leachable chloride
content of less than 50 ppm when tested according to ASTM C 871.
F. Insulation materials for use on austenitic stainless steel shall be qualified as acceptable
according to ASTM C 795.
G. Foam insulation materials shall not use CFC or HCFC blowing agents in the
manufacturing process.
H. Calcium Silicate:
R. Phenolic:
1. Preformed pipe insulation of rigid, expanded, closed-cell structure. Comply with
ASTM C 1126, Type III, Grade 1.
2. Block insulation of rigid, expanded, closed-cell structure. Comply with
ASTM C 1126, Type II, Grade 1.
3. Factory fabricate shapes according to ASTM C 450 and ASTM C 585.
4. Factory-Applied Jacket: Requirements are specified in "Factory-Applied Jackets"
Article.
a. Preformed Pipe Insulation: ASJ.
b. Board for Duct and Plenum Applications: ASJ.
c. Board for Equipment Applications: ASJ.
S. Physically cross-linked polyolefin foam with factory applied reinforced aluminium foil.
Insulation shall have the following specifications:
1. Physically cross-linked, closed cell polyolefin foam with factory applied reinforced
aluminium foil and factory applied acrylic adhesive backing.
2. Exceed the minimum thickness to prevent condensation.
3. Density: 25 kg/m3 (foam core only).
4. Thermal Conductivity (ASTM C518): Maximum 0.032 W/m.°K at mean
temperature 23°C.
5. Water absorption: <0.2 % v/v.
6. Water Vapour permeability (ASTM E96): Maximum 2.3 x 10-15 kg/Pa.s.m,
(µ>80,000).
7. Service Temperature Range: - 80°C ~ +80°C (adhesive backing).
8. Zero mould growth when tested to ASTM G21.
9. Fire Rating:
a. Class 0 to BS476 Parts 6 and 7.
b. Euroclass B-S2,d0 classification according to EN 13501Part 1.
c. Complies with NFPA 90A and B (ASTM E84 25/50 rating).
d. Complies with FM 4924 fire performance criteria and “FM Approved” by
FM Approvals certification body.
10. Smoke Density and Toxicity:
a. Complies with the requirements of International Maritime Organization
Resolution MSC 61(67) Part 2.
b. Dm<200 (ISO 5659 Part 2 gas analysis); combustion gases CO, HCl, HF,
NOx, HBr, HCN and SO2 to be within the maximum allowable
B. Fire-Rated Blanket: High-temperature, flexible, blanket insulation with FSK jacket that is
tested and certified to provide a 2-hour fire rating by a NRTL acceptable to authority
having jurisdiction.
2.05 ADHESIVES
A. Materials shall be compatible with insulation materials, jackets, and substrates and for
bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated.
G. ASJ Adhesive, and FSK and PVDC Jacket Adhesive: Comply with MIL-A-3316C,
Class 2, Grade A for bonding insulation jacket lap seams and joints.
I. Physically crosslinked adhesive: shall be suitable for indoor and outdoor use in high
humidity envinronments and shall meet Class 0 requirements when tested for fire
performance to BS 476 Part 6 and Part 7.
A. Adhesive shall be a flexible, fire resistive compound suitable for vapour sealing
insulated ducts and pipes.
B. Adhesive shall be suitable for indoor and outdoor use and in high humidity
environments.
C. Water vapour permeance shall not exceed 0.05 perms at 0.030-inch dry film thickness
when tested in compliance with ASTMF 1249.
D. When tested for surface burning characteristics in compliance with ASTM E84, flame
spread index shall be less than 25 and smoke developed index less than 50.
E. Adhesive shall be UL classified and shall meet or exceed the requirements of NFPA
90A and 90 B 25/50.
A. Fungicidal protective coatings shall be applied over external surfaces of chilled water
pipes and interior and exterior surfaces of ductwork.
B. Coating shall be a polyacrylate copolymer emulsion specially formulated for long term
fungicidal activity with no loss of activity on aging. It shall prevent the spread of molds
and odour causing bacteria on the applied surface.
2.08 MASTICS
A. Materials shall be compatible with insulation materials, jackets, and substrates; comply
with MIL-C-19565C, Type II.
B. Vapor-Barrier Mastic: Water based; suitable for indoor and outdoor use on below
ambient services.
1. Water-Vapor Permeance: ASTM E 96, Procedure B, 0.013 perm (0.009 metric
perm) at 43-mil (1.09-mm) dry film thickness.
2. Service Temperature Range: Minus 20 to plus 180 deg F (Minus 29 to plus 82
deg C).
3. Solids Content: ASTM D 1644, 59 percent by volume and 71 percent by weight.
4. Color: White.
C. Vapor-Barrier Mastic: Solvent based; suitable for indoor use on below ambient services.
1. Water-Vapor Permeance: ASTM F 1249, 0.05 perm (0.03 metric perm) at 35-mil
(0.9-mm) dry film thickness.
2. Service Temperature Range: 0 to 180 deg F (Minus 18 to plus 82 deg C).
3. Solids Content: ASTM D 1644, 44 percent by volume and 62 percent by weight.
4. Color: White.
D. Vapor-Barrier Mastic: Solvent based; suitable for outdoor use on below ambient
services.
E. Breather Mastic: Water based; suitable for indoor and outdoor use on above ambient
services.
1. Water-Vapor Permeance: ASTM F 1249, 3 perms (2 metric perms) at 0.0625-
inch (1.6-mm) dry film thickness.
2. Service Temperature Range: Minus 20 to plus 200 deg F (Minus 29 to plus 93
deg C).
3. Solids Content: 63 percent by volume and 73 percent by weight.
4. Color: White.
2.09 SEALANTS
A. Joint Sealants:
1. Materials shall be compatible with insulation materials, jackets, and substrates.
2. Permanently flexible, elastomeric sealant.
3. Service Temperature Range: Minus 100 to plus 300 deg F (Minus 73 to plus 149
deg C).
4. Color: White or gray.
C. ASJ Flashing Sealants, and Vinyl, PVDC, and PVC Jacket Flashing Sealants:
1. Materials shall be compatible with insulation materials, jackets, and substrates.
2. Fire- and water-resistant, flexible, elastomeric sealant.
3. Service Temperature Range: Minus 40 to plus 250 deg F (Minus 40 to plus 121
deg C).
4. Color: White.
A. Woven Glass-Fiber Fabric for Pipe Insulation: Approximately 2 oz./sq. yd. (68 g/sq. m)
with a thread count of 10 strands by 10 strands/sq. inch (4 strands by 4 strands/sq. mm)
for covering pipe and pipe fittings.
B. Woven Glass-Fiber Fabric for Duct and Equipment Insulation: Approximately 6 oz./sq.
yd. (203 g/sq. m) with a thread count of 5 strands by 5 strands/sq. inch (2 strands by 2
strands/sq. mm) for covering equipment.
C. Woven Polyester Fabric: Approximately 1 oz./sq. yd. (34 g/sq. m) with a thread count of
10 strands by 10 strands/sq. inch (4 strands by 4 strands/sq. mm), in a Leno weave, for
duct, equipment, and pipe.
A. Woven Glass-Fiber Fabric: Comply with MIL-C-20079H, Type I, plain weave, and
presized a minimum of 8 oz./sq. yd. (271 g/sq. m).
A. Field-applied jackets shall comply with ASTM C 921, Type I, unless otherwise indicated.
2.014 TAPES
A. ASJ Tape: White vapor-retarder tape matching factory-applied jacket with acrylic
adhesive, complying with ASTM C 1136.
1. Width: 3 inches (75 mm).
2. Thickness: 11.5 mils (0.29 mm).
3. Adhesion: 90 ounces force/inch (1.0 N/mm) in width.
B. FSK Tape: Foil-face, vapor-retarder tape matching factory-applied jacket with acrylic
adhesive; complying with ASTM C 1136.
1. Width: 3 inches (75 mm).
2. Thickness: 6.5 mils (0.16 mm).
3. Adhesion: 90 ounces force/inch (1.0 N/mm) in width.
4. Elongation: 2 percent.
5. Tensile Strength: 40 lbf/inch (7.2 N/mm) in width.
6. FSK Tape Disks and Squares: Precut disks or squares of FSK tape.
C. Aluminum-Foil Tape: Tape shall use reinforced aluminium foil of minimum 9-micron
thickness and minimum width 50mm to provide vapour ceiling of insulated ducts and
pipes.
E. Aluminum-FSK Tapes: Aluminum FSK Tapes to be used with glass wool insulation
having FSK/FRK facing. Plain Aluminum Foil Tape should be used with FSK/FRK faced
glasswool insulation. The adhesive used shall be acrylic adhesive and thickness
excluding substrate shall not be less than 195 micron. Temperature resistance to be
from 30 deg F to 250 deg F and peel adhesion not to be lower than 83 oz/inch width.
Tensile strength not be lower than 22 lbs/inch width and rolling tack to be 7-7/8” or
better with a 7/16” ball. Tapes used should not be lower than 3 inch (72 mm) width.
Confirms BS 476 Part 6, Part 7 with fire propagation Index, I=1.5. Water Vapor
Transmission value 0.304 g/h/m2 as per ASTM E 96 standards. Average Tensile
Strength of 16.17 N/mm2 and Elongation 11.49% as per ASTM D 638:03 standards.
Global Warming Potential value 0 and Ozone Depletion Potential value 5.
F. Alum Glass Cloth Tape: Alum glass Cloth Tape to be used with Glass wool insulation
having a similar facing. Aluminum Foil Thickness to be minimum of 7 micron and Alum-
Glass Cloth backing to be a minimum of 120 micron. Peel Adhesion to be 25 N/25 mm
or better and rolling tack to be 20 cm for a 11 mm ball or better. Service temperature to
be 20 deg C or better. Confirms BS 476 Part 6 and Part 7, Class O. Fungal Resistance
rating of 2 as per ASTM G 21-96. Average Tensile Strength of 47 kgf/25mm width as
per ASTM D 638 standards. Global Warming Potential value 0 and Ozone Depletion
Potential value 5.
2.015 SECUREMENTS
A. Bands:
1. Stainless Steel: ASTM A 167 or ASTM A 240/A 240M, Type 304 or Type 316;
0.015 inch (0.38 mm) thick, 3/4 inch (19 mm) wide with wing or closed seal.
A. Stainless-Steel Corner Angles: 0.024 inch (0.61 mm) thick, minimum 1 by 1 inch (25 by
25 mm), stainless steel according to ASTM A 167 or ASTM A 240/A 240M, Type 304 or
316
2.017 APPLICATION
A. Ductwork Insulation
1. Concealed supply, return, fresh air and extract air ducts- Fibre Glass
a. Unless otherwise indicated insulate all ductwork with 25 mm thick, 24
Kg/M3 density aluminium foil faced fibreglass duct insulation. Fasten the
insulation with adhesive on 200 to 250 mm centres. Butt all joints tightly
and seal all breaks and joints by adhering a 75 mm Aluminium foil vapour
barrier tape or sheet with a fire-retardant adhesive.
b. Insulate flexible connections and connections to diffusers with 25 mm
thick, 24 Kg/M3 density reinforced aluminium foil faced, flame resistant
flexible fiberglass insulation. Overlap onto adjacent insulation and seal
with adhesive duct tape to give good closure.
c. Where ductwork is installed in ceiling voids and masonry shafts, which are
not used as return air plenums insulate with 50mm thick, 48 Kg/M3
density aluminium foil faced rigid fibreglass duct insulation.
d. Finish all duct insulation with a 20x20 (thread/inch) woven glass cloth
cover adhered between two coats of fire resistant fungicidal protective
lagging adhesive.
2. Concealed Supply, Return, Fresh Air and Extract air ducts- Closed Cell
Elastomeric rubber
a. Insulate all GI rectangular supply, return, fresh air and extract air ductwork
within air-conditioned areas with 13mm thick closed cell elastomeric foam
sheets with a density of 50±10kg/m3 .
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine substrates and conditions for compliance with requirements for installation and
other conditions affecting performance of insulation application.
1. Verify that systems and equipment to be insulated have been tested and are free
of defects.
2. Verify that surfaces to be insulated are clean and dry.
3. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.02 PREPARATION
B. Mix insulating cements with clean potable water; if insulating cements are to be in
contact with stainless-steel surfaces, use demineralized water.
C. All material delivered to site shall be new and fully dried out and so maintained
throughout the progress of the works.
D. All insulating materials shall be stored in storage sheds, and in accordance with the
Manufacturer's recommendations.
E. In order to ensure that the insulation applied is in all respects in accordance with the
specification, sections shall, as required by the Consultant, be cut from the finished
insulation.
F. The Contractor is to allow in his price for the removal and replacement of two sections of
each type of insulation.
G. If, however, defects are revealed, further sections shall be cut out for inspection, and all
cutout sections shall be replaced at no cost to the Contract.
H. If further defects are revealed then the Consultant shall have the right, when in his
opinion it is necessary, to issue instructions for any part or the whole of the insulation to
be removed and replaced. The replacement with new insulation shall be to the
satisfaction of the Consultant and the cutting out and replacing shall be at no cost to the
Contract.
I. Particular attention shall be paid to the finished appearance of all thermal insulation
which must present a neat and symmetrical appearance running true in line with pipe
layouts, etc.
J. Any rough, irregular and badly finished surfaces shall be stripped down and re-insulated
to the Consultant's satisfaction.
K. In certain cases, the type of insulation specified will require a painted finish, in addition
to identifying bands and any signs which are to be applied.
L. All systems are to have been tested and approved by the Consultant prior to installation
of insulation.
M. Manufacturer shall have production process control in accordance with ISO 9002 / UNI
EN 29002 or any other equivalent standard.
N. In case of heavy ducts and pipes wherein the supports are fixed directly on ducts / pipes
the supports shall be also insulated with a thermal break / barrier.
O. The insulation thickness for pipes and ducts shall be verified by the specialist supplier/
manufacturer to confirm no condensation and temperature loss.
B. Install insulation materials, forms, vapor barriers or retarders, jackets, and thicknesses
required for each item of equipment, duct system, and pipe system as specified in
insulation system schedules.
C. Install accessories compatible with insulation materials and suitable for the service.
Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in
either wet or dry state.
D. Install insulation with longitudinal seams at top and bottom of horizontal runs.
E. Install multiple layers of insulation with longitudinal and end seams staggered.
F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and
specialties.
H. Install insulation with tight longitudinal seams and end joints. Bond seams and joints
with adhesive recommended by insulation material manufacturer.
J. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at
hangers, supports, anchors, and other projections with vapor-barrier mastic.
1. Install insulation continuously through hangers and around anchor attachments.
2. For insulation application where vapor barriers are indicated, extend insulation on
anchor legs from point of attachment to supported item to point of attachment to
structure. Taper and seal ends at attachment to structure with vapor-barrier
mastic.
3. Install insert materials and install insulation to tightly join the insert. Seal
insulation to insulation inserts with adhesive or sealing compound recommended
by insulation material manufacturer.
4. Cover inserts with jacket material matching adjacent pipe insulation. Install
shields over jacket, arranged to protect jacket from tear or puncture by hanger,
support, and shield.
M. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its
nominal thickness.
N. Finish installation with systems at operating conditions. Repair joint separations and
cracking due to thermal movement.
O. Repair damaged insulation facings by applying same facing material over damaged
areas. Extend patches at least 4 inches (100 mm) beyond damaged areas. Adhere,
staple, and seal patches similar to butt joints.
3.04 PENETRATIONS
D. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire
Rated): Install insulation continuously through walls and partitions.
KEO/21-7387-0004 23 0700 / 23 Hvac Insulation
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
E. Insulation Installation at Fire-Rated Wall and Partition Penetrations: Install insulation
continuously through penetrations of fire-rated walls and partitions. Terminate insulation
at fire damper sleeves for fire-rated wall and partition penetrations. Externally insulate
damper sleeves to match adjacent insulation and overlap duct insulation at least 2
inches (50 mm).
1. Comply with requirements in Division 07 Section "Penetration Firestopping" and
fire-resistive joint sealers.
A. Mineral Fiber, Pipe and Tank Insulation Installation for Tanks and Vessels: Secure
insulation with adhesive and anchor pins and speed washers.
1. Apply adhesives according to manufacturer's recommended coverage rates per
unit area, for 100 percent coverage of tank and vessel surfaces.
2. Groove and score insulation materials to fit as closely as possible to equipment,
including contours. Bevel insulation edges for cylindrical surfaces for tight joints.
Stagger end joints.
3. Protect exposed corners with secured corner angles.
4. Install adhesively attached or self-sticking insulation hangers and speed washers
on sides of tanks and vessels as follows:
a. Do not weld anchor pins to ASME-labeled pressure vessels.
b. Select insulation hangers and adhesive that are compatible with service
temperature and with substrate.
c. On tanks and vessels, maximum anchor-pin spacing is 3 inches (75 mm)
from insulation end joints, and 16 inches (400 mm) o.c. in both directions.
d. Do not over compress insulation during installation.
e. Cut and miter insulation segments to fit curved sides and domed heads of
tanks and vessels.
f. Impale insulation over anchor pins and attach speed washers.
g. Cut excess portion of pins extending beyond speed washers or bend
parallel with insulation surface. Cover exposed pins and washers with
tape matching insulation facing.
5. Secure each layer of insulation with stainless-steel or aluminum bands. Select
band material compatible with insulation materials.
6. Where insulation hangers on equipment and vessels are not permitted or
practical and where insulation support rings are not provided, install a girdle
network for securing insulation. Stretch prestressed aircraft cable around the
diameter of vessel and make taut with clamps, turnbuckles, or breather springs.
Place one circumferential girdle around equipment approximately 6 inches (150
mm) from each end. Install wire or cable between two circumferential girdles 12
inches (300 mm) o.c. Install a wire ring around each end and around outer
B. Flexible Elastomeric Thermal Insulation Installation for Tanks and Vessels: Install
insulation over entire surface of tanks and vessels.
1. Apply 100 percent coverage of adhesive to surface with manufacturer's
recommended adhesive.
2. Seal longitudinal seams and end joints.
A. Requirements in this article generally apply to all insulation materials except where more
specific requirements are specified in various pipe insulation material installation
articles.
A. Seal longitudinal seams and end joints with manufacturer's recommended adhesive to
eliminate openings in insulation that allow passage of air to surface being insulated.
E. Blanket Insulation Installation on Ducts and Plenums: Secure with adhesive and
insulation pins.
1. Apply adhesives according to manufacturer's recommended coverage rates per
unit area, for 100 percent coverage of duct and plenum surfaces.
2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and
transitions.
3. Install either capacitor-discharge-weld pins and speed washers or cupped-head,
capacitor-discharge-weld pins on sides and bottom of horizontal ducts and sides
of vertical ducts as follows:
a. On duct sides with dimensions 18 inches (450 mm) and smaller, place
pins along longitudinal centerline of duct. Space 3 inches (75 mm)
maximum from insulation end joints, and 16 inches (400 mm) o.c.
b. On duct sides with dimensions larger than 18 inches (450 mm), place pins
16 inches (400 mm) o.c. each way, and 3 inches (75 mm) maximum from
insulation joints. Install additional pins to hold insulation tightly against
surface at cross bracing.
c. Pins may be omitted from top surface of horizontal, rectangular ducts and
plenums.
d. Do not over compress insulation during installation.
e. Impale insulation over pins and attach speed washers.
f. Cut excess portion of pins extending beyond speed washers or bend
parallel with insulation surface. Cover exposed pins and washers with
tape matching insulation facing.
4. For ducts and plenums with surface temperatures below ambient, install a
continuous unbroken vapor barrier. Create a facing lap for longitudinal seams
and end joints with insulation by removing 2 inches (50 mm) from 1 edge and 1
end of insulation segment. Secure laps to adjacent insulation section with 1/2-
F. Board Insulation Installation on Ducts and Plenums: Secure with adhesive and
insulation pins.
1. Apply adhesives according to manufacturer's recommended coverage rates per
unit area, for 100 percent coverage of duct and plenum surfaces.
2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and
transitions.
3. Install either capacitor-discharge-weld pins and speed washers or cupped-head,
capacitor-discharge-weld pins on sides and bottom of horizontal ducts and sides
of vertical ducts as follows:
a. On duct sides with dimensions 18 inches (450 mm) and smaller, place
pins along longitudinal centerline of duct. Space 3 inches (75 mm)
maximum from insulation end joints, and 16 inches (400 mm) o.c.
b. On duct sides with dimensions larger than 18 inches (450 mm), space
pins 16 inches (400 mm) o.c. each way, and 3 inches (75 mm) maximum
from insulation joints. Install additional pins to hold insulation tightly
against surface at cross bracing.
c. Pins may be omitted from top surface of horizontal, rectangular ducts and
plenums.
d. Do not over compress insulation during installation.
e. Cut excess portion of pins extending beyond speed washers or bend
parallel with insulation surface. Cover exposed pins and washers with
tape matching insulation facing.
4. For ducts and plenums with surface temperatures below ambient, install a
continuous unbroken vapor barrier. Create a facing lap for longitudinal seams
and end joints with insulation by removing 2 inches (50 mm) from 1 edge and 1
end of insulation segment. Secure laps to adjacent insulation section with 1/2-
inch (13-mm) outward-clinching staples, 1 inch (25 mm) o.c. Install vapor barrier
consisting of factory- or field-applied jacket, adhesive, vapor-barrier mastic, and
sealant at joints, seams, and protrusions.
A. Where glass-cloth jackets are indicated, install directly over bare insulation or insulation
with factory-applied jackets.
1. Draw jacket smooth and tight to surface with 2-inch (50-mm) overlap at seams
and joints.
2. Embed glass cloth between two 0.062-inch- (1.6-mm-) thick coats of lagging
adhesive.
3. Completely encapsulate insulation with coating, leaving no exposed insulation.
C. Where metal jackets are indicated, install with 2-inch (50-mm) overlap at longitudinal
seams and end joints. Overlap longitudinal seams arranged to shed water. Seal end
joints with weatherproof sealant recommended by insulation manufacturer. Secure
jacket with stainless-steel bands 12 inches (300 mm) o.c. and at end joints.
A. Where fire-rated insulation system is indicated, secure system to ducts and duct
hangers and supports to maintain a continuous fire rating.
B. Insulate duct access panels and doors to achieve same fire rating as duct.
3.014 FINISHES
A. Duct, Equipment, and Pipe Insulation with ASJ, Glass-Cloth, or Other Paintable Jacket
Material: Paint jacket with paint system identified below and as specified in Division 09
painting Sections.
1. Flat Acrylic Finish: Two finish coats over a primer that is compatible with jacket
material and finish coat paint. Add fungicidal agent to render fabric mildew proof.
a. Finish Coat Material: Interior, flat, latex-emulsion size.
B. Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats
of insulation manufacturer's recommended protective coating.
C. Color: Final color as selected by Architect. Vary first and second coats to allow visual
inspection of the completed Work.
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
D. All insulation applications will be considered defective Work if sample inspection reveals
noncompliance with requirements.
A. Aluminium cladding shall be provided to ducts with neat 90-degree joints and finish.
Material shall be with plain finish.
B. In pipework the longitudinal joints shall be cleated or held in position with stainless steel
bands and clips. Elbows and other fittings shall be made with mitred section and riveted.
All valves strainers, flexible connection etc. shall have easily removable boxes with
stainless steel aluminium toggle clips.
C. In ductwork the joints shall be riveted or banded with stainless steel band and clips to
avoid sagging. Boxes to be made around duct traverse joints.
D. All gaps shall be to a minimum and shall be sealed with silicon mastic suitable for
outdoor.
A. Insulation materials and thicknesses are identified below. If more than one material is
listed for a type of equipment, selection from materials listed is Contractor's option.
B. Insulate indoor and outdoor equipment in paragraphs below that is not factory insulated.
C. Chillers: Insulate cold surfaces on chillers, including, but not limited to, evaporator
bundles, condenser bundles, suction piping, compressor inlets, tube sheets, water
boxes, and nozzles with one of the following:
1. Flexible Elastomeric: 1 inch (25 mm) thick.
2. Mineral-Fiber Board: 1 inch (25 mm) thick and 3-lb/cu. ft. (48-kg/cu. m) nominal
density.
3. Mineral-Fiber Pipe and Tank: 1 inch (25 mm) thick.
J. Thermal storage tank (brine, water, ice) insulation shall be one of the following:
1. Mineral-Fiber Board: 3 inches (75 mm) thick and 3-lb/cu. ft. (48-kg/cu. m)
nominal density.
2. Mineral-Fiber Pipe and Tank: 3 inches (75 mm) thick.
B. Chilled Water, All Sizes: Cellular glass, 2 inches (50 mm) thick.
C. Condenser-Water Supply and Return, All Sizes: Cellular glass, 2 inches (50 mm) thick.
D. Heating-Hot-Water Supply and Return, All Sizes, 200 Deg F (93 Deg C) and below:
Cellular glass, 3 inches (75 mm) thick.
F. Steam and Steam Condensate, All Sizes, 350 Deg F (177 Deg C) and below:
1. Calcium Silicate: 4 inches (100 mm) thick.
2. Cellular Glass: 4 inches (100 mm) thick.
G. Steam and Steam Condensate, All Sizes, above 350 Deg F (177 Deg C):
1. Calcium Silicate: 5 inches (125 mm) thick.
2. Cellular Glass: 5 inches (125 mm) thick.
H. Dual-Service Heating and Cooling, All Sizes, 40 to 200 Deg F (4 to 93 Deg C): Cellular
glass, 3 inches (75 mm) thick.
I. Fuel Oil Piping, All Sizes, Heated: Cellular glass, 2 inches (50 mm) thick.
A. Install jacket over insulation material. For insulation with factory-applied jacket, install
the field-applied jacket over the factory-applied jacket.
D. Equipment, Exposed, Larger Than 48 Inches (1200 mm) in Diameter or with Flat
Surfaces Larger Than 72 Inches (1800 mm):
1. Woven Glass-Fiber Fabric material (Item 2.09B) with vapor barrier mastic plus
2. Painted Aluminum Cladding, Smooth 0.032 inch (0.81 mm) thick finish.
E. Piping, Exposed:
1. Woven Glass-Fiber Fabric material (Item 2.09B) with vapor barrier mastic plus
Painted Aluminum Cladding, Smooth 0.032 inch (0.81 mm) thick finish.
A. Install jacket over insulation material. For insulation with factory-applied jacket, install
the field-applied jacket over the factory-applied jacket.
B. If more than one material is listed, selection from materials listed is Contractor's option.
C. Ducts and Plenums, Exposed, up to 48 Inches (1200 mm) in Diameter or with Flat
Surfaces up to 72 Inches (1800 mm):
D. Ducts and Plenums, Exposed, Larger Than 48 Inches (1200 mm) in Diameter or with
Flat Surfaces Larger Than 72 Inches (1800 mm):
1. Two Layers of Woven Glass-Fiber Fabric material (Item 2.10A) with water vapor
barrier mastic plus Aluminum Cladding, Smooth: 0.032 inch (0.81 mm) thick
finish.
E. Equipment, Concealed:
1. Woven Glass-Fiber Fabric material (Item 2.09B) with vapor barrier mastic.
G. Equipment, Exposed, Larger Than 48 Inches (1200 mm) in Diameter or with Flat
Surfaces Larger Than 72 Inches (1800 mm):
1. Two Layers of Woven Glass-Fiber Fabric material (Item 2.09B) with vapor barrier
mastic plus Painted Aluminum Cladding, Smooth 0.032 inch (0.81 mm) thick
finish.
H. Piping, Concealed:
1. Woven Glass-Fiber Fabric material (Item 2.09A) with vapor barrier mastic.
I. Piping, Exposed:
1. Woven Glass-Fiber Fabric material (Item 2.09B) with vapor barrier mastic plus
Painted Aluminum Cladding, Smooth 0.032 inch (0.81 mm) thick finish.
B. The insulation, in sizes indicated shall be applied over clean, dry surfaces. Adjoining
sections of insulation should be butted firmly together with the longitudinal seam of the
jacket located on the bottom half of the pipe.
C. Insulate and finish valves and fittings in the same manner and same thickness as piping
in which such items are installed. Moulded, factory shaped sectional pipe covering,
factory- or job-fabricated may be used subject to satisfactory visual checking by the
Consultant.
D. Direct contact between pipe and hanger shall be avoided. Hangers shall pass outside of
the sheet metal protection saddle, which shall cover a section of high-density insulation,
of sufficient length to support the pipe without crushing the insulation. The vapour barrier
shall be lapped over the saddle and securely cemented to it. Minimum thickness of
metal saddle is 1.5 mm.
END OF SECTION
COMMISSIONING OF HVAC
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes requirements for commissioning the HVAC system and its
subsystems and equipment.
1.02 DEFINITIONS
A. Architect: Includes Architect identified in the Contract for Construction between Owner
and Contractor, plus consultant/design professionals responsible for design of HVAC,
electrical, communications, controls for HVAC systems, and other related systems.
B. Test Checklists: Contractor shall develop test checklists for HVAC systems,
subsystems, and equipment, including interfaces and interlocks with other systems.
Contractor shall prepare separate checklists for each mode of operation and provide
space to indicate whether the mode under test responded as required. In addition to the
requirements specified in Division 01 Section "General Commissioning Requirements,"
checklists shall include, but not be limited to, the following:
1. Calibration of sensors and sensor function.
2. Testing conditions under which test was conducted, including (as applicable)
ambient conditions, set points, override conditions, and status and operating
conditions that impact the results of test.
3. Control sequences for HVAC systems.
4. Strength of control signal for each set point at specified conditions.
5. Responses to control signals at specified conditions.
6. Sequence of response(s) to control signals at specified conditions.
7. Electrical demand or power input at specified conditions.
8. Power quality and related measurements.
9. Expected performance of systems, and equipment at each step of test.
10. Narrative description of observed performance of systems, and equipment.
Notation to indicate whether the observed performance at each step meets the
expected results.
11. Interaction of auxiliary equipment.
12. Issues log.
1.05 SUBMITTALS
B. Testing Procedures: Contractor shall submit detailed testing plan, procedures, and
checklists for each series of tests. Submittals shall include samples of data reporting
sheets that will be part of the reports.
E. Certified Pipe Cleaning and Flushing Report: Contractor shall certify that pipe cleaning,
flushing, hydrostatic testing, and chemical treating have been completed.
F. Test and Inspection Reports: Contractor shall compile and submit test and inspection
reports and certificates and shall include them in systems manual and commissioning
report.
H. Certified TAB Reports: Contractor shall submit verified, certified TAB reports.
PART 3 - EXECUTION
A. TAB Preparation:
1. Contractor shall provide data required for "Pre-Field TAB Engineering Reports"
specified in Division 23 Section "Testing, Adjusting, and Balancing for HVAC."
a. Contractor shall use this data to certify that prestart and startup activities
have been completed for systems and equipment installation.
D. If deficiencies are identified during verification testing, Contractor shall take action to
remedy the deficiency. The Architect / Engineer shall review final tabulated checklists
and data sheets to determine if verification is complete and that system is operating
according to the Contract Documents.
E. The Architect / Engineer shall certify that TAB Work has been successfully completed.
3.03 TESTING
B. Test systems and intersystem performance after test checklists for systems,
subsystems, and equipment have been approved.
E. Detailed Testing Procedures: The Architect / Engineer with HVAC Contractor shall
prepare detailed testing plans, procedures, and checklists for HVAC systems and
equipment.
G. Pipe cleaning, flushing, hydrostatic tests, and chemical treatment requirements are
specified in Division 23 piping Sections. The Contractor shall prepare pipe system
cleaning, flushing, and hydrostatic testing plan. Plan shall include the following:
1. Sequence of testing and testing procedures for each section of pipe to be tested,
identified by pipe zone or sector identification marker. Markers shall be keyed
Drawings for each pipe sector showing the physical location of each designated
pipe test section. Drawings keyed to pipe zones or sectors shall be formatted to
allow each section of piping to be physically located and identified when referred
to in pipe system cleaning, flushing, hydrostatic testing, and chemical treatment
plan.
2. Description of equipment for flushing operations.
3. Minimum flushing water velocity.
4. Tracking checklist for managing and ensuring that all pipe sections have been
cleaned, flushed, hydrostatically tested, and chemically treated.
I. HVAC Distribution System Testing: Contractor shall prepare a testing plan to verify
performance of air, steam, and hydronic distribution systems; special exhaust; and other
distribution systems. Include HVAC terminal equipment and unitary equipment. Plan
shall include the following:
1. Sequence of testing and testing procedures for each item of equipment and
section of pipe to be tested, identified by identification marker. Markers shall be
keyed to Drawings showing the physical location of each item of equipment and
pipe test section. Drawings shall be formatted to allow each item of equipment
and section of piping to be physically located and identified when referred to in
the system testing plan.
2. Tracking checklist for managing and ensuring that all pipe sections have been
tested.
J. Vibration and Sound Tests: Contractor shall prepare testing plans to verify performance
of vibration isolation and seismic controls.
K. Deferred Testing:
1. If tests cannot be completed because of a deficiency outside the scope of the
HVAC system, the deficiency shall be documented and reported to Architect /
L. Testing Reports:
1. Reports shall include measured data, data sheets, and a comprehensive
summary describing the operation of systems at the time of testing.
2. Include data sheets for each controller to verify proper operation of the control
system, the system it serves, the service it provides, and its location. For each
controller, provide space for recording its readout, the reading at the controller's
sensor(s), plus comments. Provide space for testing personnel to sign off on
each data sheet.
3. Prepare a preliminary test report. Deficiencies will be evaluated by Architect /
Engineer to determine corrective action. Deficiencies shall be corrected and test
repeated.
END OF SECTION
REFRIGERANT PIPING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
1.03 SUBMITTALS
A. General: Submit each item in this article according to the conditions of the contract.
B. Product Data: For each type of valve and refrigerant piping specialty indicated. Include
pressure drop, based on manufacturer's test data, for the following:
1. Thermostatic expansion valves.
2. Solenoid valves.
3. Hot-gas bypass valves.
4. Filter dryers.
5. Strainers.
6. Pressure-regulating valves.
C. Shop Drawings: Show layout of refrigerant piping and specialties, including pipe, tube,
and fitting sizes, flow capacities, valve arrangements and locations, slopes of horizontal
D. Welding certificates.
F. Operation and Maintenance Data: For refrigerant valves and piping specialties to
include in maintenance manuals.
A. Welding: Qualify procedures and personnel according to ASME Boiler and Pressure
Vessel Code: Section IX, "Welding and Brazing Qualifications."
C. Comply with ASME B31.5, "Refrigeration Piping and Heat Transfer Components."
E. Listing and Labeling : Provide products specified in this section that are UL Listed and
Labeled.
A. Store piping in a clean and protected area with end caps in place to ensure that piping
interior and exterior are clean when installed.
1.06 COORDINATION
A. Coordinate size and location of roof curbs, equipment supports, and roof penetrations.
These items are specified in Division 07 Section "Roof Accessories."
1.07 Definitions
2.01 MANUFACTURERS:
A. Copper Tube: ASTM B 88, Type K or L (ASTM B 88M, Type A or B) ASTM B 280,
Type ACR.
D. Solder Filler Metals: ASTM B 32. Use 95-5 tin antimony or alloy HB solder to join
copper socket fittings on copper pipe.
F. Flexible Connectors:
1. Body: Tin-bronze bellows with woven, flexible, tinned-bronze-wire-reinforced
protective jacket.
2. End Connections: Socket ends.
3. Offset Performance: Capable of minimum 3/4-inch (20-mm) misalignment in
minimum 7-inch- (180-mm-) long assembly.
4. Pressure Rating: Factory test at minimum 500 psig (3450 kPa).
5. Maximum Operating Temperature: 250 deg F (121 deg C).
B. Packed-Angle Valves:
1. Body and Bonnet: Forged brass or cast bronze.
2. Packing: Molded stem, back seating, and replaceable under pressure.
3. Operator: Rising stem.
4. Seat: Nonrotating, self-aligning polytetrafluoroethylene.
5. Seal Cap: Forged-brass or valox hex cap.
6. End Connections: Socket, union, threaded, or flanged.
C. Check Valves:
1. Body: Ductile iron, forged brass, or cast bronze; globe pattern.
2. Bonnet: Bolted ductile iron, forged brass, or cast bronze; or brass hex plug.
3. Piston: Removable polytetrafluoroethylene seat.
4. Closing Spring: Stainless steel.
5. Manual Opening Stem: Seal cap, plated-steel stem, and graphite seal.
6. End Connections: Socket, union, threaded, or flanged.
7. Maximum Opening Pressure: 0.50 psig (3.4 kPa).
8. Working Pressure Rating: 500 psig (3450 kPa).
9. Maximum Operating Temperature: 275 deg F (135 deg C).
D. Service Valves:
1. Body: Forged brass with brass cap including key end to remove core.
2. Core: Removable ball-type check valve with stainless-steel spring.
3. Seat: Polytetrafluoroethylene.
4. End Connections: Copper spring.
5. Working Pressure Rating: 500 psig (3450 kPa).
E. Solenoid Valves: Comply with ARI 760 and UL 429; listed and labeled by an NRTL.
1. Body and Bonnet: Plated steel.
2. Solenoid Tube, Plunger, Closing Spring, and Seat Orifice: Stainless steel.
3. Seat: Polytetrafluoroethylene.
4. End Connections: Threaded.
5. Electrical: Molded, watertight coil in NEMA 250 enclosure of type required by
location with 1/2-inch (16-GRC) conduit adapter, and 24/115/208 -V ac coil.
6. Working Pressure Rating: 400 psig (2760 kPa).
7. Maximum Operating Temperature: 240 deg F (116 deg C).
8. Manual operator.
F. Safety Relief Valves: Comply with ASME Boiler and Pressure Vessel Code; listed and
labeled by an NRTL.
1. Body and Bonnet: Ductile iron and steel, with neoprene O-ring seal.
2. Piston, Closing Spring, and Seat Insert: Stainless steel.
3. Seat Disc: Polytetrafluoroethylene.
4. End Connections: Threaded.
5. Working Pressure Rating: 400 psig (2760 kPa).
6. Maximum Operating Temperature: 240 deg F (116 deg C).
A. Straight-Type Strainers:
1. Body: Welded steel with corrosion-resistant coating.
2. Screen: 100-mesh stainless steel.
3. End Connections: Socket or flare.
4. Working Pressure Rating: 500 psig (3450 kPa).
5. Maximum Operating Temperature: 275 deg F (135 deg C).
B. Angle-Type Strainers:
1. Body: Forged brass or cast bronze.
2. Drain Plug: Brass hex plug.
3. Screen: 100-mesh monel.
4. End Connections: Socket or flare.
5. Working Pressure Rating: 500 psig (3450 kPa).
6. Maximum Operating Temperature: 275 deg F (135 deg C).
C. Moisture/Liquid Indicators:
1. Body: Forged brass.
2. Window: Replaceable, clear, fused glass window with indicating element
protected by filter screen.
3. Indicator: Color coded to show moisture content in ppm.
4. Minimum Moisture Indicator Sensitivity: Indicate moisture above 60 ppm.
5. End Connections: Socket or flare.
6. Working Pressure Rating: 500 psig (3450 kPa).
7. Maximum Operating Temperature: 240 deg F (116 deg C).
F. Mufflers:
1. Body: Welded steel with corrosion-resistant coating.
2. End Connections: Socket or flare.
3. Working Pressure Rating: 500 psig (3450 kPa).
4. Maximum Operating Temperature: 275 deg F (135 deg C).
J. Insulation: Insulate refrigerant suction pipe with 25 mm pre-formed glass fibre sectional
insulation; `ksi' value of 0.0315 / 0035 at 25 / 50 C (`K' value of 0.22 / 0.24 at 77 °F /
2.05 REFRIGERANTS
C. ASHRAE 34,R-407C:Difluoromethane/Pentafluoroethane/1,1,1,2-Tetrafluoroethane.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine roughing-in for compliance with requirements for installation tolerances and
other conditions affecting performance of refrigerant piping. Do not proceed with
installation until unsatisfactory conditions have been corrected.
D. Install piping in short and direct arrangement with minimum number of joints, elbows
and fittings.
E. Arrange piping to allow normal inspection and service of compressor and other
equipment. Install valves and specialties in accessible locations to allow for service and
inspection.
F. Install piping with adequate clearance between pipe and adjacent wall and hangers, or
between pipes for insulation installation. Use sleeves through floors, walls, or ceilings,
sized to permit installation of full-thickness insulation.
H. Install branch lines to parallel compressors of equal length, and pipe and identically and
symmetrically.
L. Install exposed piping at right angles or parallel to building walls. Diagonal runs are not
permitted, unless expressly indicated.
M. Reduce pipe size using eccentric reducer fittings installed with level side down.
O. Install flexible connectors at the inlet and discharge connection, at right angles to axial
movement of compressor, parallel to crankshaft.
R. When brazing, remove solenoid-valve coils; remove sight glasses; and remove stems,
seats, and packing of valves, and accessible internal parts of refrigerant specialties. Do
not apply heat near bulb of expansion valve.
V. Charge and purge systems, after testing, and dispose of refrigerant following ASHRAE
15 procedures.
B. Install service valves for gage taps at inlet and outlet of hot-gas bypass valves and
strainers if they are not an integral part of valves and strainers.
C. Install a check valve at the compressor discharge and a liquid accumulator at the
compressor suction connection.
F. Install solenoid valves upstream from each expansion valve and hot-gas bypass valve.
Install solenoid valves in horizontal lines with coil at top.
H. Install safety relief valves where required by ASME Boiler and Pressure Vessel Code.
Pipe safety-relief-valve discharge line to outside according to ASHRAE 15.
I. Install moisture/liquid indicators in liquid line at the inlet of the thermostatic expansion
valve or at the inlet of the evaporator coil capillary tube.
J. Install strainers upstream from and adjacent to the following unless they are furnished
as an integral assembly for device being protected:
1. Solenoid valves.
2. Thermostatic expansion valves.
3. Hot-gas bypass valves.
4. Compressor.
K. Install filter dryers in liquid line between compressor and thermostatic expansion
valve, and in the suction line at the compressor.
B. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
assembly.
C. Fill pipe and fittings with an inert gas (nitrogen or carbon dioxide), during brazing or
welding, to prevent scale formation.
KEO/21-7387-0004 23 2300 / 9 Refrigerant Piping
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
D. Soldered Joints: Construct joints according to ASTM B 828 or CDA's "Copper Tube
Handbook."
E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," Chapter "Pipe
and Tube."
1. Use Type BcuP, copper-phosphorus alloy for joining copper socket fittings with
copper pipe.
2. Use Type BAg, cadmium-free silver alloy for joining copper with bronze or steel.
G. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service
application. Install gasket concentrically positioned. Use suitable lubricants on bolt
threads.
A. Hanger, support, and anchor products are specified in Division 23 Section "Hangers and
Supports for HVAC Piping and Equipment."
C. Install hangers for copper tubing with the following maximum spacing and minimum rod
sizes:
1. NPS 1/2 (DN 15): Maximum span, 60 inches (1500 mm); minimum rod size, 1/4
inch (6.4 mm).
2. NPS 5/8 (DN 18): Maximum span, 60 inches (1500 mm); minimum rod size, 1/4
inch (6.4 mm).
3. NPS 1 (DN 25): Maximum span, 72 inches (1800 mm); minimum rod size, 1/4
inch (6.4 mm).
4. NPS 1-1/4 (DN 32): Maximum span, 96 inches (2400 mm); minimum rod size,
3/8 inch (9.5 mm).
5. NPS 1-1/2 (DN 40): Maximum span, 96 inches (2400 mm); minimum rod size,
3/8 inch (9.5 mm).
6. NPS 2 (DN 50): Maximum span, 96 inches (2400 mm); minimum rod size, 3/8
inch (9.5 mm).
7. NPS 2-1/2 (DN 65): Maximum span, 108 inches (2700 mm); minimum rod size,
3/8 inch (9.5 mm).
8. NPS 3 (DN 80): Maximum span, 10 feet (3 m); minimum rod size, 3/8 inch (9.5
mm).
9. NPS 4 (DN 100): Maximum span, 12 feet (3.7 m); minimum rod size, 1/2 inch
(13 mm).
3.08 ADJUSTING
B. Adjust high- and low-pressure switch settings to avoid short cycling in response to
fluctuating suction pressure.
D. Perform the following adjustments before operating the refrigeration system, according
to manufacturer's written instructions:
1. Open shutoff valves in condenser water circuit.
2. Verify that compressor oil level is correct.
3. Open compressor suction and discharge valves.
4. Open refrigerant valves except bypass valves that are used for other purposes.
5. Check open compressor-motor alignment and verify lubrication for motors and
bearings.
E. Replace core of replaceable filter dryer after system has been adjusted and after design
flow rates and pressures are established.
3.09 CLEANING
A. Before installation of copper tubing other than Type ACR, clean tubing and fittings with
trichlorethylene.
3.010 COMMISSIONING
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes metal ducts for supply, return, outside, and exhaust air-
distribution systems in pressure classes from minus 500 to plus 2500Pa. Metal ducts
include the following:
1. Rectangular ducts and fittings.
2. Single-wall, round, and flat-oval spiral-seam ducts and formed fittings.
3. Double-wall, round, and flat-oval spiral-seam ducts and formed fittings.
4. Duct liner.
5. Fire Rated Ductwork.
6. Pre-insulated Ducts
1.02 REFERENCES
H. SMACNA - HVAC Duct Construction Standards, Metal and Flexible, Latest Edition.
I. SMACNA - HVAC Air Duct Leakage Test Manual, First Edition, 1985.
J. ASTM A 167 - Stainless and Heat Resisting Chromium-Nickel Steel Plate, Sheet and
Strip.
1.03 SUBMITTALS
A. Shop Drawings: CAD / Revit based on the project requirements-generated and drawn
to scale not greater than 1:100. Show fabrication and installation details for metal
ducts.
1. Fabrication, assembly, and installation, including plans, elevations, sections,
components, and attachments to other work.
2. Duct layout indicating sizes and pressure classes.
3. Elevations of top and bottom of ducts.
4. Dimensions of main duct runs from building grid lines.
5. Fittings.
6. Reinforcement and spacing.
7. Seam and joint construction.
8. Penetrations through fire-rated and other partitions.
9. Equipment installation based on equipment being used on Project.
10. Duct accessories, including access doors and panels.
11. Hangers and supports, including methods for duct and building attachment,
vibration isolation, and seismic restraints.
B. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following
items are shown and coordinated with each other, based on input from installers of the
items involved:
1. Ceiling suspension assembly members.
2. Other systems installed in same space as ducts.
3. Ceiling- and wall-mounting access doors and panels required to provide access
to dampers and other operating devices.
4. Ceiling-mounting items, including lighting fixtures, diffusers, grilles, speakers,
sprinklers, access panels, and special moldings.
C. Welding certificates.
D. Field quality-control test reports: Indicate and interpret test results for compliance with
performance requirements.
E. Record Drawings: Indicate actual routing, fitting details, reinforcements, supports, and
installed accessories and devices.
B. NFPA Compliance:
1. NFPA 90A, "Installation of Air Conditioning and Ventilating Systems”, unless
otherwise indicated.
2. NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems”,
unless otherwise indicated.
C. Comply with NFPA 96, "Ventilation Control and Fire Protection of Commercial Cooking
Operations," Ch. 3, "Duct System," for range hood ducts, unless otherwise indicated.
F. Unless accepted otherwise by the Engineer, use manufactures and installers that
employ a Quality Management System complying with the program described in ISO
9001-2000, or similar system.
1. DW144 : Specification for Sheet metal ductwork.
2. DW171 : Standard for Kitchen Sheet Metal Ductwork.
3. SMACNA : Sheet Metal and Air conditioning Contractor’s National
Association.
- HVAC Duct Construction Standards Metal and Flexible.
- HVAC Systems Testing, Adjusting & Balancing Standards
1.05 WARRANTY
E. Prevent end damage and prevent dirt and moisture from entering ducts and fittings.
F. Where possible store ductwork inside and protect from weather. Where necessary to
store outdoors, store above grade and enclose with waterproof wrapping.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for
acceptable materials, material thickness, and duct construction methods, unless
otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller
marks, stains, discolorations, and other imperfections.
C. Stainless Steel:
1. ASTM A 480/A 480M, Type 316, and having a No. 2D finish for concealed
ducts, and for exposed ducts No. 4 finish for surfaces of ducts exposed to view.
2. ASTM A167 stainless steel sheets; Type 304, sheet metal gauge and
construction shall conform to recommendations in SMACNA duct construction
standards, metal and flexible, latest edition.
D. Flexible Ducts
1. UL 181, Class 1, aluminum-polyester composite film with latex adhesive,
supported by helical wound spring steel wire; fiberglass insulation; aluminized
Supply, return and extract air ducts for all ductwork shall be insulated with physically cross-
linked partially open-cell polyolefin foam with factory applied reinforced aluminium foil
and adhesive backing. Insulation shall have the following specifications:
A. Density: 25 kg/m3 (foam core only).
B. Thermal Conductivity (ASTM C518): Maximum 0.035 W/m.°K at mean temperature
23oC.
C. Water absorption: <0.3 % v/v.
D. Service Temperature Range: - 80°C ~ +80°C (adhesive backing).
E. No mould growth when tested to ASTM C1338.
F. Minimum Noise Reduction Coefficient 0.50 and above (ISO 354).
G. Length of the acoustic liner should depend on the NC value required for each room.
If an NC35 shall be achieved for each room, the manufacturer or acoustic
consultant should provide complete calculations showing how many meters of liner
is required to achieve an NC 35.
H. Fire Rating:
i. Class 0 to BS476 Parts 6 and 7.
ii. Complies with NFPA 90A and B (ASTM E84 25/50 rating).
iii. UL181.11
A. Joint and Seam Sealants, General: The term "sealant" is not limited to materials of
adhesive or mastic nature but includes tapes and combinations of open-weave fabric
strips and mastics.
C. Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws;
compatible with duct materials.
D. Trapeze and Riser Supports: Steel shapes complying with ASTM A 36/A 36M.
1. Supports for Galvanized-Steel Ducts: Galvanized-steel shapes and plates.
2. Supports for Stainless-Steel Ducts: Stainless-steel support materials.
3. Supports for Aluminum Ducts: Aluminum support materials unless materials
are electrolytically separated from ducts.
A. Adhere a single layer of indicated thickness of duct liner with at least 90 percent
adhesive coverage at liner contact surface area. Attaining indicated thickness with
multiple layers of duct liner is prohibited.
B. Apply adhesive to transverse edges of liner facing upstream that do not receive metal
nosing.
C. Butt transverse joints without gaps and coat joint with adhesive.
D. Fold and compress liner in corners of rectangular ducts or cut and fit to ensure butted-
edge overlapping.
E. Do not apply liner in rectangular ducts with longitudinal joints, except at corners of
ducts, unless duct size and standard liner product dimensions make longitudinal joints
necessary.
F. Apply adhesive coating on longitudinal seams in ducts with air velocity of 12.7 m/s.
G. Secure liner with mechanical fasteners 100mm from corners and at intervals not
exceeding 300mm transversely; at 75mm from transverse joints and at intervals not
exceeding 450mm longitudinally.
H. Secure transversely oriented liner edges facing the airstream with metal nosings that
have either channel or "Z" profiles or are integrally formed from duct wall. Fabricate
edge facings at the following locations:
1. Fan discharges.
2. Intervals of lined duct preceding unlined duct.
3. Upstream edges of transverse joints in ducts where air velocities are greater
than 2500 fpm (12.7 m/s) or where indicated.
B. Diameter as applied to flat-oval ducts in this Article is the diameter of a round duct with
a circumference equal to the perimeter of a given size of flat-oval duct.
D. Duct Joints:
1. Ducts up to 500mm in Diameter: Interior, center-beaded slip coupling, sealed
before and after fastening, attached with sheet metal screws.
2. Ducts 535 to 1830mm in Diameter: Three-piece, gasketed, flanged joint
consisting of two internal flanges with sealant and one external closure band
with gasket.
3. Ducts Larger than 1830mm in Diameter: Companion angle flanged joints per
SMACNA "HVAC Duct Construction Standards--Metal and Flexible," Figure 3-
2.
4. Round Ducts: Prefabricated connection system consisting of double-lipped,
EPDM rubber gasket. Manufacture ducts according to connection system
manufacturer's tolerances.
E. 90-Degree Tees and Laterals and Conical Tees: Fabricate to comply with SMACNA's
"HVAC Duct Construction Standards--Metal and Flexible," with metal thickness
specified for longitudinal-seam straight ducts.
F. Diverging-Flow Fittings: Fabricate with reduced entrance to branch taps and with no
excess material projecting from fitting onto branch tap entrance.
A. Fire rated ductwork Shall be applicable for Smoke extract system, Car park ventilation
system, kitchen extract system, corridor pressurization system and all emergency
ventilation system.
B. Fire rated ductwork shall be NON-coated galvanized steel with CGF-1 integral flanges
to ensure low leakage.
C. Fire rated ductwork shall provide at least 2 Hrs. fire rating as per BS 476 Part 24 and
BS 5588 Part 9 standard.
F. Non-coated fire rated duct system shall be Civil Defense approved and third-party
approval certificate is suitable for applications where fire rated ductwork is required as
per BS476: Part 24 and ISO6944.
G. Non-coated fire rated ductwork is acceptable equal for use in applications of fire rated
ductwork where specifications may refer to any coated duct systems without any
prejudice so as long as performance criteria such as fire resistance required rating is
met.
J. The ductwork should be capable of providing Type A (fire outside) or Duct B (fire
inside) fire containment and, under normal non-fire operating conditions, should
conform to the pressure classification of the current HVCA DW/144 Specification for
Sheet Metal Ductwork.
L. In addition to above the fire rated ducts should meet requirements as mentioned
below.
1. Fire rated Ductwork for Smoke Control Systems (both exhaust and make-up air
ducts) shall be of at least 2-hour fire resistance rated.
2. Where a duct passes through other fire compartments of higher rating, the duct
shall be constructed to have the same rating of that compartment. The rating
shall apply to fire exposure from both interior and exterior of the duct or
structure.
3. Such fire rating of smoke control system ducts shall be evaluated and approved
for fire rating as well as for Stability, Integrity and Insulation Criteria for fire
rating.
4. The complete duct system including supports, hangers, joints, gaskets, sealant
etc. shall be in compliance with the approved test standards and fire rating
criteria.
5. Ducts for Smoke control systems (Type A, Rated for both fire outside and Type
B, fire outside and inside, 1 hour and 2 hour fire rated, tested and approved for
fire rating, stability, integrity and non-combustible insulation as per BS 476, Part
24 or EN-1366 with E60 classification as per EN 13501.
B. Certification of the Manufacturer of the UL 181 Duct Panel & Panels should indicate
the Date of Manufacture, Batch Number, UL Certification and Country of Origin. All
tradenames should be owned by Manufacturer
D. Insulation should be manufactured with a blowing agent that has zero Ozone
Depletion Potential (ODP) and Low Global Warming Potential (GWP<5) and shall be
CFC / HCFC Free.
E. Thermal Resistance for 20mm Phenolic Duct Panel = 0.61 (m2K/W) for conditioned
areas and 30mm for unconditioned areas = 0.91 (m2K/W)
G. For external applications the duct panel should be 30mm with an additional pre-clad
760micron facer for added protection.
H. Both Aluminum facers must be autohesively bonded to the insulation core during
manufacture and no secondary adhesive process will be accepted due to risk of
delamination over time.
K. VCD’s are made from a high performance rigid, thermoset phenolic insulation core,
faced on both sides with an aluminum foil. The insulation panels are fixed together
with a aluminum profile to form ductwork sections. The blades are made of aluminum
aero foil, which provides airflow.
M. 10 year warranty of the panel and ductwork only from the Manufacturer and
Fabricator warranties will not be permitted.
O. Phenolic Duct Panel Manufacturers need to visit the installation site on a regular
basis to inspect duct installation workmanship and issue a sign-off.
PART 3 - EXECUTION
A. Construct and install each duct system for the specific duct pressure classification,
duct seal class and duct leakage class indicated in the Duct System Schedule article
of this section.
A. Drawings indicate general arrangement of ducts, fittings, and accessories. Not all
required fittings or offsets are shown, the Contractor shall coordinate the installation
with other trades and provide all necessary offsets and fittings.
C. Install round and flat-oval ducts in lengths not less than 3.7m unless interrupted by
fittings.
E. Install fabricated fittings for changes in directions, size, and shape and for connections.
F. Install couplings tight to duct wall surface with a minimum of projections into duct.
Secure couplings with sheet metal screws. Install screws at intervals of 300mm, with
a minimum of 3 screws in each coupling.
G. Install ducts, unless otherwise indicated, vertically and horizontally and parallel and
perpendicular to building lines; avoid diagonal runs.
H. Install ducts close to walls, overhead construction, columns, and other structural and
permanent enclosure elements of building. Ductwork located in high bay spaces,
where the floor-to-floor clearance is in excess of 5.5 meters, shall be installed no
higher than 600 mm above finished ceiling.
J. Conceal ducts from view in finished spaces. Do not encase horizontal runs in solid
partitions unless specifically indicated.
K. Coordinate layout with suspended ceiling, fire- and smoke-control dampers, lighting
layouts, and similar finished work.
L. Seal all joints and seams. Apply sealant to male end connectors before insertion, and
afterward to cover entire joint and sheet metal screws.
M. Electrical Equipment Spaces: Route ducts to avoid passing through transformer vaults
and electrical equipment spaces and enclosures.
O. Fire-Rated Partition Penetrations: Where ducts pass through interior partitions and
exterior walls, install appropriately rated fire dampers, sleeves, and firestopping
sealant. Fire and smoke dampers are specified in Section 23 "Duct Accessories."
Firestopping materials and installation methods are specified in Section 23 "Through-
Penetration Firestop Systems."
P. Install ducts with hangers and braces designed to withstand, without damage to
equipment, seismic force required by applicable building codes. Refer to SMACNA's
"Seismic Restraint Manual: Guidelines for Mechanical Systems."
Q. Protect duct interiors from the elements and foreign materials until building is
enclosed. Follow SMACNA's "Duct Cleanliness for New Construction."
R. Paint visible interiors of metal ducts, that do not have duct liner, for 600mm upstream
of registers and grilles. Apply one coat of flat, black, latex finish coat over a compatible
galvanized-steel primer. Paint materials and application requirements are specified in
Division 9 painting Sections.
S. Supply air ductwork exposed to view in occupied spaces, and where indicated, shall
be of double wall construction.
T. Supply and return air ductwork, outside the building shall be single wall, insulated, and
finished with a weatherproof aluminum jacket. Refer to Section 23 “Mechanical
Insulation” for additional requirements.
A. Duct liner application is allowed immediately upstream and downstream of air handling
equipment and up to 3m downstream of air terminal units, unless accepted by
Engineer.
A. Install rigid round, rectangular, and flat-oval metal duct with support systems indicated
in SMACNA's "HVAC Duct Construction Standards--Metal and Flexible."
B. Support horizontal ducts within 600mm of each elbow and within 1200mm of each
branch intersection.
D. Install upper attachments to structures with an allowable load not exceeding one-fourth
of failure (proof-test) load.
3.06 CONNECTIONS
B. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for
branch, outlet and inlet, and terminal unit connections, unless specifically indicated
otherwise.
A. Perform the following field tests and inspections according to SMACNA's "HVAC Air
Duct Leakage Test Manual" and prepare test reports:
1. Disassemble, reassemble, and seal segments of systems to accommodate
leakage testing and for compliance with test requirements.
2. Test installed ductwork having a SMACNA Duct Construction Class of 1000 Pa
(4 inches water column) or above. The ductwork to be tested shall be randomly
selected by the EMPLOYER.
3. Follow the procedures outlined in SMACNA HVAC Air Duct Leakage Test
Manual, latest edition.
4. Testing apparatus and procedures shall be reviewed and accepted by the
Employer before the start of tests. Tests shall be carried out in the presence of
the Employer who shall verify the test results. Contact the Employer to
coordinate the time of testing.
5. The leakage amount shall not exceed the SMACNA leakage class indicated in
the Duct System Schedule.
A. Mark position of dampers and air-directional mechanical devices before cleaning and
perform cleaning before air balancing.
C. Vent vacuuming system to the outside. Include filtration to contain debris removed
from HVAC systems, and locate exhaust down wind and away from air intakes and
other points of entry into building.
D. Clean the following metal duct systems by removing surface contaminants and
deposits:
1. Air outlets and inlets (registers, grilles, and diffusers).
2. Supply, return, and exhaust fans including fan housings, plenums (except
ceiling supply and return plenums), scrolls, blades or vanes, shafts, baffles,
dampers, and drive assemblies.
3. Air-handling unit internal surfaces and components including mixing box, coil
section, air wash systems, spray eliminators, condensate drain pans,
humidifiers and dehumidifiers, filters and filter sections, and condensate
collectors and drains.
4. Coils and related components.
5. Return-air ducts, dampers, and actuators except in ceiling plenums and
mechanical equipment rooms.
6. Supply-air ducts, dampers, actuators, and turning vanes.
F. Cleanliness Verification:
1. Visually inspect metal ducts for contaminants.
2. Where contaminants are discovered, re-clean and reinspect ducts.
3.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
1.02 SUBMITTALS
A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and
NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."
B. Following spare parts shall be furnished, properly packed and labelled with equipment
no. / location.
1. Two (2) nos. of fusible links of Fire dampers of each type and size used in the
project.
2. Four (4) sets of Motor with damper blades and actuators for each type and size
of Smoke control dampers used in the Project.
3. Four (4) sets of Motors with damper blades and actuators for each type and size
of Motorized volume control dampers used in the project.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for
acceptable materials, material thicknesses, and duct construction methods, unless
otherwise indicated.
E. Aluminum Sheets: ASTM B 209 (ASTM B 209M), alloy 3003, temper H14; with mill
finish for concealed ducts and standard, 1-side bright finish for exposed ducts.
F. Extruded Aluminum: ASTM B 221 (ASTM B 221M), alloy 6063, temper T6.
H. Tie Rods: Galvanized steel, 1/4-inch (6-mm) minimum diameter for lengths 36 inches
(900 mm) or less; 3/8-inch (10-mm) minimum diameter for lengths longer than 36 inches
(900 mm).
E. Damper Hardware: Zinc-plated, die-cast core with dial and handle made of 3/32-inch-
(2.4-mm-) thick zinc-plated steel, and a 3/4-inch (19-mm) hexagon locking nut. Include
center hole to suit damper operating-rod size. Include elevated platform for insulated
duct mounting.
C. Frame: Curtain type with blades inside airstream, Curtain type with blades outside
airstream and Multiple-blade type; fabricated with roll-formed, 0.034-inch- (0.85-mm-)
thick galvanized steel; with mitered and interlocking corners.
H. Fusible Links: Replaceable, 165 deg F (74 deg C) 212 deg F (100 deg C) rated.
D. Round Units:
1. Outer Casings:
a. ASTM A 653/A 653M, G90 (Z275) galvanized sheet steel.
b. Up to 24 Inches (600 mm) in Diameter: 0.034 inch (0.85 mm) thick.
c. 26 through 40 Inches (660 through 1000 mm) in Diameter: 0.040 inch
(1.0 mm) thick.
d. 42 through 52 Inches (1060 through 1300 mm) in Diameter: 0.052 inch
(1.3 mm) thick.
e. 54 through 60 Inches (1370 through 1500 mm) in Diameter: 0.064 inch
(1.62 mm) thick.
f. Casings fabricated of spiral lock-seam duct may be one size thinner than
that indicated.
2. Interior Casing, Partitions, and Baffles:
a. ASTM A 653/A 653M, G90 (Z275) galvanized sheet steel.
b. At least 0.034 inch (0.85 mm) thick and designed for minimum
aerodynamic losses.
E. Sheet Metal Perforations: 1/8-inch (3-mm) diameter for inner casing and baffle sheet
metal.
F. Fill Material: Inert and vermin-proof fibrous material, packed under not less than 5
percent compression.
1. Erosion Barrier: Polymer bag enclosing fill and heat-sealed before assembly.
A. General Description: Fabricate doors airtight and suitable for duct pressure class.
B. Door: Double wall, duct mounting, and rectangular; fabricated of galvanized sheet metal
with insulation fill and thickness as indicated for duct pressure class.. Include 1-by-1-
inch (25-by-25-mm) butt or piano hinge and cam latches.
1. Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets.
2. Provide number of hinges and locks as follows:
a. Less Than 12 Inches (300 mm) Square: Secure with two sash locks.
b. Up to 18 Inches (450 mm) Square: Two hinges and two sash locks.
c. Up to 24 by 48 Inches (600 by 1200 mm): Three hinges and two
compression latches with outside and inside handles.
d. Sizes 24 by 48 Inches (600 by 1200 mm) and Larger: One additional
hinge.
C. Door: Double wall, duct mounting, and round; fabricated of galvanized sheet metal with
insulation fill and 1-inch (25-mm) thickness. Include cam latches.
1. Frame: Galvanized sheet steel, with spin-in notched frame.
D. Pressure Relief Access Door: wall and duct mounting; fabricated of galvanized sheet
metal with insulation fill and thickness as indicated for duct pressure class. Include
latches, and retaining chain.
E. Seal around frame attachment to duct and door to frame with neoprene or foam rubber.
B. Metal-Edged Connectors: Factory fabricated with a fabric strip 5-3/4 inches (146 mm)
wide attached to two strips of 2-3/4-inch- (70-mm-) wide, 0.028-inch- (0.7-mm-) thick,
galvanized sheet steel or 0.032-inch- (0.8-mm-) thick aluminum sheets. Select metal
compatible with ducts.
C. Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene.
1. Minimum Weight: 26 oz./sq. yd. (880 g/sq. m).
2. Tensile Strength: 480 lbf/inch (84 N/mm) in the warp and 360 lbf/inch (63 N/mm)
in the filling.
3. Service Temperature: Minus 40 to plus 200 deg F (Minus 40 to plus 93 deg C).
D. Outdoor System, Flexible Connector Fabric: Glass fabric double coated with
weatherproof, synthetic rubber resistant to UV rays and ozone.
1. Minimum Weight: 24 oz./sq. yd. (810 g/sq. m).
2. Tensile Strength: 530 lbf/inch (93 N/mm) in the warp and 440 lbf/inch (77 N/mm)
in the filling.
3. Service Temperature: Minus 50 to plus 250 deg F (Minus 45 to plus 121 deg C).
I. Insulated-Duct Connectors: UL 181, Class 1, aluminum laminate and polyester film with
latex adhesive supported by helically wound, spring-steel wire; fibrous-glass insulation;
polyethylene or aluminized vapor barrier film.
K. Flexible Duct Clamps: Stainless-steel band with cadmium-plated hex screw to tighten
band with a worm-gear action, in sizes 3 through 18 inches (75 to 450 mm) to suit duct
size.
A. Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw
cap and gasket. Size to allow insertion of pitot tube and other testing instruments and of
length to suit duct insulation thickness.
B. Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to
gasoline and grease.
PART 3 - EXECUTION
C. Install backdraft dampers on exhaust fans or exhaust ducts nearest to outside and
where indicated.
D. Install volume dampers in ducts with liner; avoid damage to and erosion of duct liner.
E. Provide balancing dampers at points on supply, return, and exhaust systems where
branches lead from larger ducts as required for air balancing. Install at a minimum of
two duct widths from branch takeoff.
F. Provide test holes at fan inlets and outlets and elsewhere as indicated.
G. Install fire and smoke dampers, with fusible links, according to manufacturer's UL-
approved written instructions.
I. Install duct access doors to allow for inspecting, adjusting, and maintaining accessories
and terminal units as follows:
1. On both sides of duct coils.
2. Downstream from volume dampers, turning vanes, and equipment.
3. Adjacent to fire or smoke dampers, providing access to reset or reinstall fusible
links.
4. To interior of ducts for cleaning; before and after each change in direction, at
maximum 50-foot (15-m) spacing.
5. On sides of ducts where adequate clearance is available.
L. Install the following sizes for duct-mounting, pressure relief access doors:
1. One-Hand or Inspection Access: 7 inches (175 mm) in diameter.
2. Two-Hand Access: 10 inches (250 mm) in diameter.
3. Head and Hand Access: 13 inches (330 mm) in diameter.
4. Head and Shoulders Access: 19 inches (480 mm) in diameter.
M. Label access doors according to Division 23 Section "Identification for HVAC Piping and
Equipment."
O. For fans developing static pressures of 5-inch wg (1250 Pa) and higher, cover flexible
connectors with loaded vinyl sheet held in place with metal straps.
P. Connect terminal units to supply ducts directly or with maximum 12-inch (300-mm)
lengths of flexible duct. Do not use flexible ducts to change directions.
Q. Connect diffusers or light troffer boots to low pressure ducts directly or with maximum
60-inch (1500-mm) lengths of flexible duct clamped or strapped in place.
R. Connect flexible ducts to metal ducts with liquid adhesive plus tape or adhesive plus
sheet metal screws.
S. Install duct test holes where indicated and required for testing and balancing purposes.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 RELATED SECTION: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
A. Section 23 0548 – Vibration and Seismic Control. Of HVAC Piping and Equipment.
1.03 REFERENCES
D. AMCA 301 - Method of Calculating Fan Sound Rating from Laboratory Test
A. Project Altitude: Base fan performance ratings on actual Project site elevations above
sea level.
KEO/21-7387-0004 23 3413 / 1 Axial Hvac Fans
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
B. Operating Limits: Classify according to AMCA 99.
1.05 SUBMITTALS
A. Product Data: Include rated capacities, furnished specialties, and accessories for each
type of product indicated and include the following:
1. Certified fan performance curves with system operating conditions indicated.
2. Certified fan sound-power ratings.
3. Motor ratings and electrical characteristics, plus motor and electrical accessories.
4. Material thickness and finishes, including color charts.
5. Dampers, including housings, linkages, and operators.
6. Fan speed controllers.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, method of field assembly, components, and location and size of
each field connection.
1. Wiring Diagrams: Power, signal, and control wiring.
2. Design Calculations: Calculate requirements for selecting vibration isolators and
seismic restraints and for designing vibration isolation bases.
3. Vibration Isolation Base Details: Detail fabrication, including anchorages and
attachments to structure and to supported equipment. Include auxiliary motor
slides and rails, and base weights.
C. Coordination Drawings: Show fan room layout and relationships between components
and adjacent structural and mechanical elements. Show support locations, type of
support, and weight on each support. Indicate and certify field measurements.
E. Operation and Maintenance Data: For axial fans to include in emergency, operation,
and maintenance manuals.
B. AMCA Compliance: Products shall comply with performance requirements and shall be
licensed to use the AMCA-Certified Ratings Seal.
C. NEMA Compliance: Motors and electrical accessories shall comply with NEMA
standards.
B. Disassemble and reassemble units, as required for moving to final locations, according
to manufacturer's written instructions.
C. Lift and support units with manufacturer's designated lifting or supporting points.
1.08 COORDINATION
B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in section 23.
C. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in Section 23 "Roof Accessories."
B. Following spare parts shall be furnished, properly packed and labelled with equipment
no. / location.
1. Two (2) sets of matched fan belts for each type and size of belt-driven fan used.
2. Two (2) sets of Bearings for each type and size of fans used.
3. One electrical motor each for each type and size of Fans used.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 GENERAL
D. Fans for outdoor installation shall be weather protected and provided with anticorrosion
paint.
F. Static - pressures given in the equipment Schedules are only for guidance. The
Contractor should submit static pressure calculations for all fans for approval before
ordering the equipment’s. The Contractor should give the required fan and motor h.p.
without additional cost. The contractor may propose lower motor hp as per the
calculations and as approved.
G. Contractor shall select fans for low noise application and shall provide all necessary
measures such as provision of sound attenuators, Acoustic enclosures, acoustic lining
to limit sound to acceptable noise levels as indicated in Section 23 0100. Contractor
shall submit noise calculations for the selected fan and attenuators/and or acoustic
enclosures for the approval prior to ordering the equipment.
A. Description: Fan wheel and housing, straightening vane section, factory-mounted motor
with belt drive, and accessories.
D. Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size: 1.2
2. Fan Shaft: Turned, ground, and polished steel designed to operate at no more
than 70 percent of first critical speed at top of fan's speed range.
3. Fan Pulleys: Cast iron with split, tapered bushing; dynamically balanced at
factory.
4. Motor Pulleys: Adjustable pitch for use with motors through 5 hp; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
5. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
6. Motor Mount: Adjustable base.
7. Shaft Bearings: Radial, self-aligning ball or roller bearings.
E. Accessories:
1. Mounting Clips: Horizontal ceiling or Vertical mounting clips welded to fan
housing, of same material as housing.
2. Inlet and Outlet Screens: Wire-mesh screen on fans not connected to ductwork
of same material as housing.
G. Factory Finishes:
1. Sheet Metal Parts: Prime coat before final assembly.
2. Exterior Surfaces: Baked-enamel finish coat after assembly.
3. Coatings: Epoxy or Synthetic resin or Color-match enamel or Hot-dip galvanized
Powder-baked enamel.
B. Axial Fan:
1. Ratings: Provide fan performance based on tests conducted in accordance with
AMCA Bulletin 210. Fans shall bear the AMCA Seal. Select fans to be non-
overloading with CFM vs. pressure curve that will ensure quiet, stable operation
under all conditions.
2. Casings: The fan casing shall completely cover the motor and impeller assembly
in the case of Long Case fans or the impeller in the case of Short Case fans.
The casing shall be manufactured from mild steel to BS1449: Part 1: 1972 Grade
HR14 complete with flanges. The flanges shall be integral with the casing, pre-
drilled and radiused. Long Case fans shall be complete with a pre-wired
externally mounted terminal box and a sight port closed with a rubber moulding
for normal temperature applications. The fan casing shall be hot dipped
galvanised to BS729: 1971 at a rate of 0.46 kgs of zinc per square metre up to
and including 710 mm diameter and 0.61 kgs of zinc square metre above 750
mm diameter. Casings and flanges shall be of a 2.5 mm thickness up to and
including 560 mm diameter, 3 mm up to and including 1000 mm and 4, 5 or 6
mm for larger diameters. Fans shall be provided with attachable mounting feet
suitable for horizontal or vertical mounting and matching flanges. Mounting feet
A. Duct mounted Inline exhaust fan unit suitable for Kitchen exhaust, Class "F" motor, with
class F temperature rise. Motor shall be isolated from main air stream by a tunnel which
extends to the side of the main fan casing only.
B. Unit case is manufactured in aluminium alloy and is of square section, predrilled for
installation into compatible ducting, Non rusting fastenings are used throughout. A
removable panel shall be provided for quick and easy access for commissioning,
cleaning, inspection and maintenance purposes. The casing shall have an enlarged
bore located around the motor to permit adequate cross sectional area for air to flow
around the motor tunnel
D. Provide polyester or equivalent anti corrosion protection cover for impeller, housing, and
all components.
E. The motor shall be cooled by ambient air drawn into the tunnel which extends to the
side of the casing and is suitable for continuous operation at high ambient temperature
of 50 °C.
A. Sound-Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan
Sound Ratings from Laboratory Test Data." Factory test fans according to AMCA 300,
"Reverberant Room Method for Sound Testing of Fans." Label fans with the AMCA-
Certified Ratings Seal.
B. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of
rotation, and efficiency by factory tests and ratings according to AMCA 210, "Laboratory
Methods of Testing Fans for Rating."
PART 3 - EXECUTION
3.01 INSTALLATION
A. Do not operate fans for any purpose until ductwork is clean, filters are in place, bearings
lubricated, and fan has been test run under observation.
C. Install flexible connections specified in Section 23 3300 between fan inlet and discharge
ductwork. Ensure metal bands of connectors are parallel with minimum on inch (25mm)
flex between ductwork and fan while running. Flexible connections shall not be used for
fans used for smoke exhaust applications.
H. For all fans (normal/smoke vent fans) provide fan starter switch in the space served by
the fan and location of starter switch to be as indicated on shop drawing or as approved.
Make necessary interconnections with light switch
3.02 CONNECTIONS
D. Install line-sized piping from scroll drain connection, with trap with seal equal to 1.5
times specified static pressure, to nearest floor drain
A. Perform the following field tests and inspections and prepare test reports:
1. Verify that shipping, blocking, and bracing are removed.
2. Verify that unit is secure on mountings and supporting devices and that
connections to ducts and electrical components are complete. Verify that proper
thermal-overload protection is installed in motors, starters, and disconnect
switches.
3. Verify that cleaning and adjusting are complete.
4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify
fan wheel free rotation and smooth bearing operation. Reconnect fan drive
system, align and adjust belts, and install belt guards.
5. Adjust belt tension.
6. Adjust damper linkages for proper damper operation.
7. Verify lubrication for bearings and other moving parts.
8. Verify that manual and automatic volume control and fire and smoke dampers in
connected ductwork systems are in fully open position.
9. Disable automatic temperature-control operators, energize motor and confirm
proper motor rotation and unit operation, adjust fan to indicated rpm, and
measure and record motor voltage and amperage.
10. Shut unit down and reconnect automatic temperature-control operators.
11. Remove and replace malfunctioning units and retest as specified above.
B. Test and adjust controls and safeties. Replace damaged and malfunctioning controls
and equipment.
3.04 ADJUSTING
C. Lubricate bearings.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 RELATED SECTION: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
A. Section 23 0548 – Vibration and Seismic Control. Of HVAC Piping and Equipment.
1.03 REFERENCES
D. AMCA 301 - Method of Calculating Fan Sound Rating from Laboratory Test
1.05 SUBMITTALS
A. Product Data: Include rated capacities, furnished specialties, and accessories for each
type of product indicated and include the following:
1. Certified fan performance curves with system operating conditions indicated.
2. Certified fan sound-power ratings.
3. Motor ratings and electrical characteristics, plus motor and electrical accessories.
4. Material thickness and finishes, including color charts.
5. Dampers, including housings, linkages, and operators.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, method of field assembly, components, and location and size of
each field connection.
1. Wiring Diagrams: Power, signal, and control wiring.
2. Design Calculations: Calculate requirements for selecting vibration isolators and
seismic restraints and for designing vibration isolation bases.
3. Vibration Isolation Base Details: Detail fabrication, including anchorages and
attachments to structure and to supported equipment. Include auxiliary motor
slides and rails, and base weights.
C. Coordination Drawings: Show fan room layout and relationships between components
and adjacent structural and mechanical elements. Show support locations, type of
support, and weight on each support. Indicate and certify field measurements.
B. AMCA Compliance: Products shall comply with performance requirements and shall be
licensed to use the AMCA-Certified Ratings Seal.
C. NEMA Compliance: Motors and electrical accessories shall comply with NEMA 1.
B. Disassemble and reassemble units, as required for moving to the final location,
according to manufacturer's written instructions.
C. Lift and support units with manufacturer's designated lifting or supporting points.
1.08 COORDINATION
B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
B. Following spare parts shall be furnished, properly packed and labelled with equipment
no. / location.
1. Two (2) sets of matched fan belts for each type and size of belt-driven fan used.
2. Two (2) sets of Bearings for each type and size of fans used.
3. One electrical motor each for each type and size of Fans used.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. Housings: Formed panels to make curved-scroll housings with shaped cutoff, with
doors or panels to allow access to internal parts and components.
1. Panel Bracing: Steel angle- or channel-iron member supports for mounting and
supporting fan scroll, wheel, motor, and accessories.
2. Horizontally split, bolted-flange housing.
3. Spun inlet cone with flange.
4. Outlet flange.
D. Shafts: Statically and dynamically balanced and selected for continuous operation at
maximum rated fan speed and motor horsepower, with final alignment and belt
adjustment made after installation.
1. Turned, ground, and polished hot-rolled steel with keyway. Ship with protective
coating of lubricating oil.
2. Designed to operate at no more than 70 percent of first critical speed at top of
fan's speed range.
G. Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size: 1.5
2. Fan Pulleys: Cast iron or cast steel with split, tapered bushing; dynamically
balanced at factory.
3. Motor Pulleys: Adjustable pitch for use with motors through 5 hp ; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
4. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
5. Belt Guards: Fabricate to comply with OSHA and SMACNA requirements of
diamond-mesh wire screen welded to steel angle frame or equivalent, prime
coated. Secure to fan or fan supports without short circuiting vibration isolation.
Include provisions for adjustment of belt tension, lubrication, and use of
tachometer with guard in place.
6. Motor Mount: Adjustable for belt tensioning.
H. Accessories:
1. Scroll Access Doors: Shaped to conform to scroll, with quick-opening latches
and gaskets.
2. Cleanout Door: Quick-opening, latch-type gasketed door allowing access to fan
scroll, of same material as housing.
3. Scroll Drain Connection: NPS 1 (DN 25) steel pipe coupling welded to low point
of fan scroll.
4. Companion Flanges: Rolled flanges for duct connections of same material as
housing.
5. Variable Inlet Vanes: With blades supported at both ends with two permanently
lubricated bearings of same material as housing. Variable mechanism
terminating in single control lever with control shaft for double-width fans.
6. Discharge Dampers: Assembly with parallel or opposed blades constructed of
two plates formed around and to shaft, channel frame, and sealed ball bearings;
with blades linked outside of airstream to single control lever of same material as
housing.
7. Inlet Screens: Grid screen of same material as housing.
B. Housings: Formed panels to make curved-scroll housings with shaped cutoff; with
doors or panels to allow access to internal parts and components.
1. Panel Bracing: Steel angle- or channel-iron member supports for mounting and
supporting fan scroll, wheel, motor, and accessories.
2. Horizontally split, bolted-flange housing.
3. Spun inlet cone with flange.
4. Outlet flange.
D. Shafts: Statically and dynamically balanced and selected for continuous operation at
maximum rated fan speed and motor horsepower, with final alignment and belt
adjustment made after installation.
1. Turned, ground, and polished hot-rolled steel with keyway. Ship with a protective
coating of lubricating oil.
2. Designed to operate at no more than 70 percent of first critical speed at top of
fan's speed range.
G. Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size: 1.5.
H. Accessories:
1. Scroll Access Doors: Shaped to conform to scroll, with quick-opening latches
and gaskets.
2. Cleanout Door: Quick-opening, latch-type gasketed door allowing access to fan
scroll, of same material as housing.
3. Scroll Drain Connection: NPS 1 (DN 25) steel pipe coupling welded to low point
of fan scroll.
4. Companion Flanges: Rolled flanges for duct connections of same material as
housing.
5. Variable Inlet Vanes: With blades supported at both ends with two permanently
lubricated bearings of same material as housing. Variable mechanism
terminating in single control lever with control shaft for double-width fans.
6. Discharge Dampers: Assembly with parallel or opposed blades constructed of
two plates formed around and to shaft, channel frame, and sealed ball bearings;
with blades linked outside of airstream to single control lever of same material as
housing.
7. Inlet Screens: Grid screen of same material as housing.
8. Shaft Cooler: Metal disk between bearings and fan wheel, designed to dissipate
heat from shaft.
9. Spark-Resistant Construction: AMCA 99.
10. Shaft Seals: Airtight seals installed around shaft on drive side of single-width
fans.
11. Weather Cover: Enameled-steel sheet with ventilation slots, bolted to housing.
F. Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size: 1.5.
2. Fan Pulleys: Cast iron or cast steel with split, tapered bushing; dynamically
balanced at factory.
3. Motor Pulleys: Adjustable pitch for use with motors through 5 hp; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
4. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
5. Belt Guards: Fabricate to comply with OSHA and SMACNA requirements of
diamond-mesh wire screen welded to steel angle frame or equivalent, prime
coated. Secure to fan or fan supports without short circuiting vibration isolation.
Include provisions for adjustment of belt tension, lubrication, and use of
tachometer with guard in place.
6. Motor Mount: Adjustable for belt tensioning.
G. Accessories:
1. Scroll Access Doors: Shaped to conform to scroll, with quick-opening latches
and gaskets.
2. Cleanout Door: Bolted Quick-opening, latch-type gasketed door allowing access
to fan scroll, of same material as housing.
A. Sound-Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan
Sound Ratings from Laboratory Test Data." Factory test fans according to AMCA 300,
"Reverberant Room Method for Sound Testing of Fans." Label fans with the AMCA-
Certified Ratings Seal.
B. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of
rotation, and efficiency by factory tests and ratings according to AMCA 210, "Laboratory
Methods of Testing Fans for Rating."
2.06 GENERAL
D. Fans for outdoor installation shall be weather protected and provided with anticorrosion
paint.
F. Static - pressures given in the equipment Schedules are only for guidance. The
Contractor should submit static pressure calculations for all fans for approval before
ordering the equipment’s. The Contractor should give the required fan and motor hp.
Without additional cost. The contractor may propose lower motor hp as per the
calculations and as approved.
G. Contractor shall select fans for low noise application and shall provide all necessary
measures such as provision of sound attenuators, Acoustic enclosures, acoustic lining
to limit sound to acceptable noise levels as indicated in Section 23 0100 & Acoustic
report. Contractor shall submit noise calculations for the selected fan and
attenuators/and or acoustic enclosures for the approval prior to ordering the equipment.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Do not operate fans for any purpose until ductwork is clean, filters are in place, bearings
lubricated, and fan has been test run under observation.
C. Install flexible connections specified in Section 23 3343 between fan inlet and discharge
ductwork. Ensure metal bands of connectors are parallel with minimum on inch (25mm)
flex between ductwork and fan while running. Flexible connections shall not be used for
fans used for smoke exhaust applications.
H. For all fans (normal/smoke vent fans) provide fan starter switch in the space served by
the fan and location of starter switch to be as indicated on shop drawing or as approved.
Make necessary interconnections with light switch
J. Support floor-mounting units using restrained spring isolators having a static deflection
of 1 inch (25 mm). Vibration- and seismic-control devices are specified in Division 23
Section "Vibration and Seismic Controls for HVAC Piping and Equipment."
1. Secure vibration and seismic controls to concrete bases using anchor bolts cast
in concrete base.
M. Support suspended units from structure using threaded steel rods and spring hangers
spring hangers with vertical-limit stops having a static deflection of 1 inch (25 mm).
Vibration-control devices are specified in Division 23 Section "Vibration and Seismic
Controls for HVAC Piping and Equipment."
3.02 CONNECTIONS
C. Install line-sized piping from scroll drain connection, with trap with seal equal to 1.5
times specified static pressure, to nearest floor drain.
A. Perform the following field tests and inspections and prepare test reports:
1. Verify that shipping, blocking, and bracing are removed.
2. Verify that unit is secure on mountings and supporting devices and that
connections to ducts and electrical components are complete. Verify that proper
thermal-overload protection is installed in motors, starters, and disconnect
switches.
3. Verify that cleaning and adjusting are complete.
4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify
fan wheel free rotation and smooth bearing operation. Reconnect fan drive
system, align and adjust belts, and install belt guards.
5. Adjust belt tension.
6. Adjust damper linkages for proper damper operation.
7. Verify lubrication for bearings and other moving parts.
8. Verify that manual and automatic volume control and fire and smoke dampers in
connected ductwork systems are in fully open position.
B. Test and adjust controls and safeties. Replace damaged and malfunctioning controls
and equipment.
B. Tools and spare parts supplied under this clause shall be provided in original packing,
clearly labelled and referenced
C. Spare Parts furnished under this clause shall not be used during the maintenance
period without the written permission of the owner (Contractor shall procure spare parts,
tools etc., fulfill his obligations to operate and maintain the system in the contract period)
3.05 ADJUSTING
C. Lubricate bearings.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes: Supply and installation of air outlets and inlets Ceiling and wall-
mounted diffusers, registers, and grilles.
B. Related Sections:
1. Section 23 3113: Metal Duct
2. Section 23 3300: Air Duct Accessories
1.02 SUBMITTALS
A. Grilles, diffusers, registers, louvers etc. shall be constructed from extruded aluminum,
unless mentioned otherwise elsewhere.
B. Grilles, diffusers, registers, etc. are to be furnished with a factory finish to a color
specified by the interior designer.
C. Decorative grille for the fresh air makeup shall be coordinated and approved by interior
designer.
D. Regulatory Requirements
1. ADC Test Code: Test and rate air outlets and inlets in certified laboratory under
the requirements of Air Diffusion Council (ADC) Equipment Test Code 1062
“Certification, Rating and Test Manual”.
B. Store outlets and inlets in original cartons and protect from weather and construction
work traffic. Where possible, store indoors; when necessary to store outdoors, store
above grade and enclose with waterproof wrapping.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. Performance: Provide ceiling air diffusers that have, as minimum, temperature and
velocity traverses, throw and drop, static pressure drop and noise criteria ratings for
each size device as listed in manufacturer’s current data.
C. Ceiling Compatibility: Provide diffusers with border styles that are compatible with
adjacent ceiling systems and that are specifically manufactured to fit into ceiling module
with accurate fit and adequate support.
D. Types: Provide ceiling diffusers of type, capacity and with accessories as listed on
diffuser schedule.
A. Provide linear diffusers with internal damper vanes, adjustable from face of diffuser
without removing or disturbing installation. These variable vanes shall provide 180
degree discharge pattern, left, right or vertical adjustable in each slot.
C. Where continuous strips are required, provide strip diffusers with blank off covers for
dummy diffusers.
D. Where linear diffusers are used for return air, the appearance from the room shall be
identical to supply diffusers.
C. Wall/Floor Compatibility: Provide registers and grilles with border styles that are
compatible with adjacent wall/ floor systems, and that are specifically manufactured to fit
into wall/floor construction with accurate fit and adequate support.
D. Types: Provide registers, grilles and perforated floor panels of type, capacity, and with
accessories as listed on register and grille schedule or as shown on drawings.
E. Provide all supply grilles and registers with adjustable front and rear bars with front bars
parallel to the short dimension and rear bars parallel to the long dimension. Provide
registers with an opposed blade damper behind the bars, to be key operated from the
register face.
F. Provide all return grilles or registers with fixed face bars set at a 45-degree angle and
parallel to the long dimension. Provide registers with a key operated opposed blade
damper operable from the register face.
G. Provide perforated floor tiles specially designed for computer centre floor system.
Provide volume damper operated from the face of floor tile. Limit discharge velocity to
300 FPM.
A. Continues 1/8-inch face bars with 1/2 (half) inch centers and 0 or 15 deg. core deflection
to satisfy needed throw.
D. Provide Registers/Grilles with galvanised steel sheet plenum as required, internally lined
with ½ inch thick acoustic insulation. Circular spigots are provided and fitted with
volume control dampers.
A. Continues ¾ inch width slot/s with adjustable control vanes and volume control
dampers. It shall be fully adjustable from the face of the diffuser, to any horizontal,
vertical or any intermediate setting of air flow pattern to satisfy needed throw.
C. Provide concealed mounting brackets fit in a hemmed duct collar or frame to positively
hold the diffuser in ceiling or sidewall installations.
D. Provide diffusers with galvanized steel sheet plenum as required, internally lined with 1
(one) inch thick acoustic insulation. Circular spigots are provided and fitted with volume
control dampers.
A. Provide all materials and equipment required for a complete installation of all linear and
modular slot air distribution systems as shown on the mechanical drawings. The
systems shall be complete in every respect and shall include all required
appurtenances. Mechanical contractor shall furnish and install all plenums, hoods,
blank-offs and associated sheet metal components including all duct connections
thereto.
B. Provide all continuous linear slot and modular slot diffusers as shown on the drawings.
The slot diffusers shall integrate into the ceiling system. Where curved linear slot
diffusers are indicated, they shall be stretched formed to the exact radii required. Rolled
or segmented linear slot diffusers will not be accepted.
C. The linear slot diffusers shall have a single slot unless shown otherwise and shall be
capable of being used for supply air, return air, exhaust air or any combination.
D. The linear slot diffusers shall be capable of supporting the ceiling system. Linear
diffusers supported by screws in the flanges or from air plenums are unacceptable. For
lay-in ceiling, provide hanger wire support clips that are integral with the linear slot
diffusers allowing the linear slot diffusers to be supported from the building structure with
ceiling wire. For hard ceilings, provide clips that are integral with the linear slot diffusers
allowing the diffusers to be secured directly to the ceiling framing without the
requirement for hanger supports. Provide spline clips to secure joints and ceiling tees to
the diffusers.
G. Material shall be minimum wall thickness 0.062 inches extruded aluminum. Spring steel
retainers shall be used under the spacers to hold the slot diffusers assembly tightly
together and allow the slot diffusers to be disassembled easily for field trimming.
Materials other than extruded aluminum and spring steel will not be accepted.
H. Flanges exposed to view shall be painted factory standard white. All other surfaces shall
be painted flat black. Provide paint samples if requested.
I. All slot diffusers shall be manufactured by the same manufacturer of the plenums and
hoods. No exceptions shall be allowed. Plenum lengths and entry collar sizes shall be
as indicated on the plan schedules.
J. Plenums shall be minimum 24-gauge galvanized steel and lined inside with black matte
fiberglass insulation. Hoods shall be 51 percent free area and constructed of 24-gauge
perforated sheet metal painted flat black.
K. Where shown on the drawings or otherwise indicated, provide a friction type volume
damper located in the entry collar of the supply air plenum, accessible through the slot
diffuser.
L. Air test and balance of linear and modular slot diffusers systems shall be by this section
and be in accordance with the testing and balancing portion section of the
specifications. Position all Flow Bar pattern controllers in their normal operation
positions and perform all air testing and balancing of all slot diffuser systems in full
accordance with manufacturer’s recommendations.
M. All slot diffusers shall be performance tested with air plenums as a composite assembly
in full accordance with ASHRAE, and/or ARI standards. If requested, the contractor shall
provide for a visit by the mechanical consulting engineer to the product testing
laboratory to verify performance data and testing procedures. All cost associated thereto
shall be provided at the expense of the contractor.
N. Diffusers shall be selected to achieve a throw to room length ratio which meets the
requirements of the ASHRAE Fundamentals Handbook, latest edition, at both
maximum design flow rate, and for VAV systems, at the minimum flow rate expected
during partial occupancy. Diffusers shall be selected to achieve a minimum of 70
percent ADPI over the range of expected loads in the space. The diffusers’ reported
performance shall be based on tests conducted in accordance with ASHRAE Standard
70–2006. ADPI performance on at least one-unit size of the selected diffuser shall have
A. Circular disc valves, suitable for supply and extract air, comprising valve ring with
peripheral seal, central disc with threaded spindle and locknut and installation sub frame
with volume flow rate adjustment by rotating the central disc.
B. Face sections sheet steel with electrostatic powder coating, galvanised steel threaded
spindle and lock nut, installation sub frame galvanised sheet steel.
A. Jet nozzles suitable for long throw distances with optimum acoustic properties,
preferably used for heating and cooling in critical areas. The adjustment facility –
manual allows variation in discharge angle to compensate for changing temperature
differences, adjustment angular range 30° upwards to 30° downwards. The manually
adjustable version can also be rotated through 360°.
B. The fixed jet nozzle consists of an aerodynamically shaped discharge nozzle deep-
drawn in one piece, with fixing holes. Adjustable construction consists of a discharge
nozzle with spherical outlet mounted in housing, a mounting flange and in a circular duct
rear connection spigot for direct connection to a circular duct. Also available with rear-
mounted duct connecting element with peripheral flange and optional spigot or saddle
connection with flange for fixing to the side of rectangular or circular ducts; the rear
contour of the saddle connection is profiled to the duct diameter.
C. The discharge nozzle and face cover ring are in aluminium, the mounting for the eyeball
is with two plastic rings, the connection element and saddle connection are in
galvanised sheet steel.
D. The surface shall be pre-treated, and powder coated in white (RAL 9010) or another
RAL color to suit the architectural finishes (the spigots remain galvanised finish)
A. Swirl diffusers with square or circular face with swirling horizontal discharge of supply air
with high induction, consisting of a pressed front face with radially angled fixed air guide
blades.
B. Optionally with fixed top entry plenum or top entry plenum with internal sub frame, or
circular side entry plenum box with circular spigot and additional options of lip seal or
volume control damper.
C. To measure reference pressure, the spigot can be fitted with sheathed cable adjusted
volume control damper and measuring nipple.
D. Plenum boxes complete with holes in top flange or fitted brackets for mounting. The
diffuser face can be fixed or removed by means of a centre fix screw.
PART 3 - EXECUTION
3.01 GENERAL
A. Provide all grilles, registers or diffusers which are suitable for installation in the ceiling,
wall or floor finishes. Provide all required accessories to facilitate installation.
B. Provide all air distribution devices from one manufacturer unless otherwise noted.
3.02 INSPECTION
A. Examine areas and conditions under which outlets and inlets are to be installed. Do not
proceed with work until unsatisfactory conditions have been corrected.
3.03 INSTALLATION
A. General: Install outlets and inlets in accordance with manufacturer’s written instructions
and in accordance with recognized industry practices to ensure that products serve
intended functions.
B. Provide an internally lined supply air plenum for all linear grilles, bar grilles and slot
diffusers. The lining shall be 1-inch thick minimum.
C. Coordinate with other work, including ductwork and duct accessories, as necessary to
interface installation of outlets and inlets with other work.
D. Locate ceiling air diffusers, registers, and grilles, as indicated on general construction
“Reflected Ceiling Plans”. Unless otherwise indicated, locate units in center of
acoustical ceiling modules.
E. Install perforated floor panels after full coordination with computer equipment contractor
and as approved by the Engineer’s Representative.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
1.02 SUBMITTALS
A. Product Data: For each condensing unit, include rated capacities, operating
characteristics, furnished specialties, and accessories. Include equipment dimensions,
weights and structural loads, required clearances, method of field assembly,
components, and location and size of each field connection.
C. Coordination Drawings: Plans, drawn to scale, on which the following items are shown
and coordinated with each other, based on input from installers of the items involved:
1. Structural members to which condensing units will be attached.
2. Liquid and vapor pipe sizes.
3. Refrigerant specialties.
4. Piping including connections, oil traps, and double risers.
5. Evaporators.
C. Fabricate and label refrigeration system according to ASHRAE 15, "Safety Code for
Mechanical Refrigeration."
1. Units shall be designed to operate with HCFC-free refrigerants.
D. ASME Compliance: Fabricate and label water-cooled condensing units to comply with
ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
1.04 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in Division 07 Section "Roof Accessories."
A. Provide all spare parts for 2-year operation as per the recommendation from the
supplier
PART 2 - PRODUCTS
2.01 MANUFACTURERS
C. Condenser Coil: Seamless copper-tube, aluminum-fin coil; circuited for integral liquid
subcooler, with removable drain pan and brass service valves with service ports.
E. Accessories:
1. Coastal Filter: Mesh screen to protect condenser coil from salt damage.
2. Crankcase heater.
3. Cycle Protector: Automatic-reset timer to prevent rapid compressor cycling.
4. Electronic programmable thermostat or Low-voltage thermostat and subbase to
control condensing unit and evaporator fan.
5. Evaporator Freeze Thermostat: Temperature-actuated switch that stops unit
when evaporator reaches freezing temperature.
6. Filter-dryer.
7. High-Pressure Switch: Automatic-reset switch cycles compressor off on high
refrigerant pressure.
8. Liquid-line solenoid.
9. Low-Pressure Switch: Automatic-reset switch cycles compressor off on low
refrigerant pressure.
10. PE mounting base to provide a permanent foundation.
11. Precharged and insulated suction and liquid tubing.
12. Sound Hood: Wraps around sound attenuation cover for compressor.
13. Thermostatic expansion valve.
14. Time-Delay Relay: Continues operation of evaporator fan after compressor
shuts off.
2.03 CONDENSING UNITS, AIR COOLED, 6 TO 120 TONS (21 TO 422 kW)
F. Accessories:
1. Electronic programmable thermostat or Low-voltage thermostat and subbase to
control condensing unit and evaporator fan.
2. Gage Panel: Package with refrigerant circuit suction and discharge gages.
3. Hot-gas bypass kit.
4. Part-winding-start timing relay, circuit breakers, and contactors.
G. Unit Casings: Designed for outdoor installation with weather protection for components
and controls and with removable panels for required access to compressors, controls,
condenser fans, motors, and drives. Additional features include the following:
1. Steel, galvanized or zinc coated, for exposed casing surfaces; treated and
finished with manufacturer's standard paint coating.
2. Perimeter base rail with forklift slots and lifting holes to facilitate rigging.
3. Gasketed control panel door.
4. Nonfused disconnect switch, factory mounted and wired, for single external
electrical power connection.
5. Condenser coil hail guard and grille to protect coil from physical damage.
B. Compressor: Hermetic or serviceable hermetic type; with oil pump, operating oil charge,
and suction and discharge shutoff valves. Factory mounted on base using spring
isolators. Include the following:
1. Thermally protected compressor motor.
2. Crankcase heater.
3. Capacity control using cylinder unloading, suction pressure controlled and
discharge pressure operated, designed for unloaded start.
4. Refrigerant Charge: R-407C, R-410A or HFC-134a.
2.05 MOTORS
A. General requirements for motors are specified in Division 23 Section "Common Motor
Requirements for HVAC Equipment."
1. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven
load will not require motor to operate in service factor range above 1.0.
2. Controllers, Electrical Devices, and Wiring: Electrical devices and connections
are specified in Division 26 Sections.
B. Test and inspect shell and tube condensers according to ASME Boiler and Pressure
Vessel Code: Section VIII, Division 1.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of
condensing units.
B. Examine roughing-in for refrigerant piping systems to verify actual locations of piping
connections before equipment installation.
C. Examine walls, floors, and roofs for suitable conditions where condensing units will be
installed.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 INSTALLATION
A. Install units level and plumb, firmly anchored in locations indicated; maintain
manufacturer's recommended clearances.
C. Concrete Bases:
1. Install dowel rods to connect concrete base to concrete slab. Unless otherwise
indicated, install dowel rods on 18-inch (450-mm) centers around full perimeter of
the base.
2. For equipment supported on structural slab, install epoxy-coated anchor bolts
that extend through concrete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates,
diagrams, instructions, and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to supported
equipment.
5. Install anchor bolts according to anchor-bolt manufacturer's written instructions.
H. Loose Components: Install electrical components, devices, and accessories that are
not factory mounted.
3.03 CONNECTIONS
A. Perform the following field tests and inspections and prepare test reports:
1. Perform electrical test and visual and mechanical inspection.
2. Leak Test: After installation, charge systems with refrigerant and oil and test for
leaks. Repair leaks replace lost refrigerant and oil, and retest until no leaks exist.
3. Operational Test: After electrical circuitry has been energized, start units to
confirm proper operation, product capability, and compliance with requirements.
4. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
5. Verify proper airflow over coils.
C. Remove and replace malfunctioning condensing units and retest as specified above.
C. Verify that fan wheel is rotating in the correct direction and is not vibrating or binding.
H. Verify that vibration isolation and flexible connections properly dampen vibration
transmission to structure.
I. After startup and performance test, lubricate bearings and adjust belt tension.
3.06 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes, air-handling units / energy recovery ventilators (ERV) with coils
for indoor and outdoor installations.
1.02 REFERENCES
C. AMCA 300 - Test Code for sound Rating Air Moving Devices.
D. AMCA 301 - Method of Publishing Sound Ratings for Air Moving Devices.
G. ANSI/AFBMA 11- Load Ratings and Fatigue Life for Roller Bearings.
1.03 SUBMITTALS
A. Product Data: For each type of indoor air-handling unit / energy recovery ventilator
indicated. Include the following:
1. Certified fan-performance curves with system operating conditions indicated.
2. Certified fan-sound power ratings.
3. Certified coil-performance ratings with system operating conditions indicated.
4. Motor ratings, electrical characteristics, and motor and fan accessories.
5. Material gages and finishes.
6. Filters with performance characteristics.
7. Dampers, including housings, linkages, and operators.
F. Static pressures given in the Energy Recovery Ventilator (ERV) Schedules are only for
guidance. The Contractor shall calculate the external and internal static pressures for all
ERV’s and shall obtain Engineer's approval before ordering the equipment’s. The
Contractor should provide the required fan and motor h.p. without additional cost
A. Source Limitations: Obtain indoor air-handling units / energy recovery ventilator (ERV)
through one source from a single manufacturer.
F. Eurovent Certifications for the complete range of AHU’s/ERV’s: Units should be certified
and labelled with Eurovent Certification. AHUs/ERV’s must be manufactured at locations
mentioned on the Eurovent certificate. Semi knocked down or completely knocked down
AHUs/ERV’s for assembly at site are not acceptable. Local assembly hub shall be
acceptable if it is Eurovent certified.One unit to be run tested as per FAT & Visual
inspection of all AHUs/ERV’s prior to shipment.
G. AHRI Certification/Eurovent: In the case of AHRI certified AHUs/ERV’s, the Coils shall
be AHRI certified according to the applicable portions of AHRI 410, and shall be listed
and bear the label of the Air-Conditioning Heating and Refrigeration Institute (AHRI).
H. Provide motors required as part of air-handling units that are listed and labelled by CE
and comply with applicable standards in accordance with IEC.
I. Condensation: Provide cold bridge free construction with Thermal break profile to
protect the unit against condensation.
J. Factory shall be ISO 9001:2008, ISO 14001: OHSAS 18001: certified. All valid
certifications must be part of submittal
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in Division 07 Section "Roof Accessories."
B. Tools and spare parts supplied under this clause shall be provided in original packing,
clearly labelled and referenced.
C. Spare Parts furnished under this clause shall not be used during the maintenance
period without the written permission of the owner (Contractor shall procure spare parts,
tools etc., fulfill his obligations to operate and maintain the system in the contract period)
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. The Air handling supplier should supply the first line product, which should be AHRI /
Eurovent Certified. The AHRI / Eurovent certificate should show the product series,
AHU/ERV sizes, models range, Country of origin etc.
C. Factory dynamic fan balancing shall be conducted from 14Hz to 50Hz to identify and
eliminate critical speeds to ensure stable operation through the entire operating range of
the fan and drive assembly. Field fan balancing is not acceptable. Forward factory
balancing test report to Engineer upon request.
E. Furnish each unit with a durable, deep etched, .025” thick, factory installed aluminum
identification plate, permanently mounted with the following information:
1. Unit identification as indicated on Contract Drawings.
2. Serial Number.
3. Model Number.
4. Capacity (CFM) and static pressure.
5. Motor HP.
6. Unit power supply: Volts / PH / Amps.
7. Supply Fan Type.
8. Coil GPM and pressure drop.
9. Sales Order #.
10. Date unit manufactured.
2.03 CABINET
C. Certification
1. The casing should meet Eurovent EN1886 with the following mechanical
characteristics
Casing Strength D1
Casing Air Leakage Class at -400Pa L1
Casing Air Leakage Class at +700Pa L1
Thermal Transmittance Class T2
Thermal Bridging Factor TB2
Filter Bypass Class F9
C. Direct drive single inlet centrifugal fans shall be backward curved high performance
centrifugal impellors with rotation diffuser, mounted on EC external rotor motor with
integrated control electronics.
D. Fan speed control shall be via AHU/ERV controller which shall be interfaced with the
BMS thru BACNET/IP Communication interface for remote monitoring and control.
E. Impellor shall be made of aluminum, with backward curved, continuously welded blades;
flow optimized inlet nozzle made of galvanized steel with pressure tap.
F. Motorized impellor balanced in two planes (static and dynamic) as per DIN ISO 1940 to
G 6.3 balance quality.
G. EC external rotor motor with Efficiency class IE4, magnets without use of rare earths,
maintenance free ball bearings with long term lubrication, theoretical nominal service life
of atleast 40,000 operating hours, soft start, integrated current limitation, wide input
voltage range 1-phase 230V, 60Hz or 3-phase 400V, 60Hz fan suitable for use with all
standard power supply systems with no effect on air performance.
H. Integrated electronics, low noise commutation logic; 100% speed control; PID
controllers; motors with power ratings of 750W shall be provided with an
RS485/MODBUS RTU interface.
I. Terminal box shall be made of aluminum with readily accessible connection area with
spring terminals, environment resistant cable glands or with brought out variable
connection cables (K3G250-AT39 and K3G280-AT04 only.)
K. Performance data, air performance measurements on inlet side chamber test rig shall
be in accordance with ISO 5801 and DIN 24163, noise measurements in low reflection
acoustic test chamber as per DIN EN ISO 3745.
M. Fans shall have a sharply rising pressure characteristic extending through the operating
range and continuing to rise beyond the peak efficiency to ensure quiet and stable
operation. Fans shall have non overloading design with self-limiting horsepower
characteristics and shall reach a peak in the normal selection area.
N. Factory Run Test for one AHU/ERV: All fans prior to shipment shall be completely
assembled and test run as a unit at the specified operating speed or maximum RPM
allowed for the particular construction type.
O. Blank off panels: Each multiple fan section to be provided with one fan blank off panel to
enable manual isolation of fan for servicing.
P. The following fan options shall be made available for multiple fans:
1. Piezometer Ring: Airflow station shall be factory installed in each fan inlet.
Tubing shall be manifolded so that the measurement is representative of all fans
in the array. The device shall have a measurement accuracy of ±5%.
2. Backdraft damper: Backdraft damper shall be provided for automatic isolation of
individual fans for duty and standby configuration.
Q. Shafts: Solid hot rolled steel, ground and polished, with key-way, and protectively
coated with lubricating oil. Critical speed minimum 20% greater than maximum ACMA
class speed.
R. Fans should capable of accommodating static pressure and airflow variation of minimum
plus or minus 10 percent. Do not increase the speed by more than 20 percent from
specified criteria.
T. Control panel shall be supplied by same AHU/ERV supplier with in-built isolator.
A. Performance Ratings: Tested and rated according to AHRI 410 and ASHRAE 33.
D. Tubes: ASTM B 743 copper, minimum 0.049 inch (1.245 mm) thick.
F. Suction and Distributor Piping: ASTM B 88, Type L (ASTM B 88M, Type B) copper tube
with brazed joints.
G. Frames: Galvanized-steel channel frame, minimum 0.0625 inch (1.6 mm) thick for
flanged mounting.
H. Frames: ASTM A 666, Type 316 stainless steel, minimum 0.0625 inch (1.6 mm) thick
for flanged mounting.
2.06 FILTERS
B. Vent valves.
F. Accessories: Static pressure tips with integral compression fittings, 6m, plastic tubing
and 2 or 3-way vent valves.
A. All specifications in this section for indoor units should be applicable for outdoor version
in addition to the following:
1. The outdoor Air Handling Units / Energy Recovery Ventilator should be
specifically designed for outdoor installation. Indoor air handlers weatherized for
outdoor use not accepted
2. The outdoor units outer joint of the unit should be sealed with permanently
flexible sealing compound.
3. A full-size sloping roof with drip nose for the outdoor units, which is both longer
and wider than the unit and painted in optional color.
4. All outdoor units shall be constructed and delivered on a base fabricated frame
from heavy duty structure galvanized steel channel painted in optional color. The
minimum acceptable height for the base frame is 150 mm.
5. For outdoor extract units the discharge should be fitted with an exhaust hood with
bird screen and the casing drainage shall be provided in the discharge sections.
6. The intake dampers should have contra-rotating stainless-steel profile blades
and fitted internally in a separate section. Also, for the Mixing Box the dampers
should fitted internally.
7. Provide special PVC / epoxy coating for the outer skin.
8. Fresh air inlet shall be through weather proof louver. Case stainless steel drain
pan shall be provided in the intake section.
A. Material: Hygroscopic type rotor heat exchanger designed for the transfer of both
sensible and latent heat. Bearings should be permanently lubricated roller type.
C. Thermal efficiency: The thermal wheels efficiency shall be at not less than 75%.
Measured at the recovery side.
D. Modular unit matching with air handling unit / Energy Recovery Ventilator modules in all
respects comprising, but not limited to the following to reclaim coolness / heat from the
exhaust air and transfer to the outside air intake:
1. Wheel filled with a matrix of Aluminium foil.
a. Speed controlled drive unit.
b. High performance seal provides tightness around the wheel surround and
between the air inlet and air outlet.
c. The desiccant should be water molecule selective and non-migratory.
d. The desiccant should be molecular sieve 3 Angstrom, so as to keep the
cross contamination to absolute minimum and also ensure the exclusion
of contaminants from the air streams, while transferring the water vapour
molecules.
F. Wheel matrix should be only from pure aluminum foil to allow for quick and efficient
uptake of thermal energy, sufficient mass for optimum heat transfer, maximum sensible
heat recovery during low rotational speed of 20 to 25 rpm.
G. The Desiccant for Enthalpy wheel should be water molecule selective and non-
migratory. The Desiccant should be molecular sieve 3Å, so as to keep the cross
contamination to absolute minimum and also ensure the exclusion of contaminants from
the air streams, while transferring the water vapor molecule. The desiccant should be of
sufficient mass, and should be coated with non-masking porous binder adhesive on the
aluminum substrate (matrix) so as to allow quick and easy uptake and release of water
vapor. The weight of desiccant coating and the mass of aluminum foil shall be in a ratio
so as to ensure equal recovery of both sensible and latent heat over the operating
range.
H. The Rotor/Wheel matrix shall have Equal sensible and latent recovery in the range of 60
to 80%.
I. The Rotor shall be made of alternate flat and corrugated aluminum foil of uniform width.
The Rotor honeycomb matrix foil should be so wound and adhered as to make a
structurally very strong and rigid media un-affected by temperature and humidity
changes.
J. Subject to wheel size, sectioned wheel with pie segments, capable of being assembled
at site can be acceptable as an option.
K. The surface of the wheel/rotor should be highly polished to ensure that the vertical run
out does not exceed ± 1mm for every 1 meter diameter , ensuring negligible leakage.
L. The number of wraps (of alternative corrugated and flat foil ) of the rotor over the radii
shall be very consistent so as to ensure uniform air flow and performance over the entire
face in the air stream. Flute height and pitch will be consistent to a very tight tolerance to
ensure uniform pressure drop and uniform airflow across the rotor face.
M. The rotor shall be non clogging aluminum media, having a multitude of narrow aluminum
channels, thus ensuring a laminar flow and will allow particles up to 800 microns to pass
through it.
N. The rotor should rotate at a speed lower than 20 to 25 rpm, ensuring long life of belts
and reduce wear and tear of seals.
Q. The rotor shall have a field adjustable purge mechanism to provide definite separation of
air flow minimizing the carryover of bacteria, dust and other pollutants, from the exhaust
air to supply air. With proper adjustments the cross contamination shall be limited to less
than 0.04% of the exhaust air concentration.
R. The face and radial seals shall be 4 pass non contact labyrinth seals for effective
sealing and also for minimum wear and tear.
2.010 Thermal wheels sensible and enthalpy shall be supplied with electronic speed control
center ( If shown on the schedules). The electronic speed control center shall be fully
integrated to BAS ( building automation system)
A. General
1. Heat pipes shall be included within the AHU/ERV and wrapped around the main
cooling coil. The wrap-around heat pipes precool the fresh/return air allowing
more of the cooling coil surface to be utilized for the removal of moisture. The
dehumidified air is then passively reheated by the heat pipe to the supply
condition. The incorporation of the heat pipe allows for a reduction in the size of
chiller and cooling coil as well as replacing the conventional methods of reheat
and their associated system components.
2. Heat pipes for enhanced dehumidification will comprise a precool fin block
upstream of the main cooling coil linked to a reheat fin block downstream of the
cooling coil by means of ‘wrap-around’ pipes. The heat pipes will be delivered to
the AHU/ERV manufacturer fully charged and sealed, for inclusion in the air
treatment section of the AHU/ERV.
B. Fins
The external fins shall be of aluminium with a minimum thickness of 0.15mm. Fins shall
be of the continuous plate type to maximize the external surface area rather the
individually finned tube pattern. The fins shall be of the louvered type to optimize the
airside heat transfer and spaced at such a distance as required by the conditions
specified.
C. Tubes
Tubes shall be of refrigeration standard seamless copper C106 for heat exchanger use.
Tube diameter shall be 12mm with a grooved inner surface to enhance the internal
surface area and prevent pooling of liquid. The minimum root thickness of the tube shall
be 0.35mm. The number of rows of tubes shall be selected to suit the application.
Multiple row heat pipes shall have tubes in a staggered, equilateral pattern to optimize
the airside heat transfer.
KEO/21-7387-0004 23 7313 / 11 Indoor and Outdoor Air Handling Units/Energy
Reem Hills Development Recovery Ventilator(ERV)
Twin Villas & Townhouses, Abu Dhabi
D. Casing
Casings shall be from galvanized sheet steel with a minimum thickness of 1.6mm. The
casing shall incorporate tube plates and top and bottom plates around both the precool
and reheat heat pipe blocks. Cover boxes shall be provided around the wrap-around
pipes both to protect the exposed pipes and to rigidly join the two sections. Extra sheet
metal shall be provided to ensure rigidity during manufacture and transport.
E. Working Fluid
1. The working fluid shall be refrigerant type classified as ASHRAE safety group A1.
The refrigerant shall be R134a. The heat pipe circuits shall be factory charged
and hermetically sealed with the calculated weight of refrigerant.
2. If working fluid is water, the heat pipe circuit shall be factory charged with the
calculated weight of water and hermitically sealed. Individual heat pipe shall be
manufactured in such a way as to ensure that all non-condensable gases are
removed from the tubes.
F. Circuitry
1. Heat pipes shall be formed from an array of complete loops such that the working
fluid flows around the loop in only one direction i.e. liquid and vapour flow in the
same direction to ensure that returning liquid is not entrained by the vapour.
2. There shall be a multitude of loops in the height of the heat pipe and each loop
shall be individually charged. Heat pipes with header assemblies containing a
single circuit are not suitable as a single leak will render the entire heat pipe
inoperative.
3. When multiple row heat pipes are used the rows shall be connected together in a
counter flow orientation to optimize the performance of the heat pipe. Rows shall
not be manifolded together.
4. Heat pipe loops shall be arranged to slope down to the precool side to allow
gravity assisted liquid return to maximize the internal heat transfer.
G. Performance
Heat pipes shall be designed to comply with the specified conditions when subject to the
air volumes given in the specification. Heat pipe performance shall be independently
type tested and certified in line with the requirements of British Standards BS 5141 pt1 /
European Standards EN 305 & 306 / American Standards AHRI 410 / AHRI 1060 for
testing and rating of heat exchangers. All software used to predict the performance of
heat pipes shall be based upon the results of these independent tests
A. Air handling unit/Energy Recovery Ventilator sound power data shall be submitted for
review. Sound data shall be given at the supply connections and return connections.
B. Calculations shall be provided for the investigation of the requirements for Sound
Attenuators.
PART 3 - EXECUTION
3.01 SELECTION
A. The size of units shall be selected to fit into the space available.
3.02 EXAMINATION
A. Examine areas and conditions for compliance with requirements for installation
tolerances and other conditions affecting performance.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.03 INSTALLATION
B. Concrete Bases: Install floor mounting units on 4-inch- (100-mm-) high concrete bases.
See Division 23 Section "Common Work Results for HVAC" for concrete base materials
and fabrication requirements.
C. Install indoor air-handling units / energy recovery ventilator with the vibration control
devices as specified in Division 23 Section "Vibration and Seismic Controls for HVAC
Piping and Equipment."
E. Arrange installation of units to provide access space around indoor air-handling units /
energy recovery ventilator for service and maintenance.
G. Air handling units / Energy Recovery Ventilators are to be properly supported to prevent
flexing, bending or distorting base rails.
H. All coils are to be cleaned prior to substantial completion if units are used during
construction.
I. Clean all air handling units / Energy Recovery Ventilators and return to original
manufacturer's condition prior to substantial completion. Vacuum clean all debris from
inside air handling equipment.
J. Install piping to unit with full size 6 inch long dirt leg with 1/2" valve at bottom for
cleaning.
L. Adjust fan drives as required to obtain scheduled capacities as directed by the Test and
Balance Firm to include sheave and belt replacement.
3.04 CONNECTIONS
C. Starting procedures for indoor air-handling units / Energy Recovery ventilator include the
following:
1. Energize motor; verify proper operation of motor, drive system, and fan wheel.
Adjust fan to indicated rpm. Replace fan and motor pulleys as required to
achieve design conditions].
2. Measure and record motor electrical values for voltage and amperage.
3. Manually operate dampers from fully closed to fully open position and record fan
performance.
D. Refer to Division 23 Section "Testing, Adjusting, and Balancing for HVAC" for indoor air-
handling system / Energy Recovery Ventilator testing, adjusting, and balancing.
3.08 CLEANING
B. After completing system installation and testing, adjusting, and balancing indoor air-
handling / Energy Recovery ventilator and air-distribution systems, clean filter housings
and install new filters.
3.09 DEMONSTRATION
END OF SECTION
SPLIT-SYSTEM AIR-CONDITIONERS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
1.02 SUBMITTALS
A. Product Data: Include rated capacities, furnished specialties, and accessories for
each type of product indicated. Include performance data in terms of capacities,
outlet velocities, static pressures, sound power characteristics, motor requirements,
and electrical characteristics.
C. Samples for Initial Selection: For units with factory-applied color finishes.
E. The equipment manufacturer shall be fully certified and registered to comply with the
Abu Dhabi Local authority having jurisdiction, local Green Building Code, ESMA and
QCC.
G. The system will be produced in an ISO 9001 and ISO 14001 facility, which are
standards set by the International Standard Organization (ISO). The system shall be
factory tested for safety and function.
H. The units shall be tested by a reputed Third Part as per ISO 5151.
J. The outdoor unit will be factory charged with R-32 or R-410 refrigerant.
1.04 COORDINATION
A. Coordinate size and location of concrete bases for units. Cast anchor-bolt inserts
into bases. Concrete, reinforcement, and formwork are specified in Division 03
Section "Cast-in-Place Concrete."
B. Coordinate size, location, and connection details with roof curbs, equipment
supports, and roof penetrations specified in Division 07 Section "Roof Accessories."
1.05 WARRANTY
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. The variable capacity, heat pump air conditioning system shall be an Inverter Driven
series split system. The system shall consist of a ceiling concealed and ducted
B. Evaporator / Condenser shall be factory assembled including coil, fan motor(s) and
controls in casing.
C. The outdoor unit is a horizontal or vertical discharge, variable speed, fan unit. The
system shall have a self-diagnostic function, 3-minute time delay mechanism and
have a factory pre-charge of R-32 or R410 adequate for the installation requirement.
The system shall have automatic restart capability after a power failure has occurred
and a low voltage cut-off feature to prevent stalling during power supply issues.
A. General: The indoor unit shall be factory assembled including coil, fan motor(s) and
pre-wired with all necessary electronic and refrigerant controls. Both liquid and suc-
tion lines must be individually insulated between the outdoor and indoor units.
B. Unit Cabinet:
1. Galvanized steel, 1mm thick with flanged edges, removable panels for servic-
ing and insulation on back of panel.
a. Insulation: Faced, glass fiber duct liner.
b. Drain Pans: Galvanized steel, with connection for drain and insulated.
C. Fan:
1. The evaporator fan shall be centrifugal forward-curved, double width wheel of
galvanized steel.
2. The evaporator fan shall be an assembly consisting of a direct-driven fan
connected to a motor.
3. The fan shall be statically and dynamically balanced and operate on a motor
with permanent lubricated bearings.
4. Fan driving components are mounted on rubber pad isolators to reduce noise
and vibration.
D. Fan Motors:
1. Motors are Brushless DC electric motors (ECM).
2. Provides a range of different RPM to cater for different static pressure
requirements in the field. Default static pressure can be modified to suit
installation requirements/ductwork lengths.
3. Internal Overcurrent protection provided with the motors.
E. Filter:
1. The return air filter provided will be mildew proof, removable and washable
antimicrobial filter.
F. Evaporator Coil:
1. Manufactured with seamless copper internally grooved tubes (IGT).
2. Aluminum fins are mechanically bonded with copper tubes.
3. Coils are tested at 580 PSIG N2 pressure for air-tight & helium leak testing.
4. Aluminum is treated with anti-corrosive coating & hydrophilic coating.
G. Electrical:
1. The outdoor unit shall be powered with 208-230 volts, 1 phase, and 50 hertz
power. The indoor unit shall receive 208-230 volt, 1 phase, 50 hertz power
from the outdoor unit.
2. The allowable voltage range shall be 160 volts to 265 volts.
3. Built in voltage stabilizer must be provided.
H. General: The indoor unit shall be factory assembled and pre-wired with all necessary
electronic and refrigerant controls. Both liquid and suction lines must be individually
insulated between the outdoor and indoor units.
I. Unit Cabinet:
1. The indoor unit shall have a white finish.
2. The drain and refrigerant piping shall be accessible from six (6) positions for
flexible installation (right side, right back, and right bottom; and left side, left
back, and left bottom.
3. The cabinet shall be supplied with a mounting plate to be installed onto a wall
for securely mounting the cabinet.
J. Fan:
1. The evaporator fan shall be an assembly consisting of a direct-driven fan by a
single motor.
2. The fan shall be statically and dynamically balanced and operate on a motor
with permanent lubricated bearings.
3. An auto-swing louver for adjustable air flow (both vertically and horizontally) is
standard via the wireless remote control furnished with each system.
4. The indoor fan shall offer a choice of five speeds, plus quiet and auto settings.
K. Filter:
1. The return air filter provided will be mildew proof, removable and washable
antimicrobial filter.
L. Coil:
1. The evaporator coil shall be a nonferrous, aluminum fin on copper tube heat
exchanger.
2. All tube joints shall be brazed with silver alloy or phoscopper.
3. All coils will be factory pressure tested.
4. A condensate pan shall be provided under the coil with a drain connection.
M. Electrical:
1. The outdoor unit shall be powered with 208-230 volts, 1 phase, and 50 hertz
power. The indoor unit shall receive 208-230 volt, 1 phase, 50 hertz power
from the outdoor unit.
2. The allowable voltage range shall be 160 volts to 265 volts.
3. Built in voltage stabilizer must be provided.
N. Control:
3. The remote control shall perform Fault Diagnostic functions which may
be system related, indoor unit or outdoor unit related depending on the
fault code.
O. Sound:
C. Fan:
1. The fan shall be a direct drive, propeller type fan.
2. Fans are statically & dynamically balanced for quiet operation.
3. A fan guard is provided on the outdoor unit to prevent contact with fan
operation.
D. Fan Motor:
1. Motors are Brushless DC electric motors (ECM), to cater for high con-
denser airflow requirement during high outdoor ambient operations
conditions and low airflow requirement during part load & low outdoor
ambient operations to optimize energy efficiency.
2. Motor shall be protected with Class E insulation.
E. Condenser Coil:
1. Condenser coils are manufactured with seamless copper internally
grooved tubes (IGT).
2. Aluminum fins are mechanically bonded with copper tubes.
3. Coils are tested at 580 PSIG N2 for air-tight & helium leak testing.
4. The fins are to be covered with an anti-corrosion hydrophilic blue fin
film.
F. Compressor:
1. Compressor shall be high efficiency type and hermetically sealed.
2. The compressor shall be inverter-driven compressor controlled by in-
verter for variable speed.
3. Accumulator is an integral part to save compressor from occasional
liquid flood back.
4. The compressor shall have an internal thermal overload protection.
5. Sound jackets shall be provided to reduce compressor noise.
6. The outdoor unit can operate with a maximum vertical height difference
of 15 m and overall maximum length of 30 m without any oil traps or
additional components.
7. The compressor shall be mounted on rubber anti vibration isolators.
G. Additional Accumulator:
1. Additional accumulator is provided to save the compressor from liquid
flood back & to enhance compressor’s life.
H. Electrical:
1. The electrical power requirement is 400 volt, 3-phase, and 50 Hz pow-
er.
2. The outdoor shall be controlled by a microprocessor located in the out-
door and indoor units via commands from the Thermostat.
3. Dedicated EEV’s shall be provided for capacity control during part load
of the indoor unit.
A. Current Control: If overall current of system reaches limit value, then this
protection will try to keep the system safer by reducing compressor speed.
C. Low Pressure Control: If pressure is below 0.15 Mpa, system will get
stopped and related malfunction code will appear on remote display.
E. Motor overcurrent protection: For the safe operation & better life of motor,
overcurrent protection is given.
2.07 ACCESSORIES
C. Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factory
cleaned, dried, pressurized, and sealed; factory-insulated suction line with
flared fittings at both ends.
PART 3 - EXECUTION
3.01 INSTALLATION
3.02 CONNECTIONS
B. Perform the following field tests and inspections and prepare test reports:
1. Leak Test: After installation, charge system and test for leaks. Repair leaks
and retest until no leaks exist.
2. Operational Test: After electrical circuitry has been energized, start units to
confirm proper motor rotation and unit operation.
3. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
3.05 DEMONSTRATION
END OF SECTION
AIR COILS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following types of air coils that are not an integral part of air-
handling units:
1. Refrigerant.
2. Electric.
A. Division 23 Sections for air coils that are integral to air-handling units.
1.03 REFERENCES
1.04 SUBMITTALS
A. Product Data: For each type of product indicated. Include construction details, material
descriptions, dimensions of individual components and profiles, and finishes for each air
coil. Include rated capacity and pressure drop for each air coil.
C. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which coil location
and ceiling-mounted access panels are shown and coordinated with each other.
E. Operation and Maintenance Data: For air coils to include in operation and maintenance
manuals.
B. Coils shall be the product of manufacturer regularly engaged in production of coils who
issues complete catalog data on such products
B. Following spare parts shall be furnished, properly packed and labelled with equipment
no. / location.
1. 1 set of contactors, automatic / manual reset thermostats for each coil.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 GENERAL
A. Provide extended surface type coils with tubes of copper and fins of aluminum.
B. Space fins 12 per inch maximum and minimum tube Ida. 5/8”. Helical fins may be
crimped. The whole fin shall be without any holes for easy cleaning
D. Fin collar shall cover entire tube, so there is no air contact with tube.
F. Bends in tubes shall be smooth without wrinkles to reduce erosion and pressure drop.
G. Performance rating shall be established at a maximum coil face air velocity of 2.54 mps
(500 fpm) or as per manufacturer standards.
H. Drip / drain pan shall be of sturdy construction and with inherit protection against
corrosion.
I. Protect coils so fins are not damaged. Replace loose and damaged fins. Comb out bent
fins.
D. Tubes: ASTM B 743 copper, minimum 0.049 inch (1.245 mm) thick.
F. Suction and Distributor Piping: ASTM B 88, Type L (ASTM B 88M, Type B) copper tube
with brazed joints.
G. Frames: Galvanized-steel channel frame, minimum 0.0625 inch (1.6 mm) thick for
flanged mounting.
H. Frames: ASTM A 666, Type 316 stainless steel, minimum 0.0625 inch (1.6 mm) thick
for flanged mounting.
A. Flanged / slip-on assembly fabricated from sheet steel with welded joints and finished
with heat resistant paint; with integral control panel.
C. End points of the U-shaped element shall be insulated with ceramic bushes and
terminated with threaded gland nuts and bushes, suitable for assembly on to element
plates.
E. Control Panel: Unit mounted with disconnecting means and overcurrent protection.
Include the following:
1. Mains isolator (4 pole, fully enclosed type) interlocked with door.
2. Power transformer for control power supply (as appropriate).
3. Contactor (DOL) with overload trip and ‘ON’ indicator, for each stage as
appropriate.
4. Primary thermal cut-out (disk type), with automatic reset.
5. Secondary thermal cut-out with manual reset.
6. Set of terminals / relays with volt free contacts for start / stop from the
temperature control system.
7. Air flow switch interlocked with contactor.
3.01 EXAMINATION
A. Examine ducts, plenums, and casings to receive air coils for compliance with
requirements for installation tolerances and other conditions affecting coil performance.
B. Examine roughing-in for piping systems to verify actual locations of piping connections
before coil installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 INSTALLATION
B. Install coils in metal ducts and casings constructed according to SMACNA's "HVAC
Duct Construction Standards, Metal and Flexible."
E. Construct drain pans to extend beyond coil length and width and to connect to
condensate trap and drainage
G. Extend drain pan under coil headers and exposed supply piping.
H. Install moisture eliminators for cooling coils. Extend drain pan under moisture
eliminator.
J. Clean coils using materials and methods recommended in writing by manufacturers, and
clean inside of casings and enclosures to remove dust and debris.
K. Support coil sections on steel channel or double angle frames and secure to casings.
Arrange supports for cooling coils to avoid piercing or short circuiting drip pans. Bolt
casings to other section, or unit casings. Provide airtight seal between coil and unit
cabinets.
L. Make connections to coils, including valves, air vents, unions, and connections from drip
pans, as indicated on the drawings.
M. Locate water supply at bottom of supply header and return water connection at top to
provide self-venting and reverse return arrangement. Provide float operated automatic
air vents at high points complete with stop valve. Ensure water coils are drainable and
make drain connection at low points.
3.03 CONNECTIONS
C. Connect water piping with unions and shutoff valves to allow coils to be disconnected
without draining piping. Control valves are specified in Division 23 Section
"Instrumentation and Control for HVAC," and other piping specialties are specified in
Division 23 Section "Hydronic Piping."
A. Perform the following field tests and inspections and prepare test reports:
1. Operational Test: After electrical circuitry has been energized, operate electric
coils to confirm proper unit operation.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
END OF SECTION
1.01 GENERAL
B. The list of vendors mentioned in this section is indicative and the Contract
Documents shall be construed as a Vendor Neutral set of requirements. The
Contractor may propose other vendors provided that strict compliance with
Drawings, Specifications and broader Contract Documents is guaranteed by the
Contractor and validated by the Engineer.
Safid. UAE
Trox. UK
Fire and Smoke ALDES MIDDLE EAST UAE
Dampers
Ruskin Mfg. Co. USA
Safid. UAE
Trox. UK
Turning Vanes Anemostat Products Div., USA
Dynamics Corp. of America.
A. Subject to compliance with the requirements of the Contract Documents, the warranty
and spare parts shall include but not limited to list below.
DIVISION 23 HVAC
- Warranty period is from taking over certificate to client; parts, labour, travel time expenses
are included.
- Bidder is to provide a schedule of spares as part of the submission and include delivery to
site.
- Routine maintenance visits as recommended by manufacturer during the course of the
defect notification period until performance certificate.
- Basic and advance training courses for FM staff are required.
- For items not mentioned in this warranty list, shall be covered under manufacturer
standard warranty.
23 0500 COMMON WORK RESULTS FOR Standard Manufacturers’ All spare parts
HVAC warranties (Minimum 12 required during the
months by contractor) warranty period
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The contractor shall complete, commission and hand over the works in accordance with
the design intent expressed in contract documents. In general, the project comprises of
the following works. General elements of scope of work include:
1. Provision of all labour, equipment and materials required to complete the works
according to the Design Intent. Provision means supply, installation, test,
commission and put to operation.
2. Additional hardware, incidentals and any other work necessary for completion of
the works and safe, correct operation of each system, whether such item or work
is detailed in the specifications and or on the drawings or not.
3. Verification of existing conditions on site prior to tendering. Arranging with and
paying the ADDC and the Telecom service provider authorities to re-route their
services should such services exist on site.
4. Temporary power supplies for construction purposes for the duration of the
works.
5. Arranging for and coordination of installation of new permanent supplies from
ADDC, including submission of necessary documents and securing all approvals
having relevance.
6. Arranging for and carrying out necessary approvals with the Telecom. Service
Provider for the telephone system.
7. Arranging for and carrying out necessary approvals with the Abu Dhabi Civil
Defense for the fire alarm system and emergency lighting system.
8. Preparation of shop / construction / installation drawings for approval.
9. Builder's work, ducts, inserts and sleeves required for the works
10. On-site coordination with all other services and trades, liaison with members of
the professional team, attendance on meetings as required.
11. Testing, commissioning and certification that the work has been completed and
inspected in accordance with the requirements of the relevant Regulations.
12. “As Built” drawings, “Operation and Maintenance Manuals” and other project-
specific record documents.
13. Training of the Employer’s staff in the operation of the systems installed.
14. Defects Liability: refer to contract conditions specified elsewhere.
15. Maintenance during the Defect Liability Period: refer to contract conditions
specified elsewhere.
16. Spare parts: refer to contract conditions specified elsewhere.
B. Electrical System
D. Exact location of all equipment and components to be approved on site by the Engineer.
E. Contractor shall include the cost of the credits required as per the Estidama PBRS
credits. The requirement of commissioning as per Estidama shall also be included in the
scope of the work. Please refer the sustainability/Estidama specification for details.
B. Earthing system will be provided for 0.4kV system and Telecommunication system.
Lightning protection system will cover the entire project. Transient voltage surge
suppressors will be provided.
D. Lighting Systems
1. Normal Power Lighting. The normal power lighting system shall provide lighting
throughout the building when it is in the normal operation mode.
2. Lighting in all common areas, carpark, façade, landscape and feature lights will
be controlled as indicated in the drawings.
3. Electricity metering system shall be provided as per ADDC/ADWEA specification.
The electricity and water meter shall be installed by contractor in accordance with
ADDC regulations.
B. Telecommunications infrastructure
1. The infrastructure shall be provided within the building according to the function
of the building to provide telecom services, all as per the local Service provider
guidelines.
2. Structured Cabling System (SCS) will be used within the building.
C. Telecom & IT
1. Townhouses are served directly from Local telecom service provider network.
A. Electrical Supply
1. ADDC compliant power supplies - 3 phase, 4 wire, 400 V, 50 Hertz of adequate
capacity and having the following tolerances:
a. Voltage +10% and -6%
b. Frequency +/- 0.1 %
c. Neutral solidly earthed at transformer location
B. Climatic Condition
1. The climate in Abu Dhabi in the summer months is hot and humid and a humidity
of 100% at 30ºC has been recorded.
2. Violent sand and dust storms of several hours duration occur and even on
comparatively still days, fine dust is carried in suspension in the atmosphere.
3. All apparatus and equipment shall, therefore be so designed and constructed
that they operate satisfactorily and without any deleterious effect for prolonged
and continuous periods in the conditions stated above and at the following
ambient temperature conditions:
a. Maximum sun radiation temperature in summer - 84 ºC
A. Notwithstanding the drawings and other information provided to the contractor, the
contractor shall be fully responsible for the final design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The contractor indemnifies the Employer
and Design Consultant from all claims, costs and expenses arising from any loss or
damage in connection with any error in or failure of the contractor’s designed portion of
the Works.
1. Fire alarm and voice evacuation system
2. Security systems
3. Lighting control system
4. Lightning Protection System and Risk Assessment.
5. Information Communication & Technology (ICT) Systems.
6. Energy Metering and Monitoring System.
B. Single-Source Responsibility:
1. Ensure that each category of selected material or equipment shall be of a
particular range of one manufacturer who would take full responsibility of the
product.
C. Certificate of Origin:
1. Provide certificate of origin along with the packing list on delivery of material and
equipment.
A. Electrical contractor executing this work shall be to the classifications required by ADDC
and shall carry a valid license. Electrical Contractor shall have minimum 10 years
experience in the installation of similar size and complexity systems.
C. Prior to the commencement of work, the Contractor shall notify of his intended site
staffing levels.
D. Contractor shall appoint minimum three Graduate Electrical Engineers for the site work,
(at least one of them with a certified Engineer license form ADDC) with minimum 15
years experience in similar installations.
E. The name, qualifications and experience of the nominated engineers shall be submitted
to the Engineer for approval within 15 days of the receipt of the order to commence the
works.
G. Qualified and Experienced Electricians shall be available on site to carry out the works
in accordance with the Project program. Cable jointers and terminators engaged on site
shall be certified by ADDC.
B. Progress Drawings
1. The contractor shall provide one full set of shop drawings and keep it at the job
throughout the construction period for purpose of recording any changes whether
additions, deletions or relocation resulting thereof from any co-ordination VO’s,
KEO/21-7387-0004 26 0500 / 7 Common Requirements For Electrical Installations
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
RFI’s and/or site instructions. This set of drawings will be the basis upon which
the contractor will prepare the As-built Drawings.
C. As-built Drawings
1. Upon completion of each facility under this contract, the contractor shall prepare
and furnish as-built drawings. The as-built drawings shall be a record of the
construction as installed and completed by the contractor. They shall include all
the information shown on the contract set of drawings and all other related
drawings, modifications, or changes from those drawings, however minor, which
were incorporated in the work, including all additional work not appearing on the
contract drawings, and all changes that are made after any final inspection of the
contract work. In the event the contractor performed additional work, which
changes the as-built conditions of the facility after submission of the final as-built
drawings, the contractor shall furnish revised and/or additional drawings and
drawing files as required to support final as-built condition.
2. The contractor shall certify and label all systems at the completion of the
installation project, and after any modifications are made to an existing system.
All labeling shall be plastic or metal tags that will withstand fading and/or
corrosion. Labels shall be white, ¾” high by length suitable to have address
printed with ½” black lettering. All labels shall be mechanically fastened to
surface adjacent to device with stainless steel screws or pop rivets. Glue or
plastic strip labels neither shall be used nor will it be accepted.
A. Provide warning signs, as well as prohibitions mandatory and safety signs for giving
safety information in accordance with BS 5378 Part 1: 1980and identify materials and
equipment and circuits so marked for easy recognition in a durable and lasting manner
as required by the BS7671: 2008 Requirements for Electrical Installations.
B. The Contractor shall certify and label all systems at the completion of the installation
project. All labeling shall be plastic or metal tags that will withstand fading and/or
corrosion. Labels shall be white, suitable to be printed with black lettering. All labels
shall be mechanically fastened to surface adjacent to device with stainless steel screws
or pop rivets. Glue or plastic strip labels neither shall be used nor will be accepted.
1.11 TESTING
A. General
1. The manufacturers’ technical representative shall supervise testing and
commissioning of equipment and services of a specialized nature. A visual
inspection of the installation should be made to ensure all equipment and
materials comply with the relevant standards and regulations. A checklist for
initial inspection should include those items indicated in the BS7671:2008
Requirements for Electrical Installations.
2. During erection and/or completion, the electrical installation shall be tested
before it is connected to the power supply. Sequence of test and testing
methods shall be as stipulated in the BS 7671.
3. Testing and commissioning of Electrical Systems and equipment’s shall be done
as per applicable code and standards
PART 2 - PRODUCTS
2.01 GENERAL
B. Prior to placing order for any equipment or material, the contractor shall submit
comprehensive documentation comprising working drawings, catalogues and
descriptive literature of components, maintenance manuals, samples etc. for review and
acceptance.
C. Review and acceptance of the Engineer’s Representative does not relieve the
Contractor from his contractual obligations for deviations from the requirements of the
Contract Documents.
PART 3 - EXECUTION
A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways
penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall
assemblies.
B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or
formed openings are used. Install sleeves during erection of slabs and walls.
C. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
D. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall
assemblies unless openings compatible with fire stop system used are fabricated during
construction of floor or wall.
E. Cut sleeves to length for mounting flush with both surfaces of walls.
G. Size pipe sleeves to provide 6.4-mm annular clear space between sleeve and raceway
or cable, unless indicated otherwise.
H. Seal space outside of sleeves with grout for penetrations of concrete and masonry
1. Promptly pack grout solidly between sleeve and wall so no voids remain. Tool
exposed surfaces smooth; protect grout while curing.
I. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between
sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location
of joint. Comply with requirements in Division 07 Section "Joint Sealants".
B. Use type and number of sealing elements recommended by manufacturer for raceway
or cable material and size. Position raceway or cable in center of sleeve. Assemble
mechanical sleeve seals and install in annular space between raceway or cable and
sleeve. Tighten bolts against pressure plates that cause sealing elements to expand
and make watertight seal.
3.04 FIRESTOPPING
A. Apply fire stopping to penetrations of fire-related floor and wall assemblies for electrical
installations to restore original fire-resistance rating of assembly. Fire stopping materials
and installation requirements are specified in Division 07 Section “Penetration Fire
stopping.
3.05 MAINTENANCE
A. Maintenance Service
1. Furnish complete service and maintenance of the complete electrical system and
components during the construction contract and warranty & maintenance
period. Minimum of 12 months taking over certificate to the client and as
specified in the Warranty and Extra Material List section 26 5910.
2. Contractor shall as precautionary and preventive measures list all anticipated
defects and notify the owner. This shall include the cleaning, adjusting and
maintaining of all equipment.
3. In case of failure of any of the systems included, the contractor shall rectify and
do necessary work. He shall show deep diligence to any defect within 24 hours.
4. The contractor shall rectify all faults observed and repair or replace parts that
served their expected service life. He shall use parts produced by the
manufacturer of the original equipment.
5. The contractor shall maintain in Abu Dhabi an adequate stock of replacement
parts for emergency purpose, and shall have qualified personnel available for the
maintenance work without loss of time.
6. The maintenance work shall not be assigned or transferred to any subcontractor
without the written approval of the Owner.
7. Train and provide periodical instruction to the Owner’s operating/ maintenance
staff according to an approved logical program.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUBMITTALS
A. Validate suitability of the size of cables selected to be used for the selected electric
energy-operating equipment. Refer to the technical tables of the cables available from
the approved manufacturer, with due consideration to the following parameters:
1. Type of cable and wire
2. Ambient conditions
3. Method of installation
4. The disposition of each cable relative to other cables
5. Fault power level
6. Protective device ratings
B. Voltage drop at the final point of utilization shall not exceed as in local power supply
authorities regulation and measured from the main electric service of the installations.
C. Voltage drop and current ratings shall be calculated according to local power supply
Authorities Regulations or BS 7671 and IEE regulation, whichever is more stringent.
E. Cable routes and equipment power ratings indicated on the Project Drawings are for
guidance for tendering purposes. The Contractor shall determine exact cable lengths
from site measurements and calculate cable size from the power ratings of the actual
equipment being proposed. The Contractor shall be responsible for any increase in
costs or design work associated with proposed equipment, which has different electrical
characteristics than the equipment on which the design was based.
F. Cables selected shall be from manufacturers whose product has been in satisfactory
use in similar services and environments. Substantiate with certification.
1.04 COORDINATION
A. Set sleeves in cast-in-place concrete, masonry walls, and other structural components
as they are constructed.
A. ADDC Standard Technical Specification for Electric Works – Cable & Accessories.
B. Cables and wires shall comply with the following standards as appropriate:
1. BS 1442 Galvanized mild steel wire for armouring cables
2. BS 2484 Straight concrete clay ware covers
3. BS 2897 Aluminum strip armour for cables
4. BS 3506 Unplasticised PVC pipe for industrial purposes
5. BS 4066 (IEC 332) Tests on electric cables under fire conditions
6. BS 4660 Unplasticised polyvinyl chloride (UPVC) pipes and plastic
fittings of nominal sizes 100 and 150 for below ground level.
7. BS 5308 Instrumentation cables.
8. BS 5467 (IEC 502) Cables with thermosetting Insulation for electricity supply for
voltages of up to and including 600/1000 V.
9. BS 6004 (IEC 227) PVC insulated cables (non-armoured) for electrical power
10. BS 6007 Rubber insulated cables for electric power and lighting
11. BS 6207 (IEC 245) Mineral insulated cables.
12. BS 6234 Polythene insulation and sheath for cables.
13. BS 6346 PVC insulated cables for electrical supply.
14. BS 6360 (IEC 228) Copper conductors for cables.
15. BS 6500 (IEC 227) Insulated flexible cords.
16. BS 6746 PVC Insulation and sheath of electric cables
17. BS 6746C Colour chart for insulation and sheath of electric cables
18. BS 6899 Rubber insulation and sheath of electric cables
19. BS 7671 Requirements for electrical installations
20. ISO 9000 Quality management and assurance standards.
21. BS EN 29453 Soft solder alloys-chemical composition and forms
B All components and their installations shall be free from defects. Any defective
material or workmanship and any resulting damage to work of other trades shall be
replaced or repaired as directed during the Warranty Period at the contactors
expense. Comply with General Conditions, agreeing to repair or replace any
components that have failed within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. The Contractor shall be aware of the need to supply and install all wire and cables for
this Contract, which are most suitable for the special environmental conditions prevailing
in country.
B. All conductors shall have good fatigue resistance and not be subject to breaks due to
nicks or cuts when terminating.
2.03 CABLES
A. Unless otherwise specified, cables and wires of the following specified voltage ratings
shall be used as indicated.
KEO/21-7387-0004 26 0519 / 3 Low Voltage Electrical Power Conductors And Cables
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
1. 600/1000 V rated cables: Main and sub-main distribution panels, motor control
centres, circuits serving process equipment
2. 450/750 V rated cables: Final sub-circuit supplies for lighting, socket outlets, etc.
3. 300/500 V rated cables: Instrumentation
4. 250 V rated cables: Extra low voltage wiring, communication circuits where the
maximum voltage is 50 V.
B. General:
1. Conductors shall be high conductivity copper, to BS EN 60228 unless otherwise
indicated.
2. Copper conductors shall be stranded Class 2 for sections 2.5mm2 and over.
3. Signal control cables shall have solid conductors.
4. Flexible cords shall have fine stranded Class 5 conductors.
5. Conductor’s sizes shall be metric. Conductors with cross sectional areas smaller
than those specified will not be accepted.
6. The current carrying capacity of conductors has been determined in accordance
with the specified regulations, the specified type of insulation and the expected
conditions of installation. No change will be accepted in the specified type of
insulation, unless warranted by special conditions and approved by the Engineer.
7. Insulation for each conductor shall be colour coded or otherwise identified as
required by the regulations. Colour coding shall be maintained throughout the
installation.
8. All wiring from the light fittings to light points shall be by heat resistant cable.
9. All wiring from hard wired equipment from spur outlets including FCUs and
kitchen equipment shall be wired with heat resistant cable.
10. Cables selected shall be from manufacturers whose product has been in
satisfactory use in similar services and environments. Substantiate with
certification.
11. Sub-main cables shall be XLPE/SWA/PVC type whilst final circuits shall
generally be PVC sheathed single core cables in trunking and conduits.
12. All cables that are required for life safety systems shall be fire proof. Fire rating
shall be 2 hours at 750 degree C or local Civil Defence requirements, whichever
is the most onerous.
13. Fire rated cables shall be used for all equipment related to life safety including
but not limited to the following.
a. Fire detection and alarm systems, as applicable
14. XLPE/SWA/PVC cables shall be used for underground applications.
15. All electrical cables should be FM global group 1, UL 910 plenum rated or flame
spread which doesn’t exceed 1.5 m when tested in accordance with NFPA 262.
G. Flexible Cable:
1. To BS 6007, and BS 6500, rated in accordance with manufacturer’s tables.
Flexible cables subject to excessive heat shall be insulated.
L. Cable Glands
1. Cable glands shall be used for terminating cables to switch gear, switch boards,
motor control centres, motors and other equipment
2. They shall be brass compression glands and comply with the relevant part of BS
6121, except for MICC cables, which shall comply with BS 6207 Part 2.
3. Glands for armoured or screened cables shall have suitable clamps
4. External compression glands shall have close fitting PVC shrouds
5. earthing for armouring and metallic sheaths: suitable brass or copper clamps,
and copper strip conductor in accordance with local power authority
requirements, and not less than 2.5 sq. mm
N. Cleats: shall be approved claw type cast aluminium, gunmetal, plastic or brass of
approved type, two bolts fixing for cables greater than 50 mm diameter.
O. Cable Markers:
1. Shall be precast concrete, minimum size 300 x 300 mm x 100 mm deep
2. The markers shall be engraved “HV CABLE”, “ELECTRIC CABLE”, “ELV
CABLE”, “EARTH PIT” or “CABLE JOINT”, as applicable cable marker
construction details and engravings shall be as per local power authority
regulations.
PART 3 - EXECUTION
3.01 GENERAL
A. Installing cables:
B. Bending Radius: as large as possible and cable shall not to bend to a radius less than
that specified in the relevant British Standard, local power authority regulations or
manufacturer’s recommendation, whichever is largest.
G. Cable Supports:
1. Cables shall be supported in accordance with the methods described in table 4A
of BS 7671. Other methods shall be approved
2. Cables shall be supported at regular intervals and at spacing a maximum of 400
mm for cleats for horizontal runs and 550 mm for vertical runs
3. Vertical cable runs exceeding 100 m shall incorporate tension releasing sections
steel cable supports shall be provided at 300 mm intervals
4. MICC Cables:
a. Run on surface of walls ceilings. Where embedded, run in a PVC trough
or conduit
b. Run cables in square symmetrical lines. Where single core cables are run
in groups, bend the sheaths at maximum 50 mm centers
c. Fix surface run cables with saddles at maximum 300 mm centers.
I. Flexible Cables:
1. Flexible cable shall be kept to a minimum and concealed if possible
2. Mechanical retainment shall not depend on electrical connections.
J. Sealing Cables:
1. Seal both ends of cables immediately after tests
2. Seal MICC cables immediately after cutting to prevent hygroscopic action by the
dielectric. All cables shall give an infinity test when tested on a 1000 volt Megger
immediately, and 48 hours after sealing
3. Seal aluminum sheathed cables with a metal cap plumbed to the sheath
4. Seal plastic sheathed cables with a plastic cap embracing the wires and outer
sheath
5. Mark cable ends in accordance with the relevant BS.
A. Generally:
1. Install cables on trays in a single layer, unless otherwise specified
2. Use purpose made straps or saddles to maintain cables in a neat regular
disposition
3. Secure cables with load bearing cleats securely fixed to the tray, where trays do
not directly support the cables
4. Space cleats, saddles and straps at maximum centres shall be as recommended
by cable manufacturers.
3.03 FIRESTOPPING
A. Apply fire stopping to electrical penetrations of fire-rated floor and wall assemblies to
restore original fire-resistance rating of assembly according to Division 07 Section
"Penetration Fire stopping."
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section to include methods and materials for grounding systems and equipment
and accessories work in accordance with the Project Documentation.
1. Earth Continuity Conductors
2. Main Earth Loops
3. Rod Electrodes
4. Earth Pit Covers
1.02 SUBMITTALS
B. Comply with BS 7671 for grounding and bonding materials and equipment.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 MATERIALS
A. General
1. Products used in the earthing system shall be copper or an approved copper
alloy, unless otherwise specified, and specifically manufactured for the purpose.
D. Rod Electrodes
1. Shall be the earth rod electrode type, unless impracticable to drive deep into the
particular soil.
2. Earth rod electrodes: Minimum 19 mm diameter (16 mm for communication
earth) steel core copper jacketed type, comprising a high strength steel alloy core
with a molten welded copper covering.
3. Earth rod electrode length shall be as per local Electrical Power Authority
regulations, in 1.2m sections coupled by strong bronze couplers.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Circuit Wiring
1. Shall have a green/yellow coloured insulated earth continuity cable connecting
the earth bus or earth terminal in switchboards, switchgears, motor control
centres and panel boards to the motor, equipment, outlet and other device by
earthing lugs. All hand rails and other metal works within 2 m of a potentially live
metal surface shall be earthed.
E. Bolted Connections
1. Multiple bolt type.
2. Where bare copper has bolted in connections contact surfaces shall be silver
electroplated.
F. Brazed Connections
1. Where earthing terminal connections are to be brazed to equipment, thoroughly
clean metal prior to brazing and repaint impaired surfaces to prevent corrosion.
H. Equipment Earthing
1. Connect all non-current carrying metallic parts of the electrical/mechanical
installation to the earthing system.
2. Non-current carrying metallic parts of the electrical installation include:
a. Metal conduit cable armor (steel and aluminum) raceways, outlet boxes,
cabinets, and the like.
b. Exposed metal parts of apparatus.
c. Enclosures, doors, grilles, barriers and the like protecting or shielding
electrical equipment from direct access.
3. Series earthing of one piece of equipment to another is not acceptable. Each
item shall be individually connected the earthing system.
K. Motors Earthing
1. Connect the motor terminal box to the relative earth loop. The terminal must be
mechanically connected to the frame or, where this is not feasible
2. Extend the earthing conductor through an insulated bushed opening in the
connection box and connect to the frame.
3.02 TESTING
B. The resistance of any point in the earth continuity system to the main earth electrode
shall not exceed 1 ohm, unless as approved otherwise by local Electrical Power
Authority.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
C. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads
calculated or imposed for this project, with a minimum structural safety factor of five
times the applied force.
1.03 SUBMITTALS
B. Shop Drawings: Show fabrication and installation details and include calculations for the
following:
1. Trapeze hangers. Include Product Data for components.
2. Steel slotted channel systems. Include Product Data for components.
3. Nonmetallic slotted channel systems. Include Product Data for components.
4. Equipment supports.
C. Welding certificates.
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
D. Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings,
designed for types and sizes of raceway or cable to be supported.
F. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel
plates, shapes, and bars; black and galvanized.
G. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items
or their supports to building surfaces include the following:
1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened Portland
cement concrete, steel, or wood, with tension, shear, and pullout capacities
appropriate for supported loads and building materials where used.
2. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated steel, for use in
hardened Portland cement concrete with tension, shear, and pullout capacities
appropriate for supported loads and building materials in which used.
3. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to
MSS Type 18; complying with MFMA-4 or MSS SP-58.
4. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable
for attached structural element.
5. Through Bolts: Structural type, hex head, and high strength. Comply with
ASTM A 325.
6. Toggle Bolts: All-steel springhead type.
7. Hanger Rods: Threaded steel.
H. All support systems for life safety rated cabling shall be sized in accordance with NFPA
70 & 101.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Where specific fasteners are not specified or indicated for securing items to in-place
construction, provide appropriate type, size, and number of fasteners for a secure, rigid
installation.
B. Install anchoring devices and other fasteners in accordance with manufacturer’s printed
instructions.
3.02 APPLICATION
B. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted
or other support system, sized so capacity can be increased by at least 25 percent in
future without exceeding specified design load limits.
C. Spring-steel clamps designed for supporting single conduits without bolts may be used
for 38-mm and smaller raceways serving branch circuits and communication systems
above suspended ceilings and for fastening raceways to trapeze supports.
C. Drill holes for expansion anchors in concrete at locations and to depths that avoid
reinforcing bars.
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
elevation to support and anchor electrical materials and equipment.
3.05 PAINTING
B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
galvanizing-repair paint to comply with ASTM A 780.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section to include the supply, installation and commissioning of all conduit works in
accordance with the Project Documentation.
1. Rigid PVC conduit and fittings
2. Rigid Steel conduit and fittings
3. Flexible Steel conduit and fittings
4. Hinged cover enclosures and cabinets
5. Cable Trunking
1.02 SUBMITTALS
A. Samples: Cut-away samples of all sizes of conduits, conduit boxes and fittings of each
type fixed to a board and submitted.
B. Product Data: When submitting samples submit manufacturer’s details, catalogues and
copies of test certificates confirming that offered types comply with the Specification.
C. Shop Drawings: Submit drawings of proposed conduit layouts and obtain approval
before commencing work.
E. Shop Drawings: For the following raceway components. Include plans, elevations,
sections, details, and attachments to other work:
1. Custom enclosures and cabinets.
2. For handholes and boxes for underground writing, including the following:
a. Duct entry provisions, including locations and duct sizes.
b. Frame and cover design.
c. Grounding details.
d. Dimensioned locations of cable racks inserts, and pulling-in and lifting
irons.
e. Joint details.
F. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following
items are shown and coordinated with each other, based on input from installers of the
items involves:
1. Structural members in the paths of conduit groups with common supports.
2. HVAC and plumbing items and architectural features in the paths of conduit
groups with common supports.
KEO/21-7387-0004 26 0533 / 1 Raceway And Boxes For Electrical Systems
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
G. Qualification Data: For professional engineer and testing agency.
B. Conform to the related latest BS for metallic and non-metallic conduits and accessories
stipulated in this Section.
C. Coordinate layout and installation of raceway and boxes with other construction
elements to ensure adequate headroom, working clearance, and access.
A. All electrical installations shall be carried out in accordance with the best International
Standards and Codes of Practice specifically with the current issue of IEE Regulations
(BS 7671) and the requirements of the local electrical power supply authority.
C. Listed below are the standards and codes referred to in this section.
1. BS 31 Steel conduit and fittings for electrical wiring.
2. BS 731 Flexible steel conduits and adapters for the protection of
electric cable.
3. BS 2782 Methods of testing plastics.
4. BS 4568 Specification for steel conduit and fittings with metric
threads of ISO form for electrical installations. Steel conduit,
bends and couplers.
5. BS 4607/ IEC 61386Non-metallic conduits and fittings for electrical installations
rigid PVC conduits and conduit fittings.
6. BS EN 50086 Specification for conduit systems for electrical installations.
7. BS EN 60423 Conduits for electrical purposes. Outside diameters of
conduits for electrical installations and threads for conduits
and fittings
8. BS EN 50085-1:2005 Cable Trunking
9. BS EN 10327:2004 Continuously Hot-Dip Strip and Sheet of low carbon steels
for cold forming
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 GENERAL
A. Light and power circuits, fire alarm, telephone, signal and other low current system
wiring shall be drawn in conduits unless otherwise indicated
C. Light and power circuits, fire alarm wiring, telephone wiring, signal wiring and low
current system wiring shall each be run in separate conduit and wire way.
A. Standards:
1. Conduit and fittings shall comply with BS 4607: Part 1 & 2 and CEE Publication
26. In addition, conduit and fittings shall comply with this specification where
requirements are more stringent.
B. Physical Properties:
1. Conduit and fittings shall be:
a. Resistant to high temperatures
b. Non-hygroscopic
c. Self-extinguishing
d. Of adequate insulation resistance and electric strength
e. Inert to all liquid normally discharged from residential, commercial and
industrial premises
3. Fittings:
a. Conduit entries shall be designed to ensure a watertight joint.
4. Expansion fittings:
a. Provide fittings that provide expansion and contraction for at least 0.06
mm per meter of length of straight run per degree of temperature change.
b. Provide expansion fittings for each of the following locations and provide
type and quantity of fittings that accommodate temperature changes listed
below:
1) Outdoor locations not exposed to direct sunlight: 70°C, 5°C
temperature change.
2) Outdoor locations exposed to direct sunlight: 86°C, 5°C
temperature change.
3) Indoor spaces: 70°C, 5°C temperature change.
5. PVC Conduit Boxes:
a. PVC Conduit Boxes can be used through PVC Conduit raceway system
and shall comply with BS 4607
b. metallic conduit boxes as specified elsewhere in this section can be used
alternatively if required for PVC conduit raceway system
c. all boxes shall be provided with tapped brass inserts for fixing the screws
d. all boxes for switches, sockets, outlets, etc., shall be rigid PVC or metallic
type and their dimensions shall be suitable for fixing the switches, sockets
and other accessories.
3. Conduits and fittings shall be manufactured specially for electric wiring purposes.
When manufactured by a continuous weld process, weld heads both inside and
outside the tube shall be completely removed prior to galvanizing
4. All conduits and fittings shall be free from rust or other defects on delivery to the
site and shall be properly stored in covered racking so that it is protected from
mechanical damage and damage by weather and water whilst stored on the site
5. All conduits shall be coupled to boxes and trunking wires using brass male
bushes. All such bushes shall be hexagon headed, heavy duty long threaded
type
6. All conduit expansion couplings used shall be fabricated from material equal or
equivalent to that of the conduit with which the coupling is to be used, having
factory installed packing ring and pressure ring to prevent entrance of moisture.
All coupling shall be equipped with earthing ring or earthing conductor
7. All conduit runs shall be fixed using spacer bar pattern saddles giving not less
than 3 mm clearance between the conduit and the surface to which it is fixed.
Saddles shall have finish to match the conduit and saddle clips shall be secured
to the bar by means of brass screws.
A. Flexible Conduit:
1. To BS 731, Part 1, watertight, PVC sheathed, spiraled metal type. The conduit
shall be terminated at boxes and equipment by means of approved compression
glands
2. To be of the unpacked type for normal atmospheric conditions and non-asbestos
packaged for damp situations. Adapters shall be of the solid type
3. Flexible conduit shall be used for the final connection of rigid conduit to the
terminal boxes of machines fitted with a means of drive adjustment and/or where
vibrations is likely to occur.
4. Length of flexible conduit for recessed and semi-recessed light fixtures shall be
maximum 1.5 meters.
B. Flexible Connections:
1. Where connections to electrical machines are to be by multicore glands, the final
termination shall be by ring type universal glands and locknuts, and adequate
slack cable in the form of a loop or spiral being left to allow for the movement of
motors necessitated by belt re-tensioning, vibration, etc.
A. Design
1. Surface-mounted or free-standing type, fabricated from zinc coated or galvanized
sheet steel minimum 1.5mm thick, Paint finish as approved for distribution
boards.
2. Fixed cover and padlocked hinged door; operable without obstruction.
3. Protected IP-31 for internal and IP-65 for outdoor use.
A. Steel Trunking and Accessories: Factory made BS 4678: Part 1, from minimum 16 SWG
sheet steel to BS EN 10327: 2004, with 15 microns zinc coating.
B. Trunking Covers: Manufacture to fit firmly on the body. Design of covers and fixings
shall prevent wires entangling on them. Covers shall be attached and removed from
trunking with simple tools.
E. Provide separation barrier between low voltage and line voltage cable compartment.
G. Cable Support Fixings: Projecting pin type with heat shrunk sleeve.
PART 3 - EXECUTION
3.01 PREPARATION
A. General
1. Run conduit in square, symmetrical lines, parallel to or at right angles to walls
and in accordance with the accepted practice
2. Conduit system shall be mechanically continuous and watertight after installation.
All conduit system shall be arranged wherever possible to be self draining
3. Conduit runs between draw-in positions shall conform to local Regulations
regarding number of bends and extent of straight run
4. Conduit fill shall generally be less than 45%.
5. Keep conduits at least 100 mm from pipes and other non-electrical services
6. Where conduit runs are to be concealed in the structure or are to pass through
floor slabs, the Contractor shall be responsible for marking the accurate positions
of all chases and holes on site. The Contractor shall arrange the conduit routing
to make maximum use of any preformed conduit holes and slots provided in
structural beams. Conduit installation on shear walls shall be kept to a minimum.
All routings necessary on shear walls shall be agreed with the Engineer’s
Representative before work is put in hand
7. Install conduits so as not to interfere with ceiling inserts, lights or ventilation
outlets.
8. Earth continuity of steel conduits shall be mechanically & electrically continuous
throughout.
9. Provide pull wire in all empty conduits.
E. Concealed Conduit:
1. Fix securely to prevent movement before casting of concrete and screeds,
application of plaster and the like
2. Spacing of clips shall be not greater than as follows:
F. Expansion Fittings:
1. Fix in conduit wherever it crosses as expansion joint in the structure to which it is
fixed.
G. Terminations:
1. Make with a flanged coupling, lead washer and hexagonal male brass bush,
where conduit runs terminate in cable trunking, distribution boards or any sheet
metal structure.
H. Conduit Boxes:
1. Fix at all outlet points.
A. All conduits must be secured to outlet boxes, junction boxes or cabinets by placing
locknuts on outside of box and locknuts and bushings on the inside of box.
B. Conduits connecting recessed fixtures and their adjacent junction boxes must be flexible
metallic conduit 20 mm minimum size and shall be of sufficient length to permit dropping
of the fixture below the ceiling and to gain access to the junction box.
C. Conduit to motors shall be terminated in the conduit fittings on the motors, the final
connection being made with liquid tight flexible conduit and suitable liquid tight
connectors.
D. A green insulated 4 mm2 (minimum) tinned copper earth connection shall be made
between the solid conduit or cable sheath and the equipment, the copper cable being
run inside the flexible conduit. Couplings fitted to removable covers or non-metallic
equipment etc. shall be bonded to the earthing terminal of the equipment etc. Where
changes to flexible conduits occur, a watertight outlet box with threaded entries shall be
inserted and the earth connection made to an internal terminal. The cover screws shall
not be used for earthing connections.
A. Anchor enclosures and cabinets securely to wall and structural supports at each corner.
B. Support trunking at 1.0m intervals with trapeze type hangers or wall brackets.
D. Support cables in vertical runs with pin-type supports at maximum 15m centers.
E. On vertical runs exceeding 6m support cable with projecting pin-type supports with heat
shrunk sleeve fixed to trunking body by welding or pop riveting.
F. Make connections to accessories with pop riveted or welded joints. Radius or gusset
bends and tees.
H. Fire-stop cable trunking at floor slabs and at fire walls by packing inside the trunking
with mineral wool.
I. Provide galvanized draw wire in every trunking conduit which is left for wires and cables.
Not less than 300mm slack shall be left at each end of the draw wire.
3.06 FIRESTOPPING
A. Install conduits sealing where they enter or leave hazardous locations. Provide fire
stopping at fire compartment areas. Locate fittings at suitable, approved, accessible
locations and fill them with approved sealing compound.
B. Fire stopping materials and installation requirements are specified in Division 07 Section
“Fire stopping.”
3.07 CLEANING
A. The conduit outlets when installed and before wiring shall be temporarily closed by
means of well-fitting wooden plugs, and immediately before cables are drawn in,
conduits systems shall be thoroughly swabbed out until they are dry and clean.
B. Upon completion of installation of system, including outlet fittings & devices, inspect
exposed finish, remove burrs, dirt & construction debris and repair damages finish
including chips, scratches & abrasions.
3.08 PROTECTION
C. Repair damage to PVC or paint finishes with matching touch up coatings per
manufacturer’s recommendations.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section to include the supply, installation and commissioning of Cable trays,
Ladder racks, Wire basket cable Trays and accessories work in accordance with the
Project Documentation.
1. Cable trays and accessories
2. Ladder racks and accessories
3. Cable Basket Tray.
1.02 SUBMITTALS
A. Product Data: Include data indicating dimensions and finishes for each type of cable
tray/ ladder racks indicated.
C. Coordination Drawings: Floor plans and sections, drawn to scale. Include scaled cable
tray/ ladder racks layout and relationships between components and adjacent structural,
electrical, and mechanical elements. Show the following:
1. Vertical and horizontal offsets and transitions.
2. Clearances for access above and to side of cable trays/ ladder racks.
3. Vertical elevation of cable trays/ ladder racks above the floor or bottom of ceiling
structure.
B. Source Limitations: Obtain cable tray components through one source from a single
manufacturer.
A. Store indoors to prevent water or other foreign materials from staining or adhering to
cable tray/ ladder racks. Unpack and dry wet materials before storage.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 GENERAL
A. The cable tray system shall be of one manufacturer and shall include factory-made
trays, tray fittings, connectors and necessary accessories and supports to form a
complete cable support system.
B. The cable tray system shall include the following factory-made tray elements:
C. Manufacturer’s standard accessories shall be used and site fabrication shall not be
permitted.
D. Horizontal run of cables laid on cable tray and exposed to direct sunlight shall be
provided with covering at higher level to allow for ventilation. Cable tray shall be raised
15 cm from finished floor level.
E. Determine the sizes of the cable trays based on the number and size of cables laid on
the cable trays plus 20% space for future growth. Cables laid on cable trays shall be
spaced twice their overall diameter (consider the largest cable as reference). In case of
discrepancy with the contract documents this clause shall prevail, unless approved.
A. Cable Trays:
1. The cable tray material shall be hot rolled steel sheet to
EN 10025-2:2004. The whole of the tray work, trays, fittings, and supports shall be
of mild steel hot dipped galvanized after manufacture to
BS EN ISO 1461:1999. The thickness of the protective sheath on any element
shall not be less than 55 microns.
2. Tray shall be of heavy duty formed from heavy gauge steel plates. The material
for the cable tray shall be electro galvanized steel to EN10152.
3. Insert elements, bolts, screws, pins, etc., shall be mild steel cadmium plated.
4. Tray work shall have oval perforations.
5. All trays (straight and fittings) shall be welded construction and be a heavy duty
returned flanged, perforated type, unless specified otherwise. The minimum
thickness of heavy duty returned flanged cable trays shall be 1.5mm for trays up
to 300mm wide and 2.0mm for trays up to 600mm wide.
6. Tray components shall be accurately rolled or formed to close tolerances and all
edges rounded. Flanges shall have full round smooth edges.
7. For all trays, flanges shall be a minimum of 50 mm deep, unless otherwise
specified.
8. Cable tray width and radius of curved sections shall be selected to suit the
number of cables as shown on drawings and to the approval of the Engineer.
9. Cable trays and accessories installed in hazardous and extremely corrosive
environments shall be heavy duty GRP or 316 S31 grade stainless steel.
A. Fittings: Tees, crosses, risers, elbows, and other fittings as indicated, of same materials
and finishes as cable tray.
KEO/21-7387-0004 26 0536 / 3 Cable Trays For Electrical Systems
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
B. Covers: Same materials and finishes as cable tray.
E. Cable tray mounted externally on roofs and exposed area shall be provided with heavy
duty sunshields made of electro galvanized steel. The sunshields shall be arranged to
allow adequate ventilation of the cables on the tray. All equipment and accessories shall
be manufactured to withstand ambient temperature of 50 degree C.
A. Ladder rack shall be supplied and installed in the locations indicated on the drawings.
B. The cable ladder system shall be based on two longitudinal outward facing side
members with returned edge flanges to improve safety during handling, installation and
cable pulling activities. The longitudinal side members shall form the main structural
elements of the cable ladder system and shall be longitudinally ribbed for enhanced
stiffness and rigidity.
C. The profile of the side members shall remain constant for the straight cable ladder and
the cable ladder fittings.
D. The longitudinal side members shall have a height of 125mm and a flange width of
25mm.
G. The transverse members shall be evenly spaced at 300mm centers along the length of
the straight cable ladder.
I. Cable trays shall be chamfered at all changes of direction to prevent cable damage both
during and after installation.
K. The couplers shall be profiled to match the profile of the cable ladder. The couplers shall
be secured using M10 square-shouldered bolts with rounded heads. The bolts shall be
secured with M10 hex nuts and M10 shake-proof washers as standard. The couplers
shall have a slot pattern which prevents slip between adjacent straight ladder lengths
and between cable ladder fittings. The couplers shall have a slot pattern which allows
for easy connection to cut lengths of straight cable ladder without the need for onsite
drilling.
PART 3 - EXECUTION
A. Install as a complete system, including all necessary fasteners, hold-down clips, splice-
plate support systems, barrier strips, hinged horizontal and vertical splice plates,
elbows, reducers, tees, and crosses.
B. Remove burrs and sharp edges from cable trays/ ladder rack.
D. Labelling should be supplied to cable trays at every change in tray direction and
intervals of no more than 10m. Labelling should also be supplied to sub-main cabling
detailing both the source of supply and final termination.
E. Make connections to equipment with flanged fittings fastened to cable tray/ ladder rack
and to equipment. Support cable tray/ ladder rack independent of fittings. Do not carry
weight of cable tray/ ladder rack on equipment enclosure.
F. Install expansion connectors where cable tray/ ladder rack crosses building expansion
joint. Space connectors and set gaps according to applicable standard.
I. Seal penetrations through fire and smoke barriers according to Division 07 Section "Fire
stopping."
J. Sleeves for Future Cables [where required]: Install capped sleeves for future cables
through firestop-sealed cable tray/ ladder rack penetrations of fire and smoke barriers.
K. Workspace: Install cable trays/ ladder rack with enough space to permit access for
installing cables.
L. After installation of cable trays/ ladder rack is completed, install warning signs in visible
locations on or near cable trays/ ladder racks.
B. Fasten cables on horizontal runs with cable clamps or cable ties. Tighten clamps only
enough to secure the cable, without indenting the cable jacket.
C. Metal cable ties shall be installed on all vertical inverted trays and ladders.
D. On vertical runs, fasten cables to tray every 450 mm. Install intermediate supports
when cable weight exceeds the load-carrying capacity of the tray/ rungs.
3.03 EARTHING
A. Cable trays/ ladder rack and accessories shall be electrically and mechanically
continuous throughout their length.
B. All cable trays/ ladder rack shall be bonded by flexible earth copper links in order to
provide bonding to the earth for all the metallic cable tray ladder installation.
A. After installing cable trays/ ladder racks and after electrical circuitry has been energized,
survey for compliance with requirements. Perform the following field quality-control
survey:
1. Visually inspect cable insulation for damage. Correct sharp corners,
protuberances in cable tray/ ladder rack, vibration, and thermal expansion and
contraction conditions, which may cause or have caused damage.
2. Verify that there is no intrusion of such items as pipe, hangers, or other
equipment that could damage cables.
3. Remove deposits of dust, industrial process materials, trash of any description,
and any blockage of tray/ ladder rack ventilation.
4. Visually inspect each cable tray/ ladder rack joint and each ground connection for
mechanical continuity. Check bolted connections between sections for corrosion.
Clean and retorque in suspect areas.
5. Check for missing or damaged bolts, bolt heads, or nuts. When found, replace
with specified hardware.
6. Perform visual and mechanical checks for adequacy of cable tray/ ladder rack
earthing; verify that all takeoff raceways are bonded to cable tray/ ladder rack.
3.05 PROTECTION
3.06 FIRESTOPPING
A. Install sealing fittings wherever cable trays/ ladder racks enter or leave hazardous
locations. Provide fire stopping at fire compartment areas. Locate fittings at suitable,
approved, accessible locations and fill them with approved sealing compound.
B. Fire stopping materials and installation requirements are specified in Division 07 Section
"Fire stopping."
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUBMITTALS
C. Samples: For each type of label and sign to illustrate size, colors, lettering style,
mounting provisions, and graphic features of identification products.
B. Installers Qualifications: Firm with at least 3 years of installation experience with projects
utilizing electrical identification work similar to that required for this project.
D. IEC Compliance: Comply with IEC 113 and 117 as applicable to electrical equipment
identification.
1.04 COORDINATION
C. Coordinate installation of identifying devices with location of access panels and doors.
D. Install identifying devices before installing acoustical ceilings and similar concealment.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
PART 3 - EXECUTION
G. Install signs at locations indicated or, where not otherwise indicated, a location for best
convenience of viewing without interference with operation and maintenance of
equipment. Secure to substrate with fasteners, except use adhesive where fasteners
should not or cannot penetrate substrate.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section forms part of every section of Division 25 for integrated automation
Systems, Division 26 for Electrical, Division 27 for Communication, Division 28 for
Electronic Safety system.
A. This section shall be read in conjunction with all sections of electrical specifications as
applicable.
A. Prior to acceptance, inspect, operate and test all electrical equipment, materials and
components, whether such tests are detailed in this specification or not. Tests will be
witnessed by THE CONSULTANT/EMPLOYER, to ensure that the operation of the
systems and components satisfies the requirements of the Contract Documents.
B. Include any specific testing required by the Authorities, or any other body having
jurisdiction over the installation, and as directed by THE CONSULTANT/EMPLOYER.
C. Provide all tools, equipment, labour and materials required to perform the electrical
testing. Provide three copies of the test reports to THE CONSULTANT/EMPLOYER.
F. Test in accordance with the applicable standards issued by the governing organizations
(e.g. IEC, UL, NFPA, IEE), and with the recommendations of the manufacturers.
H. The Contractor shall provide such assistance, labour, materials, electricity, fuel, stores,
apparatus and instruments as may be requisite and as reasonably deemed necessary to
carry out such tests efficiently.
I. All instruments used for the tests shall have a current calibration certificate available for
inspection at works.
J. If the Contractor fails to demonstrate the performance of the equipment offered, he will
be requested to carry out further tests until the Employer's Agent is fully satisfied that
the equipment offered meets the requirements of the specification at no extra cost to
this contract.
K. Make test records in a neat and legible manner, fully identifying the equipment or
system being tested, type of test equipment, calculation, and expiry date for the same,
the test results and the date of the test. Submit 3 copies to the
CONSULTANT/EMPLOYER at the end of each test.
L. Do not energize distribution or control equipment until the test results have been
reviewed, passed and approved by the CONSULTANT/EMPLOYER.
M. Ensure that phasing and phase rotation is the same throughout the system. Ensure that
all devices are wired for the same polarity.
N. Test all electrical systems and installation in accordance to the related standards and in
accordance to the equipment manufacturers testing procedure.
O. Carryout all tests in accordance to an approved procedure by the CONSULTANT and all
necessary data and results which may be requested by the CONSULTANT.
P. The testing and commissioning for electrical system shall cover the following as a
minimum:
1. Off-Site Tests
2. Tests carried out on items of equipment at manufacturer's works or elsewhere to
ensure compliance with the requirements of specifications and/or relevant British
Standards and Codes of Practice.
3. Pre-commissioning Site Tests
4. Tests on equipment and systems to ensure correct and safe installation and
operation in accordance with the applicable standards.
5. Commissioning
6. The process of energizing equipment and systems and setting them to full
working order and verifying the performance to specified requirements under no-
load conditions.
7. Performance Testing
8. The measuring and recording of the performance of the commissioned
installation under load conditions.
9. All the electrical systems, whether mentioned in this section or not, shall be
subject to testing and commissioning.
Q. Method Statements
R. Submittals
1. Required Submissions:
a. Submittals relating to this section shall reference this specification section
number on the submittal transmittal.
b. All documents to be submitted shall comply with the requirements of
Specification.
c. The required submittals specified herein shall be grouped in the following
categories:
1) Programs and Schedules
2) Execution Method Statement
3) Shop/Coordination Drawings
4) Design Data and Calculations
5) Product Lists
6) Samples and Mock-ups
7) Test/Inspection reports & Certificates
8) Catalogues/Manufacturer’s Instructions
9) Project Record Documents
10) Operations and Maintenance Manuals
11) Guaranty and Warranty Certificates
12) Other as necessary – none
A. Contractor to comply with the Estidama Requirements for the commissioning process
planning, execution and documentation with accordance to the Estidama IDP: R3 –
Basic Commissioning and IDP 5: Re-commissioning and as detailed in the Estidama
Design Commissioning Plan Developed by the Project Independent Commissioning
Authority”
B. The testing and commissioning shall be carried out in accordance with contract
requirements, by a firm specializing in this work, under no circumstances shall the
Contractor be allowed to use his own staff or affiliated companies for the Capital plant
such as switchboards, power factor correction equipment, fire alarm system, lighting
control and dimming system, central emergency lighting system, lifts, and specialized
ELV systems including CCTV and security systems etc.
C. The contractor shall submit to the CONSULTANT/EMPLOYER for approval his schedule
of program for the works; the program shall address the following:
1. Planned date of commencement of testing and commissioning.
2. Expected date of completion of testing and commissioning.
3. Power ON date.
4. Fire alarm ON date.
5. Telephone/Data system ‘ON’ date.
6. Actual testing and commissioning date and duration for each system.
D. The contractor shall submit for approval, a detailed method statement for each testing
and commissioning activity as described in section 1.3 above.
G. The original test sheets approved by all parties shall be submitted along with the O&M
Manuals.
1. Voltage within correct tolerances in accordance with the contract documents.
2. Power factor and harmonics in accordance with the Contract Documents.
3. Earthing in accordance with the contract Documents.
4. Illumination levels in accordance with the Contract Documents.
5. Correct control of all plant.
6. Structured cabling of telephone and data communication system
7. Fire alarm system.
8. Correct functioning of the following specialist systems and their integration:
a. Lighting Control system
b. IT system
c. Fire Alarm and voice evacuation system
H. An audit inspection at factory before dispatch and at site after receipt of the switchgear
for any manufacturing / transit defects.
B. Once the procedures are agreed up on, the Inspection and testing reports for the above
systems shall be submitted for CONSULTANT/EMPLOYER review/approval.
C. The following inspections have to be carried out for any manufacturing defects/ transit
damages and inform the supplier immediately if found any defects
D. Manufacturing Defects:
1. Inspect the doors of cubicles for proper opening/closing including door
inter locks.
2. Ensure the bus bar supports and insulation is free from cracks and damages.
3. Ensure that the correct rating of the components such as fuses, contactors and
over load relays are as per the approved drawings.
4. Ensure that the physical condition of all meters, protection relays are good and
ranges are as per approved layouts.
5. Ensure all components are properly installed including CTs.
6. Ensure the overall dimension and colour of the cubicle is as per approved layout.
E. Transit Damages
1. Inspect the external surface of the cubicle for any transit damages and paint
scratches.
2. Inspect that batteries and chargers are not damaged during transit.
3. The following pre-requisites have to be ensured before pre-commissioning /
commissioning of the respective panels:
a. Colour coding / ferruling
b. Tightening all bus bar joints with torque wrench
c. Tightening of all connections
d. Termination of cables on the panels
e. Interlocks as per approved drawings
f. Inter panel wiring between various cubicles
g. Operation of space heaters
h. Control & power diagram of respective switchgear is readily available on
the panel board for reference
i. No loose tools left inside the panel
j. Availability of first aid / firefighting equipment
2.03 SMDB
B. The contractor shall arrange for the witnessing of the following tests on the fully
equipped switchboard including primary bus bars and connections at the factory, in
accordance with IEC 439-1:
1. High voltage power frequency tests on main and auxiliary circuits
2. Dielectric/insulation resistance tests
3. Ground fault tests
4. Electrical operation of circuit breakers control circuits at the appropriate voltage
limits
5. Mechanical operations tests and tests to certify correct functioning of interlocks.
6. Primary injection tests
7. Secondary injection tests
8. Millivolt drop tests
9. Any other tests required by the CONSULTANT/EMPLOYER
C. The following tests shall be carried out after the equipment has been completely erected
and connected up on site:
1. Power frequency voltage tests on the completed switchgear
2. Insulation resistance tests on all main and secondary circuits
3. Secondary injection tests
4. Calibration checks on ammeters, voltmeters and any other instruments
5. Testing at normal voltage to prove that closing and tripping from local and remote
control points, tripping from relays and protective gear, interlocks, alarm and
indications, etc. are satisfactory.
6. Any other test required to prove compliance with the specification
7. At the end of tests, the protective relays and breaker tripping times shall be set in
accordance with the CONSULTANT/EMPLOYER approved discrimination
coordination.
G. Physical Check
1. Check general arrangements of the components, internal wiring and complete
cleanliness.
2. Check the panel against approved shop drawing to ensure that right components
(ACB, MCCB) of correct ratings are installed.
3. Check the tray riser, cable drops cable overlapping and dressing of cable to
MDB.
4. Check all the bolts / nuts and bus bar connection to ensure that all are in good
and tight condition.
5. Check earth bonding of components and other related connection.
6. Check all meters and selector switches to ensure the correct selection & rating.
7. Check the phase barriers are properly fixed for separation of circuits.
8. Check all cables and panels are properly labeled and identified.
L. Polarity Test
1. Check the polarity of incomer supply by polarity tester before energising panels.
2. Check all fuses/circuit breakers and single pole control devices are connected to
phase conductors only.
M. Overall Performance Test - Check and ensure the satisfactory operation of the boards at
full load.
1. Any other tests as requested by the CONSULTANT/EMPLOYER.
A. Physical Check
1. Check the electrical components such as conduits, wires, trunking, light fixtures,
socket outlets are connected to the final circuit of the distribution board.
2. Check the installation of distribution boards and internal wiring.
3. Check the identification and labelling of each final circuits.
4. Check that all metallic components are earthed/bonded.
5. Check the terminal insulation, cable gland termination and shrouding.
B. Polarity Check
1. Check the polarity of power / light points to ensure the light switches (single pole)
are installed in the line conductor.
2. Check for screw type lamp holders. the outer or screwed conductor is connected
to the neutral conductor.
C. Continuity Check
1. Check the continuity of the protective conductor from the farthest point to main
earth terminal of the DB for each final circuit by means of a DC ohm meter
verifies the values are within permissible limit).
D. Insulation Resistance Test - Check and measure the insulation resistance between
phase, neutral and earth through a 500 Volts, Megger.
1. RCB and Polarity Test
a. Switch on and off all ELCB and MCB and contactor relay to verify for the
desired operation.
b. Check earth leakage circuit breakers by means of ELCB tester.
c. Check the circuit performance by switching on the MCB in the DB.
d. Check the light and power points by operating all the switches connected
in the circuits.
e. Check all the sockets outlets of ring/radial circuits with 3 pin socket tester
(13A)/test lamp.
f. Tabulate the readings taken.
A. Physical Check
1. Check the cable installation and ensure the following:
a. Proper laying and dressing cable cleating /tying cable.
b. Tray supports are adequate.
c. Cable identification and labeling.
d. Glanding and gland earthing termination is correct.
e. No physical damage.
C. Phase Rotation Test- Phase rotation at all points should be same other wise rectify.
B. After installation, perform complete pre-testing and determine the compliance of the
system with requirements of the Drawings and Specification. Correct deficiencies
observed in pre-testing. Replace malfunctioning or damaged items with new ones, and
retest until satisfactory performance and conditions are achieved. Prepare forms for
systematic recording of acceptance test results.
C. After pre-testing is complete, provide a letter certifying the installation is complete and
fully operable, including the names and titles of witnesses to preliminary tests.
D. Provide a minimum of 10 days' notice in writing when the system is ready for final
acceptance testing.
A. Visual Checks
1. Check the cable entries with regards to their tightness.
2. Check the general arrangements of components and wiring.
3. Rating and details of components.
4. Labels and identifications.
5. Earthing of components and related connections.
6. Check the polarity.
C. Other Tests
2.11 LIGHTING
A. Verify the correct lamps, position, ballast and operation of all fixtures.
B. With all lighting in operation, measure the average illuminance on the floor/working
plane by establishing the maximum and minimum levels in the following locations:
C. Exits, public corridors, corridors leading to exits, electrical equipment rooms, elevator
machine rooms and hoistway pits, offices, storage rooms, service rooms, garages,
washrooms and stairways.
E. With only the emergency lighting in operation, measure the average illumination at exits,
public corridors, floor areas where the public may congregate and other rooms and
areas as directed by the CONSULTANT/EMPLOYER.
H. Take readings with a cosine corrected portable digital illuminance meter, or with a video
camcorder with suitable software for illuminance measurements. Measuring
instruments shall be tested, calibrated and certified accurate to within 2%.
I. Submit technical, testing and calibration data as well as certification on the photometer.
J. All readings results should match the required illuminance levels as specified in relevant
sections.
K. Plot lighting results on a set of reproducible plans for review by THE CONSULTANT/
EMPLOYER and submission to the authorities.
B. Tests should be carried out in accordance with Part 7 of BS 7671 together with
Guidance Notes, number 3 as issued by the IEE, and should also include the following:-
1. Conductive parts - test conductive parts simultaneously accessible with exposed
conductive parts of extraneous conductive paths.
2. Generally conductive paths are not extraneous conductive paths if separate from
earth by an impedance of greater than 50M ohms. Confirm conductive paths are
bonded to equipotential zone earth bar by an impedance not exceeding 0.1
ohms.
3. Prospective short circuit current (PSSC) - To determine suitability of terminal and
intermediate equipment the values of PSSC should be measured (unless these
can be verified by alternative means).
4. Pressure tests (see below)
5. Full load test (1 hour duration)
C. During the full load test voltage and current readings at the final sub-circuit, sub-main
and main intake positions shall be taken. This test shall be carried out at the completion
of works and again (at the discretion of the MEP Consultant) at the end of defects
period.
D. In the event of any test failing to comply, that test and those proceeding (the results
which may have been influenced by the fault) shall be repeated after rectification of the
report.
E. The Contractor shall include for the supply all test instruments and labour required to
complete the testing and commissioning works. Tests shall only be carried out by
competent persons.
F. The MEP Consultant shall be given at least seven working days notice in writing of the
time when it is proposed to carry out any test to enable him to be present during the
test(s) if required.
G. Serial numbers of all test instruments shall be logged and noted on results sheets. All
instruments shall have a current calibration certificate.
H. Duplicate typewritten copies of the completed test reports shall be forwarded to the MEP
Consultant within seven days of the date when the tests are carried out.
A. All transmission testing shall be performed with an approved UTP field tester which shall
be factory calibrated by the field test equipment manufacturer. Calibration certificate
shall be submitted for CONSULTANT/EMPLOYER approval.
B. All UTP test cords, adapters, etc to be used for testing shall be supplied and verified by
the test equipment manufacturer to meet or exceed the requirements of TSB-67 and
qualified to test CAT 6 cabling system.
E. All ‘PASS’ test result shall be down loaded into the database software that has been
provided by the field test equipment manufacturer.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Section Includes:
1. Time switches.
2. Photoelectric switches.
3. Standalone daylight-harvesting switching and dimming controls.
4. Indoor occupancy and vacancy sensors.
5. Digital timer light switches.
6. Lighting contactors.
B. Related Requirements:
1. Section 26 2726 "Wiring Devices" for wall-box dimmers, non-networkable wall-
switch occupancy sensors, and manual light switches.
B. Shop Drawings:
1. Show installation details for the following:
a. Occupancy sensors.
b. Vacancy sensors.
2. Interconnection diagrams showing field-installed wiring.
3. Include diagrams for power, signal, and control wiring.
A. Operation and Maintenance Data: For each type of lighting control device to include in
operation and maintenance manuals.
1.05 WARRANTY
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. Description: Solid state, with DPST dry contacts rated for 1800 VA inductive, to operate
connected relay, contactor coils, or microprocessor input and compatible with ballasts
and LED lamps.
1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and
marked for intended location and application.
2. Light-Level Monitoring Range: 1.5 to 10 fc (16.14 to 108 lux), with an adjustment
for turn-on and turn-off levels within that range and a directional lens in front of
the photocell to prevent fixed light sources from causing turn-off.
3. Time Delay: Fifteen-second minimum, to prevent false operation.
4. Surge Protection: Metal-oxide varistor.
5. Mounting: Twist lock complies with base-and-stem mounting or stem-and-swivel
mounting accessories as required to direct sensor to the north sky exposure.
6. Failure Mode: Luminaire stays ON.
C. PIR Type: Ceiling mounted; detect occupants in coverage area by their heat and
movement.
1. Detector Sensitivity: Detect occurrences of 6-inch- (150-mm-) minimum
movement of any portion of a human body that presents a target of not less than
36 sq. in. (232 sq. cm).
2. Detection Coverage (Room, Ceiling Mounted): Detect occupancy anywhere in a
circular area of 1000 sq. ft. (93 sq. m) when mounted on a 96-inch- (2440-mm-)
high ceiling.
3. Detection Coverage (Corridor, Ceiling Mounted): Detect occupancy within 90 feet
(27.4 m) when mounted on a 10-foot- (3-m-) high ceiling.
D. Ultrasonic Type: Ceiling mounted; detect occupants in coverage area through pattern
changes of reflected ultrasonic energy.
1. Detector Sensitivity: Detect a person of average size and weight moving not less
than 12 inches (305 mm) in either a horizontal or a vertical manner at an
approximate speed of 12 inches/s (305 mm/s).
2. Detection Coverage (Small Room): Detect occupancy anywhere within a circular
area of 600 sq. ft. (56 sq. m) when mounted on a 96-inch- (2440-mm-) high
ceiling.
3. Detection Coverage (Standard Room): Detect occupancy anywhere within a
circular area of 1000 sq. ft. (93 sq. m) when mounted on a 96-inch- (2440-mm-)
high ceiling.
4. Detection Coverage (Large Room): Detect occupancy anywhere within a circular
area of 2000 sq. ft. (186 sq. m) when mounted on a 96-inch- (2440-mm-) high
ceiling.
5. Detection Coverage (Corridor): Detect occupancy anywhere within 90 feet
(27.4 m) when mounted on a 10-foot- (3-m-) high ceiling in a corridor not wider
than 14 feet (4.3 m).
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine lighting control devices before installation. Reject lighting control devices that
are wet, moisture damaged, or mold damaged.
B. Examine walls and ceilings for suitable conditions where lighting control devices will be
installed.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
B. Install and aim sensors in locations to achieve not less than 90-percent coverage of
areas indicated. Do not exceed coverage limits specified in manufacturer's written
instructions.
A. Mount electrically held lighting contactors with elastomeric isolator pads to eliminate
structure-borne vibration unless contactors are installed in an enclosure with factory-
installed vibration isolators.
A. Wiring Method: Comply with Section 26 0519 "Low-Voltage Electrical Power Conductors
and Cables." Minimum conduit size is 1/2 inch (13 mm).
D. Splices, Taps, and Terminations: Make connections only on numbered terminal strips in
junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures.
3.05 IDENTIFICATION
B. Perform the following tests and inspections with the assistance of a factory-authorized
service representative:
1. Operational Test: After installing time switches and sensors, and after electrical
circuitry has been energized, start units to confirm proper unit operation.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
C. Lighting control devices will be considered defective if they do not pass tests and
inspections.
3.07 ADJUSTING
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 REFERENCE
A. This section forms part of every section of Division 14 for Conveying Systems, Division
26 for Electrical, Division 28 for Electronic Safety and Security.
A. Supply and installation of sub main distribution boards (SMDB), final distribution boards
(FDB) or (DB), motor starters panel (CP) and related accessories.
B. This specification section covers the design and fabrication of low voltage switch gear
including all items of equipment and materials necessary to complete the assembly and
the information, documents and data required to be supplied by the supplier.
C. Any separate panels shall be as detailed hereafter. Separate panels shall comply with
the requirements of this specification section.
A. Design, manufacture, testing and method of installation of all assemblies and the
associated equipment furnished under requirements of these specifications shall
conform to latest publications or standard rules of the following codes and standards to
the extent specified herein. When an edition date is not indicated for a Code or
Standard the latest edition enforced at the time of proposal submitted shall apply.
B. Product selection for restricted space: Drawings indicate maximum dimensions for the
equipment, including clearance between the equipment and adjacent surfaces and
items. Switchboards having equal performance characteristics and complying with
indicated maximum dimensions may be considered.
C. All panel boards shall be manufactured only by manufacturer having BSEN ISO 9001
Certificates.
D. The local panel manufacturer shall be an authorized agent of the principal switchboard
manufacturer. A stamped certificate from the principal manufacturer shall be submitted
along with the submittals confirming that all the equipment used in the panel boards by
the local manufacturer is type tested and supplied by the principal and the assembly of
The assemblies and the associated equipment shall confirm to the requirements of the
latest edition of the following standards and codes where applicable:
C. IEC61641 Enclosed low voltage switchboard and control gear assemblies Guide for
testing under conditions of arcing due to internal fault
G. IEC60947-2 Low voltage switchboard & control gear – part 2 Circuit breakers
J. IEC61140 Protection against electric shock – Common aspects for installation and
equipment – Basic safety publication
O. BS 88 Cartridge fuses.
R. BS 37 Electricity meters-General
V. The low-voltage electrical switchboard must be a fully factory Type Tested Assembly
(TTA), as per the local authority’s mandatory requirement and compliant with IEC
61439-1 and 2.
W. Prior to placing order of the equipment, ensure that the physical dimensions of the
equipment do not infringe the working space required by the applicable standards.
Y. The switchboard manufacturer must have a previous record of satisfactory service for at
least (10) years.
BB. The contractor is responsible for complying with all codes, which apply to the
equipment. Any special certification requirements or inspection by other authorities
arising from the above shall be arranged by the contractor and the costs for the same
included in this quotation.
CC. The equipment to be provided by vendor must be in complete compliance with this
specification and reference codes. Exceptions or deviations if any, shall be listed
separately, with the quotation for THE CONSULTANT's approval. Any exception, which
is not listed, shall not be considered.
B. Determine suitable path for moving switchboard into place considering project
conditions.
D. Revise locations and elevations from those indicated as required to suit project
conditions.
A. Deliver in sections or lengths that can be moved past obstructions in delivery path.
B. Store indoors in clean dry space with uniform temperature to prevent condensation.
Protect from exposure to dirt, fumes, water, corrosive substances, and physical
damage.
1.07 SUBMITTALS
B. Test Reports
1. Provide test reports prepared in accordance with ADDC requirements and to the
CONSULTANT approval. Provide other tests reports as necessary to establish
the adequacy, quality, safety, completed status, and suitable operation of each
system.
2. The test reports to include the following:
a. Test procedures used.
b. Test results that comply with requirements.
c. Results of failed tests and corrective action taken to achieve test results
that comply with requirements.
C. Installation Instructions
1. Submit the complete manufacturers installation instructions of all the products
used.
D. Calculations
1. Forward the following calculations and data:
a. Calculations and charts proving that discrimination in the breaker
characteristics is achieved.
b. Detailed short circuit level calculation to select the short circuit rating of
the various switchboards.
c. Bus bar sizing calculation for each switchboard.
d. Calculation for temperature rise inside switchboards
E. Shop drawings
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Description
1. The specification hereunder shall be applied to all panel boards referenced on
the drawings/load schedules as DB, EDB or UDB. The distribution board shall be
flush / surface mounted and shall be provided with standard extension box to
allow cable glanding if required.
2. Distribution boards shall be split busbar type, and shall have isolator as main
incomer and RCD type earth leakage protection device shall be provided for
B. Enclosures
1. The MCB Distribution Boards shall be surface/flush mounted type. The
enclosures within Electrical rooms must be surface mounting type. Powder
coated rustproof sheet steel units, complete with circuit breakers providing
thermal overload and magnetic short-circuit and earth fault protection as shown
on the drawings. The enclosure protection shall be IP 31, while the complete
assembly shall comply with IEC – 439-1.
2. Enclosures outside electrical room shall have key-lock opening.
C. Busbar
1. The MCBs shall be mounted on either 3 phase or single phase or split busbars
as appropriate. All spaces which are not provided with breakers shall be covered
with blank plates.
2. A final sub-circuit neutral assembly and an earthing bar assembly shall be
available to facilitate the connection of neutral conductors and protective
conductors respectively.
3. To be of appropriate current carrying capacity at least equal to the rating of the
main incoming MCCB isolator.
4. To be of copper.
B. Disconnect switches shall be heavy duty (AC23) with operating handle interlocked with
the switch cover, in general purpose rust proof aluminum enclosure and to IP44 finished
in gray stove finish.
C. Switches shall be quick make, quick break action. Provision shall be made for
padlocking in either the “On” or “Off” position.
E. Operating handles shall be interlocked to prevent doors from being opened when switch
is closed. Provision shall be made to defeat this interlock with a screwdriver.
F. Fuse clips shall be designed for HRC BS 88/IEC 269 fuses without adapters and shall
reject standard code fuses.
G. Switches mounted outside, in damp or dusty locations and unconditioned areas shall be
supplied in weather resistant enclosures IP 65 made of aluminium with double wall
construction.
H. The enclosures shall be provided with ON and OFF indication lights with test facility.
I. Sample and catalogues with installation details shall be submitted for approval by THE
CONSULTANT prior to ordering.
K. All disconnect switches shall be provided with tag to THE CONSULTANT approval to
indicate equipment connected to the switch. The feeding circuit reference and the
related distribution board number.
L. All disconnect switches feeding life safety equipment such as emergency lighting, fire
alarm, fire pump, jockey pump, smoke control fans, etc. shall be fire rated.
A. Description
1. Starters shall be manufactured and type tested in accordance with IEC 947-4
and IEC 947-4-1
2. All motors shall be provided with heavy duty contactor type motor fuseless
starters selected for coordination type 2 in accordance with IEC 947-4 generally
complying with the following and protected through circuit breaker.
a. 3KW direct on line starting
b. 3KW to 25KW Star Delta starting
c. 25KW and above reduced voltage electronic soft starters.
3. Each starter panel (CPs) shall be provided with a main incoming MCCB capable
of carrying the full load current. Each starter shall comprise as a minimum:
a. On load triple pole MCCB with two normally open and one normally
closed auxiliary switches. The MCCB to be mechanically interlocked with
the starter component door and capable of breaking the motor starting
current and of making onto a fault at the motor terminals.
b. Provision to be made for padlocking the MCCB in the 'OFF' position.
c. Three pole contactors to be fitted with three normally open and three
normally closed auxiliary contacts. All the auxiliary contacts to be wired
down to the starter terminal block.
d. One triple pole thermal over current relay incorporating over current,
phase sequence and single phase protection with adjustable trip settings.
e. External mechanical hand reset to be provided.
f. One control circuit MCB or fuse and one copper link.
g. Each starter shall be fitted with one set of local start/stop push buttons
and a local/remote/auto selector switch or hand/off/auto switch as
required. Each starter control wiring terminal block shall include control
terminals for connection of remote push buttons, auto circuits and local
and remote emergency stop push buttons.
h. Where more than one motor with a duty/standby or duty/backup functions
used, the starter control wiring shall be arranged to automatically change
duty upon the fault tripping of the selected motor. A duty/standby or
sequence selector switch shall be provided.
i. Each starter shall be fitted with twin led indication lamps indicating:
1) Motor running (green)
2) Motor stopped (red)
3) Overload tripped (amber)
B. Enclosure
1. Panels shall be constructed of a minimum 1.6mm thick electro galvanized steel
coated with high solid enamel polyester electrostatic spray and oven baked and
protected to IP 54.
2. Front access shall be arranged for all panels with hinged lift off doors. Dust and
damp proof gasket around the edge and fitted with lockable cam type chromium
plated handle mechanically interlocked with the starting MCCB.
3. The enclosures for the motor starters are divided into two types as follows:
a. Single starter panel.
b. Motor control centre.
4. Single starter panel
a. This specification shall be applied for starter panels used for starting a
single equipment with a maximum of two motors.
b. All equipment shall be mounted on sheet steel mounting plate with screws
into tapped holes and all live parts shall be shrouded to a minimum IP54.
c. The minimum short circuit rating for the different components shall be
35kA. However, the contractor shall forward a short circuit calculation and
upgrade the same if found necessary.
5. Compensated Equipment
6. Any motorized valve or damper controlled via a compensated system, shall be
arranged such that a manual selector switch is provided to override compensated
selection and enable manual opening/closing or on/off control, as appropriate.
Any compensator unit mounted within the control cabinet shall remain in the
manufacturer's purpose made enclosure and be installed strictly in accordance
with the manufacturer's recommendations.
7. The panels shall contain devices for automatic restart of units after power failure
where required.
A. Moulded case circuit breakers shall conform to the latest editions of BSEN60947-2.
B. The MCCB's shall have a minimum service short circuit capacity similar to the panel
board where the same is installed.
D. Three pole breakers shall have a common trip with a single operating handle and
designed so that any overload in one pole automatically causes all poles to open.
Breakers shall be trip free and each shall have a trip indication independent of ON or
OFF positions.
E. The MCCB's at the MDB’s shall be provided with the necessary number of change over
auxiliary switch and with signaling unit which shall be connected to the BAS system in
order to provide information on the breakers conditions and alarms where required.
F. Wherever shown on the drawings or required by ADDC, MCCBs shall be provided with
earth leakage alarm relay or earth leakage relay of fixed/adjustable sensitivity.
H. Construction
1. For maximum safety, the power contacts shall be insulated in an enclosure made
of a thermosetting material from other functions such as the operating
mechanism, the case, the trip unit and auxiliaries.
2. The operating mechanism of the moulded-case circuit breakers shall be of the
quick make, quick-break type with fault tripping over ridding manual operation. All
poles shall operate simultaneously for circuit breaker opening, closing and
tripping.
3. The moulded-case circuit breakers shall be front operated by a toggle or handle
that clearly indicates the three positions: ON, OFF and TRIPPED.
4. The moulded-case circuit breakers shall be equipped with a "push to trip" button
in front to test operation and the opening of the poles.
5. Where required, motor operated mechanism, shunt trip, under voltage release,
auxiliary switches up to four change over contacts and a tripped signal contact
shall be provided. Each of these units shall incorporate a pre-wired terminal strip,
which is accessible from the front of the breaker without removing the cover.
I. Current Limiting
1. The moulded case circuit breakers shall be capable of greatly limiting currents.
For short circuits, the maximum thermal stress it shall be limited to
2. 106 A2 s for ratings up to 250A.
3. 5 x 106 A2 s for ratings between 400A and 630A.
4. Amps and S : Seconds
5. These characteristics will allow high cascading performance with moulded-case
or miniature circuit-breakers.
B. MCBs shall be 35mm symmetrical rail mounted type and available in one, two, three or
four poles version.
E. Construction
1. The operating mechanism shall be mechanically trip free from the operating
handle so as to prevent the contacts from being held closed against short circuit
conditions. It shall be of the "automatic resetting type".
2. The individual operating mechanism of each pole of a multi-pole MCB shall be
directly linked within the MCB casing and not by the operating handles.
3. The operating handle shall be of the toggle type.
4. Each pole shall be provided with bi-metallic thermal element for overload
protection and magnetic element for short circuit protection.
5. Terminals shall be of the tunnel type (IP20) in order to minimize the risk of direct
contact.
B. All meters shall be moving iron type, minimum of 72 sq. mm square shape and 90 deg.
scale.
F. Kilowatt-hour meters (kWH meters) shall be provided as per the requirements of the
local Electrical Power Authority. They shall be dust and vermin proof and shall be of
robust construction so that they will keep their accuracy over many years of service
under the local climatic conditions.
G. The counters shall be of the cyclometer type with six digits to give direct reading of
power consumptions, the lowest figure being units and not tenths of units. Pointer type
counters are not acceptable. The calibrating adjustment should be operated by
screwdriver only.
H. kWH Meters should have not less than 5-mm diameter terminal holes and shall be
operated through three suitably rated current transformers and the counter of the meter
should be calibrated to read the primary KWH.
I. All kWH meters shall be handed over to the Power Supply Authorities for calibration
prior to final installation and connection.
J. All kWH meters shall be equipped with a pulse output (equivalent to the metered
energy), to provide an energy consumption scheme at a remote control and monitoring
system.
K. All kWH sub-meters shall be provided with data logging capability and be connected to
the Building Management system so that the information on the building’s energy
consumption can be monitored, recorded and analysed.
L. The energy metering monitoring system shall be able to provide hourly, daily, weekly,
monthly and annual energy consumption for each end use.
N. The energy metering monitoring system shall be able to determine ‘out-of-range’ values
and alert building operators to any unusually high consumption.
O. The energy metering monitoring system shall be able to record peak energy
consumption for each end use.
P. The information monitored, recorded and analysed via the energy metering monitoring
system shall be displayed at the screens located at main entrances. The contractor shall
B. The conditional ratings of current transformers shall correspond with the switchboard
rating and shall be such as to maintain the overall metering accuracy as is necessary to
operate relays within the tolerances specified by the manufacturer.
D. Current transformers shall have the following accuracy as a minimum, for protection
Class 5P
E. (Except for REF Protection which will have PS class CT) for indication Class 1 for
metering Class 1
F. The manufacturer shall ensure that the current transformers are such that the relays will
operate correctly when set at any point within their ranges.
B. Voltage transformers shall be suitable in rating and accuracy for their functions, loads
and duties.
F. The primary and secondary circuits of the voltage transformers shall be protected by
fuses and the secondary winding shall be earthed at one point through a removable link.
H. The manufacturer shall provide MCBs with auxiliary contacts or alternatively 4-pole
MCBs on the secondary side of the voltage transformers.
B. Duty category for lighting contactors shall be AC1 and for inductive load shall be AC3.
C. Contactors shall be protected against direct finger contact, mechanical life shall be 15 to
20 million operating cycles shall be suitable for 1200 operating cycles per hour.
D. The contactors shall be of 3 pole construction capable of handling high rush currents
and suitable for operating up to 55 deg. C ambient temperature without any derating.
A. Current operated earth leakage circuit breakers shall be in accordance with BSEN
61008 providing the functions of isolation, switching and earth leakage protection of
electrical circuits.
B. The ELCB's shall have a residual current operated electro mechanical release.
C. The ELCB's shall incorporate a filtering device to eliminate unwanted tripping due
transient voltage.
E. A trip free mechanism is required to ensure that the unit can not be held closed against
an earth fault.
F. The tripping device is connected directly to the secondary of the current balance
transformer.
H. The breaker shall be double pole when used for single phase and 4 poles when used for
three phase circuit protection.
I. The ELCB's shall have 30mA or 100mA sensitivity as indicated in the drawings.
A. Each time switch shall be of the quartz movement type with minimum 24 hour battery
reserve or operated by a 230 volt synchronous motor and of the type incorporating
separate motor supply and control switch terminals and be with a minimum of a 24 hour
self winding clockwork spring reserve.
B. Unless more sophisticated operation is specified elsewhere, then each time clock shall
be capable of two 'on' and two 'off' operations every twenty-four hour period. Also, any
control time switch incorporated within the panel, shall be complete with an associated
bypass selection facility to manually override 'on/off'.
A. These are to be used in conjunction with motor starters to provide protection against
overloads, phase sequence, phase failure (single phasing) and under voltage
conditions.
B. The relays shall be selected such that the full load current of the equipment protected
falls at the centre of the relays adjustment range.
C. Thermal overload relays shall be used for motors ratings, up to and including 11kW,
giving protection against:
1. Over-current unbalance
2. Single phase
3. Earth fault
D. For motors rated above 11KW, multi functional relays shall be used. Multi functional
relays include protection, metering, control, monitoring and annunciating functions. It is
envisaged that the following functions are available.
1. Overload
2. Over-current
3. Single phase
4. Earth fault
5. Under voltage
6. Over voltage
7. Plus digital indication of:
8. Relay settings % of FLC that the motor is taking
9. Continuous monitoring of thermal capacity of motor
10. Thermal capacity used during start of motor
11. If tripped, how much time before restart to take place
12. Stall or short circuit trip
13. Earth fault trip
14. Starting
A. Shall be of the encapsulated plug-in type and incorporate visual indication that the
operating coil is energized.
B. Bases for relays shall be mounted horizontally, to ensure relay is vertical above the
base when the control cabinet is in its intended location, with screw type terminals,
suitable for receipt of spade type crimped/soldered lugs.
C. Adjustable timer delay relays used for the star delta starter shall ensure precise
reproducibility of the timing function. The relay shall have a linear setting scale over a
350 deg. rotation by means of knurled knob with timing guide marks. The relay shall be
equipped with two electrically separated time delayed contact one normally open and
one normally close.
B. Indicator lamps shall be of the low voltage 24 volt transformer with twin LED lamp type
and accord with the signaling colours laid down in BS. 4099. Minimum lens diameter
shall be 12.5mm and all lenses on a panel shall be of a matching size and appearance
and removable from the front for lamp replacement.
A. They shall be of the complete rotary cam type rated to suit item controlled and fitted with
pointer type switching knob. Terminations shall be screw grip to receive spade type
crimped/soldered lugs.
B. Hand off auto selection switch shall have three positions with centre position off and
shall be key operated wherever necessary.
C. Selector switch when used along with the voltmeter it shall have 8 positions, i.e phase to
phase, 3 phase and 2 off position.
2.22 ACCESSORIES
A. All the push buttons shall be made of non-hygroscopic material, non-swelling and fitted
to avoid any possibility of sticking. Unless otherwise specified, they shall be of
momentary type. All push buttons shall be 22mm dia, and have minimum IP54 ingress
protection rating.
B. As a general rule, the heaters shall be placed at the bottom of the cubicle.
PART 3 - EXECUTION
3.01 GENERAL
B. Conform to the requirements of the local power supply authorities having jurisdiction.
E. Frame and mount printed, basic operating instructions for switchboards, including
control and key interlocking sequences, and emergency procedures, fabricate frame of
finished wood or metal and cover instructions with clear acrylic plastic. Mount on the
front of the switchboards.
3.02 INSTALLATION
A. After installation and leveling, render the entire switchboard rodent proof by any means
of steel plates,
D. The circuit breakers shall be situated to allow wiring to be carried out with sufficient
slack to enable them to be removed for inspection without disconnecting any circuit
wiring.
F. All panel board and distribution boards shall consist of adequately rated circuit breakers.
Circuit breakers shall be temperature compensated at the manufacturer's works to give
the design current rating at 50 deg. C. Non-compensated breakers will not be approved
and a formal certificate will be required from the manufacturer confirming that the
breakers have b0een suitably temperature compensated.
1. The contractor shall supply and install all panel board with the related voltmeters,
ammeters and energy meters of a type that meets with ADDC approval.
2. Where single core cables enter or leave any item of metal clad switchboard,
distribution gear, etc., the cable cores shall all pass through the same aperture in
the enclosure or case of the unit concerned, to avoid the setting up of eddy
currents. Where separate holes are provided by the manufacturer for the cables,
the holes shall either be cut out to form a continuous slot, or alternatively the
holes shall all be joined together with saw cuts through the solid metal separating
the holes. In all cases end plates shall be of non-ferrous metal.
3. A special termination arrangement shall be provided to CONSULTANT and
ADDC approval at the sub main and main panel boards wherever the cable size
exceeds the breaker terminal capacity.
A. Routine tests to standards shall be carried out. Evidence that type test have been
carried out provided they are relatively to the configuration of the equipment offered,
may be acceptable to THE CONSULTANT and shall be made available.
B. A full visual check and electrical functional test shall be carried out on all apparatus and
every circuit. All wiring shall be inspected. It shall be verified that the FBA is fully in
accord with the requisition. Circuit breakers shall be closed and tripped at their rated
minimum and maximum trip and close supply voltage. Primary and secondary injection
tests shall be done on protection relays and CT circuits and indicating and metering
instruments. All labels shall be checked.
E. Routine Tests
1. Following routine tests are to be carried out by the switchboard assembler,
2. Inspection of assembly including inspection of wiring and electrical operation
3. Dielectric test:
4. Checking of protective measures and of the electrical continuity of the protective
circuits.
5. Verification of insulation resistance.
END OF SECTION
WIRING DEVICES
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section shall include all labour, materials, equipment, appliances and accessories
necessary for the complete performance of all switches, socket outlets etc. In
accordance with the Specifications and Drawings.
1.02 SUBMITTALS
B. Shop Drawings: List of legends and description of materials and process used for
premarking wall plates.
C. Samples: One for each type of device and wall plate specified, in each color specified.
E. Operation and Maintenance Data: For wiring devices to include in all manufacturers'
packing label warnings and instruction manuals that include labeling conditions.
A. Source Limitations: Obtain each type of wiring device and associated wall plate through
one source from a single manufacturer. Insofar as they are available, obtain all wiring
devices and associated wall plates from a single manufacturer and one source.
B. All components and their installations shall be free from defects. Any defective
material or workmanship and any resulting damage to work of other trades shall be
replaced or repaired as directed during the Warranty Period at the contactors
expense. Comply with General Conditions, agreeing to repair or replace any
components that have failed within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 GENERAL
A. All individual items of materials shall be of the same make throughout the Project unless
specifically approved by the Engineer.
Location Finishes
Villa – FOH areas As per ID requirements
Villa – BOH areas White poly-carbonate
Car Park and IP rated
Exposed area
Plant Room White poly-carbonate
A. Outlet Boxes:
1. Galvanized one piece pressed steel, sizes and designs shall suit devices to be
fitted and shall be complete with adjustable lugs and earth terminals
2. Outlet boxes mounted externally or in damp locations shall be totally sealed to
ensure water tightness.
3. In all hazardous areas specified and/or shown on drawings: explosion proof.
2.04 SWITCHES
A. Lighting Switches
1. To BS EN 60669 - 1
2. To be rated as stated in BS7671 and ADDC regulations
3. Recessed with concealed conduit, surface pattern elsewhere
4. Quick make and break type
5. Single pole, double pole, one way, two way or intermediate as indicated
6. Surface mounted switches to be metallic
7. Flush mounted switches to be of the grid fixing type with finish.
8. All plastic switches shall be manufactured from white Urea plastic material having
properties which include anti tracking and non-flame propagation.
9. All switches shall comply with BS EN 60669-1. The switch construction should
have a clearance between the contacts in the open position not less than 3mm
as per BS60364 – 4.
10. All switches shall have large terminals to accept 2 x 2.5 mm2 conductors. All
terminals should have insulated bell mouth terminal guides for each of
termination. All switches should have slim rear projection and be suited for
mounting in 16mm/25mm/35mm deep boxes.
B. Waterproof Switches:
1. To be watertight IP 56 or as indicated in the Project Documentation
2. To be made of poly-carbonate for indoor application in damp and wet areas.
C. Switch Plates
1. Where two or more switches are grouped together and connected to the same
phase, multi-gang devices and common plates shall be used.
C. Shuttered Sockets:
1. The Shutters shall effectively screen & isolate the line & neutral socket outlets to
exclude dust & interference & shall only be operable when the interlocked earth
pin in the associated plug top has been inserted.
A. All shaver outlet units shall comply with BS 3535: Part 11990 & IEC 61558-2-5:1998.
B. Shaver units shall be flush pattern. The face plate shall be engraved with “Shaver Only'”
and be suitable for installation in bathrooms, incorporating a double wound isolating
transformer to provide an earth free supply.
D. Units shall incorporate Dual voltage output 240-115V, 20VA on either outlet, No Load
Voltage >275V.
E. Automatic Primary supply switches on while insertion of a shaver plug & switches off
automatically on removal.
J. Unite shall incorporate two pin shuttered outlet configuration and have terminals to
accept 2.5mm2 conductors.
K. The cover plate of the shaver socket shall be inscribed SHAVERS ONLY with the
addition of a pictogram symbol.
L. Unit Flush mounting boxes in 47mm deep BS 4662 2 gang metal box, rustproof by
galvanizing of equal finish and complete with a brass earthing stud secured to the back
of the box.
A. Cooker control units shall incorporate a 45 Amp. double pole switch and 13A, 3 pin
switched socket outlet and neon indicator lights for both cooker and socket
B. The cooker control unit shall be flush mounted. A selector switch will be used to select
between cooker and combi oven.
C. The unit shall be installed adjacent to the cooling appliance (not directly behind or
above).
A. 230 V fused connection units shall be switched, shall comply with BS 5733 and shall be
fitted with a fuse complying with BS 1362 with a rating as specified.
C. Live contacts shall not be exposed under normal operating conditions when replacing a
fuse.
D. 230V fuse connection units in plat areas, workshops etc. shall be surface mounted
metalclad and shall comply with BS 1363.
A. The Junction Box shall be completed with a terminal block suitable for connecting up to
10 mm2 copper conductor (phase, neutral and earth) and an all insulated moulded white
cover plate with removal covers.
2.11 TIMER
B. Timers shall be suitable for operation from supply voltage of 230V, 1-phase, 50Hz
system.
C. Timer output contacts shall be suitable for both a.c. and d.c. control circuits. The
contacts shall be suitable for duty of AC-2 or DC-3 utilisation category. The rating of
output contacts shall be co-ordinated with the application requirements.
D. Timers shall be provided with 2 independent timing scales with sets of change-over
output contacts:
1. 10 200 seconds
2. 0.10 20 seconds
G. Upon supply of rated voltage to the input terminals, the timer shall start, the output relay
remains in rest position. After the set time, the output relay pulls in. The relay resets
after the input supply has been cut-off.
I. The timer shall require a pozi-drive screw driver for changing of the settings.
A. Operation of the contactors for switching on the external lights as indicated in the
distribution board schedule shall be by means of photo electric cell.
B. Photo-electric control switch or cell shall operate from a supply voltage of 240V, 50Hz
and turn ON shall occur at 40 lux and turn OFF at 80 lux.
D. Photo - electric switches or cell shall be weatherproof complying with BS 5490, IP 54.
B. Sensor shall be equipped with a separate adjustment for delayed time off.
A. Isolators and switch fuses, where mounted individually shall be of sheet steel
construction with doors and front operated handles. They shall be of the quick make,
quick break type with removable shields over the fixed contacts, door interlocks and
'ON/OFF' indicators.
B. Isolators and switch fuses shall be single or triple pole with neutral, of ratings as
indicated on the Drawings and provided with earth terminals. They shall be in
accordance with IEC 408. The switch fuses shall be suitable for H.R.C. type fuses of
Class QI to BS 88.
C. The isolators and switch fuses installed in public places shall have aesthetically pleasing
appearance.
D. Isolators and switch fuses installed outside the building shall of IP 54 construction.
A. The mounting heights of wiring accessories shall be as stipulated in the local power
authority Regulations, or as otherwise as indicated on the drawings or approved by the
Engineer.
PART 3 - EXECUTION
A. Location of Boxes:
1. Determine exact location of boxes on site and obtain the Engineer’s approval
before commencing installation
B. Fixing:
1. Fix outlet boxes securely
2. Fix exposed outlet boxes to permanent inserts or lead anchors with machine
screws.
C. Mounting Heights:
1. Mount boxes as indicated or as approved by the Engineer
2. Where mounting height is not shown or specified, obtain instructions
3. Boxes for similar equipment: mount at uniform heights within same or similar
areas.
A. Lighting Switches:
1. Locate at the strike side of the door, approximately 150 mm from the edge of
door frame
2. Plates shall be installed with all four edges in continuous contact with finished
wall
3. Plates shall be installed with an alignment tolerance of 1.5 mm
4. All switch assembly louvered plates shall have their earthing terminal connected
to the earth terminal attached to the switch box by an insulated 2.5 mm2
protective conductor.
B. All sockets, switches, disconnect switches, fused switches, etc. located in food
preparation areas shall be mounted flush to wall.
A. Generally:
1. Fix junction, pull and terminal boxes where indicated and where required to
facilities pulling of wires and cables and connection of future appliances
2. Locate boxes as inconspicuously as possible, but accessible after work is
completed.
B. Pull Boxes:
1. Fix at maximum 10m spacing and to limit the number of bends in conduit to not
more than two 90° bends.
3.04 TESTING
A. Test all switches, socket outlets etc. for correct polarity and continuity of conductors in
the presence of and to the entire satisfaction of the Engineer.
B. Carry out live phase to earth loop impedance tests at all switches and socket outlets
with an approved earth loop impedance tester to the entire satisfaction of the Engineer.
C. Test all socket outlets for instantaneous tripping of associated distribution board current
operated earth leakage circuit breaker using testing equipment, approved by the
Engineer.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following individually mounted, enclosed switches and circuit
breakers:
1. Molded-case circuit breakers.
2. Molded-case switches.
3. Enclosures.
1.03 SUBMITTALS
A. Product Data: For each type of enclosed switch, circuit breaker, accessory, and
component indicated. Include dimensioned elevations, sections, weights, and
manufacturers' technical data on features, performance, electrical characteristics,
ratings, and finishes.
1. Enclosure types and details for types other than IP55.
2. Current and voltage ratings.
3. Short-circuit current rating.
4. UL listing for series rating of installed devices.
5. Features, characteristics, ratings, and factory settings of individual overcurrent
protective devices and auxiliary components.
6. Include time-current coordination curves (average melt) for each type and rating
of overcurrent protective device; include selectable ranges for each type of
overcurrent protective device.
B. Shop Drawings: For enclosed switches and circuit breakers. Include plans, elevations,
sections, details, and attachments to other work.
H. Operation and Maintenance Data: For enclosed switches and circuit breakers to include
in emergency, operation, and maintenance manuals. In addition to items specified in
Division 01 Section "Operation and Maintenance Data," include the following:
1. Manufacturer's written instructions for testing and adjusting enclosed switches
and circuit breakers.
2. Time-current curves, including selectable ranges for each type of circuit breaker.
C. Product Selection for Restricted Space: Drawings indicate maximum dimensions for
enclosed switches and circuit breakers, including clearances between enclosures, and
adjacent surfaces and other items. Comply with indicated maximum dimensions.
1.05 COORDINATION
A. Coordinate layout and installation of switches, circuit breakers, and components with
other construction, including conduit, piping, equipment, and adjacent surfaces.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Molded-Case Circuit Breaker: Comply with applicable BS, with interrupting capacity to
meet available fault currents.
D. Electronic Trip-Unit Circuit Breakers: RMS sensing; field-replaceable rating plug; with
the following field-adjustable settings:
1. Instantaneous trip.
2. Long- and short-time pickup levels.
3. Long- and short-time time adjustments.
4. Ground-fault pickup level, time delay, and I2t response.
2.03 ENCLOSURES
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine elements and surfaces to receive enclosed switches and circuit breakers for
compliance with installation tolerances and other conditions affecting performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
A. Coordinate size and location of concrete bases. Verify structural requirements with
structural engineer.
B. Concrete base is specified in Division 26 Section "Hangers and Supports for Electrical
Systems," and concrete materials and installation requirements are specified in
Division 03.
3.03 INSTALLATION
A. Comply with applicable portions of BS for installation of enclosed switches and circuit
breakers.
B. Mount individual wall-mounting switches and circuit breakers with tops at uniform height,
unless otherwise indicated. Anchor floor-mounting switches to concrete base.
KEO/21-7387-0004 26 2816 / 5 Enclosed Switches And Circuit Breakers
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
C. Comply with mounting and anchoring requirements specified in Division 26 Section
"Vibration and Seismic Controls for Electrical Systems."
D. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets
and temporary blocking of moving parts from enclosures and components.
3.04 IDENTIFICATION
C. Testing Agency: Engage a qualified testing and inspecting agency to perform the
following field tests and inspections and prepare test reports:
D. Perform the following field tests and inspections and prepare test reports:
1. Test mounting and anchorage devices according to requirements in Division 26
Section "Vibration and Seismic Controls for Electrical Systems."
2. Perform each electrical test and visual and mechanical inspection as per BS /
IEC standards. Certify compliance with test parameters.
3. Correct malfunctioning units on-site, where possible, and retest to demonstrate
compliance; otherwise, replace with new units and retest.
4. Infrared Scanning:
a. Initial Infrared Scanning: After Substantial Completion, but not more than
60 days after Final Acceptance, perform an infrared scan of each
enclosed switch and circuit breaker. Open or remove doors or panels so
connections are accessible to portable scanner.
b. Follow-Up Infrared Scanning: Perform an additional follow-up infrared
scan of each unit 11 months after date of Substantial Completion.
c. Instruments, Equipment and Reports:
1) Use an infrared scanning device designed to measure temperature
or to detect significant deviations from normal values. Provide
calibration record for device.
2) Prepare a certified report that identifies enclosed switches and
circuit breakers included and describes scanning results. Include
3.06 TRAINING
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
3.09 ADJUSTING
3.10 CLEANING
A. On completion of installation, vacuum dirt and debris from interiors; do not use
compressed air to assist in cleaning.
END OF SECTION
ENCLOSED CONTROLLERS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes ac, enclosed controllers rated 600 V and less, of the following
types:
1. Direct online (DOL) starters
2. Star-delta starters
3. Soft starters
1.03 SUBMITTALS
A. Product Data: For each type of enclosed controller. Include dimensions and
manufacturer's technical data on features, performance, electrical characteristics,
ratings, and finishes.
H. Load-Current and Overload-Relay Heater List: Compile after motors have been
installed and arrange to demonstrate that selection of heaters suits actual motor
nameplate full-load currents.
I. Load-Current and List of Settings of Adjustable Overload Relays: Compile after motors
have been installed and arrange to demonstrate that dip switch settings for motor
running overload protection suit actual motor to be protected.
B. Source Limitations: Obtain enclosed controllers of a single type through one source
from a single manufacturer.
E. Product Selection for Restricted Space: Drawings indicate maximum dimensions for
enclosed controllers, minimum clearances between enclosed controllers, and for
adjacent surfaces and other items. Comply with indicated maximum dimensions and
clearances.
A. Store enclosed controllers indoors in clean, dry space with uniform temperature to
prevent condensation. Protect enclosed controllers from exposure to dirt, fumes, water,
corrosive substances, and physical damage.
B. If stored in areas subject to weather, cover enclosed controllers to protect them from
weather, dirt, dust, corrosive substances, and physical damage. Remove loose packing
and flammable materials from inside controllers; install electric heating of sufficient
wattage to prevent condensation.
1.06 COORDINATION
B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03
Section "Cast-in-Place Concrete."
C. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in Division 07 Section "Roof Accessories."
D. Coordinate features of enclosed controllers and accessory devices with pilot devices
and control circuits to which they connect.
E. Coordinate features, accessories, and functions of each enclosed controller with ratings
and characteristics of supply circuit, motor, required control sequence, and duty cycle of
motor and load.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. All Motor starters shall comply with BS EN 60947-4. The components of the starter shall
be type tested and ASTA certified to achieve Type 2 co-ordination in accordance with
IEC 947.
B. The Manufacturer shall supply certified test results to confirm that the starter has been
tested to substantiate designs according to applicable standards. The tests shall verify
not only the performance of the unit and integrated assembly, but also the suitability of
the enclosure venting, rigidity and bus bracing. In addition, the unit shall be factory
tested in accordance with applicable standards.
C. The Manufacturer shall be prepared to show proper evidence of having tested for noise
immunity on both input and output power connections
D. Motor starters shall comply with the requirements of the local power supply authorities
having jurisdiction.
E. Motor starters shall be rated to carry the full load current of its rated duty at its most
severe load conditions. All starters shall be capable of at least 20 starts per hour at
100% full load torque.
F. Motor starters shall be housed in a separate enclosure and each starter enclosure shall
contain the following components, or as otherwise indicated on the Project Drawings or
Project Documentation.
1. 1 No. triple pole MCCB or fuse switch, as indicated on the Project Drawings,
externally operated and interlocked with the enclosure door. There shall be
provision for padlocking in the OFF position.
G. The following equipment shall be mounted on the door of the starter enclosure, or as
otherwise indicated in the Drawings.
1. 1 No. ammeter with selector switch and current transformer fitted with
suppressed scale to read motor running and starting current with red pointer to
indicate full load current for each motor rated 25HP and above.
2. 2 No. pilot lamps to indicate “SUPPLY ON” (Green) and “MOTOR RUNNING”
(Red).
3. 1 No. pilot lamp to indicate “MOTOR FAILED” (Amber).
4. 1 No Pilot lamps (a separate lamp for each motor fault conditions).
5. 1 No. “Hand/OFF/AUTO” Selector switch
6. 1 set “Start/Stop” push button
7. 1 No. externally operated overload reset push button
8. 1 Lamp test push button
A. DOL starters shall consist of a TP/SP contactor for switching direct on line in
accordance with BS EN 60947-4-1 and fitted with auxiliary contacts.
A. Star-delta starters shall be provided with contactors as for DOL starters, arranged in
such a manner to ensure the star contactor opens before the delta contactor closes.
B. The period of running in star and the transition time shall be controlled by adjustable
solid state type timers.
C. For closed transition type star-delta starters, further requirements shall be wire wound
porcelain core resistor banks of sufficient thermal rating to allow three (3) consecutive
starts of 30 seconds starting period followed by a 15 minutes rest and another 30
seconds starting period. Resistance value shall be chosen to give high starting current
with low transient current. A thermal cut out shall be provided for transient resistor
banks. Starter enclosure incorporating resistor banks shall be well ventilated with
vermin proof and dust ventilation louvers.
B. The starters shall use the current limit method of starting with the current adjustable
between 150 percent and 425 percent of full load current of the motor. At turn-on, the
control ramps up to the current limit in approximately 1 second and maintains that
current until the motor comes up to full speed. If a problem exists and the motor fails to
reach rated speed within a predetermined period of time, the control will shut down. The
starter shall provide a smooth, step less acceleration and deceleration of the load from
start to full speed and from full speed to stop. The starter shall be equipped with metal
oxide varistor type surge suppressers across the SCR to protect against voltage
transients and resistor/capacitor scrubber networks to protect against false firing of the
SCR. Each SCR heat sink shall have a temperature sensor that shall shut the starter
down in the event of an over temperature condition. When a starter failure occurs, the
actual problem shall be indicated by an LED on the control panel front.
C. There shall be an overcurrent protective device, which shall provide over current
protection and main disconnect function for the control unit. The position of the
operating handle shall indicate “ON” or “OFF” position of the protective device and
include provision for padlocking in the “OFF” position. This protective device shall be
equipped with a shunt trip and shall trip when there is a SCR or plant power failure.
Motor space heaters shall be energized when the motor is not running.
D. The reduced voltage starters shall be equipped with micro-processor controlled motor
protection relays to control, monitor and protect the motors. The relay shall monitor
three phase current and voltage and make trip and alarm decisions based on pre-
programmed motor current and voltage conditions. Control functions shall include start
detection, starter transition, incomplete sequence and number of starts per hour. The
relay shall monitor and display load current of each phase, percent of full load current of
each phase and running time. The relay shall protect the motor against time
overcurrent, instantaneous overcurrent, under load, phase unbalance, earth fault, phase
loss and phase reversal.
2.06 ENCLOSURES
2.07 ACCESSORIES
F. Meters: Panel type, 64-mm minimum size with 90- or 120-degree scale and plus or
minus 2 percent accuracy. Where indicated, provide transfer device with an off position.
Meters shall indicate the following:
1. Ammeter: Output current, with current sensors rated to suit application.
2. Voltmeter: Output voltage.
3. Frequency Meter: Output frequency.
H. Phase-Failure and under voltage relays: Solid-state sensing circuit with isolated output
contacts for hard-wired connection. Provide adjustable under voltage setting.
PART 3 - EXECUTION
A. Examine areas and surfaces to receive enclosed controllers for compliance with
requirements, installation tolerances, and other conditions affecting performance.
1. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.02 APPLICATIONS
A. Select features of each enclosed controller to coordinate with ratings and characteristics
of supply circuit and motor; required control sequence; duty cycle of motor, controller,
and load; and configuration of pilot device and control circuit affecting controller
functions.
3.03 INSTALLATION
A. For control equipment at walls, bolt units to wall or mount on lightweight structural-steel
channels bolted to wall. For controllers not at walls, provide freestanding racks
complying with Division 26 Section "Hangers and Supports for Electrical Systems."
D. Enclosed Controller Fuses: Install fuses in each fusible switch. Comply with
requirements in Division 26 Section "Fuses."
A. Coordinate size and location of concrete bases. Verify structural requirements with
structural engineer.
B. Concrete base is specified in Division 26 Section "Hangers and Supports for Electrical
Systems," and concrete materials and installation requirements are specified in
Division 03.
3.05 IDENTIFICATION
3.07 CONNECTIONS
C. Perform the following field tests and inspections and prepare test reports:
1. Perform each electrical test and visual and mechanical inspection, except
optional tests, Motor Control - Motor Starters. Certify compliance with test
parameters.
2. Correct malfunctioning units on-site, where possible, and retest to demonstrate
compliance; otherwise, replace with new units and retest.
3.09 ADJUSTING
3.10 TRAINING
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the lightning protection installation shall consist of air termination
network, down conductors, earthing and bonding to prevent side flashing.
1.02 SUBMITTALS
C. Qualification data for firms and persons specified in "Quality Assurance" Article to
demonstrate their capabilities and experience.
1.04 REFERENCE
A. BSEN 62305 (Part 1 to 4): 2011: British Standards for Lightning Protection
1.05 COORDINATION
KEO/21-7387-0004 26 4113 / 1 Lightning Protection For Structures
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
A. Coordinate installation of lightning protection with installation of other building systems
and components, including electrical wiring, supporting structures and building
materials, metal bodies requiring bonding to lightning protection components, and
building finishes.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Subject to compliance with the requirements of the Contract Documents, products to be
provided shall be from the manufacturer listed in the section 26 9000 - Approved
Manufacturer vendor List - Electrical.
A. The Specialist Lightning Protection Installer shall submit the Risk Evaluation and the
achieved Lightning Protection Level (LPL) calculation based on BS EN 62305 – Part 2.
In the absence of such an evaluation employment of LPL - I will be deemed mandatory.
The Specialist Lightning Protection Installer shall then submit the shop drawings based
on the achieved LPL and shall employ the air termination network consisting of mesh of
either 5m x 5m or less, in co-ordination with rolling sphere (size as per the protection
level). All the service entries to the structure i.e. power line, telecom line, gas line, water
line etc. shall be protected by installing current surge protectors (either 25KA or
18.75KA or 12.5 KA rating), depending on the Lightning Protection Level (LPL) to be
used to bring down the risk (R) below the tolerable risk level ( RT ).
B. The Specialist Lightning Protection Installer shall use 25x3 mm bare copper tape of
99.99% purity (complying with BS EN 13601), (or PVC coated as the case may require,
complying with the same) to form the air-termination mesh on the uppermost part of the
structure (typically the roof) and ring conductor around the structure (the spacing
between the ring conductors shall depend on the size of the rolling sphere) to prevent
from side flashes.
C. Air termination network should be extended and it’s determined by using rolling sphere
method.
E. Typically, if LPL I is employed, then the first horizontal conductor shall be at 20m level
(from ground). From 20m to 120m, horizontal conductors shall be installed at every 20
meters or every 5 floors. From 120m up to 400 meters, horizontal conductors/strike
pads shall be installed at every 10 meters or every 3 floors, from 400 meters and above,
the horizontal conductors / strike pads shall be installed at every 5 meters or every floor.
However, if the structure is more than 120m in height then the top 20% of the building
height is protected using ring conductors / strike pads every floor and then follow the
above rule.
F. Based on the above the Specialist Lightning Protection Installer shall use 25x3mm
copper tape as ring conductor and this tape should be bonded to all down conductors
around the periphery and a branch conductor to be taken horizontally and all these
down conductors to be bonded to the aluminum cladding wall using bi-metallic clamps.
G. Any roof (e.g. staircase) on top of the main roof shall have air termination network and it
shall be connected to lower roof network.
H. All the fixing clips for the copper tape shall be metallic (complying with Class ‘H’ of the
electrical testing based on BSEN 50164) and shall be fixed at an interval of 500mm
(1000 mm fixing distance for fixing conductors on vertical surface up to 20m from the
ground level and on the horizontal surface i.e. roof).
I. The down conductors shall be placed around the periphery of the building. A minimum
of two re-enforcing bars shall be used as down conductors in each column. The
minimum overlap dimension to connect two re-bars shall be at least 20 times the
diameter of the re-bar. If it not practical to arc-weld two re-bars then suitable clamps
should be used at a distance of each 10cm till the above dimension is achieved. Re-
enforcement bars in the designated columns should be used as down conductors, with a
suitable junction box to be recessed at approx. 500mm above the ground for the test
link.
J. The electrical continuity of the reinforcing bars shall be determined by electrical testing
between the uppermost part and the ground level. The overall electrical resistance
should not be greater than 0.2 , measured using test equipment suitable for this
purpose. If this value is not achieved, or it is not practical to conduct such testing, the
reinforcing bar shall not be used as a natural down conductor.
K. The composite glass panel shall be bonded to all the down conductors at the various
slab levels as per the rolling sphere spacing by using bi-metallic clamps complying to
BSEN 50164.
L. The earthing shall be done as per local authorities requirements. A minimum of 2400
mm solid copper electrode shall be provided with each down conductor separately.
However, the Specialist Lightning Protection Installer shall submit the calculation for
deciding the number of earth rods in each earth pit. Wherever the soil resistivity is low
(typically below <20 m), the Specialist Lightning Protection Installer must use either
solid copper rods or stainless steel rods to ensure the longitivity of the earth termination
network.
O. The terminated head of each electrode shall be located in a light weight inspection pit. If
clear earth is not available, then the Specialist Lightning Protection Installer has to install
the earth pit inside the building using double flange earth electrode seals.
P. The double flange earth seals should be designed for use in concrete slabs of nominal
thickness from 300mm to 5000mm thick, the seal will withstand water pressure up to 80
psi equal to a 55 meter head of water. The earth seal flange shall be free from dust /
debris, grease/paint before pouring of the concrete. A specialist installer should be
employed to do the installation or shall be done under the supervision of the
manufacturer or the manufacturer’s authorized representative.
Q. Specialist Lightning Protection Installer also has to ensure, based on BSEN 62305 – IV,
that suitable co-ordinated over-voltage surge protection devices with an extra low let –
through voltage are used for protecting any terminal devices i.e. DBs feeding critical
services or even the local critical electrical gadget.
R. All metallic parts protruding outside the extended air termination network (e.g. balcony
hand rails etc) shall be connected to the air termination using suitable clamps (material
complying to BSEN 50164) at every floor wherever the horizontal conductor is applied.
The equipment on the roof (i.e. Chiller units etc.) shall be protected using vertical air
terminals of suitable height so that it provides the zone of protection. This air terminal
shall be installed at a suitable separation distance so that the partial lightning current
doesn’t flow through the equipment. The cable from the equipment shall be protected
using an over – voltage protector. The equipment shall not be bonded to the air
termination network. Specialist Lightning Protection Installer shall give the calculation of
the suitable separation distance.
S. The Specialist Lightning Protection Installer shall install suitable surge protectors at local
power distribution boards feeding vulnerable equipment, in order to protect these
against transients generated downstream of the protectors in 1, above. (These
transients may be the result of inductive coupling or electrical switching.)
U. Protectors for a given Location Category shall be rated for a High Exposure Level (as
defined by BS EN 62305 - 4), unless contrary information is available.
V. The protector must not interfere with or restrict the system’s normal operation. It should
not:
1. corrupt the normal mains power supply
2. break or shutdown the power supply during operation
KEO/21-7387-0004 26 4113 / 4 Lightning Protection For Structures
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
3. have an excessive earth leakage current.
W. The protector shall be rated for a peak discharge current of no less than 10kA (8/20:s
waveform) between any two conductors (phase to neutral, phase to earth and neutral to
earth).
X. The protector shall limit the transient voltage to below equipment susceptibility levels.
Unless otherwise stated, the peak transient let-through voltage shall not exceed 600
volts, for protectors with a nominal working voltage of 230 or 240 volts, when tested in
accordance with BS EN 62305 Part - 4 (6kV 1.2/50 µs open circuit voltage, 3kA 8/20µs
short circuit current).
Y. This peak transient let-through voltage shall not be exceeded for all combinations of
conductors:
1. phase to neutral
2. phase to earth
3. neutral to earth.
AA. Remove indication of status (including loss of phase/supply) should also be possible via
a volt free contact.
BB. The status indication should warn of protection failure between all combinations of
conductors, including neutral to earth. (Otherwise a potentially dangerous short circuit
between neutral and earth could go undetected for some time.) This should include
early warning of excessive neutral to earth voltages.
CC. The protector shall be supplied with detailed installation instructions. The installer must
comply with the installation practice detailed by the protector manufacturer.
DD. The Specialist Lightning Protection Installer shall also install transient overvoltage
protectors on all data communication/signal/telephone lines in order to protect
equipment connected to the line, against transient overvoltage. (Where data lines link
equipment in separate buildings, transient overvoltage protectors should be installed at
both ends of the line in order to protect both pieces of equipment.)
FF. Protectors shall be rated for Location Category - High Exposure Level (as defined by BS
EN 62305 – 4: 2011), unless contrary information dictates a lower Exposure Level.
GG. The protector must not impair the system’s normal operation. It should not suppress the
system’s normal signal voltage
HH. The protector will have a low transient let-through voltage for tests conducted in
accordance with BS en 62305 -4: 2011 (5kV 10/700µs test).
II. This let-through performance will be provided for all combinations of conductors:
1. signal line to signal line
2. signal line to screen/earth.
JJ. The protector shall be rated for a peak discharge current of 10kA.
KK. The protector shall be supplied with detailed installation instructions. The installer must
comply with the installation practice detailed by the protector manufacturer.
LL. The protector manufacturer should allow for the facility to mount and earth large
numbers of protectors through an accessory combined mounting and earthing kit.
2.03 MATERIALS
A. Materials shall comply in weight, size and composition with the requirements of BS EN
50164.
B. All surge protection devices to be used shall be from the same manufacturer who
supplies the structural lightning protection.
C. Surge protectors shall be manufactured for the specific type and voltage of the electrical
service and shall provide clamping for both normal (L-N) and common (L-N-G) mode
protection.
A. Lightning Protection Installer shall ensure proper co-ordination between the Structural,
Civil, Electrical and the Cladding contractor
B. All installation details shall be agreed with the Engineer prior to commencement of work.
The Specialist Lightning Protection Installer shall obtain an inspection certificate from
the manufacturer or its authorized representative towards the satisfactory installation of
the system and that proper material in accordance to the above standard has been
used.
D. For structures taller than 30 meters, the specialist lightning Protection installer shall
install the equipotential bonding at either the basement or the ground level and then
every 20 meters floor thereafter. Wherever protection of internal systems against over-
voltages caused by lightning discharge requires SPDs, these shall conform to BSEN
62305 – Part 4.
E. The gas, water and other metallic systems shall all be bonded directly to the equi-
potential bar located inside but close to the outer wall near the ground floor or basement
level. The power cable shall be bonded to the equi-potential bonding bar via a suitable
SPD. The screen of the antenna cable or any shielded power supply shall also be
bonded to the equipotential bar.
F. Service entry SPDs are for metallic electrical services only - gas and water do not fall
under this category. Metallic gas and water need to be directly bonded. The service
entry data and telecom lines can handle 2.5kA (10µs/350 µs) per line, so the specialist
lightning protection installer shall provide suitable SPDs in accordance to the above
specification as per the BSEN 62305 – Part 4
G. Since the service entrance SPDs are designed to protect against dangerous sparking
only as per BS EN 62305-3. The specialist lightning protection installer shall need to fit
additional protection at the sub-distribution and near equipment to protect electronic
equipment to BS EN 62305-4. Both types of SPD are a required in accordance with this
BS EN standard if the risk assessment demands this.
H. The bonding bar shall be located close to the main distribution board and shall be
connected to earth termination network at ≤ 1 ohm, with a very short length conductor
not exceeding 10 meters in length.
J. All the bonding bars at different levels shall be connected to each other, which in-turn is
earthed at 1 ohm.
PART 3 - EXECUTION
3.01 INSTALLATION
B. Install conductors with direct paths from air terminals to ground connections. Avoid
sharp bends and narrow loops.
D. System conductors.
E. Down conductors.
F. Interior conductors.
KEO/21-7387-0004 26 4113 / 7 Lightning Protection For Structures
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
G. Conductors within normal view from exterior locations at grade within 60 m of building.
3.02 TESTING
A. On completion of the installation or of any modification to it, the following isolated and
combined measurement and / or checks has to be made and the results recorded in a
lightning protection system logbook.
B. The resistance to earth of each local earth electrode and in addition the resistance to
earth of the complete earth termination system.
C. Each local earth electrode has been measured in isolation and the test point between
the down conductor and the earth electrode in the disconnected position (isolated
measurement)
D. A further measurement has to be taken with the test point in the connected position
(combined measurement)
E. The results of visual check of all conductors, bonds and joints and their measured
electrical continuity.
F. If the resistance to earth of a lightning protection system exceeds 10 ohms, the value
must be reduced. Necessary remedial action needs to be taken to reduce the value
below or equal to 10 ohms.
H. The manufacturer or the manufacturer’s authorized representative will certify the bill of
materials, provided by the Specialist Lightning Protection Installer for the project.
I. The Specialist Lightning Protection Installer must submit the Test Certificates of the
materials used as per BSEN 50164, which should be attested in original by the
manufacturer or the manufacturer’s authorized representative.
3.03 RECORDS
A. The person has to keep on site or the following records, responsible for the upkeep of
the installation:
1. Approved shop drawings, showing the nature, dimensions, materials and position
of all component parts of the lightning protection system.
3.04 MAINTENANCE
A. The periodic inspections and tests recommended will show what maintenance, if any is
needed. Tests have to be repeated at fixed intervals, as mentioned in the BSEN 62305
– Part III.
END OF SECTION
INTERIOR LIGHTING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUBMITTALS
A. Product Data: For each type of lighting fixture, arranged in order of fixture designation.
Include data on features, accessories, finishes, and the following:
1. Physical description of lighting fixture including dimensions.
2. Emergency lighting units including battery and charger.
3. Ballast.
4. Energy-efficiency data.
5. Life, output, and energy-efficiency data for lamps.
6. Photometric data, in IESNA or lumdat format, based on laboratory tests of each
lighting fixture type, outfitted with lamps, ballasts, and accessories identical to
those indicated for the lighting fixture as applied in this Project.
a. For indicated fixtures, photometric data shall be certified by a qualified
independent testing agency. Photometric data for remaining fixtures shall
be certified by the manufacturer.
C. Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale, on
which the following items are shown and coordinated with each other, based on input
from installers of the items involved:
1. Lighting fixtures.
2. Suspended ceiling components.
3. Structural members to which suspension systems for lighting fixtures will be
attached.
D. Samples for Verification: Interior lighting fixtures designated for sample submission in
Interior Lighting Fixture Schedule. Each sample shall include the following:
1. Lamps: Specified units installed.
2. Accessories: Cords and plugs.
E. Product Certificates: For each type of ballast for bi-level and dimmer-controlled fixtures,
signed by product manufacturer.
G. Operation and Maintenance Data: For lighting equipment and fixtures to include in
emergency, operation, and maintenance manuals.
B. Comply with Civil Defence requirements for the supply and installation of the
emergency and exit lights.
1.04 COORDINATION
A. Coordinate layout and installation of lighting fixtures and suspension system with other
construction that penetrates ceilings or is supported by them, including HVAC
equipment, fire-suppression system, and partition assemblies.
1.06 COMMISSIONING
A. Contractor to comply with the Estidama Requirements for the commissioning process
planning, execution and documentation with accordance to the Estidama IDP: R3 –
Basic Commissioning and IDP 5: Re-commissioning and as detailed in the Estidama
Design Commissioning Plan Developed by the Project Independent Commissioning
Authority”
B. Seismic Performance: Luminaires and lamps shall be labeled vibration and shock
resistant.
C. The term "withstand" means "the luminaire will remain in place without separation of any
parts when subjected to the seismic forces specified and the luminaire will be fully
operational during and after the seismic event."
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. In Luminaires Schedule and Lighting Cut sheets where titles below are column or row
headings that introduce lists, the following requirements apply to product selection:
1. Available Manufacturers: Subject to compliance with requirements,
manufacturers offering products that may be incorporated into the Work include,
but are not limited to, manufacturers specified.
2. Refer to the Luminaire schedule for the specified light fittings.
2.02 LAMPS
A. General:
1. Lamps shall be furnished and installed in all luminaires covered under the
Contract
2. Lamps used for temporary lighting services shall not be utilized in the final use in
fixture units
3. Lamps for permanent installation shall not be placed in the fixtures until so
directed, and this shall be accomplished directly before the building areas are
ready for occupancy by the Employer
4. Lumen output of lamps shall be in accordance with BS EN 5225
5. Generally, high output, low consumption, tri-phosphorus lamps shall be used,
unless otherwise indicated.
2.03 LUMINAIRES
B. All lamps/drivers shall be of modular type which could be replaced in the future.
C. All lighting fittings shall be supplied complete with appropriate control gear where
necessary, lamps, mounting and fixing accessories etc. whether explicitly mentioned in
the description of each light fitting or not. All the fittings shall have the same
appearance, material, technical details and approximate dimensions.
D. Luminaires shall be connected to the main circuit wiring with heat resistant flexible
cables of a minimum conductor size of 1.5 mm2 insulated with silicon rubber.
E. Break joint rings shall be used in conjunction with batten holders, ceiling roses or back
plates mounted onto a flush installation.
G. All lamp-holders for flexible pendants shall be of the all insulated skirted pattern with
code grips and for batten or wall mounting shall be of similar pattern. All lamp holders
shall be of the bayonet cap pattern.
H. The point box suspensions and other parts of the lighting fittings shall be provided to be
erected at festival time to suit the building programme for decoration as per the
requirements of the Project Documentation.
I. The glassware diffusers, shades and lamps shall not be fitted until all building work is
complete.
J. All fittings shall be easy to clean inside and outside, when mounted.
2.04 TERMINATION/EARTHING
A. Fused terminal blocks shall be fitted and be of sufficient capacity for the wiring involved.
Each terminal shall be capable of accommodating two 2.5 mm2 conductors.
B. Connector strip terminals shall have a current rating not less than the rating of the circuit
protective device and shall be encapsulated in self-extinguishing grade polyethylene.
C. Where connector strips are provided in boxes behind heat producing appliances,
porcelain connectors shall be used where temperatures in excess of 70 °C are likely.
D. Conductors shall be clamped between metal surfaces such that no screws make direct
contact with the conductor. The metal used in construction of the connector shall be at
least 85 °C copper alloy such that good conductivity and electrolytic compatibility are
maintained at all times.
E. All light fittings shall be provided with earthing terminal which shall be connected to the
earth continuity lead of the final sub-circuit.
KEO/21-7387-0004 26 5100 / 4 Interior Lighting
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
F. The earthing of all pendant or semi-pendant fittings shall be by a separate core in the
connecting flex or cable securely bonding the earth terminal on the fitting to the glanded
joint of interconnecting cables. In no case shall pendant chains or conduit support tubes
be used as a means of earthing.
B. Luminaires installed in false ceilings shall be connected to the lighting circuit using
mechanically coupled plug-in ceiling roses.
C. Luminaires shall be positioned to provide ease of access for maintenance, cleaning etc.,
while not impairing the distribution of light.
D. The Contractor shall ensure that the luminaire manufacturer has the correct details of
the ceiling system, including suspension, tiles, etc. He shall ensure that the luminaires
are supplied with the correct trim, suspension system and are fully compatible with the
ceiling system.
A. Comply with requirements in Section "Hangers and Supports for Electrical Systems" for
channel and angle iron supports and nonmetallic channel and angle supports.
B. Single-Stem Hangers: 1/2-inch (13-mm) steel tubing with swivel ball fittings and ceiling
canopy. Finish same as luminaire.
E. Hook Hangers: Integrated assembly matched to luminaire, line voltage, and equipment
with threaded attachment, cord, and locking-type plug.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Lighting fixtures: Set level, plumb, and square with ceilings and walls. Install lamps in
each fixture.
A. Terminations:
1. General light fittings mounted direct to conduit outlet boxes shall have the circuit
wiring run direct to the fittings terminal position. Flexible conduit pigtail shall be
provided for all fixtures to J-boxes
2. Terminations for recessed, or semi-recessed pattern fittings fitted in false
ceilings, shall have the circuit-wiring terminal above the ceiling in a ceiling rose.
Outlets shall be mounted adjacent to the fitting connected by silicone cable of
minimum 1.5mm2, BS 6500 compliant.
B. Installation of Lamps
1. Generally, install new lamps in all luminaires at substantial completion of work.
D. ADJUSTING
1. Verify with Owner that adjusting service is required for Project.
2. Occupancy Adjustments: When requested within 12 months of date of
Substantial Completion, provide on-site assistance in adjusting the direction of
aim of luminaires to suit occupied conditions. Make up to two visits to Project
during other-than-normal hours for this purpose. Some of this work may be
required during hours of darkness.
END OF SECTION
EXTERIOR LIGHTING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUBMITTALS
A. Product Data: For each luminaire, pole, and support component, arranged in order of
lighting unit designation. Include data on features, accessories, finishes, and the
following:
1. Physical description of luminaire, including materials, dimensions, effective
projected area, and verification of indicated parameters.
2. Details of attaching luminaires and accessories.
3. Details of installation and construction.
4. Luminaire materials.
5. Photometric data based on laboratory tests of each luminaire type, complete with
indicated lamps, ballasts, and accessories.
a. For indicated luminaires, photometric data shall be certified by a qualified
independent testing agency. Photometric data for remaining luminaires
shall be certified by manufacturer.
6. Photoelectric relays.
7. Ballasts, including energy-efficiency data.
8. Lamps, including life, output, and energy-efficiency data.
9. Materials, dimensions, and finishes of poles.
10. Means of attaching luminaires to supports, and indication that attachment is
suitable for components involved.
11. Anchor bolts for poles.
12. Manufactured pole foundations.
B. Shop Drawings:
1. Anchor-bolt templates keyed to specific poles and certified by manufacturer.
C. Samples for Verification: For products designated for sample submission in Exterior
Lighting Device Schedule. Each sample shall include lamps and ballasts.
E. Operation and Maintenance Data: For luminaires and poles to include in emergency,
operation, and maintenance manuals.
A. Retain factory-applied pole wrappings on metal poles until right before pole installation.
For poles with nonmetallic finishes, handle with web fabric straps.
1.05 COMMISSIONING
A. Contractor to comply with the Estidama Requirements for the commissioning process
planning, execution and documentation with accordance to the Estidama IDP: R3 –
Basic Commissioning and IDP 5: Re-commissioning and as detailed in the Estidama
Design Commissioning Plan Developed by the Project Independent Commissioning
Authority”
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. In Luminaires Schedule and Lighting Cut sheets where titles below are column or row
headings that introduce lists, the following requirements apply to product selection:
1. Available Manufacturers: Subject to compliance with requirements,
manufacturers offering products that may be incorporated into the Work include,
but are not limited to, manufacturers specified.
2. Refer to the Luminaire schedule for the specified light fittings.
2.02 LUMINAIRES
A. Supply and install complete in place including but not limited to, control gears, lamps,
supports, concrete pads, earth electrodes, cables and all other necessary items for the
2.03 LAMPS
A. General:
1. Lamps shall be furnished and installed in all luminaires covered under the
Contract
2. Lamps used for temporary lighting services shall not be utilized in the final use in
fixture units
3. Lamps for permanent installation shall not be placed in the fixtures until so
directed, and this shall be accomplished directly before the building areas are
ready for occupancy by the Employer
4. Lumen output of lamps shall be in accordance with BS EN 5225
5. Generally, high output, low consumption, tri-phosphorus lamps shall be used,
unless otherwise indicated.
PART 3 - EXECUTION
B. Install on concrete base with top 100 mm above finished grade or surface at bollard
location. Cast conduit into base, and shape base to match shape of bollard base.
Finish by troweling and rubbing smooth. Concrete materials, installation, and finishing
are specified in Division 03 Section "Cast-in-Place Concrete."
A. Aluminum: Do not use in contact with earth or concrete. When in direct contact with a
dissimilar metal, protect aluminum by insulating fittings or treatment.
3.04 GROUNDING
A. Ground metal poles and support structures according to Division 26 Section "Grounding
and Bonding for Electrical Systems."
1. Install grounding electrode for each pole, unless otherwise indicated.
2. Install grounding conductor pigtail in the base for connecting luminaire to
grounding system.
A. Inspect each installed fixture for damage. Replace damaged fixtures and components.
3.06 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B. Subject to compliance with the requirements of the Contract Documents, the warranty
and spare parts shall include but not limited to the list below:
DIVISION 26 - ELECTRICAL
- Warranty period is from taking over certificate to the client; parts, labour, travel
time expenses included are included.
- Bidder is to provide a schedule of spares as part of the submission and include
delivery to site.
- Routine maintenance visits as recommended by the Manufacturer
recommendation during the defect notification period.
- Basic and advance training courses for FM staff are required.
- For items not mentioned in this warranty list, shall be covered under manufacturer
standard warranty.
-
2 years or
LOW VOLTAGE
Standard
ELECTRICAL POWER All spare parts required during
26 0519 Manufacturers’
CONDUCTORS AND warranty period as per
warranties
CABLES manufacturer recommendation
whichever is
greater
2 years or
GROUNDING AND Standard
All spare parts required during
26 0526 BONDING FOR Manufacturers’
warranty period as per
ELECTRICAL warranties
manufacturer recommendation
SYSTEMS whichever is
greater
2 years or
HANGERS AND Standard
All spare parts required during
26 0529 SUPPORTS FOR Manufacturers’
warranty period as per
ELECTRICAL warranties
manufacturer recommendation
SYSTEMS whichever is
greater
2 years or
RACEWAY AND Standard
All spare parts required during
26 0533 BOXES FOR Manufacturers’
warranty period as per
ELECTRICAL warranties
manufacturer recommendation
SYSTEMS whichever is
greater
2 years or
Standard
CABLE TRAYS FOR All spare parts required during
26 0536 Manufacturers’
ELECTRICAL warranty period as per
warranties
SYSTEMS manufacturer recommendation
whichever is
greater
2 years or
Standard
IDENTIFICATION FOR All spare parts required during
26 0553 Manufacturers’
ELECTRICAL warranty period as per
warranties
SYSTEMS manufacturer recommendation
whichever is
greater
2 years or
Standard All spare parts required during
LIGHTING CONTROL Manufacturers’
26 0923 warranty period as per
DEVICES warranties manufacturer recommendation
whichever is
greater
1.01 GENERAL
DIVISION 26 ELECTRICAL
26 0519 Low-Voltage DUCAB UAE
Electrical Power BAHRA Cables KSA
Cables and NUHAS CABLES Oman
Conductors JEDDAH CABLES KSA
ELSEWEDY CABLES Egypt
BAHRA CABLES KSA
OMAN CABLES Oman
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes:
1. 19-inch equipment cabinets.
2. Power strips.
3. Grounding.
4. Labeling.
B. Related Requirements:
1. Section 26 0526 "Grounding and Bonding for Electrical Systems"
2. Section 26 0529 "Hangers and Supports for Electrical Systems"
3. Section 26 0533 "Raceways and Boxes for Electrical Systems"
4. Section 26 0536 "Cable Trays for Electrical Systems".
5. Section 27 1323 “Communications Optical Fiber Backbone Cabling”
6. Section 27 1513 "Communications Copper Horizontal Cabling"
1.02 DEFINITIONS
A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.
A. Qualification Data: For qualified layout technician, installation supervisor, and field
inspector.
1.08 COORDINATION
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - A. PRODUCTS
2.02 All installation shall be as per UTT Guideline & Service Provider Guidelines
C. Cable Management:
1. Metal, with integral wire retaining fingers.
2. Baked-polyester powder coat finish.
3. Vertical cable management panels shall have front and rear channels, with
covers.
4. Provide horizontal crossover cable manager at top of each relay rack, with a
minimum height of two rack units each.
A. ONU shall be provided as per UTT Guideline & Service Provider Guidelines
A. Comply with requirements in Division 26 Section "Grounding and Bonding for Electrical
Systems." for grounding conductors and connectors.
2.07 LABELING
A. Comply with ANSI/TIA-606-B for a system of labeling materials, including label stocks,
laminating adhesives, and inks used by label printers.
PART 3 - EXECUTION
C. Install buried entrance pathway complying with Division 26 Section "Raceway and
Boxes for Electrical Systems."
3.02 INSTALLATION
A. Comply with BICSI TDMM for layout and installation of communications equipment
rooms.
B. Bundle, lace, and train conductors and cables to terminal points without exceeding
manufacturer's limitations on bending radii. Install lacing bars and distribution spools.
3.03 FIRESTOPPING
3.05 TRAINING
C. Obtain employers staff signatures for attendance and submit as a record that the
training has been completed and to the satisfaction of the employer.
D. Distribute copies of the operation and maintenance manuals during the training and go
thru the content in details. Please note the copies distributed during the training are not
the official copies to submitted for close out purposes.
E. Schedule training with the Employer, through Engineer, with at least 14 days' advance
notice.
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes:
1. Category 6a twisted pair cable.
2. Twisted pair cable hardware, including plugs and jacks.
3. Cabling identification products.
4. Grounding provisions for twisted pair cable.
5. Source quality control requirements for twisted pair cable.
B. Related Requirements:
1. Section 26 0533 "Raceways and Boxes for Electrical Systems"
2. Section 27 1116 “Communications Racks, Frames, and Enclosures”
3. Section 27 1323 “Communications Optical Fiber Backbone Cabling”
1.02 DEFINITIONS
A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.
A. Horizontal cable cabling system shall provide interconnections between Floor Distributor
and the equipment outlet, in the telecommunications cabling system structure. Cabling
system consists of horizontal cables, intermediate and main cross-connects, mechanical
terminations, and patch cords or jumpers used for horizontal-to-horizontal cross-
connection.
1. Horizontal cabling shall contain no more than one transition point or consolidation
point between the horizontal cross-connect and the telecommunications
equipment outlet.
2. Bridged taps and splices shall not be installed in the horizontal cabling.
B. The maximum allowable horizontal cable length is 90 m. This maximum allowable length
does not include an allowance for the length of 4.9 m to the workstation equipment or in
the horizontal cross-connect.
D. Samples: For telecommunications jacks, jack assemblies and plugs, in specified finish,
one for each size and outlet configuration and faceplates for color selection and
evaluation of technical features.
1.11 COORDINATION
D. Coordinate racks locations with other systems equipment that might be sharing the
same room in order to insure efficient use of the shared space.
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
PART 2 - PRODUCTS
2.03 PATHWAYS
C. Cable Trays:
1. Basket Cable Trays: 50 mm deep. Wire mesh spacing shall not exceed 50 by 100
mm.
D. Conduit and Boxes: Comply with requirements in Division 26 Section "Raceway and
Boxes for Electrical Systems. Flexible metal conduit shall not be used.
1. Outlet boxes shall be no smaller than 50 mm wide, 75 mm high, and 64 mm deep.
2. Use metric units.
B. Horizontal cabling
A. Description: Hardware designed to connect, splice, and terminate twisted pair copper
communications cable.
C. Source Limitations: Obtain twisted pair cable hardware from same manufacturer as
twisted pair cable, from single source.
D. Connecting Blocks:
1. 110-style IDC for Category 6a.
2. Provide blocks for the number of cables terminated on the block, plus 25 percent
spare, integral with connector bodies, including plugs and jacks where indicated.
3. Number of Terminals per Field: One for each conductor in assigned cables.
E. Patch Panel: Modular panels housing numbered jack units with IDC-type connectors at
each jack location for permanent termination of pair groups of installed cables.
1. Features:
a. Universal T568A and T568B wiring labels.
b. Labeling areas adjacent to conductors.
c. Replaceable connectors.
J. Legend:
1. Machine printed, in the field, using adhesive-tape label.
2. Snap-in, clear-label covers and machine-printed paper inserts.
A. Provide hook and loop tape, 13mm Wide and of a length equal to 130% of the
circumference of the cable bundle.
C. When used in areas considered environmental air space, all bundling materials shall be
appropriately listed.
D. Cable bundles shall not to be over tightened such that deformation occurs to the original
geometry of the cables. Such practice will be rejected and damaged cables shall be
replaced at the Contractor’s cost.
B. Distribution Rings shall be integral to all wall mounted connecting/termination blocks and
shall be of the same type and manufacture of the terminal blocks.
D. Trough Covers shall be provided for covering the patch cord field.
2.08 GROUNDING
A. Comply with requirements in Division 26 Section "Earthing and Bonding for Electrical
Systems." for grounding conductors and connectors.
C. Cable will be considered defective if it does not pass tests and inspections.
PART 3 - EXECUTION
A. Wiring Method: Install cables in raceways and cable trays except within consoles,
cabinets, desks, and counters. Conceal raceway and cables except in unfinished
spaces.
1. Install plenum cable in environmental air spaces, including plenum ceilings.
B. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors
where possible.
C. Wiring within Enclosures: Bundle, lace, and train cables to terminal points with no
excess and without exceeding manufacturer's limitations on bending radii. Provide and
use lacing bars and distribution spools.
A. Comply with requirements for demarcation point, pathways, cabinets, and racks
specified in Division 27 Section " Communications Racks, Frames, and Enclosures."
Drawings indicate general arrangement of pathways and fittings.
B. Comply with ANSI/TIA-569-D for pull-box sizing and length of conduit and number of
bends between pull points.
C. Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical
Systems" for installation of conduits and wireways.
C. Open-Cable Installation:
1. Install cabling with horizontal and vertical cable guides in telecommunications
spaces with terminating hardware and interconnection equipment.
2. Suspend copper cable not in a wireway or pathway a minimum of 200 mm above
ceilings by cable supports not more than 1500 mm apart.
3. Cable shall not be run through structural members or in contact with pipes, ducts,
or other potentially damaging items.
3.04 FIRESTOPPING
3.05 GROUNDING
C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall
allowing at least 50-mm clearance behind the grounding bus bar. Connect grounding
bus bar with a minimum 25mm2 grounding electrode conductor from grounding bus bar
to suitable electrical building ground.
D. Bond metallic equipment to the grounding bus bar, using not smaller than 16mm2
equipment grounding conductor.
3.06 IDENTIFICATION
E. Cable Schedule: Post in prominent location in each equipment room and wiring closet.
List incoming and outgoing cables and their designations, origins, and destinations.
Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final
comprehensive schedules for Project.
F. Cabling Administration Drawings: Show building floor plans with cabling administration-
point labeling. Identify labeling convention and show labels for telecommunications
closets, backbone pathways and cables, entrance pathways and cables, terminal
hardware and positions, horizontal cables, work areas and workstation terminal
positions, grounding buses and pathways, and equipment grounding conductors.
H. Labels shall be preprinted or computer-printed type with printing area and font color that
contrasts with cable jacket color but still complies with requirements in ANSI/TIA-606-B.
1. Cables use flexible vinyl or polyester that flex as cables are bent.
C. Data for each measurement shall be documented. Data for submittals shall be printed in
a summary report that is formatted similarly to Table 10.1 in BICSI's
"Telecommunications Distribution Methods Manual," or shall be transferred from the
instrument to the computer, saved as text files, printed, and submitted.
D. Remove and replace cabling where test results indicate that they do not comply with
specified requirements.
E. End-to-end cabling will be considered defective if it does not pass tests and inspections.
A. The complete installation shall be tested and commissioned by a certified third party
independent of the supplier and the contractor. The contractor shall be responsible to
demonstrate the operation of the system to the satisfaction of the Client's personnel.
The third Party testing agency shall submit the testing and commissioning reports for the
Engineers review outlining all deficiencies and course of action. The contractor shall
ensure all deficiencies outlined are rectified, retested, and certified by the third party
testing agency.
3.09 TRAINING
C. Obtain employers staff signatures for attendance and submit as a record that the
training has been completed and to the satisfaction of the employer.
D. Distribute copies of the operation and maintenance manuals during the training and go
thru the content in details. Please note the copies distributed during the training are not
the official copies to submitted for close out purposes.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
The systems used must, adhere to industry standards, ensure modular and cost-
effective growth, and permit addition of application capacities and processing power
as needed.
C. The contractor shall supply and install the HOME AUTOMATION system suitable to
project requirement as indicated in the specification as well as in drawings.
D. The manufacture shall have local support available through distributor/ system
integrators and local office presence in the country to support their supplier in the local
market.
E. It shall be the contractor’s responsibility to ensure that the equipment installed meets
the specification requirements. Equipment not meeting this performance specification
will not be accepted.
F. All materials, equipment and systems must be state-of-the-art, latest releases and
versions and be generally available in the marketplace. Experimental or prototype
equipment or systems will not be accepted. At the time of system commissioning and
acceptance, all system software must be the latest software release for the software.
This should be demonstrated by way of letter from supplier or manufacturer stating the
current software revision.
G. All user controls of the systems and interfaces, such touch screens, remote controls,
displays, must be intuitive and simple, and require minimal instruction and training.
A. The system shall comprise of a series of source controllers (which may include dimmer
packs, ballast controllers, switch packs, DMX control input and output devices,
blind/curtain controllers and any other applicable units) and user interfaces (which may
include, push button switch plates, Touch screens, time-clocks, , infrared transmitter
and receiver devices, interface units and any other applicable units). The system shall
operate using the international lighting control protocol in communication with
hardware and shall be supplied, tested and commissioned by the system supplier or
his appointed partner.
C. The system shall comprise of a series of source controllers and user interfaces which
shall be connected together on a bus, to form a single networked system. Devices on
the bus shall be connected in a bus topology / daisy chain fashion. The system shall
operate on a ‘broadcast’ messaging basis whereby a command will be broadcast onto
the network, listened to by all of the devices on the network, but only acted upon by
those with the relevant and area and channel address. There shall be no central
memory or processing devices on which the network is entirely dependent. Systems
deploying centralised processors shall not be acceptable.
D. Each component on a network shall have its own non-volatile memory device storing
a record of that device’s address and functionality within the network. Systems
employing battery-backed memory shall not be acceptable. In the event of power
failure each memory device shall hold its memory for a period of at least 10 years.
Devices within each product storing the firmware shall be of a re-programmable
“FLASH” type, thus avoiding the need to replace chipsets for firmware upgrades.
G. The system shall have a facility to upgrade all software automatically on any point of
time.
H. System shall be capable of increasing the number of control functions in the future by
25 percent of current capacity; to include equipment ratings, housing capacities, spare
relays, terminals, number of conductors in control cables, and control software. The
network design and components shall be flexible to allow expansion or reduction in
size at design or post installation with no loss of system capability and no replacement
of network devices due to size or capacity.
1.03 SUBMITTALS
A. Product Data: Prior to the submission of shop drawings, submit to the Engineer full
details, specifications, installation instructions etc. For each item or component part of
the system proposed for use, but in all cases no such item or component part shall be
ordered, delivered or installed without the prior written approval of the Engineer to the
Contractor’s shop drawings incorporating the said items/components. Any material or
B. Sample: Submit to the Engineer samples of each type of product which are going to
be used in the project for review.
C. Shop Drawings: All design layouts provided as part of this tender are for the purpose
of general guidance only. The Contractor is required to submit full design drawings,
shop drawings complete with calculations and catalogues for Engineer’s approval.
C. Quality of Materials: It is not the intention of this specification to provide all details of
design and fabrication. The Contractor shall ensure that the equipment has been
designed and fabricated to good and prevailing commercial practice in accordance
with applicable engineering codes and standards.
D. The equipment shall comply with all relevant proposed and current National, European
and international safety and technical standards for Electrical and Electronic dimming
systems. These will include strict compliance with Electro Magnetic Conduction
(EMC) standards EN50 081-1 and EN50 082-1, Low voltage standard EN60 950 and
RFI Suppression standard EN50 014.
E. All system components shall bear the CE mark to indicate compliance with the above.
B. Submit as-built drawings based on approved shop drawings. List of components and
component data sheets/catalogues.
1.06 QUALIFICATIONS
B. Local Agent: The local agent should have in stock all necessary parts supported with
skillful staff for necessary maintenance.
C. Store in a clean, dry space. Maintain factory wrapping or provide an additional heavy
canvas or heavy plastic cover to protect units from dirt, water, construction debris and
traffic.
D. Handle in accordance with manufacturer’s written instructions. Lift only with lugs
provided for the purpose.
B. All components and their installations shall be free from defects. Any defective
material or workmanship and any resulting damage to work of other trades shall be
replaced or repaired as directed during the Warranty Period at the contactors
expense. Comply with General Conditions, agreeing to repair or replace any
components that have failed within the warranty period.
C. The Contractor shall secure warranties from all equipment suppliers and provide the
Owner with copies of each as part of the “Project Manuals”. Each warranty shall state
that all work performed will be free from defects in materials and workmanship. The
warranty shall state that any defects in workmanship and/or materials appearing in the
work or operation of system or components of system will be corrected without any
additional cost to the Employer.
A. Furnish extra materials as per manufacturer recommendation and that are packaged
with protective covering for storage and identified with labels describing contents.
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
KEO/21-7387-0004 27 5100 / 4 Home Automation System
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
PART 2 - PRODUCTS
A. General:
1. The home automation system and components shall be as per latest UTT
guidelines.
2. All home automation control components shall be compatible with other
elements of light fixtures, ballasts, transformers, and lighting controls.
3. All components and equipment shall be from the reputed specified
manufacturers only.
4. The Programmable Home Automation System shall be designed & developed
in accordance with the European Installation Bus technology (KNX open
protocol system) and shall conform to all the following standards for the building
Automation purpose.
a. ISO/IEC as the International Standard ISO/IEC 14543-3 in 2006.
b. CENELEC as the European Standard EN 50090 in 2003.
c. CEN as EN 13321-1 and EN1332-2 (KNXnet/IP) in 2006.
d. SAC as the Chinese Standard GB/T 20965 in 2007.
e. ANSI/ASHRAE as the US Standard ANSI/ASHRAE 135 in 2005.
5. A two-wire bus cable shall link all sensors and actuators (on/off controllers,
shutter control , Fan coil control , dimming controllers, etc.) to each other. The
bus cable shall be a twisted pair, screened & shielded with solid conductors and
shall be capable of handling information exchange and supplying power to the
bus devices. Separate power supply to any of the sensors and actuators shall
not be acceptable. The bus cable shall be laid in the building in the form of a
linear, star or tree structure similar to the power mains. Systems requiring fixed
wiring configurations shall not be acceptable. All the sensors & actuator devices
shall be coupled to the bus via easy to install 2-wire bus connectors capable of
accepting upto 4 bus connections. Systems requiring crimping, lugging or RJ45
bus connections using CAT 5 UTP or Cat 6 cable shall not be acceptable.
6. The system shall be completely de-centralized and programmable. The
programming shall be implemented via a PC or notebook computer located
anywhere in the system and having access level passwords. Programming via
local system switches or with no password security shall not be acceptable.
Any device in the system shall be accessed for programming from the PC
location without having to manipulate the device locally.
7. The system shall work based on distributed intelligent concept. Systems which
are based on the master slave concept with polling shall not be accepted. All
A. All the Home automation modules such as Relay module, dimmer modules, HVAC
Modules , switches and other controlling elements shall be addressable and
programmable.
B. Output devices for the project (for total number required for the project refer DB
schedule of points / Home automation schematic) shall control manually via the central
capacitive touch technology Display / Timer controller located in the main areas, the
touch screen size should be minimum 7” so that the lettering and buttons will be on
legible size. The Display & control device shall be a flush mounted device or surface
mounted according to project requirement. All timer functions shall be controlled from
this touch screen from the control places and also subject to engineer’s approval. The
touch screen shall also be able to connect directly via IP network. The system shall
have ability to connect with IP cameras to monitor the building IP cameras.
C. It shall also be possible to override each of these control modules manually from the
Home Automation Panel located in the electrical room.
D. These control modules will be located in home automation Panel located (HAP) next
to the distribution boards in the electrical room on each of the floors or according to
project requirement.
E. There shall be multi channel dimmer modules (For number of channels required / DCP
refer DB schedule of points / Home Automation schematic) located in the Dimmer
control panels (DCP) on various floors to control the dimming of different types of light
fittings as shown in layouts and DB schedule of points in that relevant room.
F. In addition to the local dimming, the dimming system shall be interfaced with the A/V
system via the KNX interface module to control the volume and source selection, in
the future .
G. The system shall have also provision to integrate with Modbus RTU devices in the field
level which can be used for integration with Modbus slaves such as energy meters.
The Energy meters shall be provided in each distribution board to identify the energy
consumption.
I. The programming of the system is carried out with the Engineering Tools Software
(ETS) parameterization software via an RS232 or USB interface. They can be used in
any location within the bus system. A programming of the KNX devices by the Ethernet
shall also be possible via IP gateway.
J. The system shall have the capability to have a diagnostic functions, the devices
existence in the network shall be continuously monitored and in case of any of the
selected device , specially the output units in the network fails it shall be reported to
the central location mentioning the details of the device.
The Home Automation system shall be programmed in such a way that unnecessary
usage of power is minimized without losing comfort and safety to the client. Home
Automation requirement is as follows.
A. All the areas including common and private areas, the lighting, Blinds and Fan coil
units shall be controlled through Home automation system.
B. Bedrooms, dressing areas and the living rooms the lighting shall be dimmable, the wall
plate shall support multiple scene setting to accommodate various scenes.
C. Touch screens shall be provided in main entrance to control the room functions, the
device shall have the ability to interface with CCTV System as well as the AV Systems
. The system shall be able to connect to the cloud to monitor and control all these
functions within the premise as well as outside the building.
D. The system shall provide various interfacing option which includes ModBus RTU,
Modbus IP , BACnet/IP , KNX-TP, KNX -IP , RS232,DALI, DMX to interface any
requirement arises during the installation phase. The system shall be interfaced to the
fire alarm and intrusion detection monitoring systems with necessary modules
A. The gateway shall divide the system into discrete entities, optimizing the data-flow
between the head-end PC and the Lighting Control Modules, sensors, switches and
the system spine.
C. All home automation control components shall be compatible with other elements of
light fixtures, ballasts, transformers, and lighting controls.
A. The gateway shall divide the system into discrete entities, optimizing the data-flow
between the head-end PC and the Lighting Control Modules, sensors, switches and
the system spine.
A. The circuit switching module shall provide individual addressable control of connected
lighting circuits. Modules shall be located within electrical risers and provide individual
addressable control of multiple 16A lighting outputs each of which is conduited to a
number of luminaries.
B. The switching module shall be DIN rail mounted consisting of eight individually
programmable integral relays.
C. The module shall be equipped with 16A mechanically-latched relays which, in the
event of failure, remain in their last state and may be manually operated on and off
from the module.
D. Each channel should features manual override switch with visual indication of status.
E. A built in propagation delay reduces current surge when all channels are switched
simultaneously allowing progressive controlled switching of multiple loads.
F. The control modules shall be capable of being programmed with different applications
to suit site requirements. The application for which a relay has been programmed shall
apply irrespective of the signal from which it is controlled.
G. Each of the relays shall be capable of being programmed with its own ‘On’ and ‘Off’
delays which will be applicable irrespective of the signal from which the relays are
being controlled.
H. Standalone addressable DALI controller shall be used to switch and dim 64 short
addresses and 16 group addresses if fully addressable DALI systems are required.
A. The Switch Actuator module shall control 8 independent loads with a capability toad
expansion module to increase the load to either 16 or 24 circuits, equipped with a
voltage free, magnetically latched relay per channel or equivalent solid-state electronic
relay according to the project requirement. The load rating shall be of 16A AC1as per
IEC60947-4-1 and each relay operation shall be indicated with a visual LED display.
B. The switch actuator shall also be configured to control the lighting loads as well as the
blind actuators by the software configuration, there shall not be a separate module for
the blind control if it is required in the project.
C. The actuator shall be equipped with high inrush current rated relays in order to
accommodate the the inrush current an peak repetitive current of the LED loads. The
inrush current rating shall be minimum as follows. Relays which has less current
capacity than the mentioned are not accepted.
i. 800 A/200 μs,
ii. 165 A/20 ms
D. The mechanical life time of the relays shall be higher, and the life time shall be defined
for the each type of load connect the individual relay channels. The relay shall have
minimum switching cycle as follows.
iii. Output life endurance:
1. Mechanical: >1x 106
2. 16A AC1 operation: >6x 103
E. With the 16 A switch actuator shall have the capability Incandescent lamps: AC 230
V, max. 2300W, Halogen lamps: AC 230 V, max. 2300W, Capacitive load: AC 230 V,
10 AX, max. 140 µF Motor load AC 230 V, max. 1000 W, LED load: AC 230 V, max.
200 W. The module load shall be tested in accordance with the IEC60669-2-5
standard.
F. In the event of power failure or bus wiring failure or control module failure, each of the
relays shall attain a pre-programmed fail-safe position (‘Switch On’, ‘Switch Off’ or
‘Remain As it is’).
G. When connecting with the lighting load the control modules shall be capable of been
programmed with different applications to suit site requirements for e.g. staircase
lighting function which switches ‘Off’ the relays after a preprogrammed time from the
time it has switched ‘On’. The application for which a relay has been programmed shall
apply irrespective of the signal from which it is controlled.
H. Each of the relays shall be capable of being programmed with its own ‘On’ and ‘Off’
delays that shall be applicable irrespective of the signal from which the relays are
controlled.
I. Each of the control module shall have its own individual address and shall be capable
of being programmed from the central PC for the purpose of changing parameters
without the need to access the module locally.
J. Each main module shall have the KNX connections which shall be connected with
screwless termination, the KNX terminals shall be fully covered and with a closing lid.
K. The main and expansion module shall relate to a screwless terminations which can be
easy to push in or pull out, making it very easy to connect and disconnect the main
and the expansion module.
L. Each module shall be equipped with additional visual LED indicators, which includes
the run/error, Manual override LEDs in the main module and Run, Error,
Communication, Manual override LEDs in the expansion modules.
N. The device shall meet highest level of fire and thermal protection standards, the device
shall comply to the glow wire testing standards according to IEC60695-2-1
O. The device shall be tested in accordance with the following testing standards, the
supplier has to submit the test certificate as a part of the submittal.
1) DIN EN 60669-1 (VDE 0632 Teil 1):2009-10; EN 60669-1:1999 + A1:2002 +
A2:2008
2) DIN EN 60669-2-1 (VDE 0632-2-1):2010-03; EN 60669-2-1:2004 + A1:2009
3) DIN EN 60669-2-1/A12 (VDE 0632-2-1/A12) 2010-09; EN 60669-2-
1:2004/A12:2010
4) DIN EN 60669-2-5 (VDE 0632-2-5):2017-05; EN 60669-2-5:2016
5) DIN EN 50428 (VDE 0632-400):2010-02; EN 50428:2005 + A1:2007 + A2:2009
6) IEC 60669-1:1998
7) IEC 60669-1:1998/AMD1:1999
8) IEC 60669-1:1998/AMD2:2006
9) IEC 60669-2-1:2002
10) IEC 60669-2-1:2002/AMD1:2008
11) IEC 60669-2-1:2002/AMD2:2015
12) IEC 60669-2-5:2013
A. The Dimming Actuator module shall control 2 independent light loads with a capability
to add dimming expansion module to increase the number of controlled dimming
channels to 4 or 6.
C. The dimming actuator itself or in combination with different expansion modules shall
be configured by the software configuration
D. The device shall be based on the integrated modular concept , The installation shall
be on the basis of the dimming or switch blind modules and act as in integrated
controller with a single device address , in case of maintenance or module swapping ,
it shall be possible to do it in modular basis without the need to replace the complete
integrated device . Systems which uses a single integrated controller without modular
approach are not accepted.
E. The maximum load rating of dimmer shall be 2x 350W/VA for incandescent and high
voltage halogen lamps, electronic and wounded transformers, 2x 200W or maximum
1.3A for 230V LED lamps operating in RC mode (trailing edge control) and 2x 60W for
230V LED lamps operating in RL mode (leading edge control) with derating for
operating temperature above 35°C.
G. The dimmer module shall support predefined dimming curves for the incandescent ,
Halogen , LED lamps and also able to customise the LED dimming curve based the
Luminaire characteristics. The installer shall be able to see the dimming curve through
a visual graph.
H. The device shall support wide range of LED Luminaires with flicker free and shall
provide good dimming performance with most common LED lamps.
I. The device shall be able to accept power from different power lines for each channels
and able to dim the loads . Devices which work based on a single phase only are not
accepted.
J. The individual devices shall be DIN TH35 rail mounted within the HAP enclosure
according to EN60715.
K. In the event of power failure or bus wiring failure or control module failure, each of the
relays shall attain a pre-programmed fail-safe position (‘Switch On at selectable
brightness’, ‘Switch Off’ or ‘Remain As it is’).
L. Each of the control module shall have its own individual address and shall be capable
of being programmed from the central PC for the purpose of changing parameters
without the need to access the module locally.
M. Each main module shall have the KNX connections which shall be connected with
screwless termination, the KNX terminals shall be fully covered and with a closing lid.
While removing the connector a special vertical pull-out mechanism shall be an
integral part of the module in order to avoid the high-pressure damage to the KNX
terminals.
N. The main and expansion module shall be connected with a screwless terminations
which can be easy to push in or pull out, making it very easy to connect and disconnect
the main and the expansion module.
KEO/21-7387-0004 27 5100 / 12 Home Automation System
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
O. Each module shall be equipped with additional visual LED indicators, which includes
the run/error, Manual override LEDs in the main module and Run, Error,
Communication, Manual override LEDs in the expansion modules.
Q. The device shall meet highest level of fire and thermal protection standards, the device
shall comply to the glow wire testing standards according to IEC60695-2-1
R. The device shall support the same dimming time usage for central functionality.
A. The device shall be Din rail mounted as per the EN60715 and shall be able to support
KNX Secure.
B. The device shall able to do filtering of KNX telegrams as well as individual address
telegrams in order to maintain unnecessary telegrams passing over the network,
making effective utilisation of the communication bandwidth.
C. It shall be possible to program the device either from the main line as well as from the
subline and shall be also be capable to program just as a line repeater .
D. The device shall also have a possibility to route all the telegram for testing purpose by
pressing the push button built into it.
E. The device shall provide a Main-LED on the front to inform about the status of the Main
line like Bus voltage ok, Telegrams on line, communication error.
G. The device shall provide a Sub-LED on the front to inform about the status of the Sub-
line like Bus voltage ok, Telegrams on line, communication error.
A. The energy measurement unit shall be able to provide energy consumption, power,
and current and provide the results via the ModBus or KNX, the measured energy can
easily be available in touch screen or the tablets for the end customer to check.
B. It shall also provide the active energy consumption (max 1.5%) per channel and total
consumption with the accuracy of 10%. The device should have minimum of 3
channels and each channel should rate to measure 16A. or if the current requirement
exceeds the limit the necessary CT meters shall be used to od the integration from the
same supplier. The module should comply with TH35 DIN rain as per DIN EN 60715.
C. Operating voltage should be 230V 50/HZ +/- 10% , accuracy class of the unit shall
comply to IEC 61557-12. The size shall not exceed 4 modules ( 90HX72WX65D mm)
as it can be located in the DB/HAP according to the project requirement.
D. Based on the project requirement the energy monitoring shall be done per Distribution
board wise or by the MCB wise for better control and accuracy
2.012 POWERSUPPLY
B. The device shall be with diagnostic LEDs for the easy maintenace and troubleshooting
. the devise shall be equipped with LEDs for Overvoltage , overload, run and reset
LED indication.
C. The device shall have additional 30VDC auxilary power output shared from the same
power source, to be able to power 30V additional power to SELV devices .
E. The outputs shall have a common overload and short-circuit protection and an
opencircuit proof. The bus line is connected via a KNX connection terminal.
Powersupplies which does not have overvoltage and overload protections are not
accepted.
F. With the combination of RUN LED, Overload LED, Overvoltage LED and Reset-LED
it shall be possible to the under stand the normal operation, Soft Reset, permanent
reset, Overvoltage , Overload, short circuit, KNX voltage failed and internal error to
make the system maintence easy and effective.
H. The device shall be tested in accordance with the following testing standards and the
conformity needs to be submitted as a part of the submittal .
a. EN 50491-5-1:2010
b. EN 50491-5-2:2010
c. EN 62041:2010
d. EN 50491-3:2009
e. EN 61558-2-16:2009
f. EN 61558-2-16:2009/A1:2013
g. EN 50491-4-1:2012
h. EN 50581:2012
A. There shall be a dedicated Door Interface Unit for Smart Doors and Bells as shown in
the layouts.
B. The smart lock GPIO should have an input to connect a push button to open the door.
C. The smart lock GPIO should have specific output to differentiate between ‘Entry’, ‘Exit’,
‘Door Status’
D. The door contact will monitor the door status and if the door stays open for a long time.
The system shall be able to send an alarm as well.
E. The smart lock GPIO should have an input and output to connect ‘DND’ and ‘MUR’
F. The smart lock GPIO should have an input and output to connect Bell.
A. The Home Automation system shall support industry standard open communication
protocols such as KNX, BACnet, Modbus.
B. The Home Automation system shall support integration with Smart Home applications
and appliances such as Google Home, Amazon Alexa, Somfy curtain motors, Revox
sound systems, Sonos sound systems, Philips Hue lighting solution.
A. TOUCH INTERFACE
1. The device shall be a touch screen mounted on a standard British back box
with direct KNX connection and controls up to 36 functions depending on the
design selected by screen. Functions like switching or dimming lights,
controlling blinds or activating scenes. It is a room temperature control unit
which supports different types of control.
2. The device shall include a proximity sensor to switch on the display if you
approach into approx. 20 cms. As soon as no further movement is detected
towards the device, it switches off after a programmed time.
3. The device shall change the visible screen to the next one by swapping with
the finger (up to 8). Each screen has the design and function/functions
programmed.
4. The device shall include a gesture sensor which reacts to the movement of
the hand in one programmed direction (Vertical or horizontal) and will
activate/deactivate the programmed action. Without touching the device.
5. The device shall allow the selection of a different design for each screen. It
can be selected Rotary Design, Vertical Design or Button Design for each
screen.
6. The Button Design shall allow the control of functions by touching icons and
changing the colour from white to grey and shall be able to customize each
function with advance parameters.
7. The device shall be able to program the pop up messages which will show on
the screen in case of the condition becomes active. The device shall have the
capability to show up to 5 different customizable messages.
8. The device shall have the capability to go to locking mode (30-90) second
which can be used for cleaning purpose without activating any action in the
bus.
9. It shall be possible to create and insert Logo and activate it as a screen saver.
10. The device shall also have the possibility to have a 4 Digit lock in case it is
used in the public areas and only the authorised person wants to unlock the
function.
C. IP TOUCH PANEL
1. The LCD screen shall be 7/10 inches in size (diagonal) and shall be
connected through IP to the sever, It shall be possible to connect upto 10
Touch panel to the Single server over IP.
2. The system can be interfaced with the Smartphones and tablet PCs with the
corresponding apps.
3. The system can be browsed and discovered the control functionality by
Standard computers (PC/Mac) with suitable browsers.
4. The Touch Panel shall provide a wall mounted, colour interface to the
automation system. The Touch Screen shall include a touch sensitive LCD
screen that can display pages of graphical items, such as buttons, sliders and
images. These graphical items shall be programmed to perform control and
monitoring related functions.
A. The Ethernet Gateway should provide a connection between the system network and
an Ethernet LAN. This allows allow the user to
a. Control and configure the system on a LAN network PC or via the
internet rather than by connecting directly into the network.
b. The Ethernet Gateway should also be the host of remote applications
including iOS (iPhone®/ iPod touch®/ iPad®) and a web server front end
where applications are downloaded separately. Coupling the gateway to
a WIFI network should enable secure scene control, visual feedback and
modification from handheld devices.
c. The Ethernet Gateway should also facilitate connection to the internet
which enables remote connection for controlling, programming &
obtaining diagnostics of the lighting control system.
PART 3 - EXECUTION
3.01 GENERAL
B. The electrical contractor(s) shall purchase the Home Automation hardware and
software from the specialist system supplier and shall install the system hardware and
all cabling and bus wires as part of the electrical installation.
D. For pre-commissioning purposes, the system shall enable testing of all controls
connected to all modules on the network.
E. The contractor shall give a clear written instruction for the supplier to begin preparation
of system configuration files based on a given set of drawings. The final software
configuration shall be based on the electrical contractor's final as-built drawing of the
Home Automation System installation.
F. Install and program software with initial settings of adjustable values. Make backup
copies of software and user-supplied values. Provide current licenses for software.
A. Wiring Method:
1. Comply with requirements “Conductors and Cables."
2. Install cables for control and signal transmission conductors, complying the
documents and as per manufacturer recommendation.
B. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points.
Separate power-limited and non-power-limited conductors according to conductor
manufacturer’s written instructions.
D. Splices, Taps, and Terminations: Make connections only on numbered terminal strips
in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures.
3.03 IDENTIFICATION
E. Test Labelling: After satisfactory completion of tests and inspections, apply a label to
tested components indicating test results, date, and responsible agency and
representative.
F. Reports: Written reports of tests and observations. Record defective materials and
workmanship and unsatisfactory test results. Record repairs and adjustments.
3.05 TRAINING
A. The Home Automation system supplier shall be engaged by the contractor to set-up
and commission the system, and to carry out training of the Client’s personnel.
B. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies
and course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
KEO/21-7387-0004 27 5100 / 21 Home Automation System
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
3.07 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the
installed system. During that period, the contractor shall be responsible for the regular
inspection and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for
the system and submit to the Engineer for his approval.
A. Each point in the system shall be tested for both hardware and software functionality.
In addition, each circuit under the control of the LCS will be tested against the
appropriate sequence of operation specified herein. Successful completion of the
system test shall constitute the beginning of the warranty period. A written report will
be submitted to the owner indicating that the installed system functions in accordance
with the plans and specifications.
B. The LCS contractor shall commission and set in operating condition all major
equipment and systems, such as HAP Panel Operation and the Motion sensor
functionality in the presence of the consultant and if applicable with the client
representative.
C. Startup Testing shall be performed for each HAP Panel along with the termination
checklist, which shall be initialed by the technician and dated upon test was completion
along with any recorded data such as voltages, termination faults and any deviations
from the submitted installation plan shall also be recorded.
END OF SECTION
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUMMARY
A. The Specialist Security Integrator shall design, supply, install and commission an
audio/video intercom system as described in this Specification.
B. Section Includes
1. This section details the technical requirement for Intercom Entry system.
1.03 DEFINITIONS
A. External Audio Video intercom units shall be flush mounted weatherproof, vandal proof
and designed to give a clear audible tone. .
B. The Slave intercom unit shall be desk mounted with a handset for communication and
shall be provided with push buttons to release the electrical lock on the doors, to allow
entry.
C. Audio Video handsets shall be designed to communicate with other Slave stations.
D. The Electrical Services Installer shall provide a complete system of system wiring
containment comprising metal trunking and conduit for the door entry systems. The
wiring, cable trays, equipment etc shall be installed and earthed in accordance with BS
7671. All circuits shall be segregated as required by BS 7671. Outlet boxes for wall
mounted system equipment shall be standard recessed one-gang boxes.
1.05 SUBMITTALS
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
B. Storage: Store materials in clean, dry area indoors in accordance with manufacturer's
instructions.
A. Environmental Limitations: Do not deliver or install equipment frames and cable trays
until spaces are enclosed and weather tight, wet work in spaces is complete and dry,
and work above ceilings is complete.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
C. Spare parts shall be delivered to the Owner’s central storage facility within the Site limit.
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
PART 2 - PRODUCTS
3) There should be an integrated card reader to verify and allow the authorized
entries.
D. There shall be a button available on the intercom handset by which the call receiver
should be able to release/open the entry for the caller
A. The Specialist / integrator shall design, supply, install and commission an audio /video
entry phone system linking between the main entrance doors and intercom units as
shown in layout drawings.
B. A color digital video entry system shall provide audio and visual communication.
C. Entry panel shall provide a camera and control keypad and display. In addition, LED
lights for ‘Door Open’ and ‘Speak Now’ indication will be provided at both heights to
assist both aurally and visually impaired users.
D. The entry panels shall be flush fitting vandal resistant with a brushed stainless steel
front plate or similar and shall include integral proximity readers linked to the access
control system.
E. The internal intercom units shall be equipped with a flush wall mounted video
monitor/handset with 3.5” visible LCD TFT colour screen. Adjustable Contrast and
brightness controls shall be easily accessible by the user. The monitor/handset must
also feature a privacy control with LED,user adjustable ring tone volume and additional
‘door open’ LED indicator. A tilt screen will be allowed to facilitate lower level mounting
for wheelchair users.
F. LED lights for ‘Door Open’ and ‘Speak Now’ indication to be provided.
G. Each panel shall have the capability to call up to 200 monitors/receivers and be fitted as
standard with two CCD colour cameras with adjustable angle of view at both high and
low levels, complete with fixed focal length lens and automatic electronic shutter. The
cameras shall provide an integral lighting facility to assist image definition under low
light level conditions.
H. The entry panel shall be flush fitting, vandal resistant with a brushed stainless steel front
plate.
I. The door entry system video cameras shall be interfaced with the CCTV system such
that any images from the door entry system can be captured and stored on the CCTV
system storage and displayed on the video monitors.
J. The digital panels shall also be equipped with a Dewhurst style keypad for vandal
resistance with both standard numeric on the buttons. An easy to read, programmable
backlit LCD display showing operations mode and digits entered will also be
incorporated.
K. External intercom units shall be flush mounted weatherproof, vandal proof and designed
to give a clear audible tone. The units shall have a push button to call the reception
L. The internal intercom units shall be provided with a push buttons to release the electrical
lock on the doors, to allow entry. The Specialist Supplier shall include for the electric
locks and local break glass for emergency escape.
PART 3 - EXECUTION
3.01 EXAMINATION
B. Notify Architect of conditions that would adversely affect installation or subsequent use.
3.02 PREPARATION
3.03 INSTALLATION
A. Adjust Intercom Entry System for proper operation in accordance with manufacturer's
instructions.
A. Demonstration:
1. Demonstrate that Intercom Entry System functions properly.
KEO/21-7387-0004 27 5123 / 5 Intercom Entry System
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
2. Perform demonstration at final system inspection by qualified representative of
manufacturer.
3.06 PROTECTION
3.07 TRAINING
3.08 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B. Subject to compliance with the requirements of the Contract Documents, the warranty
and spare parts shall include but not limited to the list below:
DIVISION 27
- Warranty period is from taking over certificate to the client; parts, labour, travel
time expenses included are included.
- Bidder is to provide a schedule of spares as part of the submission and include
delivery to site.
- Routine maintenance visits as recommended by the Manufacturer
recommendation during the defect notification period.
- Basic and advance training courses for FM staff are required.
- For items not mentioned in this warranty list, shall be covered under manufacturer
standard warranty.
-
10 years or
Standard
COMMUNICATIONS All spare parts required during
Manufacturers’
27 1116 RACKS, FRAMES, AND warranty period as per manufacturer
warranties
ENCLOSURES recommendation
whichever is
greater
10 years or
Standard
COMMUNICATIONS All spare parts required during
Manufacturers’
27 1513 COPPER HORIZONTAL warranty period as per manufacturer
warranties
CABLING recommendation
whichever is
greater
2 years or
Communications Standard
All spare parts required during
Manufacturers’
27 1116 Racks, Frames, and warranty period as per manufacturer
warranties
Enclosures recommendation
whichever is
greater
END OF SECTION
1.01 GENERAL
DIVISION 27 COMMUNICATIONS
SECTION TITLE MANUFACTURER COUNTRY
27 1116 Communications COMMESCOPE USA
Racks, Frames, EXCEL UK
and Enclosures NETWORKING
DATWYLER CABLES GERMANY
BRAND-REX UK
PANDUIT USA
A&T USA
LEGRAND/ USA
ORTRONICS
HUBBELL USA
R&M SWITZERLAND
SIEMON USA
BELDEN/ CDT USA
27 1513 Communications COMMESCOPE USA
Copper Horizontal EXCEL UK
Cabling NETWORKING
DATWYLER CABLES GERMANY
BRAND-REX UK
PANDUIT USA
A&T USA
LEGRAND/ USA
ORTRONICS
HUBBELL USA
R&M SWITZERLAND
SIEMON USA
BELDEN/ CDT USA
27 5100 Home Automation SCHNEIDER
System ABB
LEVITON
LUTRON
CRESTON
27 5123 Intercom Entry AIPHONE JAPAN
System COMELIT ITALY
FERMAX SPAIN
BPT UK
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
C. Product - A sixteen channel network video recorder which is ONVIF compliant, with
support for H.265, H.264, and MJPEG compression and recording bandwidth of 128
Mbps.
D. Related Requirements
1. 27 1513 - Communications Copper Horizontal Cabling
2. 28 5910 - Warranty and Extra Material List
1.02 REFERENCES
A. Abbreviations
1. Abbreviations
2. AGC - Automatic Gain Control
3. ARP - Address Resolution Protocol
4. AWB - Automatic White Balance
5. BLC - Back light compression
6. CBR - Constant Bit Rate
7. CVBS - Color, Video, Blanking, Sync
8. DHCP - Dynamic Host Configuration Protocol
9. DNR - Digital Noise Reduction
10. DNS - Domain Name Server
11. DDNS - Dynamic Domain Name Server
12. DSCP - Differentiated Services Code Point
13. fps - frames per second
14. FTP - File Transfer Protocol
15. GOV - Group of Video
16. GUI - Graphical User Interface
17. HD - High Definition
18. HTTP - Hypertext Transfer Protocol
19. ICMP - Internet Control Message Protocol
20. IGMP - Internet Group Management Protocol
21. IP - Internet Protocol
22. JPEG - Joint Photographic Experts Group
KEO/21-7387-0004 28 2300 / 1 Security Video Surveillance System (CCTV
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
23. MJPEG - Motion JPEG
24. MP - Megapixel
25. MPEG - Moving Pictures Experts Group
26. NAS - Network Attached Storage
27. NTP - Network Time Protocol
28. PIM-SM - Protocol Independent Multicast-Sparse Mode
29. PoE - Power over Ethernet
30. PPPoE - Point to Point Protocol over Ethernet
31. RTP - Real-Time Transport Protocol
32. RTCP - Real-Time Control Protocol
33. RTSP - Real-Time Streaming Protocol
34. SDK - Software Development Kit
35. SMTP - Simple Mail Transfer Protocol
36. SNMP - Simple Network Management Protocol
37. SSL - Secure Sockets Layer
38. TCP - Transmission Control Protocol
39. UDP - User Datagram Protocol
40. UPnP - Universal Plug and Play
41. VBR - Variable Bit Rate
42. VMS - Video Management System
43. WDR - Wide Dynamic Range
44. LDC - Lens Distortion Correction
B. Reference Standards
1. Network - IEEE
a. 802.3 Ethernet Standards
b. 802.1x Port-based Network Access Control
2. Video
a. ISO / IEC 14496-10, MPEG-4 Part 10 ( ITU H.264)
b. ISO / IEC 10918 - JPEG
c. ONVIF - Profiles S G and T
3. Emissions
a. FCC-47 CFR Part 15 Subpart B Class B
b. CE EN 55022:2010
4. Immunity - CE
a. EN 50130-4:2011
b. EN 61000-3-3:2014
c. EN 61000-4-2:2009
d. EN 61000-4-3:2006+A2:2010
e. EN 61000-4-4:2012
f. EN 61000-4-5:2014
g. EN 61000-4-6:2009
5. Safety
a. UL listed
b. CE EN 50581:2012 (hazardous substances)
6. Ingress Protection and Vandal Resistance
a. ANSI / IEC60529 - Degrees of Protection Provided by Enclosures - IP66
b. IEC EN 62262 - Degrees of protection provided by enclosures for
electrical equipment against external mechanical impacts - IK10
c. IEC 60068-2-75
1.03 SUBMITTALS
A. Product Data
1. Manufacturer's printed or electronic data sheets
2. Manufacturer's installation and operation manuals
3. Warranty documentation
1.04 QUALIFICATIONS
B. Installers shall be trained and authorized by the Manufacturer to install, integrate, test,
and commission the system.
A. Manufacturer shall provide a limited 3 year warranty for the product to be free of
defects in material and workmanship.
B. Manufacturer shall provide embedded camera video analytics free of license charges.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. The sixteen channel Network Video Recorder (“NVR”) shall record video and audio
from up to sixteen network video cameras to a hard disk and enable playback of video
and audio.
B. The manufacturer shall be responsible for rigorous testing of NVR’s reliability. The
manufacturer shall provide a list of compatible hard disks that have been tested to
guarantee reliable recording. The list shall be available in the manufacturer’s home
page.
C. The NVR shall provide auto recovery backup (ARB) to transfer video that is recorded
on network camera’s SD cards during failures to the hard disk drive. The NVR shall
allow users to set transfer speed or bandwidth dedicated for ARB in three levels; low,
middle, high. If the bit-rate of video to be transferred exceeds the set bandwidth, then
the NVR shall transfer video in the order of channel number until all transfer is finished
or the video becomes more than 24 hours old based on NVR’s current time. The NVR
with ARB shall be able to handle the following failures.
1. Network disconnection between cameras and NVR
2. Unexpected shutdown of NVR
D. The sixteen channel NVR shall receive text data from external devices and overlay it
on live as well as recorded video. It shall also provide search for text data and list all
video with previews that is relevant to the search queries. The text shall include but
not limited to the following.
1. Text from PoS devices, namely the texts printed on the receipt of transactions
2. Text from automatic number plate recognition software
3. Text from automated teller machines (ATM)
E. The NVR shall provide a remote monitoring environment for video and audio over the
network using a remote computer. The remote monitoring software shall allow users
to receive live streams, search for recoded videos, and configure devices.
F. P2P Service: The NVR shall provide easy configuration of mobile viewer. The mobile
viewer shall be freely available and connection shall be established by simply
scanning QR code from a mobile device.
A. The NVR shall have a built in server which provides access for authorized users to
live view of connected cameras, NVR recording and playback functions, and NVR
configuration settings.
B. The NVR software shall provide a monitoring screen which displays live camera video
and simultaneously provides same-screen access to the following functions:
1. Screen mode, allowing set up and display of live video channels in various
layouts or sequence configurations.
2. Hallway view mode for hallway view cameras.
3. Status displays:
a. camera live status
1) model
2) connection status
3) IP address
4) compression
5) resolution
6) frame rate
7) quality
b. camera record status
1) bit rate
a) record bit rate
b) input bit rate
c) bit rate limits
2) configured video profile
3) input/record frames per second
4. Start/stop recording
5. Search recorded video
6. Play recorded video
7. Freeze live video
8. Audio on, off, and mute
9. Event monitoring
10. Digital zoom
11. Camera PTZ controls
KEO/21-7387-0004 28 2300 / 6 Security Video Surveillance System (CCTV
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
12. Manual recording
13. Image (snapshot) capture
C. The NVR software shall provide setup screens which provide access to the following
configuration settings and functions:
1. System
a. date and time
b. user passwords and permissions
c. system information
d. software upgrade
e. system logs
f. event logs
g. backup logs
2. Cameras
a. image preview of video
b. profile information
c. compression information
d. protocol information
e. model information
f. IP address
g. connection status
h. total amount of data received by channel
i. auto or manual search and register
j. select and setup ONVIF protocol operation
k. add, delete, and edit camera profile
l. adjust settings:
1) camera name
2) resolution
3) frame rate
4) quality
5) bit rate
6) brightness
7) backlight
8) exposure
9) day/night
10) defog
11) focus
12) mirror and flip
13) motion detection
m. apply settings to groups of cameras
n. live streaming settings
3. Recording
a. setup recording schedule by day and time per channel
b. record settings per channel
1) all frames, key frames, or no record
2) data limit per channel
3) pre and post event recording times
4) include audio
c. set recording profile per channel:
1) compression
2) resolution
3) frame rate
4) quality
KEO/21-7387-0004 28 2300 / 7 Security Video Surveillance System (CCTV
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
d. HDD full capacity options – stop, overwrite
e. Event configuration
1) sensor operation
2) Camera events, including motion detection and video analytics
3) video loss detection
4) alarm output parameters
4. Storage media and devices
a. display working status, including current rate of recording, recording loss
rate, and cumulative losses
b. storage use and capacity information
c. HDD temperature information
d. HDD alarm notifications
5. Monitor
a. HDMI video output
1) HDMI1: 3840x2160(30Hz), HDMI2: 1920x1080(60Hz)
b. configure display parameters
6. Text device
a. channel allocation
b. encoding type and delimiting characters
c. network port
d. event configuration
1) keyword entry
2) dollar value trigger
7. Network
a. address settings per physical port
b. bandwidth limits
c. software ports and protocol
d. multicast parameters
e. DDNS
f. UPnP
g. security:
1) IP filtering
2) SSL encryption and certificates
3) 802.1x parameters
h. NTP server
i. SMTP e-mail settings
j. SNMP settings
k. live stream selection
l. DHCP server settings
8. Notifications
a. event types
b. intervals
c. recipients
D. The NVR software shall provide Search and Playback functions as follows:
1. Search by:
a. time
b. event
c. text
d. backup device
2. Playback
a. play forward and reverse at normal or accelerated speeds, frame by
frame, and next record
KEO/21-7387-0004 28 2300 / 8 Security Video Surveillance System (CCTV
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
b. go to first and go to last functions
c. color-coded timeline with play head scrub bar
d. set audio on or off
e. initiate backup
E. The NVR shall have a built in web server which supports browser-based configuration
from a PC.
1. Acceptable browsers: Internet Explorer, Google Chrome and Apple Safari
2. The web viewer shall provide a monitoring screen which displays video from
registered cameras and simultaneously provides same-screen access to the
following functions:
a. display layout configuration
b. additional display functions as available with direct connection to the NVR
server
3. The web viewer shall provide the same functionality as available when directly
connecting to the NVR server with respect to the following:
a. system settings
b. backup and restoration of configuration settings to a file
c. camera configuration settings and functions
d. recording
e. storage media and devices
f. monitor
g. text device
h. network
i. events and notifications
j. search and playback
4. Minimum client requirements
a. Acceptable Operating Systems: Windows XP, Vista, 7, 8, 10, Mac OS X
(10.9, 10.10, 10.11)
b. Acceptable browsers: Microsoft Internet Explorer, Microsoft Edge, Google
Chrome, Apple Safari
A. Video
1. Compression: H.265, H.264, MJPEG
B. Recording
1. Channel capability: 16
2. Recording bandwidth: Up to 32 Mbps
3. Resolution range: CIF up to 8 MP
D. Playback
1. Number of simultaneous channels
a. Local : 16
b. Network : 8
2. Bandwidth: 32 Mbps
E. Storage
1. Internal
a. Number of HDD’s 2
b. Capacity per HDD: Max. 10 TB/1ea
2. External
a. Acceptable types:
1) USB HDD/Flash drive for backup of video clips, firmware update,
settings backup/restore, log export
F. Network
1. Connectivity: PoE RJ-45 16EA (LAN, 10/100), RJ-45 1ea (LAN/WAN
1Gbps)
2. Protocols supported:
a. Transmission Control Protocol (TCP), Internet Protocol (IP) v4 and v6,
User Datagram Protocol (UDP)
b. Configuration: Dynamic Host Configuration Protocol (DHCP)
c. Web services: Hypertext Transfer Protocol (HTTP), Secure HTTP
(HTTPS)
d. Network services: Address Resolution Protocol (ARP), Domain Name
System (DNS), Internet Control Message Protocol (ICMP), Network Time
Protocol (NTP), Simple Network Management Protocol (SNMP v1/2c/3 –
MIB-2), Universal Plug and Play (UPnP)
e. Media: Real-Time Transport Protocol (RTP), Real-Time Control Protocol,
Real-Time Streaming Protocol (RTSP)
f. Multicast: Internet Group Management Protocol (IGMP)
g. Notifications: Simple Mail Transfer Protocol (SMTP)
h. Remote Access: Point-to-Point Protocol over Ethernet (PPPoE)
3. DDNS – The NVR shall support DDNS services offered by the Manufacturer and
other publicly available service offerings.
4. Security features:
a. user password protection with group restrictions
b. IP address filtering - list of allowed or blocked IP addresses
c. HTTPS(SSL) login authentication
d. User access log
e. 802.1x authentication
f. Restriction of all network access/web viewer access
5. Discovery - Manufacturer shall offer a discovery program to identify all devices of
his manufacture on the network, as well as ONVIF Profile S conformant devices.
6. Transmission Bandwidth: 128Mbps
G. Alarm/sensor interface:
1. Input (4)
KEO/21-7387-0004 28 2300 / 10 Security Video Surveillance System (CCTV
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
2. Output (2)
H. Audio
1. Channel capability: 16 channels
2. Compression: AAC (16/48KHz), G.711, G.726
I. Electrical
1. Input Power 100-240 V AC ± 10%
2. PoE budget 130 W maximum
3. Power Consumption: 200 W maximum (2 HDD, PoE On)
A. Video Compression and Transmission – The camera shall have the following
properties relating to the video signals it produces.
1. H.265, H.264 and MJPEG compression, each derived from a dedicated encoder
and capable of being streamed independently and simultaneously
a. H.265 and H.264 – frame rates to 30 fps
b. MJPEG – frame rates to 15 fps
2. The camera shall be able to configure up to 10 independent video stream profiles
with differing encoding, quality, frame rate, resolution, and bit rate settings.
3. Resolution selections
a. 1920 x 1080, 1280 x 960, 1280 x 720, 800 x 600,800 x 448, 720 x 576,
720 x 480, 640 x 480, 640 x 360
4. Simultaneous unicast access by up to 6 users
5. Multicast or unicast capable
6. Dynamic DNS (DDNS) support.
7. Dynamic GOV to efficiently manage bitrate of the video stream.
B. Camera – The camera device shall have the following physical and performance
properties:
1. Dustproof, waterproof, and IP66 rated.
2. IK10 rated for protection against impacts.
3. True day/night operation with removable IR cut filter
C. Low light level operation to 0.03 lux (color) and 0 lux (black and white)
1. 2D and 3D digital noise reduction
2. Integral IR illumination, providing effective visibility of 30m at 0 Lux when
activated in Black & White mode.
3. 6 privacy masking regions utilizing a 4 point polygon
D. Intelligence and Analytics – The camera shall have a suite of integral intelligent
operations and analytic functions to include:
A. The camera shall have a built-in web server which supports browser-based
configuration using Internet Explorer, Google Chrome, Mozilla Firefox, and Apple
Safari, for which web viewer plug-ins are available, from a PC or Mac.
B. The web viewer shall provide a monitoring screen which displays live camera video
and simultaneously provides same-screen access to the following functions:
1. Live view window size
2. Resolution setting
3. Image (snapshot) capture
4. Manual recording to SD or NAS
5. Audio/microphone control
6. Access Playback and Setup menus
C. The web viewer shall provide a playback screen which provides access to the
following functions:
1. Search date and time range
2. Search event type
3. Play an event video
4. Set resolution
KEO/21-7387-0004 28 2300 / 12 Security Video Surveillance System (CCTV
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
5. Play audio if present
6. Generate a backup copy of saved video data
D. The web viewer shall provide a setup screen which provides access to the following
configuration settings and functions in the camera:
1. Digital video profile to include compression type, maximum or target bit rate,
frame rate, multicast parameters, crop encoding area
2. User profile to include password, access level, authentication
3. Date and time
4. Network settings and IP version
a. DDNS
b. SSL, including certificate management
c. 802.1x authentication
d. Quality of Service settings
e. SNMP to include version selection and settings
f. Auto configuration
5. Video setup to include flip and mirror mode, hallway view mode, video type,
privacy zone
6. Audio setup to include source, audio codec type, gain, and bit rate
7. Camera settings to include image preset, sensor frame capture, dynamic range,
white balance, back light, exposure, day/night operation, on-screen display, IR
illumination, sharpness, contrast, color level, lens distortion correction.
8. Event detection setup to include notification parameters, recording rules, time
schedule, tamper protection, motion detection, event triggers
9. System function to include reboot, upgrade, check system and event logs,
application (SDK) management
10. View profile information
A. Video
1. Imager
a. Sensor: 1/2.8" 2 MP CMOS
1) pixels per sensor: 1920 (H) x 1080(V) total; 1920 (H) x 1080 (V)
effective
2) scanning : progressive
b. Minimum illumination
1) Color mode: 0.03Lux (F1.6,1/30sec)
2) Black & white mode: 0Lux (IR LED on)
c. The following features with control settings shall be available:
1) Camera Title Off / On (Displayed up to 20 characters per
line)
a) W/W: English / Numeric / Special characters
b) China: English / Numeric / Special / Chinese
characters
B. Network
1. Connectivity: 10/100 Base-T Ethernet via RJ-45 connector
2. Protocols supported:
a. Transmission Control Protocol (TCP), Internet Protocol (IP) v4 and v6, User
Datagram Protocol (UDP)
b. Configuration: Dynamic Host Configuration Protocol (DHCP)
c. Web services: Hypertext Transfer Protocol (HTTP), Secure HTTP (HTTPS)
d. Network services: Address Resolution Protocol (ARP), Bonjour, Domain
Name System (DNS), Internet Control Message Protocol (ICMP), Network
Time Protocol (NTP), Protocol Independent Multicast-Sparse Mode (PIM-
SM), Simple Network Management Protocol (SNMP v1/2c/3 – MIB-2),
Universal Plug and Play (UPnP)
e. Media: Real-Time Transport Protocol (RTP), Real-Time Control Protocol,
Real-Time Streaming Protocol (RTSP)
f. Multicast: Internet Group Management Protocol (IGMP)
g. Notifications: File Transfer Protocol (FTP), Simple Mail Transfer Protocol
(SMTP)
h. Remote Access: Point-to-Point Protocol over Ethernet) (PPPoE)
3. DDNS – The camera shall support DDNS services offered by the Manufacturer
and other publicly available service offerings.
4. Quality of Service (QoS) – Layer 3 DSCP
5. Security features:
a. user password protection
b. IP address filtering - list of allowed or blocked IP addresses
c. HTTPS(SSL) login authentication
d. HTTPS(SSL) secured communications
KEO/21-7387-0004 28 2300 / 15 Security Video Surveillance System (CCTV
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
e. Digest login authentication
f. User access log
g. 802.1x authentication
6. Discovery - Manufacturer shall offer a discovery program to identify all devices of
his manufacture on the network.
C. Audio
1. Direction: uni-directional
2. I/O built-in mic, Line-in
3. Compression:
a. G.711 u-law/G.726 selectable
1) G.726 (ADPCM) 8KHz, G.711 8KHz
2) G.726: 16Kbps, 24Kbps, 32Kbps, 40Kbps
D. Electrical
1. Power
a. Input Voltage / Current PoE (IEEE802.3af, Class3), 12V DC
b. Power Consumption: <7.4 W (PoE), <6.5 W (12V DC)
PART 3 - EXECUTION
3.01 INSTALLERS
A. Contractor personnel shall comply with all applicable state and local licensing
requirements.
3.02 PREPARATION
A. The network design and configuration shall be verified for compatibility and
performance with the camera(s).
B. Network configuration shall be tested and qualified by the Contractor prior to camera
installation.
C. All firmware found in products shall be the latest and most up-to-date provided by the
manufacturer, or of a version as specified by the provider of the Video Management
Application (VMA) or Network Video Recorder (NVR).
E. All equipment shall be tested and configured in accordance with instructions provided
by the manufacturer prior to installation
3.03 INSTALLATION
B. All equipment shall be tested and configured in accordance with instructions provided
by the manufacturer prior to installation.
C. Before permanent installation of the system, the Contractor shall test the system in
conditions simulating the final installed environment.
3.04 STORAGE
A. The hardware shall be stored in an environment where temperature and humidity are
in the range specified by the Manufacturer.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the requirements for the installation, programming and
configuration of a complete addressable intelligent network-based fire detection and
alarm systems. The system shall include but is not limited to: fire alarm control panel(s),
automatic and manually activated voice evacuation alarm subsystem, firefighter
telephone communications, automatic and manually activated alarm initiating and
notification devices and appliances, remote annunciator, conduit, wire and accessories
required to furnish a complete and operational life safety system. All conduit, wiring and
accessories required to provide power to, and interconnect, devices supplied through
other divisions, including: electric and magnetic door holders, suppression system flow
switches, suppression system supervisory switches, elevator status and control panel
and damper related to smoke control. Equipment and labor not specifically referred to
herein or on the plans, but which are required to meet the functional intent, shall be
provided without additional cost to the Owner. Refer to the tender drawings for the
specific details.
A. All work, materials, and equipment shall comply with the rules and regulations of all
codes and ordinances of the local, state, and federal authorities having jurisdiction.
Such codes, when more restrictive, shall take precedence over these plans and
specifications. The specifications and standards listed below form part of this
specification. The system shall fully comply with the latest issue of these standards, if
applicable.:
1. National Fire Protection Association (NFPA)
a. NFPA72—National Fire Alarm Code
b. NFPA101—Life Safety Code
c. NFPA13—Sprinkler Systems
d. UAE Fire and Life Safety Code of Practice
B. Fire alarm signal initiation shall be by one or more of the following devices:
1. Manual stations.
2. Heat detectors.
3. Smoke detectors.
4. Automatic sprinkler system water flow.
5. Fire extinguishing system operation.
6. Fire standpipe system.
D. Supervisory signal initiation shall be by one or more of the following devices or actions:
1. Operation of a fire-protection system valve tamper.
E. System trouble signal initiation shall be by one or more of the following devices or
actions:
1. Open circuits, shorts and grounds of wiring for initiating device, signaling line,
and notification-appliance circuits.
2. Opening, tampering, or removal of alarm-initiating and supervisory signal-
initiating devices.
3. Loss of primary power at the FACP.
4. Ground or a single break in FACP internal circuits.
5. Abnormal ac voltage at the FACP.
6. A break in standby battery circuitry.
7. Failure of battery charging.
8. Abnormal position of any switch at the FACP or annunciator (repeater).
9. Fire-pump power failure, including a dead-phase or phase-reversal condition.
10. Low-air-pressure switch operation on a dry-pipe or preaction sprinkler system.
F. System Trouble and Supervisory Signal Actions: Ring trouble bell and annunciate at the
FACP and remote annunciator (repeater). Record the event on system printer.
1.04 SUBMITTALS
B. Shop Drawings:
1. Shop Drawings shall be prepared by persons with the following qualifications:
KEO/21-7387-0004 28 3100 / 2 Fire Detection And Alarm System
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
a. Trained and certified by manufacturer in fire alarm system design.
2. System Operation Description: Detailed description for this Project, including
method of operation and supervision of each type of circuit and sequence of
operations for manually and automatically initiated system inputs and outputs.
Manufacturer's standard descriptions for generic systems are not acceptable.
3. Device Address List: Coordinate with final system programming.
4. System riser diagram with device addresses, conduit sizes, and cable and wire
types and sizes.
5. Wiring Diagrams: Power, signal, and control wiring. Include diagrams for
equipment and for system with all terminals and interconnections identified.
Show wiring color code.
6. Batteries: Size calculations.
7. Duct Smoke Detectors: Performance parameters and installation details for each
detector, verifying that each detector is listed for the complete range of air
velocity, temperature, and humidity possible when air-handling system is
operating.
8. Floor Plans: Indicate final outlet locations showing address of each addressable
device. Show size and route of cable and conduits.
E. Operation and Maintenance Data: For fire alarm system to include in emergency,
operation, and maintenance manuals. Comply with NFPA 72, Appendix A,
recommendations for Owner's manual. Include abbreviated operating instructions for
mounting at the FACP.
Upon completion of construction work make a submittal of the final as-built drawings to
the Authorities Having Jurisdiction for their approval for purposes of their inspection
and testing of the fire alarm system installations.
G. Documentation:
1. Record of Completion Documents: Submit the "Permanent Records" according
to NFPA 72
a. Electronic media may be provided to the Architect, and concerned local fire
authority.
PART 2 - PRODUCTS
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
2.02 MANUFACTURERS
A. General Description:
1. Modular, power-limited design with electronic modules, UL 864 listed and/or
EN/BS compliant.
2. Addressable initiation devices that communicate device identity and status.
3. Smoke sensors shall additionally communicate sensitivity setting and allow for
adjustment of sensitivity at the FACP.
4. Temperature sensors shall additionally test for and communicate the sensitivity
range of the device.
5. Addressable control circuits for operation of mechanical equipment.
B. Alphanumeric Display and System Controls: Arranged for interface between human
operator at the FACP and addressable system components including annunciation and
supervision. Display alarm, supervisory, and component status messages and the
programming and control menu.
1. Annunciator and Display: Liquid-crystal type, three lines of 80 characters,
minimum.
2. Keypad: Arranged to permit entry and execution of programming, display, and
control commands and to indicate control commands to be entered into the
system for control of smoke-detector sensitivity and other parameters.
C. Circuits:
1. Signaling Line Circuits: NFPA 72, Class A.
2. Actuation of alarm notification appliances, emergency voice communications,
annunciation, smoke control, elevator recall, and actuation of suppression
systems shall occur within 20 seconds after the activation of an initiating device.
D. Smoke-Alarm Verification:
1. Initiate audible and visible indication of an "alarm verification" signal at the FACP.
2. Activate a listed and approved "alarm verification" sequence at the FACP and the
detector.
3. Record events by the system printer.
4. Sound general alarm if the alarm is verified.
5. Cancel FACP indication and system reset if the alarm is not verified.
F. Power Supply for Supervision Equipment: Supply for audible and visual equipment for
supervision of the ac power shall be from a dedicated dc power supply, and power for
the dc component shall be from the ac supply.
G. Alarm Silencing, Trouble, and Supervisory Alarm Reset: Manual reset at the FACP and
remote annunciators, after initiating devices are restored to normal.
1. Silencing-switch operation halts alarm operation of notification appliances and
activates an "alarm silence" light. Display of identity of the alarm zone or device
is retained.
2. Subsequent alarm signals from other devices or zones reactivate notification
appliances until silencing switch is operated again.
3. When alarm-initiating devices return to normal and system reset switch is
operated, notification appliances operate again until alarm silence switch is reset.
H. Walk Test: A test mode to allow one person to test alarm and supervisory features of
initiating devices. Enabling of this mode shall require the entry of a password. The
FACP and annunciators shall display a test indication while the test is underway. If
testing ceases while in walk-test mode, after a preset delay, the system shall
automatically return to normal.
L. Printout of Events: On receipt of signal, print alarm, supervisory, and trouble events.
Identify zone, device, and function. Include type of signal (alarm, supervisory, or
trouble), and date and time of occurrence. Differentiate alarm signals from all other
printed indications. Also print system reset event, including the same information for
device, location, date, and time. Commands initiate the printing of a list of existing
alarm, supervisory, and trouble conditions in the system and a historical log of events.
M. Primary Power: 24-V dc obtained from 230-V ac service and a power-supply module.
Initiating devices, notification appliances, signaling lines, trouble signal and supervisory
signal shall be powered by the 24-V dc source.
1. The alarm current draw of the entire fire alarm system shall not exceed 80
percent of the power-supply module rating.
2. Power supply shall have a dedicated fused safety switch for this connection at
the service entrance equipment. Paint the switch box red and identify it with
"FIRE ALARM SYSTEM POWER."
N. Secondary Power: 24-V dc supply system with batteries and automatic battery charger
and an automatic transfer switch.
1. The battery shall have sufficient capacity to power the fire alarm system for not
less than twenty-four hours plus 5 minutes (15 minutes for Audio Systems) of
alarm upon a normal AC power failure.
2. The batteries are to be completely maintenance free. No liquids are required.
Fluid level checks for refilling, spills, and leakage shall not be required.
3. The system shall provide a means of monitoring the battery voltages from the
front panel display for the local batteries.
4. Battery and Charger Capacity: Comply with NFPA 72.
P. Emergency Voice Evacuation Command Module (refer to the riser diagram for details)
1. The voice control shall be Digital. Digital Voice Command (DVC) controller shall
be a part of the Fire Alarm network. It shall
a. Each DVC shall support 32 minutes of Audio messages in simple WAV
format. The system shall have the capability to arrange the various audio
clips in required order to obtain different set of messages.
b. The Audio System shall support 8 simultaneous messages and 5
channels of Fireman’s telephone conversations. The DVC shall allow for 2
low level audio inputs such as Back ground music.
c. Each DVC shall support 32 Digital Audio Amplifiers (DAA) and the
communication shall be minimum 3.1 MHzs.
d. Each DAA shall support 4 Speaker circuits in Class B and two Speaker
circuits in Class A. It shall also provide for a telephone circuit.
Q. Fire Fighters Telephone Voice Control Module (refer to the riser diagram for details)
1. Voice control module (telephone) shall provide four fully supervised Class B
(NFPA Style Y) or Class A (NFPA Style Z) telephone circuits. Expansion circuit
board shall allow eight circuits per module.
2. System shall allow a minimum of seven (7) telephones connected simultaneously
to the telephone bus at a given time.
3. If a short-circuit trouble occurs on one of the telephone circuits, that circuit will
not activate on manual command.
4. Telephone circuits shall have a visual indication by zone that a call-in is taking
place and have a unique call-in tone.
A. Manual fire alarm stations shall be non-code, non-break glass type, equipped with key
lock so that they may be tested without operating the handle.
B. Stations must be designed such that after an actual activation, they cannot be restored
to normal except by key reset.
D. Manual stations shall be constructed of high impact Lexan, with operating instructions
provided on the cover. The word FIRE shall appear on the manual station in letters one
half inch (12.7 mm) in size or larger.
A. General Description:
1. UL 268 listed, operating at 24-V dc, nominal.
2. Integral Addressable Module: Arranged to communicate detector status (normal,
alarm, or trouble) to the FACP.
3. Multipurpose type, containing the following:
a. Integral Addressable Module: Arranged to communicate detector status
(normal, alarm, or trouble) to the FACP.
b. Piezoelectric sounder rated at 88 dBA at 3 m according to UL 464.
c. Heat sensor, combination rate-of-rise and fixed temperature.
4. Plug-in Arrangement: Detector and associated electronic components shall be
mounted in a plug-in module that connects to a fixed base. Provide terminals in
the fixed base for connection of building wiring.
5. Self-Restoring: Detectors do not require resetting or readjustment after actuation
to restore them to normal operation.
6. Integral Visual-Indicating Light: LED type. Indicating detector has operated and
power-on status.
7. Remote Control: Unless otherwise indicated, detectors shall be analog-
addressable type, individually monitored at the FACP for calibration, sensitivity,
and alarm condition, and individually adjustable for sensitivity from the FACP.
A. Description: Equipped for mounting as indicated and with screw terminals for system
connections.
1. Combination Devices: Factory-integrated audible and visible devices in a single-
mounting assembly.
B. Bells: Electric-vibrating, 24-V dc, under-dome type; with provision for housing the
operating mechanism behind the bell. Bells shall produce a sound-pressure level of 94
dBA, measured 3 m from the bell. 254-mm size, unless otherwise indicated. Bells are
weatherproof where indicated.
C. Horns: Electric-vibrating-polarized type, 24-V dc; with provision for housing the
operating mechanism behind a grille. Horns shall produce a sound-pressure level of 90
dBA, measured 3 m from the horn.
D. Visible Alarm Devices: Xenon strobe lights listed under UL 1971, with clear or nominal
white polycarbonate lens mounted on an aluminum faceplate. The word "FIRE" is
engraved in minimum 25-mm high letters on the lens.
1. Rated Light Output: 110candela.
2. Strobe Leads: Factory connected to screw terminals
A. Remote status and alarm indicator and test stations, with LED indicating lights. Light is
connected to flash when the associated device is in an alarm or trouble mode. Lamp is
flush mounted in a single-gang wall plate. A red, laminated, phenolic-resin identification
plate at the indicating light identifies, in engraved white letters, device initiating the
signal and room where the smoke detector or valve is located. For water-flow switches,
the identification plate also designates protected spaces downstream from the water-
flow switch.
B. Integral Relay: Capable of providing a direct signal to the elevator controller to initiate
elevator recall for designated level and to a circuit-breaker shunt trip for power
shutdown.
A. Wire and cable for fire alarm systems shall be UL listed and labeled as complying with
NFPA 70, Article 760.
PART 3 - EXECUTION
C. HVAC: Locate detectors not closer than one meter from air-supply diffuser or return-air
opening.
D. Heat Detectors in Elevator Shafts: Coordinate temperature rating and location with
sprinkler rating and location.
E. Single-Station Smoke Detectors: Where more than one smoke alarm is installed within
a dwelling or suite, they shall be connected so that the operation of any smoke alarm
causes the alarm in all smoke alarms to sound.
F. Remote Status and Alarm Indicators: Install near each smoke detector and each
sprinkler water-flow switch and valve-tamper switch that is not readily visible from
normal viewing position.
G. Audible Alarm-Indicating Devices: Install not less than 150 mm below the ceiling. Install
bells and horns on flush-mounted back boxes with the device-operating mechanism
concealed behind a grille.
H. Device Location-Indicating Lights: Locate in public space near the device they monitor.
I. FACP: Surface mount with tops of cabinets not more than 1800 mm above the finished
floor.
J. Annunciator (Repeater): Install with top of panel not more than 1800 mm above the
finished floor
B. Wiring Method:
1. Cables and raceways used for fire alarm circuits, and equipment control wiring
associated with the fire alarm system, may not contain any other wire or cable.
2. Fire-Rated Cables: Use of 2-hour fire-rated fire alarm cables, NFPA 70 Types MI
and CI, is not permitted.
3. Signaling Line Circuits: Power-limited fire alarm cables shall not be installed in
the same cable or raceway as signaling line circuits unless separated properly as
recommended by the manufacturer.
D. Cable Taps: Use numbered terminal strips in junction, pull, and outlet boxes, cabinets,
or equipment enclosures where circuit connections are made.
E. Color-Coding: Color-code fire alarm conductors differently from the normal building
power wiring. Use one color-code for alarm circuit wiring and a different color-code for
supervisory circuits. Color-code audible alarm-indicating circuits differently from alarm-
initiating circuits. Use different colors for visible alarm-indicating devices. Paint fire
alarm system junction boxes and covers red.
F. Risers: Install at least two vertical cable risers to serve the fire alarm system. Separate
risers in close proximity to each other with a minimum 1-hour-rated wall, so the loss of
one riser does not prevent the receipt or transmission of signals from other floors or
zones.
G. Wiring to Remote Alarm Transmitting Device: 25-mm conduit between the FACP and
the transmitter. Install number of conductors and electrical supervision for connecting
wiring as needed to suit monitoring function.
3.03 IDENTIFICATION
3.04 GROUNDING
A. Ground the FACP and associated circuits; comply with IEEE 1100. Install a ground wire
from main service ground to the FACP.
B. Perform the following field tests and inspections and prepare test reports:
1. Before requesting final approval of the installation, submit a written statement
using the form for Record of Completion shown in NFPA 72.
3.06 ADJUSTING
B. Follow-Up Tests and Inspections: After date of Substantial Completion, test the fire
alarm system complying with testing and visual inspection requirements in NFPA 72.
Perform tests and inspections listed for three monthly, and one quarterly, periods.
C. Semiannual Test and Inspection: Six months after date of Substantial Completion, test
the fire alarm system complying with the testing and visual inspection requirements in
NFPA 72. Perform tests and inspections listed for monthly, quarterly, and semiannual
periods. Use forms developed for initial tests and inspections.
D. Annual Test and Inspection: One year after date of Substantial Completion, test the fire
alarm system complying with the testing and visual inspection requirements in NFPA 72.
Perform tests and inspections listed for monthly, quarterly, semiannual, and annual
periods. Use forms developed for initial tests and inspections.
3.07 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B. Subject to compliance with the requirements of the Contract Documents, the warranty
and spare parts shall include but not limited to the list below:
DIVISION 28
- Warranty period is from taking over certificate to the client; parts, labour, travel
time expenses included are included.
- Bidder is to provide a schedule of spares as part of the submission and include
delivery to site.
- Routine maintenance visits as recommended by the Manufacturer
recommendation during the defect notification period.
- Basic and advance training courses for FM staff are required.
- For items not mentioned in this warranty list, shall be covered under manufacturer
standard warranty.
-
2 years or
Standard
All spare parts required during
FIRE DETECTION AND Manufacturers’
28 3100 warranty period as per manufacturer
ALARM SYSTEM warranties
recommendation
whichever is
greater
END OF SECTION
1.01 GENERAL
SITE CLEARING
PART 1 - GENERAL
1.2 SUMMARY
A. Section Includes:
B. Related Requirements:
1.4 DEFINITIONS
A. Subsoil: Soil beneath the level of subgrade; soil beneath the topsoil layers of a
naturally occurring soil profile, typified by less than 1 percent organic matter and
few soil organisms.
B. Surface Soil: Soil that is present at the top layer of the existing soil profile. In
undisturbed areas, surface soil is typically called "topsoil," but in disturbed areas
such as urban environments, the surface soil can be subsoil.
KEO/21-7387-0004 31 1000/ 1 Site Clearing
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
C. Topsoil: Top layer of the soil profile consisting of existing native surface topsoil or
existing in-place surface soil; the zone where plant roots grow.
A. Preinstallation Conference: Conduct conference at Project site one (1) week prior
to commencement of the work review the material selections, installation
procedures and co-ordination of the work with other trades. The meeting shall be
attended by the Contractor, Engineer and any other Contractor or trade requiring
co-ordination with this work.
A. Traffic: Minimize interference with adjoining roads, streets, walks, and other
adjacent occupied or used facilities during site-clearing operations.
E. Soil Stripping, Handling, and Stockpiling: Perform only when the soil is dry or
slightly moist.
PART 2 - PRODUCTS
(NOT USED)
PART 3 - EXECUTION
3.1 PREPARATION
A. Protect and maintain benchmarks and survey control points from disturbance
during construction.
B. Verify that trees, shrubs, and other vegetation to remain or to be relocated have
been flagged and that protection zones have been identified.
D. Remove erosion and sedimentation controls, and restore and stabilize areas
disturbed during removal.
A. Remove trees and shrubs not designated to remain. Remove stumps, main root
system, surface rock, etc.
C. Verify that utilities have been disconnected and capped before proceeding with site
clearing.
B. Fill depressions caused by clearing and grubbing operations with satisfactory soil
material unless further excavation or earthwork is indicated.
1. Place fill material in horizontal layers not exceeding a loose depth of 200 mm,
and compact each layer to a density equal to adjacent original ground.
1. Remove subsoil and nonsoil materials from topsoil, including clay lumps,
gravel, and other objects larger than 50 mm in diameter; trash, debris, weeds,
roots, and other waste materials.
B. Burning tree, shrub, and other vegetation waste is permitted according to burning
requirements and permitting of authorities having jurisdiction. Control such burning
to produce the least smoke or air pollutants and minimum annoyance to
surrounding properties. Burning of other waste and debris is prohibited.
END OF SECTION
EARTH MOVING
PART 1 - GENERAL
1.2 SUMMARY
A. Section Includes:
B. Related Requirements:
1.3 DEFINITIONS
1. Initial Backfill: Backfill placed beside and over pipe in a trench, including
haunches to support sides of pipe.
2. Final Backfill: Backfill placed over initial backfill to fill a trench.
B. Base Course: Aggregate layer placed between the subbase course and hot-mix
asphalt paving.
D. Borrow Soil: Satisfactory soil imported from off-site for use as fill or backfill.
I. Subbase Course: Aggregate layer placed between the subgrade and base course
for hot-mix asphalt pavement, or aggregate layer placed between the subgrade and
a cement concrete pavement or a cement concrete or hot-mix asphalt walk.
A. Product Data: For each type of the following manufactured products required:
1. Geotextiles.
2. Warning tapes.
B. Samples for Verification: For the following products, in sizes indicated below:
B. Material Test Reports: For each soil material proposed for fill and backfill as
follows:
A. Work shall comply with all rules, regulations, laws and ordinances of all authorities
having jurisdiction.
B. Obtain all necessary permits. Obtain written permission from adjoining property
employers if proposed systems of tie-back anchors will project beyond the vertical
projection of the contract limit lines. Submit such permissions with shop drawings.
A. Blasting is permitted only after obtaining the written permission from authorities
having jurisdiction and Engineer complying with requirements stipulated.
A. Traffic: Minimize interference with adjoining roads, streets, walks, and other
adjacent occupied or used facilities during earth-moving operations.
E. Prohibit heat sources, flames, ignition sources, and smoking within or near
protection zones.
G. Nature of Excavation:
PART 2 - PRODUCTS
2.1 GEOTEXTILES
A. The following and define requirements for ‘non-harmful’ fill materials suitable for
compaction to the limits specified. The Contractor may propose the use of other
materials, including if appropriate material excavated in the work, provided that they
satisfy the defined requirements related to inclusions and compaction.
B. In General,
C. Suitable ordinary fill to make up levels where required: This fill shall be
uncontaminated Ordinary/General fill with properties as noted below:
Structural fill shall meet the following criteria: In no case the structural fill material
shall contain expansive clays, vegetable or other organic material, rubbish,
previous construction elements and large rocks (Boulders and Cobbles).
E. Drainage Fill
1. Drainage fill shall be fine aggregate, clean, well graded, free-draining sand,
complying with ASTM C 33.
2. Drainage fill material shall be placed under utility trenches, behind retaining
walls, for a thickness of 60 cm below Agricultural soil at all landscaped &
planted areas and where called for in the specifications or Drawings.
2. Sand: Shall comply with requirements as specified in section 033000 “Cast In-
Place Concrete”.
2.3 ACCESSORIES
A. Warning Tape: Where indicated and complying with the Authority having jurisdiction
provide warning tape as below:
3.1 PREPARATION
A. Identify and verify that required lines, levels, contours, and datum locations for the
work are as indicated.
B. Examine site and all work prepared by others including condition of adjoining
property and sites and report to the Engineer in writing any conditions detrimental
to the proper and timely completion of the work of this Section. Locate, identify and
protect all utilities found within or in proximity of the site.
C. Protect structures, utilities, sidewalks, pavements, and other facilities from damage
caused by settlement, lateral movement, undermining, washout, and other hazards
created by earth-moving operations.
E. Protect subgrades and foundation soils from freezing temperatures and frost.
Remove temporary protection before placing subsequent materials.
F. Make provision for all temporary work, scaffolding, staging, timbering, strutting and
other works as may be necessary and required for the proper, safe and efficient
performance and construction of the works intended and all works incidental
thereto in an expeditious manner to the complete satisfaction of the Engineer. Be
responsible for any damage done to roads, mains, cables, including safety to
persons and property, by the execution of the work.
G. The cost of furnishing, placing and removing the temporary works shall be included
in the Tender for the work.
H. Examine related work and surfaces before starting the work of this Section. Report
to the Engineer, in writing, conditions, which will prevent the proper provision of this
work. Beginning the work of this Section without reporting unsuitable conditions to
the Engineer shall constitute acceptance of conditions by the Contractor. Any
required removal, repair, or replacement of the work caused by unsuitable
conditions should be done at no additional cost to the Employer.
I. Be acquainted with all site conditions. The contractor is to be held responsible for
determining the location of all installed utilities lines within the site boundaries.
Should utilities not shown on Drawings be found during excavation, promptly notify
the Engineer for instruction as to further action. Failure to do so will result in liability
for any and all damage thereto arising from operations subsequent to discovery of
such utilities not shown on Drawings.
A. Earthworks shall not commence until the Contractor has provided the Engineer with
a method statement and obtained his approval to, the methods of excavation, the
means of support to sides of excavation, the safety and support of neighbouring
private and public property, the system of dewatering, the demolition of existing
3.3 DEWATERING
A. Prevent surface water and ground water from entering excavations, from ponding
on prepared subgrades, and from flooding Project site and surrounding area.
1. Reroute surface water runoff away from excavated areas. Do not allow water
to accumulate in excavations. Do not use excavated trenches as temporary
drainage ditches.
3.5 EXCAVATION
D. Compact disturbed load bearing soil in direct contact with foundations to original
bearing capacity; perform compaction in accordance with Contract requirements.
The bearing capacity should be the minimum as determined by the Engineer.
F. The use of explosives for breaking-out rock and hard structures is strictly prohibited
for all works.
G. Grade top perimeter of excavating to prevent surface water from draining into
excavation.
I. The location of temporary Spoil Heaps for all debris and excavated material are to
be submitted for the approval of the Engineer.
M. Removal of excavated material from site and its replacement as directed by the
Engineer shall be at the Contractor's own expense.
N. When excavation has reached the required subgrade elevation, notify the Engineer
who will make an inspection of the subgrade strata to review the strength and
bearing capacity of the soils.
Q. As soon as a section of the required excavation for foundation has been approved
by the Engineer, a working mat (plain cement concrete) of approved type thickness
and limits shall be placed over the soil bearing surface on the same work day. If
excavation has begun for foundation which may not be protected by a working mat
prior to the end of that work day, the excavation bottom shall remain at least
300mm above the design bottom of foundation bearing level until just before the
working mat is placed.
R. Trench Excavation(as applicable): Trenches for piping and utilities shall be not less
than 400mm nor more than 600mm wider than the outside diameter of the pipe to
be laid therein. Bottoms of trenches shall be accurately graded with bell holes
scooped out to provide uniform bearing and support of pipe and utilities on
undisturbed soil throughout its entire length, except where other means of
supporting pipe are indicated. Rock materials shall be excavated to 150mm below
pipe invert and bed backfilled with drainage fill, well tamped in place.
A. Stockpile borrow soil materials and excavated satisfactory soil materials without
intermixing. Place, grade, and shape stockpiles to drain surface water. Cover to
prevent windblown dust.
1. Stockpile soil materials away from edge of excavations. Do not store within
drip line of remaining trees.
3.8 BACKFILL
B. Systematically backfill to allow maximum time for natural settlement. Do not backfill
over porous, wet or spongy subgrade surfaces.
E. Structural fill as noted in this Section to be spread and leveled in layers not
exceeding 150 mm. Thoroughly compact each layer with a vibratory roller, vibrating
plate compactor, vibro hammer, power rammer or other suitable means, to the
Engineer satisfaction.
F. Concrete fill: For excavations performed below the elevations shown or specified
without the Engineer prior approval shall at the Engineer discretion and without any
additional cost, be backfilled with concrete of approved strength, unless instructed
otherwise by the Engineer.
G. Employ a placement method that does not disturb or damage other work.
H. Compact each layer of fill with suitable equipment to achieve the following
percentages of maximum dry density at optimum moisture content ±2% when
tested in accordance with ASTM D1557:
2. Do not compact soil when the moisture content varies more than 2% from the
optimum moisture content. Maintain moisture content by wetting or drying
manipulation. Suspend compacting operations when satisfactory results
cannot be obtained because of rain or other unsatisfactory conditions.
M. Submit details of plant, maximum depth of each compacted layer, minimum number
of passes per layer in advance of starting work for the approval of the Engineer.
N. Surfaces to receive sheet overlays or concrete are to have sufficient sand, fine
gravel or other approved fine material applied to fill interstices and provide a closed
smooth surface.
3.9 PROTECTION
A. Protecting Graded Areas: Protect newly graded areas from traffic, freezing, and
erosion. Keep free of trash and debris.
C. Where settling occurs before Project correction period elapses, remove finished
surfacing, backfill with additional soil material, compact, and reconstruct surfacing.
A. Unless otherwise instructed by the Engineer, remove surplus satisfactory soil and
waste materials, including unsatisfactory soil, trash, and debris, and legally dispose
of them off Employer's property.
A. The Engineer will instruct the Contractor to perform compaction tests to indicate
that the work meets the specified requirements and is fit for its purpose. Such
testing shall be at no additional cost to the Contract.
END OF SECTION
DEWATERING
PART 1 - GENERAL
1.2 SUMMARY
C. Reducing the hydrostatic pressure and lowering the water table within and around
the main and, the other excavations, the holding tanks and pits, at formation levels
such that:
1. There shall be no water seepage through the sides of the excavations into
same.
2. The water table within the excavations shall be maintained at the levels below
in this specification.
3. Any dewatering required within and around the main excavation to lower the
water table below the required levels.
D. Related Requirements:
A. Pre-installation Conference: Conduct conference at Project site one (1) week prior
to commencement of the work to review the material selections, installation
procedures and co-ordination of the work with other trades. The meeting shall be
attended by the Contractor, Engineer and any other Contractor or trade requiring
co-ordination with this work.
D. Record Drawings: Identify locations and depths of capped wells and well points and
other abandoned-in-place dewatering equipment.
E. Submit to the Construction Manager and Engineer 2 copies of any required permits
for disposal of water prior to installation.
A. Project-Site Information: A geotechnical report has been prepared for this Project
and is available for information only. The opinions expressed in this report are
those of a geotechnical engineer and represent interpretations of subsoil
conditions, tests, and results of analyses conducted by a geotechnical engineer.
Owner is not responsible for interpretations or conclusions drawn from this data.
PART 2 - PRODUCTS
A. Dewatering Systems shall provide dry, stable conditions for subsequent operations
within the excavations.
B. Design shall ensure no critical amounts of soil, sand or silt are removed during the
execution of work and no damage occurs to adjacent buildings, structures,
services, other constructions or other work.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine the site, the surrounding vicinity, including structures, and the data on
subsurface conditions for determination of the procedures and equipment required
to perform the work of this section.
B. Examine the Works and advise the Engineer in writing of any conditions detrimental
to the execution of the work of this Section. The absence of any such notification
will be taken to constitute the Contractor’s acceptance of conditions.
3.2 PREPARATION
A. Complete submittals and obtain required approvals before commencing the works.
B. Protect structures, utilities, sidewalks, pavements, and other facilities from damage
caused by settlement, lateral movement, undermining, washout, and other hazards
created by dewatering operations.
E. Protect and maintain temporary erosion and sedimentation controls, which are
specified during dewatering operations.
3.3 INSTALLATION
A. Install the dewatering systems in accordance with shop drawings and approved
method statement. Keep the Engineer advised of any changes made to
B. Install dewatering system utilizing wells, well points, or similar methods complete
with pump equipment, standby power and pumps, filter material gradation, valves,
appurtenances, water disposal, and surface-water controls.
C. Place dewatering system into operation to lower water to specified levels before
excavating below ground-water level.
E. Provide standby equipment on-site, installed and available for immediate operation,
to maintain dewatering on continuous basis if any part of system becomes
inadequate or fails.
3.4 OPERATION
A. Operate system continuously until drains, sewers, and structures have been
constructed and fill materials have been placed or until dewatering is no longer
required.
C. Prevent surface water and subsurface or groundwater from flowing into the
excavations or flooding the project site and surrounding area. Do not allow water to
accumulate in excavations.
D. During the final stages of excavation to lowest levels, and thereafter whilst
continuing dewatering the piezometric levels in the sub grade soils shall be
maintained at least 0.60 metres below the final excavation level to prevent soil
disturbance, the development of excessive unbalanced seepage gradients, and
potential loss of bearing support. Install devices to monitor groundwater levels
during this period to demonstrate compliance with these requirements.
1. Observe and record daily elevation of ground water and piezometric water
levels in observation wells.
2. Repair or replace, within 24 hours, observation wells that become inactive,
damaged, or destroyed. In areas where observation wells are not functioning
properly, suspend construction activities until reliable observations can be
made. Add or remove water from observation-well risers to demonstrate that
observation wells are functioning properly.
3. Fill observation wells, remove piezometers, and fill holes when dewatering is
completed.
C. Provide continual observation to ensure that subsurface soils are not being
removed by the dewatering operation.
3.6 REMOVAL
C. Clean and make good to the satisfaction of the Engineer any items disturbed by the
dewatering system installations, operation and removals.
3.7 PROTECTION
PART 1 GENERAL
1.2 SUMMARY
1. General requirements
2. Submittals and samples
3. Quality Control
4. Granular pipe surround
5. Concrete pipe surround
6. Suitable backfill material
7. Geotextile fabric
8. Buried marking tape
9. Service protection ducts
10. Marker posts
11. Trial holes
12. Temporary fencing and flagging
13. Trench support and stability
14. Pipe installation
15. Backfilling
1.4 DEFINITIONS
A. The Contractor shall comply with the following requirements, unless otherwise
approved by the Engineer.
10. Bottom of the trenches shall be properly trimmed off and compacted to
provide a firm and uniform bearing at formation level.
13. The minimum trench width for single line pipes shall be as indicated on
the drawings, unless otherwise instructed by the Engineer.
1.6 SUBMITTALS
A. Product Approval
a. Manufacturers name.
b. Suppliers name.
c. Product name (if applicable)
d. Product description
e. Manufacturers technical data
f. Storage instructions
g. Application instructions
B. Samples
C. Method Statement
A. Prior to dispatch from the factory, the Contractor shall notify the Engineer, in
sufficient time to allow the Engineer or his representatives to inspect and test
products, if so desired.
C. Testing Laboratory
2. During the course of the work, tests shall be carried out under the
supervision of the Engineer, to:
3. The Contractor shall maintain a daily log of all tests carried out for the
Engineer’s review.
D. Test Methods
1. Compaction tests to establish maximum dry density for all soils shall be
determined by BS 1377: Part 4: Method 3.5/3.6.
2. In situ density of compacted soils shall be determined by BS 1377: Part 9
Method 2.1 or 2.2 (as appropriate).
3. Cone penetration test (TRL Method or BS 1377).
4. Compaction fraction for granular surround shall as determined below:
1. General
a. A representative sample of pipe surround material (at least 25kg)
shall be obtained, under the Engineer’s supervision.
2. Apparatus Required
a. An open ended rigid cylinder 250mm3mm long and
150mm6mm internal diameter.
b. Metal rammer with striking face of 40mm dia. 0.5mm and
weighing 1000gm to 1100gm
c. Straight edge
d. Rule
e. Balance (minimum 12kg capacity)
3. Test Method
a. Obtain a representative sample more than sufficient to fill the
cylinder (about 12kg).
i The moisture content of the sample shall not differ
significantly from that of the main body of material at the
time of its use in the trench.
b. Hold the cylinder firmly down on a flat surface to prevent
movement and gently pour the sample into it, from a height of
approximately 50mm above the top of the cylinder, loosely and
without tamping.
c. Strike off the top surface level with the top of the cylinder and
remove all surplus spilled material.
d. Lift the cylinder up clear of its contents and place on a clean area.
e. Quarter the material and place one quarter of the material back
KEO/21-7387-0004 31 2333/ 7 Trench Excavation, Pipe Installation and Backfill
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
into the cylinder and tamp vigorously until no further compaction
can be obtained.
f. Repeat with the second quarter, tamping as before and so on for
the third and fourth quarter, tamping the final surface as level as
possible.
g. Measure down from the top of the cylinder to the surface of the
compacted material.
i Record the value to the nearest 1mm.
h. Divide the measured distance by the height of the cylinder
(measured to the nearest 1mm).
i. Report the value as the compaction fraction to the nearest 0.01.
F. Testing
6. The Contractor shall visually inspect all products upon delivery and report
any damage to the Engineer.
PART 2 PRODUCTS
C. Selected sandy soil shall be clean native sand free of rocks, vegetation,
foreign materials and large agglomerated pieces of sand.
D. Natural soil bedding shall be clean excavated material free of rocks and
foreign materials.
E. Concrete pipe surround shall be Grade C20 complying with Section 03 30 00.
A. Suitable material placed above the pipe surround for general trench backfill
(not within paved roadways or paved parking areas) shall conform to the
following requirements, unless otherwise approved by the Engineer.
2.3 GEOTEXTILE
A. Geotextiles for granular pipe surround shall comply with the requirements of
Table 1 below, unless otherwise approved by the Engineer.
D. The Contractor shall provide to the Engineer a certificate stating the name of
manufacturer, product name, style number, chemical composition of filaments
or yarns and other pertinent information to describe fully the geotextile.
G. Each geotextile roll shall be wrapped with a material that will protect the
geotextile from damage due to shipment, water, sunlight and contaminants.
TABLE 1
Geotextiles for Granular Pipe surround
Criteria Standard Limits Units
Tensile strength (strip EN ISO 10319 or Min 6 KN/m
test) ASTM D5035
Puncture resistance EN ISO 12236 Min 1000 N
Pore size EN ISO 12956 Max 120 Microns
Water permeability EN ISO 60500-4 50 to 125 litres/m²/Se
10cm water column c
Weight EN 965 Min 130 G/m²
A. Polyethylene plastic tape with metallic trace wire or metallic strip for electronic
detection meeting the following criteria:
C. For spigot and socket type pipes, the expansion joint in the concrete shall be
aligned with the face of the socket. For flexible detachable sleeve type joints,
the expansion joint filler material shall be positioned on one side of the
coupling as shown on the drawings, but the filler and concrete bed or
surround shall only be placed after the application of the specified corrosion
prevention system has been applied to the pipe ends and joint. No steel
reinforcement shall pass through the concrete expansion joint.
A. Pipe wrap placed around pipe joints or around pipes at stanks shall be
suitable self-adhesive waterproof membrane or other self–adhesive tape as
approved by the Engineer.
PART 3 EXECUTION
A. Trial holes shall be excavated well ahead of the trench excavation operation
to depths sufficient to determine the soil conditions, and confirm the locations
of underground utilities or other obstructions.
1. The Contractor shall arrange for the refilling and reinstatement of trial
holes to be carried out immediately after the required information is
obtained.
2. Reinstatement of trial holes shall be approved by the Engineer.
3. Excavation and reinstatement of trial holes shall be carried out at the
Contractor’s cost.
C. The Contractor shall also provide for the safety of animals which may gain
entry to the construction area and shall ensure that all open excavations,
access routes and steep or loose slopes arising from the Contractor's
operations are adequately fenced and protected.
A. The Contractor shall fully support the sides of all trench excavations, unless
the sides are stepped back at a safe and stable slope.
1. Support shall include the use of steel sheet piles or other suitable
sheeting and shoring to prevent any fall or run from any portion of the
ground outside the excavation into the trench and to prevent settlement
or damage to structures or utilities adjacent to the excavation.
1. If, the Contractor excavates the last 150mm before he is ready or able
to commence the work, he may be required to remove and replace
additional material as directed by the Engineer.
a. Any such further excavation and replacement of additional
foundation material ordered by the Engineer shall be at the cost
of the Contractor.
B. Should the trench bottom, while acceptable to the Engineer at the time of his
inspection, subsequently become puddled, soft or loose due to exposure or
flooding during the progress of the works, the Contractor shall remove such
damaged softened or loosened material and replace it with approved material
as directed by the Engineer.
C. Any stones or flints greater than 50mm in size shall be picked out of the
trench bottom. Any holes so formed shall be filled in with suitable material
and trimmed to the correct level.
D. All shattered and loose materials shall be removed from the bottom of the
trench excavations so that the pipe surround rests on a solid and clean
foundation.
F. In-Situ density tests shall be carried out to BS 1377; Part 9: Method 2.1 or 2.2
as appropriate.
A. Because flexible pipes rely in part on the surrounding soil to resist the
development of excessive deflections, it may be necessary, where trenches
pass through soft ground, to increase the trench width and replace the soft
native soil with imported material, or to introduce other measures to limit the
KEO/21-7387-0004 31 2333/ 15 Trench Excavation, Pipe Installation and Backfill
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
pipe deflection. All such measures shall be carried out as the work proceeds
and the Contractor shall be deemed to have included for the cost of all such
work in his Tender.
1. Concrete haunching shall be provided between the pipe and the trench
walls.
2. Trench sheeting shall be left in place below a level of 300mm above
the top of the pipe.
3. Precast concrete (or other approved material) slabs, having a height of
500mm or one pipe diameter, whichever is greater, shall be placed
vertically in the granular bedding material at the sides of the pipe mid-
way between the sides of the pipe and of the trench.
4. As an alternative to any of the above measures where considerations
of available space, practicality and economics permit, the trench width
may be increased to at least the minimum value obtained from the
following table.
Notes:
a. Where the static cone penetrometer test value is less than 3 kg/cm 2 a
construction method other than wide trench will normally be required.
1. Any excess excavation from the bottom or sides of the trench shall be
filled with the designated pipe surround material, unless otherwise
2. Pipe laying shall follow closely upon the progress of trench excavation.
1. If floatation has occurred, the Contractor shall remove and replace the
pipes after drying the trench, unless otherwise agreed with the
Engineer.
C. If the Engineer considers that the Contractor is not complying with any of the
foregoing requirements, he may prohibit further trench excavation until he is
satisfied with the progress of laying and testing of pipes and refilling of trench
excavation.
A. Pipe bedding, haunching and surround shall be of the type shown in the
Typical Drawings for rigid pipe and flexible pipe, unless otherwise approved
by the Engineer.
B. Select Sandy Soil Pipe surround shall be placed as follows when required by
the Typical Drawings, unless otherwise approved by the Engineer.
C. Pipe shown to be bedded in Natural Soil in the Typical Drawings shall be set
in a minimum of 102mm thick bed of Natural Soil Bedding lightly compacted.
1. Bell holes shall be provided to ensure that the pipe barrel is properly
supported.
2. Concrete shall not be placed until the joints at each end of the pipe
have been completed.
A. General trench backfill pertains to all areas outside paved roadways and
paved parking areas.
1. These areas include, but are not limited to, service corridors,
landscaped areas, undeveloped areas, non-asphalted roads, lanes,
alleys and all private lands.
B. Suitable material for general trench backfill shall comply with the requirements
found in Part 2 of this Specification.
C. Any soils utilised for landscaping shall be replaced in their original position
and condition.
1. In-situ density test shall be carried out to BS 1377: Part 9; Method 2.2.
E. Testing
A. General Requirements
B. Joints
3. Before making any joints the Contractor shall ensure that the interior of
each pipe or fitting is clean and that it remains clean.
4. Immediately before starting a joint, the Contractor shall clean the end
of each pipe to be joined and shall otherwise specially prepare the
ends for jointing as may be necessary for the particular kind of joint.
5. The Contractor shall use only the proper jointing materials (gaskets,
lubricants, nuts, bolts, washers, etc.) as specified for pipe service and
exposure conditions, as obtained from the designated supplier.
6. All joints shall be accurately made and shall be capable of passing the
designated tests for individual joints and for the completed pipeline as
may be specified.
1. For the purpose of reducing the angular deflections at pipe joints, and
for closure sections, the Contractor may be permitted to install pipe
sections of less than standard length, with the Engineers approval.
4. Pipe and methods of jointing shall be such that the locations of fittings
and lengths of pipe can be adjusted in the field to suit field conditions
and variations in stationing.
5. No extra payment will be made for such adjustments, nor for any
welding, couplings, fittings, or special lengths required to meet this
requirement.
8. Should any errors occur, the Contractor shall remedy the same, as the
Engineer directs, at his own expense.
D. Deflection at Curves
E. Cleanliness of Pipelines:
1. Pipeline and chambers shall at all times be kept free of all silt, mortar,
debris, trash and other obstructions.
2. When work is not in progress, the open ends of the pipeline shall be
securely plugged with an approved watertight plug or stopper firmly
fixed to resist unauthorised removal.
3. Claw type plugs or any type liable to damage the pipe will not be
approved.
5. The Contractor shall clear the inside of each fitting and pipe length
immediately prior to jointing.
a. Swab all fittings and pipe lengths to remove all dirt, sand or
other matter that may clog the line or contaminate the fluid to be
transported in the pipeline.
6. After jointing, the interior of the pipes shall be free from any dirt, stones
or other matter that may have entered them.
7. For this purpose, a rubber disc, brush or other suitable implement that
will not harm the internal lining of the pipe shall be pulled through the
pipe after jointing.
A. The Contractor shall arrange to inspect by colour CCTV the pipeline, for pipe
integrity and deformation. The equipment used to undertake the inspections
shall have tilt and pan facilities with zoom and be compact and portable to
minimise disruption to vehicular traffic as much as possible.
1. That the pipeline is reasonably clean and that no debris exists in the
invert of the pipeline.
2. That no unacceptable deformations exist.
3. That all the lateral connections have been identified and their
chainages recorded.
4. That no joints are seriously misaligned.
C. The Engineer and Contractor shall jointly review the CCTV surveys.
D. If, in the opinion of the Engineer, significant debris remains in the pipeline
after cleaning, the Engineer shall direct the Contractor to carry out further
cleaning and another CCTV inspection.
1. The CCTV inspection equipment shall include, but shall not be limited
to, the following units, all to the approval of the Engineer.
2. The camera shall be capable of taking clear and close pictures in any
direction i.e. 90 degrees to the left and 90 degrees to the right
(tota1180 degrees in horizontal axis) and also 360 degrees in the
circumference of the pipe without using an extra revolving mirror
attachment.
1. The rate of travel of the camera shall be such as to enable all details to
be extracted from the video tape recording, but normally shall not
exceed 0.1m/s for pipelines below 200mm diameter, 0.15m/s for
pipelines between 200mm and 300mm diameter and 0.2m/s for
pipelines exceeding 300mm diameter.
2. The axis of the camera shall be set up to coincide with the centreline of
the pipe.
H. Programme or Inspection:
1. The programme for carrying out the CCTV Inspection and for handing
over the CCTV records shall be agreed with the Engineer.
1. The Contractor shall record the whole of the inspection in a VHS video
tape format or any other latest format approved by the Engineer
conforming with the recording equipment manufacturer's specification.
The recording shall give a continuous display of data on the monitor
screen which shall include the following information:
J. The video recording shall be stopped whenever the camera is stationary for
more than 5 seconds and shall have manual override capability.
3.15 STANKS
B. The cost of providing stanks shall be included in the Contractor's rates for
pipe laying.
A. The Contractor shall be responsible for ascertaining from his own inspection
KEO/21-7387-0004 31 2333/ 29 Trench Excavation, Pipe Installation and Backfill
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
of the Site and coordination with respective utility authorities and other public
bodies, the position of all mains, pipes and cables whether underground or
overhead, within or near the Site or existing structures.
A. Where trench excavation crosses barriers such as fences and walls, the
Contractor shall obtain written approval of the Engineer before breaching the
barrier.
B. The Contractor shall provide temporary fencing for any parts of such barriers
as have had to be removed.
C. After trench excavation has been reinstated, the Contractor shall carry out
such work as the Engineer may order, for permanent restoration of such
barriers.
A. Contractor shall be deemed to have allowed for all the additional measures
necessary for the proper construction of the pipeline where it crosses under or
over streams, culverts, pipes and other watercourses, including maintaining
the full flow of water.
A. Buried marking tape shall be placed in the trenches above all pipes.
END OF SECTION
KEO/21-7387-0004 31 2333/ 31 Trench Excavation, Pipe Installation and Backfill
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
SECTION 31 3116
TERMITE CONTROL
PART 1 - GENERAL
1.2 SUMMARY
A. Section Includes:
B. Related Requirements:
A. Preinstallation Conference: Conduct conference at Project site one (1) week prior
to commencement of the work.
B. Materials: Provide certification that toxicants are not in violation of the Authorities
having Jurisdiction.
A. Soil Treatment:
1.8 WARRANTY
A. Provide ten year warranty for material and installation under provisions of contract
from the date of certified substantial completion.
2.1 MANUFACTURERS
A. Source Limitations: Obtain termite control products from single source from single
manufacturer.
1. Service Life of Treatment: Soil treatment termiticide that is effective for not
less than ten (10) years against infestation of subterranean termites.
2. Toxicant Chemical: Approved as per requirements of Authorities Having
Jurisdiction, synthetically colour dyed to permit visual identification of treated
soil.
3. Diluents: Recommended by toxicant manufacturer.
4. Mix toxicant to manufacturer’s instructions.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Applicator present, for compliance
with requirements for moisture content of soil per termiticide label, interfaces with
earthwork, slab and foundation work, landscaping, utility installation, and other
conditions affecting performance of termite control.
B. Proceed with application only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
B. Soil Treatment Preparation: Remove foreign matter and impermeable soil materials
that could decrease treatment effectiveness on areas to be treated. Loosen, rake,
and level soil to be treated, except previously compacted areas under slabs and
footings. Termiticides may be applied before placing compacted fill under slabs if
recommended in writing by termiticide manufacturer.
KEO/21-7387-0004 31 3116/ 3 Termite Control
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
1. Fit filling hose connected to water source at the site with a backflow preventer,
according to requirements of authorities having jurisdiction.
3.5 PROTECTION
A. Avoid disturbance of treated soil after application. Keep off treated areas until
completely dry.
B. Protect termiticide solution dispersed in treated soils and fills from being diluted by
exposure to water spillage or weather until ground-supported slabs are installed.
Use waterproof barrier according to Authorities Having Jurisdiction Registered
Label instructions.
END OF SECTION
PART 1 - GENERAL
1.2 SUMMARY
B. Related Requirements:
1. Section 312000 "Earth Moving" for excavating and backfilling and for
controlling surface-water runoff and ponding.
A. Preinstallation Conference: Conduct conference at Project site one (1) week prior
to commencement of the work.
A. Interruption of Existing Utilities: Do not interrupt any utility serving facilities occupied
by Owner or others unless permitted under the following conditions and then only
after arranging to provide temporary utility according to requirements indicated:
1. Notify Architect and Construction Manager no fewer than two days in advance
of proposed interruption of utility.
2. Do not proceed with interruption of utility without Architect's, Construction
Manager's and Owner's written permission.
B. Project-Site Information: A geotechnical report has been prepared for this Project
and is available for information only. The opinions expressed in this report are
those of a geotechnical engineer and represent interpretations of subsoil
conditions, tests, and results of analyses conducted by a geotechnical engineer.
Owner is not responsible for interpretations or conclusions drawn from the data.
C. The Contractor must be familiar with below grade soil and water conditions in the
project area and have proven experience with the type of work specified in this
Section. The contractor’s site foreman must be familiar with below grade soil and
water conditions in the project area and must have proven experience for direction
to workers in the type of work specified in this Section.
A. Protect and maintain existing active sewer, water, gas, electricity and other utility
services and structures outside the property line but within the working area.
B. Co-ordinate with all utilities authorities and pay all related fees for relocating the
required utilities, including all design and installations fees.
C. Notify municipal agencies and service utility companies and comply with
requirements of governing authorities and agencies for protection, relocation,
removal and discontinuance of services.
PART 2 - PRODUCTS
A. The Contractor shall be responsible for the design, monitor, and maintain excavation
support and protection system capable of supporting excavation sidewalls and of
resisting earth and hydrostatic pressures and superimposed and construction
loads.
1. The design of the system shall be capable of supporting excavation side walls
and of resisting earth and hydrostatic pressures and superimposed and
construction loads.
C. Ground Anchors
1. Design and execution of ground anchorages shall comply with BS 8081 and
BS EN 1537.
2. Anchors shall be stressed anchors in soil or rock.
3. Temporary and permanent (if any) anchors shall be designed in accordance
with BS 8081 and BS EN 1537.
4. The anchors shall be held in with wedges, or threaded bar with bearing plate
and bolt, no welding shall be allowed for this purpose.
5. Tension couplers shall be used for anchors longer than 12m. No welding of
anchor bars is permitted.
1. On-Site Suitability Tests shall be carried out in accordance with BS 8081 and
BS EN 1537 on ground anchors constructed under identical conditions as the
working ground anchors shown on the shop drawings and loaded in the same
way to the same level. All ground anchors must be pre-stressed to 120% and
locked of at 75% of design force. Ground anchors used for On-Site Suitability
Tests may be used in the works as provided for in BS 8081, BS EN 1537 and
subject to the approval of the Engineer. Unless directed otherwise by the
Engineer the first three anchorages of each category (in terms of geometry,
ground type and load capacity) shall be tested to the satisfaction of the
Engineer. The results shall be deemed to be satisfactory provided that they
comply with the assessment criteria for On-Site Suitability tests given in BS
8081 and BS EN 1537 in terms of proof load-time data. Failure to comply with
the assessment criteria shall require the Contractor to revise his ground
anchor proposals and/or undertake further testing to the satisfaction of the
Engineer until satisfactory results can be achieved. On-Site Suitability Tests
for each category of ground anchor shall be completed to the satisfaction of
the Engineer before any working anchors in each category are installed.
2. The Contractor shall keep full records of all Proving and On-Site Suitability
Tests in accordance with this Specification. Copies of these records shall be
provided to the Engineer within 24 hours of completion of each test.
2.2 MATERIALS
D. Wood Lagging: Lumber complying to ASTM D245, ASTM D5055, ASTM D5456;
Lumber, mixed hardwood, mixed hardwood, nominal rough thickness of size and
strength required for application.
G. Tiebacks: Steel bars, ASTM A 722/A 722M. Sizes and capacities shall be
submitted by the Contractor for Engineer review and approval.
H. Tiebacks: Steel strand, ASTM A 416/A 416M. Sizes and capacities shall be
submitted by the Contractor for Engineer review and approval.
PART 3 - EXECUTION
3.1 PREPARATION
A. Protect structures, utilities, sidewalks, pavements, and other facilities from damage
caused by settlement, lateral movement, undermining, washout, and other hazards
that could develop during excavation support and protection system operations.
A. Install earthwork support systems in accordance with approved designs, details and
sequence. Notify the Engineer immediately should any deviations there from be
necessary and unavoidable.
B. Monitor the movements of the lateral support systems by carrying out regular tests
or inspections of specific reference points in the support systems. All such data
shall be collected, recorded and submitted to the Engineer for approval.
C. Take steps to control any unacceptable movement in the lateral support systems
immediately by providing supplemental bracing or other measures (working 24
hours per day if necessary) as required if any of the following occur:
A. Install steel soldier piles before starting excavation. Extend soldier piles below
excavation grade level to depths adequate to prevent lateral movement. Space
soldier piles at regular intervals not to exceed allowable flexural strength of wood
lagging. Accurately align exposed faces of flanges to vary not more than 50 mm
from a horizontal line and not more than 1:120 out of vertical alignment.
B. Install wood lagging within flanges of soldier piles as excavation proceeds. Trim
excavation as required to install lagging. Fill voids behind lagging with soil, and
compact.
A. Before starting excavation, install one-piece sheet piling lengths and tightly
interlock vertical edges to form a continuous barrier.
B. Accurately place the piling, using templates and guide frames unless otherwise
recommended in writing by the sheet piling manufacturer. Limit vertical offset of
adjacent sheet piling to 1500 mm. Accurately align exposed faces of sheet piling to
vary not more than 50 mm from a horizontal line and not more than 1:120 out of
vertical alignment.
3.5 TIEBACKS
B. Test load-carrying capacity of each tieback and replace and retest deficient
tiebacks.
3.6 BRACING
A. Bracing: Locate bracing to clear columns, floor framing construction, and other
permanent work. If necessary to move brace, install new bracing before removing
original brace.
3.9 CLEANING
A. Clean and make good to the satisfaction of the Engineer any items disturbed by the
installations of the earthwork support systems and their subsequent removals.
END OF SECTION
END OF INDEX
KEO/21-7387-0004 Index/1
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
SECTION 07 9200
JOINT SEALANTS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Furnish all labor, materials, tools appliances and equipment and perform all
operations and services necessary for the complete installation of sealants for the
following applications
1. Exterior joint sealant in horizontal traffic surfaces.
a. Joints between different materials and curbs/upstands.
B. Related Section: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 033000 - "Cast-in-Place Concrete"
2. Section 321400 - "Unit Paving"
1.02 REFERENCES
A. Provide elastomeric joint sealants that establish and maintain watertight and airtight
continuous joint seals without staining or deteriorating joint substrates.
1.04 SUBMITTALS:
B. Samples: For each type and color of joint sealant required. Install joint sealants in
13 mm wide joints formed between two 300 mm long strips of actual material the
sealant to be with. To be inspected for staining, sagging and adhesion one week
and four weeks after the sample is submitted.
E. Compatibility and Adhesion Test Reports: From sealant manufacturer indicating the
following:
1. Materials forming joint substrates and joint sealant backings have been tested
for compatibility and adhesion with joint sealants.
2. Sealants will not stain Stone, or other substrates when tested in accordance
with ASTM C 1248, or other acceptable testing criteria.
3. Interpretation of test results and written recommendations for primers and
substrate preparation needed for adhesion.
F. Product Test Reports: From a qualified testing agency indicating sealants comply
with requirements, based on comprehensive testing of current product formulations.
G. Submit a detailed schedule of sealant usage for all locations. List each sealant
material, joint fillers, color and product data for each location of use (include joint
size), along with acceptable temperature, humidity and weather conditions at time of
application.
A. Submit documented proof that the material has a proven record of successful
performance for more than 10 years, confirmed by at least five local projects.
D. Source Limitations: Obtain each type of joint sealant through one source from a
single manufacturer.
KEO/21-7387-0004 07 9200 / 2 Joint Sealants
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
E. Product Testing: Obtain test results for "Product Test Reports from a qualified
testing agency based on testing current sealant formulations within a 36-month
period preceding the commencement of the Work.
1. Testing Agency Qualifications: An independent testing agency qualified
according to ASTM C 1021 to conduct the testing indicated, as documented
according to ASTM E 548.
2. Test elastomeric joint sealants for compliance with requirements specified by
reference to ASTM C 920, and where applicable, to other standard test
methods.
3. Test other joint sealants for compliance with requirements indicated by
referencing standard specifications and test methods.
B. Joint-Width Conditions: Do not proceed with installation of joint sealants where joint
widths are less than those allowed by joint sealant manufacturer for applications
indicated, or when anticipated frequency and extent of joint movement exceed
sealant manufacturers limitations.
1.08 WARRANTY
PART 2 - PRODUCTS
A. Products and manufacturers specified hereinafter are specified for the purposes of
establishing minimum quality standards and performance requirements. Products
which are equal to, or better than those specified, and which conform to the
2.02 MATERIALS
A. Compatibility: Provide joint sealants, backings, and other related materials that are
compatible with one another and with joint substrates under conditions of service and
application, as demonstrated by sealant manufacturer based on testing and field
experience.
B. Comply with ASTM C 1193 - Standard guide for use of Joint Sealants.
A. Elastomeric Sealant Standard: Comply with ASTM C 920 and other requirements for
classifications, for type, grade, class, and uses.
1. M, G & A sealants that remain adhered to Portland cement mortar
(M), clear float glass (G), and clear-anodized aluminum (A).
2. O substrate materials other than M, G and A.
3. T joints in surfaces subject to pedestrian and vehicular traffic.
4. NT classifies sealants designed for non-traffic areas.
F. Exterior horizontal Control Joints in paving for pedestrian traffic, Control Joints in
stone paving and Joints between different paving materials and curbs/upstands;
Isolation and contraction joints in cast-in-place concrete grade slabs:
1. Single component, polyurethane elastomeric sealant capable of 25%
movement as measured in compliance with ISO 11600 Class F-25 LM.
a. Basis-of-Design Product: Mapeflex PU40 or approved equal.
b. Color: to match the surround
A. General: Provide sealant backings of material and type that are nonstaining; are
compatible with joint substrates, sealants, primers, and other joint fillers; and are
approved for applications indicated by sealant manufacturer based on field
experience and laboratory testing.
B. Cylindrical Sealant Backings: ASTM C 1330, of size and density to control sealant
depth and otherwise contribute to producing optimum sealant performance. Provide
closed-cell backing rod diameter of which should be approximately 30% greater that
joint width thus allowing correct with/depth ratio to be maintained
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine joints indicated to receive joint sealants, with Installer present, for
compliance with requirements for joint configuration, installation tolerances, and
other conditions affecting joint-sealant performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 PREPARATION
A. Surface Cleaning of Joints: Clean out joints immediately before installing joint
sealants to comply with joint sealant manufacturer's written instructions and the
following requirements:
1. Remove all foreign material from joint substrates that could interfere with
adhesion of joint sealant, including dust, paints (except for permanent,
protective coatings tested and approved for sealant adhesion and
compatibility by sealant manufacturer), old joint sealants, oil, grease,
waterproofing, water repellents, water, surface dirt, and frost.
a. Clean porous joint substrate surfaces like concrete and stone surfaces
by brushing, grinding, blast cleaning, mechanical abrading, or a
combination of these methods to produce a clean, sound substrate
capable of developing optimum bond with joint sealants. Remove
loose particles remaining from above cleaning operations by
vacuuming or blowing out joints with oil-free compressed air.
2. Remove laitance and form-release agents from concrete.
B. Joint Priming: Prime joint substrates where recommended in writing by joint sealant
manufacturer, based on preconstruction joint-sealant-substrate tests or prior
experience. Apply primer to comply with joint sealant manufacturer's written
instructions. Confine primers to areas of joint-sealant bond; do not allow spillage or
migration onto adjoining surfaces.
C. Masking Tape: Use masking tape where required to prevent contact of sealant with
adjoining surfaces that otherwise would be permanently stained or damaged by such
contact or by cleaning methods required to remove sealant smears. Remove tape
immediately after tooling without disturbing joint seal.
A. General: Comply with joint sealant manufacturer's written installation instructions for
products and applications indicated, unless more stringent requirements apply.
D. Install bond-breaker tape behind sealants where sealant backings are not used
between sealants and back of joints.
E. Install sealants by proven techniques to comply with the following and at the same
time backings are installed:
1. Place sealants so they directly contact and fully wet joint substrates.
2. Completely fill recesses provided for each joint configuration.
3. Produce uniform, cross-sectional shapes and depths relative to joint widths
that allow optimum sealant movement capability.
A. Inspect joints for complete fill, for absence of voids, for joint configuration and shall
be smooth and uniform. Any sealant found out of plumb or cracking or any work
otherwise defective shall be taken out and replaced to approval, at no additional cost
to the Project.
B. Waterproof Test: After curing exterior compounds, test joints for leaks by applying a
stream of water perpendicularly from a 20mm hose at normal city pressure. Test the
sealed joint system of not less than 5% of the construction components. Conduct
tests in the presence of the Engineer who will determine the actual percentage of
joints to be tested and the period of water flow exposure, based upon any evidence
of leakage. Repair leaks or other defects and retest as directed. Repair or replace
other works damaged by such leaks.
3.05 CLEANING
3.06 PROTECTION
A. Protect joint sealants during and after curing period from contact with contaminating
substances and from damage resulting from construction operations or other causes
so sealants are without deterioration or damage at time of Substantial Completion.
If, despite such protection, damage or deterioration occurs, cut out and remove
damaged or deteriorated joint sealants immediately so installations with repaired
areas are indistinguishable from the original work.
END OF SECTION
EARTHWORKS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section. The Contractor is
fully responsible for all permits according to the local regulations and shall bear all costs.
Where these specifications differ, or are not aligned with Standard ADM Specifications, ADM
Specifications will take precedent. This particular specification shall at all times be read in
conjunction with the Standard ADM Specifications, Contract documents and other documents
that constitute the entire contract.
A. Furnish all labour, materials, tools and equipment and perform all services and
operations necessary for earthwork including, but not limited to, the following:
1. Preparing subgrades for pavements.
2. Excavating and backfilling for landscape works.
B. The Contractor shall obtain all approvals, permits and pay all relevant fees (for 24hrs
day work schedule) associated with excavation and disposal of excavated materials.
C. Related Sections: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 32 1400.13 - Unit Pavers
2. Section 32 9300 - Plants
E. In the event asbestos is found during the earthworks operations, the Contractor shall
localise and isolate the areas; contact and coordinate with respective Government
agencies in order to ensure correct implementation of approved methods and
F. Work in other areas shall continue to mitigate any risk for delays.
1.02 REFERENCES
F. Bedding Course: Layer placed over the excavated subgrade in a trench before laying
pipe.
G. Borrow: Soil material obtained off-site when sufficient approved soil material is not
available from excavations.
H. Unyielding Material: Unyielding material shall consist of rack and granular soils with
stones greater than 50 mm, in any dimension or as defined by the pipe manufacturer,
whichever is smaller.
I. Unstable Material: Unstable material shall consist of material too wet to properly work.
K. Fill: Compacted structural fill to raise the grade to required level to receive foundation
and grade slab.
M. Utilities include on-site underground pipes, conduits, ducts, and cables, as well as
underground services within buildings.
N. Formation: Formation shall mean the surface of the ground after completion of any
excavation or filling operation.
O. Topsoil: Topsoil shall mean soil which by its nutrient content is capable of supporting
the growth of vegetation.
P. Stones: Stones shall be round or angular, greater than .13 m in dimension, but smaller
than .5 m in dimension, and average in volume of .38 cu.m. Stone shall be indigenous
material saved from excavation and stockpiled during earthwork.
Q. Boulder: Boulders shall be of size bigger than stones, but able to be moved by a
loader equipped with a 2000 mm bucket. Boulders shall be indigenous material
removed from excavations and stockpiled during earthwork
A. Construction Activity Pollution Prevention Plan to prevent pollution due to Soil Erosion,
Waterway Sedimentation and Airborne Dust Generation. A plan need to be drawn in
line with EPA Construction General Permit ,(Copy is available for inspection with the
Engineer ).The EPA’s Construction General Permit outlines requirements of NPDES (
National Pollutant Discharge Elimination System). The Affected Area need to be
graveled at perimeter and sloped inward. The entry of Vehicles need to be graveled
to prevent soil carry over.
C. Technical Data:
1. Catalogues of heavy equipment used for excavation and earth removal.
D. Shop Drawings
1. Prepared by or under the supervision of a qualified professional engineer
2. Shop drawings including plan of complete site showing area and extent of
excavation and capping of any existing underground utilities to remain.
a. Shop drawings shall show profiles, formation levels, pits, transitions etc.
E. Shop Drawings
1. Prepared by or under the supervision of a qualified professional engineer
2. Shop drawings including plan of complete site showing area and extent of
excavation and capping of any existing underground utilities to remain.
a. Shop drawings shall show profiles, formation levels, pits, transitions etc.
3. Shop Drawings and Structural Calculations for excavation support system:
a. Shop drawings and structural calculations shall bear the official seal and
signature of the Contractor’s registered engineer described in this
Section of the Specifications.
b. Show engineering calculations, fabrication, installation, anchorage, tie-
backs if any, layout, member sizes, connection details, into rock
anchoring, types, grades and strengths of materials, standards for
compliance of materials, excavations, dewatering.
H. Structural fill: A specialist design and build foundation contractor with extensive
experience (minimum 15 years) in the type of works required. The work shall be
engineered by a fully qualified registered geotechnical/foundation design engineer
with ten years minimum experience and licensed to design structural fill in the Country
where the project is being executed. This engineer may be required to demonstrate
proven experience with the design and engineering of this type of work and shall
submit professional qualifications to the Engineer for approval.
1. Delegated Design Responsibility: Notwithstanding the drawings and other
information provided, the specialist contractor shall be fully responsible for the
design, detailing of the works described herein, including (without limitation) the
I. Material Test Reports: From a qualified testing agency indicating and interpreting test
results for compliance of the following with requirements indicated:
1. Classification according to ASTM D 2487 of each on-site and borrow soil
material proposed for fill and backfill.
2. Laboratory compaction curve according to ASTM D 698, ASTM D 1557 for
each on-site and borrow soil material proposed for fill and backfill.
3. Report of actual unconfined compressive strength and/or results of bearing
tests of each stratum testing.
4. Particle size analysis shall be in accordance with ASTM D422-63.
5. Sieve analysis shall be in accordance with ASTM C136 and ASTM D422 on
sieves conforming to ASTM E11.
6. Liquid Limit and Plasticity Index: One liquid limit and plasticity index shall be
performed for each sieve analysis. Liquid limit and plasticity index shall be in
accordance with ASTM D4318.
K. Excavation Supervisor: Allow for employing full time on site, an experienced and
qualified excavation supervisor. Submit with the Tender, full resume details of the
Supervisor. No excavation shall start until the Engineer has approved the nominated
Supervisor.
KEO/21-7387-0004 31 2000 / 5 Earthworks
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
1.05 QUALITY ASSURANCE
C. Testing and Inspection: Testing and inspection shall be the responsibility of the
Contractor and shall be performed at no additional cost to the Employer.
1. Testing Facilities: Test shall be performed by an approved commercial testing
laboratory. No work requiring testing will be permitted until the facilities have
been inspected and approved by the Engineer.
2. Notice Period: Provide agreed notice to enable the Engineer to be present, if
so desired, at whatever inspections or tests are performed.
a. Notice Period: No Less Than
b. Inspection on Site 1 Day.
c. Tests performed on Site 1 Day.
d. Material inspections or tests to be witnessed offsite 5 Days.
3. Accept responsibility for providing, controlling, calibrating and maintaining
inspection, measuring and test equipment suitable to demonstrate that the
Works comply with the specified requirement. Make this or similar equipment
available to the engineer whenever required for examination of the Works.
B. Demolish and completely remove from site existing underground utilities. Coordinate
with utility companies to shut off services if lines are active.
1. The location of known services shall be confirmed by trial pits prior to
excavation works.
2. Obtain the authorities’ existing services NOC to proceed with the earth works
and obtain all necessary information and drawings to identify the existing
services.
E. Nature of Excavation:
1. Include for excavating in any type of ground encountered.
2. Include for breaking up rock materials, materials so firmly cemented as to
possess the characteristics of rock, concrete or masonry structures, or any
other hard or compacted materials encountered in excavations, all at the
Contractor's cost.
F. Protection
1. Barricade open excavations made as part of earthwork operations and post
with warning lights. Operate warning lights as recommended by the Engineer.
PART 2 - PRODUCTS
A. General: Provide borrow soil materials when sufficient satisfactory soil materials are
not available from excavations.
1. To be free from plastic fines and weakly cemented lumps of sand.
2. To be homogeneous and at the optimum moisture content for compaction
purposes when placed.
3. Sand layers which present liquefaction potential below structural filling must be
compacted so that they reach a minimum cone resistance of 5 MPa.
4. Any slopes required will be as shown on drawings.
5. Water: Water used for compacting fill shall be clean and free from oil, grease,
organic matter, suspended fine sediment and other deleterious substances.
B. Satisfactory Soil Materials: Fill, embankment, and subgrade within the building lines
of structures shall be those materials classified in ASTM D 2487 soil classification
groups as GW, GP, GM, SW, SP and SM; free of rock or gravel larger than 50 m in
any dimension, debris, waste, vegetation and other deleterious matter. In all other
areas, satisfactory soil materials shall comply with ASTM D 2487 soil classification
groups GW, GP, GM, SW, SP and SM and also shall include GC and SC. The soil
shall contain less than 30% of the fines passing the 75 micrometer sieve and not more
than 40% passing the 4.75 mm sieve. The plasticity index of the fines faction shall be
less than 12%.
F. Engineered Fill (Structural Fill): Materials for structural fill shall consist of granular,
well graded soils having a maximum particle size of 75 mm and contain less than 12%
by weight of material passing the 75 micrometer sieve. Where structural fill is used as
a sub base material for slabs on grade without lean mix blinding the surface shall be
blinded with sand or crushed fine material to form a smooth level surface with a
tolerance of ± 20 mm. The plasticity index of the fines fraction shall be less than 6%.
This material shall be defined as either soil classification GW or SW in accordance
with ASTM D2487, Method of Classification. Structural fill shall be imported from local
source and must have low sulfate and chloride concentration not exceeding 1200 mg/L
for sulfate and 500 mg/L for chloride.
J. Cohesive Soil Materials: Cohesive soil materials include materials classified in ASTM
D2487 as GC, SC, ML, CL, MH and CH.
2.02 EQUIPMENT
A. General
1. The equipment utilized in carrying out earthwork and related work shall be in
good working conditions, and the Contractor shall maintain them in such
condition for the duration of the Contract.
2. The Contractor shall supply adequate equipment as deemed necessary for the
proper execution of the Work.
3.01 EXAMINATION
A. Examine related work and surfaces before starting the work of this Section. Report
in writing, conditions, which will prevent the proper provision of this work. Beginning
the work of this Section without reporting unsuitable conditions shall constitute
acceptance of conditions by the Contractor. Any required removal, repair, or
replacement of the work caused by unsuitable conditions should be done at no
additional cost to the Employer.
3.02 PREPARATION
A. Protect structures, utilities, sidewalks, pavements, and other facilities from damage
caused by settlement, lateral movement, undermining, washout, and other hazards
created by earthwork operations.
C. Make provision for all temporary work, scaffolding, staging, timbering, strutting and
other works as may be necessary and required for the proper, safe and efficient
performance and construction of the works intended and all works incidental thereto
in an expeditious manner. Be responsible for any damage done to roads, mains,
cables, including safety to persons and property, by the execution of the work.
D. The cost of furnishing, placing and removing the temporary works shall be included in
the Tender for the work.
E. Examine related work and surfaces before starting the work of this Section. Report
in writing, conditions, which will prevent the proper provision of this work. Beginning
the work of this Section without reporting unsuitable conditions shall constitute
acceptance of conditions by the Contractor. Any required removal, repair, or
replacement of the work caused by unsuitable conditions should be done at no
additional cost to the Employer.
F. Be acquainted with all site conditions. Should utilities not shown on Drawings be
found during excavation, promptly submit Contractor’s proposed action. Failure to do
so will result in liability for any and all damage thereto arising from operations
subsequent to discovery of such utilities not shown on Drawings.
3.03 DEWATERING
A. Prevent surface water and ground water from entering excavations, from ponding on
prepared subgrades, and from flooding Project site and surrounding area.
B. Protect subgrades from softening, undermining, washout, and damage by rain or water
accumulation.
A. Structural fill to be compacted to achieve the required bearing pressure by one of the
following methods:
1. As per Sub-Clause 10.7.2, along with geosynthetics reinforced mat indicated
within Volume 4.1, Appendix A, Geotechnical Investigation Report.
2. Vibration by Dynamic Compaction.
3. By vibration and displacement of fill using Geopiers and Vibro Piers
A. Generally:
1. Excavate to the depths and profiles shown on the Drawings or as directed.
2. Allow sufficient working space where necessary for the erection of earthwork
support system.
3. Report any unexpected subsurface conditions and discontinue affected work in
area, until notified to resume work.
4. Any soft material, or non-compactable material found at the bottom of
excavated areas shall be removed and replaced with acceptable bedding
material, placed in lifts not exceeding 150mm and compacted as further
described.
B. Adjacent Excavations:
1. Where an excavation encroaches below a line drawn at an angle of 60° from
the horizontal from the nearest formation level of another higher excavation, the
lower excavation, all work within it, and backfilling thereto shall be completed
before the higher excavation is made.
C. Excavated Formations:
1. In made up ground excavate foundations down to a natural bearing formation
of undisturbed subsoil, unless otherwise instructed.
2. Obtain instructions if a natural bearing formation of undisturbed subsoil:
a. Is obtained at a lesser depth than that shown on the Soils Report.
b. Is not obtained at the depth shown on the Soils Report.
3. If, after inspection, formation becomes unsuitable for any reason, excavate
further and backfill with approved material all at the Contractor's expense.
A. Protect structures, utilities, sidewalks, pavements, and other facilities from damage
caused by settlement, lateral movement, undermining, washout, and other hazards
that could develop during excavation support and protection system operations.
1. Shore, support and protect utilities encountered and designated to be retained
2. Do not close or obstruct streets, walks or other adjacent facilities without
permission from the authorities. Provide alternate routes around closed or
obstructed traffic ways if required.
C. Monitor excavation support and protection systems daily during excavation progress
and for as long as excavation remains open. Promptly correct bulges, breakage, or
other evidence of movement to ensure that excavation support and protection systems
remain stable.
A. Excavate surfaces under walks and pavements to indicated lines, cross sections,
elevations, and subgrades.
B. The sides of trenches shall have a gradient adapted to the stability of the soil.
C. Excavate trenches to uniform widths to provide the following clearance on each side
of pipe or conduit. Excavate trench walls vertically from trench bottom to 300 mm
higher than top of pipe or conduit, unless otherwise indicated.
1. Clearance: 300 mm each side of pipe or conduit or as indicated.
D. Trench Bottoms: Excavate and shape trench bottoms to provide uniform bearing and
support of pipes and conduit. Shape subgrade to provide continuous support for bells,
joints, and barrels of pipes and for joints, fittings, and bodies of conduits. Remove
projecting stones and sharp objects along trench subgrade.
1. For pipes and conduit less than 150 mm in nominal diameter and flat-bottomed,
multiple-duct conduit units, hand-excavate trench bottoms and support pipe and
conduit on an undisturbed subgrade.
2. For pipes and conduit 150 mm or larger in nominal diameter, shape bottom of
trench to support bottom 90 degrees of pipe circumference. Fill depressions
with tamped sand backfill.
3. Excavate trenches 150 mm deeper than elevation required in rock or other
unyielding bearing material to allow for bedding course.
F. Hand excavation must be applied along the parts where existing cables, water, gas
and oil mains, sewers etc. cross the trench or in the main roads where traffic is likely
to be unreasonably disturbed by the use of machines. In other places hand or
machine excavation may be used. Excavation by machine must not normally be
executed deeper than 15cm above the bottom of the trench. Be held responsible for
making good all damage to road surfaces and private lands caused by the other use
of mechanical excavators.
KEO/21-7387-0004 31 2000 / 13 Earthworks
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
G. Excavate for utility connections by machine or micro-tunneling as required and
instructed by the local authorities.
H. If, due to negligence or error, any excavations are taken down to a level lower than is
shown on the Drawings, fill in the void so formed to the proper level with approved
material in layers not exceeding 15 cm thick which shall be thoroughly compacted by
tamping. The finished subgrade shall be prepared accurately by means of hand tools.
If concrete is necessary for this filling, then provide this at no additional cost.
A. Open-cut excavation should be braced and sheeted adequate to the strength design
to protect persons, property, traffic on the work or to prevent caving and harmful
sinking. Be responsible for adequacy of any required sheeting and bracing. Be
responsible for any accidents to people, any damage done to roads, mains, cables,
pipes, sewers, etc. by the execution of the work. When close sheeting is required, it
shall be so driven as to prevent adjacent soil from entering the excavation either below
or through such sheeting. Sheeting and bracing shall be provided as a standard for
excavations 1.50m and above depth. Where sheeting and bracing are used, trench
widths shall be increased accordingly. The strength design of the system of supports
should be based on the principles of soil mechanics as they apply to the materials
encountered. Sheeting and bracing must always comply with approved safety
requirements.
B. The Engineer’s Representative reserves the right to order the sheeting to be driven to
the full depth of the excavation or to such additional depths as may be required for the
protection of the work.
C. Bracing must be removed when the backfilling has reached the respective levels of
such bracing. Sheeting must be removed after the backfilling has been completed or
has been brought up to such an elevation as to permit its safe removal.
A. Where such excess excavation is carried out without approval, necessary extra
backfilling shall be at no expense to the Employer.
A. Stockpile borrow soil materials and satisfactory excavated soil materials. Stockpile
soil materials without intermixing. Place, grade, and shape stockpiles to drain surface
water. Cover to prevent windblown dust.
1. Stockpile soil materials away from edge of excavations.
3.14 BACKFILL
A. Place and compact backfill in excavations promptly, but not before completing the
following:
1. Construction below finish grade including, where applicable, dampproofing and
waterproofing.
2. Surveying locations of underground utilities for record documents.
3. Inspecting and testing underground utilities.
4. Removing concrete formwork.
5. Removing trash and debris.
6. Removing temporary shoring and bracing, and sheeting.
7. Installing permanent or temporary horizontal bracing on horizontally supported
walls.
A. Place and compact bedding course on trench bottoms and where indicated. Shape
bedding course to provide continuous support for bells, joints, and barrels of pipes and
for joints, fittings, and bodies of conduits.
B. Backfill trenches excavated under footings and within 450 mm of bottom of footings
with satisfactory soil compacted in layers not exceeding 200mm; fill with concrete to
elevation of bottom of footings.
C. The trench for pipes to a depth of 30cm above the top of the pipe shall be backfilled
by hand or by approved mechanical methods. Use special care in placing this portion
of the backfill so as to avoid injuring or moving the pipe. The backfill material shall be
placed in 15cm layers and compacted by tamping.
F. Fill voids with approved backfill materials while shoring and bracing, and as sheeting
is removed.
G. Place and compact final backfill of satisfactory soil material to final subgrade elevation.
H. Install warning tape directly above utilities, 300 mm below finished grade, except 150
mm below subgrade under pavements and slabs or as directed.
B. Plow, scarify, bench, or break up sloped surfaces steeper than 1 vertical to 4 horizontal
so fill material will bond with existing material.
A. Uniformly moisten or aerate subgrade and each subsequent fill or backfill layer before
compaction to within 2 percent of optimum moisture content.
1. Do not place backfill or fill material on surfaces that are muddy.
2. Remove and replace, or scarify and air-dry, otherwise satisfactory soil material
that exceeds optimum moisture content by 2 percent and is too wet to compact
to specified dry unit weight.
A. Place backfill and fill materials in layers not more than 200 mm in loose depth for
material compacted by heavy compaction equipment, and not more than 100 mm in
loose depth for material compacted by hand-operated tampers.
B. Place backfill and fill materials evenly on all sides of structures to required elevations,
and uniformly along the full length of each structure.
C. Compact soil to not less than the following percentages of maximum dry unit weight
according to ASTM D 1557:
1. Under structures, building slabs, steps, and pavements, scarify and re-compact
top 300 mm of existing subgrade and each layer of backfill or fill material at 95
percent.
3.19 GRADING
A. General: Uniformly grade areas to a smooth surface, free from irregular surface
changes. Comply with compaction requirements and grade to cross sections, lines,
and elevations indicated.
1. Provide a smooth transition between adjacent existing grades and new grades.
2. Cut out soft spots, fill low spots, and trim high spots to comply with required
surface tolerances.
C. Site Grading: Slope grades to direct water away from buildings and to prevent
ponding. Finish subgrades to required elevations within the following tolerances:
1. Planting areas or Unpaved Areas: Plus or minus 25 mm.
2. Pavements: Plus or minus 13 mm.
C. Place base course material over subbase course under hot-mix asphalt pavement.
1. Shape subbase and base course to required crown elevations and cross-slope
grades.
2. Place subbase and base 150 m or less in compacted thickness in a single layer.
D. Pavement Shoulders: Place shoulders along edges of subbase and base course to
prevent lateral movement. Construct shoulders, at least 300 mm wide, of satisfactory
soil materials and compact simultaneously with each subbase and base layer to not
less than 95 percent of maximum dry unit weight according to ASTM D 1557.
B. Proceed with subsequent earthwork only after test results for previously completed
work comply with requirements.
3.23 PROTECTION
A. Protecting Graded Areas: Protect newly graded areas from traffic and erosion. Keep
free of trash and debris.
C. Where settling occurs before Defects Liability Period elapses, remove finished
surfacing, backfill with additional soil material, compact, and reconstruct surfacing.
1. Restore appearance, quality, and condition of finished surfacing to match
adjacent work, and eliminate evidence of restoration to the greatest extent
possible.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 GENERAL
A. All sub-base and base courses, whether aggregate, bitumen, or sand asphalt, shall be
furnished and installed as indicated on the Drawings and in accordance with the
requirements of the Section III, Sub-base and Base Courses, of the Municipality of Abu
Dhabi City (ADM) Standard Specification.
B. The sub-base and base course thicknesses are indicated on the drawings.
PART 2 - PRODUCTS
2.01 MATERIALS
A. Aggregate sub-base and base courses shall consist of natural and/or crushed, screened
fine and coarse aggregates blended to the specified gradation. The aggregates for sub-
base and base courses shall be blended in a central mixing plant, as specified in the
Standard Specifications. Alternatively, the desired gradation for the aggregate sub-base
and base courses may be achieved by processing through gradation screens at the
crusher or quarry.
B. Use and/or mixing of the site excavated materials or borrow materials with the supplied
aggregate materials for sub-base and base courses is not acceptable for the
construction of the aggregate sub-base or base course layers.
A. The final gradation of aggregate sub-base and base courses delivered to site, as
proposed by the Contractor and approved by the Engineer shall be subject to the
following tolerances during construction:
1. Passing 25mm sieve and larger ± 6%
2. Passing sieves 4.75mm (No. 4) to 19mm (No. ¾”) ± 5%
3. Passing sieves 425μm (No. 40) to 2mm (No. 10) ± 4%
4. Passing 75μm (No. 200) ± 2%
A. General
B. Materials
1. Materials shall conform to the requirements for the class of "Recycled Crushed
Aggregate Base Course" specified on the plans or directed by the Engineer. All
RCA sub-base material shall be free from dirt, organic matter, shale or other
deleterious matter and shall be of such quality that it will bind readily to form a
firm stable sub-base.
2. Components: Crushed concrete aggregates shall consist of clean, hard, durable,
angular fragments of rock, concrete and sand fragments of uniform quality
complying with the general requirements specified in Clause 2.2,
3. The use of crusher fines passing the 4.75 sieve which are not produced from
crushing concrete, shall be subject to approval in writing by the Superintendent to
the proposed source and nature of these materials and the proposed amounts to
be added.
4. Physical Requirements: All base course RCA shall conform to the physical
requirements described below, for each Class of Aggregate.
5. Foreign material in the fraction retained on the 4.75 sieve shall not exceed the
percentages by mass specified:
C. Grading Requirements
1. The material for "Granular RCA Sub-base" shall conform to the requirements
specified for the class of sub-base noted on the plans. The requirements for each
class of sub-base are as follows:
2. Class A Sub-base: Class A Sub-base shall consist of well-graded RCA with sand
and silt, conforming to the following requirements:
ASTM (D1241-00)
Sieve Percent Passing
50mm 100
9.5mm 30 - 65
ASTM (D1241-00)
Percent Passing
Sieve Size
50.0mm 100
25.0mm 75 - 95
9.5mm 40 - 75
4.75mm 30 - 65
2.00mm 20 - 45
0.425mm 15 - 30
0.075mm 5 - 15
ASTM (D1241-00)
Percent Passing
Sieve Size
25.0mm 100
9.5mm 50 - 85
4.75mm 35 - 65
2.00mm 25 - 50
0.425mm 15 - 30
0.075mm 5 - 15
D. Acceptance
1. When the stationary plant method is used, the aggregate will be accepted
immediately following mixing, based on periodic samples taken from the pug mill
output. When a road mix method is used, the aggregate will be accepted after
necessary blending and before laying, based on samples taken from the
combined windrow for each layer. Acceptance of the material by the Engineer
does not constitute acceptance of the sub-base, only that the material is
approved for use in the sub-base.
E. Equipment
1. Equipment shall be according to the type and number outlined in the Contractor's
detailed Programme of Work, as approved by the Engineer.
F. Construction Requirements
1. Groundwater Levels and Protection: The Contractor must establish the high
water table levels (HWT) along the length of the road, relative to the accepted
National benchmark (New Abu Dhabi Datum (NADD)). Should the base of the
proposed road be within 1 metre of the HWT, an impermeable barrier will be
required to be installed to prevent groundwater coming in contact with the RCA
sub-base.
2. Preparation of Subgrade: The Contractor shall, as part of the Work of sub-base,
prepare the sub grade. The formation of the subgrade will vary by either placing
the "Granular RCA Sub-base" on the roadway surface as previously constructed
or by excavating sufficient material from the roadway and placing the "Granular
RCA Sub-base" on the subgrade obtained thereby. In either case, the subgrade,
shall as hereinafter described, be brought to the lines, grades and typical section
shown on the plans for the bottom of the "Granular RCA Sub-base". All soft and
yielding material or other portions of the subgrade, which will not compact
readily, when rolled or tamped, shall be removed, and all loose rock or boulders
found in the excavation shall be removed or broken off to a depth of not less than
fifteen (15) centimetres below the surface of the subgrade. All holes or
depressions made by the removal of material, as described above, shall be filled
with approved material, and the whole subgrade brought to line and grade and
compacted to density designated on the plans or directed by the Engineer.
3. Spreading: Sub-base aggregates shall be spread on subgrade which has been
approved by the Engineer. Sub-base which has been placed on a subgrade not
approved by the Engineer shall be removed at the Contractor's expense.
4. Sub-base aggregate shall be spread on the approved subgrade in layers not
exceeding fifteen (15) centimetres in compacted depth. Spreading shall be done
by means of approved mechanical box spreaders, distributing the material to the
required width and loose thickness. Where the required sub-base thickness is
greater than fifteen (15) centimetres, the material shall be placed in layers of
equal thickness, in no case shall a layer be less than seven and one half (7.5)
A. General
1. This Specification has been prepared to meet the requirements of the Order
issued by the Executive Council of the Emirate of Abu Dhabi, dated 26th July,
2010, under number BT9G25/2010 requiring the mandatory use (subject to
availability) of a minimum of 40% aggregate (by volume) of recycled construction
and demolition waste in roads projects, as well as any other infrastructure
projects throughout the Emirate of Abu Dhabi.
2. The works described below shall consist of furnishing and placing one (1) or
more layers of recycled crushed aggregate (RCA), including additives if required,
on a prepared surface in accordance with the Specifications and in conformity
with the lines, grades, thicknesses and typical cross-sections shown on the plans
or established by the Engineer.
B. Materials
1. Materials shall conform to the requirements for the class of "Recycled Crushed
Aggregate Base Course" specified on the plans or directed by the Engineer. All
RCA for base course shall consist of crushed rock, crushed concrete stone
fragments including sand.
2. Components: Crushed concrete aggregates shall consist of clean, hard, durable,
angular fragments of rock, concrete and sand fragments of uniform quality
complying with the general requirements specified in Clause 2.2.
3. The use of crusher fines passing the 4.75 sieve which are not produced from
crushing concrete, shall be subject to approval in writing by the Superintendent to
the proposed source and nature of these materials and the proposed amounts to
be added.
4. Physical Requirements: All base course RCA shall conform to the physical
requirements described below, for each Class of Aggregate.
5. Foreign material in the fraction retained on the 4.75 sieve shall not exceed the
percentages by mass specified:
Foreign Material Type %
High density materials such as metal, 3
glass, brick, and asphalt
Low density materials such as plastic, 1
KEO/21-7387-0004 32 1116.13 / 6 Subbase and Base Courses
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
rubber, plaster, clay lumps and other friable
material
Wood and other vegetable or 0.2
decomposable matter
6. Grading Requirements: Coarse materials for Aggregate Base Course shall
conform to the following grading requirements:
ASTM (D2940)
Percent Passing
Sieve Size
50mm
100
37.5mm
95 - 100
19mm
70 – 92
9.5mm
50 – 70
4.75mm
35 – 55
0.60mm
12 – 25
0.075mm
0-8
C. Acceptance
1. When the stationary plant method is used, the aggregate will be accepted
immediately following mixing, based on periodic samples taken from the pug mill
output. When a road mix method is used, the aggregate will be accepted after
necessary blending and before laying, based on samples taken from the
combined windrow for each layer. When the aggregate is a total aggregate, it
may be accepted at the crusher. Acceptance of the material by the Engineer
does not constitute acceptance of the base course, only that the material is
approved for use in the base course.
D. Equipment
1. Equipment shall be according to the type and number outlined in the Contractor's
detailed Programme of Work as approved by the Engineer.
E. Construction Requirements
1. Groundwater Levels and Protection: The Contractor must establish the high
water table levels (HWT) along the length of the road, relative to the accepted
National benchmark (New Abu Dhabi Datum (NADD)). Should the base of the
F. Method of Construction
1. Handling of RCA: Handling of RCA, including the loading of trucks and
stockpiling, shall be effected in such a manner as to minimise segregation.
2. Combining Aggregates and Water: Aggregates for base course shall be
combined into a uniform mixture and water added only in a central mixing plant
before final placement of the material; Mixing and watering by windrows will not
be permitted. When binder is to be added, it shall be combined with the
aggregate base by thoroughly mixing binder and aggregate base in the central
mixing plant.
3. The moisture added to the aggregates shall be that required, as designated by
the Engineer, to obtain the specified density thereby preparing an aggregate
completely ready for compaction after spreading on the roadbed. In no case will
be wetting of aggregates in stockpiles or trucks be permitted.
4. Spreading and Combining Aggregates: Unless otherwise specified, aggregate for
base course shall be delivered to the roadbed as an uniform mixture and shall be
placed on the existing roadway, prepared sub-base or prepared subgrade, as the
case may be, in an uniform layer or layers not exceeding fifteen (15) centimetres
in compacted depth, including any binder that is to be blended on the road.
Spreading shall be done by means of approved self-propelled stone box
spreaders, distributing the material to the required width and loose thickness.
When the required base thickness is greater than fifteen (15) centimetres, the
materials shall be spread in layers of equal thickness.
5. The material shall be so handled, as to avoid segregation. If an aggregate
spreader causes segregation in the material, or leaves ridges or other
objectionable marks on the surface which cannot be eliminated easily or
prevented by adjustment of the spreader operation, the use of such spreader
shall be removed and replaced with well-graded material. No "skin" patching
shall be permitted.
6. No hauling or placement of material will be permitted when, in the judgment of
the Engineer, the weather or road conditions are such as hauling operations will
cause cutting or rutting of the road surface or cause contamination of the base
course material.
7. Compaction: If directed by the Engineer, prior to starting the aggregate base
operation, the Contractor shall construct trial lengths in accordance with
subparagraph 4.4 "Compaction Trials" in Section 3.2 "Granular Sub-base".
8. RCA shall be laid and compacted in a manner which will not result in segregation
of the material and at a moisture content which allows the compaction stated.
9. Immediately after placing, the base course material shall be compacted. The
material shall be compacted to an average density of 100% of M.D.D. as
determined according to AASHTO T 180 Method D with no single value below
ninety-eight (98%) percent. The Field determination of density shall be made in
A. The concrete work shall be furnished and constructed in accordance with the
requirements of Section V, Concrete Works, of the ADM Standard Specifications and as
specified herein.
B. The concrete work shall include all formwork for ornamentation, all inserts embedded in
the concrete, and all grout as indicated on the Drawings and as directed by the
Engineer.
PART 3 - EXECUTION
3.01 INSTALLATION
A. The subgrade and/or aggregate base course for pedestrian and vehicular concrete
paving blocks shall be prepared as per the Standard specifications and contract
drawings, as applicable.
B. After preparation of the subgrade or aggregate base course for the concrete paving
blocks, as applicable, place 5 cm of bedding sand complying with either the
requirements of BS 7533:Part 3:1997, Category III or as per the grading limits specified
in the table below.
C. The bedding sand shall be uniformly mixed over the compacted subgrade or aggregate
base course, as applicable for pedestrian or vehicular areas, and screeded uniformly to
grade approximately 10 to 15 mm higher than required. Place the concrete paving
blocks in the approved pattern as close together as possible such that the spaces of the
joints are between 3 mm and 5 mm. It is important that the spaces be consistent so that
the pattern will remain constant.
D. The joints in the paving blocks shall be filled with sand complying BS 7533: Part 3: 1997
by sweeping in the jointing sand. The grading limits for the jointing sand specified in BS
7533: Part 3 are indicated in the table below.
F. The concrete paving blocks shall then be tamped down with a mechanical plate vibrator
until pavers are uniformly level, true to grade and free of any movement. The
mechanical plate vibrator shall be equipped with a rubber pad on the tamping face to
minimize damage to the finish surface and appearance of the paving blocks.
END OF SECTION
UNIT PAVING
PART 1 - GENERAL
1.02 SUMMARY
A. Section Includes:
1. Precast concrete pavers
2. Porcelain Tiles
B. Related Sections:
1. Section 07 9200 "Joint Sealants" for Joint sealants for expansion joints of
paving.
2. Section 31 2000 "Earthworks" for Granular base under unit pavers.
3. Section 03 3000 "Cast in Place Concrete" for concrete base under unit pavers
A. Source Limitations: Obtain each type of unit paver, joint material, and setting material
from single source with resources to provide materials and products of consistent
KEO/21-7387-0004 32 1400/ / 1 Unit Paving
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
quality in appearance and physical properties.
B. Mockups: Build mockups to verify selections made under Sample submittals and to
demonstrate aesthetic effects and set quality standards for materials and execution.
1. Approved mockups may become part of the completed Work if undisturbed at
time of Substantial Completion.
A. Store pavers on elevated platforms in a dry location. If units are not stored in an
enclosed location, cover tops and sides of stacks with waterproof sheeting, securely
tied.
B. Store cementitious materials on elevated platforms, under cover, and in a dry location.
Do not use cementitious materials that have become damp.
C. Store aggregates where grading and other required characteristics can be maintained,
and contamination avoided.
PART 2 - PRODUCTS
A. PV-02 – Villa Car Parking Paving – Precast Concrete Pavers: Solid interlocking paving
units complying with ASTM C 936[ and resistant to freezing and thawing when tested
according to ASTM C 67, made from normal-weight aggregates.
1. Manufacturers: Subject to compliance with requirements, provide products by
one of the following:
a. Consent LLC - UAE.
b. Transgulf LLC – UAE.
c. Or equal approved.
2. Thickness: 80mm
3. Face Size and Shape: 200x100mm rectangle.
4. Finish: Shot-blasted
5. Color: Beige
2.03 ACCESSORIES
C. Application: Apply to a clean dry, cured surface free from debris, dust, oil, grease
stains and the likes, in accordance to manufacturers direction. Apply repeat coats if
deemed necessary by the Architect. All surrounding materials and surfaces to be
properly protected from excess material.
D. Protect from traffic immediately after application until totally cured in accordance to
manufacturer's recommendations.
2.04 ACCESSORIES
A. The following fillers to be used as expansion joints between curbs at 10m intervals:
1. Compressible Foam Filler: Preformed strips complying with ASTM D 1056,
Grade 2A1.
A. Sand for Leveling Course: Sound, sharp, washed, natural sand or crushed stone
complying with gradation requirements in ASTM C 33 for fine aggregate.
B. Sand for Joints: Fine, sharp, washed, natural sand or crushed stone with 100 percent
passing 1.18-mm sieve and no more than 10 percent passing 0.075-mm sieve.
1. Provide sand of color needed to produce required joint color.
D. Herbicide: Commercial chemical for weed control, registered with the EPA. Provide
in granular, liquid, or wettable powder form.
C. Water: Potable.
C. Packaged Grout Mix: Proportion and mix grout ingredients according to grout
manufacturer's written instructions.
PART 3 - EXECUTION
A. Examine areas indicated to receive paving, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 PREPARATION
A. Preparation: Ensure that all underground utility lines are located and will not interfere
with the proposed edging installation before beginning work. Locate border line of
edging with string or other means to assure border straightness and curves as
designed.
B. Remove substances from concrete substrates that could impair mortar bond, including
curing and sealing compounds, form oil, and laitance.
C. Sweep concrete substrates to remove dirt, dust, debris, and loose particles.
A. Do not use unit pavers with chips, cracks, voids, discolorations, or other defects that
might be visible or cause staining in finished work.
B. Mix pavers from several pallets or cubes, as they are placed, to produce uniform blend
of colors and textures.
C. Cut unit pavers with Pavers shall be cut with a motor driven watercooled, cut-off wheel
masonry saw using a diamond blade to provide clean, sharp, unchipped edges. Cut
units to provide pattern indicated and to fit adjoining work neatly. Use full units without
cutting where possible. Hammer cutting is not acceptable.
1. For concrete pavers, a block splitter may be used.
F. All paver to be set out using fixed string lines off a fixed perpendicular or aligned
surface.
G. Pavers over Waterproofing: Exercise care in placing pavers and setting materials over
KEO/21-7387-0004 32 1400/ / 6 Unit Paving
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
waterproofing so protection materials are not displaced and waterproofing is not
punctured or otherwise damaged. Carefully replace protection materials that become
displaced and arrange for repair of damaged waterproofing before covering with
paving.
1. Provide joint filler at waterproofing that is turned up on vertical surfaces unless
otherwise indicated; where unfilled joints are indicated, provide temporary filler
or protection until paver installation is complete.
H. Tolerances: Do not exceed 0.8-mm unit-to-unit offset from flush (lippage) nor 3 mm
in 3 m from level, or indicated slope, for finished surface of paving.
I. Expansion and Control Joints: Provide for sealant-filled joints at locations and of
widths indicated on structural engineers drawings. Provide compressible foam filler
as backing for sealant-filled joints unless otherwise indicated; where unfilled joints are
indicated, provide temporary filler until paver installation is complete]. Install joint filler
before setting pavers. Sealant materials and installation are specified in Section 07
9200 "Joint Sealants."
J. Expansion and Control Joints: Provide cork joint filler at locations and of widths
indicated. Install joint filler before setting pavers. Make top of joint filler flush with top
of pavers.
K. Provide edge restraints as indicated. Install edge restraints before placing unit pavers.
1. Where pavers set in mortar bed are indicated as edge restraints for pavers set
in aggregate setting bed, install pavers set in mortar and allow mortar to cure
before placing aggregate setting bed and remainder of pavers. Cut off mortar
bed at a steep angle so it will not interfere with aggregate setting bed.
2. Where pavers embedded in concrete are indicated as edge restraints for pavers
set in aggregate setting bed, install pavers embedded in concrete and allow
concrete to cure before placing aggregate setting bed and remainder of pavers.
Hold top of concrete below aggregate setting bed.
L. Provide steps made of pavers as indicated. Install paver steps before installing
adjacent pavers.
1. Where pavers set in mortar bed are indicated for steps constructed adjacent to
pavers set in aggregate setting bed, install steps and allow mortar to cure before
placing aggregate setting bed and remainder of pavers. Cut off mortar bed at
a steep angle so it will not interfere with aggregate setting bed.
M. Cutting: Cut unit pavers with motor-driven masonry saw equipment to provide clean,
sharp, unchipped edges. Cut units to provide pattern indicated and to fit adjoining work
neatly. Use full units without cutting where possible. Hammer cutting is not acceptable.
Where cut pieces turn out to be less than 7.6 cm in any dimension they shall be
replaced by 15.24 cm x 25.4 cm, cut to fit.
B. Proof-roll prepared subgrade to identify soft pockets and areas of excess yielding.
Excavate soft spots, unsatisfactory soils, and areas of excessive pumping or rutting,
C. Place separation geotextile over prepared subgrade, overlapping ends and edges at
least 300 mm.
D. Place aggregate base, compact to 100 percent of ASTM D 1557 maximum laboratory
density, and screed to depth indicated.
E. Place leveling course and screed to a thickness of 25 to 38 mm, taking care that
moisture content remains constant and density is loose and uniform until pavers are
set and compacted.
F. Treat leveling course with herbicide to inhibit growth of grass and weeds.
G. Set pavers with a minimum joint width as indicated on Landscape Drawings, being
careful not to disturb leveling base. If pavers have spacer bars, place pavers hand
tight against spacer bars. Use string lines to keep straight lines. Fill gaps between
units that exceed 30mm with pieces cut to fit from full-size unit pavers.
1. When installation is performed with mechanical equipment, use only unit pavers
with spacer bars on sides of each unit.
H. Vibrate pavers into leveling course with a low-amplitude plate vibrator capable of a 16-
to 22-kN compaction force at 80 to 90 Hz. Use vibrator with neoprene mat on face of
plate or other means as needed to prevent cracking and chipping of pavers. Perform
at least three passes across paving with vibrator.
1. Compact pavers when there is sufficient surface to accommodate operation of
vibrator, leaving at least 900 mm of uncompacted pavers adjacent to temporary
edges.
2. Before ending each day's work, compact installed concrete pavers except for
900 mm width of uncompacted pavers adjacent to temporary edges (laying
faces).
3. As work progresses to perimeter of installation, compact installed pavers that
are adjacent to permanent edges unless they are within 90 mm of laying face.
4. Before ending each day's work and when rain interrupts work, cover pavers that
have not been compacted and cover leveling course on which pavers have not
been placed with non-staining plastic sheets to protect them from rain.
I. Spread dry sand and fill joints immediately after vibrating pavers into leveling course.
Vibrate pavers and add sand until joints are completely filled, then remove excess
sand. Leave a slight surplus of sand on the surface for joint filling.
J. Do not allow traffic on installed pavers until sand has been vibrated into joints.
A. Saturate concrete subbase with clean water several hours before placing setting bed.
Remove surface water about one hour before placing setting bed.
B. Apply mortar bed over bond coat; spread and screed mortar bed to uniform thickness
at subgrade elevations required for accurate setting of pavers to finished grades
indicated.
D. Place pavers before initial set of cement occurs. Immediately before placing pavers
on mortar bed, apply uniform 1.5-mm- thick bond coat to mortar bed or to back of each
paver with a flat trowel.
E. Tamp or beat pavers with a wooden block or rubber mallet to obtain full contact with
setting bed and to bring finished surfaces within indicated tolerances. Set each paver
in a single operation before initial set of mortar; do not return to areas already set or
disturb pavers for purposes of realigning finished surfaces or adjusting joints.
I. Cure grout by maintaining in a damp condition for seven days unless otherwise
recommended by grout or liquid-latex manufacturer.
A. Remove and replace unit pavers that are loose, chipped, broken, stained, or otherwise
damaged or that do not match adjoining units. Provide new units to match adjoining
units and install in same manner as original units, with same joint treatment and with
no evidence of replacement.
B. Pointing: During tooling of joints, enlarge voids or holes and completely fill with grout.
Point joints at sealant joints to provide a neat, uniform appearance, properly prepared
for sealant application.
C. Cleaning: Remove excess grout from exposed paver surfaces; wash and scrub clean.
END OF SECTION
AGGREGATE SURFACING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The works specified in this section cover all works necessary to prepare, construct and
finish the exterior hard landscape works of the development in coordination with soft
landscape, landscape lighting and other site works and contractors. Works include but
are not limited to the following as per drawings:
1. Washed river pebbles stones
2. Crushed stones
B. Related Sections: Related work to be coordinated and used in conjunction with this
specification includes:
1. Section 32 1116.13 - Subbase and Base Courses
2. Section 32 9300 - Plants
1.02 SUBMITTALS
1.03 COMPLIANCE
A. All works shall be carried out in accordance with the requirements of the relevant safety
codes and Local Authority requirements for this work.
A. The Contractor shall supply at time of tender certification of suitability of all materials
and installation techniques for use in the UAE including climatic conditions, expected
maintenance regimes etc.
A. Where materials used in this section have been specified elsewhere in this document,
the relevant clauses shall apply to this section. Materials and workmanship that have not
been individually specified shall be of international first class quality and the minimum
standard acceptance shall be the relevant British Standard where applicable.
KEO/21-7387-0004 32 1500 / 1 Aggregate Surfacing
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
1.06 QUALITY ASSURANCE
A. Source Limitations: Obtain each type of aggregate from a single source with resources
to provide materials and products of consistent quality in appearance and physical
properties.
C. Mockups: Build mockups to verify selections made under sample submittals and to
demonstrate aesthetic effects and set quality standards for materials and execution.
Mockup samples to be 3m x 3m for each aggregate type including interfaces as required
by the Engineer.
1. Location of mockups to be agreed with Engineer.
2. Demonstrate the proposed range of aesthetic effects and workmanship.
Obtain written approval of mockup from the Engineer before start of installation.
3. Maintain mockups during construction in an undisturbed condition as a
standard for judging the completed Work.
1.07 WARRANTY
A. Submit a written warranty signed by Contractor agreeing to repair or replace Work under
this Section that fails in materials, workmanship, finish and color at no additional cost to
the Employer.
PART 2 - PRODUCT
A. Filter fabric shall be laid under all aggregate surfaces to provide a free draining
separation layer between the associated subbase and aggregate surfacing lapped
300mm and secured at the joints.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine surfaces indicated to receive paving, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of
Work under this Section. Do not proceed with installation until unsatisfactory conditions
have been corrected.
3.02 PREPARATION
A. Proof-roll prepared subgrade surface to check for unstable areas and areas requiring
additional compaction. Do not proceed with installation until deficient subgrades have
been corrected.
A. General:
1. The Contractor shall make full allowance for the installation of pebbles and
crushed stones where and as described further in the drawings and documents.
B. Installation
1. Aggregate surfacing shall be laid over filter fabric layer. Where placed in areas
without planting, aggregate surfacing shall be installed over a compacted – 95%
subbase. The Contractor shall supply a sample area for approval by the
Engineer.
END OF SECTION
SOIL PREPARATION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Section includes planting soils and layered soil assemblies specified by composition of
the mixes.
B. Related Requirements:
1. Section 31 1000 "Site Clearing" for topsoil stripping and stockpiling.
2. Section 32 9300 "Plants" for placing planting soil for plantings.
1.02 DEFINITIONS
B. Backfill: The earth used to replace or the act of replacing earth in an excavation. This
can be amended or unamended soil as indicated.
D. Compost: The product resulting from the controlled biological decomposition of organic
material that has been sanitized through the generation of heat and stabilized to the
point that it is beneficial to plant growth.
F. Layered Soil Assembly: A designed series of planting soils, layered on each other, that
together produce an environment for plant growth.
G. Manufactured Soil: Soil produced by blending soils, sand, stabilized organic soil
amendments, and other materials to produce planting soil.
H. NAPT: North American Proficiency Testing Program. An SSSA program to assist soil-,
plant- and water-testing laboratories through interlaboratory sample exchanges and
statistical evaluation of analytical data.
I. Organic Matter: The total of organic materials in soil exclusive of undecayed plant and
animal tissues, their partial decomposition products, and the soil biomass; also called
"humus" or "soil organic matter."
J. Planting Soil: Existing, on-site soil; imported soil; or manufactured soil that has been
modified as specified with soil amendments and perhaps fertilizers to produce a soil
mixture best for plant growth.
N. Subsoil: Soil beneath the level of subgrade; soil beneath the topsoil layers of a naturally
occurring soil profile, typified by less than 1 percent organic matter and few soil
organisms.
O. Surface Soil: Soil that is present at the top layer of the existing soil profile. In
undisturbed areas, surface soil is typically called "topsoil"; but in disturbed areas such
as urban environments, the surface soil can be subsoil.
B. Samples: For each bulk-supplied material, 4Ltr volume of each in sealed containers
labeled with content, source, and date obtained. Each Sample shall be typical of the lot
of material to be furnished; provide an accurate representation of composition, color,
and texture.
B. Field Inspections, the following Hold & Witness points apply to the project for the
preparation and installation of soils. No further works to be carried until the following has
been inspected and approved in writing by the Architect or approved representative:
1. Submission of works construction program.
2. Monthly progress reports.
3. Approval of all samples & materials.
4. Receipt of soil sampling for existing conditions and proposed planting sand /
sweet soil.
5. Excavated landscape areas.
6. Approval of final soil mix before leaving mixing staging area.
7. Excavated pits and percolation tests prior to planting.
B. Sample Collection and Labeling: Have samples taken and labeled by Contractor in
presence of Architect under the direction of the testing agency.
1. Number and Location of Samples:
a. Minimum of 1 per 5 HA representative soil samples from varied agreed
locations directed by Architect for existing soils.
b. Minimum of 1 sample per 1000m3 delivered load of sweet soil sand
delivered to site for mixing.
2. Procedures and Depth of Samples: According to USDA-NRCS's "Field Book for
Describing and Sampling Soils."
3. Division of Samples: Split each sample into two, equal parts. Send half to the
testing agency and half to Owner for its records.
4. Labeling: Label each sample with the date, location keyed to a site plan or other
location system, visible soil condition, and sampling depth.
B. Physical Testing:
1. Soil Texture: Soil-particle, size-distribution analysis by one of the following
methods according to SSSA's "Methods of Soil Analysis - Part 1-Physical and
Mineralogical Methods":
a. Sieving Method: Report sand-gradation percentages for very coarse,
coarse, medium, fine, and very fine sand; and fragment-gradation (gravel)
percentages for fine, medium, and coarse fragments; according to USDA
sand and fragment sizes.
b. Hydrometer Method: Report percentages of sand, silt, and clay.
2. Total Porosity: Calculate using particle density and bulk density according to
SSSA's "Methods of Soil Analysis - Part 1-Physical and Mineralogical Methods."
3. Water Retention: According to SSSA's "Methods of Soil Analysis - Part 1-
Physical and Mineralogical Methods."
4. Saturated Hydraulic Conductivity: According to SSSA's "Methods of Soil
Analysis - Part 1-Physical and Mineralogical Methods"; at 85% compaction
according to ASTM D 698 (Standard Proctor).
C. Chemical Testing:
1. CEC: Analysis by sodium saturation at pH 7 according to SSSA's "Methods of
Soil Analysis - Part 3- Chemical Methods."
2. Clay Mineralogy: Analysis and estimated percentage of expandable clay
minerals using CEC by ammonium saturation at pH 7 according to SSSA's
"Methods of Soil Analysis - Part 1- Physical and Mineralogical Methods."
3. Metals Hazardous to Human Health: Test for presence and quantities of RCRA
metals including aluminum, arsenic, barium, copper, cadmium, chromium, cobalt,
lead, lithium, and vanadium. If RCRA metals are present, include
recommendations for corrective action.
4. Phytotoxicity: Test for plant-available concentrations of phytotoxic minerals
including aluminum, arsenic, barium, cadmium, chlorides, chromium, cobalt,
copper, lead, lithium, mercury, nickel, selenium, silver, sodium, strontium, tin,
titanium, vanadium, and zinc.
F. Recommendations for sweet sand soils: Based on the test results, state
recommendations for soil treatments and soil amendments to be incorporated to
produce satisfactory planting soil suitable for healthy, viable plants indicated. Include, at
a minimum, recommendations for nitrogen, phosphorous, and potassium fertilization,
and for micronutrients.
G. Recommendations for existing site soils: Based on the test results, state
recommendations for soil treatments to remove / sterilize and or cap contaminates.
B. Bulk Materials:
1. Do not dump or store bulk materials near structures, utilities, walkways and
pavements, or on existing turf areas or plants.
2. Provide erosion-control measures to prevent erosion or displacement of bulk
materials, discharge of soil-bearing water runoff, and airborne dust reaching
adjacent properties, water conveyance systems, or walkways.
3. Do not move or handle materials when they are wet.
4. Accompany each delivery of bulk fertilizers and soil amendments with
appropriate certificates.
PART 2 - PRODUCTS
A. General: Soil amendments, fertilizers, and rates of application specified in this article
are guidelines that may need revision based on testing laboratory's recommendations
after preconstruction soil analyses are performed.
D. Sand: Clean, washed, natural or manufactured, free of toxic materials, and according to
ASTM C 33/C 33M. Sand shall be sweet sand or marine washed sand free of calcium
carbonate, subsoil, refuse, roots, noxious weeds, phytotoxic materials, rocks, sticks,
brush, litter, construction debris or any other deleterious materials. The soil shall be
approved by the Engineer before its use. It shall be free draining, non-toxic and capable
of sustaining healthy plant growth. It should have good water holding capacity and
minimal runoff or erosion characteristics.
1. The sand will have the following composition:
Element Value
pH value: not less than 6.5 or not more
than 8
Electrical conductivity: less than 2500 micromhos /cm
(2.5 dS / m) saturated extract at
25ºC
Free carbonates: less than 0.5% air dried
Chlorides: less than 200 ppm in saturated
E. Soil Amendment: The soil additive shall be fully natural. No content of organic or
synthetic polymers, co-polymers or pozzolans shall be allowed and should conform to
the moisture retaining soil additive properties table.
1. The soil additive must not have any swelling properties.
2. The moisture retaining soil additive shall have a proven, successful history in the
GCC for at least 5 years.
3. At least 95 % of the additive should be inorganic (mineral),
4. Minimum 380 % WHC (Water Holding Capacity) is requested
5. The soil additive shall effectively reduce the consumption of irrigation water by
50% minimum for a period of at least 10years.
6. Minimum 30 Meq/100gr CEC (cationic exchange capacity) is requested in order
to increase the storage capacity of the soil for the important nutrition elements.
7. High content on nutrition elements (N,P,K,Ca,Mg) and optimal concentration on
micro and trace elements (Fe, Mn, Mo, B, Zn,Cu).
a. Moisture retaining soil additive indicative composition table:
Material Value
Rhyolitic tuff 80%
Natural phyllo silicates 18%
Natural cellulose compounds 2%
Property Value
WHC (Water Holding Capacity) 380% minimum
CEC (Catonic Exchange Capacity) 30 Meq/100gr minimum
N 1580 mg/kg
P P 693 mg/kg
K 7200 mg/kg
Ca & Mg 160 meq/kg
Location Application
Palm Pits 30kg per pit
Tree Pits 20kg per pit
Large Shrub Pits 3kg per pit
B. Shredded Coconut Fiber: Coconut fiber shall be finely shredded coconut fibre pith free
from chemical additives, sterilents and shall have more than 98% organic matter.
1. Physical Characteristics:
2. Chemical Characteristics:
Element Value
Organic matter >85%
PH 5.0 - 6.5
Salinity (ECe x 1000) 0.5 - 2.0
Total Nitrogen 0.7 - 2.0
Available Phosphorous 100 - 500 ppm
CEC (meq/100 gms) 80 - 120 ppm
Boron (by hot water extraction) <5 ppm
SAR less than 2.0 <2.0
C. Soil Inoculant - Myccoriza: For individual planting pits consiting of select edendo and
ectomycorrhizae fungi to promote the rapid development of root growth
2.04 FERTILIZERS
D. Organic Fertiliser: 100% Natural and heat treated. The content of Organic matter and
plant nutrient elements of this fertiliser should not be less than 50%. Primary and
secondary elements as percentages and trace elementsas ppm should be indicated on
the packing.
2.05 ANTI-DESICCANT
A. Emulsion form for spray application to provide a protective film over plant surface and
permeable enough to permit transpiration. Application should be made prior to
transportation of palm, tree and plant material to project site.
1. Product: To be delivered in containers of the manufacturer, mixed according to
the manufacturer's directions, and shall be one of the following:
a. Wilt-Pruf products, USA, www.wiltpruf.com
b. Plant Products, USA, www.plantprod.com
c. Or approved equal.
PART 3 - EXECUTION
3.01 GENERAL
B. Verify that no foreign or deleterious material or liquid such as paint, paint washout,
concrete slurry, concrete layers or chunks, cement, plaster, oils, gasoline, diesel fuel,
C. Proceed with placement only after unsatisfactory conditions have been corrected.
A. General: Apply manufactured soil on-site in its final, blended condition. Do not apply
materials or till if existing soil or subgrade is muddy or excessively wet.
B. Subgrade Preparation: Till subgrade to a minimum depth of 450 mm. Remove stones
larger than 75 mm in any dimension and sticks, roots, rubbish, and other extraneous
matter and legally dispose of them off Owner's property.
1. Apply approximately half the thickness of planting soil over prepared, loosened
subgrade. Mix thoroughly into top 50 mm of subgrade (unless soil testing for
existing site soil recommends for existing soils to be capped). Spread remainder
of planting soil.
C. Application: Spread planting soil to total depth as indicated on the planting detail
drawings, but not less than required to meet finish grades after natural settlement. Do
not spread if soil or subgrade is frozen, muddy, or excessively wet.
1. Lifts: Apply planting soil in lifts not exceeding 300 mm in loose depth for material
compacted by compaction equipment, and not more than 150 mm in loose depth
for material compacted by hand-operated tampers.
E. Finish Grading: Bring soil to grades as indicated on drawings and to the final approval of
the Architect, using specificied soil mix.
1. Finish grading shall insure proper drainage of the site as determined by the
Architect.
2. Grade planting soil to a smooth, uniform surface plane with loose, uniformly fine
texture. Roll and rake, remove ridges, and fill depressions to meet finish grades
3. All areas shall be graded so that the final grades will be 25mm below adjacent
paved areas, sidewalks, valve boxes, headers, tree well grates, planter rims,
clean-outs, drains, manholes, etc., or as indicated on plans for turf, and 40mm for
shrubs and groundcovers.
4. Surface drainage shall be away from all building foundations.
5. Eliminate all erosion scars prior to commencing maintenance period.
6. Compact all soil to final grades: Minimum 65%, maximum 75%.
A. Finish Grading: Grade surface to a smooth, uniform surface plane with loose, uniformly
fine texture. Roll and rake, remove ridges, and fill depressions to meet finish grades.
A. Soil will be considered defective if it does not pass tests and inspections.
C. Label each sample and test report with the date, location keyed to a site plan or other
location system, visible conditions when and where sample was taken, and sampling
depth.
3.05 PROTECTION
3.06 CLEANING
B. Remove surplus soil and waste material including excess subsoil, unsuitable materials,
trash, and debris and legally dispose of them off Owner's property unless otherwise
indicated.
1. Dispose of excess subsoil and unsuitable materials on-site where directed by
Owner.
END OF SECTION
PLANTS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Furnish all labor, materials, plants, equipment and appliances and perform all necessary
operations to execute the work of this section.
C. Related Requirements:
1. Section 32 1123 - Aggregate Base Course
2. Section 32 9113 - Soil Preparation
3. Section 32 9400 - Planting Accessories
4. Section 32 9700 - Planting Maintenance
1.02 DEFINITIONS
A. Backfill: The earth used to replace or the act of replacing earth in an excavation.
B. Balled and Burlapped Stock: Plants dug with firm, natural balls of earth in which they
were grown, with a ball size not less than diameter and depth recommended by ANSI
Z60.1 for type and size of plant required; wrapped with burlap, tied, rigidly supported,
and drum laced with twine with the root flare visible at the surface of the ball as
recommended by ANSI Z60.1.
C. Balled and Potted Stock: Plants dug with firm, natural balls of earth in which they are
grown and placed, unbroken, in a container. Ball size is not less than diameter and
depth recommended by ANSI Z60.1 for type and size of plant required.
E. Fabric Bag-Grown Stock: Healthy, vigorous, well-rooted plants established and grown
in-ground in a porous fabric bag with well-established root system reaching sides of
H. Pests: Living organisms that occur where they are not desired or that cause damage to
plants, animals, or people. Pests include insects, mites, grubs, mollusks (snails and
slugs), rodents, unwanted plants (weeds), fungi, bacteria, and viruses.
J. Planting Soil: Existing, on-site soil; imported soil; or manufactured soil that has been
modified with soil amendments and perhaps fertilizers to produce a soil mixture best for
plant growth. See Section 32 9113 "Soil Preparation" for planting soils.
K. Plant; Plants; Plant Material: These terms refer to vegetation in general, including
palms, trees, shrubs, vines, ground covers, ornamental grasses, bulbs, corms, tubers,
or herbaceous vegetation.
L. Root Flare: Also called "trunk flare." The area at the base of the plant's stem or trunk
where the stem or trunk broadens to form roots; the area of transition between the root
system and the stem or trunk.
M. Stem Girdling Roots: Roots that encircle the stems (trunks) of trees below the soil
surface.
1.03 COORDINATION
A. Coordinate final positions with all underground utility lines, chambers, openings,
structural footings and the like. All trees to be staked during installation of services to
ensure clashes are avoided.
A. Qualification Data: For landscape Installer. Include list of similar projects completed by
Installer demonstrating Installer's capabilities and experience. Include project names,
addresses, and year completed, and include names and addresses of contact persons.
B. Product Certificates: For each type of manufactured product, from manufacturer, and
complying with the following:
1. Manufacturer's certified analysis of standard products.
2. Analysis of other materials by a recognized laboratory made according to
methods established by the Association of Official Analytical Chemists, where
applicable.
D. Non packaged bulk materials delivered to site: Submit a certificate, of delivery slip with
each delivery of material in bulk. Certificates shall state source, quantity, or weight, type
and analysis and date of delivery along with an analysis completed by an approved
independent testing laboratory - if requested by the Engineer.
E. Plant Material: All Plant material to be delivered to site with a nursery growers
certificate.
B. Provide quality, size, genus, species, and variety of plants indicated, complying with
applicable requirements in ANSI Z60.1.
KEO/21-7387-0004 32 9300/ 4 Plants
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
1. Specimen plant materials may be observed at source prior to delivery to site if
determined appropriate by Engineer.
2. Upon delivery of plant material to site:
a. All plant material shall be subject to observation and may be approved or
rejected the Engineer for quality, size and variety prior to installation.
Such approval shall not impair the right of observation and rejection
during the progress of work for size and condition of ball or root mass,
latent effects, diseases, pests or injuries.
b. If any defective or non-complying plants are found during observations,
they will be rejected.
c. All rejected plant material shall be removed from the site within a
minimum of 2 working days.
D. Plant Material Observation: The Engineer may observe plant material either at place of
growth or at site before planting for compliance with requirements for genus, species,
variety, cultivar, size, and quality. The Engineer may also observe trees and shrubs
further for size and condition of balls and root systems, pests, disease symptoms,
injuries, and latent defects and may reject unsatisfactory or defective material at any
time during progress of work. Remove rejected trees or shrubs immediately from
Project site.
1. Notify the Engineer of sources of planting materials seven days in advance of
delivery to site.
B. Pre-inspection by Engineer for palms and trees prior mobilizing to plant holding facility
needs to be executed during the plant procurement stage of the works. The selection
and inspection for pest free palm shall be as per local requirement. Contractor to
obtain permit to move date palm from different region.
C. Approved sample plants to be used in this contract shall be submitted for approval.
All imported plants shall be acclimatized for a minimum 12 weeks for both locally
sourced plants and imported plants before planting at the site
D. Bulk Materials:
1. Do not dump or store bulk materials near structures, utilities, walkways and
pavements, or on existing plants area.
2. Provide erosion-control measures to prevent erosion or displacement of bulk
materials; discharge of soil-bearing water runoff; and airborne dust reaching
adjacent properties, water conveyance systems, or walkways.
3. Accompany each delivery of bulk materials with appropriate certificates.
4. The Contractor shall notify the Engineer 7 calendar days in advance of delivery of
all plant materials and shall submit an itemized list of the plants in each delivery.
E. Deliver bare-root stock plants within 24 hours of digging. Immediately after digging up
bare-root stock, pack root system in wet straw, hay, or other suitable material to keep
root system moist until planting. Transport in covered, temperature-controlled vehicles,
and keep plants cool and protected from sun and wind at all times.
H. Store bulbs, corms, and tubers in a dry place at 60 to 65 deg F (until planting.
I. Apply antidesiccant to trees and shrubs using power spray to provide an adequate film
over trunks (before wrapping), branches, stems, twigs, and foliage to protect during
digging, handling, and transportation.
1. If deciduous trees or shrubs are moved in full leaf, spray with antidesiccant at
nursery before moving and again two weeks after planting.
J. Wrap trees and shrubs with burlap fabric over trunks, branches, stems, twigs, and
foliage to protect from wind and other damage during digging, handling, and
transportation.
K. Deliver all plant blocks with legible identification labels, state correct plant name and
size indicated on plant list using durable waterproof labels with water-resistant ink which
will remain legible for at least 60 days.
L. All plants to be delivered to temporary shaded nursery for hardening off and storage
until planting zones are ready for implementation.
M. Move plants from temporary nursery to final planting area after preparations for planting
have been completed, and install immediately. If planting is delayed more than six
hours after moving, set plants and trees in their appropriate aspect (sun, filtered sun, or
shade), protect from weather and mechanical damage, and keep roots moist.
1. Set balled stock on ground and cover ball with soil, peat moss, sawdust, or other
acceptable material.
2. Do not remove container-grown stock from containers before time of planting.
3. Water root systems of plants stored on-site deeply and thoroughly with a fine-
mist spray. Water as often as necessary to maintain root systems in a moist, but
not overly wet condition.
A. Field Measurements: Verify actual grade elevations, service and utility locations,
irrigation system components, and dimensions of plantings and construction contiguous
with new plantings by field measurements before proceeding with planting work.
B. Planting Restrictions: Plant during one of the following periods. Coordinate planting
periods with maintenance periods to provide required maintenance from date of
Substantial Completion.
1. Planting Season: October - April
C. Weather Limitations: Proceed with planting only when existing and forecasted weather
conditions permit planting to be performed when beneficial and optimum results may be
1.011 WARRANTY
A. Special Warranty: Installer agrees to repair or replace plantings and accessories that
fail in materials, workmanship, or growth within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Death and unsatisfactory growth, except for defects resulting from abuse,
lack of adequate maintenance, or neglect by the Employer.
b. Structural failures including plantings falling or blowing over.
c. Faulty performance of tree stabilization and edgings.
d. Deterioration of metals, metal finishes, and other materials beyond normal
weathering.
PART 2 - PRODUCTS
A. General: Furnish nursery-grown plants true to genus, species, variety, cultivar, stem
form, shearing, and other features indicated in Plant List, Plant Schedule, or Plant
Legend indicated on Drawings and complying with ANSI Z60.1; and with healthy root
systems developed by transplanting or root pruning. Provide well-shaped, fully
branched, healthy, vigorous stock, densely foliated when in leaf and free of disease,
pests, eggs, larvae, and defects such as knots, sun scald, injuries, abrasions, and
disfigurement.
1. Trees with damaged, crooked, or multiple leaders; tight vertical branches where
bark is squeezed between two branches or between branch and trunk ("included
bark"); crossing trunks; cut-off limbs more than (20 mm) in diameter; or with stem
girdling roots are unacceptable.
2. Collected Stock: Do not use plants harvested from the wild, from native stands,
from an established landscape planting, or not grown in a nursery unless
otherwise indicated.
C. All plants not in compliance with the requirements herein specified, will be considered
defective and such plants, whether in place or not, shall be marked as rejected and
immediately removed from the site of the work and replaced with new plants at the
Contractor's expense. The plants shall be of the species, variety, size, and conditions
specified herein or as shown on the drawings. Under no conditions shall there be any
substitutions of plants or sizes listed on the accompanying plans, except with the
express consent of the Engineer.
D. Labeling: Label at least one plant of each variety, size, and caliper with a securely
attached, waterproof tag bearing legible designation of common name and full scientific
name, including genus and species. Include nomenclature for hybrid, variety, or
cultivar, if applicable for the plant.
2.02 FERTILIZERS
B. Mineral Mulch: Hard, durable stone, washed free of loam, sand, clay, and other foreign
substances, of the following type, size range, and color in areas specifically indicated on
drawings:
C. Mulch Installation: Laid loose over geotextile. Size and depths: As indicated.
2.04 PESTICIDES
A. General: Pesticide registered and approved by the EPA and UAE State, acceptable to
authorities having jurisdiction, and of type recommended by manufacturer for each
specific problem and as required for Project conditions and application. Do not use
restricted pesticides unless authorized in writing by authorities having jurisdiction.
A. Unless otherwise specified on the plans, for palms or advanced trees, two tree stakes
shall be provided for all newly planted trees and shall be sawn or riven timber treated
with an approved preservative applied by the vacuum pressure impregnation method.
1. All stakes shall be 2m free of projections and pointed at one end. Stakes shall
be 50 x 50 mm (net section); the length below ground to be 0.8 metre minimum
and the length above to be 1.2m, unless otherwise approved by the Engineer.
Smaller stakes to 1.5m may be required for some plants as determined by the
Engineer.
2. Tree Ties: three (3 pieces of buckle ties (600mm long and 38mm wide shall be
looped around tree for the purpose of tying trees and shall allow appropriate
flexibility and adjustment as the tree grows.
3. The Contractor shall submit shop drawings detailing all anchoring, connections,
materials to use etc. and obtain approval from the Engineer prior to commencing
any planting work.
E. Planter Drainage Gravel: Washed, sound crushed stone or gravel complying with
ASTM D 448. to bottom of tree pits and planters to be 10mm to 20mm pea gravel and of
clean, hard, sound, durable, uniform in quality, and free of any detrimental quantity of
soft, friable, thin, elongated, or laminated pieces, disintegrated material, organic matter,
oil, alkali, or other deleterious substance.
3.01 EXAMINATION
A. Examine areas to receive plants, with Installer present, for compliance with
requirements and conditions affecting installation and performance of the Work.
1. Verify that no foreign or deleterious material or liquid such as paint, paint
washout, concrete slurry, concrete layers or chunks, cement, plaster, oils,
gasoline, diesel fuel, paint thinner, turpentine, tar, roofing compound, or acid has
been deposited in soil within a planting area.
2. Verify that plants and vehicles loaded with plants can travel to planting locations
with adequate overhead clearance.
3. The Contractor will obtain Engineer's Certification that final grades up to +/-30mm
have been established prior to commencing planting operations. Provide for
inclusion of all amendments, settling, etc. Contractor shall be responsible for
shaping all planting areas as indicated on plans or as directed by the Engineer.
4. Suspend planting operations during periods of excessive soil moisture until the
moisture content reaches acceptable levels to attain the required results.
5. Uniformly moisten excessively dry soil that is not workable or which is dusty.
C. Proceed with installation only after unsatisfactory conditions, deficiencies have been
corrected or plants replaced.
3.02 PREPARATION
A. Protect structures, utilities, sidewalks, pavements, and other facilities and existing plants
from damage caused by planting operations.
C. Lay out individual tree and shrub locations and areas for multiple plantings. Stake
locations, outline areas, adjust locations when requested, and obtain Engineer's
acceptance of layout before excavating or planting. Make minor adjustments as
required.
D. Lay out plants at locations directed by Engineer. Stake locations of individual trees and
shrubs and outline areas for multiple plantings.
A. General: Prepare planting area for soil placement and mix planting soil according to
Section 32 9113 "Soil Preparation".
C. Before planting, obtain Engineer's acceptance of finish grading; restore planting areas if
eroded or otherwise disturbed after finish grading.
B. Backfill Soil: Subsoil and topsoil removed from excavations may be used as backfill soil
unless otherwise indicated.
A. Inspection: At time of planting, verify that root flare is visible at top of root ball according
to ANSI Z60.1. If root flare is not visible, remove soil in a level manner from the root ball
to where the top-most root emerges from the trunk. After soil removal to expose the
root flare, verify that root ball still meets size requirements.
B. Roots: Remove stem girdling roots and kinked roots. Remove injured roots by cutting
cleanly; do not break.
C. Balled and Burlapped Stock: Set each plant plumb and in center of planting pit or trench
with root flare (25mm) above adjacent finish grades.
1. Backfill: mix.Designated planting soil mix - Section 32 9113 "Soil Preparation"
2. After placing some backfill around root ball to stabilize plant, carefully cut and
remove burlap, rope, and wire baskets from tops of root balls and from sides, but
do not remove from under root balls. Remove pallets, if any, before setting. Do
not use planting stock if root ball is cracked or broken before or during planting
operation.
3. Backfill around root ball in layers, tamping to settle soil and eliminate voids and
air pockets. When planting pit is approximately one-half filled, water thoroughly
before placing remainder of backfill. Repeat watering until no more water is
absorbed.
4. Place planting tablets equally distributed around each planting pit when pit is
approximately one-half filled. Place tablets beside the root ball about (25mm)
from root tips; do not place tablets in bottom of the hole.
5. Continue backfilling process. Water again after placing and tamping final layer of
soil.
6. For palms shall be minimum 150-300mm circumference of stem measured 1m
above ground level and shall have a clear straight trunk of not less than 3.0m
from the root collar to the base of the leaf shaft. All plants are to be selected to
give a maximum height variation between plants of 300mm in stem height
between soil level and the base of the lowest leaf at the time of planting. The
heads of the palms shall be well balanced with at least 20 leaves and evidence of
one growing shoot all free from pest and disease attack. Rootball dimensions
1000mm diameter x 600mm deep minimum. No dead leaves are to be present,
and all leaves on the plants shall be free from yellowing, tears or splits, and cut
leaves will not be permitted. Any flowers, fruits and suckers shall be removed
before being brought to site, and cut cleanly from the base of their stems. Palm
shall be balled and burlapped unless container grown are available. Offshoots
will not be acceptable. They shall have a vigorous root system, crown of new
leaves, proper colour of leaves of an adult palm and sufficient hardiness. Prior to
transporting for transplanting, all suckers, flowering and fruiting parts and
approximately thirty percent of fronds shall be removed. The remaining fronds
shall be sprayed with an anti-desiccant during transplanting, lifted to enclose and
protect the growing tip, wrapped in Hessian and securely tied in position. The
roots shall be balled and the Hessian tied. The crown shall be protected at all
times and shall be burlapped for transport and until the palm is growing
successfully in its final location.
a. Quantity: As indicated on Drawings
KEO/21-7387-0004 32 9300/ 14 Plants
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
D. Balled and Potted and Container-Grown Stock: Set each plant plumb and in center of
planting pit or trench with root flare (25mm) above adjacent finish grades.
1. Backfill: Designated planting soil mix - Section 32 9113 "Soil Preparation"
2. Carefully remove root ball from container without damaging root ball or plant.
3. Backfill around root ball in layers, tamping to settle soil and eliminate voids and
air pockets. When planting pit is approximately one-half filled, water thoroughly
before placing remainder of backfill. Repeat watering until no more water is
absorbed.
4. Place planting tablets equally distributed around each planting pit when pit is
approximately one-half filled. Place tablets beside the root ball about (25 mm)
from root tips; do not place tablets in bottom of the hole.
a. Quantity: As per manufacturers recommendations.
5. Continue backfilling process. Water again after placing and tamping final layer of
soil.
E. Fabric Bag-Grown Stock: Set each plant plumb and in center of planting pit or trench
with root flare (25mm) above adjacent finish grades.
1. Backfill: Designated planting soil mix - Section 32 9113 "Soil Preparation"
2. Carefully remove root ball from fabric bag without damaging root ball or plant. Do
not use planting stock if root ball is cracked or broken before or during planting
operation.
3. Backfill around root ball in layers, tamping to settle soil and eliminate voids and
air pockets. When planting pit is approximately one-half filled, water thoroughly
before placing remainder of backfill. Repeat watering until no more water is
absorbed.
4. Place planting tablets equally distributed around each planting pit when pit is
approximately one-half filled. Place tablets beside the root ball about (25mm)
from root tips; do not place tablets in bottom of the hole.
a. Quantity: As per manufacturers recommendations.
5. Continue backfilling process. Water again after placing and tamping final layer of
soil.
F. Slopes: When planting on slopes, set the plant so the root flare on the uphill side is
flush with the surrounding soil on the slope; the edge of the root ball on the downhill side
will be above the surrounding soil. Apply enough soil to cover the downhill side of the
root ball.
A. Remove only dead, dying, or broken branches. Do not prune for shape.
B. Prune, thin, and shape trees, shrubs, and vines as directed by Engineer.
C. No dead leaves are to be present, and all leaves on the plants shall be free from
yellowing, tears or splits, and cut leaves will not be permitted.
B. Trunk Stabilization by Staking and Guying: Install trunk stabilization as follows unless
otherwise indicated on Drawings. Stake and guy trees more than (4.2 m) in height and
more than (75 mm) in caliper unless otherwise indicated.
1. Site-Fabricated, Staking-and-Guying Method: Install no fewer than three guys
spaced equally around tree.
a. Securely attach guys to stakes (760 mm) long, driven to grade. Adjust
spacing to avoid penetrating root balls or root masses. Provide
turnbuckle for each guy wire and tighten securely.
b. For trees more than (150 mm) in caliper, anchor guys to wood deadmen
buried at least (900 mm) below grade. Provide turnbuckles for each guy
wire and tighten securely.
c. Support trees with bands of flexible ties at contact points with tree trunk
and reaching to turnbuckles. Allow enough slack to avoid rigid restraint of
tree.
d. Support trees with guy cable, connected to the brass grommets of tree-tie
webbing at contact points with tree trunk and reaching to turnbuckle
compression spring. Allow enough slack to avoid rigid restraint of tree.
e. Attach flags to each guy wire, (760 mm) above finish grade.
f. Paint turnbuckles with luminescent white paint.
C. Palm dead man guying: Carry out in accordance with manufacturers details.
A. Install root barrier where trees are planted within 1200 mm of paving or other hardscape
elements, such as walls, curbs, and walkways, unless otherwise indicated on Drawings.
B. Align root barrier vertically, and run it linearly along and adjacent to the paving or other
hardscape elements to be protected from invasive roots.
C. Install root barrier continuously for a distance of 2000 mm in each direction from the tree
trunk, for a total distance of (4000)mm per tree. If trees are spaced closer, use a single
continuous piece of root barrier.
1. Position top of root barrier according to manufacturer's written recommendations.
A. Set out and space ground cover and plants other than trees, shrubs, and vines in even
rows with triangular spacing.
B. Use planting soil for backfill as per Section 32 9113 "Soil Preparation"
D. For rooted cutting plants supplied in flats, plant each in a manner that minimally disturbs
the root system but to a depth not less than two nodes.
E. Work soil around roots to eliminate air pockets and leave a slight saucer indentation
around plants to hold water.
F. Water thoroughly after planting, taking care not to cover plant crowns with wet soil.
G. Protect plants from hot sun and wind; remove protection if plants show evidence of
recovery from transplanting shock.
B. Shovel-Cut Edging (where directed): Separate mulched areas from curbs, and paving
with a 45-degree, (100mm to 150mm) deep, shovel-cut edge.
B. Leaf litter, twigs and grass cuttings shall be raked up from grass and paved areas on the
occasion of each mowing and collected separately for re-use/composting where
possible or removed from site.
D. Apply treatments as required to keep plant materials, planted areas, and soils free of
pests and pathogens or disease. Use integrated pest management practices when
possible to minimize use of pesticides and reduce hazards. Treatments include physical
controls such as hosing off foliage, mechanical controls such as traps, and biological
control agents.
A. Apply pesticides and other chemical products and biological control agents according to
authorities having jurisdiction and manufacturer's written recommendations. Coordinate
applications with Employer's operations and others in proximity to the Work. Notify
Employer before each application is performed.
A. General: Repair or replace existing or new trees and other plants that are damaged by
construction operations, in a manner approved by Engineer.
1. Submit details of proposed pruning and repairs.
2. Perform repairs of damaged trunks, branches, and roots within 24 hours, if
approved.
3. Replace trees and other plants that cannot be repaired and restored to full-
growth status, as determined by Engineer.
B. Remove and replace trees that are more than 25 percent dead or in an unhealthy
condition or are damaged during construction operations that Engineer determines are
incapable of restoring to normal growth pattern within 15days of notification.
1. Provide new trees of same size as those being replaced with matching height,
spread and caliper.
2. Species of Replacement Trees: Same species being replaced.
A. During planting, keep adjacent paving and construction clean and work area in an
orderly condition. Clean wheels of vehicles before leaving site to avoid tracking soil
onto roads, walks, or other paved areas.
B. Remove surplus soil and waste material including excess subsoil, unsuitable soil, trash,
and debris and legally dispose of them off Employer's property.
D. After installation and before Substantial Completion, remove nursery tags, nursery
stakes, tie tape, labels, wire, burlap, and other debris from plant material, planting areas,
and Project site.
A. Maintenance Service for Trees and Shrubs: Provide maintenance by skilled employees
of landscape Installer. Maintain as required in "Plant Maintenance" Article. Begin
maintenance immediately after plants are installed and continue until plantings are
acceptably healthy and well established, but for not less than maintenance period
below:
1. Maintenance Period: 12 months from date of planting practical completion.
B. Maintenance Service for Ground Cover and Other Plants: Provide maintenance by
skilled employees of landscape Installer. Maintain as required in "Plant Maintenance"
Article. Begin maintenance immediately after plants are installed and continue until
plantings are acceptably healthy and well established, but for not less than maintenance
period below:
1. Maintenance Period: 12 months from date of planting practical completion.
END OF SECTION
PLANTING ACCESSORIES
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Section Includes:
1. Planting Screens
2. Tree Stakes & Ties
3. Root Ball Fixing Systems
4. Training and Supports for Climbers
B. Related Section: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 05 5000 - Metal Fabrication
1.02 REFERENCES
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contract. Product manufacture, testing and
installation shall comply with the following references unless otherwise stated in the
specification or otherwise approved, but not limited to:
1. ASTM A380 Standard Practice For Cleaning, Descaling, And
Passivation Of Stainless Steel Parts, Equipment, And
Systems
2. ASTM A492 Standard Specification for Stainless Steel Rope Wire
3. ASTM A554-21 Standard Specification for Welded Stainless Steel
Mechanical Tubing
4. ASTM A555 Standard Specification for General Requirements for
Stainless Steel Wire and Wire Rods
5. ASTM F1145-05 Standard Specification for Turnbuckles, Swaged, Welded,
Forged
1.03 SUBMITTALS
A. Submit listed submittals in accordance with Conditions of the Contract and Division 01
Submittal Procedures Section.
1. Product Data: Submit Manufacturer’s product data sheet for specified products.
2. Shop Drawings: Show layout, sizes, dimensions, details, and installation of railing
frame components. Include Details of rope attachment, tensioning methods,
hardware, and tensioning and mounting methodology.
3. Samples: Submit samples of rope and/or hardware, as required by specifier.
4. Quality Assurance/Control Submittals:
A. Qualifications:
1. Installer Qualifications: Installer should be experienced in performing work of this
section and should have specialized in installation of work similar to that required
for this project.
B. MockUps:
1. Install at project site or appropriate location a job mockup using acceptable
products and manufacturer approved installation methods. Obtain Employer’s
and Engineer’s approval of product, application, and workmanship standards.
Comply with Division1 Quality Control Section.
2. Maintenance and Disposal: Maintain mockup during construction for
workmanship comparison.
A. General: Comply with Division 1 Product Requirements Sections Ordering: Comply with
manufacturer’s ordering instructions and lead time requirements to avoid construction
delays.
C. Storage and Protection: Store materials protected from exposure to harmful weather
conditions and at temperature and humidity conditions recommended by manufacturer.
Store cartons and panels in a secure location in a dry place at the project site.
1.06 WARRANTY
PART 2 - PRODUCTS
B. Hessian bands shall be 75mm wide to lengths necessary for wrapping tree trunks and
main branches.
A. All stakes shall be double stakes of timber, straight, free of projections and pointed at
one end. The stakes shall be pressure impregnated with non-injurious wood
preservative to be applied at least two weeks before use.
B. Stakes shall be as indicated on drawings; the length below ground to be one metre
minimum and the length above to be 1.8m, unless otherwise approved by the Engineer.
A. Tree ties shall be fabricated from UV resistant material, be fully adjustable to allow for
tree growth and shall be:
1. Rainbow Chainlock Range C219 – Chainlock No.4 (25.4 x 2.5mm) or approved
equivalent and shall be of consistent type throughout the site as shown on
drawing.
A. Provide Root Ball protection mesh, anchors, galvanized tension cable, ratchet
tensioners as indicated on drawings or as recommended by the manufacturer.
A. Provide 5mm stainless steel braided support wires with stainless steel eye fixing the the
column or base of the wall as indicated on drawings or as recommended by the
manufacturer.
PART 3 - EXECUTION
3.02 EXAMINATION
A. Supply items required to be cast into concrete or embedded in masonry with setting
templates, to appropriate sections.
B. Take field measurements after permanent end terminations are in place and prior to
preparation of shop drawings and fabrication, to ensure fitting of work.
3.04 INSTALLATION
A. Install cable plant support system in accordance with manufacturer's instructions and
the approved shop drawings.
H. After final adjustment provide tamper resistant lock tight materials on all fittings.
A. Provide 5mm stainless steel braided support wires with stainless steel eye fixing the the
column or base of the wall .
B. Plant climber about 300-450mm from the column or base of the wall, so that it has room
for root development.
C. Remove all ties; with plants from nursery , use scissors to cut off plastic ties that hold
the climber to its bamboo cane supports.
D. Untwine the climber from any canes sufficiently to spread out the stems, but leave them
still attached to their cane supports. Select three bamboo canes to train the climber at
an angle up to the wire supports on the wall.
E. Slip the bamboo canes under the wires to hold them in place, adjusting the positioning
to create a fan shape. If the climber came twined around only one bamboo cane, then
untwine it completely and find another two canes to train the stems.
F. Tie the stems and canes to the wire supports. Snip off the excess twine with scissors.
G. After trained the main stems into a basic fan shape, use secateurs to prune off any
weak or twiggy growth that does not contribute to the main framework.
KEO/21-7387-0004 32 9400 / 4 Planting Accessories
Reem Hills Development
Twin Villas & Townhouses, Abu Dhabi
3.06 CLEANING
C. Remove from project site and legally dispose of construction debris associated with this
work.
3.07 PROTECTION
END OF SECTION
PLANTING MAINTENANCE
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The works specified in this section cover all works necessary to maintain the exterior
soft landscape works of the development in coordination with hard landscape, irrigation,
landscape lighting and other site works and contractors. The works shall be carried out
at areas detailed on drawings.
B. Furnish and supply all materials, equipment and labour for maintenance of all
landscaped areas installed as part of this contract.
C. The work shall include, but not be limited to mowing, weed control, insect control,
disease control, pruning, replacement of sub-standard or dead plant material.
D. Perform all work in a manner to comply with the original installation specifications.
1.02 GENERAL
A. The Contractor is responsible for the on-going maintenance of the exterior planted
areas. The Contractor is responsible for all maintenance during the contract period.
B. Begin maintenance of plant materials immediately after planting and continue until
termination of warranty period.
C. This contract includes a 12 months maintenance period from the date of Taking Over
Certificate. The Contractor is responsible for ensuring the continued good health and
good growth of all plants throughout the maintenance period. It is anticipated that the
Contractor will visit the site at least weekly and more frequently when needed such as
during dry periods to monitor the irrigation system or hand watering as required to
ensure the continued good health and growth of all plants.
F. The Contractor shall include the cost of training personnel employed by the Employer
for the entire Maintenance period.
G. All chemicals, fertilizers, pesticides and herbicides shall be locked in specially designed
containers and maintained through the maintenance period to avoid spillage or
accidental inhalation. Pollution from spills or litter shall be removed from the
landscaping areas during normal maintenance.
H. Soil and Fertility: Use of fertilizers and soil additives are to be kept to an absolute
minimum. Soils are to have salinity levels and nutrient levels checked quarterly to inform
use of fertilizers.
B. This manual shall be submitted for approval at least two weeks prior to Date of Taking
Over Certificate.
1.04 REPORTING
PART 2 - PRODUCTS
A. During the maintenance period the Contractor shall replace at the Contractor's expense
any dead or unhealthy plant material. This does not include the replacement of plants
removed or killed by vandalism by others. Any plants removed or killed by vandalism
shall be reported to the Engineer. The Engineer may instruct a variation for the
replacement of the plant material.
A. The Contractor shall be responsible for the supply, cartage and spreading of fertiliser.
B. A proprietary fertiliser suited to the species and approved by the Employer or nominated
representative shall be applied at 6 months, 12 months, 18 months, 24 months where
plants are showing signs of lack of fertility, or to ensure maximum health and vigour in
all grades of shrubbery as identified above.
2.03 WEEDS
A. The Contractor shall carry out detailed inspections of the planted areas at least
fortnightly and programme to control the weeds within twenty four (24) hours of the
inspection. Weeds shall be controlled manually unless approved otherwise by the
Employer or nominated representative. When hoeing/pulling care shall be taken to avoid
damage to plants and their roots. Where area is not mulched the top 20mm of soil is to
be cultivated to a fine tilth. The soil shall not be mixed with mulch when removing
weeds.
2.04 MULCH
A. The Contractor will be responsible for the maintenance, top up, supply, cartage and
spreading of mulch to maintain a depth of 75mm at all times.
B. Mulching shall be carried out on an ongoing basis and at least 6 monthly to all garden
areas unless specifically excluded.
C. The process of installation of mulch includes levelling of soil surface to remove humps
and hollows, and removal of weeds and grass prior to mulching. The Contractor shall
be responsible for controlling regrowth of weeds.
F. The Contractor shall ensure that other materials including soil are not mixed with the
mulch during the work.
G. Edges shall be checked and rebuilt or repaired as necessary prior to mulching. Where
necessary the soil level shall be reduced. Edges shall hold mulch without spillage. The
edges shall not be damaged when placing the mulch.
H. Note that some garden areas may be sloping, and that mulches will require additional
maintenance to keep the edges in specification. Where mulched gardens are on a
slope, the Contractor shall maintain the mulch at 75mm depth across the whole garden.
The contractor shall rake mulch uphill from lower portions regularly to maintain the
specified mulch depth. Spilt mulches shall be collected and spread over adjacent
gardens on each visit.
I. When mulch is applied all low branches and foliage shall be lifted and mulch worked
around the plants. No mulch shall be spilled over the edges of gardens onto surrounding
surfaces. The mulch shall be spread evenly to the correct depth.
J. Where it is known that mulch affects certain species the Employer or nominated
representative shall instruct the Contractor to use alternative mulches approved by the
Employer or nominated representative.
2.05 PRUNING
A. Pruning will be required on shrubs and trees throughout the year to maintain a high
standard of presentation, display and plant vigour. Paths, roads, all other accessways
and windows are to be kept clear of excess growth.
D. Pruning for form, shape and size is to be carried out within two weeks of an instruction
from the Employer or nominated representative at the Contractor’s expense.
F. All prunings shall be removed to waste as they arise leaving the gardens and
surrounding surfaces area in a clean and tidy condition.
G. Spent flowerheads are to be removed including but not limited to the following species:
Agapanthus, arthropodium.
H. The Contractor shall carry out detailed inspections of the shrubbery’s monthly and plan
to remove dead and irrecoverable plants within three (3) days of the inspection. The
Contractor shall report the removal of dead and irrecoverable plants in their monthly
report.
A. The Contractor shall be responsible for the supply, cartage and placement of supports.
B. Prior to installation, the Contractor shall supply a sample of supports for approval by the
Engineer and Employer or nominated representative. These shall be inconspicuous and
matched throughout the Contract area. Guys, ties and supports shall be added,
replaced and adjusted as necessary to allow for growth and prevent chaffing. Ties shall
be tightened as necessary to support the plant. The Contractor shall ensure that all
stakes are sound and are sufficiently inserted to prevent lateral movement. Broken
stakes shall be replaced within 24 hours of discovery by the Contractor or notification by
the Engineer.
C. Stakes shall be installed and maintained taut and be the same height throughout the
Contract area, or lesser approved area.
D. The Contractor shall carry out detailed inspections of stakes monthly and plan to make
repairs, remove redundant tapes, tags, ties and other encumbrances to the satisfaction
of the staking specifications within twenty four (24) hours of the inspection.
E. Plants must be supported in such a way as to protect the plant and stem from damage.
G. Where chaffing has occurred, the Contractor shall reposition tie(s), insert a spacer or
replace the support to prevent further chaffing.
A. The Contractor is responsible for the monitoring and control of plant health, pests and
diseases within the Contract area. To affect this, the Contractor shall make inspections
in conjunction with other inspections and activities and arrange for eradication or
treatment of the health problem within five (5) days of inspection. Any health problem
shall be reported to the Employer or nominated representative.
B. The Contractor shall be pro active in the reporting and treatment of anything affecting
the well being of the plants. In particular significant adverse conditions, dieback or
browning of leaves, branches, or any other signs.
C. Where soil borne fungal disease such as Phytophora become evident the Contractor
shall supply and apply “Trichopel” pellets or approved equivalent according to
manufacturer’s recommendation to affected areas and other areas likely to be affected.
D. Where damage from desiccation or wind damage starts to occur an anti-transpirant shall
be applied. The Contractor shall allow to supply and apply Anti-transpirants or other
suitable treatment to prevent further desiccation in accordance with the manufacturer’s
recommendations.
E. The Contractor shall use pesticides in accordance with the Landscape Specification.
A. Where reference is made to edges and/or hard surfaces elsewhere in this document,
this section shall apply.
B. Edges
1. Edges include but are not limited to; All grass and garden edges, kerbs, paths,
structures including seats, tables and furniture, signs, statues and sculpture,
water features and ponds, rubbish bins, rocks, buildings, retainers, fences, the
interface between grass and the trunks of trees and shrubs, around trees, mulch
edges, poles, posts, cesspits, drains, roadways, footpaths and car parks, drains
and the like.
2. Edges shall be maintained so that they hold any loose materials from
encroaching onto neighbouring surfaces. Where materials do escape onto
surrounding surfaces they are to be removed or reused as appropriate.
C. Hard Surfaces
1. Hard surfaces include, but are not limited to, all paths, car parks and paved
areas, wooden decking, boardwalks, bridges, stone and retaining walls, drain
grates within the scheduled areas. These surfaces are to be maintained free of
PART 3 - EXECUTION
A. The Contractor shall carry out detailed inspections and programme vegetation control
and maintenance to ensure compliance with the specification is met at all times.
B. Vegetation shall be controlled so it does not exceed the maximum height and maximum
spread. At least 99 percent of the total edge length shall be satisfactorily treated and the
overall appearance of the garden/reserve shall be satisfactory.
C. NOTE: There are many instances where only either maximum height or maximum
spread are applicable at any edge.
D. Maximum Height: The maximum height in millimetres (mm) above firm ground level that
vegetation shall be allowed to reach at the edge defined in table below.
E. Maximum Spread: The maximum distance in millimetres (mm) that vegetation shall be
allowed to reach from the edge defined in table below.
Maximum Height Maximum Spread
mm mm
F. Where manual methods of control are used the protruding vegetation shall be cut by use
of clippers or some other mechanical device that make a precise, even cut. A
proprietary edging machine shall be used against kerbs, concrete paths, mowing strips
etc.
G. Any spraying control methods shall use non-toxic materials approved by the Employer
or nominated representative in accordance with the Landscape Specification.
H. Where the edge is not defined the edge shall be controlled when the vegetation varies
more than the maximum spread defined in the Table over two (2) metres from a straight
line or natural curve.
I. All weeds shall be removed from within hard surfaces including but not limited to car
parks, walkways, paths etc. All moss shall be prevented from building up on paths such
that the path becomes slippery.
B. Dead, missing or defective plant material shall be replaced. Replaced plants will be of
the same size and species as originally specified.
C. Weed plant beds and saucers. Prior to inspection treat these areas with an application
of approved pre-emergent herbicide.
D. Remove stakes, guy wires and wrappings from plants as directed by the Engineer.
G. A final inspection, if required, shall be undertaken by the Engineer to determine that the
deficiencies noted in the preliminary inspection have been corrected. The time for this
inspection shall be established in writing.
END OF SECTION
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - Index
UAE 1 of 12 © KEO International Consultants. All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Location: Kitchen
Luminare information:
Manufacturer Multidir Evo small / AU13-
LED C4 Model
(Design based on) 11W9F10U14
Alternative
Protection Class IP54
Manufacturer
Controlgear
Colour White Remote
(Remote/Intergral)
Luminaire
Housing Aluminium Lumen Output 2282 lm
(Delivered Lumens)
Dimmed/Switched
Reflector Wide beam S
(D/S)
Design
Mounting Ceiling recess 23W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 23 W
Lamp Key LED C4
Source Lumen Output 2700 lm
Life(@L70B20 Min) 50,000
Colour Temp 3000 K CRI 90
MacAdam Binning Step 2
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - D10 © KEO International Consultants
UAE 2 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Location: Bathroom
Luminare information:
Manufacturer
LED C4 Model lite / 90-A027-14-00
(Design based on)
Alternative
Protection Class IP54
Manufacturer
Controlgear
Colour White Remote
(Remote/Intergral)
Luminaire
Housing Polycarbonate, Graphene Lumen Output 660 lm
(Delivered Lumens)
Dimmed/Switched
Reflector Medium beam 32 degree S
(D/S)
Design
Mounting Ceiling recess 8.4 W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 8.4 W
Lamp Key LED
Source Lumen Output 750 lm
Life(@L70B20 Min) 50,000
Colour Temp 3000 K CRI 80
MacAdam Binning Step 3
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - D11 © KEO International Consultants
UAE 3 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Luminare information:
Manufacturer
Arkos Model Swap M
(Design based on)
Alternative
Protection Class IP20
Manufacturer
Controlgear
Colour White Remote
(Remote/Intergral)
Luminaire
Housing Aluminium Lumen Output 940 lm
(Delivered Lumens)
Dimmed/Switched
Reflector Medium beam 42 degree S
(D/S)
Design
Mounting Ceiling recess 7W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 8.7 W
Lamp Key LED
Source Lumen Output 940 lm
Life(@L70B20 Min) 50,000
Colour Temp 3000 K CRI 80
MacAdam Binning Step 2
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - D13 © KEO International Consultants
UAE 4 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Luminare information:
Manufacturer
iinno light Model IDL 15-B Slim Anti-dazzle
(Design based on)
Alternative
Protection Class IP20
Manufacturer
Controlgear
Colour White Remote
(Remote/Intergral)
Luminaire
Housing Aluminium Lumen Output 1955 lm
(Delivered Lumens)
Dimmed/Switched
Reflector Wide flood S
(D/S)
Design
Mounting Ceiling recess 23 W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 23 W
Lamp Key LED
Source Lumen Output 1955 lm
Life(@L70B20 Min) 50,000
Colour Temp 3000 K CRI 80
MacAdam Binning Step 2
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - D14 © KEO International Consultants
UAE 5 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Location: Toilets
Luminare information:
Manufacturer
Astro Model PALERMO 600 LED
(Design based on)
Alternative
Protection Class IP44
Manufacturer
Controlgear
Colour Polished Chrome Remote
(Remote/Intergral)
Luminaire
Housing Metal-Aluminium Lumen Output 364 lm
(Delivered Lumens)
Dimmed/Switched
Reflector S
(D/S)
Design
Mounting Wall mounted 8.1 W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 8.1 W
Lamp Key LED
Source Lumen Output 364 lm
Life(@L70B20 Min) 50,000
Colour Temp 3000 K CRI 80
MacAdam Binning
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - ML © KEO International Consultants
UAE 6 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Location: Staircase
Luminare information:
Manufacturer
Delta light Model GALAT 930/ 12220 9300
(Design based on)
Alternative
Protection Class IP20
Manufacturer
Controlgear
Colour White Remote
(Remote/Intergral)
Luminaire
Housing Aluminium Lumen Output 669 lm
(Delivered Lumens)
Dimmed/Switched
Reflector Up/Down ward lighting distribution S
(D/S)
Design
Mounting Wall mounted 11 W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 9 W
Lamp Key LED
Source Lumen Output 1479 lm
Life(@L70B20 Min) 50,000
Colour Temp 3000 K CRI 90
MacAdam Binning
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - WL10 © KEO International Consultants
UAE 7 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Luminare information:
Manufacturer
Sylvania Model 49002
(Design based on)
Alternative
Protection Class IP66
Manufacturer
Controlgear
Colour Black Remote
(Remote/Intergral)
Luminaire
Housing Polycarbonate Lumen Output 1450 lm
(Delivered Lumens)
Dimmed/Switched
Reflector Wide beam 120 degree S
(D/S)
Design
Mounting Wall mounted 14.5 W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 14.5 W
Lamp Key LED
Source Lumen Output 1450 lm
Life(@L70B20 Min) 50,000
Colour Temp 3000 K CRI 80
MacAdam Binning Step 6
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - WL11 © KEO International Consultants
UAE 8 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Luminare information:
Manufacturer AFRODITA Power Led/ 05-
LEDS C4 Model
(Design based on) E056-60-CL
Alternative
Protection Class IP65
Manufacturer
Controlgear
Colour Black Remote
(Remote/Intergral)
Luminaire
Housing Aluminium Lumen Output 1136 lm
(Delivered Lumens)
Dimmed/Switched
Reflector Medium beam 26 degree S
(D/S)
Design
Mounting Wall mounted 13 W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 13 W
Lamp Key LED
Source Lumen Output 1380 lm
Life(@L70B20 Min) 50,000
Colour Temp 3000 K CRI 80
MacAdam Binning Step 3
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - WL12 © KEO International Consultants
UAE 9 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Luminare information:
Manufacturer
Model
(Design based on)
Alternative
Protection Class IP20
Manufacturer
Controlgear
Colour
(Remote/Intergral)
Luminaire
Housing Lumen Output
(Delivered Lumens)
Dimmed/Switched
Reflector D
(D/S)
Design
Mounting 100 W (Provisional)
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 100 W (Provisional) Basic Light point provision with pendent ceiling
Lamp Key LED rose and standard lamp holder. Decorative
Source Lumen Output fixture to be selected and installed by the
Life(@L70B20 Min) 50,000 occupant.
Colour Temp 3000 K CRI >85
MacAdam Binning Step 2
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - LP © KEO International Consultants
UAE 10 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Luminare information:
Manufacturer
ZUMTOBEL Model AMP S 4600-840 CH WB EVG
(Design based on)
Alternative
Protection Class IP66
Manufacturer
Controlgear
Colour White NONE
(Remote/Intergral)
Luminaire
Housing Impact resistant Chemo Lumen Output 4430lm
(Delivered Lumens)
Dimmed/Switched
Reflector Switch
(D/S)
Design
Mounting SURFACE 34W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 34 W Length is 1100 mm
Lamp Key LED
Source Lumen Output 4430 lm
Life(@L70B20 Min) 50.000h
Colour Temp 4000 K CRI >80
MacAdam Binning Step 3
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - L61 © KEO International Consultants
UAE 11 of 12 All Rights Reserved 2021
Date 15-Feb-2023
Luminaire Specification Sheet
Rev. 0
Luminare information:
Manufacturer
Linealight Model Portik_R/ 81851W30
(Design based on)
Alternative
Protection Class IP65
Manufacturer
Controlgear
Colour White Remote Electronic
(Remote/Intergral)
Luminaire
Housing Diecast Aluminium Lumen Output 650 lm
(Delivered Lumens)
Dimmed/Switched
Reflector Wide beam S
(D/S)
Design
Mounting Ceiling surface mounted 8W
Load (watts)
Power supply, all applicable installation
Accessories
accessories
Lamp information: Notes:
Specification 8 W LED
Lamp Key LED
Source Lumen Output 770 lm
Life(@L70B20 Min) 50,000 hrs
Colour Temp 3000 K CRI 80
MacAdam Binning Step 2
KEO/21-7387-0004
REEM HILLS DEVELOPMENT TWIN VILLAS / TOWNHOUSES Lighting Cutsheets - S10 © KEO International Consultants
UAE 12 of 12 All Rights Reserved 2021