01 Elements of Power System Analysis Stevenson 1
01 Elements of Power System Analysis Stevenson 1
01 Elements of Power System Analysis Stevenson 1
system
analysis
Fourth Edition
William D.
Stevenson, Jr.
'
ELEMENTS OF POWER SYSTEM ANALYSIS
McGraw-Hill Series in Electrical Engineering
Consulting Editor
Stephen W. Director, Camegie-Mellon University
McGraw-Hill, Inc.
New York St. Louis San Francisco Auckland Bogota
Caracas Lisbon London Madrid Mexico Milan
Montreal New Delhi Paris San Juan Singapore
Sydney Tokyo Toronto
This book was set in Times Roman.
The editor was Frank J. Cerra;
the production supervisor was Diane Renda.
The cover was designed by Infield, D’Astolfo Associates.
Copyright © 1982, 1975, 1962, 1955 by McGraw-Hill, Inc. All rights reserved.
Printed in the United States of America. No part of this publication
may be reproduced, stored in a retrieval system, or transmitted, in any
form or by any means, electronic, mechanical, photocopying, recording, or
otherwise, without the prior written permission of the publisher.
HDHD 99876543
Stevenson, William D.
Elements of power system analysis.
Preface xi
2.1 Introduction 10
2.2 Single-Subscript Notation 11
2.3 Double-Subscript Notation 12
2.4 Power in Single-Phase AC Circuits 13
2.5 Complex Power 18
2.6 The Power Triangle 18
2.7 Direction of Power Flow 19
2.8 Voltage and Current in Balanced Three-Phase Circuits 22
2.9 Power in Balanced Three-Phase Circuits 28
2.10 Per-Unit Quantities 30
2.11 Changing the Base of Per-Unit Quantities 33
Problems 34
Appendix 423
Index 431
V*
* ■*
v
PREFACE
Each revision of this book has embodied many changes, this one more so than
usual. Over the years, however, the objective has remained the same. The
approach has always been to develop the thinking process of the student in
reaching a sound understanding of a broad range of topics in the power-system
area of electrical engineering. At the same time, another goal has been to promote
the student’s interest in learning more about the electric-power industry. The
objective is not great depth, but the presentation is thorough enough to give the
student the basic theory at a level that can be understood by the undergraduate.
With this beginning, the student will have the foundation to continue his educa¬
tion while at work in the field or in graduate school. Footnotes throughout the
book suggest sources of further information on most of the topics presented.
As in preparing previous revisions, I sent a questionnaire to a number of
faculty members across the country, and I appreciate greatly the prompt and in
many cases, the detailed responses to specific questions as well as the valuable
additional comments. The most popular suggestion was for a chapter on system
protection, and accordingly that subject has been added to the other four main
topics of load flow, economic dispatch, fault calculations, and system stability.
Perhaps surprisingly there were many requests to retain the material on trans¬
mission-line parameters. The per-unit system is first introduced in Chapter 2 and
developed gradually to allow the student to become accustomed to scaled, or
normalized, quantities. The need to review steady-state alternating-current circuits
still exists and so the chapter on basic concepts is not altered. Direct formulation
of the bus impedance matrix has been added. The Newton-Raphson method for
load-flow calculations has been developed more fully. Increased attention has
been given to developing the equivalent circuits of transformers and synchronous
machines to help the many students who study power systems before they have
had a course in machinery. Equations for transients on a lossless line have been
developed to lead into the discussion of surge arresters. Other topics discussed
briefly are direct-current transmission, reactive compensation, and underground
cables. The subject of automatic load dispatch has been expanded.
xii PREFACE
ONE
GENERAL BACKGROUND
The development of ac systems began in the United States in 1885, when George
Westinghouse bought the American patents covering the ac transmission system
developed by L. Gaulard and J. D. Gibbs of Paris. William Stanley, an early
l
2 ELEMENTS OF POWER SYSTEM ANALYSIS
whole country. The demand for large blocks of power and increased reliability
suggested the interconnection of neighboring systems. Interconnection is advan¬
tageous economically because fewer machines are required as a reserve for oper¬
ation at peak loads (reserve capacity) and fewer machines running without load
are required to take care of sudden, unexpected jumps in load (spinning reserve).
The reduction in machines is possible because one company can usually call on
neighboring companies for additional power. Interconnection also allows a com¬
pany to take advantage of the most economical sources of power, and a com¬
pany may find it cheaper to buy some power than to use only its own generation
during some periods. Interconnection has increased to the point where power is
exchanged between the systems of different companies as a matter of routine.
The continued service of systems depending on water power for a large part of
their generation is possible in times of unusual and extreme water shortage only
because of the power obtained from other systems through interconnections.
Interconnection of systems brought many new problems, most of which have
been solved satisfactorily. Interconnection increases the amount of current which
flows when a short circuit occurs on a system and requires the installation of
breakers able to interrupt a larger current. The disturbance caused by a short
circuit on one system may spread to interconnected systems unless proper relays
and circuit breakers are provided at the point of interconnection. Not only must
the interconnected systems have the same nominal frequency, but also the syn¬
chronous generators of one system must remain in step with the synchronous
generators of all the interconnected systems.
Planning the operation, improvement, and expansion of a power system
requires load studies, fault calculations, the design of means of protecting the
system against lightning and switching surges and against short circuits, and
studies of the stability of the system. An important problem in efficient system
operation is that of determining how the total generation required at any time
should be distributed among the various plants and among the units within each
plant. In this chapter we shall consider the general nature of these types of problems
after a brief discussion of energy production and of transmission and distribution.
We shall see the great contributions made by computers to the planning and
operation of power systems.
merits which cause redesign, public opposition to the operation of the plants,
and delays in licensing.
Many plants converted to oil between 1970 and 1972, but in the face of the
continuous escalation in the price of oil and the necessity of reducing depen¬
dence on foreign oil reconversion from oil to coal has taken place wherever
possible.
The supply of uranium is limited, but the fast breeder reactors now pro¬
hibited in the United States, have greatly extended the total energy available
from uranium in Europe. Nuclear fusion is the great hope for the future, but a
controllable fusion process on a commercial scale is not expected to become
feasible until well after the year 2000, if ever. That year, however, is now the
target date for demonstrating the first pilot model of a controlled fusion reactor.
As this comes to pass, electric power systems must continue to grow and take
over the direct fuel applications. For instance, the electric car will probably be
widely used in order to reserve the fossil fuels (including petroleum and gas
synthesized from coal) for aircraft and long-distance trucking.
There is some use of geothermal energy in the form of live steam issuing
from the ground in the United States and foreign countries. Solar energy, now
chiefly in the form of direct heating of water for residential use, should even¬
tually become practical through research on photovoltaic cells which convert
sunlight to electricity directly. Great progress has been made in increasing the
efficiency and reducing the cost of these cells, but the distance still to go is
extremely large. Windmills driving generators are operating in a number of
locations to provide small amounts of power to power systems. Efforts to extract
power from the changing tides and from waves are under way. An indirect form
of solar energy is alcohol grown from grain and mixed with gasoline to make an
acceptable fuel for automobiles. Synthetic gas from garbage and sewage is
another indirect form of solar energy.
Finally, in producing energy by any means, protection of our environment is
extremely important. Atmospheric pollution is all too apparent to residents of
industrialized countries. Thermal pollution is less obvious, but cooling water for
nuclear reactors is very important and adds greatly to construction costs. Too
great a rise in the temperature of rivers is harmful to fish, and artificial lakes for
cooling water often use up too much productive land. Here cooling towers,
though expensive, seem to be the answer for cooling at nuclear plants.
The voltage of large generators usually is in the range of 13.8 kV to 24 kV. Large
modern generators, however, are built for voltages ranging from 18 to 24 kV. No
standard for generator voltages has been adopted.
Generator voltage is stepped up to transmission levels in the range of 115 to
765 kV. The standard high voltages (HV) are 115, 138, and 230 kV. Extra-high
voltages (EHV) are 345, 500, and 765 kV. Research is being conducted on lines
in the ultra-high-voltage (UHV) levels of 1000 to 1500 kV. The advantage of
higher levels of transmission-line voltage is apparent when consideration is given
GENERAL BACKGROUND 5
A load study is the determination of the voltage, current, power, and power
factor or reactive power at various points in an electric network under existing
or contemplated conditions of normal operation. Load studies are essential in
planning the future development of the system because satisfactory operation of
the system depends on knowing the effects of interconnections with other power
systems, of new loads, new generating stations, and new transmission lines before
they are installed.
Before the development of large digital computers load-flow studies were
made on ac calculating boards, which provided small-scale single-phase replicas
of actual systems by interconnecting circuit elements and voltage sources. Setting
up the connections, making adjustments, and reading the data was tedious
and time-consuming. Digital computers now provide the solutions of load-flow
studies on complex systems. For instance, the computer program may handle
more than 1500 buses, 2500 lines, 500 transformers with tap changing under load,
and 25 phase-shifting transformers. Complete results are printed quickly and
economically.
6 ELEMENTS OF POWER SYSTEM ANALYSIS
The power industry may seem to lack competition. This idea arises because each
power company operates in a geographic area not served by other companies.
Competition is present, however, in attracting new industries to an area. Favor¬
able electric rates are a compelling factor in the location of an industry, although
this factor is much less important in times when costs are rising rapidly and rates
charged for power are uncertain than in periods of stable economic conditions.
Regulation of rates by state utility commissions, however, places constant pres¬
sure on companies to achieve maximum economy and earn a reasonable profit
in the face of advancing costs of production.
Economic dispatch is the name given to the process of apportioning the total
load on a system between the various generating plants to achieve the greatest
economy of operation. We shall see that all the plants on a system are controlled
continuously by a computer as load changes occur so that generation is al¬
located for the most economical operation.
A fault in a circuit is any failure which interferes with the normal flow of current.
Most faults on transmission lines of 115 kV and higher are caused by lightning,
which results in the flashover of insulators. The high voltage between a conduc¬
tor and the grounded supporting tower causes ionization, which provides a path
to ground for the charge induced by the lightning stroke. Once the ionized path
to ground is established, the resultant low impedance to ground allows the flow
of power current from the conductor to ground and through the ground to the
grounded neutral of a transformer or generator, thus completing the circuit.
Line-to-line faults not involving ground are less common. Opening circuit
breakers to isolate the faulted portion of the line from the rest of the system
interrupts the flow of current in the ionized path and allows deionization to take
place. After an interval of about 20 cycles to allow deionization, breakers can
usually be reclosed without reestablishing the arc. Experience in the operation of
transmission lines has shown that ultra-high-speed reclosing breakers suc¬
cessfully reclose after most faults. Of those cases where reclosure is not success-
GENERAL BACKGROUND 7
Faults can be very destructive to power systems. A great deal of study, develop¬
ment of devices, and design of protection schemes have resulted in continual
improvement in the prevention of damage to transmission lines and equipment
and interruptions in generation following the occurrence of a fault.
We shall be discussing the problem of transients on a transmission line for a
very simplified case. This study will lead us to a discussion of how surge arresters
protect apparatus such as transformers at plant buses and substations against
the very high voltage surges caused by lightning and, in the case of EHV and
UHV lines, by switching.
Faults caused by surges are usually of such short duration that any circuit
breakers which may open will reclose automatically after a few cycles to restore
normal operation. If arresters are not involved or faults are permanent the
faulted sections of the system must be isolated to maintain normal operation of
the rest of the system.
8 ELEMENTS OF POWER SYSTEM ANALYSIS
can carry. Instability results from attempting to increase the mechanical input to
a generator or the mechanical load on a motor beyond this definite amount of
power, called the stability limit. A limiting value of power is reached even if the
change is made gradually. Disturbances on a system, caused by suddenly applied
loads, by the occurrence of faults, by the loss of excitation in the field of a
generator, and by switching, may cause loss of synchronism even when the
change in the system caused by the disturbance would not exceed the stability
limit if the change were made gradually. The limiting value of power is called the
transient stability limit or the steady-state stability limit, according to whether
the point of instability is reached by a sudden or a gradual change in conditions
of the system.
Fortunately, engineers have found methods of improving stability and of
predicting the limits of stable operation under both steady-state and transient
conditions. The stability studies we shall investigate for a two-machine system
are less complex than studies of multimachine systems, but many of the methods
of improving stability can be seen by the analysis of a two-machine system.
Digital computers are used to advantage in predicting the stability limits of a
complex system.
TWO
BASIC CONCEPTS
The power-system engineer is just as concerned with the normal operation of the
system as he is with the abnormal conditions which may occur. Therefore, he
must be very familiar with steady-state ac circuits, particularly three-phase cir¬
cuits. It is the purpose of this chapter to review a few of the fundamental ideas of
such circuits, establish the notation which will be used throughout the book, and
introduce the expression of values of voltage, current, impedance, and power in
per unit.
2.1 INTRODUCTION
and
10
BASIC CONCEPTS 11
their maximum values are obviously Fmax = 141.4 V and 7max = 7.07 A, respec¬
tively. Vertical bars are not needed when the subscript max with V and / is used
to indicate maximum value. The term magnitude refers to root-mean-square or
(rms) values, which equal the maximum values divided by yj2. Thus, for the
above expressions for v and i,
These are the values read by the ordinary types of voltmeters and ammeters.
Another name for the rms value is the effective value. The average power ex¬
pended in a resistor is \I\2 R-
To express these quantities as phasors a reference must be chosen. If the
current is the reference phasor
/ = 5/p = 5+j0 A
Of course, we might not choose as the reference phasor either the voltage or
current whose instantaneous expressions are v and i, in which case their phasor
expressions would involve other angles.
In circuit diagrams it is often most convenient to use polarity marks in the
form of plus and minus signs to indicate the terminal assumed positive when
specifying voltage. An arrow on the diagram specifies the direction assumed
positive for the flow of current. In the single-phase equivalent of a three-phase
circuit single-subscript notation is usually sufficient, but double-subscript nota¬
tion is usually simpler when dealing with all three phases.
Figure 2.1 shows an ac circuit with an emf represented by a circle. The emf is Eg,
and the voltage between nodes a and o is identified as Vt. The current in the
circuit is IL and the voltage across ZL is VL. To specify these voltages as phasors,
however, the + and - markings, called polarity marks, on the diagram and an
arrow for current direction are necessary.
In an ac circuit the terminal marked + is positive with respect to the
terminal marked - for half a cycle of voltage and is negative with respect to the
\J
V#.
\p2_
Q.
other terminal during the next half cycle. We mark the terminals to enable «us to
say that the voltage between the terminals is positive at any instant when the
terminal marked plus is actually at a higher potential than the terminal marked
minus. For instance, in Fig. 2.1 the instantaneous voltage v, is positive when the
terminal marked plus is actually at a higher potential than the terminal marked
with a negative sign. During the next half cycle the positively marked terminal is
actually negative, and vt is negative. Some authors use an arrow but must specify
whether the arrow points toward the terminal which would be labeled plus or
toward the terminal which would be labeled minus in the convention described
above.
The current arrow performs a similar function. The subscript, in this case L,
is not necessary unless other currents are present. Obviously the actual direction
of current flow in an ac circuit reverses each half cycle. The arrow points in the
direction which is to be called positive for current. When the current is actually
flowing in the direction opposite that of the arrow, the current is negative. The
phasor current is
(2.1)
and
The use of polarity marks for voltages and direction arrows for currents can be
avoided by double-subscript notation. Understanding of three-phase circuits is
considerably clarified by adopting a system of double subscripts. The convention
to be followed is quite simple.
In denoting a current the order of the subscripts assigned to the symbol for
current defines the direction of flow of current when the current is considered to
be positive. In Fig. 2.1 the arrow pointing from a to b defines the positive
direction for the current IL associated with the arrow. The instantaneous current
iL is positive when the current is actually in the direction from a to b, and in
double-subscript notation this current is iab. The current iab is equal to - iba.
BASIC CONCEPTS 13
where ZA is the complex impedance through which Iab flows between nodes a
and b, which may also be called Zab.
Reversing the order of the subscripts of either a current or voltage gives a
current or voltage 180° out of phase with the original; that is,
V
vt = V
va = V
v ao V,
rL = K
rb = K
v bo
IL Iab
In writing Kirchhoff’s voltage law the order of the subscripts is the order of
tracing a closed path around the circuit. For Fig. 2.1,
K. + K, + K, = 0 (2.4)
Nodes n and o are the same in this circuit, and n has been introduced to identify
the path more precisely. Replacing Voa by - Vao and noting that Vab = IabZA
yields
— K o + KbZA + Kn — 0 (2-5)
and so
U= (2.6)
The angle 6 in these equations is positive for current lagging the voltage and
negative for leading current. A positive value of p expresses the rate at which
energy is being absorbed by the part of the system between the points a and n.
The instantaneous power is obviously positive when both van and ian are positive
but will become negative when van and ian are opposite in sign. Figure 2.2
illustrates this point. Positive power calculated as van ian results when current is
flowing in the direction of a voltage drop and is the rate of transfer of energy to
the load. Conversely, negative power calculated as van ian results when current is
flowing in the direction of a voltage rise and means energy is being transferred
from the load into the system to which the load is connected. If van and ian are in
phase, as they are in a purely resistive load, the instantaneous power will never
become negative. If the current and voltage are out of phase by 90°, as in a
purely inductive or purely capacitive ideal circuit element, the instantaneous
power will have equal positive and negative half cycles and its average value will
be zero.
By using trigonometric identities the expression of Eq. (2.7) is reduced to
where Fmax/max/2 may be replaced by the product of the rms voltage and current
I Km | • \lan\ Ot\V\ ' |/|.
Another way of looking at the expression for instantaneous power is to
consider the component of the current in phase with van and the component 90°
out of phase with van. Figure 2.3a shows a parallel circuit for which Fig. 23b is
the phasor diagram. The component of ian in phase with van is iR, and from
Fig. 23b, 17*1 = \Ian \ cos 9. If the maximum value of ian is 7max, the maximum
value of iR is 7max cos 9. The instantaneous current iR must be in phase with van.
BASIC CONCEPTS 15
ao
Similarly the component of ian lagging van by 90° is ix, whose maximum value is
/max sin 9. Since ix must lag van by 90°,
Then
V I max
r max1
cos 0(1+ cos 2cot) (2.11)
which is the instantaneous power in the resistance and is the first term in
Eq. (2.8). Figure 2.4 shows vaniR plotted versus t.
Similarly,
V 1
=---sin 0 sin 2ojt (2.12)
which is the instantaneous power in the inductance and is the second term in
Eq. (2.8). Figure 2.5 shows van, ix, and their product plotted versus t.
Figure 2.4 Voltage, current in phase with the voltage, and the resulting power plotted versus time.
16 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 2.5 Voltage, current lagging the voltage by 90°, and the resulting power plotted versus time.
Examination of Eq. (2.8) shows that the first term, the term which contains
cos 9, is always positive and has an average value of
P is the quantity to which the word power refers when not modified by an
adjective identifying it otherwise. P, the average power, is also called the real
power. The fundamental unit for both instantaneous and average power is the
watt, but a watt is such a small unit in relation to power-system quantities that P
is usually measured in kilowatts or megawatts.
The cosine of the phase angle 9 between the voltage and the current is called
the power factor. An inductive circuit is said to have a lagging power factor, and
a capacitive circuit is said to have a leading power factor. In other words, the
terms lagging power factor and leading power factor indicate, respectively,
whether the current is lagging or leading the applied voltage.
The second term of Eq. (2.8), the term containing sin 9, is alternately posi¬
tive and negative and has an average value of zero. This component of the
instantaneous power p is called the instantaneous reactive power and expresses
the flow of energy alternately toward the load and away from the load. The
maximum value of this pulsating power, designated Q, is called reactive power or
reactive voltamperes and is very useful in describing the operation of a power
system, as will become increasingly evident in further discussion. The reactive
power is
or
The square root of the sum of the squares of P and Q is equal to the product
of | V | and | /1, for
yP2 + Q2 = ^(\V\• |/| cos 9)2 + (\V\- |/| sin 9f = |K| • |/| (2.17)
Of course P and Q have the same dimensional units, but it is usual to designate
the units for Q as vars (for voltamperes reactive). The more practical units for Q
are kilovars or megavars.
In a simple series circuit where Z is equal to P + jX, we can substitute
| / | • | Z | for | V | in Eqs. (2.14) and (2.16) to obtain
cos 6 =
P2 + Q<
If the instantaneous power expressed by Eq. (2.8) is the power in a pre¬
dominantly capacitive circuit with the same impressed voltage, 9 would be nega¬
tive, making sin 9 and Q negative. If capacitive and inductive circuits are in
parallel, the instantaneous reactive power for the RL circuit would be 180° out of
phase with the instantaneous reactive power of the RC circuit. The net reactive
power is the difference between Q for the RL circuit and Q for the RC circuit. A
positive value is assigned to Q for an inductive load and a negative sign to Q for
a capacitive load.
Power-system engineers usually think of a capacitor as a generator of posi¬
tive reactive power rather than a load requiring negative reactive power. This
concept is very logical, for a capacitor drawing negative Q in parallel with an
inductive load reduces the Q which would otherwise have to be supplied by the
system to the inductive load. In other words, the capacitor supplies the Q
required by the inductive load. This is the same as considering a capacitor as a
device that delivers a lagging current rather than as a device which draws a
leading current, as shown in Fig. 2.6. An adjustable capacitor in parallel with an
inductive load, for instance, can be adjusted so that the leading current to the
capacitor is exactly equal in magnitude to the component of current in the
18 ELEMENTS OF POWER SYSTEM ANALYSIS
inductive load which is lagging the voltage by 90°. Thus, the resultant current is
in phase with the voltage. The inductive circuit still requires positive reactive
power, but the net reactive power is zero. It is for this reason that the power-
system engineer finds it convenient to consider the capacitor to be supplying this
reactive power to the inductive load. When the words positive and negative are
not used, positive reactive power is assumed.
If the phasor expressions for voltage and current are known, the calculation of
real and reactive power is accomplished conveniently in complex form. If the
voltage across and the current into a certain load or part of a circuit are ex¬
pressed by V — \ V\[cl_ and / = 17 the product of voltage times the conju¬
gate of the current is
Since a — /?, the phase angle between voltage and current, is 6 in the previous
equations,
S = P +jQ (2.23)
Reactive power Q will be positive when the phase angle a — between voltage
and current is positive, that is, when a > /I, which means that current is lagging
the voltage. Conversely, Q will be negative for /? > a, which indicates current
leading the voltage. This agrees with the selection of a positive sign for the
reactive power of an inductive circuit and a negative sign for the reactive power
of a capacitive circuit. To obtain the proper sign for Q, it is necessary to calcu¬
late S as VI*, rather than V*I, which would reverse the sign for Q.
parallel, the total P will be the sum of the average powers of the individual loads,
which should be plotted along the horizontal axis for a graphical analysis. For
an inductive load, Q will be drawn vertically upward since it is positive. A
capacitive load will have negative reactive power, and Q will be vertically down¬
ward. Figure 2.8 illustrates the power triangle composed of Pl5 Qu and Sj for a
lagging load having a phase angle 9X combined with the power triangle
composed of P2, Q2, and S2, which is for a capacitive load with a negative 02.
These two loads in parallel result in the triangle having sides Px + P2, Qi + Q2
and hypotenuse SR. The phase angle between voltage and current supplied to
the combined loads is 0R.
p.
I E
Figure 2.9 A dc representation of charging a battery if E and / are
both positive or both negative.
I I
Figure 2.10 An ac circuit represen¬
tation of an emf and current to
illustrate polarity marks.
O (a)
O
(6)
BASIC CONCEPTS 21
I ►
- I
--
Table 2.1
to be in phase rather than 180° out of phase with E, so that this component of
current would be always in the direction of the drop in potential. In this case P,
the real part of El* would be positive. Negative P here would indicate generated
power.
To consider the sign of Q, Fig. 2.11 is helpful. In Fig. 2.11a positive reactive
power equal to \I\2X is supplied to the inductance since inductance draws
positive Q. Then / lags E by 90°, and Q, the imaginary part of El*, is positive. In
Fig. 2.11h negative Q must be supplied to the capacitance of the circuit, or the
source with emf E is receiving positive Q from the capacitor. 1 leads E by 90°.
If the direction of the arrow in Fig. 2.11a is reversed, / will lead E by 90° and
the imaginary part of El* would be negative. The inductance could be viewed as
supplying negative Q rather than absorbing positive Q. Table 2.1 summarizes
these relationships.
Example 2.1 Two ideal voltage sources designated as machines 1 and 2 are
connected as shown in Fig. 2.12. If Ex = 100/0° V, E2 = 100/30° V, and
Z = 0 + j5 fi, determine (a) whether each machine is generating or consum¬
ing power and the amount, (b) whether each machine is receiving or supply¬
ing reactive power and the amount, and (c) the P and Q absorbed by the
impedance.
22 ELEMENTS OF POWER SYSTEM ANALYSIS
Solution
- E2 100 + y'O - (86.6 + ;50)
1 ~ Z ~ 75
Electric power systems are supplied by three-phase generators. Usually the gen¬
erators are supplying balanced three-phase loads, which means loads with identi¬
cal impedances in all three phases. Lighting loads and small motors are, of
course, single-phase, but distribution systems are designed so that overall the
phases are essentially balanced. Figure 2.13 shows a Y-connected generator with
neutral marked o supplying a balanced-Y load with neutral marked n. In discus¬
sing this circuit we shall assume that the impedances of the connections between
the terminals of the generator and the load, as well as the impedance of the
direct connection between o and n, are negligible.
The equivalent circuit of the three-phase generator consists of an emf in each
of the three phases, as indicated by circles on the diagram. Each emf is in series
BASIC CONCEPTS 23
with a resistance and inductive reactance composing the impedance Zg. Points
a', b', and c' are fictitious since the generated emf cannot be separated from the
impedance of each phase. The terminals of the machine are the points a, b, and c.
Some attention will be given to this equivalent circuit in a later chapter. In the
generator the emfs Ea o, Ebo, Ec o are equal in magnitude and displaced from
each other 120° in phase. If the magnitude of each is 100 V with Ea.0 as reference,
Figure 2.14 Phasor diagram of the emfs of the circuit shown in Fig. 2.13.
24 ELEMENTS OF POWER SYSTEM ANALYSIS
Since o and n are at the same potential, Vao, Vbo, and Vc0 are equal to Va^%, Vbn,
and Vcn, respectively, and the line currents (which are also the phase currents for
a Y connection) are
Eao Van
Kn =
Zg + ZR ~zR
Eb0
13
(2.25)
1
hn =
Zg + ZR
Ec'o Kn
Kn =
Zg + ZR ZR
Since Ea.0, Eb.0, and Ec 0 are equal in magnitude and 120° apart in phase and
the impedances seen by each of these emfs are identical, the currents will also be
equal in magnitude and displaced 120° from each other in phase. The same must
also be true of Van, Vbn, and Vcn. In this case we describe the voltages and
currents as balanced. Figure 2.15a shows three line currents of a balanced
system. In Fig. 2.15h the sum of these currents is shown to be a closed triangle. It
is obvious that their sum is zero. Therefore, /„ in the connection shown in
Fig. 2.13 between the neutrals of the generator and load must be zero. Then the
connection between n and o may have any impedance, or even be open, and n
and o will remain at the same potential.
If the load is not balanced, the sum of the currents will not be zero and a
current will flow between o and n. For the unbalanced condition, in the absence
of a connection of zero impedance, o and n will not be at the same potential.
The line-to-line voltages are K„, Vbc, and Vca. Tracing a path from a to b
through n in the circuit of Fig. 2.13 yields
Although Ea o and Van are not in phase, we could decide to use Van rather than
Ea.0 as reference in defining the voltages. Then Fig. 2.16a is the phasor diagram
of voltages to neutral, and Fig. 2.16b shows how Vab is found. The magnitude of
Kh is
\Vab\ =2\Van\ cos 30°
= v/3K.| (2.27)
Kt = V5 K,M (2.28)
The other line-to-line voltages are found in a similar manner, and Fig. 2.17
shows all the line-to-line and line-to-neutral voltages. The fact that the magni¬
tude of line-to-line voltages of a balanced three-phase circuit is always equal to
x/3 times the magnitude of the line-to-neutral voltages is very important.
Figure 2.18 is another way of displaying the line-to-line and line-to-neutral
voltages. The line-to-line voltage phasors are drawn to form a closed triangle
oriented to agree with the chosen reference, in this case Van. The vertices of the
triangle are labeled so that each phasor begins and ends at the vertices corre¬
sponding to the order of the subscripts of that phasor voltage. Line-to-neutral
V
Y ca V,
ao
voltage phasors are drawn to the center of the triangle. Once this phasor dia¬
gram is understood, it will be found to be the simplest way to determine the
various voltages.
The order in which the vertices a, b, and c of the triangle follow each other
when the triangle is rotated counterclockwise about n indicates the phase
sequence. We shall see later an example of the importance of phase sequence
when we discuss symmetrical components as a means of analyzing unbalanced
faults on power systems.
A separate current diagram can be drawn to relate each current properly
with respect to its phase voltage.
Balanced loads are often connected in A, as shown in Fig. 2.21. Here it is left to
the reader to show that the magnitude of a line current such as Ia is equal to
y/3 times the magnitude of a phase current such as Iab and that Ia lags Iab by
30° when the phase sequence is abc.
When solving balanced three-phase circuits it is never necessary to work with
the entire three-phase circuit diagram of Fig. 2.13. To solve the circuit a neutral
connection of zero impedance is assumed to be present and to carry the sum of the
three phase currents, which is zero, however, for balanced conditions. The circuit
is solved by applying Kirchhoff’s voltage law around a closed path which includes
one phase and neutral. Such a closed path is shown in Fig. 2.22. This circuit is
BASIC CONCEPTS 27
the single-phase equivalent of the circuit of Fig. 2.13. Calculations made for this
path are extended to the whole three-phase circuit by recalling that the currents in
the other two phases are equal in magnitude to the current of the phase calculated
and are displaced 120 and 240° in phase. It is immaterial whether the balanced
load, specified by its line-to-line voltage, total power, and power factor, is A- or
Y-connected since the A can always be replaced for purposes of calculaton by its
equivalent Y. The impedance of each phase of the equivalent Y will be one-third
the impedance of each phase of the A which it replaces.
Ia
127/- 30° A
__ V*
^3 x 2.67 = 4.62 kV
where 9p is the angle by which phase current lags the phase voltage, that is, the
angle of the impedance in each phase. If VL and IL are the magnitudes of
line-to-line voltage and line current, respectively.
Vp - ^3 and h ~ h (2.32)
Equations (2.33), (2.35), and (2.36) are the usual ones for calculating P, Q,
and | S | in balanced three-phase networks since the quantities usually known
are line-to-line voltage, line current, and the power factor, cos 9P. In speaking of
a three-phase system, balanced conditions are assumed unless described other¬
wise; and the terms voltage, current, and power, unless identified otherwise, are
understood to mean line-to-line voltage, line current, and total power of all three
phases.
If the load is connected A, the voltage across each impedance is the line-to-
line voltage and the current through each impedance is the magnitude of the line
current divided by ^/3, or
and substituting in this equation the values of Vp and Ip in Eq. (2.37) gives
which is identical to Eq. (2.33). It follows that Eqs. (2.35) and (2.36) are also
valid regardless of whether a particular load is connected A or Y.
30 ELEMENTS OF POWER SYSTEM ANALYSIS
Power transmission lines are operated at voltage levels where the kilovolt is the
most convenient unit to express voltage. Because of the large amount of power
transmitted kilowatts or megawatts and kilovoltamperes or megavoltamperes
are the common terms. However, these quantities as well as amperes and ohms
are often expressed as a percent or per unit of a base or reference value specified
for each. For instance, if a base voltage of 120 kV is chosen, voltages of 108, 120,
and 126 kV become 0.90, 1.00, and 1.05 per unit, or 90, 100, and 105%, respec¬
tively. The per-unit value of any quantity is defined as the ratio of the quantity
to its base value expressed as a decimal. The ratio in percent is 100 times the
value in per unit. Both the percent and per-unit methods of calculation are
simpler than the use of actual amperes, ohms, and volts. The per-unit method
has an advantage over the percent method because the product of two quantities
expressed in per unit is expressed in per unit itself, but the product of two
quantities expressed in percent must be divided by 100 to obtain the result in
percent.
Voltage, current, kilovoltamperes, and impedance are so related that selec¬
tion of base values for any two of them determines the base values of the
remaining two. If we specify the base values of current and voltage, base im¬
pedance and base kilovoltamperes can be determined. The base impedance is
that impedance which will have a voltage drop across it equal to the base
voltage when the current flowing in the impedance is equal to the base value of
the current. The base kilovoltamperes in single-phase systems is the product of
base voltage in kilovolts and base current in amperes. Usually base megavolt¬
amperes and base voltage in kilovolts are the quantities selected to specify the
base. For single-phase systems, or three-phase systems where the term current
refers to line current, where the term voltage refers to voltage to neutral, and
where the term kilovoltamperes refers to kilovoltamperes per phase, the follow¬
ing formulas relate the various quantities:
base kVA1(x
Base current, A = --—- (2.40)
base voltage, k\LN '
In these equations the subscripts 10 and LN denote “per phase” and “line-to-
neutral,” respectively, where the equations apply to three-phase circuits. If the
equations are used for a single-phase circuit, k\LN means the voltage across the
single-phase line, or line-to-ground voltage if one side is grounded.
Since three-phase circuits are solved as a single line with a neutral return,
the bases for quantities in the impedance diagram are kilovoltamperes per phase
and kilovolts from line to neutral. Data are usually given as total three-phase
kilovoltamperes or megavoltamperes and line-to-line kilovolts. Because of this
custom of specifying line-to-line voltage and total kilovoltamperes or megavolt¬
amperes, confusion may arise regarding the relation between the per-unit value
of line voltage and the per-unit value of phase voltage. Although a line voltage
may be specified as base, the voltage in the single-phase circuit required for the
solution is still the voltage to neutral. The base voltage to neutral is the base
voltage from line to line divided by y/3. Since this is also the ratio between
line-to-line and line-to-neutral voltages of a balanced three-phase system, the
per-unit value of a line-to-neutral voltage on the line-to-neutral voltage base is
equal to the per-unit value of the line-to-line voltage at the same point on the
line-to-line voltage base if the system is balanced. Similarly, the three-phase kilo¬
voltamperes is three times the kilovoltamperes per phase, and the three-phase
kilovoltamperes base is three times the base kilovoltamperes per phase. There¬
fore, the per-unit value of the three-phase kilovoltamperes on the three-phase kilo¬
voltampere base is identical to the per-unit value of the kilovoltamperes per phase
on the kilovoltampere-per-phase base.
A numerical example may serve to clarify the relationships discussed. For
instance, if
and
30,000
Base kVA^ = = 10,000 kVA
3
and
120
Base kVLAf = = 69.2 kV
75
For an actual line-to-line voltage of 108 kV, the line-to-neutral voltage is
108/^/i = 62.3 kV, and
„ 108 62.3
Per-unit voltage = — = 0.90
692
32 ELEMENTS OF POWER SYSTEM ANALYSIS
For total three-phase power of 18,000 kW, the power per phase is 6000 kW, and
18,000 6000
Per-unit power =—=^=0.6
base kVA3^
Base current, A = (2.47)
y/3 x base voltage, kVtL
Except for the subscripts, Eqs. (2.42) and (2.43) are identical to Eqs. (2.49) and
(2.50), respectively. Subscripts have been used in expressing these relations in
order to emphasize the distinction between working with three-phase quantities
and quantities per phase. We shall use these equations without the subscripts,
but we must (1) use line-to-line kilovolts with three-phase kilovoltamperes or
megavoltamperes and (2) use line-to-neutral kilovolts with kilovoltamperes or
megavoltamperes per phase. Equation (2.40) determines the base current for
single-phase systems or for three-phase systems where the bases are specified in
kilovoltamperes per phase and kilovolts to neutral. Equation (2.47) determines
the base current for three-phase systems where the bases are specified in total
kilovoltamperes for the three phases and in kilovolts from line to line.
Example 2.4 Find the solution of Example 2.3 by working in per unit on a
base of 4.4 kV, 127 A so that both voltage and current magnitudes will be
1.0 per unit. Current rather than kilovoltamperes is specified here since the
latter quantity does not enter the problem.
BASIC CONCEPTS 33
^
127
= 20.on
and therefore the magnitude of the load impedance is also 1.0 per unit. The
line impedance is
1.4/75°
= 0.07/75° per unit
20
= 1.0/0° + 0.07/45°
4400
VLN = 1.051 x —j=- = 2670 V, or 2.67 kV
When the problems to be solved are more complex and particularly when
transformers are involved the advantages of calculations in per unit will be
more apparent.
Example 2.5 The reactance of a generator designated X" is given as 0.25 per
unit based on the generator’s nameplate rating of 18 kV, 500 MVA. The
base for calculations is 20 kV, 100 MVA. Find X" on the new base.
or by converting the given value to ohms and dividing by the new base
impedance
0.25(182/500)
X" = 0.0405 per unit
202/100
PROBLEMS
2.1 If v = 141.4 sin (cot + 30°) V and i = 11.31 cos (cof — 30°) A, find for each (a) the maximum
value, (b) the rms value, and (c) the phasor expression in polar and rectangular form if voltage is the
reference. Is the circuit inductive or capacitive?
2.2 If the circuit of Prob. 2.1 consists of a purely resistive and a purely reactive element, find R and
X, (a) if the elements are in series and (b) if the elements are in parallel.
23 In a single-phase circuit Va = 120/45° V and Vb = 100 /-15° V with respect to a reference node
o. Find Vba in polar form.
2.4 A single-phase ac voltage of 240 V is applied to a series circuit whose impedance is 10 /60° Q.
Find R, X, P, Q, and the power factor of the circuit.
BASIC CONCEPTS 35
connected in parallel with the circuit of Prob. 2.4 and if this capacitor supplies
and Q supplied by the 240-V source, and find the resultant power factor,
inductive load draws 10 MW at 0.6 power factor lagging. Draw the power
ine the reactive power of a capacitor to be connected in parallel with the load to
or to 0.85.
induction motor is operating at a very light load during a large part of every day
jm the supply. A device is proposed to “ increase the efficiency ” of the motor,
'ation the device is placed in parallel with the unloaded motor and the current
iply drops to 8 A. When two of the devices are placed in parallel the current drops
le device will cause this drop in current? Discuss the advantages of the device. Is
e motor increased by the device? (Recall that an induction motor draws lagging
»le 2.1 if £j = 100/0° V and E2 = 120/30° V. Compare the results with Example
: conclusions about the effect of variation of the magnitude of E2 in this circuit.
;al impedances of 10 !—15° Q are Y-connected to balanced three-phase line vol-
>ecify all the line and phase voltages and the currents as phasors in polar form
ce for a phase sequence of abc.
d three-phase system the Y-connected impedances are 10/30° Cl. If Vbc = 416/^0° V,
r form.
Is of a three-phase supply are labeled a, b, and c. Between any pair a voltmeter
A resistor of 100 D and a capacitor of 100 Cl at the frequency of the supply are
connecteu m senes from a to b with the resistor connected to a. The point of connection of the
elements to each other is labeled n. Determine graphically the voltmeter reading between c and n if
phase sequence is abc and if phase sequence is acb.
2.15 Determine the current drawn from a three-phase 440-V line by a three-phase 15-hp motor
operating at full load, 90% efficiency, and 80% power factor lagging. Find the values of P and Q
drawn from the line.
2.16 If the impedance of each of the three lines connecting the motor of Prob. 2.15 to a bus is
0.3 + j'1.0 D, find the line-to-line voltage at the bus which supplies 440 V at the motor.
2.17 A balanced-A load consisting of pure resistances of 15 D per phase is in parallel with a
balanced-Y load having phase impedances of 8 + j6 D. Identical impedances of 2 + j5 D are in each
of the three lines connecting the combined loads to a 110-V three-phase supply. Find the current
drawn from the supply and the line voltage at the combined loads.
2.18 A three-phase load draws 250 kW at a power factor of 0.707 lagging from a 440-V line. In
parallel with this load is a three-phase capacitor bank which draws 60 kVA. Find the total current
and resultant power factor.
2.19 A three-phase motor draws 20 kVA at 0.707 power factor lagging from a 220-V source. Deter¬
mine the kilovoltampere rating of capacitors to make the combined power factor 0.90 lagging, and
determine the line current before and after the capacitors are added.
2.20 A coal mining “drag line” machine in an open-pit mine consumes 0.92 MVA at 0.8 power
factor lagging when it digs coal, and it generates (delivers to the electric system) 0.10 MVA at 0.5 power
factor leading when the loaded shovel swings away from the pit wall. At the end of the “dig” period,
the change in supply current magnitude can cause tripping of a protective relay which is constructed
of solid-state circuitry. Therefore it is desired to minimize the change in current magnitude. Consider
36 ELEMENTS OF POWER SYSTEM ANALYSIS
the placement of capacitors at the machine terminals and find the amount of capacitive correction
(in kvar) to eliminate the change in steady-state current magnitude. The machine is energized from a
36.5 kV, three-phase supply. Start the solution by letting Q be the total three-phase megavars of the
capacitors connected across the machine terminals, and write an expression for the magnitude of the
line current drawn by the machine in terms of Q for both the digging and generating operations.
2.21 A generator (which may be represented by an emf in series with an inductive reactance) is rated
500 MVA, 22 kV. Its Y-connected windings have a reactance of 1.1 per unit. Find the ohmic value of
the reactance of the windings.
2.22 The generator of Prob. 2.21 is in a circuit for which the bases are specified as 100 MVA, 20 kV.
Starting with the per-unit value given in Prob. 2.21, find the per-unit value of reactance of the
generator windings on the specified base.
2.23 Draw the single-phase equivalent circuit for the motor (an emf in series with inductive reactance
labeled Zm) and its connection to the voltage supply described in Probs. 2.15 and 2.16. Show on the
diagram the per-unit values of the line impedance and the voltage at the motor terminals on a base of
20 kVA, 440 V. Then using per-unit values find the supply voltage in per unit and convert the per-unit
value of the supply voltage to volts.
CHAPTER
THREE
SERIES IMPEDANCE OF
TRANSMISSION LINES
An electric transmission line has four parameters which affect its ability to fulfill
its function as part of a power system: resistance, inductance, capacitance, and
conductance. In this chapter we discuss the first two of these parameters, and we
shall consider capacitance in the next chapter.
Conductance between conductors or between conductors and the ground
accounts for the leakage current at the insulators of overhead lines and through
the insulation of cables. Since leakage at insulators of overhead lines is negli¬
gible, the conductance between conductors of an overhead line is assumed to be
zero.
When current flows in an electric circuit, we explain some of the properties
of the circuit by the magnetic and electric fields present. Figure 3.1 shows a
single-phase line and its associated magnetic and electric fields. The lines of
magnetic flux form closed loops linking the circuit, and the lines of electric flux
originate on the positive charges on one conductor and terminate on the nega¬
tive charges on the other conductor. Variation of the current in the conductors
causes a change in the number of lines of magnetic flux linking the circuit. Any
change in the flux linking a circuit induces a voltage in the circuit which is
proportional to the rate of change of flux. Inductance is the property of the
circuit that relates the voltage induced by changing flux to the rate of change of
current.
Capacitance exists between the conductors and is the charge on the conduc¬
tors per unit of potential difference between them.
37
38 ELEMENTS OF POWER SYSTEM ANALYSIS
The resistance and inductance uniformly distributed along the line form the
series impedance. The conductance and capacitance existing between conductors
of a single-phase line or from a conductor to neutral of a three-phase line form
the shunt admittance. Although the resistance, inductance, and capacitance are
distributed, the equivalent circuit of a line is made up of lumped parameters, as
we shall see when we discuss them.
In the early days of the transmission of electric power, conductors were usually
copper, but aluminum conductors have completely replaced copper because of
the much lower cost and lighter weight of an aluminum conductor compared
with a copper conductor of the same resistance. The fact that an aluminum
conductor has a larger diameter than a copper conductor of the same resistance
is also an advantage. With a larger diameter the lines of electric flux originating
on the conductor will be farther apart at the conductor surface for the same
voltage. This means a lower voltage gradient at the conductor surface and less
tendency to ionize the air around the conductor. Ionization produces the
undesirable effect called corona.
Symbols identifying different types of aluminum conductors are as follows:
AAC all-aluminum conductors
AAAC all-aluminum-alloy conductors
ACSR aluminum conductor, steel-reinforced
ACAR aluminum conductor, alloy-reinforced
High-pressure pipe-type cables are the most widely used cables for under¬
ground transmission at voltages from 69 to 550 kV. The paper-insulated cables
he in a steel pipe of diameter somewhat larger than necessary to contain the
insulated conductors which lie together along the bottom of the pipe.
Gas-insulated cables are available at voltages up to 138 kV. Research is
constantly conducted on other types of cables especially for voltage levels of 765
and 1100 kV. Manufacturers furnish details of construction for the various
cables.
In this book we shall devote our attention to overhead lines almost exclu¬
sively since underground transmission is usually restricted to large cities or
transmission under wide rivers, lakes, and bays. Underground lines cost at least
eight times as much as overhead lines and 20 times as much at the highest
voltage.
3.2 RESISTANCE
where the power is in watts and / is the rms current in the conductor in amperes.
The effective resistance is equal to the dc resistance of the conductor only if the
distribution of current throughout the conductor is uniform. We shall discuss
nonuniformity of current distribution briefly after reviewing some fundamental
concepts of dc resistance.
Direct-current resistance is given by the formula
Ro = j n (3.2)
where p = resistivity of conductor
/ = length
A = cross-sectional area
Any consistent set of units may be used. In power work in the United States, l is
usually given in feet, A in circular mils (cmil), and p in ohm-circular mils per
foot, sometimes called ohms per circular mil-foot. In SI units / is in meters, A in
square meters, and p in ohm-meters.f
A circular mil is the area of a circle having a diameter of 1 mil. A mil is
equal to 10"3 in. The cross-sectional area of a solid cylindrical conductor in
circular mils is equal to the square of the diameter of the conductor expressed in
mils. The number of circular mils multiplied by n/4 equals the number of square
t SI is the official designation for the International System of Units.
SERIES IMPEDANCE OF TRANSMISSION LINES 41
mils. Since manufacturers in the United States identify conductors by their cross-
sectional area in circular mils we must use this unit occasionally. The area
in square millimeters equals the area in circular mils multiplied by 5.067 x 10“ 4
The international standard of conductivity is that of annealed copper. Com¬
mercial hard-drawn copper wire has 97.3% and aluminum 61% of the conduc¬
tivity of standard annealed copper. At 20°C for hard-drawn copper p is
1.77 x 10“8Qm (10.66 Q-cmil/ft). For aluminum at 20°C p is 2.83 x
r8H m (17.00 Q-cmil/ft).
The dc resistance of stranded conductors is greater than the value computed
by Eq. (3.2) because spiraling of the strands makes them longer than the conduc¬
tor itself. For each mile of conductor the current in all strands except the one in
the center flows in more than a mile of wire. The increased resistance due to
spiraling is estimated as 1% for three-strand conductors and 2% for concen¬
trically stranded conductors.
The variation of resistance of metallic conductors with temperature is prac¬
tically linear over the normal range of operation. If temperature is plotted on the
vertical axis and resistance on the horizontal axis, as in Fig. 3.3, extension of the
straight-line portion of the graph provides a convenient method of correcting
resistance for changes in temperature. The point of intersection of the extended
line with the temperature axis at zero resistance is a constant of the material.
From the geometry of Fig. 3.3
R2_T+t2
(3.3)
Ri T+ u
where 1% and R2 are the resistances of the conductor at temperatures and t2,
respectively, in degrees Celsius and T is the constant determined from the graph.
Values of the constant T are as follows:
1234.5 for annealed copper of 100% conductivity
T— 241 for hard-drawn copper of 97.3% conductivity
I 228 for hard-drawn aluminum of 61% conductivity
42 ELEMENTS OF POWER SYSTEM ANALYSIS
The dc resistance of various types of conductors is easily found by Eq. (3.2), and
the increased resistance due to spiraling can be estimated. Temperature correc¬
tions are determined by Eq. (3.3). The increase in resistance caused by skin effect
can be calculated for round wires and tubes of solid material, and curves of R/R0
are available for these simple conductors.! This information is not necessary,
however, since manufacturers supply tables of electrical characteristics of their
conductors. Table A.l is an example of some of the data available.
„ 17.0 x 1000
Ro = TT73-x 102 = 0 01558 Q per 1000 ft
1,113 x 10J
t See The Aluminum Association, “Aluminum Electrical Conductor Handbook ” New York
1971.
SERIES IMPEDANCE OF TRANSMISSION LINES 43
228 4- 50
R0 = 0.01558 ——— = 0.01746 Q per 1000 ft
228 + 20
R 0.0956
R0 0.01746 x 5.280
Two fundamental equations serve to explain and define inductance. The first
equation relates induced voltage to the rate of change of flux linking a circuit.
The induced voltage is
where e is the induced voltage in volts and x is the number of flux linkages of the
circuit in weber-turns (Wbt). The number of weber-turns is the product of each
weber of flux and the number of turns of the circuit linked. For the two-wire line
of Fig. 3.1 each line of flux external to the conductors links the circuit only once.
If we had been considering a coil instead of the circuit of Fig. 3.1, most of the
lines of flux produced would have linked more than one turn of the coil. If some
of the flux links less than all the turns of a coil, the total flux linkages are
reduced. In terms of lines of flux, each line is multiplied by the number of turns it
links, and these products are added to obtain the total flux linkages.
When the current in a circuit is changing, its associated magnetic field
(which is described by the flux linkages) must be changing. If constant permeabi¬
lity is assumed for the medium in which the magnetic field is set up, the number
of flux linkages is directly proportional to the current, and therefore the induced
voltage is proportional to the rate of change of current. Thus our second fun¬
damental equation is
(3.5)
Equation (3.5) may be used where the permeability is not constant, but in such a
case the inductance is not a constant.
When Eqs. (3.4) and (3.5) are solved for L, the result is
(3.6)
44 ELEMENTS OF POWER SYSTEM ANALYSIS
If the flux linkages of the circuit vary linearly with current, which means that the
magnetic circuit has a constant permeability,
L =- H (3.7)
i
from which arises the definition of the self-inductance of an electric circuit as the
flux linkages of the circuit per unit of current. In terms of inductance the flux
linkages are
t = Li Wbt (3.8)
ip = LI Wbt (3.9)
Since tp and / are in phase, L is real, as is consistent with Eqs. (3.7) and (3.8).
The phasor voltage drop due to the flux linkages is
V = jcoLI V (3.10)
V=jco\p V (3.11)
Mutual inductance between two circuits is defined as the flux linkages of one
circuit due to the current in the second circuit per ampere of current in the
second circuit. If the current I2 produces ipl2 flux linkages with circuit 1, the
mutual inductance is
The phasor voltage drop in circuit 1 caused by the flux linkages of circuit 2 is
Vl=j(oM12I2=ja)\p12 V
Only flux lines external to the conductors are shown in Fig. 3.1. Some of the
magnetic field, however, exists inside the conductors, as we mentioned when
considering skin effect. The changing lines of flux inside the conductors also
contribute to the induced voltage of the circuit and therefore to the inductance.
The correct value of inductance due to internal flux can be computed as the ratio
of flux linkages to current by taking into account the fact that each line of
internal flux links only a fraction of the total current.
SERIES IMPEDANCE OF TRANSMISSION LINES 45
The dot between H and ds indicates that the value of H is the component of the
field intensity tangent to ds.
Let the field intensity at a distance x meters from the center of the conductor
be designated Hx. Since the field is symmetrical, Hx is constant at all points
equidistant from the center of the conductor. If the integration indicated in
Eq. (3.12) is performed around a circular path concentric with the conductor at
x meters from the center, Hx is constant over the path and tangent to it. Equa¬
tion (3.12) becomes
j> Hx ds = Ix (3.13)
2nxHx — Ix (3.14)
t Our work here applies equally to alternating and direct current. As shown, H and / are phasors
and represent sinusoidally alternating quantities. For simplicity the current / could be interpreted as
a direct current and H as a real number.
46 ELEMENTS OF POWER SYSTEM ANALYSIS
(3.15)
where / is the total current in the conductor. Then substituting Eq. (3.15) in
Eq. (3.14) and solving for Hx, we obtain
».-2At/m (316)
The flux linkages dip per meter of length, which are caused by the flux in the
tubular element, are the product of the flux per meter of length and the fraction
of the current linked. Thus
Integrating from the center of the conductor to its outside edge to find ipint, the
total flux linkages inside the conductor, we obtain
K, = j r IIIX3
r, 2nr4
dx
t In SI units the permeability of free space is n0 = 47t x 10 7 H/m, and the relative permeability
is fir = n/n0.
SERIES IMPEDANCE OF TRANSMISSION LINES 47
We have computed the inductance per unit length (henrys per meter) of a
round conductor attributed only to the flux inside the conductor. Hereafter, for
convenience, we shall refer to inductance per unit length simply as inductance, but
we must be careful to use the correct dimensional units.
The validity of computing the internal inductance of a solid round wire by
the method of partial flux linkages can be demonstrated by deriving the internal
inductance in an entirely different manner. Equating energy stored in the mag¬
netic field within the conductor per unit length at any instant to Lin( i2/2 and
solving for Lint will yield Eq. (3.22).
2nxHx = / (3.23)
Solving for Hx and multiplying by p yields the flux density Bx in the element, so
that
, _ P1 Wb/m2 (3.24)
2nx
The flux linkages dip per meter are numerically equal to the flux dcp, since flux
external to the conductor links all the current in the conductor once and only
once. The total flux linkages between P1 and P2 are obtained by integrating dip
from x = Dy to x = D2. We obtain
*Al2 —
. 1)2
pi ,
-— dx — — In —
pi , D2
Wbt/m (3.26)
Di
27TX 271 Dj
Before proceeding to the more general case of multiconductor lines and three-
phase lines, let us consider a simple two-wire line composed of solid round
conductors. Figure 3.6 shows a circuit having two conductors of radii rx and r2.
One conductor is the return circuit for the other. First consider only the flux
linkages of the circuit caused by the current in conductor 1. A line of flux set up
The total inductance of the circuit due to the current in conductor 1 only is
The expression for inductance may be put in a more concise form by factor¬
ing Eq. (3.31) and by noting that In e1/4 = 1/4, whence
L, = 2x 10-7|lne1/4 + ln (3.32)
e~ 1/4 is equal to 0.7788. Equation (3.34) gives the same value for inductance as
Eq. (3.31). The difference is that Eq. (3.34) omits the term to account for internal
flux but compensates for it by using an adjusted value for the radius of the
conductor. We should note carefully that Eq. (3.31) was derived for a solid
round conductor and that Eq. (3.34) was found by algebraic manipulation of
Eq. (3.31). Therefore, the multiplying factor of 0.7788 to adjust the radius in
order to account for internal flux applies only to solid round conductors. We
shall consider other conductors later.
Since the current in conductor 2 flows in the direction opposite to that in
conductor 1 (or is 180° out of phase with it), the flux linkages produced by
current in conductor 2 considered alone are in the same direction through the
circuit as those produced by current in conductor 1. The resulting flux for the
two conductors is determined by the sum of the mmfs of both conductors. For
constant permeability, however, the flux linkages (and likewise the inductances)
of the two conductors considered separately may be added.
By comparison with Eq. (3.34) the inductance due to current in conductor 2 is
L2 = 2 x 10 7 In ~ H/m (3.35)
r2
and for the complete circuit
A more general problem than that of the two-wire line is presented by one
conductor in a group of conductors where the sum of the currents in all the
conductors is zero. Such a group of conductors is shown in Fig. 3.7. Conductors
1, 2, 3, ..., n carry the phasor currents Iu I2,J3, /„. The distances of these
conductors from a remote point P are indicated on the figure as D1P, D2P, D3P,
..., DnP. Let us determine iJ/1PU the flux linkages of conductor 1 due to l[
including internal flux linkages but excluding all the flux beyond the point P.
SERIES IMPEDANCE OF TRANSMISSION LINES 51
Figure 3.7 Cross-sectional view of a group of n conductors carrying currents whose sum is zero.
Point P is remote from the conductors.
h
*i«-Ij + 2/, In ^) 10-7 (3.38)
IP
ij/iPi = 2 x 10 7/j In Wbt/m (3.39)
V1
The flux linkages tj/1P2 with conductor 1 due to I2, but excluding flux beyond
point P, is equal to the flux produced by I2 between the point P and conductor 1
(that is, within the limiting distances D2P and Dl2 from conductor 2), and so
D 2P
•Aip2 = 2 x 10 12 In (3.40)
D i:
The flux linkages iJ/1P with conductor 1 due to all the conductors in the group, but
excluding flux beyond point P, is
11 + f2 + /3 + ,,,4-/„ = 0
Substituting Eq. (3.43) in the second term containing /„ in Eq. (3.42) and recom¬
bining some logarithmic terms, we have
Now letting the point P move infinitely far away so that the set of terms contain¬
ing logarithms of ratios of distances from P becomes infinitesimal, since the
ratios of the distances approach 1, we obtain
By letting point P move infinitely far away we have included all the flux linkages
of conductor 1 in our derivation. Therefore, Eq. (3.45) expresses all the flux
linkages of conductor 1 in a group of conductors, provided the sum of all the
currents is zero. If the currents are alternating, they must be expressed as instan¬
taneous currents to obtain instantaneous flux linkages or as complex rms values
to obtain the rms value of flux linkages as a complex number.
o
.o
co
o
°'0 „o
o
Figure 3.8 Single-phase line consisting of two com¬
posite conductors.
V
Cond. X
^- v-'
Cond. y
•Aa = 2 x 10 7 - (In \ + In ~ + In + • ■ • + In
n\ ra Dab Dac DJ
Dividing Eq. (3.47) by the current I/n, we find that the inductance of filament a is
La + Lb + Lc + ■ ■ ■ + Ln
(3.50)
D av
La + Lb + Lc + • • • + L
(3.51)
Lx ~
Lx = 2 x 1(T7
x >/(A»a''Dgb'Dgc' ' ’ ' Dam){Dba'Dbb'Dbe' ' ' ' Abm) ' ' ' (Dna‘Dnb'Dnc' Dnm)
If we compare Eq. (3.53) with Eq. (3.34), the similarity between them is
apparent. The equation for the inductance of one conductor of a composite-
conductor line is obtained by substituting in Eq. (3.34) the GMD between con¬
ductors of the composite-conductor line for the distance between the solid
conductors of the single-conductor line and by substituting the GMR of the
composite conductor for the GMR (r') of the single conductor. Equation (3.53)
gives the inductance of one conductor of a single-phase line. The conductor is
composed of all the strands which are electrically in parallel. The inductance is
the total number of flux linkages of the composite conductor per unit of line
current. Equation (3.34) gives the inductance of one conductor of a single-phase
line for the special case where the conductor is a solid round wire.
SERIES IMPEDANCE OF TRANSMISSION LINES 55
■L — -(- Ly
Dad = Dbe = 9 m
o.
9m
o a
6m
6m
V
o C
Figure 3.9 Arrangement of conductors for
Example 3.2. Side X Side Y
56 ELEMENTS OF POWER SYSTEM ANALYSIS
Tables listing values of GMR are generally available for standard conductors
and provide other information for calculating inductive reactance as well as
shunt capacitive reactance and resistance. Since industry in the United States
continues to use units of inches, feet, and miles so do these tables. Therefore
some of our examples will use feet and miles, but others will use meters and
kilometers.
Inductive reactance rather than inductance is usually desired. The induc¬
tive reactance of one conductor of a single-phase two-conductor line is
Solution For this conductor, Table A.l lists Ds = 0.0217 ft. From Eq.
(3.55), for one conductor,
20
= 2.022 x lO"3 x 60 In
= 0.828 Q/mi
Since the conductors composing the two sides of the line are identical,
the inductive reactance of the line is
So far in our discussion we have considered only single-phase lines. The equa¬
tions we have developed are quite easily adapted, however, to the calculation of
the inductance of three-phase lines. Figure 3.10 shows the conductors of a three-
phase line spaced at the corners of an equilateral triangle. If we assume that
there is no neutral wire, or if we assume balanced three-phase phasor currents,
la + ib + jc = o. Equation (3.45) determines the flux linkages of conductor a:
and
La = 2 x 10“7 In ~ H/m , (3.59)
Equation (3.59) is the same in form as Eq. (3.34) for a single-phase line except
that Ds replaces r'. Because of symmetry, the inductances of conductors b and c
are the same as the inductance of conductor a. Since each phase consists of only
one conductor, Eq. (3.59) gives the inductance per phase of the three-phase line.
When the conductors of a three-phase line are not spaced equilaterally, the
problem of finding the inductance becomes more difficult. Then the flux linkages
and inductance of each phase are not the same. A different inductance in each
SERIES IMPEDANCE OF TRANSMISSION LINES 59
^, = 2xl0-’(/.lnT+/tlnA.+/tto
+ Ic In A.) Wbt/m (3.62)
60 ELEMENTS OF POWER SYSTEM ANALYSIS
2 x 10
(3Ia ln Ds + h ln Dl2D23D31 + Ic ^ Dl2D23D3 J (3 63)
With the restriction that Ia = —(Ib + Ic),
2 x 10- 1 1
•Aa =
3;“ln^-'“ln Dl2D23D33
'a “*
where
and Ds is the GMR of the conductor. Deq, the geometric mean of the three
distances of the unsymmetrical line, is the equivalent equilateral spacing, as may
be seen by a comparison of Eq. (3.65) with Eq. (3.59). We should note the
similarity between all the equations for the inductance of a conductor. If the
inductance is in henrys per meter, the factor 2 x 10“7 appears in all the equa¬
tions, and the denominator of the logarithmic term is always the GMR of
the conductor. The numerator is the distance between wires of a two-wire line,
\
the mutual GMD between sides of a composite-conductor single-phase line,
the distance between conductors of an equilaterally spaced line, or the equivalent
equilateral spacing of an unsymmetrical line.
'Jo-
24 8
L = 2 x 10 7 In - 13.00 x 10~7 H/m
Equation (3..55) may be used also, or, from Tables A.l and A.2,
= 0.399
and for 24.8 ft,
Xd = 0.389
At extra-high voltages (EHV), that is, voltages above 230 kV, corona with its
resultant power loss and particularly its interference with communications is
excessive if the circuit has only one conductor per phase. The high-voltage
gradient at the conductor in the EHV range is reduced considerably by having
two or more conductors per phase in close proximity compared with the spacing
between phases. Such a line is said to be composed of bundled conductors. The
bundle consists of two, three, or four conductors. The three-conductor bundle
usually has the conductors at the vertices of an equilateral triangle, and the
four-conductor bundle usually has its conductors at the corners of a square.
Figure 3.13 shows these arrangements. The current will not divide exactly
between the conductors of the bundle unless there is a transposition of the con¬
ductors within the bundle, but the difference is of no practical importance, and
the GMD method is accurate for calculations.
Reduced reactance is the other equally important advantage of bundling.
Increasing the number of conductors in a bundle reduces the effects of corona
and reduces the reactance. The reduction of reactance results from the increased
GMR of the bundle. The calculation of GMR is, of course, exactly the same as
that of a stranded conductor. Each conductor of a two-conductor bundle, for
instance, is treated as one strand of a two-strand conductor. If we let Dbs indicate
the GMR of a bundled conductor and Ds the GMR of the individual conductors
composing the bundle, we find, referring to Fig. 3.13,
—Q
©—r-©
Figure 3.13 Bundle arrangements.
62 ELEMENTS OF POWER SYSTEM ANALYSIS
Solution From Table A.l Ds = 0.0466 ft, and we multiply feet by 0.3048 to
convert to meters.
Deq = ^8 x 8 x 16 = 10.08 m
„ 0.365 x 160
X =-- = 0.049 per unit
HH
bO Ob’
Figure 3.14 Spacing of
8m <- 8m
conductors of a bundled-
conductor line. d = 45 elm
SERIES IMPEDANCE OF TRANSMISSION LINES 63
°G-18'-G~—r
10'
°i-2r-
10'
Ds = 0.0229 ft
The GMR for the parallel-circuit line is found after first obtaining the GMR
values for the three positions. The actual distance from a to a' is
^O2 4- 182 = 26.9 ft. Then GMR of each phase is
Therefore
Although computer programs are usually available or written rather easily for
calculating inductance of all kinds of lines, some understanding of the develop¬
ment of the equations used is rewarding from the standpoint of appreciating the
effect of variables in designing a line. However, tables like A.l and A.2 make the
calculations quite simple except for parallel-circuit lines. Table A.l also lists
resistance.
The important equation for inductance per phase of single-circuit three-
phase lines is given here for convenience
or
Both Deq and Ds must be in the same units, usually feet. If the line has one
conductor per phase, Ds is found directly from tables. For bundled conductors
Dbs, as defined in Sec. 3.13, is substituted for Ds. For both single- and bundled-
conductor lines
Deq=^DahDbcDca (3.73)
For bundled-conductor lines Dab, Dbc, and Dca are distances between the centers
of the bundles of phases a, b, and c.
For lines with one conductor per phase it is convenient to determine XL by
adding Xa for the conductor as found in tables like A.l to Xd as found in Table
A.2 corresponding to Deq.
Inductance and inductive reactance of parallel-circuit lines are calculated by
following the procedure of Example 3.6.
PROBLEMS
3.1 The all-aluminum conductor identified by the code word Bluebell is composed of 37 strands of
diameter 0.1672 in. Tables of characteristics of all-aluminum conductors list an area of 1,033,500 cmil
for this conductor. Are these values consistent with each other? Find the area in square millimeters.
3.2 Determine the dc resistance in ohms per km of Bluebell at 20°C by Eq. (3.2) and the information
in Prob. 3.1, and check the result against the value listed in tables of 0.01678 D per 1000 ft. Compute
the dc resistance in ohms per kilometer at 50°C and compare the result with the ac 60-Hz resistance
of 0.1024 Q/mi listed in tables for this conductor at 50°C. Explain any difference in values.
33 An all-aluminum conductor is composed of 37 strands each having a diameter of 0.333 cm.
Compute the dc resistance in ohms per kilometer at 75°C.
3.4 A single-phase 60-Hz power line is supported on a horizontal crossarm. Spacing between con¬
ductors is 2.5 m. A telephone line is supported on a horizontal crossarm 1.8 m directly below the
power line with a spacing of 1.0 m between the centers of its conductors. Find the mutual inductance
between the power and telephone circuits and the 60-Hz voltage per kilometer induced in the
telephone line if the current in the power line is 150 A.
3.5 If the power and telephone lines described in Prob. 3.4 are in the same horizontal plane and the
distance between the nearest conductors of the two lines is 18 m, find the mutual inductance between
the circuits and the voltage per mile induced in the telephone line for 150 A in the power line.
3.6 The conductor of a single-phase 60-Hz line is a solid round aluminum wire having a diameter of
0.412 cm. The conductor spacing is 3 m. Determine the inductance of the line in millihenrys per mile.
How much of the inductance is due to internal flux linkages? Assume skin effect is negligible.
3.7 Find the GMR of a three-strand conductor in terms of r of an individual strand.
66 ELEMENTS OF POWER SYSTEM ANALYSIS
3.8 Find the GMR of each of the unconventional conductors shown in Fig. 3.16 in terms of the
radius r of an individual strand.
3.9 The distance between conductors of a single-phase line is 10 ft. Each conductor is composed of
seven equal strands. The diameter of each strand is 0.1 in. Show that Ds for the conductor is 2.177
times the radius of each strand. Find the inductance of the line in millihenrys per mile.
3.10 Find the inductive reactance of ACSR Rail in ohms per kilometer at 1-m spacing.
3.11 Which conductor listed in Table A.l has an inductive reactance at 7-ft spacing of 0.651 Q/mi?
3.12 A three-phase line is designed with equilateral spacing of 16 ft. It is decided to build the line
with horizontal spacing (D13 = 2Dl2 = 2D23). The conductors are transposed. What should be the
spacing between adjacent conductors in order to obtain the same inductance as in the original
design ?
3.13 A three-phase 60-Hz transmission line has its conductors arranged in a triangular formation so
that two of the distances between conductors are 25 ft and the third distance is 42 ft. The conductors
are ACSR Osprey. Determine the inductance and inductive reactance per phase per mile.
3.14 A three-phase 60-Hz line has flat horizontal spacing. The conductors have a GMR of 0.0133 m
with 10 m between adjacent conductors. Determine the inductive reactance per phase in ohms per
kilometer. What is the name of this conductor?
3.15 For short transmission lines if resistance is neglected the maximum power which can be trans¬
mitted per phase is equal to
where Vs and VR are the line-to-neutral voltages at the sending and receiving ends of the line and X is
the inductive reactance of the line. This relationship will become apparent in the study of Chap. 5. If
the magnitudes of Vs and VR are held constant and if the cost of a conductor is proportional to its
cross-sectional area, find the conductor in Table A.l which has the maximum power-handling
capacity per cost of conductor.
3.16 A three-phase underground distribution line is operated at 23 kV.' The three conductors are
insulated with 0.5 cm solid black polyethylene insulation laid flat and side by side directly in a dirt trench.
The conductor is circular in cross section and has 33 strands of aluminum. The diameter of the
conductor is 1.46 cm. The manufacturer gives the GMR as 0.561 cm and the cross section of the
conductor as 1.267 cm2. The thermal rating of the line buried in normal soil whose maximum
temperature is 30°C is 350 A. Find the dc and ac resistance at 50°C and the inductive reactance in
ohms per kilometer. To decide whether to consider skin effect in calculating resistance determine the
percent skin effect at 50°C in the ACSR conductor of size nearest that of the underground conductor.
Note that the series impedance of the distribution line is dominated by R rather than XL because of
the very low inductance due to the close spacing of the conductors.
3.17 The single-phase power line of Prob. 3.4 is replaced by a three-phase line on a horizontal
crossarm in the same position as that of the original single-phase line. Spacing of the conductors of
the power line is D13 = 2Dl2 = 2D23, and equivalent equilateral spacing is 3 m. The telephone line
remains in the position described in Prob. 3.4. If the current in the power line is 150 A, find the
voltage per kilometer induced in the telephone line. Discuss the phase relation of the induced voltage
with respect to the power-line current.
SERIES IMPEDANCE OF TRANSMISSION LINES 67
3.18 A 60-Hz three-phase line composed of one ACSR Bluejay conductor per phase has flat horizon¬
tal spacing of 11 m between adjacent conductors. Compare the inductive reactance in ohms per
kilometer per phase of this line with that of a line using a two-conductor bundle of ACSR 26/7
conductors having the same total cross-cectional area of aluminum as the single-conductor line and
11 m spacing measured from the center of the bundles. The spacing between conductors in the
bundle is 40 cm.
3.19 Calculate the inductive reactance in ohms per kilometer of a bundled 60-Hz three-phase line
having three ACSR Rail conductors per bundle with 45 cm between conductors of the bundle. The
spacing between bundle centers is 9, 9, and 18 m.
3.20 Six conductors of ACSR Drake constitute a 60-Hz double-circuit three-phase line arranged as
shown in Fig. 3.15. The vertical spacing, however, is 14 ft; the longer horizontal distance is 32 ft; and
the shorter horizontal distances are 25 ft. Find the inductance per phase per mile and the inductive
reactance in ohms per mile.
CHAPTER
FOUR
( \['\( [ [ \\( I OF TRANSMISSION LINES
68
CAPACITANCE OF TRANSMISSION LINES 69
charging current of the line. Charging current flows in a transmission line even
when it is open-circuited. It affects the voltage drop along the line as well as
the efficiency and power factor of the line and the stability of the system of which
the line is a part.
the surface is equal to the flux leaving the conductor per meter of length divided
by the area of the surface in an axial length of 1 m. The electric flux density is
where q is the charge on the conductor in coulombs per meter of length and x is
the distance in meters from the conductor to the point where the electric flux
density is computed. The electric field intensity, or the negative of the potential
gradient, is equal to the electric flux density divided by the permittivity! of the
medium. Therefore, the electric field intensity is
(4.2)
The potential difference between two points in volts is numerically equal to the
work in joules per coulomb necessary to move a coulomb of charge between the
two points. Electric field intensity is a measure of the force on a charge in
the field. Electric field intensity in volts per meter is equal to the force in newtons
per coulomb on a coulomb of charge at the point considered. Between two
points the line integral of the force in newtons acting on a coulomb of positive
charge is the work done in moving the charge from the point of lower potential
to the point of higher potential and is numerically equal to the potential differ¬
ence between the two points.
Consider a long straight wire carrying a positive charge of q C/m, as shown
in Fig. 4.2. Points Pi and P2 are located at distances and D2 meters from the
center of the wire. The positive charge on the wire will exert a repelling force on
a positive charge placed in the field. For this reason and because D2 in this case
is greater than Du work must be done on a positive charge to move it from P2
to Pl5 and Pi is at a higher potential than P2. The difference in potential is the
amount of work done per coulomb of charge moved. On the other hand, if the
coulomb moves from Pi to P2, it expends energy, and the amount of work, or
energy, in newton-meters is the voltage drop from Px to P2. The potential
difference is independent of the path followed. The simplest way to compute the
voltage drop between the two points is to compute the voltage between the
t In SI units the permittivity of free space k0 is 8.85 x 10“12 F/m. Relative permittivity kr is the
ratio of the actual permittivity k of a material to the permittivity of free space. Thus, kr = k/k0. For
dry air kr is 1.00054 and is assumed equal to 1.0 in calculations for overhead lines.
CAPACITANCE OF TRANSMISSION LINES 71
. 02 . D2
vl2 = I $ dx = I dx =
q , °2
(4.3)
•D1 jD1
2nkx Ink Dj
where q is the instantaneous charge on the wire in coulombs per meter of length.
Note that the voltage drop between two points, as given by Eq. (4.3), may be
positive or negative depending on whether the charge causing the potential
difference is positive or negative and on whether the voltage drop is computed
from a point near the conductor to a point farther away, or vice versa. The sign
of q may be either positive or negative, and the logarithmic term is either positive
or negative depending on whether D2 is greater or less than Dt.
Capacitance between the two conductors of a two-wire line was defined as the
charge on the conductors per unit of potential difference between them. In the
form of an equation, capacitance per unit length of the line is
where q is the charge on the line in coulombs per meter and v is the potential
difference between the conductors in volts. Hereafter, for convenience, we shall
refer to capacitance per unit length as capacitance and indicate the correct
dimensions for equations derived. The capacitance between two conductors can
be found by substituting in Eq. (4.4) the expression for v in terms of q from
72 ELEMENTS OF POWER SYSTEM ANALYSIS
r.
D
Figure 4.3 Cross section of a parallel-wire line.
Eq. (4.3). The voltage vab between the two conductors of the two-wire line shown
in Fig. 4.3 can be found by determining the potential difference between the two
conductors of the line, first by computing the voltage drop due to the charge qa
on conductor a and then by computing the voltage drop due to the charge qb on
conductor b. By the principle of superposition the voltage drop from conductor
a to conductor b due to the charges on both conductors is the sum of the voltage
drops caused by each charge alone.
Consider the charge qa on conductor a, and assume that conductor b is
uncharged and merely an equipotential surface in the electric field created by the
charge on a. The equipotential surface of conductor b and the equipotential
surfaces due to the charge on a are shown in Fig. 4.4. The distortion of the
equipotential surfaces near conductor b is caused by the fact that conductor b is
also an equipotential surface. Equation (4.3) was derived by assuming all the
equipotential surfaces due to a uniform charge on a round conductor to be
cylindrical and concentric with the conductor. Such is actually true for the case
under discussion except in the region near conductor b. The potential of conduc¬
tor b is that of the equipotential surface intersecting b. Therefore, in determining
vab a path may be followed from conductor a through a region of undistorted
equipotential surfaces to the equipotential surface intersecting conductor b.
Then, moving along the equipotential surface to b gives no further change in
voltage. This path of integration is indicated in Fig. 4.4 together with the direct
path. Of course, the potential difference is the same regardless of the path over
which the integration of the field intensity is taken. By following the path
through the undistorted region, we see that the distances corresponding to D2
and Dj of Eq. (4.3) are D and ra, respectively, in determining vab due to qa.
Similarly, in determining vab due to qb, the distances corresponding to D2 and
of Eq. (4.3) are rb and D, respectively. Converting to phasor notation (qa and qb
become complex numbers), we obtain
(4.5)
(4.6)
CAPACITANCE OF TRANSMISSION LINES 73
K& = In — (4.7)
2nk rna r,
'b
_ 'la _ Ink
^ ab T/
Kb
( t\2
^ (D2/rar„)
F/m (4.8)
If ra = rb =
nk
F/m (4.9)
ab~ In (D/r)
o —k-
Cab
Figure 4.5 Relationship between the concepts of line-to-line capacitance and line-to-neutral
capacitance.
1 2.862
xc = x 109 In — Q ■ m to neutral (4.11)
2njT ~J~ r
CAPACITANCE OF TRANSMISSION LINES 75
Since C in Eq. (4.11) is in farads per meter, the proper units for Xc must be
ohm-meters. We should also note that Eq. (4.11) expresses the reactance from
line to neutral for 1 m of line. Since capacitive reactance is in parallel along the
line, Xc in ohm-meters must be divided by the length of the line in meters to
obtain the capacitive reactance in ohms to neutral for the entire length of the
line.
When Eq. (4.11) is divided by 1609 to convert to ohm-miles, we obtain
1.779 D
Xc = x 106 In Q - mi to neutral (412)
Table A.l lists the outside diameters of the most widely used sizes of ACSR.
If D and r in Eq. (4.12) are in feet, capacitive reactance at 1-ft spacing X'a is the
first term and capacitive reactance spacing factor X’d is the second term when the
equation is expanded as follows:
1 779 1 1 779
Xc = —- x 106 In - + —— x 106 In D Q mi to neutral (4.13)
/ r f
Table A.l includes values of X'a for common sizes of ACSR, and similar tables
are readily available for other types and sizes of conductors. Table A.3 lists
values of X'd.
Example 4.1 Find the capacitive susceptance per mile of a single-phase line
operating at 60 Hz. The conductor is Partridge, and spacing is 20 ft between
centers.
0.642
r = 0.0268 ft
2 x 12
A; = 0.1074 Mfi-mi
V (4.14)
Equation (4.3) enables us to include the effect of qc since uniform charge distri¬
bution over the surface of a conductor is equivalent to a concentrated charge at
the center of the conductor. Therefore, due only to the charge qc,
which is zero since qc is equidistant from a and b. However to show that we are
considering all three charges we can write
(4.15)
Similarly
1 / , D , D r\
V = (la In - + qb In - + qc In - (4.16)
* 2nk
D r
V A- V
r ab ' r ac
— 2qa In - + (qb + qc) In - (417)
2nk
In deriving these equations we have assumed that ground is far enough away to
have negligible effect. Since the voltages are assumed to be sinusoidal and ex¬
pressed as phasors, the charges are sinusoidal and expressed as phasors. If there
are no other charges in the vicinity, the sum of the charges on the three conduc¬
tors is zero and we can substitute — qa in Eq. (4.17) for qb + qc and obtain
3 <7
Kb + Kr — •in® (418)
2nk
Figure 4.7 is the phasor diagram of voltages. From this figure we obtain the
following relations between the line voltages Vab and Vac and the voltage Van from
line a to the neutral of the three-phase circuit:
V.
r ab +
' V
r ac = 3Van
*■' r
(421)
D
V (422)
r
78 ELEMENTS OF POWER SYSTEM ANALYSIS
Since capacitance to neutral is the ratio of the charge on a conductor <to the
voltage between that conductor and neutral,
For a three-phase line, the charging current is found by multiplying the voltage
to neutral by the capacitive susceptance to neutral. This gives the charging
current per phase and is in accord with the calculation of balanced three-phase
circuits on the basis of a single phase with neutral return. The phasor charging
current in phase a is
/chg =ju>CnVan A/mi (4.25)
Since the rms voltage varies along the line, the charging current is not the same
everywhere. Often the voltage used to obtain a value for charging current is the
normal voltage for which the line is designed, such as 220 or 500 kV, which is
probably not the actual voltage at either a generating station or a load.
When the conductors of a three-phase line are not equilaterally spaced, the
problem of calculating capacitance becomes more difficult. In the usual un¬
transposed line the capacitances of each phase to neutral are unequal. In a
transposed line the average capacitance to neutral of any phase for the complete
transposition cycle is the same as the average capacitance to neutral of any other
phase, since each phase conductor occupies the same position as every other
phase conductor over an equal distance along the transposition cycle. The
dissymmetry of the untransposed line is slight for the usual configuration, and
capacitance calculations are carried out as though all lines were transposed.
For the line shown in Fig. 4.8 three equations are found for Vab for the three
different parts of the transposition cycle. With phase a in position 1, b in
position 2, and c in position 3,
K„ = 2nk 1 ^12 ,
qa In- + qb In
r
r
D i;
+ qc In
^23)
dJ
V (4.26)
CAPACITANCE OF TRANSMISSION LINES 79
V (4.27)
V (4.28)
Equations (4.26) to (4.28) are similar to Eqs. (3.60) to (3.62) for the flux
linkages of one conductor of a transposed line. However, in the equations for
flux linkages we noted that the current in any phase was the same in every part
of the transposition cycle. In Eqs. (4.26) to (4.28), if we disregard the voltage
drop along the line, the voltage to neutral of a phase in one part of a transposi¬
tion cycle is equal to the voltage to neutral of that phase in any part of the cycle.
Hence, the voltage between any two conductors is the same in all parts of the
transposition cycle. It follows that the charge on a conductor must be different
when the position of the conductor changes with respect to other conductors. A
treatment of Eqs. (4.26) to (4.28) analogous to that of Eqs. (3.60) to (3.62) is not
rigorous.
The rigorous solution for capacitance is too involved to be practical except
perhaps for flat spacing with equal distances between adjacent conductors. With
the usual spacings and conductors, sufficient accuracy is obtained by assuming
that the charge per unit length on a conductor is the same in every part of the
transposition cycle. When the above assumption is made with regard to charge,
the voltage between a pair of conductors is different for each part of the transpo¬
sition cycle. Then an average value of voltage between the conductors can be
found, and the capacitance calculated from the average voltage. We obtain the
average voltage by adding Eqs. (4.26), (4.27), and (4.28) and dividing the result
by 3. The average voltage between conductors a and b, based on the assumption
of the same charge on a conductor regardless of its position in the transposition
cycle, is
D 12^23^31
Dl2D23 d31
V (4.29)
r
80 ELEMENTS OF POWER SYSTEM ANALYSIS
where
Dn=^Dl2D13D>t (4.30)
v (4'31>
= + V (4.32)
3V
** r an
v (4.33)
and
Qa_ 2nk
F/m to neutral (4.34)
Vm ln iD'Jr)
Equation (4.34) for capacitance to neutral of a transposed three-phase line corre¬
sponds to Eq. (3.65) for the inductance per phase of a similar line. In finding
capacitive reactance to neutral corresponding to C„ the reactance can be split
into components of capacitive reactance to neutral at 1-ft spacing X’a and capaci¬
tive reactance spacing factor X'd as defined by Eq. (4.13).
Example 4.2 Find the capacitance and the capacitive reactance for 1 mi of
the line described in Example 3.4. If the length of the line is 175 mi and the
normal operating voltage is 220 kV, find capacitive reactance to neutral for
the entire length of the line, the charging current per mile, and the total
charging megavolt-amperes.
Solution
1.108
r = 0.0462 ft
2 x 12
Deq 24.8 ft
2n x 8.85 x 10 12
Cn = 8.8466 x 10“12 F/m
ln (24.8/0.0462)
1012
Xc = 0.1864 x 106 Q- mi
2;r x 60 x 8.8466 x 1609
CAPACITANCE OF TRANSMISSION LINES 81
or from tables
0.1865 x 106
Capacitive reactance = = 1066 Q to neutral
175
220,000
/chg = 27r60 x 8.8466 x 10“12 x 1609 = 0.681 A/mi
73
or 0.681 x 175 = 119 A for the line. Reactive power is Q = ^3 x 220 x
119 x 10 3 = 45.3 Mvar. This amount of reactive power absorbed by the
distributed capacitance is negative in keeping with the convention discussed
in Chap. 2. In other words, positive reactive power is being generated by the
distributed capacitance of the line.
Earth affects the capacitance of a transmission line because its presence alters the
electric field of the line. If we assume that the earth is a perfect conductor in the
form of a horizontal plane of infinite extent, we realize that the electric field of
charged conductors above the earth is not the same as it would be if the equi-
potential surface of the earth were not present. The electric field of the charged
conductors is forced to conform to the presence of the earth’s surface. The
assumption of a flat, equipotential surface is, of course, limited by the irregular¬
ity of terrain and the type of surface of the earth. The assumption enables us,
however, to understand the effect of a conducting earth on capacitance
calculations.
Consider a circuit consisting of a single overhead conductor with a return
path through the earth. In charging the conductor, charges come from the earth
to reside on the conductor, and a potential difference exists between the conduc¬
tor and earth. The earth has a charge equal in magnitude to that on the conduc¬
tor but of opposite sign. Electric flux from the charges on the conductor to the
charges on the earth is perpendicular to the earth’s equipotential surface, since
the surface is assumed to be a perfect conductor. Let us imagine a fictitious
conductor of the same size and shape as the overhead conductor lying directly
below the original conductor at a distance equal to twice the distance of the
conductor above the plane of the ground. The fictitious conductor is below
the surface of the earth by a distance equal to the distance of the overhead
conductor above the earth. If the earth is removed and a charge equal and
opposite to that on the overhead conductor is assumed on the fictitious conduc¬
tor, the plane midway between the original conductor and the fictitious con¬
ductor is an equipotential surface and occupies the same position as the
82 ELEMENTS OF POWER SYSTEM ANALYSIS
equipotential surface of the earth. The electric flux between the overhead con¬
ductor and this equipotential surface is the same as that which existed between
the conductor and the earth. Thus, for purposes of calculation of capacitance,
the earth may be replaced by a fictitious charged conductor below the surface of
the earth by a distance equal to that of the overhead conductor above the earth.
Such a conductor has a charge equal in magnitude and opposite in sign to that of
the original conductor and is called the image conductor.
The method of calculating capacitance by replacing the earth by the image
of an overhead conductor can be extended to more than one conductor. If we
locate an image conductor for each overhead conductor, the flux between the
original conductors and their images is perpendicular to the plane which re¬
places the earth, and that plane is an equipotential surface. The flux above the
plane is the same as it is when the earth is present instead of the image
conductors.
To apply the method of images to the calculation of capacitance for a
three-phase line, refer to Fig. 4.9. We shall assume that the line is transposed and
that conductors a, b, and c carry the charges qa, qb, and qc and occupy positions
1, 2, and 3, respectively, in the first part of the transposition cycle. The plane of
the earth is shown, and below it are the conductors with the image charges —qa,
— qb, and —qc. Equations for the three parts of the transposition cycle can be
written for the voltage drop from conductor a to conductor b as determined by
the three charged conductors and their images. With conductor a in position 1, b
in position 2, and c in position 3,
1 H12)
Vat qfl|ln - In + qb In
2nk HJ
D23
+ <Jc (4.35)
d3 H31J
Similar equations for Vab are written for the other parts of the transposition
cycle. Accepting the approximately correct assumption of constant charge per
unit length of each conductor throughout the transposition cycle allows us to
obtain an average value of the phasor Vat . The equation for the average value of
the phasor Vac is found in a similar manner, and 3Van is obtained by adding the
average values of Kt and Vac. Knowing that the sum of the charges is zero, we
then find
2nk
F/m to neutral (4.36)
In (£>e,A)-ln
Comparison of Eqs. (4.34) and (4.36) shows that the effect of the earth is
to increase the capacitance of a line. To account for the earth the denominator
of Eq. (4.34) must have subtracted from it the term
log
If the conductors are high above ground compared with the distances between
them, the diagonal distances in the numerator of the correction term are nearly
equal to the vertical distances in the denominator and the term is very small.
This is the usual case, and the effect of ground is generally neglected for three-
phase lines except for calculations by symmetrical components when the sum of
the three line currents is not zero.
Figure 4.10 shows a bundled-conductor line for which we can write an equation
for the voltage from conductor a to conductor b as we did in deriving Eq. (4.26)
except that now we must consider the charges on all six individual conductors.
The conductors of any one bundle are in parallel, and we can assume the charge
per bundle divides equally between the conductors of the bundle since the separ¬
ation between bundles is usually more than 15 times the spacing between the
conductors of the bundle. Also, since D12 is much greater than d, we can use Dl2
84 ELEMENTS OF POWER SYSTEM ANALYSIS
£>31
in place of the distances D12 - d and D12 + d and make ather similar substitu¬
tions of bundle separation distances instead of using the more exact expressions
that occur in finding Vab. The difference due to this approximation cannot be
detected in the final result for usual spacings even when the calculation is carried
to five or six significant figures.
If the charge on phase a is qa, conductors a and a' each have the charge
qa/2; similar division of charge is assumed for phases b and c. Then
D 23
+ In + In (4.37)
+ t(ln^ D + "(,n§77 D 31
b'
The letters under each logarithmic term indicate the conductor whose charge is
accounted for by that therm. Combining terms gives
2nk
F/m to neutral (4.40)
In (DJDb/)
CAPACITANCE OF TRANSMISSION LINES 85
1.382 x 0.3048
= 0.01755 m
2 x 12
„ 2n x 8.85 x 10~12
Cm = . _ = 11.754 x 10-12 F/m
In (10.08/0.0889)
1012 x KT3
Xr = = 0.2257 x 106 Q - km per phase to neutral
2tt60 x 11.754
/v _ 0.2257
2257 x 106
= 0.1403 x 106 Q-mi per phase to neutral
\Xc ~ 1.609
Example 4.4 Find the 60-Hz capacitive susceptance to neutral per mile per
phase of the double-circuit line described in Example 3.6
86 ELEMENTS OF POWER SYSTEM ANALYSIS
r= = 0.0283 ft
2 x 12
DpsC = (^26.9 x 0.0283^/21 x 0.0283^26.9 x 0.0283)1/3
= ^0.0283 (26.9 x 21 x 26.9)1/6 = 0.837 ft
2n x 8.85 x 10"12
= 18.807 x 10"12 F/m
C" In (16.1/0.837)
4.9 SUMMARY
The similarity between inductance and capacitance calculations has been em¬
phasized throughout our discussions. As in inductance calculations, computer
programs are recommended if a large number of calculations of capacitance are
required. Tables like A.l and A.3 make the calculations quite simple, however,
except for parallel-circuit lines.
The important equation for capacitance to neutral for a single-circuit, three-
phase line is
2nk
cn = - n /n F/m to neutral (4.44)
In Deq/DsC
DsC is the outside radius r of the conductor for a line consisting of one conductor
per phase. For overhead lines k is 8.85 x 10"12 since kr for air is 1.0. Capacitive
reactance in ohm-meters is l/2nfC where C is in farads/meter. So at 60 Hz
\
Deq — y/DabDbcDca
CAPACITANCE OF TRANSMISSION LINES 87
For bundled-conductor lines Dab, Dbc, and Dca are distances between the centers
of the bundles of phases a, b, and c.
For lines with one conductor per phase it is convenient to determine Xc by
adding X'a for the conductor as found in tables like A.l to X'd as found in Table
A.3 corresponding to Deq.
Capacitance and capacitive reactance of parallel-circuit lines are found by
following the procedure of Example 4.4.
PROBLEMS
4.1 A three-phase transmission line has flat horizontal spacing with 2 m between adjacent conduc¬
tors. At a certain instant the charge on one of the outside conductors is 60 pC/km, and the charge on
the center conductor and on the other outside conductor is —30 /rC/km. The radius of each conduc¬
tor is 0.8 cm. Neglect the effect of ground, and find the voltage drop between the two identically
charged conductors at the instant specified.
4.2 The 60-Hz capacitive reactance to neutral of a solid conductor, which is one conductor of a
three-phase line with an equivalent equilateral spacing of 5 ft, is 196.1 k 12-mi. What value of reac¬
tance would be specified in a table listing the capacitive reactance in ohm-miles to neutral of the
conductor at 1-ft spacing for 25 Hz? What is the cross-sectional area of the conductor in circular
mils?
4.3 Derive an equation for the capacitance to neutral in farads per meter of a single-phase line,
taking into account the effect of ground. Use the same nomenclature as in the equation derived for
the capacitance of a three-phase line where the effect of ground is represented by image charges.
4.4 Calculate the capacitance to neutral in farads per meter of a single-phase line composed of two
single-strand conductors each having a diameter of 0.229 in. The conductors are 10 ft apart and 25 ft
above ground. Compare the values obtained by Eq. (4.10) and by the equation derived in Prob. 4.3.
4.5 A three-phase 60-Hz transmission line has its conductors arranged in a triangular formation so
that two of the distances between conductors are 25 ft and the third is 42 ft. The conductors are
ACSR Osprey. Determine the capacitance to neutral in microfarads per mile and the capacitive
reactance to neutral in ohm-miles. If the line is 150 mi long, find the capacitance to neutral and
capacitive reactance of the line.
4.6 A three-phase 60-Hz line has flat horizontal spacing. The conductors have an outside diameter of
3.28 cm with 12 m between conductors. Determine the capacitive reactance to neutral in ohm-
meters and the capacitive reactance of the line in ohms if its length is 125 mi.
4.7 A 60-Hz three-phase line composed of one ACSR Bluejay conductor per phase has flat horizon¬
tal spacing of 11 m between adjacent conductors. Compare the capacitive reactance in ohm-
kilometers per phase of this line with that of a line using a two-conductor bundle of ACSR 26/7
conductors having the same total cross-sectional area of aluminum as the single-conductor line and
the 11-m spacing measured between bundles. The spacing between conductors in the bundle is
40 cm.
4.8 Calculate the capacitive reactance in ohm-kilometers of a bundled 60-Hz three-phase line having
three ACSR Rail conductors per bundle with 45 cm between conductors of the bundle. The spacing
between bundle centers is 9, 9, and 18 m.
4.9 Six conductors of ACSR Drake constitute a 60-Hz double-circuit three-phase line arranged as
shown in Fig. 3.15. The vertical spacing, however, is 14 ft; the longer horizontal distance is 32 ft; and
the shorter horizontal distances are 25 ft. Find the capacitive reactance to neutral in ohm-miles and
the charging current per mile per phase and per conductor at 138 kV.
CHAPTER
FIVE
CURRENT AND VOLTAGE RELATIONS
ON A TRANSMISSION LINE
88
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 89
Figure 5.1 A 500-kV transmission line. Conductors are 76/19 ACSR with aluminum cross section of
2,515,000 cmil. Spacing between phases is 30 ft 3 in and the two conductors per bundle are 18 in
apart. (Courtesy Carolina Power and Light Company.)
90 ELEMENTS OF POWER SYSTEM ANALYSIS
In the modern power system data from all over the system are being fed
continuously into on-line computers for control purposes and for information.
Load-flow studies performed by a computer readily supply answers to questions
concerning the effect of switching lines into and out of the system or of changes
in line parameters. Equations derived in this chapter remain important, however,
in developing an overall understanding of what is occurring on a system and in
calculating efficiency of transmission, losses, and limits of power flow over a line
for both steady-state and transient conditions.
The general equations relating voltage and current on a transmission line recog¬
nize the fact that all four of the parameters of a transmission line discussed in the
two preceding chapters are uniformly distributed along the line. We shall derive
these general equations later but first we shall use lumped parameters which give
good accuracy for short lines and for lines of medium length. If an overhead line
is classified as short, shunt capacitance is so small that it can be omitted entirely
with little loss of accuracy, and we need to consider only the series resistance R
and the series inductance L for the total length of the line. Figure 5.2 shows a
Y-connected generator supplying a balanced-Y load through a short transmis¬
sion line. R and L are shown as concentrated, or lumped, parameters. It makes
no difference, as far as measurements at the ends of the line are concerned,
whether the parameters are lumped or uniformly distributed if the shunt admit¬
tance is neglected since the current is the same throughout the line in that case.
The generator is represented by an impedance connected in series with the
generated emf of each phase.
A medium-length line can be represented sufficiently well by R and L as
lumped parameters, as shown in Fig. 5.3, with half the capacitance to neutral of
the line lumped at each end of the equivalent circuit. Shunt conductance G, as
mentioned previously, is usually neglected in overhead power transmission lines
when calculating voltage and current.
Insofar as the handling of capacitance is concerned, open-wire 60-Hz lines
R L
Figure 5.2 Generator supplying a balanced-Y load through a transmission line where the resistance
R and inductance L are values for the entire length of the line. Line capacitance is omitted.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 91
Figure 5.3 Single-phase equivalent of the circuit of Fig. 5.2 with the addition of capacitance
to neutral for the entire length of the line divided between the two ends of the line.
less than about 80 km (50 mi) long are short lines. Medium-length lines are
roughly between 80 km (50 mi) and 240 km (150 mi) long. Lines longer than
240 km (150 mi) require calculations in terms of distributed constants if a high
degree of accuracy is required, although for some purposes a lumped-parameter
representation can be used for lines up to 320 km (200 mi) long.
Normally, transmission lines are operated with balanced three-phase loads.
Although the lines are not spaced equilaterally and not transposed, the resulting
dissymmetry is slight and the phases are considered to be balanced.
In order to distinguish between the total series impedance of a line and the
series impedance per unit length, the following nomenclature is adopted:
The equivalent circuit of a short transmission line is shown in Fig. 5.4, where Is
and IR are the sending- and receiving-end currents and Vs ahd VR are the
sending- and receiving-end line-to-neutral voltages.
Figure 5.4 Equivalent circuit of a short transmission line where the resistance R and inductance L
are values for the entire length of the line.
92 ELEMENTS OF POWER SYSTEM ANALYSIS
The circuit is solved as a simple series ac circuit. Since there are no-shunt
arms, the current is the same at the sending and receiving ends of the line and
IS = IR (5-1)
The voltage at the sending end is
Figure 5.5 Phasor diagrams of a short transmission line. All diagrams are drawn for the same
magnitudes of and IR.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 93
circuit. The magnitudes of the voltage drops IR R and IR XL for a short line have
been exaggerated with respect to VR in drawing the phasor diagrams in order to
illustrate the point more clearly. The relation between power factor and regula¬
tion for longer lines is similar to that for short lines but is not visualized so
easily.
To derive Is we note that the current in the shunt capacitance at the sending end
is Vs Y/2, which added to the current in the series arm gives
Corresponding equations can be derived for the nominal T which has all of the
shunt admittance of the line lumped in the shunt arm of the T and the series
impedance divided equally between the two series arms.
94 ELEMENTS OF POWER SYSTEM ANALYSIS
where
(5.10)
These ABCD constants are sometimes called the generalized circuit constants of
the transmission line. In general they are complex numbers. A and D are dimen¬
sionless and equal each other if the line is the same when viewed from either end.
The dimensions of B and C are ohms and mhos, respectively. The constants
apply to linear, passive, and bilateral four-terminal networks having two pairs of
terminals.
A physical meaning is easily assigned to the constants. By letting IR be zero
in Eq. (5.8) we see that A is the ratio VS/VR at no load. Similarly, B is the ratio
VS/IR when the receiving end is short-circuited. The constant A is useful in
computing regulation. If VR FL is the receiving-end voltage at full load for a
sending-end voltage of Vs, Eq. (5.3) becomes
ABCD constants are not widely used. They are introduced here because they
simplify working with the equations. Appendix Table A.6 lists ABCD constants
for various networks and combinations of networks.
The exact solution of any transmission line and the one required for a high
degree of accuracy in calculating 60-Hz lines more than approximately 150 mi
long must consider the fact that the parameters of the lines are not lumped but
are distributed uniformly throughout the length of the line.
Figure 5.7 shows one phase and the neutral connection of a three-phase line.
Lumped parameters are not shown because we are ready to consider the solu¬
tion of the line with the impedance and admittance uniformly distributed. The
same diagram also represents a single-phase line if the series impedance of the
line is the loop series impedance of the single-phase line instead of the series
impedance per phase of the three-phase line and if the shunt admittance is
the line-to-line shunt admittance of the single-phase line instead of the shunt
admittance to neutral of the three-phase line.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 95
Figure 5.7 Schematic diagram of a transmission line showing one phase and the neutral return.
Nomenclature for the line and the elemental length are indicated.
Let us consider a very small element in the line and calculate the difference
in voltage and the difference in current between the ends of the element. We shall
let x be the distance measured from the receiving end of the line to the small
element of line, and we shall let the length of the element be Ax. Then z Ax is the
series impedance of the elemental length of the line, and y Ax is its shunt admit¬
tance. The voltage to neutral at the end of the element toward the load is V, and
V is the complex expression of the rms voltage, whose magnitude and phase vary
with distance along the line. The voltage at the end of the element toward the
generator is V + AV. The rise in voltage over the elemental length of line in the
direction of increasing x is AV, which is the voltage at the end toward
the generator minus the voltage at the end toward the load. The rise in voltage
in the direction of increasing x is also the product of the current in the element
flowing opposite to the direction of increasing x and the impedance of
the element, or Iz Ax. Thus
AV = Iz Ax (5.12)
or
(5.13)
dV
~ = Iz 1/ (5.14)
Similarly, the current flowing out of the element toward the load is /. The
magnitude and phase of the current / vary with distance along the line because
of the distributed shunt admittance along the line. The current flowing into the
element from the generator is / + A/. The current entering the element from
the generator end is higher than the current flowing away from the element in
the direction of the load by the amount A/. This difference in current is the
current Vy Ax flowing in the shunt admittance of the element. Thus
A / = Vy Ax
96 ELEMENTS OF POWER SYSTEM ANALYSIS
and pursuing steps similar to those of Eqs. (5.12) and (5.13) we obtain
dl
= Vy (5.15)
dx
Let us differentiate Eqs. (5.14) and (5.15) with respect to x, and obtain
d2V dl
= z- (5.16)
dx2 dx
and
d2I dV
= y~i7.
(5.17)
dx2 dx
If we substitute the values of dl/dx and dV/dx from Eqs. (5.15) and (5.14) in
Eqs. (5.16) and (5.17), respectively, we obtain
d2V
= yzV (5.18)
dx2
and
(5.19)
Now we have an equation (5.18) in which the only variables are V and x, and
another equation (5.19) in which the only variables are I and x. The solutions of
Eqs. (5.18) and (5.19) for V and /, respectively, must be expressions which when
differentiated twice with respect to x yield the original expression times the
constant yz. For instance, the solution for V when differentiated twice with
respect to x must yield yzV. This suggests an exponential form of solution.
Assume that the solution of Eq. (5.18) is+
d2V
= yz[Ax exp {JJz x) + A2 exp (-y/yz x)] (5.21)
dx‘
which is yz times the assumed solution for V. Therefore, Eq. (5.20) is the solution
of Eq. (5.18). When we substitute in Eq. (5.14) the value for V given by
Eq. (5.20), we obtain,
t The term exp (s/yz x) in Eq. (5.20) and similar equatons is equivalent to e raised to the power
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 97
VR + IRZC VR~IrZc
Ax = and A2 —
Then, substituting the values found for Ax and A2 in Eqs. (5.20) and (5.22) and
letting y = y/yz, we obtain
Vr + IrZc ^yx
VR-1RZC yx
V = + (5.23)
Vr/Zc + IR £yx _
VR/ZC - 7# yx
/ - -
(5.24)
where Zc = xfzjy and is called the characteristic impedance of the line, and
y = sfyz and is called the propagation constant.
Equations (5.23) and (5.24) give the rms values of V and / and their phase
angles at any specified point along the line in terms of the distance x from the
receiving end to the specified point, provided VR, IR, and the parameters of the
line are known.
Both y and Zc are complex quantities. The real part of the propagation constant
y is called the attenuation constant a and is measured in nepers per unit length.
The quadrature part of y is called the phase constant /? and is measured in
radians per unit length. Thus
The properties of exx and ejpx help to explain the variation of the phasor values
of voltage and current as a function of distance along the line. The term eax
changes in magnitude as x changes, but eJfix, which is identical to cos /?x +
98 ELEMENTS OF POWER SYSTEM ANALYSIS
j sin fix, always has a magnitude of 1 and causes a shift in phase of rad per unit
length of line.
The first term in Eq. (5.26), [(VR + IR Zc)/2]eaV/i*, increases in magnitude
and advances in phase as distance from the receiving end increases. Conversely,
as progress along the line from the sending end toward the receiving end is
considered, the term diminishes in magnitude and is retarded in phase. This is
the characteristic of a traveling wave and is similar to the behavior of a wave in
water, which varies in magnitude with time at any point, whereas its phase is
retarded and its maximum value diminishes with distance from the origin. The
variation in instantaneous value is not expressed in the term but is understood
since 1^ and IR are phasors. The first term in Eq. (5.26) is called the incident
voltage.
The second term in Eq. (5.26), [(F* — IR Zc)/2]e~xxe~jPx, diminishes in mag¬
nitude and is retarded in phase from the receiving end toward the sending end. It
is called the reflected voltage. At any point along the line the voltage is the sum
of the component incident and reflected voltages at that point.
Since the equation for current is similar to the equation for voltage, the
current may be considered to be composed of incident and reflected currents.
If a line is terminated in its characteristic impedance Zc, the receiving-end
voltage VR is equal to IR Zc and there is no reflected wave of either voltage or
current, as may be seen by substituting IRZC for VR in Eqs. (5.26) and (5.27). A
line terminated in its characteristic impedance is called a flat line or an infinite
line. The latter term arises from the fact that a line of infinite length cannot have
a reflected wave. Usually power lines are not terminated in their characteristic
impedance, but communication lines are frequently so terminated in order to
eliminate the reflected wave. A typical value of Zc is 400 Q for a single-circuit
overhead line and 200 fl for two circuits in parallel. The phase angle of Zc is
usually between 0 and —15°. Bundled-conductor lines have lower values of Zc
since such lines have lower L and higher C than lines with a single conductor per
phase.
In power-system work, characteristic impedance is sometimes called surge
impedance. The term surge impedance, however, is usually reserved for the
special case of a lossless line. If a line is lossless, its resistance and conductance
are zero and the characteristic impedance reduces to yjL/C, a pure resistance.
When dealing with high frequencies or with surges due to lightning, losses are
often neglected and the surge impedance becomes important. Surge-impedance
loading (SIL) of a line is the power delivered by a line to a purely resistive load
equal to its surge impedance. When so loaded, the line supplies a current of
where \VL\ is the line-to-line voltage at the load. Since the load is pure
resistance,
W
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 99
MW (5.28)
2 = % (5.29)
The incident and reflected waves of voltage are seldom found when calculating
the voltage of a power line. The reason for discussing the voltage and current of
a line in terms of the incident and reflected components is that such an analysis
is helpful in obtaining a fuller understanding of some of the phenomena of
transmission lines. A more convenient form of the equations for computing
current and voltage of a power line is found by introducing hyperbolic functions.
Hyperbolic functions are defined in exponential form as follows:
sinh 6 = £ £ (5.31)
2
4. E~e
cosh 6 = ——— (5.32)
By rearranging Eqs. (5.23) and (5.24) and substituting hyperbolic functions for
the exponential terms, a new set of equations is found. The new equations, giving
voltage and current anywhere along the line, are
and
and
y
Is = IR cosh yl + -y sinh yl (5.36)
Zc
From examination of these equations we see that the generalized circuit con¬
stants for a long line are
sinh yl
A = cosh yl C = (5.37)
B = Zc sinh yl D = cosh yl
Equations (5.35) and (5.36) can be solved for VR and IR in terms of Fs and Is
to give
and
y
IR = Is cosh yl — ~ sinh yl (5 39)
\
For balanced three-phase lines the current in the above equations is the line
current, and the voltage is the line-to-neutral voltage, that is, the line voltage
divided by ^/3. In order to solve the equations, the hyperbolic functions must be
evaluated. Since yl is usually complex, the hyperbolic functions are also complex
and cannot be found directly from ordinary tables or electronic calculators.
Before the widespread use of the digital computer, various charts, some of them
especially adapted to the values usually encountered in transmission-line calcula¬
tions, were frequently used to evaluate hyperbolic functions of complex argu¬
ments. Now the digital computer provides the usual means of incorporating such
functions into our calculations.
For solving an occasional problem without resorting to a computer or
charts there are several choices. The following equations give the expansions of
hyperbolic sines and cosines of complex arguments in terms of circular and
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 101
Equations (5.40) and (5.41) make possible the computation of hyperbolic func¬
tions of complex arguments. The correct mathematical unit for pi is the radian,
and the radian is the unit found for (11 by computing the quadrature component
of yl. Equations (5.40) and (5.41) can be verified by substituting in them the
exponential forms of the hyperbolic functions and the similar exponential forms
of the circular functions.
Another convenient method of evaluating a hyperbolic function is to expand
it in a power series. Expansion by Maclaurin’s series yields
q2 q4 q6
cosh 0 = 1 + — + — + — + "• (5.42)
and
q3 q5 al
sinh0 = 9 + - +- + - +- (5.43)
The series converge rapidly for the values of yl usually found for power lines, and
sufficient accuracy may be found by evaluating only the first few terms.
A third method of evaluating complex hyperbolic functions is suggested by
Eqs. (5.31) and (5.32). Substituting a + jfi for 6, we obtain
£ag/p + g “e
cosh (a: + jfi) - = |(ea /£_ + e~a (5.44)
and
Solution Feet and miles rather than meters and kilometers are chosen for
the calculations in order to use Tables A.1-A.3.
/79.04° + 90°
yl = l = 230^0.8431 x 5.105 x 10'
0.8431 /79.04° - 90
= 406.4/-5.48° Q
z* = y 5.105 x 10 -6
215,000
VR =- =— = 124,130/(F V to neutral
1
V3
125,000,000
ID = = 335.7/0_° A
R ■sfe x 215,000
= 332.27/26.33°
Vs
VR =
cosh yl
So the voltage regulation is
137.85/0.8904 - 124.13
100 = 24.7%
124.13
0.4750
= 0.002065 rad/mi
230
. 2n 2n
A = 7=OS02065 = 3043 ™
Example 5.2 Solve for the sending-end voltage and current found in Exam¬
ple 5.1 using per-unit calculations.
(215)2
Base impedance = = 370 Q
125
125,000
Base current = = 335.7 A
s/3 x 215
So
406.4/-5.48c
Zc = 1.098 /-5.48° per unit
370
215 _ 215/^3
1.0 per unit
215 “215/71
104 ELEMENTS OF POWER SYSTEM ANALYSIS
337.5/0°
IR — = l.o/cr
337.5
If the power factor had been less than 100%, IR would have been greater
than 1.0 and would have been at an angle determined by the power factor.
By Eq. (5.35)
Vs = 1.0 x 0.8904 + 1.0 x 1.098 /-5.48° x 0.4596/84.94°
equivalent-;! circuit Z' and the shunt arms Y'/2 to distinguish them from the
arms of the nominal-^: circuit. Equation (5.5) gives the sending-end voltage of a
symmetrical-^ circuit in terms of its series and shunt arms and the voltage and
current at the receiving end. By substituting Z' and Y'/2 for Z and Y/2 in
Eq. (5.5), we obtain the sending-end voltage of our equivalent circuit in terms of
its series and shunt arms and the voltage and current at the receiving end:
IZ'Y' \
Vs=[~2T + 1)F« + Z7« (5-46)
For our circuit to be equivalent to the long transmission line, the coefficients of
VR and IR in Eq. (5.46) must be identical, respectively, to the coefficients of VR
and IR in Eq. (5.35). Equating the coefficients of IR in the two equations yields
sinh yl
Z' = sinh yl = zl
/
sinh yl
z' = z (5.48)
yl
where Z is equal to zl, the total series impedance of the line. The term (sinh yl)/yl
is the factor by which the series impedance of the nominal n must be multiplied
to convert the nominal n to the equivalent n. For small values of yl, sinh yl and
yl are almost identical, and this fact shows that the nominal n represents the
medium-length transmission line quite accurately, insofar as the series arm is
concerned.
To investigate the shunt arms of the equivalent-^: circuit, we equate the
coefficients of VR in Eqs. (5.35) and (5.46) and obtain
+ 1 = cosh yl (5.49)
Y’ZC sinh yl
+ 1 = cosh yl (5.50)
Y~
and
Y' 1 cosh yl — 1
(5.51)
2 Zc sinh yl
Another form of the expression for the shunt admittance of the equivalent circuit
can be found by substituting in Eq. (5.51) the identity
, yl cosh yl - 1
(5.52)
,a"h 2 = sinh yl
The identity can be verified by substituting the exponential forms of Eqs. (5.31)
106 ELEMENTS OF POWER SYSTEM ANALYSIS
Z' = Zc sinh 71 =
Y_'
2
Y tanh 11/2
Figure 5.8 Equivalent-^ circuit of
a transmission line. I 2 11/2
and (5.32) for the hyperbolic functions and by recalling that tanh 9 =
sinh 0/cosh 9. Now
(5.53)
r Y tanh (yl/2)
(5.54)
~2~2 yl/2.
where Y is equal to yl, the total shunt admittance of the line. Equation (5.54)
shows the correction factor used to convert the admittance of the shunt arms of
the nominal n to that of the equivalent n. Since tanh {yl/2) and yl/2 are very
nearly equal for small values of yl, the nominal n represents the medium-length
transmission line quite accurately, for we have seen previously that the correc¬
tion factor for the series arm is negligible for medium-length lines. The
equivalent-7r circuit is shown in Fig. 5.8. An equivalent-T circuit can also be
found for a transmission line.
Example 5.3 Find the equivalent-7r circuit for the line described in Exam¬
ple 5.1 and compare it with the nominal n.
Solution Since sinh yl and cosh yl are already known from Example 5.1,
Eqs. (5.47) and (5.51) will be used.
For this line the impedance of the series arm of the nominal n exceeds
that of the equivalent n by 3.8%. The conductance of the shunt arms of the
nominal n is 2.0% less than that of the equivalent n. So we conclude that the
nominal n may represent long lines sufficiently well if a high degree of
accuracy is not required.
Although power flow at any point along a transmission line can always be found
if the voltage, current, and power factor are known or can be calculated, very
interesting equations for power can be derived in terms of A BCD constants. Of
course, the equations apply to any two-terminal-pair network. Repeating
Eq. (5.8) and solving for the receiving-end current IR yields
A = MlZs. b=\b\h
(5.57)
,R |B| |B| te—L
Then the complex power VR /£ at the receiving end is
p +i0 - lK>NK«l
Pr+iQr |B|
,»
IS_S
* \a\-\vr\2
|fl| l»_* (5.58)
V3T -%.*
Figure 5.9 Phasors of Eq. 5.58 plotted in the Figure 5.10 Power diagram obtained by
complex plane, with magnitudes and angles shifting the origin of the coordinate axes of
as indicated. Fig. 5.9.
at an angle 0R with the horizontal axis. As expected, the real and imaginary
components of | PR + jQR | are
Pr=\Vr\-\Ir\cosOr (5.61)
and
Example 5.4 In order to show the relative changes in the B constant with
respect to the change of the A, C, and D constants of a line when series
compensation is applied, find the constants for the line of Example 5.1 un¬
compensated and for a series compensation factor of 70%.
A = D = cosh yl = 0.8904^.34°
B = Z' = 186.78/79.46° Q
^ sinh yl 0.4596/^4.94°
Zc ~ 406.4/-5.48°
= 0.001131/90.42° U
The series compensation alters only the series arm of the equivalent-?:
circuit. The new series arm impedance is also the generalized constant B. So
= 0.001180/90.41° 13
Lh„ = (Bc-BL)|P|
= Bcln(l-|) (564)
Example 5.5 Find the voltage regulation of the line of Example 5.1 when a
shunt inductor is connected at the receiving end of the line during no-load
conditions if the reactor compensates for 70% of the total shunt admittance
of the line.
The equation in Table A.6 for combining two networks in series tells us that
for the line and inductor
137.85/1.0411 - 124.13
6.67%
124.13
which is a considerable reduction from the value of 24.7% for the regulation
of the uncompensated line.
The transient overvoltages which occur on a power system are either of external
origin (for example, a lightning discharge) or are generated internally by
switching operations. In general the transients on transmission systems are caused
by any sudden change in the operating condition or configuration of the systems.
Lightning is always a potential hazard to power system equipment, but
switching operations can also cause equipment damage. At voltages up to about
230 kV the insulation level of the lines and equipment is dictated by the need to
protect against lightning. On systems where voltages are above 230 kV but less
than 700 kV switching operations as well as lightning are potentially damaging
to insulation. At voltages above 700 kV switching surges are the main determinant
of the level of insulation.
Underground cables are, of course, immune to direct lightning strokes and
can be protected against transients originating on overhead lines. However, for
economic and technical reasons overhead lines at transmission voltage levels
prevail except under unusual circumstances and for short distances such as
under a river.
Overhead lines can be protected from direct strokes of lightning in most
cases by one or more wires at ground potential strung above the power-line
conductors as mentioned in the description of Fig. 5.1. These protecting wires,
called ground wires, are connected to ground through the transmission towers
supporting the line. The zone of protection is usually considered to be 30° on
each side of vertical beneath a ground wire; that is, the power lines must come
within this 60° sector. The ground wires, rather than the power line, receive the
lightning strokes in most cases.
114 ELEMENTS OF POWER SYSTEM ANALYSIS
i(RAx) + (LAx)-^
dt
and we can write
t For further study see A. Greenwood, Electrical Transients in Power Systems, Wiley-Interscience,
New York, 1971.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 115
The negative sign is necessary because v + (dv/dx) Ax must be less than v for
positive values of i and di/dt. Similarly
diA
|gu + C Ax (5.66)
Jt)
We can divide through both Eqs. (5.65) and (5.66) by Ax, and since we are
considering only a lossless line, R and G will equal zero to give
8v _ , di
(5.67)
dx dt
and
— = -r— (5.68)
dx dt
Now we can eliminate i by taking the partial derivative of both terms in
Eq. (5.67) with respect to x and the partial derivative of both terms in Eq. (5.68)
with respect to t. This procedure yields d2i/dxdt in both resulting equations, and
eliminating this second partial derivative of i between the two equations yields
1 d2v d2v
(5.69)
LC dx2 dt2
Equation (5.69) is the so-called traveling-wave equation of a lossless trans¬
mission line. A solution of the equation is a function of (x — vt), and the voltage
is expressed by
The function is undefined but must be single valued. The constant v must have
the dimensions of meters per second if x is in meters and t is in seconds. We can
verify this solution by substituting this expression for v into Eq. (5.69) to determine
v. First we make the change in variable
u = x — vt (5.71)
and write
v(x, t)=f(u) (5.72)
Then
dv df(u) du
dt du dt
d/(“) (5.73)
du
and
d2v = 2 d2f(u)
(5.74)
dt2 du2
116 ELEMENTS OF POWER SYSTEM ANALYSIS
Similarly we obtain
82v d2f(u)
(5.75)
= 8u2
Substituting these second partial derivatives of v into Eq. (5.69) yields
J_ 82f{u) = d2f{u)
(5.76)
LC du2 du2
and we see that Eq. (5.70) is a solution of Eq. (5.69) if
1
v = —,- (5.77)
s/lc
x — vt = a constant
dx 1
~r = v = .— m/s
dt yic
for I and C in H/m and F/m, respectively. Thus the voltage wave travels in the
positive x direction with the velocity v.
A function of (x + vt) can also be shown to be a solution of Eq. (5.69) and,
by similar reasoning, can be properly interpreted as a wave traveling in the
negative x direction. The general solution of Eq. (5.69) is thus
Figure 5.13 A voltage wave which is a function of (x - vt) is shown for values of t equal to q and t2.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 117
r=jhcMx-n) <5-8i>
r = -7hcMx+n) (5.83)
(5.84)
(5.85)
We shall now consider what happens when a voltage is first applied to the
sending end of a transmission line which is terminated in an impedance ZR. For
our very simple treatment we will consider ZR to be a pure resistance. If the
termination is other than a pure resistance we would resort to Laplace trans¬
forms. The transforms of voltage, current, and impedance would be functions of
the Laplace transform variable s.
When the switch is closed applying a voltage to a line a wave of voltage v+
118 ELEMENTS OF POWER SYSTEM ANALYSIS
accompanied by a wave of current i+ starts to travel along the line. The radio of
the voltage vR at the end of the line at any time to the current iR at the end of the
line must equal the terminating resistance ZR. Therefore the arrival of v+ and i+
at the receiving end where their values are vR and iR must result in backward
traveling or reflected waves v~ and i~ having values vR and iR at the receiving
end such that
VR _ VR T VR _ 7
— .+ . — ^R
(5.86)
lR lR + lR
where vR and iR are the reflected waves v and i measured at the receiving end.
If we let Zc = yjL/C we find from Eqs. (5.84) and (5.85)
a =$ (5-87)
and
ir —
(5.88)
Zr zc
Vr Vr (5.89)
ZR + Zc
The voltage vR at the receiving end is evidently the same function of t as vR (but
with diminished magnitude unless ZR is zero or infinity). The reflection
coefficient pR for voltage at the receiving end of the line is defined as vR/vR so,
for voltage,
Zr Zc
Pr — (5.90)
Zr + Zc
We note from Eqs. (5.87) and (5.88) that
(5.91)
and that therefore the reflection coefficient for current is always the negative of
the reflection coefficient for voltage.
If the line is terminated in its characteristic impedance Zc, we see that the
reflection coefficient for both voltage and current will be zero. There will be no
reflected waves, and the line will behave as though it is infinitely long. Only
when a reflected wave returns to the sending end does the source sense that the
line is not either infinitely long or terminated in Zc.
Termination in a short circuit results in a pR for voltage of — 1. If the
termination is an open circuit, ZR is infinite and pR is found by dividing the
numerator and denominator in Eq. (5.90) by ZR and allowing ZR to approach
infinity to yield pR = 1 in the limit for voltage.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 119
We should note at this point that waves traveling back toward the sending
end will cause new reflections as determined by the reflection coefficient at the
sending end ps. For impedance at the sending end equal to Zs Eq. (5.90)
becomes
zs-zc
Ps = (5.92)
Zs + ze
With sending-end impedances of Zs the value of the initial voltage impressed
across the line will be the source voltage multiplied by ZJ(ZS + Zc). Equation
(5.84) shows that the incident wave of voltage experiences a line impedance of
Zf, and at the instant when the source is connected to the line Zc and Zs in series
act as a voltage divider.
v = 120C/(vf - x)
where U(vt — x) is the unit step function which equals zero when (vr — x) is
negative and equals unity when (vr — x) is positive. There can be no reflected
wave until the incident wave reaches the end of the line. Impedance to the
incident wave is Zc = 30 Q. Since resistance of the source is zero,
v+ = 120 V
90- 30 1
pR ~ 90 + 30 ” 2
When v+ reaches the end of the line a reflected wave originates of value
iT = (^)120 = 60 V
and so
vR = 120 + 60 = 180 V
When t = 2 T the reflected wave arrives at the sending end where the sending
end reflection coefficient ps is calculated by Eq. (5.92). The line termination
for the reflected wave is Zs, the impedance in series with the source, or zero
in this case. So
0-30
= -1
Ps ~ 0 + 30
and a reflected wave of — 60 V starts toward the receiving end to keep the
120 ELEMENTS OF POWER SYSTEM ANALYSIS
sending-end voltage equal to 120 V. This new wave reaches the receiving end
at t = 3T and reflects toward the sending end a wave of
i(_60)= -30 V
180 — 60 — 30 = 90 V
Lattice diagrams for current may also be drawn. We must remember, how¬
ever, that the reflection coefficient for current is always the negative of the
reflection coefficient for voltage.
If the resistance at the end of the line of Example 5.6 is reduced to 10 Cl
as shown in the circuit of Fig. 5.15a, the lattice diagram and plot of voltage are
as shown in Figs. 5.15b and c. The resistance of 10 £2 gives us a negative value
for the reflection coefficient for voltage, which will always occur for resistance
where ZR is less than Zc. As we see by comparing Figs. 5.14 and 5.15 the
negative pR causes the receiving-end voltage to build up gradually to 120 V
while a positive pR causes an initial jump in voltage to a value greater than
that of the voltage originally applied at the sending end.
Reflections do not necessarily arise only at the end of a line. If one line is
joined to a second line of different characteristic impedance, as in the case of an
overhead line connected to an underground cable, a wave incident to the junction
will behave as though the first line is terminated in the Zc of the second line.
However, the part of the incident wave which is not reflected will travel (as a
refracted wave) along the second line at whose termination a reflected wave will
occur. Bifurcations of a line will also cause reflected and refracted waves.
It should now be obvious that a thorough study of transmission-line
transients in general is a complicated problem. We realize, however, that a
voltage surge such as that shown in Fig. 5.13 encountering an impedance at
the end of a lossless line (for instance, at a transformer bus) will cause a
voltage wave of the same shape to travel back toward the source of the surge.
The reflected wave will be reduced in magnitude if the terminal impedance is
other than a short or open circuit, but if ZR is greater than Zc our study has
shown that the peak terminal voltage will be higher than, often close to, double
the peak voltage of the surge.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 121
Figure 5.14 Circuit diagram, lattice dia¬ Figure 5.15 Circuit diagram, lattice dia¬
gram, and plot of voltage versus time for gram, and plot of voltage versus time when
Example 5.6 where the receiving-end resis¬ the receiving-end resistance for Example 5.6
tance is 90 fL is changed to 10 £1
t See E. C. Sakshaug, J. S. Kresge, and S. A. Miske, Jr., “A New Concept in Station Arrester
Design,” IEEE Trans. Power Appar. Syst., vol. PAS-96, no. 2, March/April 1977, pp. 647-656.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 123
Minnesota, a distance of 740 km (460 mi). Preliminary studies showed that the
dc line including terminal facilities would cost about 30% less than the compar¬
able ac line and auxiliary equipment. This line operates at + 250 kV (500 kV
line-to-line) and transmits 500 MW.
Direct-current lines usually have one conductor which is at a positive poten¬
tial with respect to ground and a second conductor operating at an equal nega¬
tive potential. Such a line is said to be bipolar. The line could be operated with
one energized conductor with the return path through the earth, which has a
much lower resistance to direct than to alternating current. In this case, or with
a grounded return conductor, the line is said to be monopolar.
In addition to the lower cost of dc transmission over long distances there are
other advantages. Voltage regulation is less of a problem since at zero frequency
a>L is no longer a factor, whereas it is the chief contributor to voltage drop in an
ac line. Another advantage of direct current is the possibility of monopolar
operation in an emergency when one side of a bipolar line becomes grounded.
The fact that underground ac transmission is limited to about 50 km be¬
cause of excessive charging current at longer distances, direct current was
chosen to transfer power under the English Channel between Great Britain and
France. The use of direct current for this installation also avoided the difficulty
of synchronizing the ac systems of the two countries.
No network of dc lines is possible at this time because no circuit breaker is
available for direct current comparable to the highly developed ac breakers. The
ac breaker can extinguish the arc which is formed when the breaker opens
because zero current occurs twice in each cycle. The direction and amount of
power in the dc line is controlled by the converters in which grid-controlled
mercury-arc devices are being displaced by the semiconductor rectifier (SCR). A
rectifier unit will contain perhaps 200 SCRs.
Still another advantage of direct current is the smaller amount of right of
way required. The distance between the two conductors of the North Dakota-
Duluth 500-kV line is 25 feet. The 500-kV ac line shown in Fig. 5.1 has 60.5 feet
between the outside conductors. Another consideration is the peak voltage of
the ac line which is yjl x 500 = 707 kV. So the line requires more insulation
between the tower and conductors as well as greater clearance above the earth.
We conclude that dc transmission has many advantages over alternating
current, but dc transmission remains very limited in usage except for long lines
because there is no dc device which can provide the excellent switching opera¬
tions and protection of the ac circuit breaker. There is also no simple device to
change the voltage level, which the transformer accomplishes for ac systems.
5.14 SUMMARY
The long-line equations given by Eqs. (5.35) and (5.36) are, of course, valid for a
line of any length. The approximations for the short and medium-length lines
make analysis easier in the absence of a computer.
124 ELEMENTS OF POWER SYSTEM ANALYSIS
PROBLEMS
5.1 An 18-km 60-Hz single circuit three-phase line is composed of Partridge conductors equilaterally
spaced with 1.6 m between centers. The line delivers 2500 kW at 11 kV to a balanced load. What
must be the sending-end voltage when the power factor is (a) 80% lagging, (b) unity, and (c) 90%
leading? Assume a wire temperature of 50°C.
5.2 A 100-mi, three-phase transmission line delivers 55 MVA at 0.8 power factor lagging to the load
at 132 kV. The line is composed of Drake conductors with flat horizontal spacing of 11.9 ft between
adjacent conductors. Determine the sending-end voltage, current, and power. Assume a wire temper¬
ature of 50°C.
5.3 Find the ABCD constants of a n circuit having a 600-D resistor for the shunt branch at the
sending end, a 1-kD resistor for the shunt branch at the receiving end, and an 80-D resistor for the
series branch.
5.4 The ABCD constants of a three-phase transmission line are
The load at the receiving end is 50 MW at 220 kV with a power factor of 0.9 lagging. Find the
magnitude of the sending-end voltage and the voltage regulation. Assume the magnitude of the
sending-end voltage remains constant.
5.5 Use per-unit values on a base of 230 kV, 100 MVA to find voltage, current, power, and power
factor at the sending end of a transmission line delivering a load of 60 MW at 230 kV with 0.8
power-factor lagging. The three-phase line is arranged in flat, horizontal spacing with 15 ft between
adjacent Ostrich conductors. Line length is 70 mi. Assume a wire temperature of 50°C. Note that base
admittance must be the reciprocal of base impedance.
5.6 Evaluate cosh 9 and sinh 9 for 9 = 0.5/82°.
5.7 Justify Eq. (5.52) by substituting for the hyperbolic functions the equivalent exponential
expressions.
5.8 A 60-Hz three-phase transmission is 175 mi long. It has a total series impedance of 35 + )140 D
and a shunt admittance of 930 x KT6/901U. It delivers 40 MW at 220 kV, with 90% power factor
lagging. Find the voltage at the sending end by (a) the short-line approximation, (b) the nominal-n
approximation, (c) the long-line equation.
5.9 Determine the equivalent-71 circuit for the line of Prob. 5.8.
5.10 Determine the voltage regulation for the line described in Prob. 5.8. Assume that the sending-
end voltage remains constant.
5.11 A three-phase 60-Hz transmission line is 250 mi long. The voltage at the sending end is 220 kV.
The parameters of the line are R = 0.2 D/mi, X = 0.8 D/mi, and Y = 5.3 ^U/mi. Find the sending-
end current when there is no load on the line.
CURRENT AND VOLTAGE RELATIONS ON A TRANSMISSION LINE 125
5.12 If the load on the line described in Prob. 5.11 is 80 MW at 220 kV, with unity power factor,
calculate the current, voltage, and power at the sending end. Assume that the sending-end voltage is
held constant, and calculate the voltage regulation of the line for the load specified above.
5.13 Rights of way for transmission circuits are becoming difficult to obtain in urban areas and
existing lines are often upgraded by reconductoring the line with larger conductors or by reinsulating
the line for operation at higher voltage. Thermal considerations and maximum power which the line
can transmit are the important considerations. A 138-kV line is 50 km long and is composed of
Partridge conductors with flat horizontal spacing of 5 m between adjacent conductors. Neglect
resistance and find the percent increase in power which can be transmitted for constant | Ks | and
| VR | while 6 is limited to 45° (a) if the Partridge conductor is replaced by Osprey which has more
than twice the area of aluminum in square millimeters, (f>) if a second Partridge conductor is placed
in a two-conductor bundle 40 cm from the original conductor and a center-to-center distance between
bundles of 5 m, and (c) if the voltage of the original line is raised to 230 kV with increased conductor
spacing of 8 m.
5.14 Construct a receiving-end power-circle diagram similar to Fig. 5.10 for the line of Prob. 5.8.
Locate the point corresponding to the load of Prob. 5.8, and locate the center of circles for various
values of | Fs| if | VR | = 220 kV. Draw the circle passing through the load point. From the measured
radius of the latter circle determine I U I, and compare this value with the values calculated for
Prob. 5.8.
5.15 Use the diagram constructed for Prob. 5.14 to determine the sending-end voltage for various
values of kilovars supplied by synchronous condensers in parallel with the designated load at the
receiving end. Include values of added kilovars to give unity power factor and a power factor of 0.9
leading at the receiving end. Assume that the sending-end voltage is adjusted to maintain 220 kV at
the load.
5.16 A receiving-end power-circle diagram is drawn for a constant receiving-end voltage. For a
certain load at this receiving-end voltage the sending-end voltage is 115 kV. The receiving-end circle
for | Fs| = 115 kV has a radius of 5 in. The horizontal and vertical coordinates of the receiving-end
circles are —0.25 and —4.5 in, respectively. Find the voltage regulation for the load.
5.17 A three-phase transmission line is 300 mi long and serves a load of 400 MVA, 0.8 lagging-power
factor at 345 kV. The A BCD constants of the line are
A = D = 0.8180/1.3°
B = 172.2/84.2° ft
C = 0.001933/90.4° 15
(a) Determine the sending-end line-to-neutral voltage, the sending-end current and the percent
voltage drop at full load.
(b) Determine the receiving-end line-to-neutral voltage at no load, the sending-end current at
no load, and the voltage regulation.
5.18 A series capacitor bank is to be installed at the midpoint of the 300-mi line of Prob. 5.17. The
A BCD constants for 150 mi of line are
A=D = 0.9534/0.3°
B = 90.33Ml° ft
C = 0.001014/90.1° 15
A=D = l/W
B = 146.6/-90° ft
C =0
(a) Determine the equivalent ABCD constants of the series combination of the line-capacitor-
line. (See Table A.6 in the Appendix.)
(b) Rework Prob. 5.17 using these equivalent ABCD constants.
126 ELEMENTS OF POWER SYSTEM ANALYSIS
Determine the ABCD constants of a shunt reactor that will compensate for 60% of the total shunt
admittance.
5.20 A 250-Mvar, 345-kV shunt reactor whose admittance is 0.0021 /—90Q U is connected to the
receiving end of the 300-mi line of Prob. 5.17 at no load.
(a) Determine the equivalent ABCD constants of the line in series with the shunt reactor. (See
Table A.6 in the Appendix.)
(b) Rework part (b) of Prob. 5.17 using these equivalent ABCD constants and the sending-end
voltage found in Prob. 5.17.
5.21 Draw the lattice diagram for current and plot current versus time at the sending end of the line
of Example 5.6 for the line terminated in (a) an open circuit and (b) a short circuit.
5.22 Plot voltage versus time for the line of Example 5.6 at a point distant from the sending end
equal to one-fourth of the length of the line if the line is terminated in a resistance of 10 Q.
5.23 Solve Example 5.6 if a resistance of 54 D is in series with the source.
5.24 Voltage from a dc source is applied to an overhead transmission line by closing a switch. The
end of the overhead line is connected to an underground cable. Assume both the line and the cable
are lossless and that the initial voltage along the line is v+. If the characteristic impedances of the line
and cable are 400 fi and 50 Q, respectively, and the end of the cable is open-circuited, find in terms of
v+ (a) the voltage at the junction of the line and cable immediately after the arrival of the incident
wave and (b) the voltage at the open end of the cable immediately after arrival of the first voltage
wave.
CHAPTER
SIX
SYSTEM MODELING
t For a much more detailed discussion of synchronous machines and transformers, consult any of
the texts on electric machinery such as A. E. Fitzgerald, C. Kingsley, Jr., and A. Kusko, Electric
Machinery, 3d ed., McGraw-Hill Book Company, New York, 1971, or L. W. Matsch, Electromag¬
netic and Electromechanical Machines, 2d ed., IEP, New York, 1977.
127
128 ELEMENTS OF POWER SYSTEM ANALYSIS
The transformer provides the link between the generator and the transmis¬
sion line and between the transmission line and the distribution system which
delivers energy through still other transformers to the loads on the system. As
with the synchronous machine our treatment of the transformer will not be
comprehensive but will provide us with the circuit model suitable to our further
study.
Then we shall see how a one-line diagram describes the combination of the
component models to form a complete system, and we shall devote some further
study to the application of per-unit quantities to calculations for the system.
Figure 6.1 Photograph showing the threading of a four-pole cylindrical rotor into the stator of a
1525-MVA generator. (Courtesy Utility Power Corporation, Wisconsin.)
dc field
winding cdils
Stator
Rotor
slots b and b' and slots c and d. Coil sides in slots a, b, and c are 120° apart. The
conductors shown in the slots indicate a coil of only one turn, but such a coil
may have many turns and is usually in series with identical coils in adjacent slots
to form a winding having ends designated a and a'. Windings designated b and b'
and c and c' are the same as the a-a! winding except for their location around the
armature.
Figure 6.3 shows a salient-pole machine which has four poles. Opposite sides
of an armature coil are 90° apart. So there are two coils for each phase. Coil
sides a, b, and c of adjacent coils are 60° apart. The two coils of each phase may
be connected in series or in parallel.
Although not shown in Fig. 6.3 salient-pole machines usually have damper
windings which consist of short-circuited copper bars through the pole face
similar to part of a “ squirrel cage ” winding of an induction motor. The purpose
of the damper winding is to reduce the mechanical oscillations of the rotor about
synchronous speed which is determined, as we shall soon see, by the number of
poles of the machine and the frequency of the system to which the machine is
connected.
In the two-pole machine one cycle of voltage is generated for each revolu¬
tion of the two-pole rotor. In the four-pole machine two cycles are generated in
each coil per revolution. Since the number of cycles per revolution equals the
number of pairs of poles the frequency of the generated voltage is
P N
/=2fio HZ <61>
where P is the number of poles and N is the rotor speed in revolutions per
minute.
Since one cycle of voltage (360° of the voltage wave) is generated every time
a pair of poles passes a coil we must distinguish between electrical degrees used
SYSTEM MODELING 131
to express voltage and current and mechanical degrees to express position of the
rotor. In a two-pole machine electrical and mechanical degrees are equal. In a
four-pole machine two cycles, or 720 electrical degrees, are produced per revolu¬
tion of 360 mechanical degrees. The number of electrical degrees equals P/2 times
the number of mechanical degrees in any machine.
By proper design of the rotor and by proper distribution of the stator
windings around the armature very pure sinusoidal voltages will be generated.
These voltages are called no-load generated voltages or simply generated voltages.
For our analysis in later sections we shall consider the mmf produced by the
rotor to be sinusoidally distributed.
If the ends of the windings are connected to each other and the junction is
designated o, the generated voltages (labeled Ea0, Ebo, and Eco to agree with the
notation adopted in Chap. 2) are displaced 120 electrical degrees from each
other.
where co is in electrical degrees per second. For our two-pole machine to is also
the angular velocity of the rotor in mechanical degrees per second. We shall
assume that the positive direction chosen for current is toward the observer in
conductor a in Fig. 6.2 and make similar assumptions for currents in conductors
b and c.
Positions around the armature will be identified by the angular displacement
9d measured from the axis of coil a as in Fig. 6.2. The subscript d is used to
distinguish the displacement angle 6d from the angle 9 which we are accustomed
to use to express the time phase between a voltage and a current. We recognize
that the mmf around the armature produced by the armature current in any
phase must be a function of both displacement 9d and time t. We shall designate
the mmf due to the current in phase a as &a(9d, t). Since this mmf is produced
by ia it must be a sinusoidal function of time in phase with ia.
132 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 6.4 Distribution around the armature of mmf produced by the current in phase a of the
generator of Fig. 6.2 for various values of cot when ia is expressed by Eq. (6.2).
The distribution of mmf around the periphery of the armature due to arma¬
ture current is not sinusoidal. In a practical machine each coil occupies a
number of slots and the distribution of mmf is nearly triangular, but in the
analysis we are about to make it is customary to consider only the fundamental
harmonic of the triangular wave, and this we shall do.
For the assumption of sinusoidal distribution of mmf the solid line in
Fig. 6.4 shows the mmf of phase a around the armature as a function of 9d at
t — 0; that is when ia has its maximum value. At this time the distribution of a
around the armature is expressed by
0) = cos 6d (6.5)
and
The sum of these three mmfs is the resultant mmf 3F ar which is called the mmf of
armature reaction. By using the trigonometric identity
and by recognizing that the sum of three sinusoidal terms of equal magnitude
displaced in phase by 120° and 240° is zero we find
(6.12)
Equation (6.12) tells us that the mmf of armature reaction is rotating around
the armature at the angular velocity a> equal to the angular velocity of the rotor.
Therefore this mmf is stationary with respect to the mmf produced by the dc
winding of the rotor. The net flux across the air gap between the stator and rotor
is produced by the resultant of these two mmfs.
If we neglect saturation and recall that we are considering a cylindrical-rotor
machine, we can consider separately the fluxes produced by each of these mmfs
and speak of <j)f produced by the dc current in the rotor and (j)ar produced by
armature reaction. When a flux having sinusoidal distribution is rotating around
the armature the maximum flux linkages with a coil occur when the direction of
the mmf causing the flux coincides with the axis of the coil, but the rate of
change of flux linkages is then zero. Likewise when the rotor has turned through
90° the flux linkages become zero, but their rate of change is a maximum. Thus
the voltage induced in the coil is 90° out of phase with the flux linkages. By
applying Lenz’s law and taking into account the assumed positive directions of
current in the coil and of the mmf in Fig. 6.2 we could show that the induced
voltage is lagging rather than leading the mmf.
To draw the phasor diagram for phase a we visualize the separate components of
the flux at the axis of coil a; that is where 9d equals zero. The rotor flux (pf is the
only one to be considered when the armature current is zero. This flux (j)f
generates the no-load voltage Eao which we shall designate here as Ef. The flux
134 ELEMENTS OF POWER SYSTEM ANALYSIS
<par due to the armature-reaction mmf .9' aT is in phase with the current ia
(at 6d = 0) as may be seen by comparing Eqs. (6.2) and (6.10) and recognizing
that cos cot = cos ( — cot). The sum of cpf and 0ar, saturation neglected, is cf)r, the
resultant flux which generates the voltage Er in the coil windings composing
phase a. The phasor diagram for phase a is shown in Fig. 6.5. Voltages Ef and
Ear lag by 90° the fluxes 0f and cpar which generate them. The resultant flux 0r
is the flux across the air gap of the machine and generates Er in the stator.
Similar diagrams can be drawn for each phase.
In Fig. 6.5 we note particularly that Ear is lagging Ia by 90°. The magnitude
of Ear is determined by <par which in turn is proportional to |/a| since it is the
result of armature current. So we can specify an inductive reactance Xar such that
Vt = Er-jIaXl (6.15)
The product IaXt accounts for the voltage drop caused by that portion of the
flux (produced by armature current) which does not cross the air gap of the
machine. So from Eqs. (6.14) and (6.15)
K= Ef ~ £aXar ~ £(6.16)
generated due to armature due to armature
at no load reaction leakage reactance
or
Vi = Ef — jIaX. (6.17)
SYSTEM MODELING 135
^T
r-^rOTT- -TttftP—W^—
6 Vi
where Xs, called the synchronous reactance, is equal to Xar + Xt. If the resist¬
ance of the armature Ra is to be considered, Eq. (6.17) becomes
V, = E,-I.(R.+jX.) (6.18)
Ra is usually so much smaller than Xs that its omission is not of great con¬
sequence here, where we are most interested in a qualitative approach.
Now we have arrived at a relationship which allows us to represent the
generator by the simple but very useful equivalent circuit shown in Fig. 6.6
which corresponds to Eq. (6.18).
Examination of Fig. 6.5 reveals a very important point about a synchronous
generator. When the current Ia lags the no-load generated voltage Ef by 90°, (f)ar
subtracts directly from <j>f, and <pr is greatly reduced. Conversely, armature
current leading the no-load voltage by 90° causes (f)ar to add directly to <j)f, and
4>r is greatly increased. The relationship between Ef, Ear, and E, for these two
cases is shown in Fig. 6.7. If a highly inductive load is applied to a generator the
terminal voltage will be considerably below the no-load terminal voltage. On the
other hand a capacitive load will cause the terminal voltage to rise considerably
above its no-load value. These results help to verify our phasor diagram and
equivalent circuit.
In developing this theory we restricted ourselves to considering a two-pole
machine. The theory applies equally well to multiple-pole machines but is a little
more complicated to develop because of keeping in mind the differences between
electrical and mechanical degrees.
The principles we have discussed could be extended to a synchronous motor.
Er Ef
Em Ef Er
(a) (b)
Figure 6.7 Phasor diagrams showing the relation between Ef and E„ when current delivered by a
generator is (a) lagging Ef by 90° and (b) leading Ef by 90°.
136 ELEMENTS OF POWER SYSTEM ANALYSIS
E,m
The equivalent circuit for the motor is identical with that of the generator with
the direction shown for Ia reversed. The generated voltages of the generator and
motor are often identified by single-subscript notation as Eg and Em, respec¬
tively, instead of Ef, especially when they are in the same circuit as in Fig. 6.8,
for which the equations are.
(6.19)
and
(6.20)
Synchronous reactances of the generator and motor are Xg and Xm, respectively,
and armature resistance is neglected.
When we study faults on a synchronous machine in Chap. 10 we shall see
that the current flowing immediately after the occurrence of a fault differs from
the steady-state value. Instead of synchronous reactance Xs, we use subtransient
reactance X" or transient reactance X' in modeling the synchronous machine for
fault calculations. These reactances will be used in some problems before our
further study of them in Chap. 10.
If we had considered salient-pole machines we would have had to account
for the difference between the flux path directly into the pole face (called the
direct axis) and the path between poles (called the quadrature axis). To do so the
armature current is divided into two components. One component is 90° out of
phase with the no-load generated voltage Ef, and the other is in phase with Ef.
The first component produces the mmf whose flux causes a voltage drop ac¬
counted for by the product of the current and the so-called direct-axis syn¬
chronous reactance Xd. The other component is in phase with Ef and produces
the mmf and flux which causes a voltage drop accounted for by the product of
this component of current and the quadrature-axis synchronous reactance Xq.
Table A.4 in the Appendix lists per-unit values of various reactances for
synchronous machines. As the table shows, values of Xd and Xq in cylindrical-
rotor machines are essentially equal. For this reason we did not need to consider
Xd and Xq separately in our discussion of armature reaction but simply called
the synchronous reactance Xs. To simplify our work we shall continue to
assume all synchronous machines to have cylindrical rotors. Two-reaction
theory discussing direct- and quadrature-axis reactances can be found in most
textbooks on ac machinery. Table A.4 also gives values of X'd and Xd.
SYSTEM MODELING 137
Figure 6.9 Phasor diagrams of (a) overexcited and (b) underexcited generator. Ia is current delivered
by the generator.
138 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 6.10 Phasor diagrams of (a) overexcited and (b) underexcited motor. Ia is current drawn by
the motor.
viewed from the network. We see from Fig. 6.10 that Em lags V, in order to
satisfy Eq. (6.20), and this is always true for a synchronous motor. Briefly,
Figs. 6.9 and 6.10 show us that overexcited generators and motors supply reac¬
tive power to the system and underexcited generators and motors absorb reactive
power from the system.
We now have models for transmission lines and synchronous machines and are
ready to consider transformers which consist of two or more coils placed so that
they are linked by the same flux. In a power transformer the coils are placed on
an iron core in order to confine the flux so that almost all of the flux linking any
one coil links all the others. Several coils may be connected in series or parallel
to form one winding, the coils of which may be stacked on the core alternately
with those of the other winding or windings.
Figure 6.11 is the photograph of a three-phase transformer which raises the
voltage of a generator in a nuclear power station to the transmission-line
voltage. The transformer is rated 750 MVA 525/22.8 kV.
Figure 6.12 shows how two windings may be placed on an iron core to form
a single-phase transformer of the so-called shell type. The number of turns in a
winding may be several hundred up to several thousand.
We shall begin our analysis by assuming that the flux varies sinusoidally in
the core and that the transformer is ideal, which means that the permeability p of
the core is infinite and the resistance of the windings is zero. With infinite
permeability of the core all of the flux is confined to the core and therefore links
all of the turns of both windings. The voltage e induced in each winding by the
changing flux is also the terminal voltage v of the winding since the winding
resistance is zero.
We can see from the relationship of the windings shown in Fig. 6.12 that
voltages et and e2 induced by the changing flux are in phase when they are
defined by the -I- and — polarity marks indicated. Then by Faraday’s law
(6.22)
= =
SYSTEM MODELING 139
Figure 6.11 Photograph of a three-phase transformer rated 750 MV A 525/22.8 kV. (Courtesy Duke
Power Company.)
and
v2 = e2 = N2^ (6.23)
where 0 is the instantaneous value of the flux and Nt and N2 are the number of
turns on windings 1 and 2, as shown in Fig. 6.12. Since we have assumed sinu¬
soidal variation of the flux we can convert to phasor form after dividing Eq. (6.22)
h
+ ' +
Vl V2
Figure 6.13 Schematic representation of a two-winding
transformer. r
by Eq. (6.23) to yield
Usually we do not know the direction in which the coils of a transformer are
wound. One device to provide winding information is to place a dot at the end
of each winding such that all dotted ends of windings are positive at the same
time; that is, voltage drops from dotted to unmarked terminals of all windings
are in phase. Dots are shown on the two-winding transformer in Fig. 6.12
according to this convention. We also note that the same result is achieved by
placing the dots so that current flowing from the dotted terminal to the un¬
marked terminal of each winding produces a magnetomotive force acting in the
same direction in the magnetic circuit. Figure 6.13 is a schematic representation
of a transformer and provides the same information about the transformer as is
provided by Fig. 6.12.
To find the relation between the currents and i2 in the windings we apply
Ampere’s law which states that the magnetomotive force around a closed path is
jHds = i (6.25)
where i is the current enclosed by the line integral of the field intensity H around
the path. In applying the law around each of the closed paths of flux shown by
dotted lines in Fig. 6.12, it is enclosed Nt times and the current i2 is enclosed N2
times. However, IVji! and lV2i2 produce magnetomotive' forces in opposite
directions and
The minus sign would change to plus if we had chosen the opposite direction for
the current i2. The integral of the field intensity H around the closed path is zero
when permeability is infinite. So upon converting to phasor form we have
h=N2
(6.28)
I2 Nt
SYSTEM MODELING 141
and /j and I2 are in phase. Note then that Ix and /2 are in phase if we choose
the current to be positive when entering the dotted terminal of one winding and
leaving the dotted terminal of the other. If the direction chosen for either cur¬
rent is reversed they are 180° out of phase.
From Eq. (6.28)
(6.29)
= r
12
(«-3<>)
but upon substituting for V2 and /2 values determined from Eqs. (6.24) and
(6.28)
(N2/NX)VX
2 (N1/N2)I1
Thus the impedance connected to the secondary side is referred to the primary
side by multiplying the impedance on the secondary side of the transformer by
the square of the ratio of primary to secondary voltage.
We should note also that Vx I x and V212 are equal as shown by the following
equation which again makes use of Eqs. (6.24) and (6.28)
(6.33)
and similarly
VXI* = V2I* (6.34)
so the voltamperes and complex power input to the primary winding equal the
output of these same quantities from the secondary winding since we are con¬
sidering an ideal transformer.
142 ELEMENTS OF POWER SYSTEM ANALYSIS
Example 6.1 If Nt = 2000 and N2 = 500 in the circuit of Fig. 6.13 and if
y = 1200/0° V and /x = 5 /—30° A with an impedance Z2 connected across
winding 2, find V2, I2, Z2 and the impedance Z'2 which is defined as the
value of Z2 referred to the primary side of the transformer.
Solution
500
Vo = (1200/tT) = 300/(F V
2000
2000
Io = (5 /— 30°) = 20 /— 30° A
500
300/0^
Z, = = 15/30° fi
20/-30
Zi = (15^0!)(^)'2 = 240/30! O
or
Figure 6.14 Transformer equivalent circuit using the ideal transformer concept.
and
rrW-^TOff
R1 Xi
~t+—W—p
h
Vi aV2
Figure 6.16 Transformer equivalent circuit with magnetizing
current neglected. -—-^
to obtain the equivalent circuit of Fig. 6.16. All impedances .and voltages in the
part of the circuit connected to the secondary terminals must now be referred to
the primary side.
Solution
Nt 2000
= 4
N2 500
R1 = 2 + 0.125(4)2 = 4.0 Q
Xy = 8 + 0.5(4)2 = 16 Q
1200
/i = = 6.10 7-4.67° A
192 + 4 + j 16
1171.6/-4.67°
V-> = = 292.9 7-4.67° V
1200/4 — 292 9
Voltage regulation =-^929—~ = 00242 or 2-42%
4 Q j16 Q
1200 V 192 Q
(6.37)
and since rx and xx are very small compared to the measured impedance, G and
Bl can be determined in this manner.
The parameters R and X of the two-winding transformer are determined by
the short-circuit test where impedance is measured across the terminals of one
winding when the other winding is short-circuited. Just enough voltage is
applied to circulate rated current. Since only a small voltage is required the
magnetizing current is insignificant and the measured impedance is essentially
equivalent to R + jX.
Solution
_ 30,000
= 250 A
120
_ 30,000
= 125 A
240
\L\/&= \h\/l
|/,„| = 250 + 125 = 375 A
Input kVA is
Output kVA is
From this example we see that the autotransformer has given us a larger
voltage ratio than the ordinary transformer and transmitted more kilovolt¬
amperes between the two sides of the transformer. So an autotransformer provides
a higher rating for the same cost. It also operates more efficiently since the losses
remain the same as for the ordinary connection. However, the loss of electrical
isolation between the high- and low-voltage sides of the autotransformer is
usually the decisive factor in favor of the ordinary connection in most applica¬
tions. In power systems three-phase autotransformers are frequently used to
make small adjustments of bus voltages.
Solution
t * • u , 0.1102 x 1000
Low-tension base impedance =-—- = 4.84 Q
2.5
In per unit
0.06
X = —— = 0.0124 per unit
4.84
If leakage reactance had been measured on the high-tension side, the value
would be
440
X = 0.06 = 0.96 Q
TlO
0.4402 x 1000
High-tension base impedance = —-—- = 77.5 Q
2.5
In per unit
0.96
X - = 0.0124 per unit
If the base in circuit B is chosen as 10,000 kVA, 138 kV, find the per»unit
impedance of the 300-D resistive load in circuit C referred to circuits C, B,
and A. Draw the impedance diagram neglecting magnetizing current, trans¬
former resistances, and line impedances. Determine the voltage regulation if
the voltage at the load is 66 kV with the assumption that the voltage input
to circuit A remains constant.
Solution
300
Per-unit impedance of load in circuit C = = 0.63 per unit
12
Per-unit impedance of load referred to A = — = 0.63 per unit
1-10
A-B
y'0.1 j 0.08
-npsw'—nnnnp-
;0.63+y'0
Figure 6.20 Impedance diagram for Example 6.5. Im¬
pedances are marked in per unit.
j . 0.957 +j0 n
Load current = —--— = 1.52 + ;0 per unit
0.63 4- jO
Therefore
0.995 - 0.957
Regulation =--x 100 = 3.97 %
Figure 6.22a shows the same three transformers connected Y-A to the same
resistive load of 0.6 Q per phase. So far as the voltage magnitude at the low-
tension terminals is concerned the Y-A transformer can be replaced by a Y-Y
transformer bank having a turns ratio for each individual transformer (or for
each pair of phase windings of a three-phase transformer) of 38.1/2.2 kV as
shown in Fig. 6.22b. The transformers of Fig. 6.22a and b are equivalent if we are
not concerned with phase shift. As we shall see in Chap. 11, there is a phase shift
of the voltages between sides of the Y-A transformer that need not be considered
here. Figure 6.22b shows us that, viewed from the high-tension side of the trans¬
former, the resistance of each phase of the load is
0.6 = 180 Q
Here the multiplying factor is the square of the ratio of line-to-line voltages and
66'kN
(b)
Figure 6.22 Transformer of Fig. 6.21 (a) connected Y-A and (b) replaced by a Y-Y transformer with
line-to-line voltage ratio equal to that of the Y-A.
not the square of the turns ratios of the individual windings of the Y-A
transformer.
This discussion leads to the conclusion that to transfer the ohmic value of
impedance from the voltage level on one side of a three-phase transformer to the
voltage level on the other, the multiplying factor is the square of the ratio of
line-to-line voltages regardless of whether the transformer connection is Y-Y or
Y-A. Therefore in per-unit calculations involving transformers in three-phase
circuits we follow the same principle developed for single-phase circuits and
require the base voltages on the two sides of the transformer to have the same
ratio as the rated line-to-line voltages on the two sides of the transformer. The
kVA base is the same on each side.
Example 6.6 The three transformers rated 25 MVA, 38.1/3.81 kV are con¬
nected Y-A as shown in Fig. 6.22a with the balanced load of three 0.6-fi,
Y-connected resistors. Choose a base of 75 MVA, 66 kV for the high-tension
side of the transformer and specify the base for the low-tension side. Deter¬
mine the per-unit resistance of the load on the base for the low-tension side.
Then determine the load resistance RL referred to the high-tension side and
the per-unit value of this resistance on the chosen base.
152 ELEMENTS OF POWER SYSTEM ANALYSIS
(3.81)2
0.1935
75
and on the low-tension side
0.6
rl = = 3.10 per unit
0.1935
0.121
= 0.10 per unit
(22)2/400
If the three impedances measured in ohms are referred to the voltage of one of
the windings, the impedances of each separate winding referred to that same
winding are related to the measured impedances so referred as follows:
Zps = Zp + Zs
Zpt — Zp + Z( (6.38)
zst = zs + z,
where Zp, Zs, and Z, are the impedances of the primary, secondary, and tertiary
windings referred to the primary circuit if Zps, Zpt, and Zst are the measured
impedances referred to the primary circuit. Solving Eqs. (6.38) simultaneously
yields
(6.39)
The impedances of the three windings are connected in star to represent the
single-phase equivalent circuit of the three-winding transformer with magnetiz¬
ing current neglected, as shown in Fig. 6.23. The common point is fictitious and
unrelated to the neutral of the system. The points p, s, and t are connected to the
parts of the impedance diagrams representing the parts of the system connected
to the primary, secondary, and tertiary windings of the transformer. Since the
ohmic values of the impedances must be referred to the same voltage, it follows
that conversion to per-unit impedance requires the same kilovoltampere base for
all three circuits and requires voltage bases in the three circuits that are in the
same ratio as the rated line-to-line voltages of the three circuits of the
transformer.
154 ELEMENTS OF POWER SYSTEM ANALYSIS
>0.05
resistive load are connected to the secondary and tertiary of the transformer.
Draw the impedance diagram of the system and mark the per-unit im¬
pedances for a base of 66 kV, 15 MVA in the primary.
We now have the circuit models for transmission lines, synchronous machines,
and transformers. We shall see next how to portray the assemblage of these
components to model a complete system. Since a balanced three-phase system is
always solved as a single-phase circuit composed of one of the three lines and a
neutral return, it is seldom necessary to show more than one phase and the
neutral return when drawing a diagram of the circuit. Often the diagram is
simplified further by omitting the completed circuit through the neutral and by
indicating the component parts by standard symbols rather than by their equiva¬
lent circuits. Circuit parameters are not shown, and a transmission line is repre¬
sented by a single line between its two ends. Such a simplified diagram of an
electric system is called a one-line diagram. It indicates by a single line and
standard symbols the transmission lines and associated apparatus of an electric
system.
156 ELEMENTS OF POWER SYSTEM ANALYSIS
Fuse
Three-phase wye,
neutral ungrounded T
Three-phase wye,
Current transformer
neutral grounded
+ See Graphic Symbols for Electrical and Electronics Diagrams, IEEE Std 315-1975.
SYSTEM MODELING 157
the various components shown in Fig. 6.26 to form the impedance diagram of
the system. If a load study is to be made, the lagging loads A and B are
represented by resistance and inductive reactance in series. The impedance dia¬
gram does not include the current-limiting impedances shown in the one-line
diagram between the neutrals of the generators and ground because no current
flows in the ground under balanced conditions and the neutrals of the generators
are at the potential of the neutral of the system. Since the magnetizing current of
a transformer is usually insignificant compared with the full-load current, the
shunt admittance is usually omitted in the equivalent circuit of the transformer.
As previously mentioned, resistance is often omitted when making fault
calculations even in digital-computer programs. Of course, omission of resis¬
tance introduces some error, but the results may be satisfactory since the induc¬
tive reactance of a system is much larger than its resistance. Resistance and
inductive reactance do not add directly, and impedance is not far different from
the inductive reactance if the resistance is small. Loads which do not involve
rotating machinery have little effect on the total line current during a fault and
are usually omitted. Synchronous motor loads, however, are always included in
making fault calculations since their generated emfs contribute to the short-
circuit current. The diagram should take induction motors into account by a
generated emf in series with an inductive reactance if the diagram is to be used
to determine the current immediately after the occurrence of a fault. Induction
motors are ignored in computing the current a few cycles after the fault occurs
because the current contributed by an induction motor dies out very quickly
after the induction motor is short-circuited.
If we decide to simplify our calculation of fault current by omitting all static
loads, all resistances, the magnetizing current of each transformer, and the capa¬
citance of the transmission line, the impedance diagram reduces to the reactance
diagram of Fig. 6.28. These simplifications apply to fault calculations only and
not to load-flow studies, which are the subject of Chap. 8. If a computer is
available, such simplification is not necessary.
The impedance and reactance diagrams discussed here are sometimes called
the positive-sequence diagrams since they show impedances to balanced currents
in a symmetrical three-phase system. The significance of this designation will
become apparent when Chap. 11 is studied.
If data had been supplied with the one-line diagram we could mark values of
reactance on Fig. 6.28. If ohmic values were to be shown, all would have to be
Figure 6.28 Reactance diagram adapted from Fig. 6.27 by omitting all loads, resistances, and shunt
admittances.
SYSTEM MODELING 159
referred to the same voltage level such as the transmission-line side of the
transformer. As we have concluded, however, when bases are specified properly
for the various parts of a circuit connected by a transformer the per-unit values
of impedances determined in their own part of the system are the same when
viewed from another part. Therefore it is necessary only to compute each im¬
pedance on the base of its own part of the circuit. The great advantage of using
per-unit values is that no computations are necessary to refer an impedance from
one side of a transformer to the other.
The following points should be kept in mind:
03.8 kV) Mi
(20 kV)
r. (230 kV)
13.2
In the motor circuit: 230—— = 13.8 kV
These bases are shown in parentheses on the one-line diagram of Fig. 6.29.
The reactances of the transformers converted to the proper base are
300
Transformer 7% X = 0.1 x = 0.0857 per unit
/13.2\2
Transformer T2: X = 0.l(^-^l = 0.0915 per unit
(230)2
= 176.3 Q
300
and the reactance of the line is
0.5 x 64
= 0.1815 per unit
176.3
300
Reactance of motor =0.2
200 )(§)’-»■ 2745 per unit
'300
Reactance of motor M, = 0.2
100 )(§)■-» 5490 per unit
Example 6.11 If the motors Mx and M2 of Example 6.10 have inputs of 120
and 60 MW respectively at 13.2 kV, and both operate at unity power factor,
find the voltage at the terminals of the generator.
SYSTEM MODELING 161
Figure 6.30 Reactance diagram for Example 6.10. Reactances are in per unit on the specified base.
180
300 = 0 6 per Umt
I =
05^5 = °'6273^ unit
At the generator
0.9826 x 20 = 19.65 kV
materially for machines of different ratings. For this reason, when the^ im-
pedance is not known definitely, it is generally possible to select from tab¬
ulated average values a per-unit impedance which will be reasonably correct.
Experience in working with per-unit values brings familiarity with the proper
values of per-unit impedance for different types of apparatus.
3. When impedance in ohms is specified in an equivalent circuit, each impedance
must be referred to the same circuit by multiplying it by the square of the
ratio of the rated voltages of the two sides of the transformer connecting
the reference circuit and the circuit containing the impedance. The per-unit
impedance, once it is expressed on the proper base, is the same referred to
either side of any transformer.
4. The way in which transformers are connected in three-phase circuits does not
affect the per-unit impedances of the equivalent circuit, although the transfor¬
mer connection does determine the relation between the voltage bases on the
two sides of the transformer.
6.14 SUMMARY
The introduction in this chapter of the simplified equivalent circuits for the
synchronous generator and transformer is of great importance for the remainder
of our discussion throughout this book.
We have seen that the synchronous generator will deliver an increasing
amount of reactive power to the system to which it is connected as its excitation
is increased. Conversely, as its excitation is reduced it will furnish less reactive
power and when underexcited will draw reactive power from the system. This
analysis was made on the assumption of a generator supplying such a large
system that the terminal voltage remained constant. In Chap. 8, we will extend
this analysis to a generator supplying a system represented by its Thevenin
equivalent.
Per-unit calculations will be used almost continuously throughout the chap¬
ters to follow. We have seen how the transformer is eliminated in the equivalent
circuit by the use of per-unit calculations. It is important to remember that the
square root of three does not enter the detailed per-unit computations because of
the specification of a base line-to-line voltage and base line-to-neutral voltage
related by the square root of three.
The concept of proper selection of base in the various parts of a circuit
linked by transformers and the calculation of parameters in per unit on the base
specified for the part of the circuit in which the parameters exist is fundamental
in building an equivalent circuit from a one-line diagram.
SYSTEM MODELING 163
PROBLEMS
6.1 Show the steps by which the sum of the three mmfs expressed in Eqs. (6.6) to (6.8) can be
equated to the traveling wave of mmf given in Eq. (6.10).
6.2 Determine the highest speed at which two generators mounted on the same shaft can be driven
so that the frequency of one generator is 60 Hz and the frequency of the other is 25 Hz. How many
poles does each machine have?
6.3 The synchronous reactance of a generator is 1.0 per unit, and the leakage reactance of its
armature is 0.1 per unit. The voltage to neutral of phase a at the bus of a large system to which the
generator is connected is 1.0/0° per unit, and the generator is delivering a current Ia equal
to 1.0 /—30° per unit. Neglect resistance of the windings and find (a) the voltage drop°in the
machine due to armature reaction, (b) the no-load voltage to neutral Eg of phase a of the generator,
and (c) the per-unit values of P and Q delivered to the bus.
6.4 Solve parts (b) and (c) of Prob. 6.3 for Ia = 1.0/30 per unit and compare the results of these two
problems.
6.5 For a certain armature current in a synchronous generator the mmf due to the field current is
twice that due to armature reaction. Neglect saturation and find the ratio of the voltage Er generated
by the air-gap flux to the no-load voltage of the generator (a) when armature current Ia is in phase
with £r, (b) when I0 lags Er by 90°, and (c) when /„ leads Er by 90°.
6.6 A single-phase transformer is rated 440/220 V, 5.0 kVA. When the low-tension side is short-
circuited and 35 V is applied to the high-tension side, rated current flows in the windings and the
power input is 100 W. Find the resistance and reactance of the high- and low-tension windings if the
power loss and ratio of reactance to resistance is the same in both windings.
6.7 A single-phase transformer rated 30 kVA, 1200/120 V is connected as an autotransformer to
supply 1320 V from a 1200-V bus.
(a) Draw a diagram of the transformer connections showing the polarity marks on the wind¬
ings and directions chosen as positive for current in each winding so that the currents will be in
phase.
(b) Mark on the diagram the values of rated current in the windings and at the input and
output.
(c) Determine the rated kilovoltamperes of the unit as an autotransformer.
(d) If the efficiency of the transformer connected for 1200/120-V operation at rated load unity
power factor is 97%, determine its efficiency as an autotransformer with rated current in the wind¬
ings and operating at rated voltage to supply a load at unity power factor.
6.8 Solve Prob. 6.7 if the transformer is to supply 1080 V from a 1200-V bus
6.9 A A-connected resistive load of 8000 kW is connected to the low-tension, A-connected side of a
Y-A transformer rated 10,000 kVA, 138/13.8 kV. Find the load resistance in ohms in each phase as
measured from line to neutral on the high-tension side of the transformer. Neglect transformer
impedance and assume rated voltage is applied to the transformer primary.
6.10 Solve Prob. 6.7 if the same resistors are reconnected in Y.
6.11 Three transformers, each rated 5 kVA, 220 V on the secondary side, are connected A-A and
have been supplying a 15 kW purely resistive load at 220 V. A change is made which reduces the
load to 10 kW, still purely resistive. Someone suggests that, with two-thirds of the load, one trans¬
former can be removed and the system can be operated open-A. Balanced three-phase voltages will
still be supplied to the load since two of the line voltages (and thus also the third) will be unchanged.
To investigate further the suggestion
(a) Find each of the line currents (magnitude and angle) with the 10 kW load and the transformer
between a and c removed. (Assume Vab = 220/0° V, sequence a b c.)
(ib) Find the kilovoltamperes supplied by each of the remaining transformers.
(c) What restriction must be placed on the load for open-A operation with these transformers?
(d) Think about why the individual transformer kilovoltampere values include a Q component when
the load is purely resistive.
164 ELEMENTS OF POWER SYSTEM ANALYSIS
6.12 A transformer rated 200 MVA, 345Y/20.5A kV connects a load of rated 180 MV A, 22.5 kY*0.8
power factor lag to a transmission line. Determine (a) the rating of each of three single-phase
transformers which when properly connected will be equivalent to the three-phase transformer and
(b) the complex impedance of the load in per unit in the impedance diagram if the base in the
transmission line is 100 MVA, 345 kV.
6.13 A 120 MVA, 19.5 kV generator has Xs = 1.5 per unit and is connected to a transmission line by
a transformer rated 150 MVA, 230Y/18A kV with X = 0.1 per unit. If the base to be used in the
calculations is 100 MVA, 230 kV for the transmission line, find the per-unit values to be used for the
transformer and generator reactances.
6.14 A transformer’s three-phase rating is 5000 kVA, 115/13.2 kV, and its impedance is 0.007 +
y'0.075 per unit. The transformer is connected to a short transmission line whose impedance is
0.02 + y0.10 per unit on a base of 10 MVA, 13.2 kV. The line supplies a three-phase load rated
3400 kW, 13.2 kV, with a lagging power factor of 0.85. If the high-tension voltage remains constant
at 115 kV when the load at the end of the line is disconnected, find the voltage regulation at the load.
Work in per unit and choose as base 10 MVA, 13.2 kV at the load.
6.15 The one-line diagram of an unloaded power system is shown in Fig. 6.31. Reactances of the two
sections of transmission line are shown on the diagram. The generators and transformers are rated as
follows:
Generator 1: 20 MVA, 13.8 kV, X" = 0.20 per unit
Generator 2: 30 MVA, 18 kV, X" = 0.20 per unit
Generator 3: 30 MVA, 20 kV, X" = 0.20 per unit
Transformer T,: 25 MVA, 220Y/13.8A kV, X = 10%
Transformer T2 : Single-phase units each rated 10 MVA, 127/18 kV, X = 10%
Transformer T3 : 35 MVA, 220Y/22Y kV, X = 10%
Draw the impedance diagram with all reactances marked in per unit and with letters to indicate
points corresponding to the one-line diagram. Choose a base of 50 MVA, 13.8 kV in the circuit of
generator 1.
6.16 Draw the impedance diagram for the power system shown in Fig. 6.32. Mark impedances in per
unit. Neglect resistance, and use a base of 50 kVA, 138 kV in the 40-fi line. The ratings of the
generators, motors, and transformers are:
Generator 1: 20 MVA, 18 kV, X" = 20%
Generator 2: 20 MVA, 18 kV, X" = 20%
Synchronous motor 3: 30 MVA, 13.8 kV, X" = 20%
Three-phase Y-Y transformers: 20 MVA, 138Y/20Y kV, X = 10%
Three-phase Y-A transformers: 15 MVA, 138Y/13.8A kV, X = 10%
YYi
;'40n
^(Thd- —c}-(5)
_J20
-D[-D- j20n £L-^[-a-
5. 57" B
6.17 If the voltage of bus C in Prob. 6.16 is 13.2 kV when the motor draws 24 MW at 0.8 power
factor leading, calculate the voltages of buses A and B. Assume that the two generators divide the
load equally. Give the answer in volts and in per unit on the base selected for Prob. 6.16. Find the
voltages at A and B when the circuit breaker connecting generator 1 to bus A is open while
the motor draws 12 MW at 13.2 kV with 0.8 power factor leading. All other circuit breakers remain
closed.
CHAPTER
SEVEN
NETWORK CALCULATIONS
166
NETWORK CALCULATIONS 167
For the circuit having the constant emf Eg and series impedance Zg, the
voltage across the load is
Vl = Eg — IL Zg (7.1)
where IL is the load current. For the circuit having a source of constant current
Is with the shunt impedance Zp, the voltage across the load is
The two sources and their associated impedances will be equivalent if the voltage
VL is the same in both circuits. Of course, equal values of VL will mean equal
load currents IL for identical loads.
Comparison of Eqs. (7.1) and (7.2) shows that VL will be identical in both
circuits and therefore that the emf and its series impedance can be interchanged
with the current source and its shunt impedance provided
Eg = ISZP (7.3)
z9 = zp (7.4)
These relations show that a constant-current source and shunt impedance can be
replaced by a constant emf and series impedance if the emf is equal to the
product of the constant current and the shunt impedance and if the series im¬
pedance equals the shunt impedance. Conversely, a constant emf and series
impedance can be replaced by a constant-current source and shunt impedance if
the shunt impedance is identical to the series impedance and if the constant
current is equal to the value of the emf divided by its series impedance.
We have shown the conditions for equivalence of sources connected to a
passive network. By considering the principle of superposition we can show that
the same provisions apply if the output is an active network, that is, if the output
network includes voltage and current sources. To determine the contribution
from the supply if the output network is active, the principle of superposition
calls for shorting emfs in the output network and replacing current sources by
open circuits while impedances remain intact. Thus the output is a passive
network so far as the current component from the interchangeable sources is
concerned. To determine the current components due to the sources in the load
network, the emf of the supply source is shorted in one case and the current
168 ELEMENTS OF POWER SYSTEM ANALYSIS
source is opened in the other case. Thus, only Z0 or its equivalent Zp is con¬
nected across the input to the load to determine the effect of sources in the load
network regardless of which type of source is the supply. So, in applying super¬
position, the components contributed by the sources in the load network are
independent of the type of supply so long as the series impedance of the emf
equals the shunt impedance of the constant-current source. Therefore, the same
provisions for equivalence apply whether the load network is active or passive.
The junctions formed when two or more pure elements (R, L, or C, or an ideal
source of voltage or current) are connected to each other at their terminals are
called nodes. Systematic formulation of equations determined at nodes of a
circuit by applying Kirchhoff’s current law is the basis of some excellent com¬
puter solutions of power-system problems. Usually it is convenient to consider
only those nodes to which more than two elements are connected and to call
these junction points major nodes.
In order to examine some features of node equations, we shall begin with the
one-line diagram of a simple system shown in Fig. 7.2. Generators are connected
through transformers to high-tension buses 1 and 3 and supply a synchronous
motor load at bus 2. For purposes of analysis, all machines at any one bus are
treated as a single machine and represented by a single emf and series reactance.
The reactance diagram, with reactances specified in per unit, is shown in Fig. 7.3.
Nodes are indicated by dots, but numbers are assigned only to major nodes. If
the circuit is redrawn with the emfs and the impedances in series connecting
them to the major nodes replaced by the equivalent current sources and shunt
admittances, the result is the circuit of Fig. 7.4. Admittance values in per unit are
shown instead of impedance values.
Figure 7.2 One-line diagram of a simple Figure 7.3 Reactance diagram for the system
system. of Fig. 7.2. Reactance values are in per unit.
NETWORK CALCULATIONS 169
Similar equations can be formed for nodes 2 and 3, and the four equations can
be solved simultaneously for the voltages Vt, V2, V3, and V4. All branch currents
can be found when these voltages are known, and so the required number of
node equations is one less than the number of nodes in the network. A node
equation formed for the reference node would yield no further information. In
other words, the number of independent node equations is one less than the
number of nodes.
We have not written the other two equations because we can already see
how to formulate node equations in standard notation. In both Eqs. (7.7) and
(7.8) it is apparent that the current flowing into the network from current
sources connected to a node is equated to the sum of several products. At any
node one product is the voltage of that node times the sum of all the admittances
which terminate on the node. This product accounts for the current that flows
away from the node if the voltage is zero at each other node. Each other product
equals the negative of the voltage at another node times the admittance con¬
nected directly between the other node and the node at which the equation is
170 ELEMENTS OF POWER SYSTEM ANALYSIS
formulated. For instance, at node 1 a product is -V3Yf, which accounts for the
current away from node 1 when all node voltages are zero except that at node 3.
The standard form for the four independent equations in matrix form is
_1
-1
>7
>7
>7
>7
U V4
IN
m
The symmetry of the equations in this form makes them easy to remember, and
their extension to any number of nodes is apparent. The order of the Y subscripts
is effect-cause', that is, the first subscript is that of the node at which the current
is being expressed, and the second subscript is that of the voltage causing this
component of current. The Y matrix is designated Ybus and called the bus admit¬
tance matrix.f It is symmetrical around the principal diagonal. The admittances
*ii, y22, y33, and Y44 are called the self-admittances at the nodes, and each
equals the sum of all the admittances terminating on the node identified by the
repeated subscripts. The other admittances are the mutual admittances of the
nodes, and each equals the negative of the sum of all admittances connected
directly between the nodes identified by the double subscripts. For the netwqrk
of Fig. 7.4 the mutual admittance T13 equals —Yf. Some authors call the self-
and mutual admittances of the nodes the driving-point and transfer admittances
of the nodes.
The general expression for the source current toward node k of a network
having N independent nodes, that is, N buses other than the neutral, is
h= i I',/. (7.10)
n = 1
One such equation must be written for each of the N buses at which the voltage
of the network is unknown. If the voltage is fixed at any node, the equation is
not written for that node. For instance, if both the magnitude and angle of the
voltages at two of the high-tension buses of our example are fixed, only two
equations are needed. Node equations would be written for the other two buses,
the only ones at which the voltage would be unknown. A known emf and series
impedance need not be replaced by the equivalent current source if one terminal
of the emf element is connected to the reference node, for then the node which
separates the emf and series impedance is one where voltage is known.
Example 7.1 Write in matrix form the node equations necessary to solve
for the voltages of the numbered buses of Fig. 7.4. The network is equiv¬
alent to that of Fig. 7.3. The emfs shown in Fig. 7.3 are Ea — 1.5/0°.
Eb = 1.5 /—36.87°. and Ec = 1.5/0^, all in per unit.
1.5/0°
^1 = I3 — ~Ji25 = ^ ® — 71-20 per unit
r 1.5 7-36.87°
I2 —-JY25- = 1-2 !—126.87° = —0.72 — 70.96 per unit
The square matrix above is recognized as the bus admittance matrix Ybus.
Example 7.2 Solve the node equations of the preceding example to find the
bus voltages by inverting the bus admittance matrix.
<N
O
0 0 10
0 0
The square matrix above obtained by inverting the bus admittance matrix is
172 ELEMENTS OF POWER SYSTEM ANALYSIS
called the bus impedance matrix Zbus. Performing the indicated matrix mul¬
tiplication yields
1.4111 -70.2668 Vi
1.3830 - 70.3508 V2
1.4059 -70.2824 y3
1.4009-70.2971 K
an a12 a13
A =
a21 a22 a23 (7.11)
a31 a3 2 a33
The matrix is partitioned into four submatrices by the horizontal and vertical
dashed lines. The matrix may be written
D E
A = (7.12)
F G
au a12 a13
D = E =
a21 a22_ a23.
C, where
*11
B= *21
(7.13)
*31
H
B = (7.14)
J
where the submatrices are
and J = h31
D E H
C = AB = (7.15)
F G J
DH + EJ
(7.16)
FH + GJ
(7.17)
M = DH + EJ (7.18)
N = FH + GJ (7.19)
I = Yb„,V (7.21)
where I and V are column matrices and Ybus is a symmetrical square matrix. The
column matrices must be so arranged that elements associated with nodes to be
eliminated are in the lower rows of the matrices. Elements of the square admit¬
tance matrix are located correspondingly. The column matrices are partitioned
so that the elements associated with nodes to be eliminated are separated from
the other elements. The admittance matrix is partitioned so that elements
identified only with nodes to be eliminated are separated from the other ele¬
ments by horizontal and vertical lines. When partitioned according to these
rules, Eq. (7.21) becomes
lA K L
h LT M V*
Since all elements of I* are zero, subtracting L^V,, from both sides of Eq. (7.24)
and multiplying both sides by the inverse of M (denoted by M-1) yields
-M~1Lt\a = V* (7.25)
This admittance matrix enables us to construct the circuit with the unwanted
nodes eliminated, as we shall see in the following example.
Example 7.3 If the generator and transformer at bus 3 are removed from the
circuit of Fig. 7.3, eliminate nodes 3 and 4 by the matrix-algebra procedure
just described, find the equivalent circuit with these nodes eliminated, and
find the complex power transferred into or out of the network at nodes 1
and 2. Also find the voltage at node 1.
Solution The bus admittance matrix of the circuit partitioned for elimina¬
tion of nodes 3 and 4 is
■'T
O
O
Tj"
O
NO
LM xLr =
[72.5 75.0 J 70.0406 70.0736 (75.0 75.0J
74.9264 74.0736
74.0736 73.4264
0.0
Ybus = K — LM1 - LM_1Lr
-78.3
—74.8736 74.0736
Ybus
y'4.0736 -74.8736
Examination of the matrix shows us that the admittance between the two
remaining buses 1 and 2 is —74.0736, the reciprocal of which is the per-unit
impedance between these buses. The admittance between each of these buses
and the reference bus is
The resulting circuit is shown in Fig. 1.5a. When the current sources are
converted to their equivalent emf sources the circuit, with impedances in per
unit, is that of Fig. 1.5b. Then the current is
) 1 1-J0.8 —JO. 81
3 <= c>
e/J 1.5/0! Ebf
(a)
1 (b)
Figure 7.5 Circuit of Fig. 7.3 without the source at node 3 (a) with the equivalent current sources
and (b) with the original voltage sources at nodes 1 and 2.
In the simple circuit of this example node elimination could have been
accomplished by Y-A transformations and by working with series and parallel
combinations of impedances. The matrix partitioning method is a general method
which is thereby more suitable for computer solutions. However, for the elimin¬
ation of a large number of nodes, the matrix M whose inverse must be found
will be large.
Inverting a matrix is avoided by eliminating one node at a time, and the
process is very simple. The node to be eliminated must be the highest numbered
node, and renumbering may be required. The matrix M becomes a single element
and M-1 is the reciprocal of the element. The original admittance matrix
partitioned into submatrices K, L, LT, and M is
K
... y,. ...
*11 *i„
v
1 bus Yki ••• YkJ ••• *kn (7.28)
I/r M
NETWORK CALCULATIONS 177
[Yn 1 (7.29)
and when the indicated manipulation of the matrices is accomplished, the ele¬
ment in row k and column j of the resulting (n — 1) x (n — 1) matrix will be
i<7»)
^nn
Each element in the original matrix K must be modified. When Eq. (7.28) is
compared to Eq. (7.30) we can see how to proceed. We multiply the element in
the last column and the same row as the element being modified by the element
in the last row and the same column as the element being modified. We then
divide this product by Enn and subtract the result from the element being
modified. The following example illustrates the simple procedure.
Example 7.4 Perform the node elimination of Example 7.3 by first removing
node 4 and then by removing node 3.
Solution As in Example 7.3, the original matrix now partitioned for re¬
moval of one node is
74.0
© -7*14.5 m
75-0 7*5-0 7*8-0 -7*18.0 _
To modify the element j2.5 in row 3, column 2 subtract from it the product
of the elements enclosed by rectangles and divided by the element in the
lower right corner. We find the modified element
78.0 x j5.0
Y32=j 2.5 = 74.7222
-7*18.0
7*5-0 x j5.0
Yn = -7*9.8 - —78.4111
-7*18.0
178 ELEMENTS OF POWER SYSTEM ANALYSIS
-74.8736 74.0736
Y bus
74.0736 -74.8736
In Example 7.2, we inverted the bus admittance matrix Ybus and called the
resultant matrix the bus impedance matrix Zbus. By definition
1
^bus =
- Y~1
* bus
(7.31)
Since Ybus is symmetrical around the principal diagonal, Zbus must be symmetri¬
cal in the same manner.
The impedance elements of Zbus on the principal diagonal are called driving-
point impedance of the nodes, and the off-diagonal elements are called the transfer
impedances of the nodes.
The bus admittance matrix need not be determined in order to obtain Zbus,
and in another section of this chapter we shall see how Zbus may be formulated
directly.
The bus impedance matrix is important and very useful in making fault
calculations as we shall see later. In order to understand the physical significance
of the various impedances in the matrix we shall compare them with the node
admittances. We can easily do so by looking at the equations at a particular
node. For instance, starting with the node equations expressed as
I = YbusV (7.33)
® ©
If V1 and F3 are reduced to zero by shorting nodes I and 3 to the reference node
and current I2 is injected at node 2, the self-admittance at node 2 is
(7.35)
Tl = C3=0
Y12 =
h (7.37)
V,
Thus the mutual admittance is measured by shorting all nodes except node 2 to
the reference node and injecting a current I2 at node 2, as shown in Fig. 7.6.
Then Y12 is the ratio of the negative of the current leaving the network in the
short circuit at node 1 to the voltage V2. The negative of the current leaving
node 1 is used since It is defined as the current entering the network. The
resultant admittance is the negative of the admittance directly connected beween
nodes 1 and 2, as we would expect.
We have made this detailed examination of the node admittances in order to
differentiate them clearly from the impedances of the bus impedance matrix.
We solve Eq. (7.33) by premultiplying both sides of the equation by
Ybus = Zbus to yield
V = Zbus I (7.38)
and we must remember when dealing with Zbus that V and I are column matrices
of the node voltages and the currents entering the nodes from current sources,
180 ELEMENTS OF POWER SYSTEM ANALYSIS
From Eq. (7.40) we see that the driving-point impedance Z22 is determined
by open-circuiting the current sources at nodes 1 and 3 and injecting the current
12 at node 2. Then
Z22 = £ (7.42)
Figure 7.7 shows the circuit described. Since Z22 is defined by opening the
current sources connected to the other nodes whereas T22 was found with the
other nodes shorted, we must not expect any reciprocal relation between these
two quantities.
The circuit of Fig. 7.7 also enables us to measure some transfer impedances,
for we see from Eq. (7.39) that with current sources I x and /3 open-circuited
/l=/3 = 0
/l=/3 = 0
Thus we can measure the transfer impedances Z12 and Z32 by injecting current
at node 2 and finding the ratios of Vx and V3 to 12 with the sources open at all
nodes except node 2. We note that a mutual admittance is measured with all but
one node short-circuited and that a transfer impedance is measured with all
sources open-circuited except one.
Equation (7.39) tells us that if we inject current into node 1 with current
sources 2 and 3 open, the only impedance through which Ix flows is Zn. Under
© ©
the same conditions Eqs. (7.40) and (7.41) show that lx is causing voltages at
buses 2 and 3 expressed by
Eth = 1.432/-11,97°
which is the voltage at node 4 before the capacitor is connected and is the
voltage V4 found in Example 7.2.
To find the Thevenin impedance the emfs are short-circuited or the
current sources are open-circuited, and the impedance between node 4 and
the reference node must be determined. From V = Z^I we have at node 4
With emfs short-circuited (or with the emfs and their series impedances
replaced by the equivalent current sources and shunt admittances with the
current sources open) no current is entering the circuit from sources at
nodes 1, 2, and 3. The ratio of a voltage applied at node 4 to the current this
voltage will cause to flow in the network is Z44, and this impedance is
known since Zbus was calculated in Example 7.2. By referring to that
example we find
Solution With original emfs short-circuited, the voltages at the nodes due
only to the injected current will be calculated by making use of the bus
182 ELEMENTS OF POWER SYSTEM ANALYSIS
impedance network which was found in Example 7.2. The required^ im¬
pedances are in column 4 of Zbus. From V = ZbusI, the voltages with all
emfs shorted are
Since the changes in voltages due to the injected current are all at the same
angle and this angle differs little from the angles of the original voltages, an
approximation will give satisfactory answers. The change in voltage magnitude
at a bus is about equal to the product of the magnitude of the per-unit current
and the magnitude of the appropriate impedance. These values added to the
original voltage magnitudes give the magnitudes of the new voltages very closely.
This approximation is valid because the network is purely reactive, but it pro¬
vides a good estimate where the reactance is considerably larger than the resis¬
tance, as is usually the case.
The last two examples illustrate the importance of the bus impedance matrix
and incidentally show how adding a capacitor at a bus will cause a rise in bus
voltages. The assumption that the angles of voltage and current sources remain
constant after connecting capacitors at a bus is not entirely valid if we are
considering operation of a power system. We shall consider capacitors again in
Chap. 8 and see an example using a computer load-flow program to calculate
the effect of capacitors.
matrix inversion even for a small number of buses. Also when we know how to
modify Zbus we can see how to build it directly.t
We recognize several types of modifications involving the addition of a
branch having impedance Zb to a network whose original Zbus is known and is
identified as Zorig, annxn matrix.
In our analysis existing buses will be indentified by numbers or the letters h,
i, j, and k. The letter p will designate a new bus to be added to the network to
convert Zorig to an (n + 1) x (n + 1) matrix. Four cases will be considered.
Case 1: Adding Zbfrom a new bus p to the reference bus The addition of the
new bus p connected to the reference bus through Zb without a connection to
any of the buses of the original network cannot alter the original bus voltages
when a current Ip is injected at the new bus. The voltage Vp at the new bus is
equal to Ip Zb. Then
h
h
(744)
Z bus(new)
We note that the column matrix of currents multiplied by the new Zbus will not
alter the voltages of the original network and will result in the correct voltage at
the new bus p.
^k(orig)
t See H. E. Brown, Solutions of Large Networks by Matrix Methods, John Wiley & Sons, Inc.,
New York, 1975.
184 ELEMENTS OF POWER SYSTEM ANALYSIS
Orig. network
with bus k
and the
reference bus
extracted
We now see that the new row which must be added to Zorig in order to find Vp is
Since Zbus must be a square matrix around the principal diagonal we must add a
new column which is the transpose of the new row. The new column accounts
for the increase of all bus voltages due to Ip. The matrix equation is
(7.48)
Z bus(new)
Note that the first n elements of the new row are the elements of row k of Zorig
and the first n elements of the new column are the elements of column k of Znrio.
Case 3: Adding Zbfrom an existing bus k to the reference bus To see how to
alter Z(orig) by connecting an impedance Zb from an existing bus k to the refer¬
ence bus we shall add a new bus p connected through Zb to bus k. Then we
short-circuit bus p to the reference bus by letting Vp equal zero to yield the same
matrix equation as Eq. (7.48) except that Vp is zero. So for the modification we
proceed to create a new row and new column exactly the same as in case 2 but
we then eliminate the (n + 1) row and (n + 1) column, which is possible because
of the zero in the column matrix of voltages. We use the method developed in
Eqs. (7.28) to (7.30) to find each element Zhi in the new matrix where
Orig. network
with buses
j, k and
reference bus
extracted
shown flowing through Zb from bus k to bus j. We now write some equations for
node voltages.
(7.52)
+
*»<
Vk ~ Vj = ibzb (7.54)
or
0 = IbZb + Vj - vk (7.55)
and substituting the expressions for Vj and Vk given by Eqs. (7.52) and (7.53) in
Eq. (7.55) we obtain
0 — 7bZb + (Zj! — Zfcl)/ j + + (Zjj — Zkj)Ij + ••■
>r
■ •
Vj Zjj Zjk
7
K orig Zkj — zkk
(7.58)
K Z„j — Znk
The new column is column j minus column k of Zorig with Zbb in the (n + 1) row.
The new row is the transpose of the new column.
Eliminating the (n + 1) row and (n + 1) column of the square matrix of
Eq. (7.58) in the same manner as previously we see that each element Zhi in the
new matrix is
7 _ 7_Zh(„ + i)Z(n+ 1)f . .
^hi(new) ^/ii(orig) 7 , 7 . 7 _ 97 \ ' y)
Z/j, T" Z, jj 1 t-'kk jk
We need not consider the case of introducing two new buses connected
by Zb because we could always connect one of these new buses through an
impedance to an existing bus or to the reference bus before adding the second
new bus.
Example 7.7 Modify the bus impedance matrix of Example 7.2 to account
for the connection of a capacitor having a reactance of 5.0 per unit between
bus 4 and the reference bus of the circuit of Fig. 7.4. Then find V4 using the
impedances of the new matrix and the current sources of Example 7.2.
Compare this value of V4 with that found in Example 7.6.
Solution We use Eq. (7.48) and recognize that Zorig is the 4x4 matrix of
Example 7.2, that subscript k = 4, and that Zb = — y'5.0 per unit to find
Vi 70.4142
V2 70.4126
7 70.4232
y3 ong
K 70.4733
The terms in the fifth row and column were obtained by repeating the fourth
row and column of Zorig and noting that
Then eliminating the fifth row and column we obtain for Zbus(new) from
Eq. (7.49)
;0.4142 x ;0.4142
Zn =70.4774 - = 70.5153
—74.5267
70.4733 x ;0.4126
Z24 = ;0.4126 - - j0.4557
-74.5267
and other elements in a similar manner to give
We have seen how to determine Zbus by first finding Ybus and inverting it.
However, formulation of ZbUS directly is a straightforward process on the com¬
puter and simpler than inverting Ybus for a large network.
To begin we have a list of the impedances showing the buses to which they
are connected. We start by writing the equation for one bus connected through
an impedance Za to the reference bus as
vl = ilzm
and this can be considered as a matrix equation where each of the three matrices
has one row and one column. Now we might add a new bus connected to the
first bus or to the reference bus. For instance, if the second bus is connected to
the reference but through Zb we have the matrix equation
>1 Za 0 11
V2_ 0 zb h.
and we proceed to modify our matrix by adding other buses following the
procedures described in Sec. 7.6. Usually the buses of a network must be re¬
numbered to agree with the order in which they are to be added to Zbus as it is
built up.
Example 7.8 Determine Zbus for the network shown in Fig. 7.10 where im¬
pedances are shown in per unit. Preserve all three nodes.
70.3
Vi
^bus — 71-2
To establish bus 2 with its impedance to bus 1 we follow Eq. (7.48) to write
j1.2 j1-2
Z* us (new)
71-2 71.4
The term j 1.4 above is the sum of j 1.2 and j0.2. The elements 71.2 in the new
row and column are the repetition of the elements of row 1 and column 1 of
the matrix being modified.
Bus 3 with the impedance connecting it to bus 1 is established by writing
Since node 1 is the node to which the new node 3 is being connected, the
term j 1.5 above is the sum of Z1X of the matrix being modified and the
impedance Zb of the branch being connected to bus 1 from bus 3. The other
elements of the new row and column are the repetition of the row 1 and
column 1 of the matrix being modified since the new node is being con¬
nected to bus 1.
If we now decide to add the impedance Zb — j 1.5 from node 3 to the
reference bus, we follow Eq. (7.48) to connect a new bus 4 through Zb and
obtain the impedance matrix
where 73.0 above is the sum of Z33 + Zb. The other elements in the new row
and column are the repetition of row 3 and column 3 of the matrix being
modified since bus 3 is the one which we are connecting to the reference bus
through Zb.
NETWORK CALCULATIONS 189
We now eliminate row 4 and column 4. Some of the elements of the new
matrix from Eq. (7.49) are
;1-2x;1.2
Zn=i 1.2 = jOJ2
AO
jl-2 x 71.2
Z22=jlA = j0.92
7 3.0
So we write
A 72 A 72 A60 A12
J0.12 J0.92 ;0.60 70.32
j0.60 A 60 jo.is -A15
J0.12 A32 —A 15 A 62
The procedure is simple for a computer which first must determine, the
types of modification involved as each impedance is added. However, the
operations must follow a sequence such that we avoid connecting an im¬
pedance between two new buses.
As a matter of interest we can check the impedance values of Zbus by the
network calculations of Sec. 7.5.
y'0.3 x y'0.3 5
= y'0.1615
y'0.3 + 70.35
yT.2(y'1.5+y'0.1615)
= 70.6968
11 7(1.2+1.5 + 0.1615)
7.8 SUMMARY
Equivalence of sources and node equations were reviewed briefly in this chapter
to provide the essential background for understanding the bus admittance
matrix which is the basis for most load-flow studies. Matrix partitioning was
reviewed because of its usefulness in node-elimination methods.
The bus impedance matrix is preferred by some engineers for load-flow
studies but finds its greatest value in fault calculations which we shall discuss
later.
NETWORK CALCULATIONS 191
PROBLEMS
7.1 Write the two node equations similar to Eqs. (7.5) and (7.6) required to find the voltages at
nodes 1 and 2 of the circuit of Fig. 7.11 without changing the emf sources to current sources. Then
write the equations in standard form after changing the emf sources to current sources.
7.2 Find the voltages at nodes 1 and 2 of the circuit of Fig. 7.11 by solving the equations determined
in Prob. 7.1.
73 Eliminate nodes 3 and 4 of the network of Fig. 7.12 simultaneously by the method of partitioning
employed in Example 7.3 to find the resulting 2x2 admittance matrix Ybus. Draw the circuit
corresponding to the resulting matrix and show on the circuit the values of the parameters. Solve for
Kj and V2 by matrix inversion.
7.4 Eliminate nodes 3 and 4 of the network of Fig. 7.12 to find the resulting 2x2 admittance matrix
by eliminating node 4 first and then node 3 as in Example 7.4.
7.5 Modify Zbus given in Example 7.2 for the circuit of Fig. 7.4 by adding a new node connected to
bus 4 through an impedance of j 1.2 per unit.
7.6 Modify Zbus given in Example 7.2 by adding a branch having an impedance of y 1.2 per unit
between node 4 and the reference bus of the circuit of Fig. 7.4.
7.7 Determine the impedances in the first row of Zbus for the circuit of Fig. 7.4 with the impedance
connected between bus 3 and the reference bus removed by modifying the Zbus found in Example 7.2.
Then with the current sources connected only at buses 1 and 2 find the voltage at bus 1 and compare
this value with that found in Example 7.3.
7.8 Modify Zbus given in Example 7.2 by removing the impedance connected between nodes 2 and 3
of the network of Fig. 7.4.
7 0.2
-710
Figure 7.12 Circuit for Probs. 7.3 and 7.4. Values shown are currents and admittances in per unit.
192 ELEMENTS OF POWER SYSTEM ANALYSIS
Jl-O
Figure 7.13 Circuit for Prob. 7.9. Values shown are reac¬
tances in per unit. Reference bus
7.9 Find Zbus for the network of Fig. 7.13 by the direct determination process discussed in Sec. 7.7.
7.10 For the reactance network of Fig. 7.14 find (a) Zbus by direct formulation or by inversion of
Ybus, (b) the voltage at each bus, (c) the current drawn by a capacitor having a reactance of 5.0 per
unit connected from bus 3 to neutral, (d) the change in voltage at each bus when the capacitor is
connected at bus 3, and (e) the voltage at each bus after connecting the capacitor. The magnitude
and angle of each of the generated voltages may be assumed to remain constant.
© 70.5 ©
-nror-
70.2
-'’TT57P'— 70.4
70.1 71.0
EIGHT
LOAD-FLOW SOLUTIONS AND CONTROL
Either the bus self- and mutual admittances which compose the bus admittance
matrix Ybus or the driving-point and transfer impedances which compose Zbus
may be used in solving the load-flow problem. We shall confine our study to
methods using admittances. The starting point in obtaining the data which must
be furnished to the computer is the one-line diagram of the system. Values of
series impedances and shunt admittances of transmission lines are necessary so
that the computer can determine all the Ybus or Zbus elements. Other essential
information includes transformer ratings and impedances, shunt capacitor rat¬
ings, and transformer tap settings.
Operating conditions must always be selected for each study. At each bus
except one the net real power into the network must be specified. The power
drawn by a load is negative power input to the system. The other power inputs
are from generators and positive or negative power entering over interconnec¬
tions. In addition, at these buses either the net flow of reactive power into the
193
194 ELEMENTS OF POWER SYSTEM ANALYSIS
network or the magnitude of the voltage must be specified; that is, at each b^s a
decision is required whether the voltage magnitude or the reactive-power flow is
to be maintained constant. The usual case is to specify reactive power at load
buses and voltage magnitude at generator buses, although sometimes reactive
power is specified for the generators. In digital-computer programs provision is
made for the calculation to consider voltage to be maintained constant at a bus
only so long as the reactive-power generation remains within designated limits.
The one bus at which real-power flow is not specified, called the swing bus, is
usually a bus to which a generator is connected. Obviously, the net power flow
to the system cannot be fixed in advance at every bus because the loss in the
system is not known until the study is complete. The generators at the swing bus
supply the difference between the specified real power into the system at the
other buses and the total system output plus losses. Both voltage magnitude and
angle are specified at the swing bus. Real and reactive power at this bus are
determined by the computer as part of the solution.
The complexity of obtaining a formal solution for load flow in a power system
arises because of the differences in the type of data specified for the different
kinds of buses. Although the formulation of sufficient equations is not difficult,
the closed form of solution is not practical. Digital solutions of the load-flow
problems we shall consider at this time follow an iterative process by assigning
estimated values to the unknown bus voltages and calculating a new value for
each bus voltage from the estimated values at the other buses, the real power
specified, and the specified reactive power or voltage magnitude. A new set of
values for voltage is thus obtained for each bus and used to calculate still
another set of bus voltages. Each calculation of a new set of voltages is called an
iteration. The iterative process is repeated until the changes at each bus are less
than a specified minimum value.
We shall examine first the solution based on expressing the voltage of a bus
as a function of the real and reactive power delivered to a bus from generators or
supplied to the load connected to the bus, the estimated or previously calculated
voltages at the other buses, and the self- and mutual admittances of the nodes.
The derivation of the fundamental equations starts with a node formulation of
the network equations. We shall derive the equations for a four-bus system and
write the general equations later. With the swing bus designated as number 1,
computations start with bus 2. If P2 and Q2 are the scheduled real and reactive
power entering the system at bus 2,
and in terms of self- and mutual admittances of the nodes, with generators and
loads omitted since the current into each node is expressed as in Eq. (8.2),
^2 — jQl
Y2lVl + Y22V2 + Y23V3 + Y2AV4 (8.3)
V\
p2 — iQ2
V2 v* ~(y21v1 + y23v3 + y24v4) (8.4)
Equation (8.4) gives a corrected value for V2 based upon scheduled P2 and Q2
when the values estimated originally are substituted for the voltage expressions
on the right side of the equation. The calculated value for V2 and the estimated
value for V\ will not agree. By substituting the conjugate of the calculated value
of V2 for V\ in Eq. (8.4) to calculate another value for V2, agreement would be
reached to a good degree of accuracy after several iterations and would be the
correct value for V2 with the estimated voltages and without regard to power at
the other buses. This value would not be the solution for V2 for the specific
load-flow conditions, however, because the voltages upon which this calculation
for V2 depends are the estimated values of voltage at the other buses and the
actual voltages are not yet known. Two successive calculations of V2 (the second
being like the first except for the correction of V\) are recommended at each bus
before proceeding to the next one.
As the corrected voltage is found at each bus, it is used in calculating the
corrected voltage at the next. The process is repeated at each bus consecutively
throughout the network (except at the swing bus) to complete the first iteration.
Then the entire process is carried out again and again until the amount of
correction in voltage at every bus is less than some predetermined precision
index.
This process of solving linear algebraic equations is known as the Gauss-
Seidel iterative method. If the same set of voltage values is used throughout a
complete iteration (instead of immediately substituting each new value obtained
to calculate the voltage at the next bus), the process is called the Gauss iterative
method.
Convergence upon an erroneous solution may occur if the original voltages
are widely different from the correct values. Erroneous convergence is usually
avoided if the original values are of reasonable magnitude and do not differ too
widely in phase. Any unwanted solution is usually detected easily by inspection
of the results since the voltages of the system do not normally have a range in
phase wider than 45° and the difference between nearby buses is less than about
10° and often very small.
For a total of N buses the calculated voltage at any bus k where Pk and Qk
are given is
1 (Pk-jQk (8.5)
M v*k
196 ELEMENTS OF POWER SYSTEM ANALYSIS
where nfk. The values for the voltages on the right side of the equation are, the
most recently calculated values for the corresponding buses (or the estimated
voltage if no iteration has yet been made at that particular bus).
Experience with the Gauss-Seidel method of solution of power-flow prob¬
lems has shown that an excessive number of iterations are required before the
voltage corrections are within an acceptable precision index if the corrected
voltage at a bus merely replaces the best previous value as the computations
proceed from bus to bus. The number of iterations required is reduced con¬
siderably if the correction in voltage at each bus is multiplied by some constant
that increases the amount of correction to bring the voltage closer to the value it
is approaching. The multipliers that accomplish this improved convergence are
called acceleration factors. The difference between the newly calculated voltage
and the best previous voltage at the bus is multiplied by the appropriate acceler¬
ation factor to obtain a better correction to be added to the previous value. The
acceleration factor for the real component of the correction may differ from that
for the imaginary component. For any system, optimum values for acceleration
factors exist, and poor choice of factors may result in less rapid convergence or
make convergence impossible. An acceleration factor of 1.6 for both the real and
imaginary components is usually a good choice. Studies may be made to deter¬
mine the best choice for a particular system.
At a bus where voltage magnitude rather than reactive power is specified,
the real and imaginary components of the voltage for each iteration are found by
first computing a value for the reactive power. From Eq. (8.5)
n - iQk = (n* k £ n. l) vt
+ (8.6)
where n f k. If we allow n to equal k
Pt-jQt=V!I.YknV„ (8.7)
n=1
e,= -Im [vt £y,„F„! (8.8)
\ n=1 I
where Im means “ imaginary part of.”
Reactive power Qk is evaluated by Eq. (8.8) for the best previous voltage
values at the buses, and this value of Qk is substituted in Eq. (8.5) to find a new
Vk. The components of the new Vk are then multiplied by the ratio of the
specified constant magnitude of Vk to the magnitude of the Vk found by Eq. (8.5).
The result is the corrected complex voltage of the specified magnitude.
Taylor’s series expansion for a function of two or more variables is the basis for
the Newton-Raphson method of solving the load-flow problem. Our study of the
method will begin by a discussion of the solution of a problem involving only
LOAD-FLOW SOLUTIONS AND CONTROL 197
two equations and two variables. Then we shall see how to extend the analysis to
the solution of load-flow equations.
Let us consider the equation of a function of two variables xt and x2 equal
to a constant Kx expressed as
(8.9)
II
<N
and a second equation
where the partial derivatives of order greater than 1 in the series of terms of the
expansion have not been listed. The term d/j/dxj |(0) indicates that the partial
derivative is evaluated for the values of x^ and x(20). Other such terms are
evaluated similarly.
If we neglect the partial derivatives of order greater than 1 we can rewrite
Eqs. (8.13) and (8.14) in matrix form. We then have
dA dA
K i ~fi{x xf) dx2 dx2 Ax<0)
(8.15)
K2 -fi{x x<0)) df2 8A Ax(20)
QXy dx2
where the square matrix of partial derivatives is called the jacobian J or in this
case J(0) to indicate that the initial estimates x(10) and x(20) have been used to
compute the numerical value of the partial derivatives. We note that/i(x(10), x(20))
is the calculated value of Kt for the estimated values of x{0) and x(20) but this
calculated value of is not the value specified by Eq. (8.9) unless our estimated
values x(i} and x(20) are correct. If we designate as Athe specified value of Kx
minus the calculated value of Kx and define A/C(20) similarly we have
A K[0) Ax*0’
= J<°> (8.16)
A Xl20) Ax(20)
198 ELEMENTS OF POWER SYSTEM ANALYSIS
So by finding the inverse of the jacobian we can determine Axf* and A*(20).
However, since we truncated the series expansion, these values added to our
initial guess do not determine for us the correct solution and we must try again
by assuming new estimates and x(2' where
and repeat the process until the corrections become so small that they satisfy a
chosen precision index.
To apply the Newton-Raphson method to the solution of load-flow equa¬
tions we may choose to express bus voltages and line admittances in polar form
or rectangular form. If we choose polar form and separate Eq. (8.7) into its real
and imaginary components with
and A| Vk\( ’ correspond to Ax'/*' and Ax^01 and are the corrections to be added
to the original estimates 5^°’ and I Ft|(0) to obtain new values for computing
Aand AQ[l\ *
For the sake of simplicity we shall write the matrix equation for a system of
only three buses. If the swing bus is number 1 we start our calculations at bus 2
since voltage magnitude and angle are specified at the swing bus. In matrix form
dPk
VkV„Yk„| sin (0t, + <>„ - St) (8.21)
K
where n ^ k and
dP N
-rr‘= I KLUsin (e^ + S.-S,) (8.22)
„=1
n^k
In the above summation n ± k, which is apparent since 3k drops out of Eq. (8.17)
when n = k. Similar general forms of the partial derivatives may be found from
Eqs. (8.18) and (8.19) for calculating the elements in the other submatrices.
Equation (8.20) and similar equations involving more buses are solved by
inverting the jacobian. The values found for A<5* and A | Vk | are added to the
previous values of voltage magnitude and angle to obtain new values for P[]
and g^calc for starting the next iteration. The process is repeated until the
precision index applied to the quantities in either column matrix is satisfied. To
achieve convergence, however, the initial estimates of voltage must be reason¬
able, but this is seldom a problem in power-system work.
200 ELEMENTS OF POWER SYSTEM ANALYSIS
Voltage controlled buses are taken into account easily. Since the voltage
magnitude is constant at such a bus we omit in the jacobian the column of
partial differentials with respect to voltage magnitude of the bus. We are not
interested at this point in the value of Q at the bus so we omit the row of partial
differentials of Q for the voltage controlled bus. The value of Q at the bus can be
determined after convergence by Eq. (8.19).t
The Newton-Raphson method, as noted previously, may also be used when
equations are expressed in rectangular form. We chose to develop the equations
in polar form because the jacobian provides interesting information which is
lacking in the rectangular form. For instance, the dependence of Pk on Sk and of
Qk on | Vk\ is seen immediately in the jacobian in polar form. Later in Sec. 8.10
we shall see how voltage regulating transformers in transmission lines principally
affect the transfer of Q in a system while phase-shifting transformers principally
affect the transfer of P.
Example 8.1 Figure 8.1 shows the one-line diagram of a very simple power
system. Generators are connected at buses 1 and 3. Loads are indicated at
buses 2, 4, and 5. Base values for the system are 100 MVA, 138 kV in the
high-tension lines considered here. Table 8.1 gives impedances for the six
lines which are identified by the buses on which they terminate. The charg¬
ing megavars listed in the table account for the distributed capacitance of
the lines and will be neglected in this example but discussed in Sec. 8.4 and
t For a more detailed explanation of the Newton-Raphson method and for excellent numerical
examples carried through to a converging solution for both Gauss-Seidel and Newton-Raphson
methods, see G. W. Stagg and A. H. El-Abiad, Computer Methods in Power System Analysis, chaps. 7
and 8, McGraw-Hill Book Company, New York, 1968.
Table 8.1
Line, Length
bus to R X R X Charging
bus km mi Q n per unit per unit Mvart
+ At 138 kV.
included in the computer runs for the system. Table 8.2 lists values of P, Q,
and V at each bus. Since values of P and Q in Eqs. (8.18) and (8.19) are
positive for real power and inductive reactive voltamperes input to the
network at each bus, net values of P and Q for these equations are negative
at buses 2, 4, and 5. Generated Q is not specified where voltage magnitude is
constant. In the voltage column the values for the load buses are the original
estimates. Listed values of voltage magnitude and angle are to be held
constant at the swing bus, and the listed voltage magnitude is to remain
constant at bus 3. A load-flow study is to be made by the Newton-Raphson
method using the polar form of the equations for P and Q. Determine the
number of rows and columns in the jacobian. Calculate AP(20) and the value
of the second element in the first row of the jacobian using the specified
values or initial estimates of the voltages.
Solution Since the swing bus does not require a row and column of the
jacobian an 8 x 8 matrix would be necessary if P and Q are specified for the
remaining four buses. However, voltage magnitude is specified (held
constant) at bus 3, and the jacobian will be a 7 x 7 matrix.
Table 8.2
Generation Load
1
5.7747/104.04°
0.042 + 70.168
1
7.7067/103.82°
0.031 + 70.126
115
= —1.15 per unit
100
So
AP<20) - -1.15 - (-0.0928) = -1.0572 per unit
dP2
= ~\V2V3Y23\ sin (d23 + d3-S2)
85 -.
1. Determine values of Pk calc and Qk caIc flowing into the system at every bus for
the specified or estimated values of voltage magnitudes and angles for the first
iteration or the most recently determined voltages for subsequent iterations.
2. Calculate AP at every bus.
3. Calculate values for the jacobian using estimated or specified values of vol¬
tage magnitude and angle in the equations for partial derivatives determined
by differentiation of Eqs. (8.18) and (8.19).
LOAD-FLOW SOLUTIONS AND CONTROL 203
4. Invert the jacobian and calculate voltage corrections Adk and A | Vk | at every
bus.
5. Calculate new values of Sk and | Vk | by adding ASk and A | Vk | to the previous
values.
6. Return to step 1 and repeat the process using the most recently determined
values of voltage magnitudes and angles until either all values of AP and AQ
or all values of A<5 and A | V | are less than a chosen precision index.
Power companies use very elaborate programs for making load-flow studies. A
typical program is capable of handling systems of more than 2000 buses, 3000
lines, and 500 transformers. Of course programs can be expanded to even greater
size provided the available computer facilities are sufficiently large.
Data supplied to the computer must include the numerical values given in
Tables 8.1 and 8.2 and an indication of whether a bus is a swing bus, a regulated
bus where voltage magnitude is held constant by generation of reactive power Q,
or a bus with fixed P and Q. Where values are not to be held constant the
quantities given in the tables are interpreted as initial estimates. Limits of P and
Q generation usually must be specified as well as the limits of line kilovolt¬
amperes. Unless otherwise specified, programs usually assume a base of
100 MVA.
Total line charging in megavars specified for each line accounts for shunt
capacitance and equals y/3 times the rated line voltage in kilovolts times Jchg, as
defined by Eqs. (4.24) and (4.25), divided by 103. This equals a>Cn \V\2 where
| V | is the rated line-to-line voltage in kilovolts, and C„ is line-to-neutral capaci¬
tance in farads for the entire length of the line. The program creates a nominal-/!
representation of the line by dividing equally between the two ends of the line
the capacitance computed from the given value of charging megavars. For a long
line, the computer could be programmed to compute the equivalent n for capaci¬
tance distributed evenly along the line.
204 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 8.2 Digital-computer solution of load-flow for the system of Example 8.1. Base is 100 MVA.
toco
ao CC
a <1 zz
I uj Q: a • CO
I CC «1 1 c
I N> U1UJ
1 a.r yjto
1<
ao O^T
a —in
a • •
a x 00
a a x
1 a < ac
a a > ao
a a x a rvi
a q a u in J
XX
a _j
a a
a a x
» • 7 • in
ao
• cj- hO
DK
a x
a — o
< a x
z-< ac
a—
— —X a rv
UJ UJ
X X I z
C *3. U«3f
_l OJI a -r
u or a am
CD • a7
C u X
<1 x
3 to
CD
Z
> <1
z _i a
<t d a
Cl l_) I
X _ I
C < l rv/
u u a O'
a
a x a > — G —
o a
a a
•— 1
oc a
co
3
oj a 33
or x
205
206 ELEMENTS OF POWER SYSTEM ANALYSIS
To bus 1 To bus 3
The load-flow study for the system described in Example 8.1 for which Fig. 8.2 is
the printout was run on a program attributed to the Philadelphia Electric Com¬
pany and subsequently modified. Three Newton-Raphson iterations were
required. Similar size studies run using other programs also required three
Newton-Raphson iterations but required 22 Gauss-Seidel iterations with the
same precision index. Figure 8.2 may be examined for more information than
just the tabulated results. For instance, the megawatt loss in any of the lines can
be found by comparing the values of P and Q at the two ends of the line. As an
example we see that 95.68 MW flow from bus 1 into line 1-5 and 92.59 MW
flow into bus 5 from the line. Evidently the \I\2 R loss in the line is 3.09 MW.
On another page of the printout, not reproduced here, \I\2 R losses of the
system are listed as 9.67 MW.
Information provided by Fig. 8.2 can be displayed on a diagram showing the
entire system. Figure 8.3 shows a portion of such a diagram at bus 2.
Figure 8.4 Phasor diagrams of a generator having constant values of \Eg\ and | V,\ for (a) angle <5
small and (b) angle 6 larger to show the increase in power delivered as 5 increases.
may be seen by comparing Figs. 8.4a and 8.4b. The generator will therefore
deliver more power to the network, and the input from the prime mover will
again equal the output to the network if losses are disregarded. Equilibrium will
be reestablished at the speed corresponding to the frequency of the infinite bus
with a larger 5. Figure 8.4b is drawn for the same dc field excitation and there¬
fore the same \Eg\ as Fig. 8.4a, but the power output equal to | Vt | • | Ia | cos 9
is greater for the condition of Fig. 8.4b, and the increase in d has caused the
generator to deliver the additional power to the network.
The dependence of power on the power angle is also shown by an equation
giving P + jQ supplied by a generator in terms of 5. If
and
(8.24)
Therefore
P+jQ = v,i*
\V,\-)E.\/=£- \Vl
~jX,
(8.25)
(8.26)
208 ELEMENTS OF POWER SYSTEM ANALYSIS
Q= sin (90
When volts rather than per-unit values are substituted for Vt and Eg in
Eqs. (8.26) and (8.27), we must be careful to note that V, and Eg are line-to-
neutral voltages and P and Q will be per-phase quantities. However, line-to-line
voltage values substituted for Vt and Eg will yield total three-phase values for P
and Q. The per-unit P and Q of Eqs. (8.26) and (8.27) are multiplied by base
three-phase megavoltamperes or base megavoltamperes per phase depending on
whether total three-phase power or power per phase is wanted.
Equation (8.26) shows very clearly the dependence of power transferred to
the network on the power angle 5 if \Eg\ and | Vt | are constant. However, if P
and Vt are constant, Eq. (8.26) shows that 5 must decrease if \Eg\ is increased by
increasing the dc field excitation. In Eq. (8.27) with P constant both an increase
in | Eg | and a decrease in d mean that Q will increase if already positive or
decrease in magnitude and perhaps become positive if Q is negative before
increasing the field excitation. This agrees with the conclusions reached in
Sec. 6.4.
Equation (8.26) can be interpreted as the power transferred from one bus in
a network to another bus through a reactance X connecting the two buses. If the
bus voltages are V1 and V2 and d is the angle by which V1 leads V2,
P= sin 5 (8.28)
The equations derived in Sec. 5.8 to develop circle diagrams are more general
than Eqs. (8.28) and (8.29) because they account for resistance and capacitance.
Equations (5.59) and (5.60), however, are identical with Eqs. (8.28) and (8.29) if
the only line parameter considered is the inductance.
From Eqs. (8.28) and (8.29) we see that an increase in d causes a larger
change in P than in Q when S is small. This difference is explained when we
recognize that sin <S changes widely but cos <5 changes by only a small amount
with a change in S when S is less than 10 or 15°.
LOAD-FLOW SOLUTIONS AND CONTROL 209
In Chap. 6 and Sec. 8.7 we have been considering the synchronous generator
from the viewpoint of supplying power to an infinite bus. We have examined the
effect of generator excitation and power angle when the terminal voltage of the
generator remains constant. In load-flow studies on a digital computer, however,
we found that it was necessary to specify voltage magnitude or reactive power at
every bus except the swing bus, where voltage was specified by both magnitude
and angle. Although the computer can easily tell us the results over the entire
system of specifying various voltage magnitudes at particular buses, it may be
helpful to look at what happens in a very simple case.
Usually it is at the buses on which there is generation that the voltage
magnitude is specified when a load-flow study is made on a computer. At such
buses real power P supplied by the generator is also specified. The reactive
power Q is then determined by the computer in solving the problem. Therefore,
our purpose at this point is to examine the effect of the magnitude of the
specified bus voltage on the value of Q supplied by the generator to the power
network.
Figure 8.5 shows a generator represented by its equivalent circuit with the
relatively small resistance neglected in order to simplify our analysis. The power
system is represented by its Thevenin equivalent voltage Eth in series with the
Thevenin impedance Xth, where again resistance has been neglected. Any local
load on the bus is included in the Thevenin equivalent. For constant power
delivered by the generator the component of / in phase with Elh must remain
constant. The voltage specified at the bus is | Vt |, and
Vt = Eth+jIXth (8.30)
The phasor diagram for the circuit of Fig. 8.5 is shown in Fig. 8.6 for three
different phase angles between Eth and I. In all three cases, however, the com¬
ponent of / in phase with Eth is constant.
Figure 8.6 shows that larger magnitudes of bus voltage Vt with constant
power input to the bus require a larger \Eg\, and, of course, the larger \Eg\ is
obtained by increasing the excitation of the dc field winding of the generator.
Increasing the bus voltage by increasing | Eg | causes the current to become more
lagging, as we see from Fig. 8.6 and as we expect from our discussion of the
synchronous generator. When we are making a load-flow study, increasing the
voltage specified at a generator bus means that the generator feeding the bus will
xth
increase its output of reactive power to the bus. From the standpoint of opera¬
tion of the system we are controlling bus voltage and Q generation by adjusting
the generator excitation.
Since we have represented the system by its Thevenin equivalent, we are
assuming that all Eg and Em values in the system remain constant in magnitude
and angle. This assumption is not strictly true under actual operating conditions.
When a change is made in the excitation of one generator, other changes may be
made elsewhere in the system. An example which would require changing Eg of
generators or motors at other buses is the specification to hold voltage constant
at these buses. The computer program takes care of all such conditions that are
imposed. However, our assumption of constant Eg and Em values in the system
except where we are making a change is very useful to illustrate the effect of a
change of voltage magnitude at a particular bus.
(b) To find P and Q when \Vt\ = 1.0 we must find the phase angle of Vt,
as follows:
The phase angle of Vt is determined by finding the angle 3 between V, and Eth
for | Vt\ = 1.0 and P = 0.776. By Eq. (8.28)
1.0 x 0.944
sin 3 = 0.776
0.2
S = 9.46°
(by which Vt leads Eth). Therefore,
■‘th
Ir = (8.31)
Zth — jX c
The phasor diagram is shown in Fig. 8.8. The increase in Vt caused by adding the
capacitor is very nearly equal to \IC\ Xth if we assurfie that Elh remains un-
Figure 8.7 Circuit showing a capacitor to be Figure 8.8 Phasor diagram of the circuit of
connected through switch S to a system Fig. 8.7 with the capacitor connected. Before
represented by its Thevenin equivalent. connection of the capacitor V, = Eth.
LOAD-FLOW SOLUTIONS AND CONTROL 213
changed since Eth and Vt are identical before adding the capacitor. This phasor
diagram serves to explain the increase in voltage at the bus where the capacitor
is installed. Example 7.6 was introduced as a part of our study of Zbus; and this
example should be reviewed because it shows how the change in voltage magni¬
tude due to the added capacitor can be calculated at all the buses of a system
where there are no regulated buses and loads are represented by impedances.
Here again we have made the assumption that Eg and Em values in the
system remain constant. As described in Sec. 8.8, the assumption is not strictly
true but provides a good estimate of the increase of bus voltages due to adding
capacitors except at buses where voltage is held constant. If the capacitors are
added to a load bus which is remote from any generation, the estimate is quite
good for nearby buses.
The digital load-flow printout of Fig. 8.2 shows a voltage at bus 4 of 0.920
per unit. The same load-flow program can be used to determine the amount of
reactive power which must be supplied by capacitors at this bus to raise the
voltage to any specified value. The procedure is to designate bus 4 as a regulated
bus to be held at the specified voltage and with a generator at the bus to supply
only reactive power. If generator losses are neglected, such a generator is equiva¬
lent to a lossless, unloaded, and overexcited synchronous motor and is known as
a synchronous condenser. The computer determines the necessary amount of
reactive power, which may be supplied to the system by either static capacitors
or a synchronous condenser.
When the voltage of bus 4 is specified to be 0.950 per unit, the required
reactive-power generation is found to be 15.3 kvar. This reactive-power input at
bus 4 also raises the voltage of bus 5 from 0.968 to 0.976 per unit. At bus 2, the
only other unregulated bus, the voltage is unchanged because of its separation
from bus 4 by regulated buses 1 and 3.
The flow of real and reactive power determined by the computer in the lines
connected to bus 4 with and without the added capacitors is shown in Fig. 8.9.
condenser
(a) ib)
Figure 8.9 Flow of P and Q at bus 4 of the system of Example 8.1 (a) as found in the original
load-flow study and (b) with capacitors added at the bus to raise the voltage to 0.950 per unit.
214 ELEMENTS OF POWER SYSTEM ANALYSIS
The voltage drops on the lines from buses 3 and 5 to bus 4 are reduced by
supplying reactive power at bus 4 because the reactive power flowing in these
lines is reduced. The increase of voltage at bus 4 obtained by applying capacitors
at the bus results in causing the reactive power reaching bus 4 over the two
transmission lines to be apportioned between the lines to accomplish the
required voltage drop in each.
regulating transformer for control of voltage magnitude, and Fig. 8.11 shows a
regulating transformer for phase-angle control. The phasor diagram of Fig. 8.12
helps to explain the shift in phase angle. Each of the three windings to which
taps are made is on the same magnetic core as the phase winding whose voltage
is 90° out of phase with the voltage from neutral to the point connected to the
center of the tapped winding. For instance, the voltage to neutral Van is increased
by a component AV^, which is in phase or 180° out of phase with Vbc. Figure 8.12
shows how the three line voltages are shifted in phase angle with very little
change in magnitude.
The procedure to determine Ybus and Zbus in per unit for a network contain¬
ing a regulating transformer is the same as the procedure to account for any
transformer whose turns ratio is other than the ratio used to select the ratio of
base voltages on the two sides of the transformer. Such a transformer, which we
shall now investigate, is said to have an off-nominal turns ratio.
If we have two buses connected by a transformer, and if the ratio of the
line-to-line voltages of the transformer is the same as the ratio of the base
Figure 8.13 Transformers with differing turns ratios connected in parallel: (a) the one-line diagram;
(b) the reactance diagram in per unit. The turns ratio 1/a is equal to n/ri.
voltages of the two buses, the equivalent circuit (with the magnetizing current
neglected) is simply the transformer impedance in per unit on the chosen base
connected between the buses. Figure 8.13a is a one-line diagram of two transfor¬
mers in parallel. Let us assume that one of them has the voltage ratio 1/n, which
is also the ratio of base voltages on the two sides of the transformer, and that the
voltage ratio of the other is 1/n'. The equivalent circuit is then that of Fig. 8.13b.
We need the ideal (no impedance) transformer with the ratio 1/a in the per-unit
reactance diagram to take care of the off-nominal turns ratio of the second
transformer because base voltages were determined by the turns ratio of the first
transformer.
If we have a regulating transformer (rather than the LTC, which changes
voltage level as well as providing the tap-changing feature), Fig. 8.13b may be
interpreted as two transmission lines in parallel with a regulating transformer in
one line.
Evidently our problem is to find the node admittances of Fig. 8.14, which is
a more detailed representation of the LTC with a turns ratio of 1/n' or of the
regulating transformer with the transformation ratio 1/a. The admittance Y in
the figure is the reciprocal of the per-unit impedance of the transformer. Since
the admittance Y is shown on the side of the ideal transformer nearest node 1,
the tap-changing side (or the side corresponding to n') is nearest node 2. This
designation is important in using the equations which are to be derived. If we are
considering a transformer with off-nominal turns ratio, a is the ratio n'/n. If we
have a regulating transformer, a may be real or imaginary, such as 1.02 for a 2%
boost in magnitude or ejn/6° for a 3° shift per phase.
transformer )
©
-rAAA/—cnnp
+■ V I
Figure 8.14 has been labeled to show currents Ix and I2 entering the two
nodes, and the voltages are V1 and V2 referred to the reference node. The
complex expression for power into the ideal transformer in the direction from
node 1 is
Si (8.32)
S2 - V2I*2 (8.33)
Since we are assuming that we have an ideal transformer with no losses, the
power into the ideal transformer from node 1 must equal the power out of the
transformer from node 2, and so
— f* — _ v r* (8.34)
a h ~ Vlh
and
/j = —a* 12 (8.35)
The current 11 can be expressed by
a 1^
27
*-<
(8.36)
II
or
h = VlY-V2- (8.37)
a
Y Y
h= -Ki— +V2—- (8.38)
a* aa*
Comparing Eqs. (8.37) and (8.38), we have, since aa* = \a\2, the node
admittances
*n = *
(8.39)
Y12 =
Solution
1.0
I2 = -0.8 + j0.6
0.8 + j0.6
a = 1.05
h = v, r2i + v2y22
where the node admittances are those of the parallel combination of the two
transformers. For transformer Ta alone
*21 =
i'0.1
=;io
y“ “ jSI - -jl°
0.8
n, = -^
21 1.05
= 7 9.52
y _ Vft-l
= -)9.07
22 11.0512
V1 = 1.008 + 70.041
- V2 = 0.008 + 70.041
Therefore
;o.i
005
/circ = Jo! = ~j025 pCr Umt
With AT short-circuited the current in each path is half of the load current, or
0.4 — y‘0.3. Then superimposing the circulating current gives
so that
and
To bus 5
necessarily be exactly 0.950 per unit. The results achieved at bus 4 are shown in
the one-line diagram of Fig. 8.18. A per-unit reactance of 0.08 was assumed for
the LTC.
When the voltage of bus 4 is raised by the LTC in line 5-4, the voltage drop
over line 3-4 must be less and we expect this to be accomplished by a reduced
flow of reactive power through the line with little change in real power. By
comparing Fig. 8.18 with Fig. 8.9a we see that the Q flowing into bus 4 through
line 3-4 is reduced from 18.90 to 12.26 Mvar without much change in P. To
supply the 30 Mvar required by the load 17.71 Mvar now flows into bus 4
through the line from bus 5 and the LTC. The increased megavars on the line
cause the voltage on the low-tension side of the LTC to be quite low, but the
transformer steps up the voltage to 0.946 per unit at bus 4 by selecting the
proper tap setting.
The voltage at bus 5 dropped from the original value of 0.968 per unit to
0.962 per unit. As a comparison, we noted in Sec. 8.9 that the voltage at bus 5
increased to 0.976 per unit when capacitors were added to bus 4. The reason for
the decrease in the voltage at bus 5 in the present case is that the increased
reactive power supplied to bus 4 from bus 5 caused an increase in the reactive
power which had to be fed to bus 5 from the voltage-regulated buses 1 and 3.
To determine the effect of phase-shifting transformers we need only let a be
complex with a magnitude of unity in Eqs. (8.39).
Example 8.4 Repeat Example 8.3 except that Tb includes both a transformer
having the same turns ratio as Ta and a regulating transformer with a phase
shift of 3° (a = cjnl60 = 1.0/^). The impedance of the two components of Tb
is y'0.1 per unit on the base of Ta.
l, = ^ = io£r
Y — _ _ _/io
22 “11.0/3! I2 ;
= 1.03 + ;0.013
Again the approximate values are close to the values found previously.
LOAD-FLOW SOLUTIONS AND CONTROL 223
To bus 5
8.11 SUMMARY
PROBLEMS
8.1 Evaluate AP(°] for continuing Example 8.1.
8.2 Determine the value of the element (dP3/d<54) in the third column and second row of the jacobian
for the first iteration in continuing Example 8.1.
8.3 Evaluate for the first iteration the element in the third column and third row of the jacobian of
Example 8.1.
8.4 Evaluate for the first iteration the element in the sixth column and third row of the jacobian of
Example 8.1.
8.5 Draw a diagram similar to Fig. 8.3 for bus 3 of the system of Example 8.1 from the information
provided by the printout of load flow in Fig. 8.2. What is the apparent megawatt and megavar
mismatch at this bus?
8.6 Reproduce Fig. 8.20 and on it indicate for Example 8.1 the values of
(a) P and Q leaving bus 5 on line 5-4.
(b) Q supplied by the fixed capacitance of the nominal n of line 5-4 at bus 5. (Note that this value of
Q varies as | V512.)
(c) P and Q at both ends of the series part of the nominal n of the line.
© * ©
(d) Q supplied by the fixed capacitance of the nominal n of line 5-4 at bus 4.
(e) P and Q into bus 4 on line 5-4.
8.7 As part of the load-flow solution of Example 8.1 the computer listed a total line loss of 9.67 MW.
How does this compare with the sum of the losses which can be found from the load-flow listings of
each individual line?
8.8 The effect of field excitation discussed in Sec. 6.4 can now be calculated. Consider a generator
having a synchronous reactance of 1.0 per unit and connected to a large system. Resistance may be
neglected. If the bus voltage is 1.0/0° per unit and the generator is supplying to the bus a current of
0.8 per unit at 0.8 power-factor lagging, find the magnitude and angle of the no-load voltage Eg of the
generator and P and Q delivered to the bus. Then find the angle S between Eg and the bus voltage,
the current Ia, and Q delivered to the bus by the generator if the power output of the generator
remains constant but the excitation of the generator is (a) decreased so that | Eg\ is 15% smaller and
(b) increased so that |£j is 15% larger. What is the percent change in Q upon reducing and
increasing |Ej ? Do the results of this problem agree with the conclusions reached in Sec. 6.4?
8.9 A power system to which a generator is to be connected at a certain bus may be represented by
the Thevenin voltage E,h = 0.9/0° per unit in series with Zlh = 0.25/90° per unit. When connected to
the system, Eg of the generator is 1.4/30° per unit. Synchronous reactance of the generator on the
system base is 1.0 per unit, (a) Find the bus voltage V, and P and Q transferred to the system at the
bus; (b) if the bus voltage is to be raised to \V,\ = 1.0 per unit for the same P transferred to
the system, find the value of Eg required and the value of Q transferred to the system at the bus.
Assume all other system emfs are unchanged in magnitude and angle; that is, Elh and Zlh are
constant.
8.10 In Prob. 7.10 voltages at the three buses were calculated before and after connecting a capacitor
from neutral to bus 3. Determine P and Q entering or leaving bus 3 over transmission lines, through
the reactance connected between the bus and neutral, and from the capacitor before and after the
capacitor is connected. Assume generated voltages remain constant in magnitude and angle. Draw
diagrams similar to those of Fig. 8.9 to show the values calculated.
8.11 Figure 8.9 shows that 15.3 Mvar must be supplied by a capacitor bank at bus 4 of the 60-Hz
system of Example 8.1 to raise the bus voltage to 0.950 per unit. If the base voltage is 138 kV, find
the capacitance in each phase if the capacitors are (a) connected in Y and (b) connected in A.
8.12 Two buses a and b are connected to each other through impedances X 2 =0.1 and X 2 = 0.2 per
unit in parallel. Bus b is a load bus supplying a current / = 1.0/— 30° per unit. The per-unit bus
voltage Vb is 1.0/0°. Find P and Q into bus b through each of the parallel branches (a) in the circuit
described, (b) if a regulating transformer is connected at bus b in the line of higher reactance to give a
boost of 3% in voltage magnitude toward the load (a = 1.03), and (c) if the regulating transformer
advances the phase 2° (a = sinl90). Use the circulating-current method for parts (b) and (c), and
assume that Va is adjusted for each part of the problem so that Vb remains constant. Figure 8.21 is the
one-line diagram showing buses a and b of the system with the regulating transformer in place.
Neglect the impedance of the transformer.
8.13 Two reactances A", = 0.08 and X2 = 0.12 per unit are in parallel between two buses a and b in a
power system. If Va = 1.05/10° and Vb = 1.0/0° per unit, what should be the turns ratio of the regulating
transformer to be inserted in series with X2 at bus b so that no vars flow into bus b from the
branch whose reactance is A" j ? Use the circulating-current method, and neglect the reactance of the
regulating transformer. P and Q of the load and Vb remain constant.
© ©
X = >0.1
8.14 Two transformers each rated 115Y/13.2A kV operate in parallel to supply a load of 35 MVA,
13.2 kV at 0.8 power-factor lag. Transformer 1 is rated 20 MVA with X = 0.09 per unit, and trans¬
former 2 is rated 15 MVA with X =0.07 per unit. Find the magnitude of the current in per unit
through each transformer, the megavoltampere output of each transformer, and the megavolt-
amperes to which the total load must be limited so that neither transformer is overloaded. If the taps
on transformer 1 are set at 111 kV to give a 3.6% boost in voltage toward the low-tension side of
that transformer compared to transformer 2, which remains on the 115 kV tap, find the megavolt¬
ampere output of each transformer for the original 35 MVA total load and the maximum megavolt-
amperes of the total load which will not overload the transformers. Use a base of 35 MVA, 13.2 kV
on the low-tension side. The circulating-current method is satisfactory for this problem.
8.15 If the impedance of the load on bus b of the circuit described in Prob. 8.12 is 0.866 + y'0.5 per
unit, and if Va is 1.04/0° per unit (the voltage Vb and the load current no longer specified), find Vb for
the conditions described in parts (a), (b), and (c) of Prob. 8.12. Also find P and Q into bus b through
each of the parallel branches in all three cases. Equations (8.39) should be used in this problem, and
the load impedance can be included in Y22 of the node admittance equations of the complete circuit.
CHAPTER
NINE
ECONOMIC OPERATION OF POWER SYSTEMS
An engineer is always concerned with the cost of products and services. For a
power system to return a profit on the capital invested, proper operation is very
important. Rates fixed by regulatory bodies and the importance of conservation
of fuel place extreme pressure on power companies to achieve maximum
efficiency of operation and to improve efficiency continually in order to maintain
a reasonable relation between cost of a kilowatthour to a consumer and the cost
to the company of delivering a kilowatthour in the face of constantly rising
prices for fuel, labor, supplies, and maintenance.
Engineers have been very successful in increasing the efficiency of boilers,
turbines, and generators so continuously that each new unit added to the gener¬
ating plants of a system operates more efficiently than any older unit on the
system. In operating the system for any load condition the contribution from
each plant and from each unit within a plant must be determined so that the cost
of delivered power is a minimum. How the engineer has met and solved this
challenging problem is the subject of this chapter.
An early method of attempting to minimize the cost of delivered power
called for supplying power from only the most efficient plant at light loads. As
load increased, power would be supplied by the most efficient plant until the
point of maximum efficiency of that plant was reached. Then for further increase
in load the next most efficient plant would start to feed power to the system, and
a third plant would not be called upon until the point of maximum efficiency of
the second plant was reached. Even with transmission losses neglected this
method fails to minimize cost.
We shall study first the most economic distribution of the output of a plant
between the generators, or units, within the plant. Since system generation is
often expanded by adding units to existing plants, the various units within a
plant usually have different characteristics. The method that will be developed is
also applicable to economic scheduling of plant outputs for a given loading of
the system without consideration of transmission losses. We shall proceed to
227
228 ELEMENTS OF POWER SYSTEM ANALYSIS
To determine the economic distribution of load between the various units con¬
sisting of a turbine, generator, and steam supply the variable operating costs of
the unit must be expressed in terms of the power output. Fuel cost is the
principal factor in fossil-fuel plants, and cost of nuclear fuel can also be ex¬
pressed as a function of output. Most of our electric energy will continue to
come from fossil and nuclear fuels for many years until other energy sources are
able to assume some of the task. We shall base our discussion on the economics
of fuel cost with the realization that other costs which are a function of power
output can be included in the expression for fuel cost. A typical input-output
curve which is a plot of fuel input for a fossil-fuel plant in Btu per hour versus
power output of the unit in megawatts is shown in Fig. 9.1. The ordinates of the
curve are converted to dollars per hour by multiplying the fuel input by the cost
of fuel in dollars per million Btu.
If a line is drawn through the origin to any point on the input-output curve,
the reciprocal of the slope can be expressed in megawatts divided by input in
millions of Btu per hour, or the ratio of energy output in megawatthours to fuel
input measured in millions of Btu. This ratio is the fuel efficiency. Maximum
efficiency occurs at that point where the slope of the line from the origin to a
point on the curve is a minimum, that is, at the point where the line is tangent to
ECONOMIC OPERATION OF POWER SYSTEMS 229
the curve. For the unit whose input-output curve is shown in Fig. 9.1, the maxi¬
mum efficiency is at an output of approximately 280 MW, which requires an
input of 2.8 x 109 Btu/h. The fuel requirement is 10.0 x 106 Btu/MWh. By
comparison, when the output of the unit is 100 MW, the fuel requirement is
11.0 x 106 Btu/MWh.
Of course the fuel requirement for a given output is easily converted into
dollars per megawatthour. As we shall see, the criterion for distribution of the
load between any two units is based upon whether increasing the load on one
unit as the load is decreased on the other unit by the same amount results in an
increase or decrease in total cost. Thus, we are concerned with incremental cost,
which is determined by the slopes of the input-output curves of the two units. If
we express the ordinates of the input-output curve in dollars per hour and let
Fn = input to unit n, dollars per hour
Pn = output of unit n, MW
the incR “'ental fuel cost of the unit in dollars per megawatthour is dFn/dPn.
Incre lental fuel cost for a unit for any given power output is the limit of the
ratio of the increase in cost of fuel input in dollars per hour to the corresponding
increase in power output in megawatts as the increase in power output
approaches zero. Approximately, the incremental fuel cost could be obtained by
determining the increased cost of fuel for a definite time interval during which
the power output is increased by a small amount. For instance, the approximate
incremental cost at any particular output is the additional cost in dollars per
hour to increase the output by 1 MW. Actually incremental cost is determined
by measuring the slope of the input-output curve and multiplying by cost per
Btu in the proper units. Since mills (tenths of a cent) per kilowatthour are equal
to dollars per megawatthour, and since a kilowatt is a very small amount of
power in comparison with the usual output of a unit of a steam plant, incremen¬
tal fuel cost may be considered to be the cost of fuel in mills per hour to supply
an additional kilowatt output.
A typical plot of incremental fuel cost versus power output is shown in
Fig. 9.2. This figure is obtained by measuring the slope of the input-output curve
of Fig. 9.1 for various outputs and applying a fuel cost of $1.30 per million Btu.
However, the cost of fuel in terms of Btu is not very predictable, and the reader
should not assume that cost figures throughout this chapter are applicable at
any particular time. Figure 9.2 shows that incremental fuel cost is quite linear
with respect to power output over an appreciable range. In analytical work the
curve is usually approximated by one or two straight lines. The dashed line in
the figure is a good representation of the curve. The equation of the line is
dF
—- = 0.0126 P + 8.9
dPn
so that when the power output is 300 MW, the incremental cost determined by
the linear approximation is $12.68 per megawatthour. This value is the approxi¬
mate additional cost per hour of increasing the output by 1 MW and the saving
230 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 9.2 Incremental fuel cost versus power output for the unit whose input-output curve is shown
in Fig. 9.1.
in cost per hour of reducing the output by 1 MW. The actual incremental cost at
300 MW is $12.50 per megawatthour, but this power output is near the point of
maximum deviation between the actual value and the linear approximation of
incremental cost. For greater accuracy two straight lines may be drawn to repre¬
sent this curve in its upper and lower range.
We now have the background to understand the guiding principle for dis¬
tributing the load among the units within a plant. For instance, suppose that the
total output of a plant is supplied by two units and that the division of load
between these units is such that the incremental fuel cost of one is higher than
that of the other. Now suppose that some of the load is transferred from the unit
with the higher incremental cost to the unit with the lower incremental cost.
Reducing the load on the unit with the higher incremental cost will result in a
greater reduction of cost than the increase in cost for adding that same amount
of load to the unit with the lower incremental cost. The transfer of load from one
to the other can be continued with a reduction in total fuel cost until the
incremental fuel costs of the two units are equal. The same reasoning can be
extended to a plant with more than two units. Thus the criterion for economical
division of load between units within a plant is that all units must operate at the
same incremental fuel cost. If the plant output is to be increased, the incremental
cost at which each unit operates will rise but must remain the same for all.
The criterion which we have developed intuitively can be found mathema¬
tically. For a plant with K units, let
where FT is the total fuel cost and PR is the total power received by the plant bus
and transferred to the power system. The fuel costs of the individual units are F1?
•••» Fk wdh corresponding outputs Pu P2, PK. Our objective is to
obtain a minimum FT for a given PR, which requires that the total differential
dFT = 0. Since total fuel cost is dependent on the power output of each unit
dFj
dFT = ^dP1+^~dP2 + dPk = 0 (9.3)
dP i dP, dP>
With total fuel cost FT dependent upon the various unit outputs, the require¬
ment of constant PR means that Eq. (9.2) is a constraint on the minimum value
of Ft. The restriction that PR remain constant requires that dPR = 0, and so
dP i + dP + ■ ■ ■ T dPR — 0
2 (9.4)
Multiplying Eq. (9.4) by X and subtracting the resulting equation from Eq. (9.3)
yields, when terms are collected.
dFT dFT
dP i + dP f ‘ ” T
2 X dPk- = 0 (9.5)
8P~i dP~K
This equation is satisfied if each term is equal to zero. Each partial derivative
becomes a full derivative since only the fuel cost of any one unit will vary if only
the power output of that unit is varied. For example dFT/dPK becomes
dFK/dPK. Equation (9.5) is satisfied if
dF i _ ^ dF 2 _ dFK,
dp[~ ,dF2 ~ ,'",dFK ~
and so all units must operate at the same incremental fuel cost X for minimum
cost in dollars per hour. Thus we have proved mathematically the same criterion
which we reached intuitively. The procedure is known as the method of lagran-
gian multipliers. We shall need this mathematical method when we consider the
effect of transmission losses on the distribution of loads between several plants
to achieve minimum fuel cost for a specified loading of a power system.
When the incremental fuel cost of each of the units in a plant is nearly linear
with respect to power output over a range of operation under consideration,
equations that represent incremental fuel costs as linear functions of power
output will simplify the computations. A schedule for assigning loads to each
unit in a plant can be prepared by assuming various values of X, obtaining the
corresponding outputs of each unit, and adding outputs to find plant load for
each assumed X. A curve of X versus plant load establishes the value of X at
which each unit should operate for a given total plant load. If maximum and
minimum loads are specified for each unit, some units will be unable to operate
at the same incremental fuel cost as the other units and still remain within the
limits specified for light and heavy loads.
Example 9,1 Incremental fuel costs in dollars per megawatthour for a plant
consisting of two units are given by
Assume that both units are operating at all times, that total load varies from
250 to 1250 MW, and that maximum and minimum loads on each unit are
to be 625 and 100 MW, respectively. Find the incremental fuel cost and the
allocation of load between units for the minimum cost of various total loads.
Solution At light loads unit 1 will have the higher incremental fuel cost
and will operate at its lower limit of 100 MW for which dFj jdPx is $8.8 per
megawatthour. When the output of unit 2 is also 100 MW, dF2/dP2 is $7.36
per megawatthour. Therefore, as plant output increases, the additional load
should come from unit 2 until dF2/dP2 equals $8.8 per megawatthour. Until
that point is reached the incremental fuel cost 2 of the plant is determined by
unit 2 alone. When the plant load is 250 MW, unit 2 will supply 150 MW
with dF2/dP2 equal to $7.84 per megawatthour. When dF2/dP2 equals $8.8
per megawatthour
0.0096P2 + 6.4 = 8.8
2.4
P2 = 250 MW
0.0096
and the total plant output is 350 MW. From this point on the required
output of each unit for economic load distribution is found by assuming
various values of X and calculating each unit’s output and the total plant
output. Results are shown in Table 9.1.
Figure 9.3 shows plant X plotted versus plant output. We note in Table
9.1 that at X = 12.4, unit 2 is operating at its upper limit, and that additional
load must come from unit 1, which then determines the plant X.
If we wish to know the distribution of load between the units for a plant
output of 1000 MW, we could plot the output of each individual unit versus
plant output as shown in Fig. 9.4 from which each unit’s output can be read
for any plant output. A digital computer could easily determine the correct
pl + p2= 1000
and
P1 = 454.55 MW
P2 = 545.45 MW
Plant output, MW
Figure 9.4 Output of each unit versus plant output for economical operation of the plant of
Example 9.1.
234 ELEMENTS OF POWER SYSTEM ANALYSIS
and for each unit X = 11.636. Such accuracy, however, is not necessary-be-
cause of the uncertainty in determining costs and the use of an approximate
equation in this example to express the incremental costs.
The savings effected by economic distribution of load rather than some
arbitrary distribution can be found by integrating the expression for in¬
cremental fuel cost and comparing increases and decreases of cost for the
units as load is shifted from the most economical allocation.
Example 9.2 Determine the saving in fuel cost in dollars per hour for the
economic distribution of a total load of 900 MW between the two units of
the plant described in Example 9.1 compared with equal distribution of the
same total load.
Solution Example 9.1 shows that unit 1 should supply 400 MW and unit 2
should supply 500 MW. If each unit supplies 450 MW, the increase in cost
for unit 1 is
450
0.004P\ + 8 P1 = $570 per hour
400
Plant 1 Plant 2
a a o
©
increasing it at the plant with the higher incremental cost. To coordinate trans¬
mission loss in the problem of determining economic loading of plants, we need
to express the total transmission loss of a system as a function of plant loadings.
Determining the transmission loss in a simple system consisting of two
generating plants and one load will help us see the principles involved in express¬
ing loss in terms of power output of the plants.! Figure 9.5 shows such a
system. If Ra, Rb, and Rc are the resistances of lines a, b, and c, respectively, the
total loss for the three-phase transmission system is
Pi (9.10)
I'll = v^lFil pf, and /,! =
v/3|ni/>/2
R, B-b + Rc
Pl = Pl , f+2 PtP2 + P\
KrlW ' “ * WIVlWMl) V2\2(pf2)1
t For a simple discussion of loss formulas in a manner similar to our approach, see D. C. Harker,
A Primer on Loss Formulas, Trans. AIEE, vol. 77, pt. Ill, 1958, pp. 1434-1436.
236 ELEMENTS OF POWER SYSTEM ANALYSIS
where
Ra + Rc
5n =
W1?
R,
B12 '
(9.12)
V1\\V2\(pf1)(pf2)
+ Fc
B22 ~
V7\2 (pfif
The terms Blx, B12, and B22 are called loss coefficients or B coefficients. If the
voltages in Eq. (9.12) are line-to-line kilovolts with resistances in ohms, the units
for the loss coefficients are reciprocal megawatts. Then, in Eq. (9.11), with three-
phase powers Px and P2 in megawatts, PL will be in megawatts also. Of course,
the computations may be made in per unit.
For the system for which they are derived and the assumption of I x and 12
in phase, these coefficients yield the exact loss by Eq. (9.11) only for the particu¬
lar values of Px and P2 which result in the voltages and power factors used in
Eqs. (9.12). The B coefficients are constant, as Px and P2 vary, only insofar as
bus voltages at the plants maintain constant magnitude and plant power factors
remain constant. Fortunately, the use of constant values for the loss coefficients
in Eq. (9.11) yields reasonably accurate results when the coefficients are cal¬
culated for some average operating condition and if extremely wide shifts of load
between plants or in total load do not occur. In practice large systems are
economically loaded by calculations based on several sets of loss coefficients
depending on load conditions.t
Example 93 For the system whose one-line diagram is shown in Fig. 9.5,
assume I x = 1.0/0° per unit and I2 = 0.8/0° per unit. If the voltage at bus 3
is V3 — 1.0/0° per unit, find the loss coefficients. Line impedances are 0.04 +
;0.16 per unit, 0.03 + ;'0.12 per unit, and 0.02 + /0.08 per unit for sections a,
b, and c, respectively.
Solution Ordinarily load currents and bus voltages are available from load
studies. For this problem bus voltages can be calculated from the data given:
t For two of many sources of further information see L. K. Kirchmayer, Economic Operation of
Power Systems, John Wiley and Sons, Inc., New York, 1958; W. S. Meyer and V. D. Albertson,
Improved Loss Formula Computation by Optimally Ordered Elimination Techniques, IEEE
Trans. Power Appar. Syst., vol. 90, 1971, pp. 716-731. Also see the footnotes in Sec. 9.4 for a method
used by a number of companies.
ECONOMIC OPERATION OF POWER SYSTEMS 237
magnitude times power factor equals the real part of the complex expression
for voltage. Therefore
n 0.04 + 0.02
Bi i =-— = 0.0554 per unit
Example 9.4 Calculate the transmission loss for Example 9.3 by the loss
formula of Eq. (9.11), and check the result.
Solution Source powers are ordinarily available from the load study for
the operating condition used to calculate loss coefficients. For this problem
Pj and P2 must be calculated.
Exact agreement between methods is expected since the loss coefficients were
determined for the condition for which loss was calculated. The amount of
error introduced by using the same loss coefficients for two other operating
conditions may be seen by examining the results shown in Table 9.2.
Pi. by
loss
coeffi¬
h P2 cients PL byI2R Conditions
The general form of the loss equation for any number of sources is
m n
<913>
where and indicate independent summations to include all sources. For
instance, for three sources,
PL = PTBP (9.15)
1
0., ^ ••
Bn B12 B13 • Bu
-H
B2i • BU
<N
B22 B23
p = and B =
Ft is now the total cost of all the fuel for the entire system and is the sum of the
fuel costs of the individual plants Fu F2,..., FK. The total input to the network
from all the plants is
where Pu P2, ..., PK are the individual plant inputs to the network. The total
fuel cost of the system is a function of the power inputs. The constraining
relation on the minimum value of FT is
Z,P,-PL-PR= 0 (9.18)
n= 1
where PR is the total power received by the loads on the system and PL is the
transmission loss expressed as a function of the loss coefficients and the power
ECONOMIC OPERATION OF POWER SYSTEMS 239
input to the network from each plant. Since PR is constant, dPR = 0; therefore
K
K dF
dFr=YJ~~ dPn = 0 (9.20)
n=1 crn
dFT .dPL
X\dP = 0 (9.22)
SPn dPn
This equation is satisfied provided that
dFT dJ\
+ A X=0 (9.23)
Wn 8P„
for every value of n. Rearranging Eq. (9.23) and recognizing that changing the
output of only one plant can affect the cost at only that plant, we have
dF„ 1
= X (924)
dPn l - dPL/dPn
or
dF n
(925)
dPnLn~
where Ln is called the penalty factor of plant n and
i,=_I_ (926)
” i - spjdp.
The multiplier X is in dollars per megawatthour when fuel cost is in dollars per
hour and power is in megawatts. The result is analogous to that for scheduling
units within a plant. Minimum fuel cost is obtained when the incremental fuel
cost of each plant multiplied by its penalty factor is the same for all plants in the
system. The products are equal to X, which is called the system X and is approxi¬
mately the cost in dollars per hour to increase the total delivered load by 1 MW.
For a system of three plants, for instance,
dF, r dF 2 r dF3
Lr, = X (9.27)
dP^1 ~ dP2Ll~ dP3
The transmission loss PL is expressed by Eq. (9.13). For K plants partial
differentiation with respect to Pn yields
dP,
X ep.v. / j pmBn
2 y m rt (9.28)
dP„ dP n m=1 n=1 m= 1
240 ELEMENTS OF POWER SYSTEM ANALYSIS
The simultaneous equations obtained by writing Eq. (9.24) for each plqqt of
the system can be solved by assuming a value for X. Economical loading for each
plant is found for the assumed X. By solving the equations for several values of X,
data are found for plotting generation at each plant against total generation. If
transmission loss is calculated for each X, plant outputs can be plotted against
total received load. If fixed amounts of power are transferred over tie lines with
other systems or received from hydro stations, the distribution of the remaining
load among the other plants is affected by the changes in transmission loss
brought about by the flow through these additional points of entry to the
system. No new variables are introduced, but additional loss coefficients are
required. For instance, a system having five steam plants, three hydro plants, and
seven interconnections would require a 15 x 15 matrix of loss coefficients, but
the only unknowns to be found for any given X would be the five inputs to the
system from the steam plants.
SPl
= 2PlBll + 2P2Bl2 = 0.0008 Px
dP 1
dP2
= 2P 2B22 + 2Pj Bl2 = 0
W,
Penalty factors are
1
Li = and L-, = 1.0
1 - 0.0008Pj
ECONOMIC OPERATION OF POWER SYSTEMS 241
For X = 12.5
0.010^+8.5
1 - O.OOO8P1
P, = 200 MW
P2 = 200 MW
PL = 0.0004 x 2002 = 16 MW
and the delivered load is
Example 9.6 For the system of Example 9.5 with 384 MW received by the
load, find the savings in dollars per hour obtained by coordinating rather
than neglecting the transmission loss in determining the load of the plants.
Pi + P2 — 0.0004P? = 384
Solving these two equations for Pl and P2 gives the following values for
plant generation with losses not coordinated:
The load on plant 1 is increased from 200 to 290.7 MW. The increase in
fuel cost is
290.7
0.010
P\ + 8.5Pi
200
The load on plant 2 is decreased from 200 to 127.1 MW. The decrease
(negative increase) in cost for plant 2 is
. 127.1 omsp2 127.1
dj\= £ dP^ddi
(9.29)
dPn ,4 d6jdPn
where 9j is the phase angle of the voltage at node j in a system of N buses. If bus
voltages are assumed constant, it can be shown that in terms of voltage phase
angles,
N
dP_L
= 21 Vk\Gjk sin (9k 0j) (9.30)
d9j k= 1
where Gjk is the real part of Yjk of the bus admittance matrix. The difficulty with
Eq. (9.29) is in expressing d9j/dPn; direct differentiation is impossible because
voltage phase angles cannot be expressed in terms of plant generated powers.
The terms d9j/dPn remain quite constant for changes in load levels and
system generation schedules. Since the terms express a Change in the voltage
phase angles 9j for a change in plant generation Pn with all other plant genera¬
tion remaining constant, these terms can be approximated very closely through
load-flow studies. For some typical load pattern the total received load is in¬
creased by increasing each individual load by the same small amount, say 5%.
The change in total received power plus losses is provided by one plant n while
other plant outputs are held constant. The changes in each voltage phase angle
9j are determined, and the ratios of change in phase angle to change in plant
input to the system A9j/AP„ are found for all values of j for plant rt. The
load-flow program of the digital computer is used and the process is repeated for
every plant supplying the load change in turn. A set of Ain coefficients is found
where
Ain = J (9.31)
Jn A Pn
Then incremental loss for plant n is given by
1 N N d2P
Bmn ~ 2 ;?! ;?! d0t 86j ^'33^
Computer control of the output of each plant and of each unit within a plant is
common practice in power-system operation. By continually monitoring all
plant outputs and the power flowing in interconnections interchange of power
with other systems is controlled. Most control systems are digital or a combina¬
tion of digital and analog. In this section we shall consider one of a variety of
ways in which computer control is accomplished.
In discussing control the term area means that part of an interconnected
system in which one or more companies control their generation to absorb all
their own load changes and maintain a prearranged net interchange of power
with other areas for specified periods. Monitoring the flow of power on the tie
lines between areas determines whether a particular area is absorbing satisfac¬
torily all the load changes within its own boundaries. The function of the com¬
puter is to require the area to absorb its own load changes, to provide the agreed
t See E. F. Hill and W. D. Stevenson, Jr., A New Method of Determining Loss Coefficients, IEEE
Trans. Power Appar. Syst., vol. PAS-87, July 1968, pp. 1548-1552.
244 ELEMENTS OF POWER SYSTEM ANALYSIS
Total actual
generation
Figure 9.6 Block diagram to illustrate the operation of a computer controlling a particular area.
+ Subtraction of standard or reference value from actual value to obtain the error is the accepted
convention of power-system engineers and is the negative of the definition of control error found in
the literature of control theory.
ECONOMIC OPERATION OF POWER SYSTEMS 245
A negative ACE means that the area is not generating enough power to send the
desired amount out of the area. There is a deficiency in net power output.
Without frequency bias the indicated deficiency would be less because there
would be no positive offset BAf added to Ps (subtracted from Pa) when actual
frequency is less than scheduled frequency and the ACE would be less. The area
would produce sufficient generation to supply its own load and the prearranged
interchange but would not provide the additional output to assist neighboring
interconnected areas to raise the frequency.
Station control error (SCE) is the amount of actual generation of all the area
plants minus the desired generation as indicated at position 6 of the diagram.
This SCE is negative when desired generation is greater than existing generation.
The key to the whole control operation is the comparison of ACE and SCE.
Their difference is an error signal, as indicated at position 7 of the diagram. If
ACE and SCE are negative and equal, the deficiency in the output from the area
equals the excess of the desired generation over the actual generation and no
error signal is produced. However this excess of desired generation will cause a
signal indicated at position 11 to the plants to increase their generation to
reduce the magnitude of the SCE, and the resulting increase in output from the
area will reduce the magnitude of the ACE at the same time.
If ACE is more negative than SCE, there will be an error signal to increase
the X of the area and this increase will in turn cause the desired plant generation
to increase (position 9). Each plant will receive a signal to increase its output as
determined by the principles of economic dispatch.
This discussion has considered specifically only the case of scheduled net
interchange out of the area (positive scheduled net interchange) greater than
actual net interchange with ACE equal to or more negative than SCE. The
reader should be able to extend the discussion to the other possibilities by
referring to Fig. 9.6.
Position 10 on the diagram indicates the computation of penalty factors for
each plant. Here the B coefficients are stored to calculate dPJdP,,. Non-
conforming loads, plants where generation is not to be allowed to vary, and
tie-line loading enter the calculation of penalty factors. The penalty factors are
transmitted to the section (position 9) which calculates the individual plant
generation to provide with economic dispatch the total desired plant generation.
One other point of importance (not indicated on Fig. 9.6) is the offset in
246 ELEMENTS OF POWER SYSTEM ANALYSIS
PROBLEMS
9.1 For a certain generating unit in a plant the fuel input in millions of Btu per hour expressed as a
function of power output F in megawatts is
(a) Determine the equation for incremental fuel cost in dollars per megawatthour as a function of
power output in megawatts based on a fuel cost of $1.40 per million Btu.
(b) Find the equation for a good linear approximation of incremental fuel cost as a function of power
output over a range of 20 to 120 MW.
(c) What is the average cost of fuel per megawatthour when the plant is delivering 100 MW?
(d) What is the approximate additional fuel cost per hour to raise the output of the plant from 100
to 101 MW?
9.2 The incremental fuel costs for two units of a plant are
where F is in dollars per hour and P is in megawatts. If both units operate at all times and maximum
and minimum loads on each unit are 625 and 100 MW, plot A in dollars per megawatthour versus
plant output in megawatts for lowest fuel cost as total load varies from 200 to 1250 MW.
9.3 Find the savings in dollars per hour for economical allocation of load between the units of
Prob. 9.2 compared with their sharing the output equally when the total output is 750 MW.
9.4 A plant has two generators supplying the plant bus, and neither is to operate below 100 MW or
above 625 MW. Incremental costs with F, and P2 in megawatts are
dF
= 0.012F1 + 8.0 $/MWh
For economic dispatch find the plant A when Ft + P2 equals (a) 200 MW, (b) 500 MW, and
(c) 1150 MW.
9.5 Calculate the power loss in the system of Example 9.3 by the loss coefficients of the example and
by | /121R | for / j = 1.5/01 per unit and I2 = 1.2/01 per unit. Assume V3 = l.O/Ol per unit.
9.6 Find the loss coefficients that will give the true power loss for the system of Example 9.3 for
/ j = 0.8/01 per unit, I2 = 0.8/01 per unit, and V3 = 1.0/01 per unit.
9.7 A power system has only two generating plants, and power is being dispatched economically
with F, = 140 MW and P2 = 250 MW. The loss coefficients are:
To raise the total load on the system by 1 MW will cost an additional $12 per hour. Find (a) the
penalty factor for plant 1, and (b) the additional cost per hour to increase the output of this plant by
1 MW.
9.8 On a system consisting of two generating plants the incremental costs in dollars per megawatt-
hour with Pl and P2 in megawatts are
dF. dF2
= 0.008P. + 8.0 —- =0.012P2 +9.0
dP2 dP2
The system is operating on economic dispatch with Pt = P2 = 500 MW and SPL/dP.2 = 0.2. Find
the penalty factor of plant 1.
9.9 A power system is operating on economic load dispatch with a system 2 of $12.5 per megawatt-
hour. If raising the output of plant 2 by 100 kW (while other outputs are kept constant) results in
increased | /121R | losses of 12 kW for the system, what is the approximate additional cost per hour
if the output of this plant is increased by 1 MW?
9.10 A power system is supplied by only two plants, both of which are operating on economic
dispatch. At the bus of plant 1 the incremental cost is $11.0 per megawatthour, and at plant 2 is $10.0
per megawatthour. Which plant has the higher penalty factor? What is the penalty factor of plant 1 if
the cost per hour of increasing the load on the system by 1 MW is $12.5?
9.11 Calculate the values listed below for the system of Example 9.5 with system X = $13.5 per
megawatthour. Assume fuel costs at no load of $200 and $400 per hour for plants 1 and 2,
respectively.
(a) Pj, P2, and power delivered to the load for economic dispatch with transmission loss
coordinated.
(b) P, and P2 for the value of power delivered to the load found in part (u) but with transmission
loss not coordinated. Transmission loss must be included, however, in determining the total
power input to the system.
(c) Total fuel cost in dollars per hour for parts (a) and (b).
CHAPTER
TEN
SYMMETRICAL THREE-PHASE FAULTS
The selection of a circuit breaker for a power system depends not only upon the
current the breaker is to carry under normal operating conditions but also upon
the maximum current it may have to carry momentarily and the current it may
have to interrupt at the voltage of the line in which it is placed.
t For a book devoted entirely to fault studies see P. M. Anderson, Analysis of Faulted Power
Systems, Iowa State University Press, Ames, Iowa, 1973.
248
SYMMETRICAL THREE-PHASE FAULTS 249
i I
\ Time
Figure 10.1 Current as a function of time in an Figure 10.2 Current as a function of time in an
RL circuit for a - 6 = 0, where 0 = tan_1 RL circuit for a - 6 = - nil, where 6 = tan “1
(coL/R). The voltage is Fmaxsin (cot + a) applied (coL/R). The voltage is Fmax sin (cot + a)
at t = 0. applied at t = 0.
250 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 10.3 Current as a function of time for a synchronous generator short-circuited while running
at no load. The unidirectional transient component of current has been eliminated in redrawing the
oscillogram.
SYMMETRICAL THREE-PHASE FAULTS 251
accounts for the reduction of flux due to armature reaction and applies to the
steady-state condition after the dc transient has disappeared and after the ampli¬
tude of the wave shown in Fig. 10.3 has become constant. When a short circuit
occurs at the terminals of a synchronous machine, time is required for
the reduction in flux across the air gap. As the flux diminishes, the armature
current decreases because the voltage generated by the air-gap flux determines
the current which will flow through the resistance and leakage reactance of
the armature winding.
t For a more complete discussion see C. F. Wagner, “ Machine Characteristics,” in Central Station
Engineers of the Westinghouse Electric Corporation, Electrical Transmission and Distribution Refer¬
ence Book, 4th ed., Chap. 6, pp. 145-194, East Pittsburgh, Pa., 1964; and A. E. Fitzgerald, C. Kings¬
ley, and A. Kusko, Electric Machinery, 3d ed., pp. 312-319, 479-492, McGraw-Hill Book Company,
New York, 1971.
252 ELEMENTS OF POWER SYSTEM ANALYSIS
sustained value represented by oa, as shown in Fig. 10.4. The straight-line por¬
tion of this curve is extended to the zero-time axis, and the intercept is added to
the maximum instantaneous value of the sustained current to obtain the maxi¬
mum instantaneous value of transient current corresponding to ob in Fig. 10.3.
The rms value of the current determined by the intercept of the current
envelope with zero time is called the subtransient current | I" |. In Fig. 10.3 the
subtransient current is 0.707 times the ordinate oc. Subtransient current is often
called the initial symmetrical rms current, which is more descriptive because it
conveys the idea of neglecting the dc component and taking the rms value of the
ac component of current immediately after the occurrence of the fault. Direct-
axis subtransient reactance X'J for an alternator operating at no load before the
occurrence of a three-phase fault at its terminals is | Eg \/ | 7" |.
The currents and reactances discussed above are defined by the following
equations, which apply to an alternator operating at no load before the occur¬
rence of a three-phase fault at its terminals:
oa \E„\
I' xd
(10.3)
ob 1 E,\
\r X’d
(10.4)
r, OC |E,I (10.5)
X*4
SYMMETRICAL THREE-PHASE FAULTS 253
Generator 1: v*
75,000
X* 0.25 = 0.375 per unit
50,000
66
E,i 69
= 0.957 per unit
Generator 2:
75,000
x2 0.25
25,000
= 0.750 per unit
66
— - 0.957 per unit
69
Transformer:
X = 0.10 per unit
Figure 10.6 shows the reactance diagram before the fault. A three-phase fault
at P is simulated by closing switch S. The internal voltages of the two
machines may be considered to be in parallel since they must be identical in
magnitude and phase if no circulating current flows between them. The
equivalent parallel subtransient reactance is
0.375 x 0.75
= 0.25 per unit
0.375 + 0.75
Therefore, as a phasor with Eg as reference, the subtransient current in the
short circuit is
0.957
/" —y'2.735 per unit
;0.25 + ;0.10
The voltage on the delta side of the transformer is
n 0.957 - 0.274
i2 —y'0.912 per unit
70.75
To find the current in amperes, the per-unit values are multiplied by the
base current of the circuit:
Although machine reactances are not true constants of the machine and
depend on the degree of saturation of the magnetic circuit, their values usually
lie within certain limits and can be predicted for various types of machines.
Table A.4 gives typical values of machine reactances that are needed in making
fault calculations and in stability studies. In general, subtransient reactances of
generators and motors are used to determine the initial current flowing on the
occurrence of a short circuit. For determining the interrupting capacity of circuit
breakers, except those which open instantaneously, subtransient reactance is
used for generators and transient reactance is used for synchronous motors. In
stability studies where the problem is to determine whether a fault will cause a
machine to lose synchronism with the rest of the system if the fault is removed
after a certain time interval, transient reactances apply.
e; = v,+jilxj (10.6)
256 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 10.7 Equivalent circuits for a generator supplying a balanced three-phase load. Application of
a three-phase fault at P is simulated by closing switch S. (a) Usual steady-state generator equivalent
circuit with load. (b) Circuit for calculation of I".
and this equation defines E", which is called the subtransient internal voltage.
Similarly when calculating transient current /' which must be supplied through
the transient reactance X'd the driving voltage is the transient internal voltage E'g,
where
Eg — Vt + jILX'd (10.7)
Voltages Eg and E'g are determined by IL and are both equal to the no-load
voltage Eg only when IL is zero, at which time Eg is equal to Vt.
At this point it is important to note that £" in series with Xd represents the
generator before the fault occurs and immediately after the fault only if the
prefault current in the generator is IL. On the other hand, Eg in series with
the synchronous reactance Xs is the equivalent circuit of the machine under
steady-state conditions for any load. For a different value of IL in the circuit of
Fig. 10.7 Eg would remain the same but a new value of £" would be required.
Synchronous motors have reactances of the same type as generators. When
a motor is short-circuited, it no longer receives electric energy from the power
line, but its field remains energized and the inertia of its rotor and connected
load keeps it rotating for an indefinite period. The internal voltage of a
synchronous motor causes it to contribute current to the system, for it is then
acting like a generator. By comparison with the corresponding formulas for a
generator, the subtransient internal voltage and transient internal voltage for a
synchronous motor are given by
E’m=Vt-jILX: (10.8)
Systems that contain generators and motors under load may be solved either
by Thevenin’s theorem or by the use of transient or subtransient internal vol¬
tages, as is illustrated in the following examples.
Example 10.2 A synchronous generator and motor are rated 30,000 kVA,
13.2 kV, and both have subtransient reactances of 20%. The line connecting
SYMMETRICAL THREE-PHASE FAULTS 257
them has a reactance of 10% on the base of the machine ratings. The motor
is drawing 20,000 kW at 0.8 power factor leading and a terminal voltage of
12.8 kV when a symmetrical three-phase fault occurs at the motor terminals.
Find the subtransient current in the generator, motor, and fault by using the
internal voltage of the machines.
12 8
vf =
- 0.97/0° per unit
13.2
30,000
Base current = = 1312 A
V3 x 13.2
20,000 /36.9°
4 =
0.8 x V3 x 12.8
= 1128 /36.9° A
1128 736.9
0.86 736.9° per unit
1312
0.814 + yO.207
/" = = 0.69 - 72.71 per unit
19
70.3
In the fault,
r = i/
~ z„ + Z», +jXj)
zL(zm+jx:)
(10.10)
Zth
*6 sN
Figure 10.9 Thevenin equivalent of the circuit of Fig. 10.7b.
SYMMETRICAL THREE-PHASE FAULTS 259
Solution
/0.3 x j0.2
= j0.12 per unit
j0.3 + j0.2
In the fault,
„ _ 0-97 + jO
—j8.08 per unit
f jO.12
Figure 10.10 Circuits illustrating the application of the superposition theorem to determine the
proportion of the fault current in each branch of the system.
260 ELEMENTS OF POWER SYSTEM ANALYSIS
the branch after the fault. Applying the above principle to the present
example gives
i03
Fault current from motor = —j8.08 x —y'4.85 per unit
jO.5
To these currents must be added the prefault current IL to obtain the total
subtransient currents in the machines:
Note that IL is in the same direction as /" but opposite to /". The per-unit
values found for I"f, /", and /" are the same as in Example 10.2, and so the
ampere values will also be the same.
Usually load current is omitted in determining the current in each line
upon the occurrence of a fault. In the Thevenin method neglect of load
current means that the prefault current in each line is not added to the
component of current flowing toward the fault in the line. The method of
Example 10.2 neglects load current if the subtransient internal voltages of all
machines are assumed equal to the voltage Vf at the fault before the fault
occurs, for such is the case if no current flows anywhere in the network prior
to the fault.
Neglecting load current in Example 10.3 gives
The current in the fault is the same whether or not load current is con¬
sidered, but the contributions from the lines differ. When load current is
included, we find from Example 10.2
The arithmetic sum of the generator and motor current magnitudes does not
equal the fault current because the currents from the generator and motor
are not in phase.
SYMMETRICAL THREE-PHASE FAULTS 261
Ea j 0.2 j 0.1 _
i_
_1
-1
when the superscript A indicates that the voltages are due only to — Vf. The A
sign is chosen to indicate the change in voltage due to the fault.
By inverting the bus admittance matrix of the network of Fig. 10.12 we
obtain the bus impedance matrix. The bus voltages due to — Vf are given by
1_
0 '
Vj 0
^bus
(10.12)
_1
1
Vi 0
1
and so
(10.13)
and
'14
VA1 — T" 7
i/Z' 14 -
-44
VA2 (10.14)
V2 = Vf+VA2 = Vf J" 7
24
(10.15)
V3 = Vf+V*= Vf T" 7
i/z' 34
V4=Vf-Vf = 0
These voltages exist when subtransient current flows and ZbUS has been formed
for a network having subtransient values for generator reactances.
In general terms for a fault on bus k, and neglecting prefault currents,
(10.16)
K = vf- (10.17)
SYMMETRICAL THREE-PHASE FAULTS 263
Using the numerical values of Eq. (10.11), we invert the square matrix Ybus
of that equation and find
Usually Vf is assumed to be 1.0/0° per unit, and with this assumption for our
faulted network
J0.1058
K = 1 — = 0.3244 per unit
jO. 1566
Currents in any part of the network can be found from the voltages and
impedances. For instance, the fault current in the branch connecting nodes 1 and
3 flowing toward node 3 is
Vt - V3 0.3755 - 0.3244
1l"13 —
j0.25 j0.25
= -y'0.2044 per unit
From the generator connected to node 1 the current is
Other currents can be found in a similar manner, and voltages and currents
with the fault on any other bus are calculated just as easily from the impedance
matrix.
Equation (10.16) is simply an application of Thevenin’s theorem, and we
recognize that the quantities on the principal diagonal of the bus impedance
matrix are the Thevenin impedances of the network for calculating fault current
at the various buses. Power companies furnish data to a customer who must
determine the fault current to specify circuit breakers for an industrial plant or
distribution system connected to the utility system at any point. Usually the data
supplied lists the short-circuit megavoltamperes, where
With resistance and shunt capacitance neglected, the single-phase Thevenin equi¬
valent circuit which represents the system is an emf equal to the nominal line
voltage divided by y/3 in series with an inductive reactance of
(nominal kV/^/3) x 1000
X» = n (10.20)
Solving Eq. (10.19) for Isc and substituting in Eq. (10.20) yield
(nominal kV)2
(10.21)
th short-circuit MVA
If base kilovolts is equal to nominal kilovolts, converting to per unit yields
base MVA
xth = short-circuit
-:-.
MVA
per unit (10.22)
[ base
X* = per unit (10.23)
identify transfer impedances of node 4 of the bus impedance matrix. The driving-
point impedances of the bus impedance matrix are Zu, Z22, Z33, and Z44. No
current can flow in any branches when switch S is open. When S is closed,
current flows in the circuit only toward node 4. This current is Vf/Z44, which,
according to Eq. (10.13), is If for a fault on node 4. We shall interpret the
brackets to mean that the current If toward node 4 in the network induces
voltage drops of /}Z14, /}Z24, and /}Z34 in the branches connected to nodes
1, 2, and 3, respectively. These voltage drops are in the direction toward the
respective nodes.
If switch S in the circuit of Fig. 10.13 is open, all nodes will be at the voltage
of Vf, as in Fig. 10.11 if £", ££, and E” equal Vf. If S is closed, examination of
the circuit shows that the voltages at all four nodes with respect to the reference
node 0 will be the values specified by Eqs. (10.15). Therefore, if we interpret the
indicated transfer impedances of this circuit as described above, the circuit is the
equivalent of that shown in Fig. 10.11 with S open and Fig. 10.12 with switch S
closed, where we are still neglecting prefault current.
Of course, we can simulate short circuits at the other buses in a similar
manner and extend this approach to a general network having any number of
nodes. We could indicate the other transfer impedances of the equivalent circuit
by additional brackets and have not done so only because it becomes confusing
to have so many brackets to indicate the transfer impedances. In fact we shall
usually omit the brackets when drawing this network equivalent for the bus
impedance matrix, but we have to realize that the transfer impedances do exist
and must be considered in interpreting the network.
Example 10.4 Determine the bus impedance matrix for the network of
Example 8.1, for which the results of a load-flow study are shown in Fig. 8.2.
Generators at buses 1 and 3 are rated 270 and 225 MV A, respectively. The
generator subtransient reactances plus the reactances of the transformers
connecting them to the buses are each 0.30 per unit on the generator rating
as base. The turns ratios of the transformers are such that the voltage base in
each generator circuit is equal to the voltage rating of the generator. Include
the generator and transformer reactances in the matrix. Find the subtran¬
sient current in a three-phase fault at bus 4 and the current coming to the
faulted bus over each line. Prefault current is to be neglected and all voltages
are assumed to be 1.0 per unit before the fault occurs. System base is
100 MVA. Neglect all resistances.
100
Generator at bus 3: X = 0.30 x — = 0.1333 per unit
266 ELEMENTS OF POWER SYSTEM ANALYSIS
The network with admittances marked in per unit is shown in Fig. 10.14
from which the node admittance matrix is
1.0
/" - = —;4.308 per unit
y'0.2321
\
From the same short-circuit matrix we can find similar information for
faults on any of the other buses.
SYMMETRICAL THREE-PHASE FAULTS 267
Much study has been given to circuit-breaker ratings and applications and our
discussion here will give some introduction to the subject. For additional gui¬
dance necessary to specify the breakers the reader should consult the ANSI
publications listed in the footnotes which accompany this section.
The subtransient current to which we have devoted most of our attention to
this point is the initial symmetrical current and does not include the dc compo¬
nent. As we have seen, inclusion of the dc component results in a rms value of
current immediately after the fault, which is higher than the subtransient current.
For oil circuit breakers above 5 kV the subtransient current multiplied by 1.6 is
considered to be the rms value of the current whose disruptive forces the breaker
must withstand during the first half cycle after the fault occurs. This current is
called the momentary current, and for many years circuit breakers were rated in
terms of their momentary current as well as other criteria.!
The interrupting rating of a circuit breaker was specified in kilovoltamperes
or megavoltamperes. The interrupting kilovoltamperes equal ^/3 times the kilo¬
volts of the bus to which the breaker is connected times the current which the
breaker must be capable of interrupting when its contacts part. This current is,
of course, lower than the momentary current and depends on the speed of the
breaker, such as 8, 5, 3, or 1^ cycles, which is a measure of the time from the
occurrence of the fault to the extinction of the arc.
The current which a breaker must interrupt is usually asymmetrical since it
still contains some of the decaying dc component. A schedule of preferred
ratings for ac high-voltage oil circuit breakers specifies the interrupting current
ratings of breakers in terms of the component of the asymmetrical current which
is symmetrical about the zero axis. This current is properly called the required
symmetrical interrupting capability or simply the rated symmetrical short-circuit
current. Often the adjective symmetrical is omitted. Selection of circuit breakers
may also be made on the basis of total current (dc component included)-! We
shall limit our discussion to a brief treatment of the symmetrical basis of breaker
selection.
Breakers are identified by nominal-voltage class, such as 69 kV. Among
other factors specified are rated continuous current, rated maximum voltage,
voltage range factor K, and rated short-circuit current at rated maximum kilo¬
volts. K determines the range of voltage over which rated short-circuit current
times operating voltage is constant. For a 69-kV breaker having a maximum
t See G. N. Lester, “High Voltage Circuit Breaker Standards in the USA: Past, Present, and
Future,” IEEE Trans. Power Appar. Syst., vol. 93, 1974, pp. 590-600.
J See Schedules of Preferred Ratings and Related Required Capabilities for AC High-Voltage
Circuit Breakers Rated on a Symmetrical Current Basis, ANSI C37.06-1971 and Guide for Calculation
of Fault Currents for Application of AC High-Voltage Circuit Breakers Rated on a Total Current
Basis, ANSI C37.5-1979, American National Standards Institute, New York.
268 ELEMENTS OF POWER SYSTEM ANALYSIS
rated voltage of 72.5 kV, a voltage range factor K of 1.21, and a continuous
current rating of 1200 A, the rated short-circuit current at the maximum voltage
(symmetrical current which can be interrupted at 72.5 kV) is 19,000 A. This
means that the product 72.5 x 19,000 is the constant value of rated short-circuit
current times operating voltage in the range 72.5 to 60 kV since 72.5/1.21 equals
60. The rated short-circuit current at 60 kV is 19,000 x 1.21, or 23,000 A. At
lower operating voltages this short-circuit current cannot be exceeded. At 69 kV
the rated short-circuit current is
x 19,000 = 20,000 A
+ See Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current
Basis, ANSI C37.010-1972, American National Standards Institute, New York. This publication is
also IEEE Std 320-1972.
SYMMETRICAL THREE-PHASE FAULTS 269
-D-O
-D-O
Gen. -o-0:
25,000 kVA, 13.8/6.9 kV, with a leakage reactance of 10%. The bus voltage
at the motors is 6.9 kV when a three-phase fault occurs at the point P. For
the fault specified, determine (a) the subtransient current in the fault, (b) the
subtransient current in breaker A, and (c) the symmetrical short-circuit
interrupting current (as defined for circuit-breaker applications) in the fault
and in breaker A.
Solution (a) For a base of 25,000 kVA, 13.8 kV in the generator circuit,
the base for the motors is 25,000 kVA, 6.9 kV. The subtransient reactance of
each motor is
25,000
X'i = 0.20—%— = 1.0 per unit
d 5000 F
25,000
2090 A
73 x 6.9
8 x 2090 = 16,720 A
1.0 0.375
—;4.0 per unit
j0A5 X 0.625
The usual procedure is to rate all the breakers connected to a bus on the
basis of the current into a fault on the bus. In that case the short-circuit
current interrupting rating of the breakers connected to the 6.9-kV bus must
be at least
4 + 4 x 0.67 = 6.67 per unit
or
6.67 x 2090 = 13,940 A
The required capability of 13,940 A is well below 80% of 20,000 A, and the
breaker is suitable with respect to short-circuit current.
The short-circuit current could have been found by using the bus im¬
pedance matrix. For this purpose two nodes have been identified in
Fig. 10.16. Node 1 is the bus on the low-tension side of the transformer, and
node 2 is on the high-tension side. For motor reactance of 1.5 per unit
y12=no
Y22 = ~j 10 -j6.67 = -j 16.67
-12.67 10.0 ]
10.0 -16.67 J
and its inverse is
0.150 0.090
bus-;[o.090 0.114
1.0
Isc =j015 = ~/'6'67 per unit
which agrees with our previous calculations. The bus impedance matrix also
gives us the voltage at bus 2 with the fault on bus 1.
and since the admittance between nodes 1 and 2 is —710, the current into the
;“=j0^ = -/8'77perunit
Even this simple example illustrates the value of the bus impedance
matrix where the effects of a fault at a number of buses are to be studied.
Matrix inversion is not necessary, for, as we have seen in Sec. 7.7, Zbus can
be generated directly by the computer.
PROBLEMS
10.1 A 60-Hz alternating voltage having a rms value of 100 V is applied to a series RL circuit by
closing a switch. The resistance is 15 D, and the inductance is 0.12 H.
(a) Find the value of the dc component of current upon closing the switch if the instantaneous value
of the voltage is 50 V at that time.
(b) What is the instantaneous value of the voltage which will produce the maximum dc component
of current upon closing the switch?
(c) What is the instantaneous value of the voltage which will result in the absence of any dc
component of current upon closing the switch?
(d) If the switch is closed when the instantaneous voltage is zero, find the instantaneous current 0.5,
1.5, and 5.5 cycles later.
10.2 A generator connected through a 5-cycle circuit breaker to a transformer is rated 100 MV A,
18 kV, with reactances of X"d = 19%, X'd = 26%, and Xd = 130%. It is operating at no load and rated
voltage when a three-phase short circuit occurs between the breaker and the transformer. Find
(a) the sustained short-circuit current in the breaker, (b) the initial symmetrical rms current in the
breaker, and (c) the maximum possible dc component of the short-circuit current in the breaker.
10.3 The three-phase transformer connected to the generator described in Prob. 10.2 is rated
100 MVA, 240Y/18A kV, X = 10%. If a three-phase short circuit occurs on the high-tension side of
the transformer at rated voltage and no load, find (a) the initial symmetrical rms current in the
transformer windings on the high-tension side and (b) the initial symmetrical rms current in the line
on the low-tension side.
10.4 A 60-Hz generator is rated 500 MVA, 20 kV, with X"d =0.20 per unit. It supplies a purely
resistive load of 400 MW at 20 kV. The load is connected directly across the terminals of the
generator. If all three phases of the load are short-circuited simultaneously, find the initial symmetri¬
cal rms current in the generator in per unit on a base of 500 MVA, 20 kV.
10.5 A generator is connected through a transformer to a synchronous motor. Reduced to the same
base, the per-unit subtransient reactances of the generator and motor are 0.15 and 0.35, respectively,
and the leakage reactance of the transformer is 0.10 per unit. A three-phase fault occurs at the
terminals of the motor when the terminal voltage of the generator is 0.9 per unit and the output
current of the generator is 1.0 per unit at 0.8 power factor leading. Find the subtransient current in
per unit in the fault, in the generator, and in the motor. Use the terminal voltage of the generator as
the reference phasor, and obtain the solution (a) by computing the voltages behind subtransient
reactance in the generator and motor and (b) by using Thevenin’s theorem.
SYMMETRICAL THREE-PHASE FAULTS 273
10.6 Two synchronous motors having subtransient reactances of 0.80 and 0.25 per unit, respectively,
on a base of 480 V, 2000 kVA are connected to a bus. This motor bus is connected by a line having a
reactance of 0.023 fl to a bus of a power system. At the power-system bus the short-circuit megavolt-
amperes of the power system are 9.6 MVA for a nominal voltage of 480 V. When the voltage at the
motor bus is 440 V, neglect load current and find the initial symmetrical rms current in a three-phase
fault at the motor bus.
10.7 The bus impedance matrix of a four-bus network with values in per unit is
Generators are connected to buses 1 and 2, and their subtransient reactances were included when
finding Zbus. If prefault current is neglected, find the subtransient current in per unit in the fault for a
three-phase fault on bus 4. Assume the voltage at the fault is 1.0 per unit before the fault occurs. Find
also the per-unit current from generator 2 whose subtransient reactance is 0.2 per unit.
10.8 For the network shown in Fig. 10.18 find the subtransient current in per unit from generator 1
and in line 1-2 and the voltages at buses 1 and 3 for a three-phase fault on bus 2. Assume that no
current is flowing prior to the fault and that the prefault voltage at bus 2 is 1.0 per unit. Use the bus
impedance matrix in the calculations.
10.9 If a three-phase fault occurs at bus 1 of the network of Fig. 10.11 when there is no load (all
node voltages 1.0 per unit), find the subtransient current in the fault, the voltages at buses 2, 3, and 4,
and the current from the generator connected to bus 2.
10.10 Find the subtransient current in per unit in a three-phase fault on bus 5 of the network of
Example 8.1. Neglect prefault current, assume all bus voltages are 1.0 per unit before the fault occurs,
and make use of calculations already made in Example 10.4. Find the current in lines 1-5 and 3-5
also.
10.11 A 625-kVA 2.4-kV generator with X"d = 0.20 per unit is connected to a bus through a circuit
breaker as shown in Fig. 10.19. Connected through circuit breakers to the same bus are three
synchronous motors rated 250 hp, 2.4 kV, 1.0 power factor, 90% efficiency, with X"d = 0.20 per unit.
The motors are operating at full load, unity power factor, and rated voltage, with the load equally
divided between the machines.
(a) Draw the impedance diagram with the impedances marked in per unit on a base of 625 kVA,
2.4 kV.
(b) Find the symmetrical short-circuit current in amperes which must be interrupted by breakers A
and B for a three-phase fault at point P. Simplify the calculations by neglecting the prefault
current.
(c) Repeat part (b) for a three-phase fault at point Q.
(d) Repeat part (b) for a three-phase fault at point R.
10.12 A circuit breaker having a nominal rating of 34.5 kV and a continuous current rating of
1500 A has a voltage range factor K of 1.65. Rated maximum voltage is 38 kV, and. the rated
short-circuit current at that voltage is 22 kA. Find (a) the voltage below which rated short-circuit
current does not increase as operating voltage decreases and the value of that current and (b) rated
short-circuit current at 34.5 kV.
CHAPTER
ELEVEN
SYMMETRICAL COMPONENTS
In 1918 one of the most powerful tools for dealing with unbalanced polyphase
circuits was discussed by C. L. Fortescue at a meeting of the American Institute
of Electrical Engineers.! Since that time the method of symmetrical components
has become of great importance and has been the subject of many articles and
experimental investigations. Unsymmetrical faults on transmission systems,
which may consist of short circuits, impedance between lines, impedance from
one or two lines to ground, or open conductors, are studied by the method of
symmetrical components.
275
276 ELEMENTS OF POWER SYSTEM ANALYSIS
Ki val
Figure 11.1 Three sets of balanced phasors which are the symmetrical components of three
unbalanced phasors.
SYMMETRICAL COMPONENTS 277
The synthesis of a set of three unbalanced phasors from the three sets of symme¬
trical components of Fig. 11.1 is shown in Fig. 11.2.
The many advantages of analysis of power systems by the method of symme¬
trical components will become apparent gradually as we apply the method to the
study of unsymmetrical faults on otherwise symmetrical systems. It is sufficient
to say here that the method consists in finding the symmetrical components of
current at the fault. Then the values of current and voltage at various points in
the system can be found. The method is simple and leads to accurate predictions
of system behavior.
11.2 OPERATORS
We have seen (Fig. 11.2) the synthesis of three unsymmetrical phasors from three
sets of symmetrical phasors. The synthesis was made in accordance with
Eqs. (11.1) to (11.3). Now let us examine these same equations to determine how
to resolve three unsymmetrical phasors into their symmetrical components.
First, we note that the number of unknown quantities can be reduced by
expressing each component of Vb and Vc as the product of some function of the
operator a and a component of Va. Reference to Fig. 11.1 verifies the following
relations:
Vbl = a2Val Vcl = aVal
Repeating Eq. (11.1) and substituting Eqs. (11.4) in Eqs. (11.2) and (11.3) yield
1 1 1
A = 1 a2 a (11.9)
1 a a2
1 1
A'1 = 1 a a (11.10)
1 a2 a
Va0 l l l
Ki 1 a a2 K (11.11)
Kz 1 a2 a V,
which shows us how to resolve three unsymmetrical phasors into their symmetri¬
cal components. These relations are so important that we shall write the separate
equations in ordinary fashion. From Eq. (11.11)
Ko = MK+vb+vc) (11.12)
If required, the components Vb0, Vbl, Vb2, Vc0, Vcl, and Vc2 can be found by
Eqs. (11.4).
Equation (11.12) shows that no zero-sequence components exist if the sum
of the unbalanced phasors is zero. Since the sum of the line-to-line voltage
phasors in a three-phase system is always zero, zero-sequence components are
never present in the line voltages, regardless of the amount of unbalance. The
sum of the three line-to-neutral voltage phasors is not necessarily zero, and
voltages to neutral may contain zero-sequence components.
The preceding equations could have been written for any set of related
phasors, and we might have written them for currents instead of for voltages.
They may be solved either analytically or graphically. Because some of the
preceding equations are so fundamental, they are summarized for currents:
K ~ a 1 + aZIa2 + IaO
(11.17)
aO = Wa + lb + Ic)
(11.18)
al = Wa + + a2lc) (11.19)
In a three-phase system the sum of the line currents is equal to the current/„ in
the return path through the neutral. Thus,
K— (11.22)
Solution Figure 11.4 is a diagram of the circuit. The line currents are
Ia = 10/01 A Ib = 10/180° A /c = 0 A
= 5 -/2.89 = 5.78/-30° A
= 5 + ;2.89 = 5.78/30! A
ho = 0 Ic o = 0
7„ = 10/0° amp
a
b
Z
c
Figure 11.4 Circuit for Example 11.1.
Ic= 0
SYMMETRICAL COMPONENTS 281
We note that components Icl and Ic2 have definite values although line c
is open and can carry no net current. As is expected, therefore, the sum of
the components in line c is zero. Of course, the sum of the components in
line a is 10^F A, and the sum of the components in line b is 10/l80° A.
Figure 11.6 Wiring diagram and voltage phasors for a three-phase transformer connected Y-A where
the Y side is the high-tension side.
Ht, H2, and H3 are in phase with the voltages to neutral from terminals Xu X2,
and X3, respectively.
Figure 11.6a is the wiring diagram of a Y-A transformer. The high-tension
terminals Ht, H2, and H3 are connected to phases A, B, and C, respectively, and
the phase sequence is ABC. The arrangement and notation of the diagram
conform to a convention that we shall follow in all our computations. Windings
that are drawn in parallel directions are those linked magnetically by being
wound on the same core. When capital letters are assigned to phases on one side
of the transformer, lowercase letters will be assigned to the phases on the other
side. It is customary to use uppercase letters on the high-tension side of the
transformer and lowercase letters on the low-tension side. In Fig. 11.6a winding
AN is the phase on the Y-connected side which is linked magnetically with the
phase winding be on the A-connected side. The location of the dots on
the windings shows that Van is in phase with vbc. We shall examine later the case
where the Y-connected side is the low-tension winding. If H3 is the terminal to
which line A is connected, it is customary to connect phase B to H2 and phase C
to H3.
The American standard for designating terminals H3 and Xt on Y-A trans¬
formers requires that the positive-sequence voltage drop from H3 to neutral lead
the positive-sequence voltage drop from Xt to neutral by 30°, regardless of
whether the Y or the A winding is on the high-tension side. Similarly, the voltage
from H2 to neutral leads the voltage from X2 to neutral by 30°, and the voltage
from H3 to neutral leads the voltage from X3 to neutral by 30°. The phasor
SYMMETRICAL COMPONENTS 283
diagrams for the sequence components of voltage are shown in Fig. 11.6b. We
designate the positive-sequence voltage VAtn as VA1 and other voltages to neutral
in a similar manner and see that VA1 leads Vbl by 30°, which enables us to
determine that the terminal to which phase b is connected should be labeled Xv
Figure 11.7a shows the connections of the phases to the transformer ter¬
minals so that the positive-sequence voltage to neutral VA1 leads the positive-
sequence voltage to neutral Vbl by 30°. It is not necessary, however, to label the
lines attached to the transformer terminals as we have done since no standards
have been adopted for such labeling. Very frequently the designation of lines will
be as shown in Fig. 11.7b. We shall follow the scheme of Fig. 11.7a which con¬
forms to the wiring and phasor diagrams of Fig. 11.6 since such nomenclature is
most convenient for computations. If the scheme of Fig. 11.7b is preferred, it is
necessary only to exchange a for b, b for c, and c for a in the work which follows.
Inspection of the positive- and negative-sequence phasor diagrams of
Fig. 11.6 shows that Val leads VA1 by 90° and that Va2 lags VA2 by 90°. The
diagrams show VA1 and VA2 in phase, which is not necessarily true, but phase
shift between VA1 and VA2 does not alter the 90° relation between VAl and Val or
between VA2 and K 2-
Since the direction specified for IA in Fig. 11.6a is away from the dot in the
transformer winding and the direction of Ibc is also away from the dot in its
winding, these currents are 180° out of phase. Therefore, the phase relation
between the Y and A currents is as shown in Fig. 11.8. We note that 7al leads IA1
Negative-sequence
components
Figure 11.8 Current phasors of a three-phase transformer connected Y-A where the Y side is the
high-tension side.
284 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 11.9 Wiring diagram and voltage phasors for a three-phase transformer connected Y-A where
the A side is the high-tension side.
by 90° and Ia2 lags IA2 by 90°. Summarizing the relations between the symmetri¬
cal components of the line currents on the two sides of the transformer gives
Ki = +jVa i Ki — +j!ai
(11.23)
fa2 = ~j^A2 Ia2 = ~j^A2
where each voltage and current is expressed in per unit. Transformer impedance
and magnetizing current are neglected, which explains why the per-unit magni¬
tudes of voltage and current are exactly the same on both sides of the transfor¬
mer (for instance, | Val | equals | V411).
Up to this point our discussion of the Y-A transformer has been confined to
the case where the high-tension windings are connected in Y. Figure 11.9 shows
the A-connected windings on the high-tension side of the transformer. The figure
shows that in order to have the positive-sequence voltage from to neutral
lead the positive-sequence voltage from Xx to neutral by 30 I'bci and Val must
be 180° out of phase, and the currents /BC1 and Ial must be 180° out of phase as
shown in Fig. 11.10. The phasor diagrams for the voltages and currents show
that Eqs. (11.23) are still valid.
We have assumed the power flow from the high-tension to the low-tension
windings by showing IA, JB, and Ic toward the transformer and Ia, Ib, and Ic
away from the transformer. If we were assuming power flow in the opposite
direction, voltage relationships would remain the same but all line currents
would be shown in the opposite direction. However, this would cause no change
SYMMETRICAL COMPONENTS 285
Ic 2
Ib2
Positive-sequence Negative-sequence
components components
Figure 11.10 Current phasors of a three-phase transformer connected Y-A where the A side is the
high-tension side.
in the phase angles of primary and secondary line currents with respect to each
other. Therefore Eqs. (11.23) are valid for both voltages and currents regardless
of which windings are the primary.
| Vab\ = 0.8 per unit \Vbc\ = 1.2 per unit \Vca\ = 1.0 per unit
Assume that the neutral of the load is not connected to the neutral of the
transformer secondary. Find the line voltages and currents in per unit on the
A side of the transformer.
Solution Assuming an angle of 180° for Vca and using the law of cosines to
find the angles of the other line voltages, we have
balanced-Y loads for positive and negative sequences. Consider Fig. 11-11,
where Vabl and Vab2 are taken as reference arbitrarily. The choice of the
reference has no effect on the results. We see that
and
K. 2 = -4 (11.25)
Kn ~ Kn 1 + Van2 (11.26)
The other voltages to neutral are found by obtaining their components from
and Vm2 by Eqs. (11.4). If the voltages to neutral are in per unit referred
to the base voltage to neutral and the line voltages are in per unit referred to
the base voltage from line to line, the 1/^/3 factor must be omitted in
Eqs. (11.24) and (11.25). If both voltages are referred to the same base, the
equations are correct as given.
The absence of a neutral connection means that zero-sequence currents
are not present. Therefore, the phase voltages at the load contain positive-
and negative-sequence components only. The phase voltages are found from
Eqs. (11.24) and (11.25) with the factor 1/^/3 omitted, since the line voltages
are expressed in terms of the base voltage from line to line and the phase
voltages are desired in per unit of the base voltage to neutral. Thus
The direction assumed to be positive for the currents is from the supply
toward the A primary of the transformer and away from the Y side toward
the load.
Multiplying both sides of Eqs. (11.23) by j, we obtain for the high-
tension side of the transformer
VA1 = ~jVal = 0.985 /— 46.4° = 0.680 - jO.713
VA2 = jVa2 = 0.235 /- 19.7° - 0.221 - ;0.079
2.06
/— 22.6 = 1.19 /—22.6° per unit (line-line voltage base)
73
FBC = - Kc = -1.0 - 0.099 - jO.792 = -1.099 - /0.792
_ 1.355
= 0.782/215.8° per unit (line-line voltage base)
= 7^
VCA = VC-VA = 0.099 + ;0.792 - 0.901 + /0.792 = -0.802 + jl.584
= 1.78/116.9° per unit (line-neutral voltage base)
1.78
/116.9° = 1.028/116.9° per unit (line-line voltage base)
288 ELEMENTS OF POWER SYSTEM ANALYSIS
Since the load impedance in each phase is resistance of 1.0/0° per unit,
Ial and Val are found to have identical per-unit values in this problem.
Likewise, Ia2 and K 2 are identical in per unit. Therefore, IA must be identi¬
cal to VA expressed in per unit. Thus
If the symmetrical components of current and voltage are known, the power
expended in a three-phase circuit can be computed directly from the compo¬
nents. Demonstration of this statement is a good example of the matrix manipula¬
tion of symmetrical components.
The total complex power flowing into a three-phase circuit through three
lines a, b, and c is
where Va, Vb, and Vc are voltages to neutral at the terminals and Ia, Ib, and Ic
are the currents flowing into the circuit in the three lines. A neutral connection
may or may not be present. In matrix notation
S = [Ea Vb K] (11.28)
S = [AV]r[AI]* (11.29)
where
va0 I aO
V = Ki and I= Ll (11.30)
va2 h 2.
SYMMETRICAL COMPONENTS 289
The reversal rule of matrix algebra states that the transpose of the product of
two matrices is equal to the product of the transposes of the matrices in reverse
order. According to this rule
1 1 1 1 1 1 I aO
s = [Va0 Val Va2] l a2 a 1 a a2 (11.33)
1 a a2 1 a2 a Kl
or, since ArA* is equal to
1 0 0
0 1 0
0 0 1
I aO
(11.34)
S = 3[Fa0 Val Va2]
Kl
So complex power is
which shows how complex power can be computed from the symmetrical com¬
ponents of the voltages and currents of an unbalanced three-phase circuit.
We shall be concerned particularly with systems that are normally balanced and
become unbalanced only upon the occurrence of an unsymmetrical fault. Let us
look, however, at the equations of a three-phase circuit when the series im¬
pedances are unequal. We shall reach a conclusion that is important in analysis
by symmetrical components. Figure 11.12 shows the unsymmetrical part of a
system with three unequal series impedances Za, Zb, and Zc. If we assume no
la za
a — —wvw-- a'
h
b - —VVNAA-— b'
mutual inductance (no coupling) between the three impedances, the voltage
drops across the part of the system shown are given by the matrix equation
Ka' z„ 0 o ■ la
vw — 0 Z„ 0 h (11.36)
_1
N
O
VCC‘ h
u
1
and in terms of the symmetrical components of voltage and current
^aa'O 0 0 ' l aO
A 1 = 0 0 A lay
(11.37)
Vaa. 2_ 0 0 lal
where A is the matrix defined by Eq. (11.9). Premultiplying both sides of the
equation by A'1 yields the matrix equation from which we obtain
+ jIao{Za + Zb + Zc)
If the impedances are made equal (that is, if Za = Zb = Zc), Eqs. (11.38)
reduce to
V — 17 (11.39)
y aa' 1 1 a 1 ^a Kia'2 — al ■Z.
In') ^aa'O IaO ^a
In any part of a circuit, the voltage drop caused by current of a certain sequence
depends on the impedance of that part of the circuit to current of that sequence.
The impedance of any section of a balanced network to current of one sequence
may be different from impedance to current of another sequence.
The impedance of a circuit when positive-sequence currents alone are
flowing is called the impedance to positive-sequence current. Similarly, when only
negative-sequence currents are present, the impedance is called the impedance to
negative-sequence current. When only zero-sequence currents are present, the
impedance is called the impedance to zero-sequence current. These names of the
impedances of a circuit to currents of the different sequences are usually
shortened to the less descriptive terms positive-sequence impedance, negative-
sequence impedance, and zero-sequence impedance.
The analysis of an unsymmetrical fault on a symmetrical system consists in
finding the symmetrical components of the unbalanced currents that are flowing.
Since the component currents of one phase sequence cause voltage drops of like
sequence only and are independent of currents of other sequences, in a balanced
system, currents of any one sequence may be considered to flow in an indepen¬
dent network composed of the impedances to the current of that sequence only.
The single-phase equivalent circuit composed of the impedances to current of
any one sequence only is called the sequence network for that particular
sequence. The sequence network includes any generated emfs of like sequence.
Sequence networks carrying the currents Ial, Ia2, and Ia0 are interconnected to
represent various unbalanced fault conditions. Therefore, to calculate the effect
of a fault by the method of symmetrical components, it is essential to determine
the sequence impedances and to combine them to form the sequence networks.
Usually the components of current and voltage for phase a are found from
equations determined by the sequence networks. The equations for the compo¬
nents of voltage drop from point a of phase a to the reference bus (or ground) are,
SYMMETRICAL COMPONENTS 293
Ial
Reference bus
hi
Reference bus
13 Zn
"Z0 va0
Li
*a0
Figure 11.14 Paths for current of each sequence in a generator and the corresponding sequence
networks.
Kl _ Eg Igl Zy (11.41)
Va2=-Ia2Z2 (11.42)
N
(11.43)
II
1
o
o
3
t The reader who wishes to study machine impedances should consult such books as Central
Station Engineers of Westinghouse Electric Corporation, Electrical Transmission and Distribution
Reference Book, 4th ed., chap. 6, pp. 145-194, East Pittsburgh, Pa., 1964; or A. E. Fitzgerald, C.
Kingsley, Jr., and A. Kusko, Electric Machinery, 3d ed., chaps. 6 and 9, McGraw-Hill Book
Company, New York, 1971.
SYMMETRICAL COMPONENTS 295
returns through the ground, through overhead ground wires, or through both.
Because zero-sequence current is identical in each phase conductor (rather than
equal only in magnitude and displaced in phase by 120° from other phase
currents), the magnetic field due to zero-sequence current is very different from
the magnetic field caused by either positive- or negative-sequence current. The
difference in magnetic field results in the zero-sequence inductive reactance of
overhead transmission lines being 2 to 3.5 times as large as the positive-sequence
reactance. The ratio is toward the higher portion of the specified range for
double-circuit lines and lines without ground wires.
A transformer in a three-phase circuit may consist of three individual single¬
phase units, or it may be a three-phase transformer. Although the zero-sequence
series impedances of three-phase units may differ slightly from the positive- and
negative-sequence values, it is customary to assume that series impedances of all
sequences are equal regardless of the type of transformer. Table A.5 lists trans¬
former reactances. Reactance and impedance are almost equal for transformers
of 1000 kVA or larger. For simplicity in our calculations we shall omit shunt
admittance, which accounts for exciting current.
The zero-sequence impedance of balanced Y- and A-connected loads equals
the positive and negative-sequence impedance. The zero-sequence network for
such loads is discussed in Sec. 11.11.
The object of obtaining the values of the sequence impedances of a power system
is to enable us to construct the sequence networks for the complete system. The
network of a particular sequence shows all the paths for the flow of current of
that sequence in the system.
We discussed the construction of some rather complex positive-sequence
networks in Chap. 6. The transition from a positive-sequence network to a
negative-sequence network is simple. Three-phase synchronous generators and
motors have internal voltages of positive sequence only, since they are designed
to generate balanced voltages. Since the positive- and negative-sequence im¬
pedances are the same in a static symmetrical system, conversion of a positive-
sequence network to a negative-sequence network is accomplished by changing,
if necessary, only the impedances that represent rotating machinery and by omit¬
ting the emfs. Electromotive forces are omitted on the assumption of balanced
generated voltages and the absence of negative-sequence voltages induced from
outside sources.
Since all the neutral points of a symmetrical three-phase system are at the
same potential when balanced three-phase currents are flowing, all the neutral
points must be at the same potential for either positive- or negative-sequence
currents. Therefore the neutral of a symmetrical three-phase system is the logical
reference potential for specifying positive- and negative-sequence voltage drops
296 ELEMENTS OF POWER SYSTEM ANALYSIS
Reference bus
and is the reference bus of the positive- and negative-sequence networks. Im¬
pedance connected between the neutral of a machine and ground is not a part of
either the positive- or negative-sequence network because neither positive- nor
negative-sequence current can flow in an impedance so connected.
Negative-sequence networks, like the positive-sequence networks of Chap. 6,
may contain the exact equivalent circuits of parts of the system or may be
simplified by omitting series resistance and shunt admittance.
Example 11.3 Draw the negative-sequence network for the system des¬
cribed in Example 6.10. Assume that the negative-sequence reactance of each
machine is equal to its subtransient reactance. Omit resistance.
Solution Since all the negative-sequence reactances of the system are equal
to the positive-sequence reactances, the negative-sequence network is identi¬
cal to the positive-sequence network of Fig. 6.30 except for the omission of
emfs from the negative-sequence network. The required network is drawn in
Fig. 11.15.
Reference bus
■VNAAA-*N
z
(a)
Reference bus
YWW 'N
z
I
(b)
Reference bus
fqQ ^
l-vww
i z
(c)
Reference bus
b'AVJ
Figure 11.17 A-connected load Z
and its zero-sequence network.
The absence of a path through one winding prevents current in the other. An
open circuit exists for zero-sequence current between the two parts of the system
connected by the transformer.
Case 2: Y-Y Bank, Both Neutrals Grounded Where both neutrals of a Y-Y
bank are grounded, a path through the transformer exists for zero-sequence
currents in both windings. Provided the zero-sequence current can follow a
complete circuit outside the transformer on both sides, it can flow in both
windings of the transformer. In the zero-sequence network, points on the two
sides of the transformer are connected by the zero-sequence impedance of the
transformer in the same manner as in the positive- and negative-sequence
networks.
Figure 11.18 Zero-sequence equivalent circuits of three-phase transformer banks, together with dia¬
grams of connections and the symbols for one-line diagrams.
300 ELEMENTS OF POWER SYSTEM ANALYSIS
Case 5: A-A Bank Since a A circuit provides no return path for zero-
sequence current, no zero-sequence current can flow into a A-A bank, although it
can circulate within the A windings.
<y%
oy
Reference bus
-*W'J
Figure 11.19 One-line diagram of a small power system and the corresponding zero-sequence
network.
SYMMETRICAL COMPONENTS 301
YIlro^L
Q.
A SCL A
<'1% A rv~|^n> A
JTsJC
o V- £O
w ■
m
<Yi xYY
Figure 11.20 One-line diagram of a small power system and the corresponding zero-sequence
network.
Example 11.4 Draw the zero-sequence network for the system described in
Example 6.10. Assume zero-sequence reactances for the generators and
motors of 0.05 per unit. Current limiting reactors of 0.4 Q each are in the
neutral of the generator and the larger motor. The zero-sequence reactance
of the transmission line is 1.5 Q/km.
300,f 13.21 2
;
*°=°-05iJ
Base Z = = 1.333 Q
300
302 ELEMENTS OF POWER SYSTEM ANALYSIS
Reference bus
Base Z = = 0.635 Q
300
0.4
3Z„ = 3 -= 0.900 per unit
1.333
11.12 CONCLUSIONS
\
Unbalanced voltages and currents can be resolved into their symmetrical com¬
ponents. Problems are solved by treating each set of components separately and
superimposing the results.
In balanced networks having no coupling between phases the currents of
one phase sequence induce voltage drops of like sequence only. Impedances of
circuit elements to currents of different sequences are not necessarily equal.
A knowledge of the positive-sequence network is necessary for load studies
on power systems, for fault calculations, and for stability studies. If the fault
calculations or stability studies involve unsymmetrical faults on otherwise sym¬
metrical systems, the negative- and zero-sequence networks are needed also.
Synthesis of the zero-sequence network requires particular care, because the
zero-sequence network may differ from the others considerably.
SYMMETRICAL COMPONENTS 303
PROBLEMS
11.2 If Vani = 50/0°, Van2 = 20/90°. and Van0 = 10/l80° V. determine analytically the voltages to
neutral Van, Vbn and Vc„, and also show graphically the sum of the given symmetrical components
which determine the line-to-neutral voltages.
113 When a generator has terminal a open and the other two terminals are connected to each other
with a short circuit from this connection to ground, typical values for the symmetrical components of
current in phase a are Ial = 600/-90° A, Ia2 = 250/90° A, and Ia0 = 350/90° A. Find the current
into the ground and the current in each phase of the generator.
11.4 Determine the symmetrical components of the three currents /„ = l()/o°, Ib — 10/230°, and
Ic = 10/l30° A.
11.5 The currents flowing in the lines toward a balanced load connected in A are Ia = 100/0°
/;,= 141.4/225°, and Ic = 100/90° A. Determine a general expression for the relation between the
symmetrical components of the line currents flowing toward a A-connected load and the phase
currents in the load, that is, between Ial and Iabl and between Ia2 and Iab2. Start by drawing phasor
diagrams of the positive- and negative-sequence line and phase currents. Find Iab in amperes from
the symmetrical components of the given line currents.
11.6 The voltages at the terminals of a balanced load consisting of three 10-0 resistors connected in
Y are Vab = 100/0°, Vbc = 80.8 /— 121.44°, and Vca = 90/l30° V. Determine a general expression for
the relation between the symmetrical components of the line and phase voltages, that is, between Vabl
and Vml and between Vab2 and Vm2. Assume that there is no connection to the neutral of the load.
Find the line currents from the symmetrical components of the given line voltages.
11.7 Find the power expended in the three 10-0 resistors of Prob. 1F6 from the symmetrical com¬
ponents of currents and voltages. Check the answer.
11.8 Three single-phase transformers are connected as shown in Fig. 11.22 to form a Y-A transfor¬
mer. The high-tension windings are Y-connected with polarity marks as indicated. Magnetically
coupled windings are drawn in parallel directions. Determine the correct placement of polarity
marks on the low-tension windings. Identify the numbered terminals on the low-tension side (a) with
the letters a, b, and c where lAl leads lal by 30° and (b) with the letters a', b', and c! so that Ia i is 90°
out of phase with IAl.
11.9 Assume that the currents specified in Prob. 11.5 are flowing toward a load from lines connected
to the Y side of a A-Y transformer rated 10 MVA, 13.2A/66Y kV. Determine the currents flowing in
the lines on the A side by converting the symmetrical components of the currents to per unit on the
base of the transformer rating and by shifting the components according to Eq. (11.23). Check the
results by computing the currents in each phase of the A windings in amperes directly from
the currents on the Y side by multiplying by the turns ratio of the windings. Complete the check by
computing the line currents from the phase currents on the A side.
■
11.10 Balanced three-phase voltages of 100 V line-to-line are applied to a Y-connected load consisting
of three resistors. The neutral of the load is not grounded. The resistance in phase a is 10 ft, in phase
b is 20 ft, and in phase c is 30 ft. Select voltage to neutral of the three-phase line as reference and
determine the current in phase a and the voltage Van.
11.11 Draw the negative- and zero-sequence impedance networks for the power system of Prob. 6.15.
Mark the values of all reactances in per unit on a base of 50 MVA, 13.8 kV in the circuit of generator
l. Letter the networks to correspond to the one-line diagram. The neutrals of generators 1 and 3 are
connected to ground through current-limiting reactors having a reactance of 5%, each on the base of
the machine to which it is connected. Each generator has negative- and zero-sequence reactances of
20 and 5%, respectively, on its own rating as base. The zero-sequence reactance of the transmission
line is 210 ft from B to C and 250 ft from C to E.
11.12 Draw the negative- and zero-sequence impedance networks for the power system of Prob. 6.16.
Choose a base of 50 MVA, 138 kV in the 40-ft transmission line, and mark all reactances in per unit.
The negative-sequence reactance of each synchronous machine is equal to its subtransient reactance.
The zero-sequence reactance of each machine is 8% based on its own rating. The neutrals of the
machines are connected to ground through current-limiting reactors having a reactance of 5%, each
on the base of the machine to which it is connected. Assume that the zero-sequence reactances of the
transmission lines are 300% of their positive-sequence reactances.
CHAPTER
TWELVE
UNSYMMETRICAL FAULTS
Most of the faults that occur on power systems are unsymmetrical faults, which
may consist of unsymmetrical short circuits, unsymmetrical faults through im¬
pedances, or open conductors. Unsymmetrical faults occur as single line-to-
ground faults, line-to-line faults, or double line-to-ground faults. The path of the
fault current from line to line or line to ground may or may not contain
impedance. One or two open conductors result in unsymmetrical faults, either
through the breaking of one or two conductors or through the action of fuses
and other devices that may not open the three phases simultaneously.
Since any unsymmetrical fault causes unbalanced currents to flow in the
system, the method of symmetrical components is very useful in an analysis to
determine the currents and voltages in all parts of the system after the occur¬
rence of the fault. First, we shall discuss faults at the terminals of an unloaded
generator. Then we shall consider faults on a power system by applying Theven-
in’s theorem, which allows us to find the current in the fault by replacing the
entire system by a single generator and series impedance. Finally, we shall in¬
vestigate the bus impedance matrix as applied to the analysis of unsymmetrical
faults.
Regardless of the type of fault which occurs at the terminals of a generator
we can apply Eqs. (11.41) to (11.43), derived in Sec. 11.8. In matrix form these
equations become
305
306 ELEMENTS OF POWER SYSTEM ANALYSIS
For each type of fault we shall use Eq. (12.1), together with equations that
describe conditions at the fault, to derive Ial in terms of Ea, Zu Z2, and Z0.
4=0 Ic= 0 Fa = 0
With Ib — 0 and Ic = 0 the symmetrical components of current are given by
Uo 1 1 Ia
Ll 1 a a 0
hi 1 a2 a 0
Kl =
Ea
— 0 Zi 0 Ial (12.3)
Kl 0 0 0 z2 Ial
Since Va = Va0 + Val + Va2 = 0, we solve Eq. (12.4) for Ial and obtain
Eg
/ a 1 (12.5)
Z\ + Z2 + Z0
Equations (12.2) and (12.5) are the special equations for a single line-to-
ground fault. They are used with Eq. (12.1) and the symmetrical-component
relations to determine all the voltages and currents at the fault. If the three
sequence networks of the generator are connected in series, as shown in
Fig. 12.2, we see that the currents and voltages resulting therefrom satisfy the
equations above, for the three sequence impedances are then in series with the
voltage Ea. With the sequence networks so connected, the voltage across each
sequence network is the symmetrical component of Va of that sequence.
The connection of the sequence networks as shown in Fig. 12.2 is a convenient
means of remembering the equations for the solution of the single line-to-ground
fault, for all the necessary equations can be determined from the sequence-
network connection.
If the neutral of the generator is not grounded, the zero-sequence network is
open-circuited and Z0 is infinite. Since Eq. (12.5) shows that Ial is zero when Z0
is infinite, Ia2 and Ia0 must be zero. Thus no current flows in line a since Ia is the
sum of its components, all of which are zero. The same result can be seen
without the use of symmetrical components since inspection of the circuit shows
that no path exists for the flow of current in the fault unless there is a ground at
the generator neutral.
unit. The neutral of the generator is solidly grounded. Determine the sub¬
transient current in the generator and the line-to-line voltages fof sub-
transient conditions when a single line-to-ground fault occurs at the
generator terminals with the generator operating unloaded at rated voltage.
Neglect resistance.
Solution On a base of 20 MV A, 13.8 kV, Ea= 1.0 per unit since the inter¬
nal voltage is equal to the terminal voltage at no load. Then, in per unit,
„ 20,000
Base current = —7=- = 837 A
^3 x 13.8
K = aKi + a2Ki + Ko
= 0.643( —0.5 + 70.866) - 0.50( —0.5 -70.866) - 0.143
Since the generated voltage-to-neutral Ea was taken as 1.0 per unit, the
above line-to-line voltages are expressed in per unit of the base voltage to
neutral. Expressed in volts, the postfault line voltages are
13.8
Vab = 1.01 x -W77.7° = 8.05/77,7° kV
13.8
Vbc = 1.980 x -W270° = 15.78/270° kV
13.8
Vca = 1.01 x —^/102.3° = 8.05/102.3° kV
Before the fault the line voltages were balanced and equal to 13.8 kV. For
comparison with the line voltages after the fault occurs, the prefault voltages,
with Vm = Ea as reference, are given as
Vab = 13.8/301 kV Vbc = 13.8/270° kV Vca = 13.8 kV
The phasor diagrams of prefault and postfault voltages are shown in
Fig. 12.3.
Ki = Vm2 (12.6)
Since Ib = — Ic and Ia = 0, the symmetrical components of current are given by
l aO 1 1
/at a 32
Ia2 a
and therefore
I aO=0 (12.7)
la2 l aX (12.8)
With a connection from the generator neutral to ground, Z0 is finite, and so
Va0 = 0 (12.9)
since Ia0 is zero by Eq. (12.7).
Equation (12.1), with the substitutions allowed by Eqs. (12.6) to (12.9),
becomes
■ 0 ‘ 'O' Z0 0 0 ' 0 '
Ki = Ea — 0 Zi 0 lax (12.10)
Vai 0 0 0 z2 -lax
Iai = (12.12)
Zt + Z2
Equations (12.6) to (12.8) and (12.12) are the special equations for a line-to-
line fault. They are used with Eq. (12.1) and the symmetrical-component rela¬
tions to determine all the voltages and currents at the fault. The special
UNSYMMETRICAL FAULTS 311
equations indicate how the sequence networks are connected to represent the
fault. Since Z0 does not enter into the equations, the zero-sequence network is
not used. The positive- and negative-sequence networks must be in parallel since
Val — K2 ■ The parallel connection of the positive- and negative-sequence
networks without the zero-sequence network makes Ial = — Ia2, as specified by
Eq. (12.8). The connection of the sequence networks for a line-to-line fault is
shown in Fig. 12.5. The currents and voltages in the sequence networks, when so
connected, satisfy all the equations derived for the line-to-line fault.
Since there is no ground at the fault, there is only one ground in the circuit
(at the generator neutral) and no current can flow in the ground. In the deriva¬
tion of the relations for the line-to-line fault we found that Ia0 = 0. This is
consistent with the fact that no ground current can flow, since the ground
current /„ is equal to 3Ia0. The presence or absence of a grounded neutral at the
generator does not affect the fault current. If the generator neutral is not
grounded, Z0 is infinite and Va0 is indeterminate, but line-to-line voltages may be
found since they contain no zero-sequence components.
Example 12.2 Find the subtransient currents and the line-to-line voltages at
the fault under subtransient conditions when a line-to-line fault occurs at the
terminals of the generator described in Example 12.1. Assume that the gener¬
ator is unloaded and operating at rated terminal voltage when the fault
occurs. Neglect resistance.
Solution
1-0+J0
Ial
—j 1.667 per unit
j0.25 + ;0.35
I aO 0
/. = o
Ib = -2.886 x 837 = 2416/180° A
/c = 2.886 x 837 = 2416/01A
K=o vc = o ia = o
UNSYMMETRICAL FAULTS 313
Ia
a
Ko 11 1' K
_ 1
Ki 1 a a2 0
_ 3 0
Val l a2 a
Therefore Va0, Val, and Va2 equal Ka/3, and
Substituting £a - /fllZ, for Val, Va2, and Va0 in Eq. (12.1) and premultiplying
both sides by Z~\ where
1
Zo 0 0 ' -1 0 0
1
0 Zi 0 = 0 0
Zt
1
0 0 z2 0 0
Zi_
give
0 0
Z~o Zo
0 0 0 Ial (12.14)
J_
0 0 0 hi
Z^
Premultiplying both sides of Eq. (12.14) by the row matrix [1 1 1] and recog¬
nizing that Ial -I- Ia2 + Ia0 = Ia = 0, we have
E* (12.15)
Zo
and upon collecting terms we obtain
Figure 12.7 Connection of the sequence networks of an unloaded generator for a double line-to-
ground fault on phases b and c at the terminals of the generator.
and
Equations (12.13) and (12.17) are the special equations for a double line-to-
ground fault. They are used with Eq. (12.1) and the symmetrical-component
relations to determine all the voltages and currents at the fault. Equation (12.13)
indicates that the sequence networks should be connected in parallel, as shown
in Fig. 12.7, since the positive-, negative-, and zero-sequence voltages are equal
at the fault. Examination of Fig. 12.7 shows that all the conditions derived above
for the double line-to-ground fault are satisfied by this connection. The diagram
of network connections shows that the positive-sequence current Ial is
determined by the voltage Ea impressed on Zx in series with the parallel combin¬
ation of Z2 and Z0. The same relation is given by Eq. (12.17).
In the absence of a ground connection at the generator no current can flow
into the ground at the fault. In this case Z0 would be infinite and Ia0 would be
zero. Insofar as current is concerned, the result would be the same as in a
line-to-line fault. Equation (12.17) for a double line-to-ground fault approaches
Eq. (12.12) for a line-to-line fault as Z0 approaches infinity, as may be seen by
dividing the numerator and denominator of the second term in the denominator
of Eq. (12.17) by Z0 and letting Z0 be infinitely large.
Example 12.3 Find the subtransient currents and the line-to-line voltages at
the fault under subtransient conditions when a double line-to-ground fault
occurs at the terminals of the generator described in Example 12.1. Assume
that the generator is unloaded and operating at rated voltage when the fault
occurs. Neglect resistance.
Solution
1.0 +;0
Iai =
Zi + Z2Z0/(Z2 + Z0) j0.25 + (jO.35 x ;0.10)/(/0.35 + y'0.10)
1.0 1.0
= —j3.05 per unit
j0.25 + ;0.0778 j0.3278
UNSYMMETRICAL FAULTS 315
II
II
(N
o
= 1.0 - 0.763 = 0.237 per unit
Va2 0.237
= j0.68 per unit
Z2 ~ j0.35
Ko 0.237
IaO = 7*2.37 per unit
‘ 20 ~ J0.10
h= a2Ial + ala 2 3” Ko
= (— 0.5 — ;'0.866)( — ;3.05) + (-0.5 + ;0.866)(/0.68) + ;2.37
/. = 0
lb = 837 x 4.80/132.3° = 4017/132.3° A
Ic = 837 x 4.80/47.7° = 4017/47.7° A
/„ = 837 x 7.11/90° -- 5951/90° A
13.8
Kb = 0.711 X 5.66/01 kV
73
Kc = o
V„ = -0.711 x ~ = 5.66/mi kV
316 ELEMENTS OF POWER SYSTEM ANALYSIS
Ml
b
Figure 12.8 Three conductors of a three-phase sys¬
tem. The stubs carrying currents /„, Ib, and Ic may
Ml
C
be interconnected to represent different types of
faults. M
UNSYMMETRICAL FAULTS 317
J?*"T (^)—
HF
jT t>
(e) Thevenin
equivalent of the positive-
sequence network
h2
(c) Negative-sequence network (f) Thevenin
equivalent of the negative-
sequence network
Tao
Figure 12.9 One-line diagram of a three-phase system, the three sequence networks of the system,
and the Thevenin equivalent of each network for a fault at P.
Since Ia is the current flowing from the system into the fault, its components
/ai, Ia2, and Ia0 flow out of their respective sequence networks and out of the
equivalent circuits of the networks at P, as shown in Fig. 12.9. The Thevenin
equivalents of the positive-, negative, and zero-sequence networks of the system
are the same as the networks of a single generator. The matrix equations for the
symmetrical components of voltages at the fault, therefore, must be the same as
Eq. (12.1) except that Vf replaces Ea; that is,
For a single line-to-ground fault, the hypothetical stubs on the three lines are
connected as shown in Fig. 12.10. The following relations exist at the fault:
Ib = 0 Ic = 0 Va = 0
These three equations are the same as those which apply to a line-to-ground
fault on a single generator. These equations with Eq. (12.18) and the relations of
symmetrical components must have the same solutions as are found for similar
equations in Sec. 12.1, except that Vf replaces Ea. Thus, for a line-to-ground
fault,
hi = hi = ho (12.19)
and
/a 1 Vf (12.20)
Zi + Z2 + z0
Equations (12.19) and (12.20) indicate that the three sequence networks should
be connected in series through the fault point in order to simulate a single
line-to-ground fault.
c
Figure 12.10 Connection diagram of the hypotheti¬
cal stubs for a single line-to-ground fault.
UNSYMMHTRICAL FAULTS 319
4j
For a line-to-line fault, the hypothetical stubs on the three lines at the fault are
connected as shown in Fig. 12.11. The following relations exist at the fault:
vb=K ia = o i„=-ic
The above equations are identical in form to those which apply to a line-to-line
fault on an isolated generator. Their solution in the manner of Sec. 12.2, with
Eq. (12.18) replacing Eq. (12.1), yields
Ki = V.2 (1221)
/a 1 Vf (12.22)
Zi + z2
Equations (12.21) and (12.22) indicate that the positive- and negative-sequence
networks should be connected in parallel at the fault point in order to simulate a
line-to-line fault.
vb = K =o
la = 0
b
41
c Is
4J
Figure 12.12 Connection diagram of the hypotheti¬
cal stubs for a double line-to-ground fault.
320 ELEMENTS OF POWER SYSTEM ANALYSIS
K i = va2 = K
aO
(12.23)
/a1 Vf (12.24)
Zx + Z2Z0/(Z2 + z0)
Equations (12.23) and (12.24) indicate that the three sequence networks should
be connected in parallel at the fault point in order to simulate a double line-to-
ground fault.
In the preceding sections we have seen that the sequence networks of a power
system can be so interconnected that solving the resulting network yields the
symmetrical components of current and voltage at the fault. The connections of
the sequence networks to simulate various types of faults, including a symmetri¬
cal three-phase fault, are shown in Fig. 12.13. The sequence networks are in¬
dicated schematically by rectangles enclosing a heavy line to represent the
reference bus of the network and a point marked P to represent the point in the
network where the fault occurs. The positive-sequence network contains emfs
that represent the internal voltages of the machines.
Pos.-seq. net.
Val
Pos.-seq. net. Neg.-seq. net.
Tvo2
_!£L_ _E_
i± ±L
(a) Three-phase fault Tal Ta2
Figure 12.13 Connections of the sequence networks to simulate various types of faults. The sequence
networks are indicated by rectangles. The point at which the fault occurs is P.
UNSYMMETRICAL FAULTS 321
If the emfs in a positive-sequence network like that shown in Fig. 12.14a are
replaced by short circuits, the impedance between the fault point P and the
reference bus is the positive-sequence impedance Zx in the equations developed
for faults on a power system and is the series impedance of the Thevenin equiva¬
lent of the circuit between P and the reference bus. If the voltage Vf is connected
in series with this modified positive-sequence network, the resulting circuit,
shown in Fig. 12.146, is the Thevenin equivalent of the original positive-sequence
network. The circuits shown in Fig. 12.14 are equivalent only in their effect on
any external connections made between P and the reference bus of the original
networks. We can easily see that no current flows in the branches of the equiva¬
lent circuit in the absence of an external connection, but current will flow in the
branches of the original positive-sequence network if any difference exists in the
phase or magnitude of the two emfs in the network. In Fig. 12.14a the current
flowing in the branches in the absence of an external connection is the prefault
load current.
When the other sequence networks are interconnected with the positive-
sequence network of Fig. 12.14a or its equivalent shown in Fig. 12.146, the cur¬
rent flowing out of the network or its equivalent is Ial and the voltage between P
and the reference bus is Val. With such an external connection, the current in any
branch of the original positive-sequence network is the positive-sequence current
in phase a of that branch during the fault. The prefault component of this
current is included. The current in any branch of the Thevenin equivalent of
Fig. 12.146, however, is only that portion of the actual positive-sequence current
found by apportioning Ial of the fault among the branches according to their
impedances and does not include the prefault component.
An alternate method of studying unsymmetrical faults is by means of the bus
impedance matrix. We shall discuss this method after we look at the following
example to become more familiar with the sequence networks.
X" = 0.20, X2 = 0.20, and X0 = 0.04 and each is grounded through a<reac-
tance of 0.02 per unit. The motors are connected to the 4.16-kV bus through
a transformer bank composed of three single-phase units, each of which is
rated 2400/600 V, 2500 kVA. The 600-V windings are connected in A to the
motors and the 2400-V windings are connected in Y. The leakage reactance
of each transformer is 10%.
The power system which supplies the 4.16 kV bus is represented by a
Thevenin equivalent generator rated 7500 kVA, 4.16 kV with reactances of
X" = X2 = 0.10 per unit, X0 = 0.05 per unit, and Xn from neutral to ground
equal to 0.05 per unit.
Each of the identical motors is supplying an equal share of a total load
of 3730 kW (5000 hp) and is operating at rated voltage, 85% power-factor
lag, and 88% efficiency when a single line-to-ground fault occurs on the
low-tension side of the transformer bank. Treat the group of motors as a
single equivalent motor. Draw the sequence networks showing values of the
impedances. Determine the subtransient line currents in all parts of the
system with prefault current neglected.
Solution The one-line diagram of the system is shown in Fig. 12.15. The
600-V bus and the 4.16 kV bus are numbered 1 and 2, respectively. Choose
the rating of the equivalent generator as base: 7500 kVA, 4.16 kV at the
system bus.
Since
6000 x 0.746
= 5000 kVA
0.895
® _
© KD YWl
-O Y®^
,E"r 0“
Equivalent Y^el
jfTP
generator -=r
and the reactances of the equivalent motor in percent are the same on the
base of the combined rating as the reactances of the individual motors on
the base of the rating of an individual motor. The reactances of the equiva¬
lent motor on the selected base are
7500
X" = 0.2—— =0.3 per unit
5000 F
7500
X2 = 0.2—— = 0.3 per unit
2 5000 F
7500
X0 = 0.04—— = 0.06 per unit
0 5000 F
7500
3X„ = 3 x 0.02= 0.09 per unit
For the equivalent generator the reactance from neutral to ground in the
zero-sequence network is
Figure 12.16 shows the connection of the sequence networks. Reactances are
shown in per unit.
324 ELEMENTS OF POWER SYSTEM ANALYSIS
Since the motors are operating at rated voltage equal to the base voltage
of the motor circuit, the prefault voltage of phase a at the fault is
Vf = 1.0 per unit
7,500^000 _ 72i7 A
73 X 600
746 x 5000
= 4798 A
0.88 x ^3 x 600 x 0.85
The per-unit current drawn by the motor through line a before the fault
occurs is
4798
/— cos~1 0.85 = 0.665 7-31.8° - 0.565 -70.350 per unit
72l7
If prefault current is neglected, £" and £" are made equal to 1.0/0°, or
the positive-sequence network is replaced by its Thevenin equivalent circuit
which is shown in Fig. 12.17. The computations follow.
(,/0.1 +,/0.1)(,/Q-3)
= y'0.12 per unit
1 ;(0.1 + 0.1 + 0.3)
(70.1 +70-1X70.3)
= 70.12 per unit
2 7(0.1+0.1+0.3)
Z0 = jO. 15 per unit
1.0 1.0
/ V' -72.564
al Zj + Z2 + Z0 70.12 + 70.12 + 70.15 7039
L2 = Li = -72.564
Lo = Iai = -72.564
Current in the fault = 3Ia0 = 3(-72.564) = —77.692 per unit. The compo¬
nent of Ial flowing toward P from the transformer is
-72.564 x 70.30
= -71.538
70.50
Reference bus
vs
S
y'O.lO § 3; 0.30
■nm^
Figure 12.17 Thevenin equivalent of the positive-sequence j 0.10
network of Example 12.4.
UNSYMMETRICAL FAULTS 325
-j2.564 x jO.20
-j 1-026
jO.50
Similarly the component of Ia2 from the transformer is -/1.538, and the
component of Ia2 from the motor is —j1.026. All of Ia0 flows toward P from
the motor.
Currents in the lines at the fault are:
la li r -J 2.564 —>4.616
.•00*00
h — 1 a2 a -j 1.026 — 1
Ic 1 a a2 —jf 1.026
1
1
Our method of labeling the lines is such that currents IA1 and IA2 on
the high-tension side of the transformer are related to the currents 7al and
Ia2 on the low-tension side by
^a = Cu + 1a2 — 0
IB1 = a2IAl = (-0.5 — y'0.866)( —1.538) = 0.769 + >1.332
7,500,000
= 1041 A
•v/3 x 4160
Currents in the lines between the transformer and the fault are:
Currents in the lines between the motor and the fault are:
Currents in the lines between the 4.16 kV bus and the transformer are:
\
In line A: 0
The currents we have calculated are those which would flow upon the
occurrence of a fault when there is no load on the motors. These currents are
correct only if the motors are drawing no current whatsoever. The statement
of the problem specifies the load conditions at the time of the fault, however,
and the load can be considered. To account for the load, we add the per-unit
current drawn by the motor through line a before the fault occurs to the
component of Ial flowing toward P from the transformer and subtract the
same current from the component of Ial flowing from the motor to P. The
UNSYMMETRICAL FAULTS 327
Figure 12.18 Per-unit values of subtransient line currents in all parts of the system of Example 12.4,
prefault current neglected.
and the new value of positive-sequence current from the motor to the fault in
phase a is
These values are shown in Fig. 12.16. The remainder of the calculation,
using these new values, proceeds as in the example.
Figure 12.18 gives the per-unit values of subtransient line currents in all
parts of the system when the fault occurs at no load. Figure 12.19 shows the
values for the fault occurring on the system when the load specified in the
example is considered. In a larger system where the fault current is much
higher in comparison with the load current, the effect of neglecting the load
current is less than is indicated by comparing Figs. 12.18 and 12.19. In the
large system, however, the prefault currents determined by a load-flow study
could simply be added to the fault current found with the load neglected.
0.665-y'2.685 -0.586+71.224
Figure 12.19 Per-unit values of subtransient line currents in all parts of the system of Example 12.4,
prefault current considered.
328 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 12.20 Connections of the bus impedance equivalent sequence networks of a three-bus system
to simulate various types of faults. Transfer impedances not shown.
UNSYMMETRICAL FAULTS 329
Ial = (12.26)
'33 ■1 + Z 33-2 + z 33-0
which should be compared with Eq. (12.20). Obviously Z33_x, Z33_2, and
Z33_0 are equal to the values of Zl5 Z2, and Z0 of Eq. (12.20) if the fault is on
bus 3. The positive-, negative-, and zero-sequence bus impedance matrices enable
us to see immediately the values to be used for Zu Z2, and Z0 in Eqs. (12.20),
(12.22), and (12.24). The transfer admittances (not shown in Fig. 12.20) enable us
to calculate the voltages at the unfaulted buses, from which the currents in the
lines are found.
Solution We refer to Fig. 12.16 to find the elements of the node admittance
matrices of the three sequence networks, as follows:
y
Ui-i n-2■> = —-|—-
,, . = y,, ai 0_3 = -/'13.3
J
;0.1 jO.
^22- 1 1 +i = -j20
yO.l jO.l
1
^11-0 = —j'6.67 F12-o = 0
A15
1 1
-j 15.0
Y22-°~]02 + jO.l
-13.3 10.0
^bus— 1 = Y bus - 2 = J
10.0 - 20.0
-6.67 0.0
^bus — 0 =J 0.0 -15.0
330 ELEMENTS OF POWER SYSTEM ANALYSIS
Inverting the three matrices above gives the three bus impedance
matrices
0.12 0.06
^bus-l ^bus—2 j
0.06 0.08
0.150 0.0
Zbus-0 ~j
0.0 0.067
r 3 x 1.0
= — /7.692 per unit
f ;0.12+;0.12+;'0.15
which agrees with the value found in Example 12.4. If the fault is on bus 2,
3 x 1.0
= — y'13.216 per unit
If y'0.08 + y0.08 + ;0.067
By studying Fig. 12.20 and realizing that transfer impedances are present we
see that at bus 2 with the fault on bus 1 and neglecting phase shift the
sequence components of voltage are
VaO = 0
Accounting for phase shift we have from Eqs. (11.23)
Although the method of solution using the bus impedance matrix does not
appear to have any great advantage over the method of Example 12.4 in this
very simple network, it does give us the current for the fault on each of the buses.
For a large network the method is well suited to the digital computer, which can
build the bus impedance matrix directly and add or remove particular lines quite
easily. Thus, with the bus impedance matrix for each sequence network all the
features of digital-computer solutions for symmetrical three-phase faults can be
extended to unsymmetrical faults.
All the faults discussed in the preceding sections consisted of direct short circuits
between lines and from one or two lines to ground. Although such direct short
circuits result in the highest value of fault current and are therefore the most
conservative values to use when determining the effects of anticipated faults, the
fault impedance is seldom zero. Most faults are the result of insulator flashovers,
where the impedance between the line and ground depends on the resistance of
the arc, of the tower itself, and of the tower footing if ground wires are not used.
Tower-footing resistances form the major part of the resistance between line and
ground and depend on the soil conditions. The resistance of dry earth is 10 to
100 times the resistance of swampy ground. The effect of impedance in the fault
is found by deriving equations similar to those for faults through zero
impedance. Connections of the hypothetical stubs for faults through impedance
are shown in Fig. 12.21.
A balanced system remains symmetrical after the occurrence of a three-phase
fault having the same impedance between each line and a common point. Only
4| Ia\
h\ M
JZf Zf
Figure 12.21 Connection diagrams of the hypothetical stubs for various faults through impedance.
332 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 12.22 Connections of the sequence networks to simulate various types of faults through
impedance at point P.
positive-sequence currents flow. With the fault impedance Zf equal in all phases,
as shown in Fig. 12.21a, the voltage at the fault is
K = i.zf
and since only positive-sequence currents flow,
Val = IalZf=Vf-IalZ1
and
/a 1 Vf (12.27)
Z\ + zf
The sequence-network connection is shown in Fig. 12.22a.
A formal derivation can be made for the single line-to-ground and double
line-to-ground faults through impedance shown in Fig. 12.21b and d, but we shall
arrive at the correct sequence-network connections by comparison with faults
without impedance. Consider a generator with all terminals open and its neutral
grounded. On such a generator a single or double line-to-ground fault through
Zf is no different with respect to the value of the fault current than the same
type of fault without impedance but with Zf placed in the connection between
the generator neutral and ground. To account for an impedance Z{ in the
neutral of a generator we add 3Zf to the zero-sequence network. Thevenin’s
theorem enables us to apply the same reasoning to these types of faults on a
UNSYMMETRICAL FAULTS 333
Ial I a2 I aO
/.! = Zj -f Z2 + Z0 + 3Zj
(12.28)
Ki = Ka2
/a 1 Yl (12.29)
z, + Z2(Z0 + 3Z/)/(Z2 + Z0 + 3 Zf)
A line-to-line fault through impedance is shown in Fig. 12.21c. The condi¬
tions at the fault are
I al ~ I a2
ya0 l l l
Ki 1 a a2 K (12.30)
va2 1 a2 a K - hZf
or
3Ffll = Va + (a + a2)Vb - a2IbZf (12.31)
Equation (13.35) requires the insertion of Zf between the fault points in the
positive- and negative-sequence networks to fulfill the required conditions for
the fault. The connections of the sequence networks for a line-to-line fault
through impedance are shown in Fig. 12.22c. Of course the bus impedance
matrix can be used to advantage to find Zl5 Z2, and Z0 of Eqs. (12.27), (12.28),
(12.29), and (12.35).
334 ELEMENTS OF POWER SYSTEM ANALYSIS
Modern fault-current programs for the digital computer are usually based on the
bus impedance matrix. Three-phase and single line-to-ground faults are usually
the only types of fault studied. Since circuit-breaker applications are made
according to the symmetrical short-circuit current that must be interrupted, this
current is calculated for the two types of fault. The printout includes the total
fault current and the contributions from each line. The results also list those
quantities when each line connected to the faulted bus is opened in turn while all
others are in operation.
The program uses the data listed for the lines and their impedances as
provided for the load-flow program and includes the appropriate reactance for
each machine in forming the positive- and zero-sequence bus impedance
matrices. As far as impedances are concerned the negative-sequence network is
the same as the positive-sequence network. So, for a single line-to-ground fault
at bus 1, Ial is calculated in per unit as 1.0 divided by the sum of 2Z11_1 and
Zu —o-
The bus voltages are included in the computer printout, if called for, as well
as the current in lines other than those connected to the faulted bus since this
information can easily be found from the bus impedance matrix.
PROBLEMS
12.1 A 60-Hz turbogenerator is rated 500 MVA, 22 kV. It is Y-connected and solidly grounded and
is operating at rated voltage at no load. It is disconnected from the rest of the system. Its reactances
are X" = X2 = 0.15 and X0 = 0.05 per unit. Find the ratio of the subtransient line current for a
single line-to-ground fault to the subtransient line current for a symmetrical three-phase fault.
12.2 Find the ratio of the subtransient line current for a line-to-line fault to the subtransient current
for a symmetrical three-phase fault on the generator of Prob. 12.1.
12.3 Determine the ohms of inductive reactance to be inserted in the neutral connection of the
generator of Prob. 12.1 to limit the subtransient line current for a single line-to-ground fault to that
for a three-phase fault.
12.4 With the inductive reactance found in Prob. 12.3 inserted in the neutral of the generator of
Prob. 12.1, find the ratios of the subtransient line currents for the following faults to the subtransient
line current for a three-phase fault: (a) single line-to-ground fault, (b) line-to-line fault, (c) double
line-to-ground fault.
12.5 How many ohms of resistance in the neutral connection of the generator of Prob. 12.1 would
limit the subtransient line current for a single line-to-ground fault to that for a three-phase fault?
UNSYMMETRICAL FAULTS 335
12.6 A generator rated 100 MVA, 20 kV has X" = X2 = 20% and X0 = 5%. Its neutral is grounded
through a reactor of 0.32 fl The generator is operating at rated voltage without load and is discon¬
nected from the system when a single line-to-ground fault occurs at its terminals. Find the sub¬
transient current in the faulted phase.
12.7 A 100-MVA 18-kV turbogenerator having X" = X2 = 20% and X0 = 5% is about to be con¬
nected to a power system. The generator has a current-limiting reactor of 0.162 12 in the neutral.
Before the generator is connected to the system, its voltage is adjusted to 16 kV when a double
line-to-ground fault develops at terminals b and c. Find the initial symmetrical rms current in the
ground and in line b.
12.8 The reactances of a generator rated 100 MVA, 20 kV, are X" = X2 = 20% and X0 = 5%. The
generator is connected to a A-Y transformer rated 100 MVA, 20A-230Y kV, with a reactance of
10%. The neutral of the transformer is solidly grounded. The terminal voltage of the generator is
20 kV when a single line-to-ground fault occurs on the open-circuited, high-tension side of the
transformer. Find the initial symmetrical rms current in all phases of the generator.
12.9 A generator supplies a motor through a Y-A transformer. The generator is connected to the Y
side of the transformer. A fault occurs between the motor terminals and the transformer. The
symmetrical components of the subtransient current in the motor flowing toward the fault are
Iai — ~0-8 — j2.6 per unit, Ia2 = —j2.0 per unit, and Ia0 = —j3.0 per unit. From the transformer
toward the fault Ial = 0.8 -;0.4 per unit, Ia2 = —j 1.0 per unit, and Ia0 = 0. Assume X'[ = X2 for
both the motor and the generator. Describe the type of fault. Find (a) the prefault current, if any, in
line a, (b) the subtransient fault current in per unit, and (c) the subtransient current in each phase of
the generator in per unit.
12.10 Calculate the subtransient currents in all parts of the system of Example 12.4 with prefault
current neglected if the fault on the low-tension side of the transformer is a line-to-line fault.
12.11 Repeat Prob. 12.10 for a double line-to-ground fault.
12.12 The machines connected to the two high-tension buses shown in the one-line diagram of
Fig. 12.23 are each rated 100 MVA, 20 kV with reactances of X" = X2 = 20% and Y0 = 4%. Each
three-phase transformer is rated 100 MVA, 345Y/20A kV, with leakage reactance of 8%. On a base
of 100 MVA, 345 kV the reactances of the transmission line are X2 = X2 = 15% and A"0 = 50%.
Find the 2x2 bus impedance matrix for each of the three sequence networks. If no current is
flowing in the network, find the subtransient current to ground for a double line-to-ground fault on
lines B and C at bus 1. Repeat for a fault at bus 2. When the fault is at bus 2, determine the current in
phase b of machine 2 if the lines are so named that VAl and Val are 90° out of phase. If the phases are
named so that IA1 leads Ial by 30° what letter (a, b, or c) would identify the phase of machine 2
which would carry the current found for phase b above?
12.13 Two generators Gl and G2 are connected through transformers 7j and T2 to a high-tension
bus which supplies a transmission line. The line is open at the far end at which point F a fault occurs.
The prefault voltage at point F is 515 kV. Apparatus ratings and reactances are:
© Y C>
Figure 12.23 Circuit for Prob. 12.12.
336 ELEMENTS OF POWER SYSTEM ANALYSIS
The neutral of Gj is grounded through a reactance of 0.04 fl. The neutral of G2 is not grounded.
Neutrals of all transformers are solidly grounded. Work on a base of 1000 MV A, 500 kV in the
transmission line. Neglect prefault current and find subtransient current (a) in phase c of Gl for a
three-phase fault at F, (b) in phase B at F for a line-to-line fault on lines B and C, (c) in phase A at F
for a line-to-ground fault on line A, and (d) in phase c of G2 for a line-to-ground fault on line A.
Assume VAl leads Val by 90° in Tv
12.14 For the network shown in Fig. 10.18, find the subtransient current in per unit (a) in a single
line-to-ground fault on bus 2, and (b) in the faulted phase of line 1-2. Assume no current is flowing
prior to the fault and that the prefault voltage at all buses is 1.0 per unit. Both generators are
Y-connected. Transformers are at the ends of each transmission line in the system and are Y-Y with
grounded neutrals except that the transformers connecting the lines to bus 3 are Y-A with the neutral
of the Y solidly grounded. The A sides of the Y-A transformers are connected to bus 3. All line
reactances shown in Fig. 10.18 between buses include the reactances of the transformers. Zero-
sequence reactance values for these lines including transformers are 2.0 times those shown in
Fig. 10.18. Zero-sequence reactances of generators connected to buses 1 and 3 are 0.04 and 0.08 per
unit, respectively. The neutral of the generator at bus 1 is connected to ground through a reactor of 0.02
per unit, and the neutral of the generator at bus 3 is solidly grounded.
12.15 Find the subtransient current in per unit in a line-to-line fault on bus 2 of the network of
Example 8.1. Neglect resistance and prefault current, assume all bus voltages are 1.0 before the fault
occurs, and make use of calculations already made in Example 10.4. Find the current in lines 1-2 and
3-2 also. Assume that lines 1-2 and 3-2 are connected to bus 2 directly rather than through transfor¬
mers and that the positive- and negative-sequence reactances are identical.
CHAPTER
THIRTEEN
SYSTEM PROTECTION
337
338 ELEMENTS OF POWER SYSTEM ANALYSIS
Which one of these effects will predominate in a given case depends upon the
nature and operating conditions of the power system.
Circuit breakers have been mentioned briefly in Chap. 10. Relays are the devices
which sense the fault and cause the circuit-breaker trip circuits to be energized
and the breakers to open their contacts. Transducers provide the input to the
relays. Each of these subsystems will be discussed further as we continue to
develop the material of this chapter.
Usually we will use a double-numbering notation to identify circuit breakers
and relays. Thus the line 1-2 in Fig. 13.1 has a circuit breaker B12 at the bus-1
SYSTEM PROTECTION 339
Figure 13.1 One-line diagram showing two transmission lines and elements of the protection system
for line 1-2.
end of the line and a circuit breaker B21 at the bus-2 end. Relays at these points
are labeled R12 and R21, respectively. A relay R23, although not shown here, is
understood to be associated with B23. Sometimes, however, for the simple
systems we will be examining it is more convenient to refer to circuit breakers by
letters. For example, B12 and B21 could have been labeled A and B without
numerical designation.
Separate breakers may be operated in each phase, or the relays may control
one three-phase breaker which will open all three phases upon operation of any
one of the relays.
When a fault occurs at P on the lines of Fig. 13.1, increased currents flow
from both terminals of the transmission line toward the fault if we assume that
sources of power are available beyond both buses 1 and 2. When this assump¬
tion is not the case, the protection system becomes somewhat simpler. We will
consider the protection of such radial systems later. The increase in current at
the line terminals is accompanied by a reduction in voltages. It should be
realized that the currents and voltages of the transmission line are at kiloampere
and kilovolt levels. These high-level signals are unsuitable for use by the protec¬
tion system. The power line signals are converted to a lower level (tens of
amperes and volts) by the transducers T. Transducers will be discussed at greater
length a little later.
The increase in current and reduction in voltage caused by the fault can be
used to detect that a fault has occurred on the transmission line. Relays are the
logic elements of the protection system. The lower-level signals produced by the
transducers are reasonably faithful reproductions of the actual voltages and
currents of the transmission line. Relays R12 and R21 process these input signals
and make the decision that a fault has in fact occurred on the transmission line
1-2. This decision is reached within a very short time after the occurrence of the
fault, typically 8 to 40 milliseconds depending upon the design of the relays.
The decision by relays R12 and R21 that a fault has occurred on the line
leads to the tripping of their associated circuit breakers B12 and B21. Circuit
breakers are the final link in the fault removal process. They were mentioned
briefly in Chap. 10. When the trip circuit of a circuit breaker is energized by its
relay the contacts of the circuit breaker—which are in series with the transmis¬
sion line—begin to move apart very rapidly. As the current through the breaker
340 ELEMENTS OF POWER SYSTEM ANALYSIS
contacts (the fault current) passes through zero, the space between the contacts
becomes a dielectric, and is able to prevent the fault current from flowing again
through the circuit breaker. This leads to the disconnection of the transmission
line from the rest of the system and the elimination of the fault. The entire
process from the time of initiation of the fault to its final clearance takes between
30 and 100 milliseconds depending upon the type of protective system employed.
Certain attributes of a relay are important measures of the quality of its
performance. The sequence of events described above indicates that to do its job
properly a relay must be fast and reliable (that is, dependable and selective.) The
first attribute—speed—is self-explanatory. A relay should make its decision as
quickly as possible, consistent with other requirements placed upon it. The
attribute of dependability means that the relay should operate consistently for all
the faults for which it is designed to operate, and should refrain from operating
for any other system condition. Selectivity of a relay refers to the requirement
that the smallest possible portion of a system should be isolated following a
fault. Selectivity can be illustrated with the help of Fig. 13.1. Consider the relay
R23 connected at terminal 2 of line 2-3. The current and voltage inputs to this
relay will also change due to the fault at P. This effect of the fault at P upon the
relay R23 is often described by saying that the relay R23 also “ sees ” the fault at
P. However, the relay R23 must be selective so that it does not operate for the
fault at P if P is outside the area of responsibility known as reach of this relay. In
general the reliability requirements of a relay are in conflict with its speed
requirement, and a compromise must be made in designing the protection
system so as to obtain a reasonable measure of these attributes.
Zone 2 Zone 4
Figure 13.2 Zones of protection indicated by dashed lines enclosing power-system components in
each zone.
system. Since the isolation (or deenergization) under faulted conditions is done
by circuit breakers, it should be clear that at each point where connection is
made between the equipment inside the zone and the rest of the power system, a
circuit breaker should be inserted. In other words, the circuit breakers help
define the boundaries of the zones of protection.
Another important aspect of zones of protection is that the neighboring
zones always overlap. This overlap is necessary, since without it a small part of
the system which falls between the neighboring zones, however small it may be,
would be left without protection. By overlapping neighboring zones no part of
the power system is left without protection, although clearly if a fault should
occur within the overlapped region, a much larger portion of the power system
(that corresponding to both the zones involved in the overlap) will be isolated
and lost from service. To reduce such a possibility to a minimum the region of
overlap is made as small as possible.
Example 13.1 (a) Consider the power system shown in Fig. 13.3a with gen¬
erating sources beyond buses 1, 3, and 4. What are the zones of protection in
which this system should be divided? Which circuit breakers will open for
faults at Pj and P2?
(b) If three circuit breakers are added at the tap point 2, how would the
zones of protection be modified? Which circuit breakers will operate for
faults at Pj and P2 under these conditions?
Solution (a) Using the principles of defining the zones of protection, the
system of Fig. 13.3a can be divided into zones as shown by dashed lines in
that figure. For the fault at Pj breakers A, B, and C will operate. For the
fault at P2 breakers A, B, C, D, and E will operate.
(ib) If three circuit breakers F, G, and H are added at bus 2 as shown in
Fig. 13.3b the zones of protection will be as shown by the dashed lines in
that figure. In this case breakers A and F will operate for the fault at P1;
whereas breakers G, C, D, and E will operate for the fault at P2. Note that in
this case a much smaller portion of the power system is deenergized follow¬
ing the two faults. This improved performance is achieved at the expense of
three additional circuit breakers and the associated protection equipment.
342 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 13.3 One-line diagram for Example 13.1 showing (a) original zones of protection and
(b) modified zones when additional breakers are added at bus 2.
13.3 TRANSDUCERS
Currents and voltages of the protected power equipment are converted by cur¬
rent and voltage transformers to low levels for relay operation. These reduced
levels are necessary for two reasons: (1) the lower level input to the relays
ensures that the physical hardware used to construct the relays will be quite
small and thus less expensive; (2) the personnel who work with the relays will be
working in a safe environment. In principle these transducers are no different
from the power transformers discussed in Chap. 6. However, the use made of
these transformers is rather specialized. For example, it is necessary that a cur¬
rent transformer reproduce in its secondary winding a current which duplicates
the primary current waveform as faithfully as possible. It performs this function
quite well. Similar considerations hold for a voltage transformer. The amount of
SYSTEM PROTECTION 343
power delivered by these transformers is rather modest, since the load connected
to them consists only of relays and meters that may be in use at a given time.
The load on current transformers (CTs) and voltage transformers (VTs) is
commonly known as their burden. The term burden usually describes the im¬
pedance connected to the transformer secondary winding but may specify the
voltamperes delivered to the load. For example, a transformer delivering 5 am¬
peres to a resistive burden of 0.1 ohm may also be said to have a burden of 2.5
voltamperes at 5 amperes.
We will now consider current transformers and voltage transformers
separately.
50 : 5 300 : 5 800 : 5
100 : 5 400 : 5 900 : 5
150 : 5 450: 5 1000 : 5
200 : 5 500 : 5 1200 : 5
250 : 5 600 : 5
SYSTEM PROTECTION 345
Voltage transformers are generally far more accurate than the current trans¬
formers, and their ratio and phase-angle errors are generally neglected. On the
other hand it is often necessary to pay attention to the transient response of the
CVTs under fault conditions, as errors under these conditions are possible.
Transient response of CVTs is beyond the scope of our discussion.
The job of a relay is to discriminate between a fault within its zone of protection
and all other system conditions. It must act (energize the trip coil of its asso¬
ciated circuit breakers) dependably for faults within its zones of protection, and
provide security against false tripping for faults outside those zones. A relay is
made secure and dependable by designing into it a logical decision-making
capability such that, based upon the condition of its input signals, it is able to
produce the correct output for every possible state of its input signals. We will
now consider several classes of relays and their logical functional descriptions. In
spite of the great variety of relays found on power systems, a majority of them
fall into five categories. Their logical performance can be defined in terms of the
inputs and outputs of the relay independently of the hardware used in building
the relay. For each type of relay, we will specify conditions on their input signals
(usually voltages and currents) and the corresponding state of the relay output.
The relay output of interest in the present context is the input to the breaker trip
coil. Consequently the output state of the relay will be, with its contacts closed,
called trip, or with its contacts open, called block or block to trip. The five relay
classes to be considered here are:
1. Magnitude relays
2. Directional relays
3. Ratio relays
4. Differential relays
5. Pilot relays
1. Magnitude relays In their most common form these are current magnitude
relays—or overcurrent relays. They respond to the magnitude of their input
346 ELEMENTS OF POWER SYSTEM ANALYSIS
current, and operate to trip whenever the current magnitude exceeds a certain
value which is adjustable. If a value | Ip | expressed in terms of the secondary
winding of the CT can be found from system short circuit studies such that for
all faults within the zone of protection of a relay, the fault current magnitude
| If | also expressed in terms of the secondary winding will be greater than \Ip\,
then the following functional description will produce a dependable and secure
relay:
h\ > Up\ triP
(13.1)
\lf\ < \Ip\ block
where T is the relay operating time, and 0 is a function which describes its
dependence upon the fault-current level. This functional dependence can be
illustrated by adding the time circles such as Tj and T2 to the phasor diagram of
Fig. 13.6 as shown. The length of phasor 11f\ then falls on a time line (or
between two time lines) which represents the operating time of the relay for that
fault current. The traditional method of representing the characteristics of a time
overcurrent relay is as shown in Fig. 13.7. The pickup setting \lp\ of a relay is
adjustable through the taps on its input winding. For example, the relay IFC-53
(General Electric Company) whose characteristic curves are shown in Fig. 13.7
is available with tap settings of 1.0, 1.2, 1.5, 2.0, 3.0, 4.0, 5.0, 6.0, 7.0, 8.0, 10.0,
12.0 A. The function </> is usually asymptotic to the pickup value and decreases
as some inverse power of the current magnitude for \If\ > \Ip\. The character¬
istic curves are generally presented with multiples of pickup amperes as the
abscissa and operating time as the ordinate. Multiples of pickup amperes means
the ratio of relay current to pickup current. The inverse-time characteristic can
be shifted up or down by an adjustment known as the time-dial setting. In
Fig. 13.7, a time-dial setting of 1/2 produces the fastest operation of the relay,
whereas a setting of 10 produces the slowest operation for a given current.
Although time-dial adjustments are specified as discrete settings, intermediate
values can be obtained by interpolating between the discrete curves.
2. Directional relays In some applications, the zone of a relay includes all of the
power system that is situated in only one direction from the relay location. For
example, consider the relay R21 shown in Fig. 13.8a. This relay is required to
operate for faults to the left of its location, and block for all other conditions.
Since the transmission-line impedance is mostly reactive, the faults to the left of
R21 have currents flowing from bus 2 toward bus 1 which lag the voltage at bus
2 by an angle of about 90 degrees. On the other hand, for faults to the right of
bus 2, the current from bus 2 to bus 1 will lead the voltage at bus 2 by an angle
of about 90 degrees. The operation of the relay is described by dividing the
complex plane of the phasor diagram of Fig. 13.86 such that for all faults pro¬
ducing current phasors lying in the shaded region (when the voltage at bus 2 is
used as a reference) the relay would trip, and for all other faults it would block.
Such a relay is called directional, since it depends for its operation upon the
direction of the current with respect to the voltage. The quantity that provides
the reference phasor is called a polarizing quantity. Thus the directional relay
described above uses a polarizing voltage. Sometimes certain current signals may
also be used as polarizing signals. The relay can be made more selective by
defining a narrower region around the fault-current phasor. In general the oper¬
ating principle of a directional relay can be described by
Time-dial, settings
Figure 13.7 Characteristic curves of type IFC-53 time overcurrent relays (Courtesy General Electric
Company).
SYSTEM PROTECTION 349
Trip i Block
-hi (reverse)
©
-D
R21
(6)
Figure 13.8 Operating principle of a directional relay: (a) one-line diagram to show location and
(b) relay performance characteristic in the complex plane.
where 9op is the phase angle of the operating quantity measured with the polariz¬
ing phasor as the reference, and 0min and 0max are the two angles defining the
boundary of the operating characteristic.
3. Ratio relays Consider the relay R12 shown in Fig. 13.9a. In some applica¬
tions, it is necessary that the relay operate for faults within a certain distance of
its location on any of the lines originating at bus 1. The vicinity is described by
the distance along the lines, or equivalently by the impedance between bus 1 and
the fault location. The zone of protection is thus a region such that the length of
a line originating at bus 1 and having an impedance less than the required
setting |Zr| is included in the zone. This condition can be conveniently ex¬
pressed as a requirement on the ratio of the voltage and current at the location
of R12. Let this ratio (which has the dimensions of an impedance) be
(13.4)
and the relay is called an impedance or distance relay. In the complex impedance
plane, the locus of constant \Zr \ is a circle as shown in Fig. 13.9b. Note that the
impedance Z is defined in Eq. (13.4) as a ratio of the voltage and current at relay
location 1. During normal system conditions this ratio will be a complex number
with some arbitrary phase angle determined by the load power factor. Since the
load current is usually much smaller than the fault current, the ratio Z will have
a large magnitude (and an arbitrary phase angle) during normal system condi¬
tions. Therefore Z plotted in the complex plane under normal system conditions
will lie outside the circle of radius | Zr | and consequently the circuit breaker will
not trip during normal system conditions. Under faulted conditions Z appears to
the relay to be a load whose impedance is that of the line between the relay
350 ELEMENTS OF POWER SYSTEM ANALYSIS
location and the fault. The angle associated with Z is 6 or n 4- 9 depending upon
whether the fault is to the right or left of bus 1 in the circuit of Fig. 13.9a.
A simple modification of an impedance relay is often found to be quite
useful. The circle in Fig. 13.9h, which is centered at the origin, can be offset by an
amount Z' producing the characteristic of the offset impedance relay shown in
Fig. 13.9c. The performance of this type of relay is described by
unit). Then for normal conditions, as well as for faults outside the zone of
protection
I\ — I2 = 0
11 12 — If
where If is the fault current as seen from the secondary side of the CTs. It
should be realized that due to the errors of the current transformers, these
equations will not exactly hold in practice. To account for these inaccuracies, a
low value of current | Ip | may be chosen such that
lc-ci<ici
for normal system conditions or for faults external to the zone of protection; and
Such a relay is known as a percent differential relay. The current (/x + 12)/,2 is
called the restraining current, and the current (I{ — I2) is the tripping current of
the relay. The relay coils 1 and 2 in Fig. 13.10 have currents It and I2 flowing
through them. If a differential relay is constructed in such a fashion that the
currents through coils 1 and 2 oppose the effect of current through 3, then such a
relay will exhibit the percent differential characteristic expressed by (13.8). The
relative effectiveness of coils 1 and 2 compared to coil 3 is determined by the
constant k of the percent differential relay. In an electromechanical percent
differential relay, coils 1, 2, and 3 are wound on a common magnetic core in such
a direction that currents through 1 and 2 produce a magnetomotive force that is
in opposition to that produced by current in 3. In an electronic relay the desired
characteristic is obtained by amplification factors in the appropriate signal
paths.
A relay of this type can also be used to protect a bus and, of course, a motor.
5. Pilot relays The differential relays discussed above require that the boundary
points of the protected zone be physically close to each other so that the signals
from these boundary points can be connected to the relay. This is possible only
when the zone of protection contains some power equipment of limited size such
as a transformer, a generator, or a bus. When transmission lines are to be
protected by a relay, their terminals may be hundreds of miles apart, and it
becomes impractical to connect the signals from the ends of the transmission line
to one relay. Pilot relaying provides a technique of communicating information
from a remote zone boundary to the relay at each terminal. Although a direct
substitution of pilot communication channels for each differential current signal
wire is not economically or technically feasible, equivalent information trans¬
mission schemes have been devised. The physical medium used for pilot channels
could be conductors of a telephone circuit, high-frequency signals coupled on to
the power transmission line itself (known as the power-line carrier), or micro-
wave channels. Application of pilot relaying will be considered in Sec. 13.6.
It was pointed out at the beginning of this chapter that the protection system
contains many subsystems, and the successful removal of a fault requires that
each subsystem and component function correctly. The protection systems con¬
sidered so far were primarily responsible for the removal of the fault as soon as
possible while deenergizing as little of the system as required. These protection
systems are known as the primary protection systems. However, it is conceivable
that some components or subsystems of the primary protection systems may fail
to operate correctly, and it is the usual practice to allow for a backup protection
system which would take over the job of protection in case the appropriate
primary protection system fails to clear the fault. Consider the power system
shown in Fig. 13.11. For a fault at P, the primary (main) protection system must
SYSTEM PROTECTION 353
open circuit breakers F and G. One method of backing up the primary protec¬
tion system is to duplicate it entirely (or as much of it as is economically
feasible) so that the failure of one primary system does not prevent the removal
of the fault. Such a backup protection system is known as duplicate primary, for
obvious reasons, and is used on important circuits where the added cost can be
justified. However, there are certain components that are inevitably common to
the first primary and the duplicate primary. (Examples are circuit breakers,
batteries which operate breaker trip coils, CTs and CVTs.) It is therefore pos¬
sible that both primaries may be affected by the failure of one of these common
components, and provision must be made to furnish backup protection from a
remote location where the possibility of a common mode of failure with the
primary protection system is slight. This remote backup function is easily incor¬
porated in the primary protection system at the remote location. For example,
suppose that the primary protection system at bus 1 in Fig. 13.11 has failed to
clear the fault at P. (The bus-5 end is assumed to operate correctly.) Recognizing
this failure, we can arrange the primary protection systems at buses 2, 3, and 4 to
trip circuit breakers A, D, and H, respectively. The protection systems at 2, 3,
and 4, in addition to providing their primary protection for lines 2-1, 3-1, and
4-1, will also provide a remote backup protection for the primary protection
system at bus 1 for line 1-5. The operation of a remote backup system removes a
far greater portion of the power system from service than does the operation of
the primary protection system. In the above example, lines 2-1, 3-1, and 4-1 are
removed in addition to the originally faulted line 1-5 when the fault is removed
by the remote backup protection system. The service to any loads that may be
connected at buses 2, 3, and 4 may be affected, and there will be no service to
bus 1. Secondly, the backup system must allow a sufficient time for the primary
protection system to function normally. A too-hasty operation of the backup
protection may lead to unnecessary removal of the larger portion of the power
system. The backup system is thus made slower-acting by introducing a delay
between the maximum time for fault clearing by the primary system, and the
fastest possible response of the backup system. This delay is called the coordina¬
tion time delay, and it is required to help coordinate the operation of the primary
and the backup protection system.
Returning once again to Fig. 13.11 we note that, upon the failure of the
primary protection at bus 1 associated with line 1-5, a backup system equivalent
to the remote backup system described so far may be designed to trip circuit
breakers B, C, and E all located at bus 1. Such a protection system is known as
354 ELEMENTS OF POWER SYSTEM ANALYSIS
the local backup protection, and is generally provided to back up the failure of
the circuit breaker responsible for fault clearing (breaker F in this example). For
this reason, the local backup protection system is also known as breaker-failure
protection. Since the primary protection system and the local breaker-failure
protection system may share certain subsystems—such as station battery—there
are certain modes of failure which are common to the two systems, and some
form of remote backup protection is considered essential to a well-designed
protection system.
with the distance to the fault from the generator, the fault current will be in¬
versely proportional to this distance. The fault current If as a function of dist¬
ance from bus 1 is shown qualitatively in Fig. 13.12b. Furthermore, the fault
current magnitudes will change depending upon the type of fault and the
amount of generation connected at bus 1. For example, if the generator at bus 1
is an equivalent representation of two parallel transformers, then fault currents
would be lower when one of the transformers is out of service for any reason. In
general, there will be a fault current magnitude curve as shown in Fig. 13.12b for
maximum fault-current levels (obtained when maximum generation is in service
and a three-phase fault is considered), and one for minimum fault levels (ob¬
tained when minimum generation is in service and a line-to-line or a line-to-
ground fault, whether or not through impedance to ground, is considered.) The
time-overcurrent relays discussed earlier can be set to provide primary protec¬
tion for a line, as well as the remote backup for a neighboring line for this
system. Relays at each of the three buses 1, 2, and 3, are provided to protect their
respective lines as primary protection relays, and to provide remote backup
protection to one line downstream from the relay location. Thus the relay at 1,
in addition to providing primary protection for line 1-2, also provides the
remote backup protection for line 2-3. The relay at 3 need provide only primary
protection for line 3-4, since there is no other line to the right of line 3-4. When
the relay at 1 provides backup protection for line 2-3, it must be so adjusted that
it operates with a sufficient time delay (its coordination time delay) such that the
relay at bus 2 will always be expected to operate first for faults on line 2-3. It is
not considered necessary, nor is it practical, to provide backup protection for
any line beyond bus 3 with the relay at bus 1. We will illustrate these concepts
with the following numerical examples.
J5.0 ®
-^Nbi
o j 9.6
j5-0
Figure 13.13 One-line diagram of the radial system for Examples 13.2 and 13.3. Line and
transformer reactance values are marked in ohms.
the transformer is an infinite bus. The protection system for line-to-line and
three-phase faults is to be designed. Transmission line reactances in ohms
are shown in Fig. 13.13, and the transformer reactances are in ohms referred
to the 13.8-kV side. Neglect resistance and calculate the minimum and maxi¬
mum fault currents for a fault at bus 5.
Solution Maximum fault current will occur for a three-phase fault with
both transformers in service. At bus 5 for this case
13,800/^/3
—/202.75 A
f ~ j(2.5 + 9.6 + 6.4 + 8.0 + 12.8)
Minimum fault current will occur with only one transformer in service
for a line-to-line fault. For a three-phase fault with just one transformer
13,800/^/3
—7190.6 A
f ~ j(5.0 + 9.6 + 6.4 + 8.0 + 12.8)
(—;'190.6) = -7165.1 A
2
Fault at bus 1 2 3 4 5
Maximum fault current, A 3187.2 658.5 430.7 300.7 202.7
Minimum fault current, A 1380.0 472.6 328.6 237.9 165.1
SYSTEM PROTECTION 357
Example 133 Select CT ratios, relay tap (pickup) settings, and relay time-
dial settings for the system of Example 13.2. Use at all locations the IFC-53
relay whose characteristic curves are given in Fig. 13.7 and whose tap set¬
tings are listed in Sec. 13.4. Since each line has a breaker at only one end,
simplify the notation by designating the relays at buses 1, 2, 3, and 4 by Rl,
R2, R3, and R4, respectively. The breaker at each bus will open all three
phases when tripped by any of the three associated relays. All three relays at
bus 1, for example, will be designated Rl.
Solution Settings for relay R4: This relay must operate for all currents
above 165.1 A, but for reliability a relay would be selected which will oper¬
ate when current in the line is one third of minimum, or
165.1
/p 55 A
3
For this current a CT ratio of 50/5 (Table 13.1) will result in a relay
current of
L= 5.5 A
300.7 x ^ = 30.1 A
and for a relay tap setting of 5 the ratio of relay current to tap setting for
both is 30.1/5 = 6.0. Figure 13.7 tells us the operating time for R4 is 0.135 s
since the time-dial setting is 1/2. So in the event of failure of R4, relay R3
must operate in
0.135 + 0.3 = 0.435 s
and Fig. 13.7 tells us the required time-dial setting for R3 is 2.0.
If we had provided for R3 a delay of 0.3 s for the lowest rather than the
highest fault current seen by R4, we would have determined a time-dial
setting of less than 2.0, which would not have provided a delay of 0.3 s for
the highest current seen by R4.
Setting for relay R2: The smallest fault current for which R2 must pick
up to provide backup for R3 is 237.9 A as given in Table 13.2. We might
choose a CT ratio of 100/5. Then with the required reliability which causes
us to design for pickup at one third of the minimum fault current we com¬
pute a pickup setting of
l x 237.9 x ~ 3.9 A
3 100
430.7 x A x i = 8.6
50 5
\
Since the time-dial setting of R3 is 2.0 that relay will operate in 0.31 s as
read from Fig. 13.7. So for proper coordination with R3 relay R2 must
operate in
0.31+0.3 =0.61 s
430.7 = 5.4
R1 R2 R3 R4
© ©
_ A B C D E F
O-o- —Q-O
(a)
Figure 13.14 One-line diagrams for loop systems. Heavy arrows beside each circuit breaker show
the direction to the fault for which the relay will respond. Relays having all arrows pointing in the
same direction around the loop coordinate with each other.
360 ELEMENTS OF POWER SYSTEM ANALYSIS
directional and overcurrent units in such a manner that a logical “and” operation
between their outputs is performed. Their associated breakers will not operate
unless both relays provide a trip signal.
©'/ Pl'\
-D- B21
hO t>|
B12 P B23 3QO
B32 1
^3 Zone 1 } P:
-OH B24 @
l\
\V _Zone_2_ 4/
o-j
B42'
Zone 3
(a)
(b)
Figure 13.15 Coordination of distance (impedance) relays. The zone of protection shown by the solid
line in (a) is replaced by zones 1 and 2 identified by dashed lines. Zone 3 provides backup protection
for neighboring protection systems. Time delay and operating time is shown in (b) for R12 R23 and
R24.
SYSTEM PROTECTION 361
B23 has failed to operate. Clearly the zone-2 clearing time must be slower than
the slowest possible zone-1 clearing time of relay R23, so that R12 does not trip
for the fault at P3 prematurely. A similar zone-2 setting also exists at bus 4 for
relay R42 and circuit breaker B42. The fault at P3 lies in zone 2 of relay R42.
The response time of relays R12, R23, and R24 to their respective zone-1 and
zone-2 faults is shown schematically in Fig. 13.156. The abscissa in the response¬
time diagram is the fault location along the appropriate lines, and the ordinate is
the relay operating time. The zone-1 operating time is of the order of 1 cycle,
whereas the zone-2 operating time varies between 15 and 30 cycles.
In most cases, the distance relays are provided with another zone of protec¬
tion known as their zone 3 to provide remote backup for the neighboring lines.
The third zone of a relay must reach beyond the longest line emanating from the
bus at the remote end of its protected line. The remote backup function must
coordinate with the primary protection which it backs up. Thus the third zone of
relay R12 must be coordinated with zone 2 of the relays at bus 2 (R23 and R24).
Notice also that the Fig. 13.156 points to an important principle of relay coor¬
dination. The coordination is by time and also by distance. A faster zone of
protection must reach in distance beyond the reach of its slower backup. Thus
the zone-2 reach of relay R12 is shorter than the zone-1 reach of relay R23 or
R24. Similarly zone-3 reach of relay R12 is shorter than the zone-2 reach of R23
and R24. Unless this coordination by distance was employed, for certain faults,
instead of high-speed clearing an unnecessarily slow backup time clearing would
result. The zone-3 coordinating time is generally of the order of one second. The
three zones of protection of relay R12 and the operating times for the three
zones are shown schematically in Fig. 13.156.
The characteristic of a directional distance relay in the complex R-X plane is
shown in Fig. 13.16a. A straight line called the line impedance locus is shown in
the figure. Along this line the positive-sequence impedances of the protected line
Figure 13.16 Characteristics of (a) directional impedance relay and (b) mho relay for Example 13.4.
SYSTEM PROTECTION 363
as seen by the relay between its location and different points along the protected
line can be plotted. The directional unit of the relay causes separation of the trip
and block regions of the relay characteristic in Fig. 13.16a by a line drawn
perpendicular to the line impedance locus. The impedance measured from bus 1
to buses 2 and 4 along the line impedance locus are indicated by numerals
enclosed in circles. Zone circles whose centers are at the origin of the R-X plane
have radii equal to the magnitudes of the impedances of the protected line seen
by R12 from bus 1 to the end of the zone identified by the numbers of the circles.
Thus, the intersection of a zone circle with the line impedance locus is the line
impedance between the relay and the end of the zone. After a fault occurs the
impedance seen by the relay is very small compared to the load impedance seen
during normal operation. The relays operate when the impedance seen by the
relay lies within a zone circle. For impedances inside the zone-1 circle, operation
occurs in minimum time. Time delays are set for later operation for zone-2 and
then zone-3 faults.
The characteristic of a mho relay is shown in Fig. 13-166 with the centers
of the zone circles lying on the line impedance locus. Note that the radii of the
zone circles are half of the radii of the corresponding zone circles of the direc¬
tional distance relay for the same impedances since the intersection of a zone
circle with the line impedance locus must still be the impedance of the line seen
by the relay between its location and the end of the zone.
The three-step distance relaying scheme described here provides a versatile
protection system for high-voltage transmission lines. With minor modifications
to accommodate the nature of a given system this protection is used almost
universally to protect transmission lines of a modern power network. In many
cases ground faults are provided for by the directional time overcurrent relays of
the type described earlier, while three-phase and line-to-line faults are covered by
distance relays. Occasionally it becomes very difficult to coordinate the third
zone times of a relay with the second zones of the neighboring lines; especially at
EHV levels. In such cases, the remote backup (zone-3) function of the distance
relays may be omitted.
During emergency load-flow conditions when the load is quite high the
impedance seen by the relay is low and must be checked to make sure that it
does not fall within one of the zone circles of the relay characteristic.
50 x 106
209.2 A
^3 x 138 x 103
138 x 103
= 79.67 x 103 V
^7T
It was pointed out in Sec. 13.3 that the industry standard for CVT secondary
voltage is 67 V for line-to-neutral voltages. Consequently we select a CVT
ratio of
79.67 x 103
1189.1/1
67
in which case a normal system voltage will produce 67 volts for each phase
on the CVT secondary. Denoting primary and secondary voltages of the
CVT at bus 1 as Vp and the primary current of the CT as Ip, we have for the
impedance measured by the relay
7P/1189.1
= Z,line X 0.0336
V40
Thus the impedances of the three lines as seen by the relay R12 are
approximately
Line 1-2 0.11 + j 1.1 Q, secondary
Line 2-3 0.11 + jl.l Q, secondary
Line 2-4 0.16 +j 1.6 Q, secondary
67 .
Z|oad ~ 209.2(5/200) ^°'8 +;0'6)
The zone-1 setting of the relay R12 must underreach the line 1-2, so that
the setting should be
The zone-2 setting should reach past terminal 2 of the line 1-2. To allow for
the various possible inaccuracies of the transducer-relay system, zone 2 is
usually set at about 1.2 times the length of the line being protected. Zone 2
for R12 is therefore set at
The zone-3 setting should reach beyond the longest line connected to bus 2.
Thus the zone-3 setting must be
Note that once again a factor of 1.2 is used as a multiplier on the impedance
of the longest line connected to bus 2 to make sure that zone 3 of relay R12
will reach past bus 4 even in the presence of inaccuracies introduced in the
relaying system. A directional impedance relay with the characteristic shown
in Fig. 13.16a can be used.
Both Figs. 13.16a and 13.166 apply to this example, and points 2 and 4
on the line impedance locus correspond to the calculated impedances from
bus 1 to buses 2 and 4. As seen by the relay the load impedance Z,oad is more
than 3 times the line impedance from bus 1 to bus 4 and lies well beyond the
zone-3 circle of both the directional impedance relay and the mho relay.
Consequently there is no danger of tripping the line during any load swings
that may occur on the transmission line. If the maximum load had been too
close to the zone-3 setting of the directional impedance relay, it might have
been necessary to replace it by the mho relay whose zone-3 circle encloses a
smaller area of the R-X plane, as is well apparent in Fig. 13.16.
G)
Pi
—□“
B12
Figure 13.17 Line to be protected by pilot relaying.
366 ELEMENTS OF POWER SYSTEM ANALYSIS
In modern HV and EHV systems, this delayed clearing from the remote end
is often found to be unacceptable because of the complex nature of the modern
interconnected network and the tighter stability margins. It then becomes neces¬
sary to provide high-speed protection for the entire line (instead of the middle 60
percent). High-speed protection for the entire line is provided by pilot relaying of
the type described in Sec. 13.4. For a fault anywhere on the protected line, the
directional relays R12 and R21 see a unique condition: both relays see the fault
current flowing in the forward direction. This information, when communicated
to the remote ends over a pilot channel, confirms that a fault is indeed on the
protected line. Consider faults at P2 and P3 on line 1-2 shown in Fig. 13.15.
Although the relay R12 sees no difference between the two faults, the relay R21
sees P2 as an internal fault and P3 as an external fault (being in the reverse
direction from its zone of protection). Upon receiving this directional informa¬
tion at R12, that relay will be able to block (prevent) tripping for the fault at P3.
(Note that the fault at P3 is in the zone of protection of bus 2 but not of the line
1-2). The fault at P2 is tripped simultaneously at high speed from both ends.
Such a system is called a “directional comparison” pilot scheme. Equivalent
performance can be obtained by comparing the phase angles of the fault currents
seen at the two ends of a line, and exchanging this phase angle information over
the pilot channel. Such a scheme is known as a “ phase comparison ” scheme. A
discussion of the merits and demerits of the two schemes is beyond the scope of
this book, although it may be mentioned that both types of protection schemes
are used in practice.
As in the case of transmission lines, the type of protection used for power
transformers depends upon their size, voltage rating, and the nature of their
application. For small transformers (smaller than about 2 MVA) protection with
fuses may be adequate; whereas for transformers of greater than 10-MVA capa¬
city differential relays with harmonic restraint may be used-
Consider first the differential protection of a single-phase two-winding
power transformer shown in Fig. 13.18. If the power transformer is carrying load
ii v2
-► • • -
currents /j and /'2 in the primary and secondary windings, we know that with
magnetizing current neglected
(13.9)
12 Nt
where Nt and N2 are the turns of the primary and secondary windings of the
power transformer, respectively. The CT secondary currents are Ix and /2, and
the turns ratio of the CTs on the primary and secondary side of the power
transformer are n1 and n2, respectively (one turn on the primary of a CT means
n turns on the secondary). So
h=— 12 = - (13.10)
»1 n2
To prevent tripping under normal conditions when Eq. (13.9) must be true the
current /j - I2 through the trip coil must be zero; that is Ix must equal I2. So
from Eqs. (13.9) and (13.10) we require that
«I =N2
(13.11)
n2 N,
With an internal fault on the secondary side of the power transformer and with
current I'f in the fault
For a fault on the primary side of the transformer, the right-hand side of
Eq. (13.12) would be If the relay is set with a sufficiently small value of
pickup current | Ip | the differential relay would trip for an internal fault, while
blocking for external faults or normal load.
As we discussed in Sec. 8.10, a power transformer is usually equipped with
variable tap settings, which allow its secondary voltage to be adjusted over a
certain range. The adjustments usually vary in small steps over a range ± 10
percent from the nominal turns ratio of Nl/N2. If tap settings result in an
off-normal turns ratio, the relay will see a differential current during normal load
conditions. To avoid improper operation in this case a percent differential relay
must be used.
Three-phase transformers with Y-A windings require further discussion. As
pointed out in Sec. 11.4 the primary and secondary currents of such transformers
differ in magnitude and phase angles during normal operating conditions. The
current transformers must therefore be connected in such a manner that the CT
secondary line currents as seen by the relay are in phase, and the CT ratios must
also be adjusted so that the current magnitudes as seen by the relay are equal
under normal (unfaulted) conditions. The correct phase-angle relationship is
obtained by connecting the CTs on the wye side of the power transformer in
delta, and those on the delta side of the power transformer in wye. In this
368 ELEMENTS OF POWER SYSTEM ANALYSIS
manner, the CT connections compensate for the phase shift created by> the
Y-A-connected power transformer. These considerations are illustrated by the
following example.
Solution The currents on the 345-kV side and 34.5-kV side of the trans¬
former when it is carrying its maximum expected load are
60 x 106 60 x 106
100.4 A and = 1004.1 A
73 x 345 x 103 73 x 34.5 x 103
We will use CT ratio of 1000/5 on the 34.5-kV side. Since the CTs on
this side are connected in wye, the current flowing to the differential relay
from this side will be
1004 x £ 5.0 A
1000
To balance this current, the line currents produced from the A-connected
CTs on the 345-kV side must also be 5.0 A. This will require that each of the
secondary windings of the A-connected CTs have a current of
5.0
2.9 A
75
This current in the CT secondary windings would require CT ratios of
100.4
34.64
2.9
for the CTs on the 345-kV side. The nearest available* standard CT ratio is
200/5. If we use this ratio, the CT secondary currents would be
100.4 2.51 A
and the line currents from the A-connected CTs to the differential relays
would be
2.51 x ^3 = 4.35 A
Clearly this current cannot balance the 5.0 A produced by the 34.5-kV side.
This situation of mismatched currents when standard CT ratios are used
is quite commonly encountered in designing the protection system for Y-A-
connected transformers. A convenient solution is provided by auxiliary cur¬
rent transformers which provide a wide range of turn ratios. These auxiliary
SYSTEM PROTECTION 369
Figure 13.19 Wiring diagram showing currents in amperes for the power and relaying circuits
of Example 13.5.
CTs are small and inexpensive devices since their primary and secondary
windings are low-voltage low-current circuits. Using a set of three auxiliary
CTs with turns ratios of
5.0
1.155
435
would produce a balanced set of currents in the differential relay when the
power transformer is carrying normal load. For an assumed power factor 0.8
lagging, the currents in the power transformer and the various CTs are as
shown in Fig. 13.19.
normal operation and the magnetizing current is very small. However, wjien a
transformer is energized, it can draw very heavy magnetizing currents (known as
the magnetizing inrush currents) which decay with time to the very small steady-
state value. If this high inrush current does flow during energization of the trans¬
former, it appears as differential current since it flows in the primary winding only.
It is essential to detect such a condition and stop the differential relay from tripping
the transformer. One of the more common methods used to accomplish this func¬
tion is based upon the fact that the magnetizing inrush current is rich in
harmonics whereas a fault current is a purer fundamental frequency sinusoid. To
take advantage of this fact, in addition to the fundamental frequency restraining
current of (7j + l2)/2, another restraining signal proportional to the harmonic
content of the differential current is generated in the differential relay. By selecting
a proper weighting coefficient for the harmonic component, it is possible to prevent
the differential relay from tripping the transformer during its energization, even
though a substantial tripping current may be produced due to the magnetizing
inrush current.
13.9 SUMMARY
In this chapter we have concentrated on the discussion of protective relaying
systems for modern high-voltage power networks. We did not study the applica¬
tion of fuses and reclosers, which are more commonly used on distribution
SYSTEM PROTECTION 371
CD
PROBLEMS
13.1 In the system whose one-line diagram and zones of protection are shown in Fig. 13.36 where is
the fault located if the breakers tripped are (a) G and C, (b) F, G, and H, (c) F, G, H, and B, and
(d) D, C, and F?
13.2 Determine the time-dial setting for R3 of Example 13.3 if the setting had been determined for
the lowest fault current seen by R4? Why is the setting made for the highest rather than the lowest
fault current seen by R4?
13.3 In Example 13.3, assume that a line-to-line fault occurs at the midpoint of line 2-3. Which relay
will operate for this fault? What will be its operating time? Assume that this relay fails to clear the
fault, which relay will operate to clear the fault now? How long will it take?
13.4 An 11-kV radial system is shown in Fig. 13.20. The positive- and zero-sequence impedances of
line 1-2 are 0.8 Q and 2.5 fl, respectively. Impedances of line 2-3 are three times as large. The positive-
and zero-sequence impedances of each of the two transformers are j'2.0 ohms and j 3.5 ohms, respectively.
Under emergency conditions, the system may be operated with one transformer out of service. Deter¬
mine the CT ratios, pickup values, and time-dial settings for IFC-53 relays designed to provide single
line-to-ground fault protection for this system. Assume the high-tension bus is an infinite bus whose
voltage will provide 11 kV at the low-tension bus at no load.
13.5 A portion of a 765-kV network is shown in Fig. 13.21. The positive and zero sequence impedances
of the transmission lines are 0.01 -I- j0.6 ohm and 0.1 + yl .8 ohms per mile respectively. Assume that
the generator impedance isylO.O ohms for positive and negative sequence, andy'20.0 ohms for the zero
sequence.
(a) Relays R12, R23, and R34 use inverse-time directional IFC-53 overcurrent relays for single
line-to-ground fault protection of this system. Determine the fault current needed for setting the pickup
value of R12 ground relay. You may neglect line resistances for this calculation.
t See, for instance, C. R. Mason, The Art and Science of Protective Relaying, John Wiley and
Sons, Inc., New York, 1956, and Westinghouse Electric Corporation, Applied Protective Relaying,
Relay Instruments Division, Newark, N.J., 1976.
©B12 @
B21 B23 B32 B34 B43
o-o- -Q
Figure 13.21 One-line diagram for Prob.
-300 mi ■ -150 mi ■ -100 mi-
13.6.
372 ELEMENTS OF POWER SYSTEM ANALYSIS
(b) Select CT and CVT ratios for phase distance relays at bus 1. You may assume that the relay
current coils can carry 10 A continuously, and that the emergency line loading limit is 3000*MVA.
Use standard CT ratios.
(c) Determine and show on the (secondary) R-X diagram the three zones of a directional im¬
pedance relay at bus 1 for phase fault protection.
(d) Also show the location of the equivalent impedance of the emergency load on the R-X
diagram. Do you see any problems with line operating at emergency load? What solution would you
propose ?
13.6 A three-phase fault occurs at the terminals of the delta winding in Fig. 13.19 within the zone of
protection of the differential relay. Assume that the positive-sequence impedance of the transformer
as seen from the 345-kV side is j250 ohms, and that the power system feeding the 345-kV side is of
infinite short-circuit capacity. What are the currents flowing in all the leads shown in Fig. 13.19 in
this case? Neglect prefault current and assume no fault current originates in the low-tension part of
the system.
CHAPTER
FOURTEEN
POWER SYSTEM STABILITY
Power system stability may be defined as that property of the system which
enables the synchronous machines of the system to respond to a disturbance
from a normal operating condition so as to return to a condition where their
operation is again normal. Stability studies are usually classified into three types
depending upon the nature and order of magnitude of the disturbance. These are
transient, dynamic, and steady-state stability studies.
373
374 ELEMENTS OF POWER SYSTEM ANALYSIS
These assumptions permit the use of phasor algebra for the transmission
network and solution by load-flow techniques using 60-Hz parameters. Also,
negative- and zero-sequence networks can be incorporated into the positive-
sequence network at the fault point. As we shall see, three-phase balanced faults
are generally considered. However, in some special studies, circuit-breaker clear¬
ing operations may be such that consideration of unbalanced conditions is
unavoidable.t
The mechanical torque Tm and the electrical torque Te are considered positive for
the synchronous generator. This means that Tm is the resultant shaft torque
t For information beyond the scope of this book, see P. M. Anderson and A. A. Fouad, Power
System Control and Stability, The Iowa State University Press, Ames, Iowa, 1977.
376 ELEMENTS OF POWER SYSTEM ANALYSIS
Figure 14.1 Representation of a machine rotor comparing direction of rotation and mechanical and
electrical torques for (a) a generator and (b) a motor.
dm = cosmt + Sm (14.2)
where cosm is the synchronous speed of the machine in mechanical radians per
second and 5m is the angular displacement of the rotor, in mechanical radians,
POWER SYSTEM STABILITY 377
from the synchronously rotating reference axis. The derivatives of Eq. (14.2) with
respect to time are
djL ,ddm
(143)
dt a,- + ~df
and
d2em = d2Sm
(14.4)
dt2 dt2
Equation (14.3) shows that the rotor angular velocity d6m/dt is constant and
equals the synchronous speed only when ddm/dt is zero. Therefore dSm/dt repre¬
sents the deviation of the rotor speed from synchronism and the units of measure
are mechanical radians per second. Equation (14.4) represents the rotor accelera¬
tion measured in mechanical radians per second-squared.
Substituting Eq. (14.4) into Eq. (14.1), we obtain
dOm
co m (14.6)
dt
for the angular velocity of the rotor. We recall from elementary dynamics that
power equals torque times angular velocity and so, multiplying Eq. (14.5) by com,
we obtain
where Pm is the shaft power input to the machine less rotational losses, Pe is the
electrical power crossing its air-gap and Pa is the accelerating power which
accounts for any unbalance between those two quantities. Usually we will neg¬
lect rotational losses and armature \I\2R losses and think of Pm as power
supplied by the prime mover and Pe as the electrical power output.
The coefficient Jcom is the angular momentum of the rotor; at synchronous
speed cosm, it is denoted by M and called the inertia constant of the machine.
Obviously the units in which M is expressed must correspond to those of J and
(om. A careful check of the units in each term of Eq. (14.7) shows that M is
expressed in joule-seconds per mechanical radian and we write
and
iJoiL iMUsm
MJ/MVA (14.9)
H
5mach 5mach
where Smach is the three-phase rating of the machine in MVA. Solving for M in
Eq. (14.9), we obtain
2H
M = Smach MJ/mech rad (14.10)
co«
2H d*Sm P. =K^P,
(14.11)
^sm dt ^mach “^mach
2Hd*d
= p
x a
= xp m - xpe per unit (14.12)
cos dt2
provided both S and cos have consistent units which may be mechanical or
electrical degrees or radians. H and t have consistent units since megajoules per
megavoltampere is in units of time in seconds and Pa, Pm, and Pe must be in per
unit on the same base as H. When the subscript m is associated with co, cos, and 5
it means mechanical units are used; otherwise electrical units are implied. Ac¬
cordingly, cos is the synchronous speed in electrical units. For a system with an
electrical frequency of/hertz, Eq. (14.12) becomes
H^cPS
= P
A a
= APm - per unit (1413)
nf dt2
H d2S
= P
1 a = 1P m - x
Pe per unit (14.14)
180/ dt2
Equation (14.12), called the swing equation of the machine, is the fundamen¬
tal equation which governs the rotational dynamics of the synchronous machine
in stability studies. We note that it is a second-order differential equation which
can be written as the two first-order differential equations
IHdco
— — = pm-Pe per unit (14.15)
cos at
dS
~ = (O-0)s (14.16)
in which a>, cos, and S involve electrical radians or electrical degrees. We will use
the various equivalent forms of the swing equation throughout this chapter to
determine the stability of a machine within a power system. When the swing
equation is solved we obtain the expression for d as a function of time. A graph
of the solution is called the swing curve of the machine and inspection of the
swing curves of all the machines of the system will show whether the machines
remain in synchronism after a disturbance.
The MVA base used in Eq. (14.11) is the machine rating which is introduced by
the definition of H. In a stability study of a power system with many synchro¬
nous machines, only one MVA base common to all parts of the system can be
chosen. Since the right-hand side of the swing equation for each machine must
be expressed in per unit on this common system base, it is clear that H on the
left-hand side of each swing equation must be also consistent with the system
base. This is accomplished by converting the H constant for each machine based
on its own individual rating, to a value determined by the system base, Ssystem.
Equation (14.11), multiplied on each side by the ratio (Smach/Ssystem), leads to the
conversion formula
(14.17)
^system
in which the subscript for each term indicates the corresponding base being used.
In industry studies the system base usually chosen is 100 MVA.
The inertia constant M is rarely used in practice and the forms of the swing
equation involving H are more often encountered. This is because the value of M
varies widely with the size and type of the machine whereas H assumes a much
narrower range of values as shown in Table 14.1. Machine manufacturers also
use the symbol WR2 to specify for the rotating parts of a generating unit (includ¬
ing the prime mover) the weight in pounds multiplied by the square of the radius
of gyration in feet. Hence WR2/32.2 is the moment of inertia of the machine in
slug-feet squared.
380 ELEMENTS OF POWER SYSTEM ANALYSIS
Turbine generator:
Condensing, 1800 r/min 9-6
3600 r/min 7-4
Noncondensing, 3600 r/min 4-3
Waterwheel generator:
Slow-speed, < 200 r/min 2-3
High-speed, >200 r/min 2-4
Synchronous condenser :§
Large 1.25
Small 1.00
Synchronous motor with load 2.00
varies from 1.0 to 5.0 and
higher for heavy flywheels
Example 14.1 Develop a formula to calculate the H constant from WR2 and
evaluate H for a nuclear generating unit rated at 1333 MVA, 1800 r/min
with WR2 = 5,820,000 lb-ft2.
1 WR2 27i(r/min)
KE = ft-lb
2 32.2 60
Since 550 ft-lb/s equals 746 W, it follows that 1 ft-lb equals 746/550 J. Hence,
converting foot-pounds to megajoules and dividing by the machine rating in
megavoltamperes, we obtain
= 3.27 MJ/MVA
1333
h = 3 27 x 1UU
= 4156 mJ/mva
2Hx d25x .
—l--nr = Pmi-Pei per unit (14.18)
cos at
Adding the equations together, and denoting <5, and S2 by S since the rotors
swing together, we obtain
where H = (Hx + H2), Pm = (Pml + Pm2) and Pe = (Pel + Pe2). This single
equation, which is in the form of Eq. (14.12), can be solved to represent the plant
dynamics.
Example 14.2 Two 60-Hz generating units operate in parallel within the
same power plant and have the following ratings:
Hx = 4.8 MJ/MVA
H2 = 3.27 MJ/MVA
Calculate the equivalent H constant for the two units on a 100-MVA base.
382 ELEMENTS OF POWER SYSTEM ANALYSIS
H = 67.59 MJ/MVA
and this value can be used in a single swing equation provided the machines
swing together so that their rotor angles are in step at each instant of time.
Machines which swing together are called coherent machines. It is noted that,
when both cos and S are expressed in electrical degrees or radians, the swing
equations for coherent machines can be combined together even though, as in
the example, the rated speeds are different. This fact is often used in stability
studies involving many machines in order to reduce the number of swing equa¬
tions which need to be solved.
For any pair of non-coherent machines in a system, swing equations similar to
Eqs. (14.18) and (14.19) can be written. Dividing each equation by its left-hand-
side coefficient and subtracting the resultant equations, we obtain
which also may be written more simply in the form of the basic swing equation,
Eq. (14.12), as follows
1H Ahi-P — p el 2 (14.23)
CO, 12 dt2 ~Fm12
Here the relative angle S12 equals 5X — S2 and an equivalent inertia and
weighted input and output powers are defined by
HiH 2
H12 = (14.24)
H i + H2
Pm\H2 ~ Pm2Pd\
Pm 12 — (14.25)
Hx + H2
PelH2-Pe2Hx
Pe 12 — (14.26)
Hx + H2
2H11d^S11 =
cos dt2 m e
which is also the format of Eq. (14.12) which applies for a single machine.
Equation (14.22) demonstrates that stability of a machine within a system is
a relative property associated with its dynamic behavior with respect to the
other machines of the system. The rotor angle of one machine, say <5l5 can be
chosen for comparison with the rotor angle of each other machine, symbolized
by S2. In order to be stable the angular differences between all machines must
decrease after the final switching operation such as the opening of a circuit-
breaker to clear a fault. While we may choose to plot the angle between a
machine’s rotor and a synchronously rotating reference axis, it is the relative
angles between machines which are important. Our discussion above emphasizes
the relative nature of the system stability property and shows that the essential
features of a stability study are revealed by consideration of two-machine prob¬
lems. Such problems are of two types; those having one machine of finite inertia
swinging with respect to an infinite bus and those having two finite-inertia
machines swinging with respect to each other. An infinite bus may be considered
for stability purposes as a bus at which is located a machine of constant internal
voltage, having zero impedance and infinite inertia. The point of connection of a
generator to a large power system may be regarded as such a bus. In all cases the
swing equation assumes the form of Eq. (14.12), each term of which must be
explicitly described before it can be solved. The equation for Pe is essential to
this description and we now proceed to its characterization for a general two-
machine system.
In the swing equation for the generator, the input mechanical power from the
prime mover Pm will be considered constant. As we have mentioned previously,
this is a reasonable assumption because conditions in the electrical network can
be expected to change before the control governor can cause the turbine to react.
Since Pm in Eq. (14.12) is constant, the electrical power output Pe will determine
whether the rotor accelerates, decelerates, or remains at synchronous speed.
When Pe equals Pm the machine operates at steady-state synchronous speed;
when Pe changes from this value the rotor deviates from synchronous speed.
384 ELEMENTS OF POWER SYSTEM ANALYSIS
i
\S>mSLr
(a)
the network. The elements of the bus admittance matrix for the network reduced
to two nodes in addition to the reference node is
Y ^11 ^12
K bus (14.28)
^21 ^22
Pk-jQk=vtYJYknv„ (14.29)
n=1
which upon letting k and N equal 1 and 2, respectively, and substituting E2 for V,
can be written
we obtain
Pi= \E'1\2G11+ \E\ | \E'211 ^ii | cos (<51 S2 $12) (14.31)
_ Q n
y-el2 2
Since Pt represents the electric power output of the generator (armature. Joss
neglected) we have replaced it by Pe in Eq. (14.35) which is often called the
power-angle equation; its graph as a function of <5 is called the power-angle curve.
The parameters Pc, Pmax, and y are constants for a given network configuration
and constant voltage magnitudes |E\ | and \E'2\. When the network is con¬
sidered without resistance all the elements of Ybus are susceptances and so both
Gn and y are zero. The power-angle equation which then applies for the pure
reactance network is simply the familiar equation
Pe = Pmaxsin<5 (14.37)
where Pmax = \E\ \ \E'2\/X and X is the transfer reactance between E\ and E'2.
Example 14.3 The single-line diagram of Fig. 14.4 shows a generator con¬
nected through parallel transmission lines to a large metropolitan system
considered as an infinite bus. The machine is delivering 1.0 per unit power
and both the terminal voltage and the infinite-bus voltage are 1.0 per unit.
Numbers on the diagram indicate the values of the reactances on a common
system base. The transient reactance of the generator is 0.20 per unit as
indicated. Determine the power-angle equation for the system applicable to
the operating conditions.
Solution The reactance diagram for the system is shown in Fig. 14.5a. The
series reactance between the terminal voltage and the infinite bus is
0.4
X = 0.10 + — =0.3 per unit
and therefore the 1.0 per unit power output of the generator is determined
by the power-angle equation
\vt\\v\ . (1.0)(1.0) .
' 1 ' 1 Sin a = ~ 1 sin a = 1.0
A (J.3
where V is the voltage of the infinite bus and a is the angle of the terminal
voltage relative to the infinite bus. Solving for a, we obtain
j‘0-40
1.0/0°
1.0/0°
-j 3.333
-nmm-
-72.5
+
/ 1.05/6. 1.0/0°
-7'5.0 -j 5.0S
(c)
Figure 14.5 Reactance diagram (a) for prefault network for Example 14.3 with impedances in
per unit and (b) and (c) for the faulted network for Example 14.4 with the same impedances con¬
verted to admittances and marked in per unit.
1.0/17.458° - 1.0/CT
/ =
j0.3
The power-angle equation relating the transient internal voltage E and the
infinite bus voltage V is determined by the total series reactance
0.4 ^ r
X = 02 + 0.1+— = 0.5 per unit
where 3 is the machine rotor angle with respect to the infinite bus.
388 ELEMENTS OF POWER SYSTEM ANALYSIS
This power-angle equation is plotted in Fig. 14.6. Note that the mechanical
input power Pm is constant and intersects the sinusoidal power-angle curve at
the operating angle = 28.44°. This is the initial angular position of the genera¬
tor rotor corresponding to the given operating conditions. The swing equation
for the machine may be written
Example 14.4 The system of Example 14.3 is operating under the indicated
conditions when a three-phase fault occurs at point P in Fig. 14.4. Deter¬
mine the power-angle equation for the system with the fault on and the
corresponding swing equation. Take H = 5 MJ/MVA.
\
Solution The reactance diagram is shown in Fig. 14.56 with the fault on
the system at point P. Values shown are admittances in per unit. The effect
of the short circuit caused by the fault is clearly shown by redrawing the
reactance diagram as in Fig. 14.5c. As calculated in Example 14.3, transient
internal voltage of the generator remains at E = 1.05/28.44° based on the
assumption of constant flux linkages in the machine. The net transfer admit¬
tance connecting the voltage sources remains to be determined. The buses
are numbered as shown and the Ybus is formed by inspection of Fig. 14.5c as
follows
'-3.333 0 3.333'
Ybus —j 0 -7.50 2.50
. 3.333 2.50 -10.833.
POWER SYSTEM STABILITY 389
Bus 3 has no external source connection and it may be removed by the node
elimination procedure of Sec. 7.4 to yield the reduced bus admittance matrix
5 d2S
= 1-0 ~ 0.808 sin <5 per unit (14.39)
For later reference note that, because of its inertia, the rotor cannot change
position instantly upon occurrence of the fault. Therefore, the rotor angle
5 is initially 28.44° as in Example 14.3 and the electrical power output is
Pe = 0.808 sin 28.44° = 0.385. The initial accelerating power is
Pa — 1.0 — 0.385 = 0.615 per unit
and the initial acceleration is positive with the value given by
Example 14.5 The fault on the system of Example 14.4 is cleared by simul¬
taneous opening of the circuit breakers at each end of the affected line.
Determine the power-angle equation and the swing equation for the post¬
fault period.
Solution Inspection of Fig. 14.5a shows that, upon removal of the faulted
line, the net transfer admittance across the system is
1
—j1.429 per unit
yi2 ~ j(0.2 + 0.1 +0.4)
F12 =71.429
390 ELEMENTS OF POWER SYSTEM ANALYSIS
In Example 14.3 the operating point on the sinusoidal Pe curve of Fig. 14.6 was
found to be at 30 equal to 28.44° where the mechanical power input Pm equals
the electrical power output Pe. In the same figure it is also seen that Pe equals
Pm at 3 = 151.56° and this might appear to be an equally acceptable operating
point. However, this is now shown not to be the case.
A common-sense requirement for an acceptable operating point is that the
generator shall not lose synchronism when small temporary changes occur in the
electrical power output from the machine. To examine this requirement, for fixed
mechanical input power Pm, consider small incremental changes in the operating
point parameters, that is, consider
Substituting the incremental variables of Eq. (14.40) into the basic swing equa¬
tion, Eq. (14.12), we obtain
2H d2(S0 + <5a)
— Pm ~ {Pe0 + PeA) (14.45)
cos dt2
Replacing the right-hand side of this equation by Eq. (14.44) and transposing
terms, we obtain
2H d2i5a ,
+ (pmax cos <50)<SA = 0 (14.46)
since <50 is a constant value. Noting that Pmax cos <50 is the slope of the power-
angle curve at the angle <50, we denote this slope as SP and define it as
dP
SP = -JT = pmax cos S0 (14.47)
dO 6=6o
d23A
(14.48)
dt2 + “ws*=0
This is a linear, second-order differential equation, the solution to which depends
upon the algebraic sign of SP. When SP is positive, the solution SA(t) corresponds
to that of simple harmonic motion; such motion is represented by the oscilla¬
tions of an undamped swinging pendulum.! When SP is negative, the solution
SA(t) increases exponentially without limit. Therefore, in Fig. 14.6 the operating
point <5 = 28.44° is a point of stable equilibrium, in the sense that the rotor angle
swing is bounded following a small perturbation. In the physical situation,
damping will restore the rotor angle to S0 = 28.44° following the temporary
electrical perturbation. On the other hand, the point S = 151.56° is a point of
unstable equilibrium since SP is negative there. So this point is not a valid
operating point.
The changing position of the generator rotor swinging with respect to the
infinite bus may be visualized by an analogy. Consider a pendulum swinging
from a pivot on a stationary frame, as shown in Fig. 14.7a. Points a and c are the
maximum points of the oscillation of the pendulum about the equilibrium point
b. Damping will eventually bring the pendulum to rest at b. Now imagine a disk
rotating in a clockwise direction about the pivot of the pendulum, as shown in
Fig. 14.76, and superimpose the motion of the pendulum on the motion of the
disk. When the pendulum is moving from a to c, the combined angular velocity
t The equation of simple harmonic motion is d2x/dt2 + w2nx = 0 which has the general solution
A cos co„ t + B sin a>n t with constants A and B determined by the initial conditions. The solution
when plotted is an undamped sinusoid of angular frequency co„.
392 ELEMENTS OF POWER SYSTEM ANALYSIS
is slower than that of the disk. When the pendulum is moving from c to a, the
combined angular velocity is faster than that of the disk. At points a and c,
the angular velocity of the pendulum alone is zero and the combined angular
velocity equals that of the disk. If the angular velocity of the disk corresponds to
the synchronous speed of the rotor, and if the motion of the pendulum alone
represents the swinging of the rotor with respect to an infinite bus, the super¬
imposed motion of the pendulum on that of the disk represents the actual
angular motion of the rotor.
From the above discussion, we conclude that the solution to Eq. (14.48)
represents sinusoidal oscillations provided the synchronizing power coefficient
SP is positive. The angular frequency of the undamped oscillations is given by
1 / cosSP
Hz (14.50)
2n\J ~2H~
Example 14.6 The machine of Example 14.3 is operating at <5 = 28.44° when
it is subjected to a slight temporary electrical-system disturbance. Determine
the frequency and period of oscillation of the machine rotor if the distur¬
bance is removed before the prime mover responds. H = 5 MJ/MVA.
Solution The applicable swing equation is Eq. (14.48) and the synchroniz¬
ing power coefficient at the operating point is
1311 x 1,8466
co,
V 2x5
= 8.343 elec rad/s
POWER SYSTEM STABILITY 393
8.343
= 1.33 Hz
271
1
T = 0.753 s
fn
This example is an important one from the practical viewpoint since it indicates
the order of magnitude of the frequencies which can be superimposed upon the
nominal 60-Hz frequency in a large power system having many interconnected
machines. As load on the system changes randomly throughout the day, inter¬
machine oscillations involving frequencies of the order of 1 Hz tend to arise but
these are quickly damped out by the various damping influences caused by the
prime mover, the system loads, and the machine itself. It is worthwhile to note
that even if the transmission system in our example contains resistance, nonethe¬
less, the swinging of the rotor is harmonic and undamped. Problem 14.8
examines the effect of resistance on the synchronizing power coefficient and the
frequency of oscillations. In a later section we again discuss the concept of
synchronizing coefficients. In the next section we examine a method of determin¬
ing stability under transient conditions caused by large disturbances.
—o
cHb — ©
i—i FT-
"LI 1_r
Figure 14.8 One line-diagram of the system -q£
of Fig. 14.4 with the addition of a short A
transmission line. I Open
394 ELEMENTS OF POWER SYSTEM ANALYSIS
unaltered. At point P close to the bus, a three-phase fault Qccurs and is cleared
by circuit breaker A after a short period of time. Therefore, the effective trans¬
mission system is unaltered except while the fault is on. The short circuit caused
by the fault is effectively at the bus and so the electrical power output from the
generator is zero until the fault is cleared. The physical conditions before, during,
and after the fault can be understood by analyzing the power-angle curves in
Fig. 14.9.
Originally the generator is operating at synchronous speed with a rotor
angle of S0 and the input mechanical power Pm equals the output electrical
power Pe as shown at point a in Fig. 14.9a. When the fault occurs at t = 0, the
electrical power output is suddenly zero while the input mechanical power is
unaltered as shown in Fig. 14.9b. The difference in power must be accounted for
by a rate of change of stored kinetic energy in the rotor masses. This can be
accomplished only by an increase in speed which results from the constant
POWER SYSTEM STABILITY 395
accelerating power Pm. If we denote the time to clear the fault by tc, then for
time t less than tc the acceleration is constant and is given by
d2S a)s
(14.51)
~dtI = 2HPm
While the fault is on, the velocity increase above synchronous speed is found by
integrating this equation to obtain
dS CO, „ , co„
—- p dt = —- P t (14.52)
dt 02 H m 2H m
A further integration with respect to time yields
(14.53)
s=-w‘ +s°
dS = cosPm
(14.54)
dt t=tc 2H ‘
and
m MsPn
4H
te + <50 (14.55)
When the fault is cleared at the angle Sc, the electrical power output abruptly
increases to a value corresponding to point d on the power-angle curve. At d the
electrical power output exceeds the mechanical power input and thus the
accelerating power is negative. As a consequence the rotor slows down as Pe
goes from d to e in Fig. 14.9c. At e the rotor speed is again synchronous
although the rotor angle has advanced to 5X. The angle Sx is determined by the
fact that areas Ax and A2 must be equal, as will be explained later. The acceler¬
ating power at e is still negative (retarding), and so the rotor cannot remain at
synchronous speed but must continue to slow down. The relative velocity is
negative and the rotor angle moves back from Sx at e along the power-angle
curve of Fig. 14.9c to point a at which the rotor speed is less than synchronous.
From a to f the mechanical power exceeds the electrical power and rotor in¬
creases speed again until it reaches synchronism at f Point / is located so that
areas A3 and A4 are equal. In the absence of damping the rotor would continue
to oscillate in the sequence f-a-e, e-a-f etc., with synchronous speed occurring at
e and f.
As noted, we shall soon show that the shaded areas Ax and A2 in Fig. 14.9b
must be equal, and similarly, areas A3 and A4 in Fig. 14.9c must be equal. In a
396 ELEMENTS OF POWER SYSTEM ANALYSIS
system where one machine is swinging with respect to an infinite bus we may. use
this principle of equality of areas, called the equal-area criterion, to determine the
stability of the system under transient conditions without solving the swing
equation. Although not applicable to multimachine systems, the method helps in
understanding how certain factors influence the transient stability of any system.
The derivation of the equal-area criterion is made for one machine and an
infinite bus although the considerations in Sec. 14.3 show that the method can
be readily adapted to general two-machine systems. The swing equation for the
machine connected to the bus is
2Md*d
= Pm~ (14.56)
a)s dt2
dd
cor - — = CO ~0)s (14.57)
It is clear that when the rotor speed is synchronous, co equals cos and cor is zero.
Multiplying both sides of Eq. (14.58) by cor = dS/dt, we have
. dco. , „ „ ,dS
2cor^ = (Fm-r,)- (14.59)
cos
~ K22 - O =
Ws
(
JSi
V™ - p.) ds (14.61)
The subscripts for the cor terms correspond to those for the S limits, that is, the
rotor speed corl corresponds to that at the angle ^ and cor2 corresponds to S2.
Since cor represents the departure of the rotor speed from synchronous speed, we
readily see that if the rotor speed is synchronous at (5X and d2, then, corre¬
spondingly, corl = cor2 = 0. Under this condition Eq. (14.61) becomes
*62
j (Pm-Pe)dS = 0 (14.62)
This equation applies to any two points <5j and <5 2 on the power-angle diagram,
provided they are points at which the rotor speed is synchronous. In Fig. 14.96
POWER SYSTEM STABILITY 397
two such points are a and e corresponding to <50 and 5X. If we perform the
integration in two steps, we can write
The left integral applies to the fault period while the right integral corresponds
to the immediate postfault period up to the point of maximum swing Sx. In
Fig. 14.% Pe is zero during the fault. The shaded area At is given by the
left-hand side of Eq. (14.64) and the shaded area ^42 is given by the right-hand
side. So the two areas Ax and A2 are equal.
Since the rotor speed is synchronous at <5^. and also at dy in Fig. 14.9c the
same reasoning as above shows that A3 equals A4. The areas A3 and A4 are
directly proportional to the increase in kinetic energy of the rotor while it is
accelerating, whereas areas A2 and A3 are proportional to the decrease in kinetic
energy of the rotor while it is decelerating. This can be seen by inspection of
both sides of Eq. (14.61). Therefore the equal-area criterion merely states that
whatever kinetic energy is added to the rotor following a fault must be removed
after the fault to restore the rotor to synchronous speed.
The shaded area Ax is dependent upon the time taken to clear the fault. If
there is delay in clearing, the angle Sc is increased; likewise the area Ax increases
and the equal-area criterion requires that area A2 also increase to restore the
rotor to synchronous speed at a larger angle of maximum swing dx. If the delay
in clearing is prolonged so that the rotor angle S swings beyond the angle (5max in
Fig. 14.9 then the rotor speed at that point on the power-angle curve is above
synchronous speed when positive accelerating power is again encountered.
Under the influence of this positive accelerating power the angle <5 will increase
without limit and instability results. Therefore there is a critical angle for clear¬
ing the fault in order to satisfy the requirements of the equal-area criterion for
stability. This angle, called the critical clearing angle dcr, is shown in Fig. 14.10.
The corresponding critical time for removing the fault is called the critical clear¬
ing time tCT.
In the particular case of Fig. 14.10, both the critical clearing angle the
critical clearing time can be calculated as follows. The rectangular area is
,6 c
Al = \ Pmd3 = Pm(Scr-d0) (14.65)
J6o
Equating the expressions for At and A2, and transposing terms, yields
and
Pm = Pmax SHI (14.69)
Substituting for <5max and Pm in Eq. (14.67), simplifying the result and solving for
<5cr, we obtain
for the critical clearing angle. The value for <5cr calculated from this equation,
when substituted for the left-hand side of Eq. (14.55), yields
s _ ^sPm .2 . <;
(14.71)
^cr 4// tcr +
(14.72)
Example 14.7 Calculate the critical clearing angle and the critical clearing
time for the system of Fig. 14.8 when the system is subjected to a three-phase
fault at point P on the short transmission line. The initial conditions are the
same as those in Example 14.3 and H is 5 MJ/MVA.
and mechanical input power Pm is 1.0 per unit. Therefore, from Eq. (14.70)
we obtain
for the critical clearing angle. Inserting this value with the other known
quantities in Eq. (14.72) we obtain
/4 x 5(1.426 - 0.496)
tcr ~ V 377 x 1
= 0.222 s
This example serves to establish the concept of critical clearing time which is
essential to the design of proper relaying schemes for fault clearing. In more
general cases, the critical clearing time cannot be explicitly found without solv¬
ing the swing equations by digital computer simulation.
Although the equal-area criterion can be applied only for the case of two ma¬
chines or one machine and an infinite bus, it is a very useful means for beginning to
see what happens when a fault occurs. The digital computer is the only practical
way to determine the stability of a large system. However, because the equal-
area criterion is so helpful in understanding transient stability, we shall continue
to examine it briefly before discussing the determination of swing curves and the
digital-computer approach.
When a generator is supplying power to an infinite bus over two parallel
transmission lines, opening one of the lines may cause the generator to lose
synchronism even though the load could be supplied over the remaining line
under steady-state conditions. If a three-phase short circuit occurs on the bus to
which two parallel lines are connected, no power can be transmitted over either
line. This is essentially the case in Example 14.7. However, if the fault is at the
end of one of the lines, opening breakers at both ends of the line will isolate the
fault from the system and allow power to flow through the other parallel line.
When a three-phase fault occurs at some point on a double-circuit line other
than on the paralleling buses or at the extreme ends of the line, there is some
impedance between the paralleling buses and the fault. Therefore, some power is
transmitted while the fault is still on the system. The power-angle equation in
Example 14.4 demonstrates this fact.
400 ELEMENTS OF POWER SYSTEM ANALYSIS
" r2 ~ rl
A literal form solution for the critical clearing time tcr is not possible in this case.
For the system and fault location shown in Fig. 14.8, the values are rx = 0,
r2 — 1 and the equation then reduces to Eq. 14.67.
Regardless of their location, short-circuit faults not involving all three
phases allow the transmission of some power, because they are represented by
connecting some impedance rather than a short circuit between the fault point
and the reference bus in the positive-sequence impedance diagram. The larger the
impedance shunted across the positive-sequence network to represent the fault,
the larger the power transmitted during the fault. The amount of power trans¬
mitted during the fault affects the value of A1 for any given clearing angle. Thus,
smaller values of rx result in greater disturbances to the system, as low rt means
low power transmitted during the fault and larger Ax. In order of increasing
severity (decreasing /q Pmax) the various faults are:
The single line-to-ground fault occurs most frequently, and the three-phase fault
is least frequent. For complete reliability a system should be designed for tran¬
sient stability for three-phase faults at the worst locations, and this is virtually
the universal practice.
POWER SYSTEM STABILITY 401
Example 14.8 Determine the critical clearing angle for the three-phase fault
described in Examples 14.4 and 14.5 when the initial system configuration
and prefault operating conditions are as described in Example 14.3.
1 000
<5max = 180° - sin-1 = 138.190° = 2.412 rad
= 0.127
Hence
3cr = 82.726°
To determine the critical clearing time we must obtain the swing curve of 3
versus t for this example. In Sec. 14.9 we shall discuss one method of com¬
puting such swing curves.
The equal area criterion cannot be used directly in systems where three or more
machines are represented. Although the physical phenomena observed in the
two-machine problems basically reflect that of the multimachine case, nonethe¬
less, the complexity of the numerical computations increases with the number of
machines considered in a transient stability study. When a multimachine system
operates under electromechanical transient conditions, intermachine oscillations
occur between the machines through the medium of the transmission system
which connects them. If any one machine could be considered to act alone as the
402 ELEMENTS OF POWER SYSTEM ANALYSIS
(a) The mechanical power input to each machine remains constant during the
entire period of the swing curve computation.
(b) Damping power is negligible.
(c) Each machine may be represented by a constant transient reactance in series
with a constant transient internal voltage.
(d) The mechanical rotor angle of each machine coincides with 3, the electrical
phase angle of the transient internal voltage.
(ie) All loads may be considered as shunt impedances to ground with values
determined by conditions prevailing immediately prior to the transient
conditions.
The system stability model based on these assumptions is called the classical
stability model and studies which use this model are called classical stability
studies. These assumptions, which we shall adopt, are in addition to the fun¬
damental assumptions set forth in Sec. 14.1 for all stability studies. Of course,
detailed computer programs with more sophisticated machine and load models
are available to modify one or more of assumptions (n) to (c). However,
throughout this chapter the classical model is used to study system disturbances
originating from three-phase faults.
As already seen, in any transient stability study, the system conditions before
the fault and the network configuration during and after its occurrence must be
known. Consequently, in the multimachine case, two preliminary steps are
required:
1. The steady-state prefault conditions for the system are calculated using a
production-type load-flow program.
2. The prefault network representation is determined and then modified to
account for the fault and for the postfault conditions.
From the first preliminary step we know the values for power, reactive power,
and voltage at each generator terminal and load bus with all angles measured
with respect to the swing bus. The transient internal voltage of each generator is
then calculated using the equation
E = Vt +jX'dI (14.74)
POWER SYSTEM STABILITY 403
where Vt is the corresponding terminal voltage and /, the output current. Each
load is converted into a constant admittance to ground at its bus using the
equation
(14.75)
where PL + jQL is the load and \ VL \ is the magnitude of the corresponding bus
voltage. The bus-admittance matrix used for the prefault load-flow calculation is
augmented to include the transient reactance of each generator and the shunt load
admittances as suggested in Fig. 14.12. Note that the injected current is zero at
all buses except the three-generator internal buses. The second preliminary step
determines the modified bus-admittance matrices corresponding to the faulted
and postfault conditions. Since only the generator internal buses have injections,
all other buses can be eliminated to reduce the dimensions of the modified
matrices to correspond to the number of generators. During and after the fault,
the power flow into the network from each generator is calculated by the corre¬
sponding power-angle equations. For example, in Fig. 14.12 the power out of
generator 1 is given by
where Sl2 equals <5X — S2. Similar equations are written for Pe2 and Pe3 with the
Yij values chosen from the 3 x 3 bus-admittance matrices appropriate to the
fault or postfault condition. The power-angle equations form part of the swing
equations
(14.77)
to represent the motion of each rotor for the fault and postfault periods. The
solutions depend upon the location and duration of the fault, and the Ybus which
Boundary of
/ augmented network
r n
l!
5
results when the faulted line is removed. The basic procedures used in digital
computer programs for classical stability studies are revealed in the following
examples.
Example 14.9 A 60-Hz, 230-kV transmission line has two generators and an
infinite bus as shown in Fig. 14.13. The transformer and line data are given
in Table 14.2. A three-phase fault occurs on line 4-5 near bus 4. Using the
prefault load-flow solution shown in Table 14.3 determine the swing equa¬
tion for each machine during the fault period. The generators, with reac¬
tances and H values expressed on a 100-MVA base, are described as follows:
Generator 1 400 MVA, 20 kV, X'd = 0.067 per unit, H = 11.2 MJ/MVA
Generator 2 250 MVA, 18 kV, X'd = 0.10 per unit, H = 8.0 MJ/MVA
Bus Series Z
to Shunt T
bus R X B
Generation Load
Bus Voltage P Q P Q
{Pi+jQi)* 3.50—,0.712
h = = 3.468 A2.619c
v* 1.030 A 8.88 ‘
and similarly
1.850-,0.298
/, = 1.020 7-6.38°
= 1.837 /-2.771
f3 = e3 = 1.000/0.0°
and so
0.50-,0.16
= 0.4892 - ,0.1565
"L5_ (1.011)2
These admittances, together with the transient reactances, are used with the
line and transformer parameters to form for the prefault system the aug¬
mented bus admittance matrix which includes the transient reactances of the
406 ELEMENTS OF POWER SYSTEM ANALYSIS
Bus 1 2 3 4 5
1
Yu —7*11.236
y'0.067 + y'0.022
1
^34= - = -4.2450 + 724.2571
0.007 + ;0.040
The sum of the admittances connected to nodes 3, 4, and 5 must include the
shunt capacitances of the transmission lines. So
/0.082 /0.226
Y44 = -711.236 + + 4.2450
= 6.6587 -744.6175
Faulted network
Bus 1 2 3
Postfault network
Pe 1=0
Pel = | E'l |2G22 + | E2 | | £31 | Y23 | cos (<523 - 023)
= (1.065)2(0.1362) + (1.065)(1.0)(5.1665) cos (<52 - 90.755°)
Therefore, while the fault is on the system, the desired swing equations (values
of Pml and Pm2 from Table 14.3) are
180/
[L6955 15023 sin (<52 - 0755°)] elec deg/s2
8.0 Pm ~ P, y
408 ELEMENTS OF POWER SYSTEM ANALYSIS
Solution When the fault is cleared by removing line 4-5, the prefault Ybus
of Table 14.4 must again be modified. This is accomplished by substituting
zero for Y45 and Y54 and subtracting the series admittance of line 4-5 and
the capacitive susceptance of one-half the line from elements Y44 and Y55 of
Table 14.4. The reduced bus-admittance matrix applicable to the postfault
network is shown in the lower half of Table 14.5 and it is noted that a zero
element appears in the first and second rows. This reflects the fact that,
physically, the generators are not interconnected when line 4-5 is removed.
Accordingly, each generator is connected radially to the infinite bus. There¬
fore, the per-unit power-angle equations for postfault conditions are
and
180 f
[2 8944 — 8.3955 sin (<5X — 1.664°)] elec deg/s2
\
and
d2b2 180 f
-gy {1.85 - [0.1804 + 6.4934 sin (S2 - 0.847°)]}
dt2
ISQf
= -j~ [1.6696 - 6.4934 sin (S2 - 0.847°)] elec deg/s2
Each of the power-angle equations obtained in Example 14.9 and in this example
is of the form of Eq. (14.35). The resultant swing equation in each case assumes
the form
d*8 180/
dt2 H
[Pm ~ Pc ~ Pmax ^ (5 ~ y)] (14.78)
POWER SYSTEM STABILITY 409
where the bracketed right-hand term represents the accelerating power on the
rotor. Accordingly, we may write the equation in the form
d1 25 180/ , , , ,
-^2 = Pa elec deg/s2 (14.79)
where
pa = Pm- Pc- pmax sin (d - y) (14.80)
In the next section we shall discuss how to solve equations of the form of Eq. (14.79)
to obtain 3 as a function of time for specified clearing times.
For large systems we depend on the digital computer which determines d versus
t for all the machines in which we are interested; and S may be plotted versus t
for a machine to obtain the swing curve of that machine. The angle <5 is cal¬
culated as a function of time over a period long enough to determine whether <5
will increase without limit or reach a maximum and start to decrease. Although
the latter result usually indicates stability, on an actual system where a number
of variables are taken into account it may be necessary to plot 3 versus t over a
long enough interval to be sure 5 will not increase again without returning to a
low value.
By determining swing curves for various clearing times the length of time
permitted before clearing a fault can be determined. Standard interrupting times
for circuit breakers and their associated relays are commonly 8, 5, 3, or 2 cycles
after a fault occurs, and thus breaker speeds may be specified. Calculations
should be made for a fault in the position which will allow the least transfer of
power from the machine and for the most severe type of fault for which protec¬
tion against loss of stability is justified.
A number of different methods are available for the numerical evaluation of
second-order differential equations in step-by-step computations for small incre¬
ments of the independent variable. The more elaborate methods are practical
only when the computations are performed on a digital computer. The step-by-
step method used for hand calculation is necessarily simpler than some of the
methods recommended for digital computers. In the method for hand calcula¬
tion the change in the angular position of the rotor during a short interval of
time is computed by making the following assumptions:
Figure 14.14 will help in visualizing the assumptions. The accelerating power
is computed for the points enclosed in circles at the ends of the n — 2, n — 1, and
n intervals, which are the beginnings of the n — 1, n, and n + 1 intervals. The step
curve of Pa in Fig. 14.14 results from the assumption that Pa is constant between
midpoints of the intervals. Similarly, a>r, the excess of the angular velocity o>
over the synchronous angular velocity cos, is shown as a step curve that is
constant throughout the interval at the value computed for the midpoint. Be¬
tween the ordinates n — § and n — \ there is a change of speed caused by the
constant accelerating power. The change in speed is the product of the accelera¬
tion and the time interval, and so
d28 180/
1/2 - n-3/2= ~^2 At = ~~ Pa,n^ At (14.81)
POWER SYSTEM STABILITY 411
The change in 3 over any interval is the product of a>r for the interval and the
time of the interval. Thus, the change in 3 during the n — 1 interval is
(14.85)
Equation (14.84) is the important one for the step-by-step solution of the
swing equation with the necessary assumptions enumerated, for it shows how to
calculate the change in 3 during an interval if the change in 3 for the previous
interval and the accelerating power for the interval in question are known.
Equation (14.84) shows that, subject to the stated assumptions, the change in
torque angle during a given interval is equal to the change in torque angle
during the preceding interval plus the accelerating power at the beginning of the
interval times k. The accelerating power is calculated at the beginning of each
new interval. The solution progresses through enough intervals to obtain points
for plotting the swing curve. Greater accuracy is obtained when the duration of
the intervals is small. An interval of 0.05 s is usually satisfactory.
The occurrence of a fault causes a discontinuity in the accelerating power Pa
which is zero before the fault and a definite amount immediately following the
fault. The discontinuity occurs at the beginning of the interval, when t = 0.
Reference to Fig. 14.14 shows that our method of calculation assumes that the
accelerating power computed at the beginning of an interval is constant from
the middle of the preceding interval to the middle of the interval considered.
When the fault occurs, we have two values cr Pa at the beginning of an interval,
and we must take the average of these two values as our constant accelerating
power. The procedure is illustrated in the following example.
Example 14.11 Prepare a table showing the steps taken to plot the swing
curve for machine 2 for the fault on the 60-Hz system of Examples 14.9 and
14.10. The fault is cleared by simultaneous opening of the circuit breakers at
the ends of the faulted line at 0.225 s.
are made in per unit on 100 MVA base. For the time interval At = 0.05 s the
parameter k applicable to machine 2 is
180/ 180 x 60
k = (At)2 = x 25 x 10 4 = 3.375 elec deg
H 8.0
When the fault occurs at t = 0 the rotor angle of machine 2 cannot change
instantly. Hence, from Example 14.9,
<50 = 16.19°
and, during the fault,
A S1 = 0 + 0.3898 = 0.3898°
is the change in rotor angle of machine 2 as time advances over the first
interval from 0 to At. Therefore at the end of the first time interval
and it follows that the increase in rotor angle over the second time interval is
The subsequent steps in the computations are shown in Table 14.6. Note
that the postfault equation found in Example 14.10 is needed.
POWER SYSTEM STABILITY 413
In Table 14.6 the terms Pmax sin (<5 — y), Pa, and bn are values computed
at the time t shown in the first column but A<5„ is the change in rotor angle
during the interval that begins at the time indicated. For example, in the row
for t = 0.10 s the angle 17.6279° is the first value calculated and is found
by adding the change in angle during the preceding time-interval
Table 14.6 Computation of swing curve for machine 2 of Example 14.11 for
clearing at 0.225 s.
k= (180//H)(Ar)2 = 3.375 elec deg. Before clearing Pm — Pc = 1.6955p.u., Pmax = 5.5023p.u., and
y = 0.755°. After clearing these values become 1.6696, 6.4934, and 0.847, respectively.
0- 0.00 16.19
0+ 15.435 1.4644 0.2310 16.19
0 av 0.1155 0.3898 16.19
0.3898
0.05 15.8248 1.5005 0.1950 0.6583 16.5798
1.0481
0.10 16.8729 1.5970 0.0985 0.3323 17.6279
1.3804
0.15 18.2533 1.7234 -0.0279 -0.0942 19.0083
1.2862
0.20 19.5395 1.8403 -0.1448 -0.4886 20.2945
0.7976
0.25 20.2451 2.2470 -0.5774 -1.9487 21.0921
-1.1511
0.30 19.0940 2.1241 -0.4545 -1.534 19.9410
-2.6852
0.35 16.4088 1.8343 -0.1647 -0.5559 17.2558
-3.2410
0.40 13.1678 1.4792 0.1904 0.6425 14.0148
-2.5985
0.45 10.5693 1.1911 0.4785 1.6151 11.4163
-0.9833
0.50 9.5860 1.0813 0.5883 1.9854 10.4330
1.0020
0.55 10.5880 1.1931 0.4765 1.6081 11.4350
2.6101
0.60 13.1981 1.4826 0.1870 0.6312 14.0451
3.2414
0.65 16.4395 1.8376 -0.1680 -0.5672 17.2865
2.6742
0.70 19.1137 2.1262 -0.4566 -1.5411 19.9607
1.1331
0.75 20.2468 2.2471 -0.5775 -1.9492 21.0938
-0.8161
0.80 19.4307 2.1601 -0.4905 —1.6556 20.2777
-2.4716
0.85 17.8061
414 ELEMENTS OF POWER SYSTEM ANALYSIS
We note that for the points calculated for Table 14.6, the angle of S for machine 2
varies between 10.43 and 21.09°. Using either angle makes little difference in the
POWER SYSTEM STABILITY 415
Figure 14.15 Swing curves for machines 1 and 2 of Examples 14.9 to 14.11 for clearing at 0.225 s.
value found for SP. If we used the average value of 15.76°, we find
1 / 377 x 6.274
/„ = 2w 2x8
= 1.935 Hz
T= = 0.517 s
1.935
are chosen, the intermachine oscillations between the two generators occur because
there is no decoupling of the machines. The swing-curve computations are more
unwieldy. For such cases, manual calculations are time consuming and should be
avoided. Digital computer programs of great versatility are generally available and
should be used.
t For further information, see G. W. Stagg and A. H. El-Abiad, Computer Methods in Power
System Analysis, chaps. 9 and 10, McGraw-Hill Book Company, New York, 1968.
418 ELEMENTS OF POWER SYSTEM ANALYSIS
There are two factors which can act as guideline criteria for the relative stability
of a generating unit within a power system. These are the angular swing of the
machine during and following fault conditions and the critical clearing time. It is
apparent from the equations which we have developed in this chapter that the H
constant and the transient reactance X'd of the generating unit have a direct effect
on both of these criteria.
Inspection of Eqs. (14.84) and (14.85) indicates that the smaller the H
constant, the larger the angular swing during any time interval. On the other
hand, Eq. (14.36) shows that Pmax decreases as the transient reactance of the
machine increases. This is so because the transient reactance forms part of the
overall series reactance of the system which is the reciprocal of the transfer
admittance. Examination of Fig. 14.11 shows that all three power curves are
lowered when Pmax is decreased. Accordingly, for a given shaft power Pm, the
initial rotor angle 50 is increased, <5max is decreased, and a smaller difference
between <50 and <5cr exists for a smaller Pmax. The net result is that a decreased
Pmax constrains a machine to swing through a smaller angle from its original
position before it reaches the critical clearing angle. Thus, any developments
which lower the H constant and increase the transient reactance of a machine
cause the critical clearing time to decrease and lessens the probability of main¬
taining stability under transient conditions. As power systems continually in¬
crease in size, there is a corresponding need for higher-rated generating units.
These larger units have advanced cooling systems which allow higher-rated
capacities without comparable increase in rotor size. As a result, H constants
continue to decrease with potential adverse impact on generating unit stability.
At the same time, this uprating process tends to result in higher transient and
synchronous reactances which makes the job of designing a reliable and stable
system even more challenging.
Fortunately, stability control techniques and transmission system designs
have also been evolving to increase overall system stability. The control schemes
include
Excitation systems
Turbine valve control
Single-pole operation of circuit breakers
Faster fault clearing times
POWER SYSTEM STABILITY 419
When a fault occurs on a system the voltages at all buses are reduced. At
generator terminals the reduced voltages are sensed by the automatic voltage
regulators which act within the excitation system to restore generator terminal
voltages. The general effect of the excitation system is to reduce the initial rotor
angle swing following the fault. This is accomplished by boosting the voltage
applied to the field winding of the generator through action of the amplifiers in
the forward path of the voltage regulators. The increased air-gap flux exerts a
restraining torque on the rotor which tends to slow down its motion. Modern
excitation systems employing thyristor controls rapidly respond to bus voltage
reduction and can effect from one-half to one-and-one-half cycles gain in critical
clearing times for three-phase faults on the high-side bus of the generator step-up
transformer.
Modern electrohydraulic turbine governing systems have the ability to close
turbine valves to reduce unit acceleration during severe system faults near the
unit. Immediately upon detecting differences between mechanical input and elec¬
trical output, control action initiates the valve closing which reduces the power
input. A gain of one to two cycles in critical clearing time can be achieved.
Reducing the reactance of the system during fault conditions increases
vi Pmax decreasing the acceleration area of Fig. 14.11, and thereby enhances the
possibility of maintaining stability. Since single-phase faults occur more often
than three-phase faults, relaying schemes, allowing independent or selective
circuit-breaker pole operation, can be used to clear the faulted phase while
keeping the unfaulted phases intact. Separate relay systems, trip coils, and oper¬
ating mechanisms can be provided for each pole so that stuck breaker contin¬
gencies following three-phase faults can be mitigated in effect. Independent-pole
operation of critical circuit breakers can extend the critical clearing time by 2 to
5 cycles depending upon whether 1 or 2 poles fail to open under fault conditions.
Such gain in critical clearing time can be important especially if backup clearing
times are a problem for system stability.
Reducing the reactance of a transmission line is another way of raising Pmax.
Compensation for line reactance by series capacitors is often economical for
increasing stability. Increasing the number of parallel lines between two points is
a common means of reducing reactance. When parallel transmission lines are
used instead of a single line, some power is transferred over the remaining line
even during a three-phase fault on one of the lines unless the fault occurs at a
paralleling bus. For other types of faults on one line, more power is transferred
during the fault if there are two lines in parallel than is transferred over a single
faulted line. For more than two lines in parallel the power transferred during the
420 ELEMENTS OF POWER SYSTEM ANALYSIS
fault is even greater. Power transferred is subtracted from power input to obtain
accelerating power. Thus increased power transferred during a fault means'lower
accelerating power for the machine and increased chance of stability.
PROBLEMS
14.1 A 60-Hz four-pole turbogenerator rated 500 MVA, 22 kV has an inertia constant of
H = 7.5 MJ/MVA. Find (a) the kinetic energy stored in the rotor at synchronous speed and (b) the
angular acceleration if the electrical power developed is 400 MW when the input less the rotational
losses is 740,000 hp.
14.2 If the acceleration computed for the generator described in Prob. 14.1 is constant for a period of
15 cycles, find the change in S in electrical degrees in that period and the speed in revolutions per
minute at the end of 15 cycles. Assume that the generator is synchronized with a large system and has
no accelerating torque before the 15-cycle period begins.
14.3 The generator of Prob. 14.1 is delivering rated megavolt-amperes at 0.8 power factor lag when a
fault reduces the electric power output by 40%. Determine the accelerating torque in newton-meters at
the time the fault occurs. Neglect losses and assume constant power input to the shaft.
14.4 Determine the WR2 of the generator of Prob. 14.1.
14.5 A generator having H = 6 MJ/MVA is connected to a synchronous motor having// = 4 MJ/MVA
through a network of reactances. The generator is delivering power of 1.0 per unit to the motor when a
fault occurs which reduces the delivered power. At the time when the reduced power delivered is 0.6 per
unit determine the angular acceleration of the generator with respect to the motor.
14.6 A power system is identical to that of Example 14.3 except that the impedance of each of the
parallel transmission lines is j0.5 and the delivered power is 0.8 per unit when both the terminal voltage
of the machine and the voltage of the infinite bus are 1.0 per unit. Determine the power-angle equation
for the system during the specified operating conditions.
14.7 If a three-phase fault occurs on the power system of Prob. 14.6 at a point on one of the transmission
lines at a distance of 30% of the line length away from the sending-end terminal of the line, determine
(a) the power-angle equation during the fault and (b) the swing equation. Assume the system is operating
under the conditions specified in Prob. 14.6 when the fault occurs. Let H = 5.0 MJ/MVA as in
Example 14.4.
14.8 Series resistance in the transmission network results in positive values for Pc and y in Eq. (14.80).
For a given electrical power output, show the effects of resistance on the synchronizing coefficient SP,
the frequency of rotor oscillations, and the damping of these oscillations.
14.9 A generator having H = 6.0 MJ/MVA is delivering power of 1.0 per unit to an infinite bus through
a purely reactive network when the occurrence of a fault reduces the generator output power to zero.
The maximum power that could be delivered is 2.5 per unit. When the fault is cleared the original
network conditions again exist. Determine the critical clearing angle and critical clearing time.
14.10 A 60-Hz generator is supplying 60% of Pmax to an infinite bus through a reactive network. A fault
occurs which increases the reactance of the network between the generator internal voltage and the
infinite bus by 400%. When the fault is cleared the maximum power that can be delivered is 80% of the
original maximum value. Determine the critical clearing angle for the condition described.
14.11 If the generator of Prob. 14.10 has an inertia constant of H = 6 MJ/MVA and Pm (equal to
0.6 Pmax) is 1.0 per-unit power, find the critical clearing time for the condition of Prob. 14.10. Use
At = 0.05 s to plot the necessary swing curve.
14.12 For the system and fault conditions described in Probs. 14.6 and 14.7 determine the power-angle
equation if the fault is cleared by the simultaneous opening of breakers at both ends of the faulted line
at 4.5 cycles after the fault occurs. Then plot the swing curve of the generator through r = 0.25 s.
14.13 Extend Table 14.6 to find <5 at t = 1.00 s.
POWER SYSTEM STABILITY 421
14.14 Calculate the swing curve for machine 2 of Examples 14.9 to 14.11 for fault clearing at 0.05 s by
the method described in Sec. 14.9. Compare the results with the values obtained by the production-type
program and listed in Table 14.7.
14.15 If the three-phase fault on the system of Example 14.9 occurs on line 4-5 at bus 5 and is cleared by
simultaneous opening of breakers a*, both ends of the line at 4.5 cycles after the fault occurs prepare a
table like that of Table 14.6 to plot the swing curve of machine 2 through t = 0.30 s.
14.16 By applying the equal-area criterion to the swing curves obtained in Examples 14.9 and 14.10 for
machine 1, (a) derive an equation for the critical clearing angle, (b) solve the equation by trial and error
to evaluate <5cr, and (c) use Eq. (14.72) to find the critical clearing time.
V*
'
.
APPENDIX
423
APPENDIX 425
G
C3
1 O^NWJONHio^NoOOHftiO
ON^iOTjiCOMHOOJOOOOOOtOtO © ©
© Tf<
<N ©
r-t <N
© ©
© © 00
© ©
©
© <N
CO oj OJ
©
©©©©©©©©©©©©©0505
G M
O in ft - © ©
© ©
© ©
© ©
00 00 00 Of) 00 00 Of) Of) Of) Of) Of) t^
© © © © © © © © © © © ©
o * S ooooooooooooooo © © © © © © © © © © © © © © © ©
a>
£ S
(OiOCONHiCNHHNOTt*NMOiONO)tOiOOO(OOOONHiOT)iC(lT)(
N50i0C0i0^i0^^C*5M(Nf0NNHH05O0)0505C000NNNC0t0‘0'}i
^.^l^.^^'^^^'^'^^^^^^^co^wcocccoeocowrtcocoroco
Pi P
“* ooooooooooooooooooooooooooooooo
OON05(NCOiC^rf^^a5^^CO^NiOM(NCO(N(NiCcO^{OO^OOMCO
03H(NN^iOTf®(DCOOOOOOOH(N«NiOOOOOHCO^tON050)NlXl
oi a
S s ooooooooooooooooooooooooooooooo
O Q oooooooooo ooooooooooooooooooooo
Table A.l Electrical characteristics of bare aluminum conductors steel-reinforced (ACSR)t
t Data, by permission, from Aluminum Association, "Aluminum Electrical Conductor Handbook,” New York, September 1971.
HINNNCONINHOO^ONWNOMCOTJ'INININ
MONMOOONW^MNO^nNOOiOOOOOO
HNINHCOIOCONIO
TfCCMW^CONCO-H
OOt^CO©©©iO©f-<.-i,-<rHOOOOOO©iO<NCO©© CDOICOOONNPPIC
cowwmmnnnnninnhhhhhhhhh ooooooooo
w ooooooooooooooooooooooooooooooo
OONONNO)NMNMH®0)05COHTf(NOONOOTfH(ONHTt<COMNtO
OOiONOWH^NiOi'MHNtOtOtOiONOOOJOOWtOiOfOiOCONNHN
p p
^^ONNN«W050:OJ05t0®©Tf^HH0)050500C0NNCOC0©CDTf(
COCOCO<N<NC4C4C4»—<rH»—ii—<*—it—<»—if—(»—1©©0©©0©©©©©©
©©©©’©©©©©*©*©*©©©©©©©©©©©©©©©©©©©©
PS
© © 0©OJNNT}'CCOHaiNiC0300N«OOOiCt*HONiCiCtO»OHOaiCOO
TfTjicO^OOCOrtCOiOifliOOOO'OC'HHCiOOOCOiCiCCOeOlNCtOOOO
(N © ©©lOl^lOlCTfrf-MMMMWMMNNNlNHHHHHHHHHHHO
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
Q G ©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
$> a)
If ONO^FHHfOM^tOOOCOOJ^NNOOOMiOOfOOMUliNNiONiOlN
CT)iCOCOlNT}'T)'OOHf)iiOOONHNN050tOCO®HiOO)^OON©OTC®
” §o3
3 OOOCDNNNNOOCOXOOIXIOJCIOOhOhhNININCOCO^^iO'CN
o 3 ©'©'© ©©'©©©©©© ©©©©©©f-tf-li-t»-<»-'--H^-l^-.f-Hf-.f-H^-lTHf-H
o 3
CQ G
C *3
& £
£ *
hP aS NNiNiNN(N(N(NN(NN(NN(N(N(NNNM«««MCO«eOW««CO^
12 -
3 $o t^ t^-
g \
00©©CO©©CO©OOTt<cO©COrt<©T^©©»0‘0'^iOiO'^
&<
©©©©©©©©©©©©©©©©©©©©©©©©©©O©©©©
S - OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
CCCOO^r)<T}<iOiOOOOOiCiOiOOOO©©0,00©OOCOOOO
I i ©©©©©©r^-t''- NNNN©©©©©W5‘C^^WCOCO(NNhhOOO
r^r^t^r^ioio©coco©©‘0‘Oco.-<»-'£-£-coco©©io
©©©COCO CO©© T}i'T}<>ti,‘ClC>0©©t'N0505OHHiN(N^,fl0»0H
I 8 NCtCOCOCOCOCOCO
*< a3
t Most used multilayer sizes.
Ml © M
G M G
t3 ja a 1 S & 0^
V
nd
o
IM
aS
•c
Oj
i a ® 5 M
C -2 a o .2 00
" .5 -c
CD
!ia|!^!isJ!!i!Iil!i!
•3 aS a> ® oj O O
gWWO^QpHOQHtfUOWPNfflpHWPHHlfeW
u »h a> aS
f o JJ f j§ § i
aS m f2 B •- G O ^
©
^ oS-h
o i* Ph o S ij o n
U t-H Ph
Separation
426
ELEMENTS OF POWER SYSTEM ANALYSIS
“Electrical Transmission and Distribution Reference Book,” by permission of the Westinghouse Electric Corporation.
Table A.3 Shunt capacitive-reactance spacing factor Xd at 10 Hzt (megohm-miles per conductor) APPENDIX
427
428 ELEMENTS OF POWER SYSTEM ANALYSIS
Values are per unit. For each reactance a range of values is listed below the typical value.J
Turbine-generators
*0§
t Percent on rated kilovoltampere base. Typical transformers are now designed for the minimum
reactance value shown. Distribution transformers have considerably lower reactance. Resistances of
transformers are usually lower than 1%.
APPENDIX 429
z
A
A/W
A = 1
B = Z
C = 0
D = 1
Series impedance
Is Ir
A = 1
B = 0
C = Y
D = 1
Shunt admittance
A = 1 + YZi
B = Z\ A Zi A YZ\Zi
C - Y
D = 1 + YZi
Unsymmetrical T
Is Z IR
A = 1 + YYZ
B = Z
C = Y\ -(- Yi A ZY1Y2
D = 1 A FiZ
Unsymmetrical 7r
/s _ _
-► A = A1A2 A B\Ci
n-
A
B = A1B2 A B1D2
vs A\BxClDl A2 ^2 C2&2
C — A2C1 A C2D1
1
- ♦
D = BiCi + DiDi
Networks in series
Networks in parallel
INDEX
431
432 INDEX
Skin effect, 42
Sources: Thevenin’s theorem:
in calculation of three-phase fault currents,
of electric power, 3-4
equivalence of, 166-168 256, 258-260, 263
in representing power systems, 181, 209-211
Stability:
definition of, 373 Three-phase circuits:
factors affecting, 418-420 power in, 28, 29
rotor dynamics for, 375-379 voltage and current in, 22-28
436 INDEX