ATT.2 - Standby Generator Requirement As Per Shell DEP

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Comments on transmitted documents

Qatar Petroleum

Project: 4154 ECS FOR NEW LABORATORY BLDG AT QPR MESID


Transmittal : PID/LC19103100/EXT/TN/0188
Issue date: 25-08-2020

Document Rev.

4154-0-TQ-0005 2 TECHNICAL QUERY #5 - UPS LOADS


Seq. Section Comment

1 0 -EGEC will provide the initial equipment list to be connected to the UPS which was prepared by laboratory
specialist to PTE Team.
-As per our meeting held on 24/8/2020, QP internal meeting with all concerned parties will be held to assess the
Lab equipment loads on UPS.
-The comments on UPS load will be provided based on the meeting outcomes.
2 OAE/31R •UPS configuration shall be 4 feeder configuration ( double static UPS) as in DBM. Please modify.
•Nominal output voltage must be 415V
•Please confirm batteries shall be 2 X 100% as per QP requirement.
3 OBL/1R We confirm that All GCs Equipment are connected to Electricity 24 Hr .

1-EQ 240 Now working


2-342 Now working but we keep it as backup

Page 1 of 1
All electrical works shall be carried out in accordance with the latest version of
SHELL DEPs and SHELL standard drawings. Project specific requirements
over and above SHELL DEPs and SHELL Standard drawings are furnished in
the following section.
17.1 Project Specific Requirements For Electrical Design over SHELL DEPs
General

1. Additional/ specific requirements over the SHELL DEP's meant for


electrical discipline are furnished in this section. Applicable DEP clause
is indicated for quick reference.

2. All electrical equipment installed in airconditioned indoor environment


shall be designed for an ambient temperature of 45 deg.C. All equipment
located outdoor under shade shall be designed for an ambient
temperature of 52 deg.C. For other environmental conditions, reference
shall be made to the project specifications and Environmental Data in
the Contract.

3. All electrical equipment shall be designed for 30 years of life as


stipulated in project specifications/Appendix A.

4. All indoor equipment shall be suitable for IP41 (minimum) degree of


protection unless otherwise stated. All outdoor equipment shall be
suitable for IP55 unless otherwise higher degree of protection
specified/required.

5. All electrical equipment shall bear the colour finished to RAL7032


(Classic RAL System).

6. LV systems shall be suitable for 415V/240V, 50Hz, three phase with


neutral, unless otherwise specified.

7. LV switchboard (415 V) shall be secondary selective type.

8. Where electrical power is received from Kahramaa, all tie-ins shall

comply with Kahramaa specification requirements.

9. al requirement that the


manufacturer offers only equipment that is within his standard range of
equipment, and that such equipment is not scheduled to be withdrawn
from production within 5 years of it being installed at the QP site. Any
bought-
standard range of products from the third party, but subject to the
approval of QP. The equipment shall not be a proto-type or a new
product-line that has not been sold in reasonable numbers to similar
users as QP. The manufacturer shall include in his tender
Page 7 of 16
DEP 33.64.10.10-Gen.
February 2018
Page 13

2.4 STANDARDISATION OF EQUIPMENT AND MATERIALS


1. Equipment of similar nature and incorporating similar or identical components and of
similar or identical construction should be from the same Manufacturer (e.g., power
and convenience outlets, luminaries, junction boxes, RCUs, switches.).

2.5 CERTIFICATES, DECLARATIONS AND TEST REPORTS


1. The Contractor shall obtain the Manufacturer's test reports in accordance with the
equipment DEP specifications, e.g., for generators, HV motors, VSDS, HV and LV
switchgear, UPS equipment, and transformers.
2. Further certificates or declarations relating to the application of equipment for use in
hazardous areas may be required by local authorities:
a. for electrical apparatus in Zone 0, Zone 1 and Zone 2 areas, a certificate of
conformity shall be obtained from the Manufacturer:
i. in addition for EU regions, electrical apparatus with a category indication 1
or 2, a certificate of a Notified Body and a CE Declaration of conformity shall
be obtained from the Manufacturer.
b. for electrical apparatus in Zone 2 areas, which has type of protection 'n', a
declaration of compliance is acceptable instead of a certificate of conformity:
i. in addition for EU regions, electrical apparatus with a category indication 3, a
certificate of an independent authorisation authority and a CE Declaration of
conformity shall be obtained from the Manufacturer.
3. The Contractor shall obtain the Manufacturer's requirements for installation from the
certificate or declaration of conformity and incorporate these in the design and
engineering for installation.

3. ELECTRICAL SYSTEM DESIGN

3.1 GENERAL
3.1.1 Design philosophy
1. The design of the electrical facilities shall meet the specific design criteria, philosophy
and/or objective stated in the project definition phase, e.g., in the basis of design
document or project specification, relating to a particular plant or facility.
For instance, it may be defined by plant lifetime, skill of operating and maintenance
personnel, operational flexibility, extension possibilities or noise limitations, etc.
The philosophies to be employed will depend on the size and complexity of the
installation.
2. Refer to Standard Forms DEP 00.00.07.75-Gen and DEP 00.00.07.96-Gen for
guidance on application of Design Class to electrical installations.Electrical installation
design per this DEP meets the requirements of Design Class 3 as specified in DEP
00.00.07.75-Gen. and DEP 00.00.07.96-Gen. (standard form).
If specified by the Principal, a (different) Design Class may be given for the design
of the electrical installation.
3. The conceptual designs and philosophies relating to the electrical system shall be
documented by a system design description, a key line diagram, basic layout drawings
and functional/outline specifications. Refer to Appendix G.
The overall design intent is a suitably robust system, with reduced energy
consumption through the selection and utilisation of efficient electrical equipment.

This document has been supplied under license by Shell to:


praveen.mohan@albalagh.com 15/05/2019 10:35:30
ECCN EAR 99
Design Class Detail Table
ELECTRICAL PROJECT Date

Capacity Utilization

Design Class
Design Item
Class 1 Class 2 Class 3

Backup Power Backup power shall be Backup power shall be Backup power shall be
provided as required for provided as required for a provided as required for a
a safe, orderly shutdown safe, orderly shutdown in safe, orderly shutdown in
in accordance with vital accordance with vital load accordance with vital load
load specifications. To specifications. Standby specifications. Standby
comply with safety generator(s) may be used generator(s) shall be used
requirements, this may for back up of UPS for back up of UPS
include standby systems if power is systems if power is
generators. (N+0) required for extended time required for extended time
periods to support critical periods to support critical
safety-operability loads. safety-operability loads.
(N+1) Provisions may be
provided for black-start
capability. (N+1)
Substation Substation Substation configuration Substation configuration
Configurations configurations shall be shall be consistent with shall be consistent with the
single ended, radial fed if the reliability and reliability and maintenance
the risk (likelihood and maintenance strategy, strategy, and shall include
consequences) of and may include redundant configurations
expected outages is redundant configurations such as ring buses, double
acceptable and if circuits such as double ended ended buses or
and equipment can be buses or maintenance maintenance buses
released for buses (double buses). (double buses).
maintenance in
accordance with Shell
and industry practices.
Transformers, Transformers shall be Transformers shall be Transformers shall be
Power sized based upon sized based upon sized based upon
(Radial System) designed load. No future designed and approved designed and future loads
loads shall be future loads using ONAN using ONAN rating. They
considered. There is no rating. They may be shall be suitable for
requirement for addition suitable for addition of addition of forced cooling
of forced cooling. forced cooling to allow for to allow for further load
further load growth. growth.
Transformers, Transformers shall be Transformers shall be Transformers shall be
Power sized based upon sized based on designed sized based on designed
(Double Ended designed load. No future load and may include and future loads using
System) loads shall be approved future loads ONAN rating. When a
considered. There is no using ONAN rating. single transformer is
requirement for addition When a single required to supply entire
of forced cooling. transformer is required to load of two or more
supply entire load of two systems, ONAF rating shall
or more systems, ONAF be used. (N+1)
rating shall be used.
(N+1)

DEP 00.00.07.75-Gen. February 2015 Page 5 of 7


All rights reserved. No part of this document may be reproduced, stored in a retrieval system, published or transmitted, in any form or by any means, without the prior
written permission of the copyright owner or Shell Global Solutions International BV. © 2015 Shell Group of companies