Nothing Special   »   [go: up one dir, main page]

Specs-Div 07

Download as pdf or txt
Download as pdf or txt
You are on page 1of 33

LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS

KINGDOM OF SAUDI ARABIA

DIVISION 07

THERMAL AND MOISTURE PROTECTION

INDEX

1. Section 07 16 00 Cementitious Waterproofing


2. Section 07 21 00 Thermal Insulation
3. Section 07 84 00 Firestopping
4. Section 07 92 00 Joint Sealants
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

SECTION 07 16 00

CEMENTITIOUS WATERPROOFING

Revision History

03 Dec. 2023 100% Design Development - Revised CC MS ST


02 Jun. 2023 100% Design Development - Revised CC MS ST
01 Apr. 2023 100% Design Development Submission CC MS ST
00 Jan. 2023 50% Design Development Submission CC MS ST
Prepared Checked Approved
Rev. Date Description of Revision
By By By
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

SECTION 07 16 00

CEMENTITIOUS WATERPROOFING

INDEX

PAGE

PART 1 - GENERAL 2
1.1 RELATED DOCUMENTS 2
1.2 SECTION INCLUDES 2
1.3 RELATED SECTIONS 2
1.4 REFERENCES 2
1.5 SUBMITTALS 3
1.6 QUALITY ASSURANCE 3
1.7 WARRANTY 4
1.8 DELIVERY, STORAGE AND HANDLING 4
1.9 JOB CONDITIONS 4

PART 2 - PRODUCTS 4
2.1 ACCEPTABLE MANUFACTURERS 4
2.2 WATERPROOFING MATERIALS 4
2.3 CONCRETE MIX 5
2.4 SCREED AND PLASTER 5
2.5 WATERSTOPS AND MASTIC 5
2.6 GUNITING 5

PART 3 - EXECUTION 5
3.1 EXAMINATION 5
3.2 PREPARATION 5
3.3 INSTALLATION/ APPLICATION 5
3.4 CLEANING AND PROTECTION 6

Section 07 16 00 Cementitious Waterproofing Page 1 of 6 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

PART 1 - GENERAL

1.1 RELATED DOCUMENTS


A. The Drawings and general provisions of the Contract, including General and Particular Conditions and
Division 01 Specification Sections, apply to this Section.

1.2 SECTION INCLUDES


A. The Section includes flexible acrylic, two component cementitious waterproofing for positive side
application to concrete. The system shall provide waterproof concrete, in the following:
1. MEP/ Elevator shafts, OTS, Wet areas, Kitchen

1.3 RELATED SECTIONS


A. Section 03 30 00 - Cast-In-Place Concrete
B. Section 04 22 00 - Concrete Unit Masonry.
C. Section 07 92 00 - Joint Sealants
D. Section 09 24 00 - Portland cement plastering.

1.4 REFERENCES
A. American Society for Testing and Materials (ASTM)
1. ASTM B117-16 Standard Practice for Operating Salt Spray (Fog) Apparatus.
2. ASTM C109-16a Standard Test Method for Compressive Strength of Hydraulic
Cement Mortars (Using 2-in. or [50-mm] Cube Specimens).
3. ASTM C348 Standard Test Method for Flexural Strength of Hydraulic-Cement
Mortars.
4. ASTM C469-14 Standard Test Method for Static Modulus of Elasticity and Poisson’s
Ratio of Concrete in Compression.
5. ASTM C531 Coefficient of Thermal Expansion.
6. ASTM E84 Test Method for Surface Burning Characteristics of Building
Materials.
7. ASTM E96 Water Vapor Transmission of Materials.
8. ASTM G26 Accelerated Weathering.
B. British Standards Institution (BSI)
1. BS1881: Part 122 Testing concrete. Method for determination of water absorption.
2. BS 8102 Code of practice for protection of structures against water from the
ground.
3. BS 8500-2 Concrete. Complementary British Standards to BS EN 206-1.
Specification for constituent materials and concrete.
4. CP 144 Roofing Works
C. German Institute for Standardization (DIN)
1. DIN 1048: Part 5 Testing concrete. Testing hardened concrete (specimens in mould)
(Water penetration).
D. Federal Standard (FS)
1. FS TT-P-29B Fungus Growth Resistance.
2. FS TT-P-141b Abrasion Strength.

Section 07 16 00 Cementitious Waterproofing Page 2 of 6 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

E. Scientific and Technical Centre for Construction (CSTB)


1. DTU 20-12 Code of Practice - Concrete roofs to receive waterproofing
2. DTU 43-1 Code of Practice - Roofing over concrete deck
3. DTU 14.1 Code of Practice - Below grade Tanking works
F. Ministry of Interior (MOI)
G. Saudi Electric Company (SEC)
H. Saudi Building Codes (SBC)

1.5 SUBMITTALS
A. Product Data: For each type of product indicated. Include recommendations for the method of
application, primer, number of coats, coverage or thickness, and protection course. For coatings,
indicating VOC content.
B. Material Certificates: For each product, signed by manufacturers.
C. Manufacturer's printed specification on the product with installation instructions, including procedures
and materials for termination, penetrations, flashing, compatibility and bonding.
D. The Contractor shall provide with his submittals all the relevant documentation.
E. The Shop Drawings indicating the layout of sheets including side and end laps, mechanical equipment
flashing, parapet flashing and drain details. All details shall be with suitable drawing scale.
F. Samples of all components required to complete the works.
G. Accepted samples will be retained to serve as a basis for checking at the time of delivery of materials to
Site. The manufacturer shall furnish when requested, proof of origin and quality of the materials that
will be used or details of where it has previously been applied. Only materials specified by the Engineer
will be permitted to be used. The Engineer will stipulate acceptance tests and their mode of operation to
be carried out on materials supplied by the Contractor.
H. Laboratory Test Reports: For coatings, indicating compliance with requirements for low-emitting
materials.

1.6 QUALITY ASSURANCE


A. Manufacturer: Obtain primary waterproofing materials of each type required from a single
manufacturer to the greatest extent possible. Provide secondary materials only as recommended by the
manufacturer of primary materials.
B. Applicator Qualifications: A firm experienced in applying polymer-modified cement waterproofing
similar in material, design, and extent to that indicated for this Project, whose work has resulted in
applications with a record of successful in-service performance, and that employs workers trained and
approved by the manufacturer.
C. Mockups: Build mockups to verify selections made under Sample submittals and to set quality
standards for installation.
1. Retain option in first subparagraph below if using pavers.
2. Build mockup for each typical waterproofing installation including accessories to demonstrate
surface preparation, crack and joint treatments, inside and outside corner treatments, and
protection.
a. Size: as directed by Engineer.
3. Approval of mockups does not constitute approval of deviations from the Contract Documents
contained in mockups unless Engineer specifically approves such deviations in writing.
4. Subject to compliance with requirements, approved mockups may become part of the completed
Work if undisturbed at time of Taking over Certificate.

Section 07 16 00 Cementitious Waterproofing Page 3 of 6 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

1.7 WARRANTY
A. Provide written warranty, agreeing to replace and repair defective materials and workmanship.
Warranty includes responsibility for removal and replacement of other work which conceals sheet
waterproofing. Ten (10) year warranty (covering products and installation) from the date of Taking
Over Certificate shall be provided by the Contractor, manufacturer and installer. Warranty shall include:
1. Defective materials and installation.
2. Failure to comply with requirements stated in technical specifications.
3. Structural failures including, but not limited to, excessive deflection.
4. Delamination of exterior or interior facing materials.
5. Making good and installation and finishing all items that are disturbed and that may be required
due to repair or replacement of defective items. Coordinate with Employer, manufacturer, and
installer of adjacent disturbed items to ensure that their warranty is not cancelled due to the repair
work.

1.8 DELIVERY, STORAGE AND HANDLING


A. Deliver materials in manufacturer's unopened, labelled packing and in compliance with the
manufacturer's storage, handling, installation and protection requirements.

1.9 JOB CONDITIONS


A. Substrate: Proceed with waterproofing after completing substrate construction, openings and
penetrating works.
B. Weather: Proceed with waterproofing and associated works only when existing and forecast weather
conditions permit work to be performed in accordance with manufacturer's recommendations and
warranty requirements.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS


A. Refer List of Approved Manufacturers.

2.2 WATERPROOFING MATERIALS


A. Positive-Side, Cementitious Waterproofing: Flexible, Cementitious acrylic waterproof coating shall be
a two component, crack accommodating coating with the following physical properties.
1. Physical properties
a. Maximum particle size 0.63 mm
b. Water vapour permeability (mCO2) 985
c. CO2 permeability (mCO2) 100000
d. Water resistance
1). Positive pressure 1.5 bar
2). Negative pressure 1.0 bar
e. Water absorption (ASTM 642C) 1.48%
f. Capillary water absorption 17.5 x 10-3 kg/m2h0.5
g. Elongation (28days)
1). Ambient 23.4%
2). Underwater 16.2%

Section 07 16 00 Cementitious Waterproofing Page 4 of 6 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

h. Freeze/thaw resistance
1). (ISO/DIS 4846.2) no scaling after 50 cycles
i. Strength (39days) N/mm²
1). Tensile 0.64
2). Adhesive 1.00

2.3 CONCRETE MIX


A. Concrete Mix: Same concrete mix as described in Section 03 30 00 “Cast-In-Place Concrete”.
B. Compressive Strength: At least 35N/mm² at 28days, or greater if required by the Engineer.

2.4 SCREED AND PLASTER


A. Waterproofed Screed and Cement Plaster: Same screed and plaster as described in Section 03 53 00
”Concrete Topping” and Section 09 24 00 “Portland Cement Plaster.”

2.5 WATERSTOPS AND MASTIC


A. Waterstops: Consist of hydrophilic polyacrylate elastomeric material designed for internal sealing of all
construction joints for the cast-in-place concrete application. Waterstops expands upon contact with
water for form a positive seal even in saline conditions and performs successfully under hydrostatic
pressure and under both continuous immersion and wet/dry cycling.
B. Mastic: Fast cure, non-sag, moisture curing, high-performance polyurethane-based single pack
adhesives compatible with water stops described above.

2.6 GUNITING
A. Gunite shall have average 125mm thick using one part of SRC and four parts of crushed washed
aggregate by weight to achieve 30N/mm² at 28days.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with applicator present, for suitable conditions where
waterproofing is to be applied.
B. Proceed with application only after unsatisfactory conditions have been corrected.
C. Notify the Engineer in writing of active leaks or defects that would affect system performance.

3.2 PREPARATION
A. Protect other work from damage caused by cleaning, preparation, and application of waterproofing.
Provide temporary enclosure to confine spraying operation and to ensure adequate ambient
temperatures and ventilation conditions for application.
B. Do not allow waterproofing, patching, and plugging materials to enter reveals or annular spaces
intended for resilient sealants or gaskets, such as joint spaces between pipes and pipe sleeves.
C. Stop active water leaks with plugging compound according to waterproofing manufacturer's written
instructions.
D. Repair damaged or unsatisfactory substrate with patching compound according to manufacturer's
written instructions.

3.3 INSTALLATION/ APPLICATION


A. General: Install/apply cement waterproofing system shall be done in strict compliance with
manufacturer’s User Guide for Concrete Waterproofing System and with the approval of the Engineer.

Section 07 16 00 Cementitious Waterproofing Page 5 of 6 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

B. The application shall be in two coats either spray applied or brush applied. Typical layer thickness shall
be 1mm.Second coat shall be applied after the curing of the first layer at least 6hours at 20ºC.
C. Waterproofing works shall be executed by a Subcontractor recommended by the waterproofing
manufacturer and approved by the Engineer.
D. Curing: Moist-cure waterproofing for not less than three (3) days immediately after the application has
set, followed by air drying before being placed in service unless otherwise recommended in writing by
the manufacturer.

3.4 CLEANING AND PROTECTION


A. Do not permit foot or vehicular traffic on unprotected membrane.
B. Protect waterproofing from damage and wear during remainder of construction period.
C. Clean spillage and soiling from adjacent construction using cleaning agents and procedures
recommended by manufacturer of affected construction.

END OF SECTION

Section 07 16 00 Cementitious Waterproofing Page 6 of 6 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

SECTION 07 21 00

THERMAL INSULATION

Revision History

00 Dec. 2023 100% Design Development - Revised CC MS ST


Prepared Checked Approved
Rev. Date Description of Revision
By By By
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

SECTION 07 21 00

THERMAL INSULATION

INDEX

PAGE

PART 1 - GENERAL 2
1.1 RELATED DOCUMENTS 2
1.2 SECTION INCLUDES 2
1.3 RELATED SECTIONS 2
1.4 REFERENCES 2
1.5 SUBMITTALS 2
1.6 QUALITY ASSURANCE 3
1.7 DELIVERY, STORAGE AND HANDLING 3
1.8 WARRANTY 3

PART 2 - PRODUCTS 3
2.1 ACCEPTABLE MANUFACTURERS 3
2.2 RIGID INSULATION 4
2.3 EXPANDED INSULATION 4
2.4 MINERAL FIBRE INSULATION 4
2.5 PHENOLIC INSULATION 4
2.6 SEPARATION LAYER (BETWEEN INSULATION AND ROOF TILES) 4
2.7 HIGH-DENSITY POLYSTYRENE SKIRTING (IF APPLICABLE) 5
2.8 ADHESIVE 5
2.9 ACCESSORIES 5

PART 3 - EXECUTION 5
3.1 EXAMINATION 5
3.2 INSTALLATION OF INSULATION 5
3.3 PROTECTION 6

Section 07 21 00 Thermal Insulation Page 1 of 6 Rev. 00 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

PART 1 - GENERAL

1.1 RELATED DOCUMENTS


A. The Drawings and general provisions of the Contract, including General and Particular Conditions and
Division 1 Specification Sections, apply to this Section.

1.2 SECTION INCLUDES


A. Expanded Polystyrene boards for the roof, and walls and soffits as indicated on the Drawings.
B. Thermal Mineral Fibre Insulation for walls, columns, cavity walls and soffits as indicated.
C. Phenolic Insulation
D. Vapour Barrier
E. High-Density Polystyrene Skirting (if applicable)

1.3 RELATED SECTIONS


A. Section 03 30 00 - Cast-In Place Concrete
B. Section 04 22 00 - Concrete Unit Masonry
C. Section 07 84 00 - Firestopping.
D. Section 09 21 16 - Gypsum Board Assemblies
E. Division 23 - HVAC Insulation

1.4 REFERENCES
A. American Society for Testing and Materials (ASTM)
1. ASTM C171 Standard Specification for Sheet Materials for Curing Concrete.
2. ASTM C665 Standard Specification for Mineral-Fiber Blanket Thermal Insulation Frame
Construction and Manufactured Housing.
3. ASTM D1621 Standard Test Method for Compressive Properties of rigid Cellular
Plastics.
4. ASTM D1622 Standard Test Method for Apparent Density of Rigid Cellular Plastics.
5. ASTM D2842 Standard Test Method for Water Absorption of Rigid Cellular Plastics.
6. ASTM D4533 Standard Test Method for Trapezoid Tearing Strength of Geotextiles.
7. ASTM D4595 Standard Test Method for Tensile Properties of Geotextiles by the Wide-
Width Strip Method.
8. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building
Materials.
9. ASTM E136 Standard Test Method for behavior of Materials in a Vertical Tube
Furnace at 750ºC
B. Ministry of Interior (MOI)
C. Saudi Electric Company (SEC)
D. Saudi Building Codes (SBC)

1.5 SUBMITTALS
A. A complete list of all items proposed to be installed under this Section.
B. Manufacturer's Specifications and other data necessary to demonstrate compliance with the
Specification.

Section 07 21 00 Thermal Insulation Page 2 of 6 Rev. 00 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

C. Material Certificates.
D. Qualification Data:
1. Qualification data for firms and persons specified in "Quality Assurance" article to demonstrate
their capabilities and experience. Include list of completed projects with project name, addresses,
names of Engineer and Employers, and other information specified.
2. For Testing Agency Qualifications include proof of qualifications in the form of a recent report on
the inspection of the testing agency by a recognized authority.
E. Product Data: For each type of product indicated. For coatings, indicating VOC content.
F. Laboratory Test Reports: For coatings, indicating compliance with requirements for low-emitting
materials.
G. Shop Drawings indicating the layout of sheets and details with suitable drawing scale.

1.6 QUALITY ASSURANCE


A. Manufacturer Qualifications: Minimum Five (5) years manufacturing similar products.
B. Installer's Qualifications: The installer shall be experienced in handling rigid insulation materials and
shall be fully conversant with current manufacturer's published data.
C. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E 84
by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
D. Source Limitation: Obtain each type of building insulation from a single source with resources to
provide products complying with requirements without delaying progress of the work.

1.7 DELIVERY, STORAGE AND HANDLING


A. Generally; Protect insulation board against damage during delivery and storage, also against
deterioration by ultraviolet light.
B. Protect insulation materials from physical damage and from deterioration by moisture, soiling, and
other sources. Store inside and in a dry location. Comply with manufacturer's written instructions for
handling, storing, and protecting during installation.
C. Protect plastic insulation as follows:
1. Do not expose to sunlight, except to extent necessary for period of installation and concealment.
2. Protect against ignition at all times. Do not deliver plastic insulating materials to Project site
before installation time.
3. Complete installation and concealment of plastic materials as rapidly as possible in each area of
construction.

1.8 WARRANTY
A. A written certification shall be required that insulation meets Thermal Warranty.
B. Warranty shall also state that roof insulation’s actual thermal resistance will not vary by more than 10%
from the designed R-Value for a period of fifteen (15) years.
C. Submit documented proof that the material has a proven record of successful performance for more than
10 years, confirmed by at least five local projects.
D. Comply with all requirements of the project and the local Authorities.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS


A. Refer Separate List of Manufacturers

Section 07 21 00 Thermal Insulation Page 3 of 6 Rev. 00 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

2.2 RIGID INSULATION


A. The insulation shall be a non-absorbent, foam extruded, closed cell polystyrene board specifically
manufactured for use in roofing and as wall insulation.
B. Edges of boards shall be rebated.
C. Physical properties:
1. Thermal conductivity (K Value) : 0.0301w/m.ºK .to DIN52612 (K=0.25 Imperial)
2. Coefficient of thermal expansion : 80 x 10-6 longitudinal
60 x 10-6 transverse
3. Water Absorption : 1% volume to ASTM D2842
4. Capillary reaction : Nil
5. Density : 35kg/m³ to ASTM D1622.
6. Compressive strength : 0.2N/mm² to ASTM D-1621
7. Combustion Characteristics : Class A as per ASTM E-84
8. Thicknesses : As indicated on the Drawings.
D. Vapour barrier shall be 0.25mm thick clear polyethylene conforming to ASTM C171 lapped and taped
100mm on sides and ends. Physical properties for materials shall conform to ASTM E154.

2.3 EXPANDED INSULATION


A. Expanded Polystyrene meeting the following specification for Insulation Board as per ASTM C578.
1. Thickness: 110mm, 120mm at locations indicated on the Drawings.
2. Density: 26-27Kg/m³
3. Thermal conductivity: 0.035W/m.K

2.4 MINERAL FIBRE INSULATION


A. Thermal Insulation: ASTM C-665, Type I produced by combining thermosetting resins with mineral
fibres with the densities and thicknesses as indicated on Drawings shall be used to achieve the required
thermal and acoustical properties.

2.5 PHENOLIC INSULATION


A. The soffit insulation shall be rigid thermoset phenolic (as defined in EN 13166) insulation core with
low emissivity composite foil on its exposed face and glass tissue based facing on its reverse face. The
product shall be manufactured with a blowing agent that has zero ODP and low GWP. Installation shall
be done as per manufacturer’s recommendation with mechanical screws and joints shall be treated with
self-adhesive fiber glass joint tapes to receive paint system as per Schedule of Finishes. The product
shall be Loacl Civil Defence certified for soffit application.
1. Thickness: 60mm as indicated on the Drawings.
2. Thermal Conductivity: 0.021W/mk
3. Thermal Resistance: 1.531m2K/W
4. Flame Spread Index: 25 or less (ASTM E-84)
5. Smoke Developed Index: 450 or less (ASTM E-84)

2.6 SEPARATION LAYER (BETWEEN INSULATION AND ROOF TILES)


A. Non-woven Geotextile fabric composed of thermally bonded continuous 100% polypropylene filaments
with fibre diameter 40-50 microns with the following properties:

Section 07 21 00 Thermal Insulation Page 4 of 6 Rev. 00 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

1. Tensile strength (ASTM D 4595): 8.7kN/m


2. Elongation at break: 45%
3. Tear strength (ASTM D 4533): 340 N
4. Permeability at 20kN/m²: 2.2 x 10 –4 m/s
5. Thickness: 0.45mm

2.7 HIGH-DENSITY POLYSTYRENE SKIRTING (IF APPLICABLE)


A. Extruded polystyrene; fine and closed-cell, white, homogeneous foam glue applied on clean, dry, free
from dust, degreased and flat surfaces to the size as indicated on the Drawings.
B. Density: Approx. 350kg/m3.

2.8 ADHESIVE
A. As recommended by insulation manufacturer for the specific application with demonstrated capacity to
bond insulation securely to substrate indicated without damaging insulation and substrates.
B. VOC Limits for Installation Adhesives and Glues: Use installation adhesives that comply with the
following limits for VOC content when calculated according to South Coast Air Quality Management
District Rule 1168:
1. Adhesive: 70g/L.

2.9 ACCESSORIES
A. Insulation Fasteners: Impale clip type of plain finished steel; of the type to be adhered to the surface to
receive rigid insulation; length to suit insulation thickness; capable of securely and rigidly fasting
insulation in place.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Surfaces to receive insulation: Ensure that surfaces to receive insulation are clean, dry, and suitable to
provide a complete and satisfactory installation.

3.2 INSTALLATION OF INSULATION


A. General: Apply insulation units to substrates, complying with manufacturer's written instructions. Bond
units to substrate with the adhesive or use mechanical anchorage to provide permanent placement and
support of units.
B. Rigid Insulation Boards
1. Install in accordance with manufacturer's recommendations and staggering joints in both
directions.
2. Cut clearly to fit closely around projections, upstands, rainwater outlets etc.
3. Protect from damage after installation.
C. Thermal Insulation
1. Install thermal insulation without gaps or voids in accordance with manufacturer's instructions.
2. Trim insulation neatly to fit spaces. Use insulation free of damage.
3. Place blankets in cavities formed by framing members to produce a friction fit between edges of
insulation and adjoining framing members.
4. Fit insulation tight in spaces and tight to the exterior side of mechanical and electrical services
within the plane of insulation. Leave no gaps or voids.

Section 07 21 00 Thermal Insulation Page 5 of 6 Rev. 00 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

5. Thermal insulation to internal walls &soffits shall be concealed with cement/gypsum boards at
locations indicated on the Drawings.
D. Insulation Fasteners
1. Apply fasteners to surfaces in accordance with manufacturer’s instructions. Check for
compatibility of adhesive with any concrete form release agent used.
2. Provide the minimum of four fasteners per 600mm x 1200mm board, allowing for a maximum
load per fastener of 1.5kg.
3. Install separation fabric according to manufacturer’s written instruction, overlapping sides and
ends.
4. Where there is return air movement allowed through, the insulation shall be provided with the
suitable black fabric covering to avoid glass fibres mixing with return air.

3.3 PROTECTION
A. Protect all insulation from unnecessary construction traffic after installation. Protection shall be
approved and shall prevent any damage likely to result in a decrease in the efficiency of the insulation.
B. Protect from long periods of exposure before being concealed, by proper sequencing of the work.

END OF SECTION

Section 07 21 00 Thermal Insulation Page 6 of 6 Rev. 00 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

SECTION 07 84 00

FIRESTOPPING

Revision History

02 Dec. 2023 100% Design Development - Revised CC MS ST


01 Jun. 2023 100% Design Development - Revised CC MS ST
00 Apr. 2023 100% Design Development Submission CC MS ST
Prepared Checked Approved
Rev. Date Description of Revision
By By By
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

SECTION 07 84 00

FIRESTOPPING

INDEX

PAGE

PART 1 - GENERAL 2
1.1 RELATED DOCUMENTS 2
1.2 SECTION INCLUDES 2
1.3 RELATED SECTIONS 2
1.4 REFERENCES 2
1.5 SUBMITTALS 3
1.6 QUALITY ASSURANCE 3
1.7 DELIVERY, STORAGE AND HANDLING 3
1.8 PROJECT CONDITIONS 4
1.9 WARRANTY 4
1.10 MOCK-UPS 4
1.11 COORDINATION: 4

PART 2 - PRODUCTS 5
2.1 ACCEPTABLE MANUFACTURERS 5
2.2 FIRESTOPPING COMPONENTS AND ACCESSORIES 5
2.3 FIRESTOP SYSTEM SCHEDULE 6

PART 3 - EXECUTION 7
3.1 EXAMINATION 7
3.2 PREPARATION 7
3.3 INSTALLATION 7
3.4 FIELD QUALITY CONTROL 8
3.5 IDENTIFICATION AND DOCUMENTATION 8
3.6 CLEANING AND PROTECTION 8

Section 07 84 00 Firestopping Page 1 of 8 Rev. 02 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

PART 1 - GENERAL

1.1 RELATED DOCUMENTS


A. The Drawings and general provisions of the Contract, including General and Particular Conditions and
Division 1 Specification Sections, apply to this Section.

1.2 SECTION INCLUDES


A. The Section includes fire stopping for the following:
1. Penetrations through fire-resistance-rated walls, partitions, floor and roof construction including
both empty openings and openings containing cables, pipes, ducts, conduits, and other penetrating
items.
2. All openings in slabs at Mechanical Rooms including spaces leftover in the shaft after installation
of ducts shall be sealed with non-combustible materials to maintain the required fire-rating
continuity of the floor construction.
3. Penetrations through smoke barriers and construction enclosing compartmentalised areas
involving both empty openings and openings containing penetrating items.
4. Sealant joints in fire-resistance construction.
5. Safing slot gaps between the edge of floor slabs and curtain walls.
6. Openings between structurally separate sections of wall or floors.
7. Gaps between the top of walls and ceilings or roof assemblies.
8. Expansion joints in walls and floors (If Applicable)

1.3 RELATED SECTIONS


A. Section 03 30 00 - Cast-In-Place Concrete
B. Section 04 22 00 - Masonry
C. Section 07 21 00 - Thermal Insulation
D. Section 07 92 00 - Joint Sealants
E. Division 23 Section specifying ducts and piping penetrations.
F. Division 26 and 27 Sections specifying cable & conduit penetrations.

1.4 REFERENCES
A. American Society for Testing and Materials (ASTM)
1. ASTM C719 Standard Test Method for Adhesion and Cohesion of Elastomeric Joint
Sealants under Cyclic Movement (Hockman Cycle)
2. ASTM C920 Standard Specification for Elastomeric Joint Sealants.
3. ASTM C1193 Standard Guide for Use of Joint Sealants.
4. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building
Materials.
5. ASTM E119 Standard Test Methods for Fire Tests of Building Construction and Materials.
6. ASTM E136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at
750ºC.
7. ASTM E814 Standard Test Method for Fire Tests of Penetration Firestop Systems.
B. National Fire Protection Association (NFPA)
1. NFPA 101 Life Safety Code

Section 07 84 00 Firestopping Page 2 of 8 Rev. 02 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

2. NFPA 70 National Electric Code


C. IBC 2009 International Building Code
D. KSA Life and Safety Code
E. Ministry of Interior (MOI)
F. Saudi Electric Company (SEC)
G. Saudi Building Codes (SBC)

1.5 SUBMITTALS
A. Product data for each type of product specified.
B. The Shop Drawings detailing materials, installation methods, and relationships to adjoining
construction for each through-penetration firestop system, and each kind of construction condition
penetrated and penetrating item. Include firestop design designation of qualified testing and inspecting
agency evidencing compliance with requirements for each condition indicated.
C. Product certificates signed by manufacturers of firestopping products certifying that their products
comply with specific requirements.
D. Product test reports from and based on tests performed by, a qualified testing and inspecting agency
evidencing compliance of firestopping with requirements based on comprehensive testing of current
products.
E. Qualification data for firms and persons specified in "Quality Assurance" article to demonstrate their
capabilities and experience. Include the list of completed projects with project names, addresses, names
of engineers and employers, and other information specified.
F. Certification by firestopping manufacturer that products supplied complies with local regulations
controlling use of volatile organic components (VOCs) and is nontoxic to building occupants.

1.6 QUALITY ASSURANCE


A. Installer Qualifications: Engage an experienced installer who is certified, licensed, or otherwise
qualified by the firestopping manufacturer as having the necessary experience, staff, and training to
install manufacturer's products per specified requirements. A manufacturer's willingness to sell its
firestopping products to the Contractor or an installer engaged by the Contractor does not in itself
confer qualification on the buyer.
B. Single-Source Responsibility: Obtain through-penetration firestop system for each kind of penetration
and construction condition indicated from a single manufacturer.
C. Field-Construction Mockup: Before installing fire- stopping, erect mockups for each different through-
penetration firestop system indicated to verify selections made and to demonstrate qualities of materials
and execution. Build mockups using materials indicated for final installations.
D. Co-ordination Works: Co-ordinate construction of openings and penetrating items to ensure that
designated through-penetration firestop systems are installed per specified requirements.

1.7 DELIVERY, STORAGE AND HANDLING


A. Deliver firestopping products to Site in original, unopened containers or packages with intact and
legible manufacturers' labels identifying product and manufacturer, date of manufacture, lot number,
shelf life, if applicable; qualified testing and inspecting agency classification marking applicable to
Project; curing time, and mixing instructions for multi-component materials.
B. Store and handle firestopping materials to prevent their deterioration or damage due to moisture,
temperature changes, contaminants, or other causes.
C. Do not cover up those firestopping installations that will become concealed behind other construction
until the Employer's inspection agency and Statutory Authorities having jurisdiction, if required, have
examined each installation.

Section 07 84 00 Firestopping Page 3 of 8 Rev. 02 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

1.8 PROJECT CONDITIONS


A. Do not use materials that contain flammable solvents.
B. Schedule installation of firestopping after completion of penetrating item installation but before
covering or concealing of openings.
C. Verify the existing conditions and substrates before starting work. Correct unsatisfactory conditions
before proceeding.
D. Weather conditions: Do not proceed with installation of firestop materials when temperatures exceed
the manufacturer's recommended limitations for installation printed on the product label and product
data sheet.
E. During installation, provide masking and drop cloths to prevent firestopping materials from
contaminating any adjacent surfaces.

1.9 WARRANTY
A. Manufacturer’s Warranty: Provide complete system warranty in which Manufacturer, Contractor and
Installer are jointly and severally liable and agree to repair or replace component of firestopping in case
of failure in materials or workmanship to meet the specifications within specified warranty period.
1. Warranty Period: 5 years from date of Taking Over.

1.10 MOCK-UPS
A. Install mock-ups for each firestopping system, including typical penetrations, construction joints, and
perimeter firestop systems, as required to maintain each fireresistive rated assembly.
1. System Components: Include as necessary to illustrate compete system for each hourly rating.
2. UL Classified System: Attach drawing and instructions required for installation adjacent to each
mock-up. Do not remove prior to acceptance of mock-up
3. Testing and Verification: Determine depth and configuration of each fieldinstalled firestopping
system. Destructive testing is not required for factorymetered systems.
4. Obtain Engineer's approval of mockups before start of Work.
5. Retain and maintain mockups during construction in an undisturbed condition as a standard for
judging the completed Work.
a. Approved mockups in an undisturbed condition at the time of Substantial Completion may
become part of the completed Work.
B. Fire-Test-Response Characteristics: Penetration firestopping shall comply with the following
requirements:
1. Penetration firestopping tests are performed by a qualified testing agency acceptable to authorities
having jurisdiction.
2. Penetration firestopping is identical to those tested per testing standard referenced in "Penetration
Firestopping" Article. Provide rated systems complying with the following requirements:
3. Penetration firestopping products bear classification marking of qualified testing and inspecting
agency.
4. Classification markings on penetration firestopping correspond to designations as per applicable
authorities.

1.11 COORDINATION:
A. Coordinate construction of openings and penetrating items to ensure that penetration firestopping
systems are installed according to specified requirements.
B. Coordinate sizing of sleeves, openings, core-drilled holes, or cut openings to accommodate penetration
firestopping systems.

Section 07 84 00 Firestopping Page 4 of 8 Rev. 02 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

C. Notify Employer's inspecting agency at least seven days in advance of through-penetration firestop
system installations; confirm dates and times on days preceding each series of installations.
D. Do not cover up through-penetration firestop system installations that will become concealed behind
other construction until each installation has been examined by Employer's inspecting agency and
building inspector, if required by authorities having jurisdiction.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS


A. (Refer Separate List of Manufacturers)

2.2 FIRESTOPPING COMPONENTS AND ACCESSORIES


A. All firestopping materials shall be as approved by Local Authorities.
B. Compatibility: Provide through-penetration firestop systems that are compatible with one another, with
the substrates forming openings, and with the items, if any, penetrating through-penetration firestop
systems, under conditions of service and application, as demonstrated by through-penetration firestop
system manufacturer based on testing and field experience.
C. Fill materials for through-penetration firestop systems.
1. Cast-in-Place Firestop Devices: Factory-assembled devices for use in cast-in-place concrete floors
and consisting of an outer metallic sleeve lined with an intumescent strip, a radial extended flange
attached to one end of the sleeve for fastening to concrete formwork, and a neoprene gasket.
2. Latex Sealants: Single-component latex formulations that after cure do not re-emulsify during
exposure to moisture.
3. Firestop Devices: Factory-assembled collars formed from galvanised steel and lined with
intumescent material sized to fit the specific diameter of penetrant.
4. Intumescent Putties: Nonhardening dielectric, water-resistant putties containing no solvents,
inorganic fibres, or silicone compounds.
5. Flexible Fire Seal: Compressible fire retardant foam faced either side with an intumescent sheet.
6. Non-shrink putty: One part intumescent non-setting compound which will expand in volume when
exposed to high temperatures.
7. Silicone Sealants: Moisture-curing, single-component, silicone-based, neutral-curing elastomeric
sealants.
D. Accessories: Use only approved components specified by the firestopping manufacturer for the
designated fire-resistance - rated systems. Accessories include but are not limited to the following
items:
1. Permanent forming/ damming/ backing materials including the following:
a. Semi-refractory fibre (mineral wool) insulation.
b. Sealants used in combination with other forming/damming materials to prevent leakage of
fill materials in the liquid state.
c. Fire-rated formboard.
d. Joint fillers of joint sealants.
2. Temporary forming materials.
3. Substrate primers.
4. Collars.
5. Steel sleeves.

Section 07 84 00 Firestopping Page 5 of 8 Rev. 02 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

2.3 FIRESTOP SYSTEM SCHEDULE


A. Type of Fill Materials for firestop Systems with No Penetrating Items: One or more of the following:
1. Latex sealant.
2. Silicone sealant.
3. Intumescent putty.
B. Type of Fill Materials Firestop Systems for Metallic Pipes, Conduit, or Tubing: One or more of the
following:
1. Latex sealant.
2. Silicone sealant.
3. Intumescent putty.
C. Type of Fill Materials for Firestop Systems for nonmetallic Pipe, Conduit, or Tubing: One or more of
the following:
1. Latex sealant.
2. Silicone sealant.
3. Intumescent putty.
4. Firestop device.
D. Type of Fill Materials for Firestop Systems for Electrical Cables: One or more of the following:
1. Latex sealant.
2. Silicone sealant.
3. Intumescent putty.
4. Non-shrink putty.
E. Type of Fill Materials for Firestop Systems for Cable Trays: One or more of the following:
1. Latex sealant.
2. Intumescent putty.
3. Non-shrink putty.
F. Type of Fill Materials for Firestop Systems for Insulated Pipes: One or more of the following:
1. Latex sealant.
2. Intumescent putty.
3. Non-shrink putty.
G. Type of Fill Materials for Firestop Systems for Miscellaneous Electrical Penetrants: One or more of the
following:
1. Latex sealant.
2. Intumescent putty.
H. Type of Fill Materials Firestop Systems for Miscellaneous Mechanical Penetrations: One or both of the
following:
1. Latex sealant.
I. Type of Fill Materials for Firestop Systems for Groupings of Penetrations: One or more of the
following:
1. Latex sealant.
2. Firestop device.

Section 07 84 00 Firestopping Page 6 of 8 Rev. 02 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

J. Use flexible fire seal separation in raised floor areas where indicated on the Drawings.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Examine substrates and conditions with the installer present, for compliance, with requirements for
opening configurations, penetrating items, substrates, and other conditions affecting the performance of
firestopping. Do not proceed with installation until unsatisfactory conditions have been corrected.

3.2 PREPARATION
A. Surface cleaning: Clean out openings and joints immediately prior to installing firestopping to comply
with recommendations of firestopping manufacturer and the following requirements:
B. Remove all foreign materials from surfaces of opening and joint substrates and from penetrating items
that could interfere with adhesion of firestopping.
C. Clean opening and joint substrates and penetrating items to produce clean, sound surface capable of
developing the optimum bond with firestopping. Remove loose particles remaining from cleaning
operation.
D. Priming: Prime substrate where recommended by firestopping manufacturer using the manufacturers
recommended products and methods. Confine primers to areas of bond; do not allow spillage and
migration onto exposed surfaces.
E. Masking Tape: Use masking tape to prevent firestopping from contacting adjoining surfaces that will
remain exposed upon completion of Works, and that would otherwise be permanently stained or
damaged by such contact or by cleaning methods used to remove smears from firestopping materials.
Remove tape as soon as it is impossible to do so without disturbing firestopping seal with substrates.

3.3 INSTALLATION
A. Install forming/ damming materials and other accessories of types required to support fill materials
during their application and in the position needed to produce the cross-sectional shapes and depths
required to achieve fire ratings of designated through-penetration firestop systems. After installing fill
materials, remove combustible forming materials and other accessories not indicated as permanent
components of firestop systems.
B. Install joint fillers to provide support of sealants application and at the position required to produce the
cross-sectional shapes and depths of installed sealants relative to joint widths that allow optimum
sealant movement capability and develop fire-resistance rating required.
C. Install sealant by proven techniques that result in sealants directly contacting and fully wetting joint
substrates, completely filling recesses provided for each joint configuration, and providing uniform,
cross-sectional shapes and depths relative to the joint width that provide optimum sealant movement
capability. Install sealants at the same time joint fillers are installed.
D. Tool nonsag sealant immediately after sealant application and prior to the time skinning or curing
begins. Form smooth, uniform beads of configuration indicated or required to produce fire-resistance
rating, as well as to eliminate air pockets, and to ensure contact and adhesion of sealant with sides of
joint. Remove excess sealant from the surface adjacent to joint. Do not use tooling agents that
discolour sealants or adjacent surfaces or are not approved by sealant manufacturer.
E. Cleaning
1. Clean off excess fill materials and sealants adjacent to openings and joints as work progresses by
methods and with cleaning materials approved by manufacturers of firestopping products and of
products in which opening and joints occur.
2. Protect firestopping during and after curing period of contact with contaminating substances or
from damage resulting from construction operations or other causes so that they are without
deterioration or damage at the time of Taking Over. If, despite such protection, damage or
deterioration occurs, cut out and remove damaged or deteriorated fire stopping immediately and

Section 07 84 00 Firestopping Page 7 of 8 Rev. 02 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

install new materials to produce firestopping complying with specified requirements.

3.4 FIELD QUALITY CONTROL


A. Examine sealed penetration areas to ensure proper installation before concealing or enclosing areas.
B. Keep areas of work accessible until inspection by applicable code authorities.
C. Inspection of fire stopping shall be performed in accordance with ASTM E 2174 for through-
penetration & ASTM E 2393 Joints & Curtain Wall Joints, “Standard Practice for On-Site Inspection of
Installed Fire Stops” or other recognized standard.
D. Perform under this section patching and repairing of firestopping caused by cutting or penetrating of
existing firestop systems already installed by other trades.
E. Manufacturer's Field Services: After the Initial Installation of Fire Stop System is complete, provide
destructive testing inspections to assure proper installation of the application, submit findings in writing
indicating whether or not the installation of the tested system identified was installed correctly. This
cannot be treated as an inspection, but this service is more to see that the systems included in the
submittal are being implemented on Site.

3.5 IDENTIFICATION AND DOCUMENTATION


A. The Contractor is to supply documentation (to be included in submittal) for every single application
addressed. This documentation is to identify each penetration and joint location on the entire Project.
B. Identify firestop systems with pressure-sensitive, self-adhesive, preprinted vinyl labels. Attach labels
permanently to surfaces of penetrated construction on both sides of each firestop system installation
where labels will be visible to anyone seeking to remove penetrating items or firestop systems. Include
the following information on labels:
1. The words: "Warning - Through-Penetration Firestop System - Do Not Disturb. Notify Building
Management of Any Damage."
2. The Contractor's Name.
3. Firestop system reference.
4. Firestop system manufacturer's name.

3.6 CLEANING AND PROTECTION


A. Clean off excess fill materials adjacent to openings as the Work progresses by methods and with
cleaning materials that are approved in writing by penetration firestopping manufacturers and that do
not damage materials in which openings occur.
B. Provide final protection and maintain conditions during and after installation that ensure that
penetration firestopping is without damage or deterioration at the Date of Taking Over.
C. If, despite such protection, damage or deterioration occurs, immediately cut out and remove damaged or
deteriorated penetration firestopping and install new materials to produce systems complying with
specified requirements.

END OF SECTION

Section 07 84 00 Firestopping Page 8 of 8 Rev. 02 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

SECTION 07 92 00

JOINT SEALANTS

Revision History

03 Dec. 2023 100% Design Development - Revised CC MS ST


02 Jun. 2023 100% Design Development - Revised CC MS ST
01 Apr. 2023 100% Design Development Submission CC MS ST
00 Jan. 2023 50% Design Development Submission CC MS ST
Prepared Checked Approved
Rev. Date Description of Revision
By By By
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

SECTION 07 92 00

JOINT SEALANTS

INDEX

PAGE

PART 1 - GENERAL 2
1.1 RELATED DOCUMENTS 2
1.2 SECTION INCLUDES 2
1.3 RELATED SECTIONS 2
1.4 REFERENCES 2
1.5 PERFORMANCE REQUIREMENTS 3
1.6 SUBMITTALS 3
1.7 QUALITY ASSURANCE 4
1.8 DELIVERY, STORAGE AND HANDLING 5
1.9 PROJECT CONDITIONS 5
1.10 WARRANTY 5

PART 2 - PRODUCTS 5
2.1 ACCEPTABLE MANUFACTURERS 5
2.2 MATERIALS, GENERAL 5
2.3 ELASTOMERIC JOINT SEALANTS 6
2.4 LATEX JOINT-SEALANT 6
2.5 ACOUSTICAL JOINT SEALANTS 6
2.6 JOINT-SEALANT BACKING 6
2.7 MISCELLANEOUS MATERIALS 7

PART 3 - EXECUTION 7
3.1 EXAMINATION 7
3.2 PREPARATION 7
3.3 INSTALLATION OF JOINT SEALANTS 7
3.4 FIELD QUALITY CONTROL 8
3.5 CLEANING 8
3.6 PROTECTION 8

Section 07 92 00 Joint Sealants Page 1 of 8 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

PART 1 - GENERAL

1.1 RELATED DOCUMENTS


A. The Drawings and general provisions of the Contract, including General and Particular Conditions and
Division 1 Specification Sections, apply to this Section.

1.2 SECTION INCLUDES


A. Exterior joints in the following vertical surfaces and non-traffic horizontal surfaces:
1. Control joints in cast-in-place concrete and precast concrete units.
2. Control joints in unit masonry.
3. Joints between different materials listed above.
4. Perimeter joints between materials listed above and frames of doors and windows.
5. Other joints as indicated.
B. Exterior joints horizontal traffic surface:
1. Control and expansion joints in pavers.
C. Interior joints in the following vertical surfaces and horizontal non-traffic surfaces:
1. Control joints on exposed interior surfaces of exterior walls.
2. Perimeter joints of exterior openings where indicated.
3. Tile control and expansion joints.
4. Vertical control joints on exposed surfaces of interior unit masonry and concrete walls and
partitions.
5. Perimeter joints between interior wall surfaces and frames of interior doors, windows, and elevator
entrances.
6. Joints between plumbing fixtures and adjoining walls, floors, and counters.
7. Other joints as indicated.
D. Interior joints in the following horizontal traffic surfaces:
1. Control joints in cast-in-place concrete slabs.
2. Control joints in tile flooring.
3. Other joints as indicated.

1.3 RELATED SECTIONS


A. Section 04 22 00 - Concrete Unit Masonry.
B. Section 07 84 00 - Firestopping.
C. Section 08 81 00 - Glazing.
D. Section 09 21 16 - Gypsum Board Assemblies.

1.4 REFERENCES
A. ASTM C 719 Standard Test Method for Adhesion and Cohesion of Elastomeric Joint
Sealants Under Cyclic Movement (Hockman Cycle).
B. ASTM C834 Standard Specification for Latex Sealants
C. ASTM C 919-12 Standard Practice for Use of Sealants in Acoustical Applications.
D. ASTM C 920-14a Standard Specification for Elastomeric Joint Sealants.
E. ASTM C 1193-16 Standard Guide for Use of Joint Sealants.

Section 07 92 00 Joint Sealants Page 2 of 8 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

F. ASTM C 1247-14 Standard Test Method for Durability of Sealants Exposed to Continuous
Immersion in Liquids.
G. ASTM C 1248-08 Standard Test Method for Staining of Porous Substrate by Joint Sealants
H. ASTM E90 Standard Test Method for Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions and Elements.
I. ASTM C 1330 Standard Specification for Cylindrical Sealant Backing for Use with Cold
Liquid-Applied Sealants.
J. ASTM D 1056-14 Standard Specification for Flexible Cellular Materials—Sponge or Expanded
Rubber.
K. Ministry of Interior (MOI)
L. Saudi Electric Company (SEC)
M. Saudi Building Codes (SBC)

1.5 PERFORMANCE REQUIREMENTS


A. Provide elastomeric joint sealants that establish and maintain watertight and airtight continuous joint
seals without staining or deteriorating joint substrates.
B. Provide joint sealants for interior applications that establish and maintain airtight and water-resistant
continuous joint seals without staining or deteriorating joint substrates.

1.6 SUBMITTALS
A. Product Data: For each joint-sealant product indicated.
B. Samples for Initial Selection: Manufacturer's colour charts consisting of strips of cured sealants
showing the full range of colours available for each product exposed to view.
C. Samples for Verification: For each type and colour of joint sealant required, provide samples with joint
sealants in 13mm wide joints formed between two 300mm long strips of material matching the
appearance of exposed surfaces adjacent to joint sealants.
D. Product Certificates: For each type of joint sealant and accessory, signed by the product manufacturer.
E. Qualification Data: For Manufacturer, Installer and testing agency to demonstrate their capabilities and
experience. Include lists of five completed projects (minimum) of a similar nature carried out
successfully with project names and addresses, names and addresses of engineers and employers, and
any other information specified or required by Engineer.
F. Installer Certificates: Signed by product manufacturer certifying that installer is approved, authorized,
or licensed by manufacturer to install his products.
G. Preconstruction Field Test Reports: Indicate which sealants and joint preparation methods resulted in
optimum adhesion to joint substrates based on preconstruction testing specified in “quality assurance”
Article.
H. Compatibility and Adhesion Test Reports: From sealant manufacturer, indicating the following:
1. Materials forming joint substrates and joint-sealant backings have been tested for compatibility
and adhesion with joint sealants.
2. Interpretation of test results and written recommendations for primers and substrate preparation
needed for adhesion.
I. Field Test Report Log: For each elastomeric sealant application.
J. Product Test Report Log: Based on comprehensive testing of product formulations performed by a
qualified testing agency, indicating that sealants comply with requirements.
K. Warranties: Special warranties specified in the Section.
L. Submit a detailed schedule of sealant usage for all locations. List each sealant material, joint fillers,
colour and product data for each location of use.

Section 07 92 00 Joint Sealants Page 3 of 8 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

1.7 QUALITY ASSURANCE


A. Installer Qualifications: An experienced installer who has specialized in installing joint sealants similar
in material, design, and extent to those indicated for this Project and whose work has resulted in joint-
sealant installations with a record of successful in-service performance.
B. Manufacturer of sealants shall provide a qualified technical representative who will visit the Site for the
purpose of advising the Installer of the proper procedures and precautions in the application of the
materials.
C. Source Limitations: Obtain each type of joint sealant through one source from a single manufacturer.
D. Preconstruction Compatibility and Adhesion Testing: submit to joint-sealant manufacturers, for testing
indicated below, samples of materials that will contact or affect joint sealants.
1. Use manufacturer’s standard test method to determine whether priming and other specific joint
preparation techniques are required to obtain rapid, optimum adhesion of joint sealants to joint
substrates.
2. Submit not fewer than eight (8) pieces of each type of material, including joint substrates, shims,
joint-sealants backings, secondary seals and miscellaneous materials.
3. Schedule sufficient time for testing and analyzing results to prevent delaying the Work.
4. For materials failing tests, obtain joint-sealants manufacturer’s written instructions for corrective
measures including use of specially formulated primers.
5. Testing will not be required if joint-sealant manufacturers submit joint preparation data that are
based on the previous testing of current sealant products for adhesion to, and compatibility with,
joint substrates and other materials matching those submitted.
E. Product Testing: Obtain test results for “Product Test Reports” paragraph in “Submittals” Article from a
qualified testing agency based on testing current sealant formulations within a 36-month period
preceding the Notice to Proceed with the Work.
1. Testing Agency Qualifications: An independent qualified testing agency as approved by the
Engineer to conduct the testing.
2. Test elastomeric joint sealants for compliance with requirements specified by reference to ASTM
C 920 and/or where applicable, to other standard test methods.
3. Test other joint sealants for compliance with requirements indicated by referencing standard
specifications and test methods.
F. Preconstruction Field-Adhesion Testing: Before installing elastomeric sealants, field tests their adhesion
to Project joint substrates as follows:
1. Locate test joints where indicated on the Project or, if not indicated, as directed by the Engineer.
2. Conduct field tests for each application indicated below:
a. Each type of elastomeric sealant and joint substrate indicated.
b. Each type of nonelastomeric sealant and joint substrate indicated.
3. Notify the Engineer seven (7) days in advance of dates and times when test joints will be erected.
4. Arrange for tests to take place with joint-sealant manufacturer’s technical representative present.
a. Test method: Test joint sealants according to Method A, Field- Applied Sealant Joint Hand
Pull Tab, in appendix X1 in ASTM C 1193 and where applicable to other Standard Test
Method.
b. For joints with dissimilar substrates, verify adhesion to each substrate separately; extend cut
along one side, verifying adhesion to opposite side. Repeat procedure for opposite side.
5. Report whether sealant in joint connected to pulled-out portion failed to adhere to joint substrates
or tore cohesively. Include data on pull distance used to test each type of product and the joint
substrate. For sealants that fail adhesively, retest until satisfactory adhesion is obtained.

Section 07 92 00 Joint Sealants Page 4 of 8 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

6. Evaluation of Preconstruction Field-Adhesion-Test Results: Sealants not evidencing adhesive


failure from testing, in the absence of other indications of noncompliance with requirements, will
be considered satisfactory. Do not use sealants that fail to adhere to joint substrates during testing.
G. Mockups: Install sealant in mockups of assemblies specified in other Sections that are indicated to
receive joint sealants specified in this Section. Use materials and installation methods specified in this
Section.

1.8 DELIVERY, STORAGE AND HANDLING


A. Deliver materials to Project in original unopened containers or bundles with labels indicating
manufacturer, product name and designation, colour, expiration date, pot life, curing time, and mixing
instructions for multi-component materials.
B. Store and handle materials in compliance with manufacturer's written instructions to prevent their
deterioration or damage due to moisture, high or low temperatures, contaminants, or other causes.

1.9 PROJECT CONDITIONS


A. Environmental Limitations: Do not proceed with installation of joint sealants under the following
conditions:
1. When ambient and substrate temperature conditions are outside limits permitted by joint sealant
manufacturer.
2. When joint substrates are wet.
B. Joint Width Conditions: Do not proceed with installation of joint sealants where joint widths are less
than those allowed by joint sealant manufacturer for applications indicated.
C. Joint Substrate Conditions: Do not proceed with installation of joint sealants until contaminants capable
of interfering with adhesion are removed from joint substrates.

1.10 WARRANTY
A. Special Warranty: Written warranty, signed by Contractor agreeing to repair or replace joint sealants
that do not comply with performance and other requirements specified in this Section within specified
warranty period.
B. Warranty Period: Five (5) years from the date of Taking Over.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS


A. Refer approved List of Manufacturers

2.2 MATERIALS, GENERAL


A. Compatibility: Provide joint sealants, backings, and other related materials that are compatible with one
another and with joint substrates under conditions of service and application, as demonstrated by sealant
manufacturer based on testing and field experience.
B. Colours of Exposed Joint Sealants: To match adjacent surfaces and as per benchmark installations.
C. Elastomeric Sealant Standard: Comply with ASTM C 920 and other requirements indicated for each
liquid-applied chemically curing sealant.
D. Stain-Test-Response Characteristics: For sealants to be non-staining to porous substrates such as
marble, limestone, granite etc., provide products that have undergone testing according to ASTM C
1248 and have not stained porous joint substrates indicated for Project.
E. Continuous-Immersion-Test-Response Characteristics: Where elastomeric sealants will be immersed
continuously in water, provide products that have undergone testing according to ASTM C 1247.

Section 07 92 00 Joint Sealants Page 5 of 8 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

F. VOC Content of Interior Sealants: Provide sealants and sealant primers for use inside the
weatherproofing system that complies with the following limits for VOC content when calculated
according to 40 CFR 59, Part 59, Sub part D (EPA Method 24):
1. Architectural Sealants: 250 g/L.
2. Sealant Primers for Nonporous Substrates: 250 g/L.
3. Sealant Primers for Porous Substrates: 775 g/L.

2.3 ELASTOMERIC JOINT SEALANTS


A. Silicone sealant: One part, non-sag, silicone sealant; capable of +50% movement as measured in
compliance with ASTM C 719; ASTM C920, Type S, Grade NS, Class 25, use 'O' related to the joint
substrate for vertical joints.
B. Mildew Resistant Silicone Sealant: One part, non-sag, elastomeric silicone sealant formulated with
fungicide for mildew resistance; ASTM C920, Type S, Grade NS, Class 25, for use around plumbing
fixtures and ceramic tile joints in wet areas and countertops to walls.
C. Two-component, urethane - based elastomeric sealant, self-levelling, capable of +25% movement as
measured in compliance with ASTM C719, ASTM C920, Type M, Grade P, Class 25, use T. for use in
typical exterior and interior horizontal traffic joints.
D. Single component, urethane elastomeric sealant, capable of +25% movement as measured in
compliance with ASTM C719, ASTM C920, Type S, Grade NS, Class 25, use T for use in exterior
traffic joints where slopes occur.

2.4 LATEX JOINT-SEALANT


A. Latex Sealant: One part non-sag, mildew resistant, acrylic-emulsion sealant complying with ASTM
C834, formulated to be paintable and recommended for exposed applications on interior locations
involving the joint movement of not more than plus or minus 5%.

2.5 ACOUSTICAL JOINT SEALANTS


A. Acoustical Sealant where indicated on the Drawings: Provide manufacturer's standard non-sag,
paintable, non-staining latex sealant complying with ASTM C 834 and the following:
1. The product effectively reduces airborne sound transmission through perimeter joints and
openings in building construction as demonstrated by testing representative assemblies according
to ASTM E 90.

2.6 JOINT-SEALANT BACKING


A. General: Provide sealant backings of material and type that are non-staining; are compatible with joint
substrates, sealants, primers, and other joint fillers; and are approved for applications indicated by
sealant manufacturer based on field experience and laboratory testing.
B. Cylindrical Sealant Backings: ASTM C 1330, of size and density to control sealant depth and
otherwise contribute to producing optimum sealant performance.
C. Elastomeric Tubing Sealant Backings: Neoprene, butyl, EPDM, or silicone tubing complying with
ASTM D 1056, nonabsorbent to water and gas, and capable of remaining resilient at temperatures down
to minus 26ºF (minus 32ºC). Provide products with low compression set and of size and shape to
provide a secondary seal, to control sealant depth, and otherwise contribute to optimum sealant
performance.
D. Bond-Breaker Tape: Polyethylene tape or other plastic tape recommended by sealant manufacturer for
preventing sealant from adhering to rigid, inflexible joint-filler materials or joint surfaces at the back of
joint where such adhesion would result in sealant failure. Provide self-adhesive tape where applicable.

Section 07 92 00 Joint Sealants Page 6 of 8 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

2.7 MISCELLANEOUS MATERIALS


A. Primer: Material recommended by joint sealant manufacturer where required for adhesion of the sealant
to joint substrates indicated, as determined from preconstruction joint-sealant-substrate tests and field
tests.
B. Cleaners for Nonporous Surfaces: Chemical cleaners acceptable to manufacturers of sealants and
sealant backing materials, free of oily residues or other substances capable of staining or harming joint
substrates and adjacent nonporous surfaces in any way, and formulated to promote optimum adhesion
of sealants with joint substrates.
C. Masking Tape: Non-staining, nonabsorbent material compatible with joint sealants and surfaces
adjacent to joints.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Examine joints indicated to receive joint sealants, with Installer present, for compliance with
requirements for joint configuration, installation tolerances, and other conditions affecting joint-sealant
performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
C. Surface Cleaning of Joints: Clean out joints immediately before installing joint sealants to comply with
joint sealant manufacturer's written instructions and the following requirements:

3.2 PREPARATION
A. Remove all foreign material from joint substrates that could interfere with adhesion of joint sealant,
including dust, paints (except for permanent, protective coatings tested and approved for sealant
adhesion and compatibility by sealant manufacturer), old joint sealants, oil, grease, waterproofing,
water repellents, water and surface dirt.
B. Clean porous joint substrate surfaces like concrete, masonry, unglazed surfaces of ceramic tiles etc. by
brushing, grinding, blast cleaning, mechanical abrading, or a combination of these methods to produce a
clean, sound substrate capable of developing the optimum bond with joint sealants.
C. Remove loose particles remaining from above cleaning operations by vacuuming or blowing out joints
with oil-free compressed air.
D. Remove laitance and form-release agents from concrete.
E. Clean, nonporous surfaces like metal, glass, porcelain enamel, glazed surfaces of ceramic tile etc. with
chemical cleaners or other means that do not stain, harm substrates, or leave residues capable of
interfering with adhesion of joint sealants.
F. Joint Priming: Prime joint substrates where recommended in writing by joint sealant manufacturer,
based on preconstruction joint-sealant-substrate tests or prior experience. Apply primer to comply with
joint sealant manufacturer's written instructions. Confine primers to areas of joint-sealant bond; do not
allow spillage or migration onto adjoining surfaces.
G. Masking Tape: Use masking tape where required to prevent contact of sealant with adjoining surfaces
that otherwise would be permanently stained or damaged by such contact or by cleaning methods
required to remove sealant smears. Remove tape immediately after tooling without disturbing joint
seal.

3.3 INSTALLATION OF JOINT SEALANTS


A. General: Comply with joint sealant manufacturer's written installation instructions for products and
applications indicated unless more stringent requirements apply.
B. Sealant Installation Standard: Comply with recommendations of ASTM C 1193 for the use of joint
sealants as applicable to materials, applications, and conditions indicated.

Section 07 92 00 Joint Sealants Page 7 of 8 Rev. 03 – Dec. 2023


100% Design Development - Revised
LAHEQ ISLAND PROGRAM 02 - COMMUNITY VILLAS
KINGDOM OF SAUDI ARABIA

C. Acoustical Sealant Application Standard: Comply with recommendations of ASTM C 919 for the use of
joint sealants in acoustical applications as applicable to materials, applications, and conditions
indicated.
D. Install sealant backings of the type indicated or required to support sealants during application and at
the position required to produce cross-sectional shapes and depths of installed sealants relative to joint
widths that allow optimum sealant movement capability.
1. Do not leave gaps between ends of sealant backings.
2. Do not stretch, twist, puncture, or tear sealant backings.
3. Remove absorbent sealant backings that have become wet before sealant application and replace
them with dry materials.
E. Install bond-breaker tape behind sealants where sealant backings are not used between sealants and
back of joints.
F. Install sealants by proven techniques to comply with the following and at the same time backings are
installed:
1. Place sealants so they directly contact and fully wet joint substrates.
2. Completely fill recesses provided for each joint configuration.
3. Produce a uniform, cross-sectional shapes and depths relative to joint widths that allow optimum
sealant movement capability.
G. Tooling of Non-sag Sealants: Immediately after sealant application and before skinning or curing
begins, tool sealants according to requirements specified below to form smooth, uniform beads of
H. Configuration indicated; to eliminate air pockets, and to ensure contact and adhesion of sealant with
sides of joint.
1. Remove excess sealants from surfaces adjacent to joint.
2. Use tooling agents that are approved in writing by sealant manufacturer and that do not discolour
sealants or adjacent surfaces.
3. Provide concave joint configuration per Figure 5A in ASTM C 1193, unless otherwise indicated.
4. Provide flush joint configuration, per Figure 5B in ASTM C 1193, where indicated.
5. Provide recessed joint configuration, per Figure 5C in ASTM C 1193, of recess depth and at
locations indicated.
a. Use masking tape to protect adjacent surfaces of recessed tooled joints.

3.4 FIELD QUALITY CONTROL


A. Inspect joints for complete fill, for the absence of voids, and for joint configuration. Any sealant found
out of plumb or cracking or any work otherwise defective shall be taken out and replaced to the
complete satisfaction of the Engineer, at no additional cost to the Project.

3.5 CLEANING
A. Clean off excess sealants or sealant smears adjacent to joints as the Work progresses by methods and
with cleaning materials approved in writing by manufacturers of joint sealants and of products in which
joints occur.

3.6 PROTECTION
A. Protect joint sealants during and after curing period of contact with contaminating substances and from
damage resulting from construction operations or other causes, so sealants are without deterioration or
damage at the time of Taking Over. If, despite such protection, damage or deterioration occurs, cut out
and remove damaged or deteriorated joint sealants immediately, so installations with repaired areas are
indistinguishable from the original work.
END OF SECTION

Section 07 92 00 Joint Sealants Page 8 of 8 Rev. 03 – Dec. 2023


100% Design Development - Revised

You might also like