104 08655 440 DSH e 004 - 1
104 08655 440 DSH e 004 - 1
104 08655 440 DSH e 004 - 1
10 CON TR-204
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
0000 GENERAL
0001 Supplier -----
0002 Manufacturer -----
0003 Location of assembly plant -----
2000 STANDARDS
Equipment, materials, components, and functions shall be designed, built,
rated, tested, and shall perform in accordance with the latest standards:
2001 UL 508 YES
2002 UL 845 YES
In addition to the above, applicable requiremets of the standards published by
the following organizations shall apply:
2003 ANSI American National Standards Institute YES
2004 ASME American Society of Mechanical Engineers YES
2005 ASTM American Society for Testing and Materials YES
2006 AWS American Welding Society YES
2007 IEEE Institute of Electrical and Electronics Engineers YES
2008 NEMA National Electrical Manufacturers Association YES
2009 UL Underwriters Laboratories YES
4000 ENCLOSURE
4001 NEMA 12, gasketed YES
4002 90 inch high (nominal)rigid free standing steel structure for indoor service. YES
4003 20 or 24 inch (nominal) wide vertical section with full height vertical wireway YES
equipped with independent hinged doors.
4004 Oversized vertical sections and sections without vertical wireways may be
furnished to accommodate oversize
4005 Enclosures and housings shall be designed to be bolted to their foundations YES
for all service conditions.Bottom plates for NEMA 1 or 2
4006 Lifting angles YES
4007 Base channels with rodent barriers YES
Pagina 1 de 9
4-08655-440-DSH-E-004-Rev1
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
4008 NEMA 3R enclosure housing With vent fans
4009 Factory pre-assembled NEMA 3R enclosure housing
4010 Walk-in housing
4011 Walk-through housing
6000 VOLTAGE
6001 Rated Nominal Voltage for Insulation: 600 VAC
6002 Nominal Operating Voltage: wye 3-phase, 3 wire, solidly grounded 480 VAC
6003 Control Power Supply for MCC interior circuits, Nominal Voltage 24V DC
6004 Control Power Supply Single / Dual Redundant 1
6005 Control Power Supply for field circuits 24V DC / 120V AC 120 VAC
6006 Space Heaters Power supply 120V AC YES
Pagina 2 de 9
4-08655-440-DSH-E-004-Rev1
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
9006 Manual Operator
9007 Manual Operator with Shunt Trip YES
9008 Electric Operator
9009 Close Voltage
9010 Trip Voltage
9011 Solid State Trip
9012 Programmable Solid State Trip YES
9013 Fixed Lone Time Trip
9014 Adjustable Long Time Trip YES
9015 Adjustable Long Time Trip Delay YES
9016 Adjustable Short Time Trip YES
9017 Adjustable Short Time Trip Delay YES
9018 Adjustable Instantaneous Trip YES
9019 Adjustable Ground Fault Trip YES
9020 Adjustable Ground Fault Trip Delay YES
9021 Automatic Trip Alarm Contact
9022 Overload Alarm Contact
9023 Time Trip Alarm Contact
9024 Instantaneous Trip Alarm Contact
9025 Ground Fault Trip Alarm Contact
9026 Undervoltage Trip
9027 Time Delay Undervoltage Trip
9028 N.O.Auxiliarv Contacts 2
9029 N.C. Auxiliary Contacts 2
9030 Key Interlock
9031 Control Switch & indicating Lights
9032 Control Power Source(s) :
Pagina 3 de 9
4-08655-440-DSH-E-004-Rev1
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
10006 Material
a. silver plated copper
b. tin plated copper YES
c. tin plated aluminum
10007 Horizontal Main Bus uninsulated
10008 Vertical Bus
a. bus to unit compartment isolation
b. automatic shutters YES
c. phase to phase (labyrinth) bus insulation YES
13000 ARRANGEMENT
13001 13-16 inches deep, front mounting only
13002 20-21 inches deep, front mounting only YES
13003 20-21 inches deep, back to back mounting
13004 with 4" wide vertical wireways YES
13005 with 8" wide vertical wireways
13006 Type C Terminal Board Mounting
a. Top
b. Bottom
13007 Selected by Seller
13008 Selected by Buyer(Seller must furnish firm space requirements for all
YES
components with proposal)
13009 Outgoing Motor / Load Feeder Cables (Top or Bottom) Bottom
Pagina 4 de 9
4-08655-440-DSH-E-004-Rev1
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
16000 NEMA CLASS AND WIRING TYPE
16001 Class I X
16002 Class II
16003 Type A
16004 Type B YES
16005 Type C
Pagina 5 de 9
4-08655-440-DSH-E-004-Rev1
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
19015 Size 4 drawout or pull-apart
19016 Size 4 fixed
19017 Size 4 Cu wire
19018 Size 4 Al wire
19019 Size 5 fixed (And larger )
19020 Size 5 Cu wire (And larger)
19021 Size 5 Al wire (And larger)
Pagina 6 de 9
4-08655-440-DSH-E-004-Rev1
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
f. solid state trip for breakers larger than 400 A
g. ground fault trip: all starters larger than size 2
h. interlock to prevent installation or removal of unit with disconnect
closed when applicable
i. ground fault trip: all starter size
24002 Contactor N/A
a. Adjustable magnetic trip only circuit breaker
b. adjustable magnetic trip only circuit breaker with current limiting fuses
c. thermal magnetic trip circuit breaker
d. thermal magnetic trip circuit breaker with current limiting fuses
e. current limiting thermal magnetic trip circuit breaker
f. solid state trip for breakers larger than 400 A
g. ground fault trip: all contactorss larger than size 2
h. ground fault trip: all feeders size
24003 Feeder (Including Inverters) YES
a. Adjustable magnetic trip only circuit breaker
b. adjustable magnetic trip only circuit breaker with current limiting fuses
c. thermal magnetic trip circuit breaker YES
d. thermal magnetic trip circuit breaker with current limiting fuses
e. current limiting thermal magnetic trip circuit breaker
f. solid state trip for breakers larger than 400 A YES
g. ground fault trip: all feeders larger than 50 A
h. ground fault trip: all feeders size X
Pagina 7 de 9
4-08655-440-DSH-E-004-Rev1
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
27000 INTERPOSING RELAYS N/A
27001 for each externally controlled contactor larger than size 3 (see Schematic
Diagrams)
27002 for each inverter
27003 for each solid state controller
30000 NAMEPLATES
30001 manufacturer' standard X
30002 white letters with black background engraved lamicoid plastic
30003 black letters with white background engraved lamicoid plastic X
Pagina 8 de 9
4-08655-440-DSH-E-004-Rev1
104-08655-440-DSH-E-004
CENTRO DE CONTROL DE MOTORES EN BAJA TENSIÓN
LOW VOLTAGE MOTOR CONTROL CENTER
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
31003 DSA Communication (Module I/O) - MODEL
31004 In the event of loss communication, one contact of output of the DSA module
must closed to permit the operation of motors locally.
32000 MISCELLANEOUS
32001 provide maintenance releases for the disconnect/door interlocks X
32002 Size 5 and 6 contactors shall be vacuum-break contactors X
32003 lugs or terminals shall be provided for all external connections X
32004 each electrically operated circuit breaker shall be wired for remote control X
1 08-Sep-10 Emitido para Compra, con modificaciones indicadas A. Calle E. J. Calle D. Rivero Antamina S.A.
0 05-Ago-10 Emitido para Compra A. Calle E. J. Calle D. Rivero Antamina S.A.
B 03-Jun-10 Emitido para Aprobación de Antamina A. Calle E. J. Calle D. Rivero Antamina S.A.
A 21-May-10 Emitido para Coordinación Interna A. Calle E. J. Calle D. Rivero Antamina S.A.
REV DATE REASON FOR REVISION BY CHECK APPROVED CLIENT
Pagina 9 de 9
4-08655-440-DSH-E-004-Rev1