Approval Sheet Specifications of Hermetic Scroll Compressor
Approval Sheet Specifications of Hermetic Scroll Compressor
Approval Sheet Specifications of Hermetic Scroll Compressor
: C-SC753H8K-00-GGS-0
APPROVAL SHEET
SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR
△
△
△
△
△
NO. DATE PAGE REVISION DETAILS PAPCDL SIGNED CLIENT SIGNED
REVISION RECORD
USER: MANUFACTURER:
Panasonic Appliances Compressor (Dalian) Co., Ltd.
PURCHASING TECHNICAL
LEADER APPROVED CHECKED DRAFTED
MANAGER MANAGER
1
Model: C-SC753H8K
File No: C-SC753H8K-00-GGS-0
Section 1. General Specifications
Content Unit Specification
Compressor Model (Code) — C-SC753H8K (809 203 88)
Type — Hermetic Scroll Compressor
Application — High Back Pressure
Evap. Temp. Range °C (°F) -15~12 (5~54)
Compressor Cooling Type — Natural Cooling
Phase — 3
Power Source Rated Voltage V 380-415/440-460
Rated Frequency Hz 50/60
Voltage Range V 342~456/396~506
Weight (Including Oil) kg (lb) 69.5(153.2)
Refrigerant — R22
Oil Type — Mineral Oil(SAY56T or Equivalent)
Oil Charge ml (fl oz) 2800 (94.7)
3 3
Displacement cm (in ) /rev 171.2(10.4)
Motor Type — 3-PH Induction Motor
Number of Poles — 2
Electrical Insulation Class E
Nominal Revolution min-1 —
Motor
Locked Rotor Ampere A 96/101
U-V 1.308
Winding Resistance
Ω U-W 1.373
[at 25°C (77°F)]
V-W 1.351
Suction Line (O.D.) mm (in) 25.4 (1.000)
Connection Tube
Discharge Line (O.D.) mm (in) 19.05 (0.750)
Compressor Surface Paint — Black Paint
Notes
1 Voltage range is applied at standard rating conditions.
2 Motor specifications in the table are the average values for your reference.
3 ( ): All units with parentheses are reference values.
Expiration of Specification
Expiration of this specification shall be effected until issuing a notice with indication of the expiration date from the
issued date . In case of improvement or elimination of this specification , it shall be handled by the revision record
based on agreement between both sides.
2
Model: C-SC753H8K
File No: C-SC753H8K-00-GGS-0
2.1 Performance
Hz 50 60 Remark
Power Source (3PH)
V 380 440
W 30,600 36,900 ±5%
Capacity
(BTU/hr) 104,407 125,903 reference
Input Power W 9,050 11,100 ±5%
Current A 15.40 16.10 ±5%
Standard Rating Conditions
Condensing Temp. °C (°F) 54.4(130)
Evaporating Temp. °C (°F) 7.2( 45 )
Suction Gas Temp. °C (°F) 18.3( 65 )
Liquid Temp. °C (°F) 46.1(115)
Ambient Temp. °C (°F) 35.0( 95 )
MP 427.7
2.2 Sound Level
Hz 50 60
Power Source (3PH)
V 380 440
Sound Level dB(A) 72Max. 74Max.
Notes
1 The operating conditions are the same as 2.1.
2 MIC location is the distance of 1m (3.28feet) from the compressor.
3 Sound Level is an average sound pressure level in four directions.
Conditions
Compressor Temp. °C (°F) 10~60(50~140)
Ambient Temp. °C (°F) 10~40(50~105)
High Pressure MPa(G)/psig 2.0(290)
Low Pressure MPa(G)/psig 0.5(72)
2.4 Others
Content Unit Specification
L.P. S. MPa(G)/psig 1.6(232)
Design Pressure
H. P. S. MPa(G)/psig 3.0(435)
Insulation Resistance MΩ 100 (without refrigerant)
Dielectric Strength V 2400 (1 second)
Residual Moisture mg 500
Note:
1. The insulation resistance be measured with a DC500V megohm tester.
3
Model: C-SC753H8K
File No: C-SC753H8K-00-GGS-0
Section 3. Standard Accessories
3.1 Accessories List
4
Model: C-SC753H8K
File No: C-SC753H8K-00-GGS-0
FOR LIQUID
REFRIGERANT
CHARGING
CAPILLARY
LIQUID LINE
SERVICE
OUTDOOR VALVE
INDOOR
HEAT HEAT
EXCHANGER EXCHANGER
GAS LINE
REVERSING SERVICE VALVE
VALVE
LOW
PRESSURE
SWITCH
COMPRESSOR CRANKCASE
HEATER
5
Section 5. Operating Envelope
70 Transient Operation
60
Condensing Temperature(℃)
50
Normal Operation
40
30
20
10
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Evaporating Temperature(℃)
6
Section 6. Application Standard & Limit
Voltage at compressor
9 Running Voltage Within ±10% of the rated voltage
terminals.
Voltage at compressor
Three Phase Models: 85% of the rated voltage min.
10 Starting Voltage terminals.
Single Phase Models: 90% of the rated voltage min.
On Period: Until the oil level returns to the center of the lower bearing For at least 7 minutes -
11 On/Off Cycling on/3 minutes-off is
Off Period: Until balance of high and low pressure is obtained recommendable.
Abnormal Pressure Pressure Rise: 3.0MPa(G) (435psig) Max. By high pressure switch
15
Rise/Drop Pressure Drop: 0.03MPa(G) (4.35psig) Min. By low pressure switch
System Moisture
16 200ppm Max.
Level
System 1 Vol.% Max. 24 hrs. after vacuuming:
17 Uncondensable Gas
Residual Oxygen 0.1 Vol.% Max. 1.01kPa Max.
Level
18 Tilt 5。Deg.Max.
Operation beyond the above limits must be approved by Panasonic Appliances Compressor (Dalian) Co., Ltd.
7
Notes
1 Installation should be completed within 15 minutes after removing the rubber plugs.
4 Evacuation and Refrigerant charge : Evacuate internal section in the refrigeration system from high and low pressure
sides and charge liquid refrigerant from condenser outlet side. Additional charge shall be done with gas condition from
low side.
7 Crankcase heater is required when the oil sump temperature is too low to meet the requirement of item 6 on page7.
8 Voltage fluctuation between compressor terminals, during operation, shall be within 2% of the rated voltage.
8
Section 7. Selection of Electrical Wire
Voltage drop may occur due to the large current draw during compressor starting.
We recommend selecting the wire size from the table below.
③
terminal plate compressor
indoor
outdoor
power ① ② ③
terminal
source indoor plate
compressor
5m max. 10m max. 15m max. 20m max. 30m max. 50m max. 1m max.
20max. 2.0 2.0 2.0 3.5 5.5 8.0 2.0
30max. ↑ ↑ 3.5 5.5 ↑ 14.0 ↑
40max. ↑ 3.5 5.5 ↑ 8.0 ↑ ↑
50max. ↑ ↑ ↑ 8.0 14.0 22.0 ↑
60max. ↑ 5.5 ↑ ↑ ↑ ↑ ↑
70max. 3.5 ↑ 8.0 14.0 ↑ ↑ 3.5
80max. ↑ ↑ ↑ ↑ 22.0 30.0 ↑
90max. ↑ ↑ 14.0 ↑ ↑ ↑ ↑
100max. ↑ 8.0 ↑ ↑ ↑ 38.0 ↑
110max. ↑ ↑ ↑ ↑ ↑ ↑ ↑
120max. 5.5 ↑ ↑ 22.0 30.0 ↑ ↑
140max. ↑ 14.0 ↑ ↑ ↑ 50.0 5.5
160max. ↑ ↑ 22.0 ↑ ↑ ↑ ↑
180max. ↑ ↑ ↑ ↑ 38.0 60.0 8.0
200max. 8.0 ↑ ↑ 30.0 ↑ ↑ ↑
220max. ↑ ↑ ↑ ↑ 50.0 80.0 ↑
240max. ↑ ↑ ↑ ↑ ↑ ↑ 14.0
7.3 Caution of Ground
The internal motor protector does not protect the compressor against all possible conditions.
Please be sure that the system utilizes the ground connection when installed in the field.
9
COMP. CODE A B C D E
809 28* 8*
809 18* 8* 538 284 486 7.9 289
809 29* 8* [21.18] [11.18] [19.13] [0.31] [11.38]
809 19* 8*
809 20* 8*
809 10* 8*
809 22* 8* 553 299 501 9 304
809 12* 8* [21.77] [11.77] [19.21] [0.35] [11.97]
C-SCP270,315,
360,400
77.2
U W
68.2
TAPPING SCREWS M4
TERMINAL
Part Code
D-0104-DSC
Name
Compressor Outline Drawing
10
No. Part QTY Name
1 M-0101-DSC 4 Mounting Grommet
2 M-0202-DSC 4 Mounting Sleeve
11
Part Code
M-5102-DSC
Name
Mounting Parts Listing
`
Compressor Code A
80928*8*
682
80918*8*
[26.850]
80929*8*
80920*8*
80910*8* 697
80922*8* [27.441]
80912*8*
12
Part Code
D-0201-DSC
Name
Packing Dimensions
SWITCH
DISCHARGE GAS
V TEMP. SENSOR
POWER SUPPLY
50Hz 380~415V INTERNAL
PROTECTOR
R
U W
S
T
COMPRESSOR
TERMINAL MAGNETIC SWITCH
A 14
13
B 11
POWER SUPPLY C 12
50Hz 220V
REVERSAL
DEFENSIBLE RELAY
CRANKCASE HEATER
Part Code
E-0910-DSC
Name
Wiring Diagram