Nothing Special   »   [go: up one dir, main page]

MPPT 100 600 and MPPT 80 600 Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

MPPT PV Optimization

600 Vdc Solar Charge Controllers


6 kW MPPT 100 600 (Part Number 865-1034)
4.8 kW MPPT 80 600 (Part Number 865-1032)

The MPPT 80 and MPPT 100 600 Vdc Solar Charge Controllers optimize the power from
PV arrays for DC coupled solar and storage installations, with easy, flexible installation.

Optimum System Performance Compatible with Insight


• High power, 600 Vdc MPPT PV optimization and battery charge Energy Management
control
• Setup and configuration
• Flexibility for oversized PV array power ratings up to 8.5 kW with the
MPPT 100 or 6.8 kW with the MPPT 80 • Remote monitoring & control with
advanced data security
• High efficiency from PV to battery to grid, ideal for the self-
consumption of solar energy • Web and mobile app
• Black start batteries from solar, providing maximum energy resilience • Multi-site management for installers
for longer duration grid outages
• Harvest more energy with shade tolerant fast sweep MPPT algorithm

Flexible
• Flexible string sizing with a wide MPPT and PV operating voltage
range
• Compatible with XW Pro and SW series hybrid inverters for a
complete grid tied or off grid solar and storage solution

Easy to Install
• 2 string installations and smaller wire sizing with 600 Vdc PV arrays, Insight Energy Management
allowing faster, lower cost installations
• No need for a combiner box with DC breakers or fuses
• Easy to install PV disconnect and NEC 2017 compliant rapid
shutdown transmitter with the MPPT Disconnect RS accessory, solar.se.com
UL1741 PVRSS certified
MPPT 80 600 | MPPT 100 600 | 2

Technical Specifications
MPPT 80 600 MPPT 100 600
Electrical Specifications
Max PV array open circuit voltage 600 V 600 V
MPPT voltage range 195 to 510 VDC 195 to 510 VDC
PV array operating voltage 195 to 550 V 195 to 550 V
Max. array short circuit current at STC 28 A 35 A
Max. input operating current 23 A 29 A
Max. output power 4800 W (nominal 48 V systems) 6000 W (nominal 48 V systems)
Nominal battery voltage 24 and 48 VDC 24 and 48 VDC
Battery voltage operating range 16 to 67 VDC 16 to 67 VDC
Max. output charge current 80 A 100 A
Three‑stage (bulk, absorption, float) plus manual equalization
Charger regulation method
Two-stage (bulk, absorption) plus manual equalization
Supported battery types Flooded, GEL, AGM, Lithium-ion, Custom
Efficiency
Max. power conversion efficiency 95% (nominal 48 V), 92% (nominal 24 V)
General Specifications
Power consumption, night time <1W
Battery temperature sensor Included
Auxiliary output Dry contact switching up to 60 VDC, 30 VAC, 8 A
Enclosure material Enclosure material: Indoor, ventilated, aluminium sheet metal chassis
44.0 mm, 35.0 mm , 28.2 mm, and 22.2 mm knockouts for 1-1/4, 1, ¾, and ½ inch
Knockout dimensions
trade size fittings
IP degree of protection IP20
Product weight 13.5 kg (29.8 lb)
Shipping weight 20.4 kg (45 lb)
Product dimensions (H x W x D) 76.0 × 22.0 × 22.0 cm (30.0 × 8.6 × 8.6 in)
Shipping dimensions (H x W x D) 113.39 × 28.68 × 31.90 cm (44.64 × 11.29 × 12.56 in)
Ambient air temperature for operation -20 °C to 65 °C (-4 °F to 149 °F), power derating above 40 °C
Storage temperature range -40 °C to 85 °C (-40 °F to 185 °F)
Operating altitude Sea level to 2000 m (6562 ft)
System network and remote monitoring Available with Insight Energy Management
Please refer to our website, solar.se.com for the latest version of the warranty
Warranty
statement.
Part number 865-1032 865-1034
Regulatory Approvals
CSA certified (UL1741, CSA 107.1) and CE marked for the Low-voltage Directive
Safety
(EN50178)
FCC and Industry Canada (Class B), CE marked for the EMC Directive (EN61000-6-
EMC
1, -6-3)
Compatible Products List
XW Pro hybrid inverter XW Pro 6848 120/240 VAC (865-6848-21), XW Pro 8548 230 VAC 865-8548-55)
XW+ hybrid inverter XW+ 8548 230 VAC (865-8548-61)
SW IEC (230 VAC) SW 4024 230 VAC (865-4024-55), SW 4048 230 VAC (865-4048-55)
SW UL (120/240 VAC) SW 4024 120/240 VAC (865-4024-21), SW 4048 120/240 VAC (865-4048-21)
XW Power Distribution Panels 865-1015-01, 865-1014-01
XW Mini Power Distribution Panels 865-1013-01
MPPT Disconnect RS and RS initiator Switch 865-1036, 865-1039
Insight Energy Management InsightHome (865-0330), InsightFacility (865-0335), Insight
Conext Automatic Generator Start 865-1060-01
Conext Battery Monitor 865-1080-01

© 2022 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries
SAS or its affiliated companies. All information is preliminary and will need to be confirmed at the time of order.
DS20220511_MPPT 80 600 | MPPT 100 600.indd