AQT 250 Edit
AQT 250 Edit
AQT 250 Edit
com
Diesel Power Generation
Control System & Power Solutions
Output Rating:
PRIME: STANDBY:
Standard Specifications:
50 Hz—1500 Rpm 400 V, 3ph
225 kVA 180 kW 250 kVA 200 kW
1 PrimeRating: 60 Hz—1800 Rpm 480 V, 3ph
Unlimited hours usage, with an average
load factor of 80% over each 24 hour peri-
225 kVA 180 kW 250 kVA 200 kW
od. 10% overload is available for 1 hour in ENGINE SPECIFICATIONS
every 12 hours operation. Engine Make PERKINS
o overload is permitted on standby power. Engine Model 1206A-E70TTAG2
No. of Cylinders 6 vertical in-line
2 StandbyRating: Cycle 4 Stroke DI
Limited to 500 hours annual usage, with an Aspiration Turbocharged after cooled
average load factor of 80% of the pub- Cooling Method Water cooled
lished standby power rating over each 24 Governing Type Electronic
hour period. Up to 300 hours of annual Governing Class G2 - ISO 8528 Part 1
usage may be run continuously. Compression Ratio 16.1:1
No overload is permitted on standby pow- Displacement 8.8 L
er. Bore/Stroke 112 x 149 mm
Dynamic Charging Alternator 45AMP, 24V
3 Engine:
Perkins, including air filters, fuel filters,
ALTERNATOR SPECIFICATIONS
Alternator Make Leroy Somer | STAMFORD | AQT
oil filter, starting motor and charging alter-
nator etc. Alternator Model TAL-046-C
Number of Poles 4
4Alternator Type: Number of Winding Leads 6
brushless AC alternator Type of Bearing Single Bearing
Insulation Class - Temp Rise Cont. H - 125/40 C
5 Radiator: Ingress Protection Rating IP 23
50°C, fan protective shroud Excitation System Self Excited
AVR Model R150
www.aqtgenerators.com | info@aqtgenerators.Com | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Standard Specifications:
Control System:
6– Fuel Tank:
Large back-lit text display Fuel and start outputs, configurable when
Multiple display languages using CAN
Capacity of fuel tank is for 8 hours 4 configurable DC outputs
DSENet® expansion compatible
running Data logging facility 4 configurable analogue/digital inputs
Built in fuel tank up to 800 kVA Fully configurable via PC using USB com- Automatically transfers between mains
munication (utility) and generator
Front panel configuration (DSE6120 MKII only)
7- Circuit Breaker: Efficient power save mode Increased input and output expansion
3 phase generator sensing capability via DSENet®
Accumulated power monitoring IP65 rating (with optional gasket) offers
3 pole LS MCCB (kW h, kVA h, kVAr h) increased resistance to water ingress
Generator/load current monitoring and
8– Control system alarms: protection DIGITAL INPUTS
Generator overload protection (kW) ANALOGUE INPUT
Breaker control via fascia buttons
•Over and Under Speed
•Low and High Battery Volt.
•Start and Stop Failure
•Over Current
•Under / Over Generator Voltage DSE6120 MKII
•Low Oil Pressure AUTO START & AUTO MAINS
•Emergency stop FAILURE CONTROL
•High engine temperature
9– Warranty policy:
www.aqtgenerators.com | info@aqtgenerators.Com | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Engine: Optional configurations:
Engine accessories:
⦁ Heavy-duty air filter
⦁ Coolant heater
⦁ Lubricant oil heater
⦁ Fuel and Water Separator
⦁ Lube oil rotary pump
Cooling System:
⦁ 55 degree Radiator
⦁ Remote Radiator
Control System:
⦁ AMF
Perkins heavy duty high performance industrial type diesel engine.
⦁ Parallel
⦁ Practical type in low temperature environment
COOLING SYSTEM ⦁ Control Screen Heater
Total Coolant Capacity (L) 29.6 L ⦁ Remote Annunciators
Cooling Fan Air Flow 370 m3/ min ⦁ Other(Comp, DEIF)
Radiator Fan Load 5 kW
Circuit Breaker:
Heat Radiation to Room (PRP) 13.2 kW
⦁ 3/4 poles
Heat Radiation to Room (ESP) 13.9 kW ⦁ Fixed/handcart type
LUBRICATION SYSTEM ⦁ Electric mechanism
Oil Filter Type Spin-On Full Flow
Automatic Transfer Switch (ATS):
Total Oil Capacity 41 L ⦁ ATS cabinet
Oil Type API-CH-4 or ACEA E5 ⦁ Contractor type ATS
EXHAUST SYSTEM ⦁ Motorized changeover type ATS
www.aqtgenerators.com | info@aqtgenerators.Com | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703