Contactor, 3 pole, 380 V 400 V 18.5 kW, 110 V 50 Hz, 120 V 60 Hz, AC
operation, Screw terminals
380 V 400 V Ie A 40
AC-1
Open
at 40 °C Ith =Ie A 60
enclosed Ith A 45
660 V 690 V P kW 23
AC-4
220 V 230 V P kW 5
380 V 400 V P kW 9
660 V 690 V P kW 12
Contact sequence
Connection to SmartWire-DT no
Frame size 3
Lifespan, mechanical
AC operated Operations x 10
6 10
Ambient temperature
Enclosed °C - 25 - 40
Storage °C - 40 - 80
Mounting position
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Weight
AC operated kg 0.872
Solid mm
2 1 x (0.75 - 16)
2 x (0.75 - 16)
Stranded mm
2 1 x (16 - 50)
2 x (16 - 35)
Stripping length mm 14
Terminal screw M6
Tool
Stripping length mm 10
Tool
Up to 690 V A 560
Breaking capacity
500 V A 400
Short-circuit rating
Open
at 40 °C Ith =Ie A 60
at 50 °C Ith =Ie A 57
at 55 °C Ith =Ie A 55
at 60 °C Ith =Ie A 50
enclosed Ith A 45
AC-3
Open, 3-pole: 50 – 60 Hz
220 V 230 V Ie A 40
240 V Ie A 40
380 V 400 V Ie A 40
440V Ie A 40
500 V Ie A 40
660 V 690 V Ie A 25
240V P kW 13.5
415 V P kW 24
440 V P kW 25
500 V P kW 28
660 V 690 V P kW 23
AC-4
Open, 3-pole: 50 – 60 Hz
220 V 230 V Ie A 18
240 V Ie A 18
380 V 400 V Ie A 18
415 V Ie A 18
440 V Ie A 18
500 V Ie A 18
660 V 690 V Ie A 14
220 V 230 V P kW 5
240 V P kW 5.5
380 V 400 V P kW 9
415 V P kW 9.5
440 V P kW 10
500 V P kW 11
660 V 690 V P kW 12
DC
Rated operational current, open
DC-1
60 V Ie A 50
110 V Ie A 50
220 V Ie A 45
50 Hz Pick-up VA 149
50 Hz Sealing VA 16
50 Hz Sealing W 4.1
60 Hz Pick-up VA 178
60 Hz Sealing VA 19
60 Hz Sealing W 4.1
Main contacts
AC operated
Opening delay ms 8 - 13
Arcing time ms 10
Electromagnetic compatibility (EMC)
Emitted interference to EN 60947-1
Three-phase
200 V HP 10
208 V
230 V HP 15
240 V
460 V HP 30
480 V
575 V HP 40
600 V
Single-phase
115 V HP 3
120 V
230 V HP 7.5
240 V
General use A 63
Basic Rating
SCCR kA 10
max. CB A 250
SCCR (CB) kA 65
max. CB A 100
SCCR (CB) kA 30
max. CB A 250
Elevator Control
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching (ecl@ss10.0.1-27-37-10-03 [AAB718015])
Modular version No
Approvals
Product Standards IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking
Characteristics
1: Overload relay
2: Suppressor
3: Auxiliary contact modules
DILM40…DILM72
DILMC40…DILMC65
DILMF40…DILMF65