1.00 Operation, Maitenance & Trouble Shooting Manual
1.00 Operation, Maitenance & Trouble Shooting Manual
1.00 Operation, Maitenance & Trouble Shooting Manual
2
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Table of contents
3
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation...........................................................................................................34
5.1 ALARM Procedure..............................................................................................34
5.2 Procedure in case of Fault .................................................................................36
5.3 Switching off / Switching on................................................................................37
5.3.1 Switching a detector zone off / on.......................................................37
5.3.2 Switching a detector off / on................................................................39
5.3.3 Temporary switching-off......................................................................42
5.3.4 Switching off / on the remote transmission Fire..................................44
5.3.5 Switching off alarm activation .............................................................47
5.3.6 Switching off sabotage evaluation [DE] ..............................................48
5.4 Log in / Change access level .............................................................................49
5.5 Logging out from an access level.......................................................................49
5.6 Switching between 'Manned' / 'Unmanned' operation modes ............................50
5.7 Changing visibility...............................................................................................51
5.7.1 Deactivating standby...........................................................................51
5.7.2 Activating / deactivating expanded visibility........................................51
5.8 Main menu / Open menu item ............................................................................52
5.9 Executing commands - Basics ...........................................................................53
5.9.1 Executing commands - General..........................................................54
5.9.2 Executing commands - object-oriented...............................................55
5.9.3 Executing commands – function-oriented...........................................57
5.9.4 Hide command confirmation message................................................58
5.10 Selecting elements or events .............................................................................58
5.10.1 Select events.......................................................................................58
5.10.2 Selection in the topology.....................................................................60
5.10.3 Searching for elements .......................................................................61
5.11 Testing................................................................................................................64
5.11.1 Testing detectors.................................................................................64
5.11.2 Testing the installation ........................................................................65
5.11.3 Control test..........................................................................................65
5.12 Activation / Deactivation / Reset.........................................................................66
5.12.1 Activating an alarm indicator (AI) ........................................................67
5.12.2 Deactivating / Activating alarm devices ..............................................69
5.12.3 Activating / resetting zone...................................................................70
5.12.4 Activating / deactivating universal control ...........................................72
5.12.5 Activating evac controls ......................................................................74
5.13 Show information................................................................................................76
5.13.1 Polling alarm counters / remote transmissions ...................................76
5.14 Entering the configuration ..................................................................................77
5.15 Auto-configure station.........................................................................................77
5.16 Auto-configure line..............................................................................................78
5.17 Enabling / disabling Cerberus Remote...............................................................80
5.18 Connecting Cerberus Remote............................................................................81
5.19 Setting up Cerberus Remote link with integrated IP ..........................................82
5.20 Operating Cerberus Remote ..............................................................................83
5.21 Polling / Deleting the event memory...................................................................83
4
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5.22 Settings / Administration.....................................................................................84
5.22.1 Change language................................................................................84
5.22.2 PIN administration...............................................................................84
5.22.3 Testing indicators................................................................................86
5.22.4 Setting the buzzer volume ..................................................................86
5.22.5 Adjusting the display brightness .........................................................87
5.22.6 Setting time and date ..........................................................................87
5.23 Entering/Changing customer text.......................................................................88
5.24 Inserting printing paper.......................................................................................88
5.25 Switching off the printer......................................................................................91
5.26 Show version......................................................................................................91
6 System functions .............................................................................................92
6.1 Note on the configuration of the local fire detection installation.........................92
6.2 Operating condition ............................................................................................93
6.3 Operation modes................................................................................................93
6.3.1 Normal operation ................................................................................93
6.3.2 Test .....................................................................................................94
6.3.3 Isolation...............................................................................................95
6.3.4 Renovation..........................................................................................96
6.4 Access level and access rights ..........................................................................96
6.4.1 PIN input dialog...................................................................................97
6.4.2 Logout timeout ....................................................................................97
6.4.3 Cerberus Remote enabling .................................................................97
6.5 Visibility...............................................................................................................98
6.5.1 Standby visibility .................................................................................98
6.5.2 Expanded visibility ..............................................................................99
6.6 Sabotage ALARM [DE].......................................................................................99
7 List of all commands and required access levels ......................................100
7.1 'Switching on/off' command group ...................................................................100
7.2 Command zone 'Test'.......................................................................................101
7.3 'Activating/deactivating' command group .........................................................102
7.4 Command group 'Information' ..........................................................................103
7.5 'Configuration' command group .......................................................................103
7.6 'Maintenance' command group ........................................................................104
7.7 Other commands..............................................................................................105
8 List of elements ..............................................................................................106
5
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description ........................................................................................108
9.1 Overview...........................................................................................................108
9.2 Topology...........................................................................................................110
9.2.1 Hardware tree ...................................................................................111
9.2.2 Detection tree....................................................................................112
9.2.3 Control tree .......................................................................................116
9.2.4 Operating tree ...................................................................................117
9.2.5 Network tree......................................................................................120
9.2.6 Linking with the hardware tree ..........................................................121
9.2.7 Functional allocation .........................................................................122
9.3 Acquisition ........................................................................................................123
9.4 Evaluation.........................................................................................................124
9.5 Control ..............................................................................................................128
9.5.1 Universal control ...............................................................................129
9.5.2 Evacuation control.............................................................................130
9.5.3 Extinguishing control with sprinkler...................................................132
9.5.4 Extinguishing control with extinguishing control unit XC10 ..............133
9.6 Alarm verification concept (AVC) .....................................................................134
9.6.1 Attendance check..............................................................................135
9.6.2 Investigation time ..............................................................................135
9.6.3 Example of a verification process .....................................................135
9.6.4 Fire alarming .....................................................................................137
9.7 Intervention concept (IC) ..................................................................................138
9.7.1 Attendance check..............................................................................139
9.7.2 Intervention monitoring .....................................................................139
9.7.3 Example of an intervention process..................................................139
9.7.4 Intervention alarming.........................................................................141
9.8 Events...............................................................................................................142
9.8.1 Event categories ...............................................................................142
9.8.2 Event status identification .................................................................143
9.8.3 Event memory ...................................................................................144
9.8.4 Message summary............................................................................144
9.9 List representation and types of lists ................................................................145
9.9.1 Event lists..........................................................................................145
9.9.2 Element lists......................................................................................146
9.9.3 Selection lists ....................................................................................147
9.10 Version indication station / Configuration data.................................................147
10 Faults / Troubleshooting ...............................................................................148
11 System maintenance......................................................................................149
11.1 Maintenance recommendation .........................................................................149
11.2 Opening the control panel [DE] ........................................................................149
12 Glossary ..........................................................................................................150
Index ................................................................................................................156
6
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
About this document
1
Display indication in the document
Scope
This document applies to the fire control panels and the fire terminal of the type
Fx72x, market package MP3.0 XS.
Target groups
The information in this document is intended for the following target groups:
7
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
1 About this document
Display indication in the document
Document identification
Position Information
Title page Product type
Product designation
Document type
Footers Document ID
– ID_ModificationIndex_Language_COUNTRY
Edition date
Last page Document ID
Edition date
Manual (product line)
Register (table of contents for whole documentation, folder register)
The 'i' symbol identifies supplementary information and tips for an easier way of
working, for example.
Applicable documents
Document ID Title
008399 XC10 Extinguishing Control Panel, Technical Manual
A6V10210416 FS720 Fire Detection System, Commissioning / Maintenance /
Repair
A6V10210424 FS720 Fire Detection System, Configuration
A6V10217440 FS720 Fire Detection System, Inscription Strips
8
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
About this document
1
Display indication in the document
History of changes
The reference document's modification index applies to all languages into which
the reference document is translated.
The first edition of a language version or a country variant may for example have
the modification index "d" instead of "a" if the reference document already has this
modification index.
9
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
1 About this document
Display indication in the document
ABCDEFG LLLLLLL 30
ABCDEFG ABCDEFG ABCDEFG
AAAAAAA ABCDEFGHI EEEEEEE
(1) (5)
BBBBBBB ABCDEFGHI FFFFFFF
(2) (6)
CCCCCCC ABCDEFGHI GGGGGGG
(3) (7)
DDDDDDD ABCDEFGHI HHHHHHH
(4) (8)
ZZZ ABCDEFGHI ZZZ (5) ZZZ
ABCDEFGHI ABCDEFGHI ABCDEFGHI
Display with window and bar
The table representation has the following key deviations from the
original:
Font and representation (not inverted)
Windows are indicated separately without display background
No bars to indicate the position and list length
No frame around selection
10
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Safety
2
Safety notices
2 Safety
Battery Heat
11
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
2 Safety
Safety notices
Signal word
The signal word classifies the danger as defined in the following table:
Signal word Danger level
DANGER DANGER identifies a dangerous situation, which will result
directly in death or serious injury if you do not avoid this
situation.
WARNING WARNING identifies a dangerous situation, which may
result in death or serious injury if you do not avoid this
situation.
CAUTION CAUTION identifies a dangerous situation, which could
result in slight to moderately serious injury if you do not
avoid this situation.
WARNING
Nature and origin of the danger
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
12
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Safety
2
Safety regulations for the method of operation
Electrical installations
WARNING
Electrical voltage
Electric shock
Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
Lock volt-free areas to prevent them being switched back on again by mistake.
Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
Produce earthing as stated in local safety regulations.
13
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
2 Safety
Safety regulations for the method of operation
The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following
instructions must be observed:
– Use the correct potential for activation; this is generally the potential of the
building installation.
– Only check controls up to the interface (relay with blocking option).
– Make sure that only the controls to be tested are activated.
Inform people before testing the alarm control devices and allow for possible
panic responses.
Inform people about any noise or mist which may be produced.
Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
14
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Safety
2
Standards and directives complied with
Disclaimer
We have checked that the content of this document matches the hardware and
software described. Despite this, we cannot rule out deviations and cannot
therefore assume liability for them matching completely. The details in this
document are checked regularly and any corrections needed included in
subsequent editions.
WARNING
Limited or non-existent fire detection
Personal injury and damage to property in the event of a fire.
Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
NOTICE
Incorrect planning and/or configuration
Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
15
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
3 PMI
Release Notes
3 PMI
The following figure shows the PMI (fire control panel or fire terminal).
PMI Station
You can use inscription strips to inscribe the PMI. There is a template for this in
document A6V10217440.
16
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
PMI
3
Buttons on the PMI
<Silence buzzer>
Switches the 'Station' buzzer off.
<Acknowledge>
Acknowledges all events that can be acknowledged.
Confirms presence ('AVC', 'IC')
Switches the buzzer off
<Reset>
Resets all events that can be reset (password required).
17
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
3 PMI
Buttons on the PMI
<Premises manned>
Switches between 'Manned operation' and 'Unmanned operation' operation
modes (password required).
Opens the event list in case of a "mixed" condition (i.e., visibility on several
'Areas' with different 'Manned operation' and 'Unmanned operation' settings)
<Alarm device>
Deactivates the alarm devices in the event of alarm (password required).
Configurable buttons
The two buttons a and b in the figure above are configurable standard buttons.
You can, for example, configure these two buttons with the following functions:
'Poll RT counter'
'Non-MCP zones OFF'
3.1.3 Softkeys
The figure below shows the part of the PMI including the softkeys.
1 2 3
1 Softkey 1 3 Softkey 3
2 Softkey 2
Softkeys are buttons which you can use to carry out functions that are displayed in
the three fields of the softkey line on the display. These three black fields contain
the names of the functions in white font.
18
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
PMI
3
Buttons on the PMI
The functions of the softkeys change dynamically depending on the situation and
the contents of the display.
Always the most important functions are assigned to the softkeys 1 and 2.
When the user navigates through the topology, the softkey allocation does not
change depending on the context; the assignment is fix. If a softkey function
cannot be executed at a point in the topology, the inscription in the field is hidden.
1 Softkey / Option is only displayed when intervention text is available at this point
2 Softkey / Option only available in 'Access level 3'
3 Softkey / Option only available as of 'Access level 2.1'
See also
Normal view [➙ 24]
19
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
3 PMI
Buttons on the PMI
1 Navigation buttons
The navigation buttons work in the same way as the arrow keys on a PC
keyboard.
With the buttons <▲> and <▼> the next entry in a list can be highlighted.
Changing to a higher or lower hierarchy level is possible with the buttons <◄>
and <►>.
In a command list, the highlighted command may be executed with the button
<►>.
When characters are entered, the character to the left of the cursor position is
deleted by pressing the button <▲>.
3.1.5 Keypad
The following figure shows the keyboard and <MENU>, <ok> and <C> (Cancel)
buttons:
2
4 3
1 Keypad 3 <ok>
2 <MENU> 4 <C> (Cancel button)
20
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
PMI
3
Buttons on the PMI
Numeric entry
Numeric entry is applicable in the following cases:
PIN entry (password)
Shortcuts (Menus)
Address entry (Element ID)
Parameter entry
Alphanumeric entry
Alphanumeric entry is applicable in the following case:
Entering customer texts
21
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
3 PMI
EVAC NL
3.2 EVAC NL
Ontruimingsalarm b
Bedrijf
a Uitgeschakeld c
1 Totaal Storing
Alarm d
Zoemer Zone 1 7
2 uit
3 Zone 2
4 Zone 3
Zone 4
5 IN/UIT Zone 5
6 Zone 6
g
Zone 7
f
Zone 8
Selecteer
Zone 9
i Start
e
Zone 10
Stop 2x
Button LED
1 Totaal alarm a Totaal alarm (red)
2 Zoemer uit b Bedrijf (green)
3 Start c Uitgeschakeld (yellow)
4 Stop d Storing (yellow)
5 IN/UIT e EVAC zone selection (yellow)
6 LED TEST f Fault/Isolation (yellow)
7 Selecteer g Alarm (red)
i Information about using the keys
22
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
PMI
3
EVAC NL
LED Function
a Totaal alarm Indicates that Overall Alarm has been activated.
b Bedrijf Active as long as power supply is available.
c Uitgeschakeld Active when at minimum one EVAC zone is
switched off.
d Storing Active when at least one fault is present in an
EVAC zone.
Active (flashing) when the connection to the
fire control panel is faulty
e EVAC zone selection Active when the zone has been selected.
f Fault/Isolation Active when an EVAC zone has been switched
off or a fault is present.
g Alarm Active when all EVAC zones are activated.
23
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
3 PMI
Display
3.3 Display
The display of the station has two displaying variants:
Display without window
– Normal view
– Expanded visibility
– Fire department view
Display with window for following representations
– Lists
– Input fields
– Command responses
001 AAA 1
001 ABC YYYY 1
ABC
2
Identification of messages
Events occurring in the fire detection installation are indicated on the display. A
special identification informs on the status of an event.
Details on the identification can be found in the chapter Event status identification.
See also
Event status identification [➙ 143]
24
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
PMI
3
Display
003 AAA
With the <Switch to Extended view> and <Switch to Standard view> softkeys, you
can switch from normal view to extended view and vice-versa.
Alternatively, the navigation buttons <►> and <◄> can be used to switch over.
25
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
3 PMI
Display
ABCDEFG LLLLLLL 30
ABCDEFG ABCDEFG ABCDEFG
AAAAAAA ABCDEFGHI EEEEEEE
(1) (5)
BBBBBBB ABCDEFGHI FFFFFFF
(2) (6)
CCCCCCC ABCDEFGHI GGGGGGG
(3) (7)
DDDDDDD ABCDEFGHI HHHHHHH
(4) (8)
ZZZ ABCDEFGHI ZZZ (5) ZZZ
ABCDEFGHI ABCDEFGHI ABCDEFGHI
Example of the display with window and list
ABCDEFG LLLLLLL 30
ABCDEFG ABCDEFG / IJKLMNO
AAAAAAA AAAAAAA
01 /05 /06 10:40:55 (5)
BBBBBBB BBBBBBB (6)
CCCCCCC ABCDEF <OK>/ GHI <ESC>.
CCCCCCC (7)
EEEEEEE EEEEEEE (8)
XXX ZZZ <Cursor up>
ZZZ ZZZ ZZZ
ABCDEFGHI ABCDEFGHI ABCDEFGHI
Example of the display with window and input field
26
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
PMI
3
LEDs
ABCDEFG LLLLLLL 30
ABCDEFG ABCDEFG
XXX
AAAAAAA AAAAAAA (5)
BBBBBBB BBBBBBB (6)
CCCCCCC ABCDEF ABCDEF ABCDEF.
CCCCCCC (7)
EEEEEEE EEEEEEE (8)
ZZZ ZZZ ZZZ
ABCDEFGHI ABCDEFGHI ABCDEFGHI
Example of the display with window and command response
3.4 LEDs
The LEDs on the Person Machine Interface signal 'Events' and conditions. In
addition, the LEDs support the operator's orientation.
In general, the colors of the LEDs signal the following information:
Red 'ALARM'
Activation of the remote transmission
Yellow / green 'Fault'
Status confirmation
Configured event categories
See also
Logout timeout [➙ 97]
27
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
3 PMI
Menu structure
28
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
PMI
3
Cerberus Remote
The connection to a 'Station' with a licence key is also possible via a 'Station'
without a license key.
Cerberus-Remote has the same visibility as the connected 'Station'. You can use
Cerberus-Remote in a fire detection installation with networked 'Stations' to gain
global visibility. Just one licence key is needed for this per network if the licence
key is installed in a 'Station' with global visibility.
See also
Cerberus Remote operating modes [➙ 33]
Enabling / disabling Cerberus Remote [➙ 80]
Operating Cerberus Remote [➙ 83]
29
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
4 Operation functions
Selection and opening / execution
4 Operation functions
The following chapters contain descriptions of important functions for directly
operating the system.
Information on the system functions can be found in the corresponding chapter.
See also
System functions [➙ 92]
Button Consequence
<▼> next entry
<▲> previous entry
<More alarms> opens alarm list / jumps to the next entry in
the alarm list shown
<Number> + <ok> Goes to the entry with the number entered –
not in selection lists
'More Options' + 'Jump to begin' softkeys Jump to the top of the list
'More Options' + 'Jump to end' softkeys Jump to the end of the list
See also
List representation and types of lists [➙ 145]
30
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation functions
4
Scrolling
4.2 Scrolling
With the navigation buttons you can scroll through a list indicated on the display.
You can scroll to the start/end of the lists (limited function) and back in the following
lists:
Option lists
Command lists
Element category lists
In all other lists, you can scroll beyond the end of the list to the start of the list and
back.
See also
Event status identification [➙ 143]
31
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
4 Operation functions
Shortcut
4.4 Shortcut
A shortcut serves for the direct execution of an entry in a selection list by pressing
a numeric key.
In a command list, for example, you can execute a command directly by entering
the corresponding number.
The numbers for the shortcut are shown in the list entry line, on the right and in
brackets.
4.5 Favourites
You can perform several operation steps or an operation sequence in one step by
means of favorites.
A maximum of 8 favourites are configured and you can select them from the
favorite list in the 'Favorites' main menu item.
Numeric entry
The number of underscores corresponds to the number of possible positions
for the entry.
The overwrite mode is set by default; there is no insert mode.
Horizontal navigation within the input field is possible with the keys <◄> and
<►>.
Use <▲> to delete the character to the left of the cursor position.
Use <ok> to save the entered value and exit the input field.
– When there are several input fields in the dialog, the cursor jumps to the
next field by pressing <ok>.
– If the cursor position is in the last or only input field, close the input dialog
by pressing <ok>.
Use <C> to cancel the input and close the dialog without saving.
Alphanumeric entry
Alphanumeric entries are only possible in particular input fields, e.g. for
customer text.
Letters are entered in the same way as letters on telephones. You can select
the corresponding letter by pressing a key several times.
Switching between lower and upper case letters is possible with the key <*>
and only applies for the next character.
In input fields with more than one line, you cannot change back to a line above
the cursor position.
32
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation functions
4
Cerberus Remote operating modes
Indicators
In this operation mode Cerberus-Remote indicates the same as the 'Station'
connected to it, but you cannot operate the linked 'Station'.
Cerberus-Remote indicates the display with all indicated texts, all LEDs in their
current state and all buttons.
See also
Enabling / disabling Cerberus Remote [➙ 80]
33
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
ALARM Procedure
5 Operation
This part of the document provides brief descriptions and detailed operation
sequences for the important functions of the fire detection installation. In addition,
you can find your preferred procedures in the representation of exemplary
operation sequences.
34
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
ALARM Procedure
35
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Procedure in case of Fault
A list of possible 'Faults' and how they are eliminated can be found in the chapter
'Faults / Troubleshooting'. If you cannot eliminate 'Fault', please contact your
service provider.
Acknowledge 'Fault'
1. Press <Acknowledge> before the expiry of t1.
2. Read the 'Fault'location on the display.
3. Go to the 'Fault' location.
4. Rectify 'Fault'.
See also
Intervention concept (IC) [➙ 138]
Faults / Troubleshooting [➙ 148]
36
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Switching off / Switching on
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the 'Site' back on as soon as possible.
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the 'Site' back on as soon as possible.
The fastest method for switching off or on is to enter a known address in the
'Enter address' window.
In the configuration, a standard button can be given the function of directly
opening the menu with the 'Enter address' input dialog to select a detector zone.
In the following exemplary operating sequence the process is shown without a
known address.
37
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Switching off / Switching on
Enter address
Zone ---------
38
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Switching off / Switching on
021 Zones
Select command
OFF (2)
OFF/timer (4)
Execute command
OFF
Command executed
See also
Executing commands - object-oriented [➙ 55]
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the 'Site' back on as soon as possible.
39
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Switching off / Switching on
'Detector'
1. In the main menu, select the 'Topology' menu item.
The 'Topology' window is open.
2. Select 'Detection tree' and click <ok>.
The elements of 'Detection tree' are displayed.
3. Select the element 'Area 1'.
The elements of 'Area 1' are displayed.
4. Select 'Area 1' and press 'Lower level' <softkey 2>.
All 'Sections' in 'Area 1' are displayed.
5. Select 'Section 1' and press 'Lower level' <softkey 2>.
All 'Zones' in 'Section 1' are displayed.
6. Select 'Zone 1' and press 'Lower level' <softkey 2>.
All detectors of 'Zone 1' are displayed.
7. Select 'Detect. 1' and press 'More Options' <softkey 3>.
The 'Select option' window is open.
8. Select 'Execute commands'.
The 'Select command' window is displayed.
9. Select 'OFF'.
The command is executed.
The window with the command response is open.
The detector is switched off.
Exemplary representation of the aforementioned operation sequence for switching
off a detector:
Area 1 Portaphone AG
Lower Execute
level Commands
40
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Switching off / Switching on
Select element 'Zone 1', continue with 'Lower level' <softkey 2>
Upper More
level Options
Selecting option
Execute commands (3)
Jump to link (4)
Show details (5)
Select command
OFF (1)
Activate alarm indicator (3)
Deactivate alarm indicator (4)
41
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Switching off / Switching on
Command response
Execute command
OFF
Command executed
'Detector'
Proceed in the same way as when switching off 'Detector', but select the 'ON'
command as shown below.
Select command
ON (2)
**As an alternative, you can also select the corresponding detector or 'Zone' via
the 'Message summary' main menu item and the 'Isolations' message category
and switch it back on with the 'More Options', 'Execute commands' and 'ON'
softkey.
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the 'Site' back on as soon as possible.
You can only carry out temporary switching off at 'Area' or 'Section' level.
With this function, 'Isolation' can be temporary limited. The part of the 'Site' that has
been switched off is automatically switched on again after the expiry of the
specified period.
42
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Switching off / Switching on
The figures below show an exemplary operation sequence to temporarily switch off
'Section':
Enter address
Section 1--------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Select command
All zones ON (2)
All zones OFF/timer (3)
MCP zones OFF (4)
Non-MCP zones ON (5)
Non-MCP zones OFF (6)
Enter duration
05:00
(hh:mm)
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Execute command
All zones OFF/timer
Command executed
43
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Switching off / Switching on
WARNING
When the remote transmission Fire has been switched off, the fire brigade cannot
be called up in the event of fire!
Fire may spread unhindered.
Deploy staff to monitor the 'Site'.
You must switch the 'RT Fire' back on as soon as possible.
The 'RT Fire' is normally switched on and may only be switched off in particular
cases, e.g. for a function check of controls.
LED statuses:
Off
Permanently on with isolation
Flashing with fault
Example of switching off 'RT Fire' using 'Topology' main menu item:
Topology Access level 2.1
Exit with <C>
Detection tree (1)
Hardware tree (2)
Control tree (3)
44
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Switching off / Switching on
Lower Execute
level Commands
RT ch. 1
Upper More
level Options
Selecting option
Execute commands (3)
Jump to link (4)
Show details (5)
45
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Switching off / Switching on
Select command
OFF (1)
Set customer text (3)
Activate (5)
Time limited activation (6)
Execute command
OFF
Command executed
Example of switching off 'RT Fire' using 'On / Off' menu item in
'Functions' menu:
Selecting element category
Zone (3)
Sounder (4)
Fire control group (5)
RT control (6)
Alarming control group (7)
Enter address
Alarmg. ---------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Select command
Internal/external sounders OFF (1)
RT FIRE channels OFF (2)
Internal/external sounders ON (3)
RT FIRE channels ON (4)
46
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Switching off / Switching on
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the 'Site' back on as soon as possible.
You can switch off the fire detection installation alarm activation for specific
elements with this function.
Faults such as the removal of a detector are nevertheless evaluated and displayed.
You can only run the 'Alarm evaluation OFF' command on the following
elements:
'XC10 zone'
'Section'
'Automatic zone'
'Technical zone'
47
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Switching off / Switching on
NOTICE
Sabotage ALARM with police or security service
Costs due to unnecessary deployment.
In a site with 'FSD', switch off sabotage evaluation before you open the
housing of a control panel.
48
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Log in / Change access level
Login/logout
Enter PIN: *
For guest-login no PIN required
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
The present 'Access level' is indicated in the main menu in the header of the
display.
49
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Switching between 'Manned' / 'Unmanned' operation modes
When there is at least one 'Premises manned' event, the 'Premises manned' LED
is on.
By means of configured switching from 'Manned operation' to 'Unmanned
operation' at predefined times, the operation mode may switch although no
manual switching has been performed.
There is no possibility of an automatic switching from 'Unmanned operation' to
'Manned operation'.
See also
Operation modes [➙ 93]
50
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Changing visibility
See also
Standby visibility [➙ 98]
51
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Main menu / Open menu item
5. Select the 'expand.' element and press the 'More Options' softkey or the
command at the bottom directly, depending on the 'Access level'.
The 'Selection option' window is displayed depending on the 'Access level'.
6. Select 'Execute commands'.
The 'Select command' window is displayed.
7. Select 'Activate expanded visibility'
'Expanded visibility' is activated.
See also
Expanded visibility [➙ 99]
Without PIN entry, the 'Main menu' only includes the menu items that are
available without logging-in. To view an extended menu list in the 'Main menu',
you need to log in on a corresponding access level.
52
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Executing commands - Basics
See also
Menu button [➙ 21]
Depending on the 'Access level', the possible selection of commands via softkeys
or the 'Main menu' is extended or restricted.
See also
Selection in the topology [➙ 60]
Searching for elements [➙ 61]
List of all commands and required access levels [➙ 100]
53
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Executing commands - Basics
Enter address
Zone ---------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
54
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Executing commands - Basics
021 Zones
Select command
OFF (2)
OFF/timer (4)
Execute command
OFF
Command executed
Select 'Topology' menu item in the main menu, continue with <ok>
55
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Executing commands - Basics
Area 2 Portaphone AG
Lower Execute
level Commands
56
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Executing commands - Basics
Upper Execute
level Commands
Select command
OFF (1)
Activate alarm indicator (3)
Deactivate alarm indicator (4)
Execute command
OFF
Command executed
'Functions' menu
57
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Selecting elements or events
58
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Selecting elements or events
Selecting events
1. In the 'Main menu', select the 'Event memory' menu item.
A list with 'Stations' is displayed. The 'Station', where the selection is made
is identified accordingly.
2. Select the 'Station'.
A list of all events is displayed.
You can use the 'Select Date/time range' softkey to enter the timespan.
59
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Selecting elements or events
Selecting option
Select station (3)
Execute commands (4)
Jump to begin (5)
Jump to end (6)
Delete event memory (8)
60
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Selecting elements or events
Lower Execute
level Commands
Select command
OFF (1)
Deactivate (2)
Poll RT counter (3)
61
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Selecting elements or events
When you enter a valid address in the 'Enter address' field, only that element is
listed.
'Start with address'
Here you enter a valid address at the beginning. All elements with this address
are listed.
The elements may belong to different element categories such as 'Area' 2,
'Section' 2, 'Zone' 2, 'Alarming control group' 2 or 'Fire control group' 2, after
the entry of address 2..
Search by category
The tables below indicate steps of the 'Element search' with 'Start with category':
Enter address
Zone 2--------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
62
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Selecting elements or events
001 Zone
Zone 2 Corridor
Search by address
The tables below indicate steps of the 'Element search' with 'Start with address':
Enter address
Address 2--------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
050 Elements
Area 2 Portaphone AG
Section 2 1. floor
Zone 2 Corridor
RT fire 2 RT channel Fire
Execute Execute commands
Commands Topology
63
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Testing
5.11 Testing
The following chapters with operation sequences for testing include sample tests.
See also
Test [➙ 94]
64
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Testing
WARNING
During the system test, the alarming and fire control are activated!
Personal injury resulting from extinguishing activation
The fire brigade is called up unnecessarily.
Set the 'Fire controls' to 'Control test' in advance.
Inform the fire brigade in advance.
Before the 'Installation test' you can set 'Fire controls' to 'Control test'.
See also
Control test [➙ 65]
Testing detectors [➙ 64]
During the 'Control test', the controls function in the same way as during normal
operation; however, the hardware is not actuated.
The effects of the controls, e.g. the actuation of digital outputs and the sounders or
the execution of commands is ensured, however, the corresponding hardware
does not receive a signal and is thus not activated.
Testing a control
1. In the main menu, select the 'Functions' menu item.
The 'Functions' window is open.
2. Select the 'Test' menu item.
A list of all element categories on which a command of the 'Test' command
group can be executed is indicated.
3. Select the 'Fire control group' element category.
The 'Enter address' window is open.
65
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Activation / Deactivation / Reset
Select command
Control test END (1)
Control test (2)
See also
Testing detectors [➙ 64]
WARNING
Deactivated controls hinder appropriate measures in case of fire!
Personal injury and damage to property in the event of a fire.
Deploy staff to monitor the deactivated area.
You must reactivate deactivated controls as soon as possible.
WARNING
Activated parts of the system may actuate alarming and universal control devices!
Personal injury resulting from extinguishing activation.
The fire brigade is called up unnecessarily.
Set the 'Fire controls' to 'Control test' in advance.
Inform the fire brigade in advance.
66
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Activation / Deactivation / Reset
Area 1 Portaphone AG
Lower More
level Options
67
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Activation / Deactivation / Reset
Select element 'Section 3', continue with 'Lower level' <softkey 2>
Select element 'Zone 11', continue with 'Lower level' <softkey 2>
Select element 'Detect. 1', continue with 'More Options' <softkey 3>
Selecting option
Execute commands (3)
Jump to link (4)
Show details (5)
Select command
OFF (1)
Set customer text (3)
Activate alarm indicator (5)
Select PS MANNED (6)
Select PS UNMANNED (7)
68
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Activation / Deactivation / Reset
Command response
Execute command
Activate alarm indicator
Command executed
PMI
When activated alarm devices have been deactivated after an alarm event, they
are automatically re-activated when a new alarm event occurs.
69
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Activation / Deactivation / Reset
Activating 'Zone'
1. In the main menu, select the 'Functions' menu item.
The 'Functions' menu is open.
2. Select the 'Activate / deactivate' menu item.
A list of all element categories on which a command of the 'Activate /
deactivate' command group can be executed is indicated.
3. Select the 'Zone' element category.
The 'Enter address' window is open.
4. Press <ok> without entering an address.
A list with all 'Zones' is open.
5. Select an 'Zone' and press <softkey 1>.
The 'Select command' window is open.
6. Select 'Activate'.
'Zone' is activated.
The window with the command response is open.
Select 'Activate / deactivate' function in the main menu, continue with <ok>
70
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Activation / Deactivation / Reset
Enter address
Zone ---------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
004 Zones
Zone 1 FSE Zone1
Zone 2 Manual Zone 2
Zone 3
Zone 4
Execute Execute commands
Commands Topology
Select command
Activate (1)
Execute command
Activate
Command executed
After a 'Zone' zone has been activated, the 'ALARM' event is indicated on the
display:
'ALARM' event
71
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Activation / Deactivation / Reset
Acknowleding 'ALARM'
Press <Acknowledge>.
The alarming equipment is switched off.
Execute command
Acknowledge
Command executed
Command response
Resetting 'Zone'
1. Press <Reset>.
The 'Login/logout' dialogue is open.
2. Enter an admissible PIN.
'Zone' is reset.
72
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Activation / Deactivation / Reset
Enter address
Fire ct 1--------
OUTFire 1--
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
009 OUTFire
Select command
OFF (1)
Activate (4)
73
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Activation / Deactivation / Reset
Execute command
Activate
Command executed
74
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Activation / Deactivation / Reset
Enter address
Evac gr --------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Select command
Activate/ALERT+EVAC (1)
Activate/EVAC (2)
Activate/ALERT (3)
Deactivate (4)
Execute command
Activate/EVAC
Command executed
75
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Show information
Execute command
Poll alarm counter
76
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Entering the configuration
NOTICE
Overwriting an existing configuration
An existing customer-specific configuration is lost.
First save an existing customer-specific configuration.
77
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Auto-configure line
NOTICE
Overwriting an existing configuration
Parts of an existing customer-specific configuration are lost.
First save an existing customer-specific configuration.
Auto-configuring a line:
1. In the main menu, select the 'Topology' menu item.
The 'Topology' window is open.
2. Select 'Hardware tree'.
The 'Element' window is open.
3. Select a 'Station' and press the 'Lower level' <softkey>.
The elements of 'Station' are displayed.
4. Select the corresponding 'C-NET line card (onboard/FCL2001)' module and
press the 'Lower level' <softkey>.
All lines of 'C-NET line card (onboard/FCL2001)' are indicated.
5. Select a line and press 'More Options' <softkey>.
The 'Select option' window is open.
6. Select 'Execute commands' and confirm with <ok>.
The window including the possible commands is displayed.
7. Select the 'Auto-configure line' command and confirm with <ok>.
The line is auto-configured.
78
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Auto-configure line
Lower More
level Options
Selecting option
Execute commands (3)
Show details (5)
79
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Enabling / disabling Cerberus Remote
Select command
Read in installed devices (1)
Detector line OFF (2)
Auto-configure line (3)
Set customer text (4)
Accept replaced devices (6)
Enabling Cerberus-Remote
License key is installed.
1. In the 'Main menu', select the 'Functions' menu item.
The 'Functions' window is open.
2. Select 'Maintenance' and confirm with <ok>.
A list of all element categories on which a command of the 'Maintenance'
command group can be executed is indicated.
3. Select 'Cerberus-Remote'
The 'Enter address' window is open.
4. Enter the number of the 'Station on which Cerberus-Remote is to be enabled
and confirm with <ok>.
The 'Select command' window is open.
5. Select the 'Enable Cerberus-Remote operation' command and confirm with
<ok>.
Enabling for viewing and operating the 'Station' with Cerberus-Remote is
granted.
or
80
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Connecting Cerberus Remote
Select the 'Enable Cerberus-Remote viewer' command and confirm with <ok>.
Enabling for viewing the 'Station' with Cerberus-Remote is granted.
Press <ok>
Connection with Cerberus-Remote is broken.
Enabling for Cerberus-Remote is canceled.
Cerberus-Remote has the same visibility as the connected 'Station'. You can use
Cerberus-Remote in a fire detection installation with networked 'Stations' to gain
global visibility. Just one licence key is needed for this per network if the licence
key is installed in a 'Station' with global visibility.
81
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Setting up Cerberus Remote link with integrated IP
Establishing connection
1. Click on the 'Cerberus-Remote' task card.
The PMI of a 'Station' is shown.
2. In the menu bar, click on the 'Cerberus-Remote' menu item.
The 'Connect' (and 'Disconnect') submenu is displayed.
3. Select 'Connect'.
A window showing the selection of connection type is indicated.
Option
Execution of 'Cerberus-Remote' with additional parameters (IP address and
PIN).
Save modified program execution as link.
82
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Operating Cerberus Remote
Procedure
Start 'Cerberus-Remote' as own application (FX2020) and not from
corresponding register in 'Cerberus-Engineering-Tool' (FX2030).
1. Right-click on link in 'Start' > 'Siemens' > 'FX2020' > … to go to executable
'Cerberus-Remote' file and copy link to clipboard or an editor.
2. Add following parameters to program execution:
- IP address for GAP.
- Host ID for 'C-WEB'-'Station' to be viewed with 'Cerberus-Remote'.
- PIN for 'Access level' 3.
Modified program execution with integrated IP is created.
Example:
C:\Program Files\Siemens\F-FX2020\XL_en_1-V2.1>F-FXS2009.exe"
-visualizer ip=192.168.200.1 host=1 pin=0000
Test program execution command using 'Start' > 'Execute'
83
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Settings / Administration
Depending on the country-specific BDV, either one or two firmware languages are
integrated.
'Change language'
1. In the 'Main menu', select the 'Settings/administration' menu item.
2. Select the 'Change language' command.
If a second language is not integrated, this information is displayed: 'Only 1
language is available'.
The language will be changed.
'Change PIN'
1. In the 'Main menu', select the 'Settings/administration' menu item.
2. Select the 'Change PIN' menu item.
3. Enter the PINs in accordance with the input fields and confirm with <ok>.
The PIN has been changed.
84
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Settings / Administration
Change PIN
'Create PIN'
You have the required authorisation level.
1. In the 'Main menu', select the 'Settings/administration' menu item.
2. Select the 'Create PIN' menu item.
3. Enter an admissible access level.
4. Enter the PIN in accordance with the input fields and confirm with <ok>.
A new PIN has been created.
Create PIN
Access level: __
Enter PIN: ****
Verify PIN: ****
'Delete PIN'
PIN is present.
You have the required authorisation level.
1. In the 'Main menu', select the 'Settings/administration' menu item.
2. Select the 'Delete PIN' menu item.
3. Enter the PIN in accordance with the input fields and confirm with <ok>.
PIN has been deleted.
Delete PIN
85
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Settings / Administration
86
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Settings / Administration
87
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Entering/Changing customer text
Once customer text has been entered or changed, the updated display is only
shown the next time the element is accessed.
Entering or changing customer text does not lead to a reboot.
See also
Entry of numbers and letters [➙ 32]
Selecting elements or events [➙ 58]
88
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Inserting printing paper
Please make sure that the side that will be unwound is at the back of the drum,
corresponding to the dashed line in the figure below.
Closing printer
1. Pull some of the paper out of the printer.
2. Hold the paper end upwards.
3. Close the printer by holding the bracket upwards until the clips audibly engage.
The printer is ready.
89
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
5 Operation
Inserting printing paper
Closing printer
Printer is ready
90
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Operation
5
Switching off the printer
Version indication
1. In the main menu, select the 'Topology' menu item.
The three partial trees of the topology tree are indicated.
2. Select 'Hardware tree'.
3. Select the 'Station'.
4. Press the 'More Options' softkey.
The 'Select option' window is open.
5. Select 'Show details'.
The version of the 'Station' and configuration data are indicated.
91
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
6 System functions
Note on the configuration of the local fire detection installation
6 System functions
See also
Event categories [➙ 142]
Parameter Configuration
Operation level access O via password
O via key switch
Remote transmission of 'ALARMS' O yes
O no
Alarm sequence taking into account the staff present on site O yes
O no
Switching from 'Manned operation' to 'Unmanned operation' O automatic
O manual
Automatic switching time from 'Manned operation' to 'Unmanned operation' O indicated
O not indicated
Automatic switching time from 'Manned operation' to 'Unmanned operation' O not activated
Delay t1 ____ minutes
Delay t2 ____ minutes
Switchover O automatic
Summer time / Winter time O manual
Remote transmission of 'Faults' O yes
O no
Function Evacuate O activated
O not activated
Access to acknowledgement O always possible
O via password / key switch
'Faults' must be reset O yes
O no
'Faults' are generally immediately transmitted to the receiving centre O yes
O no
Manual call points in mixed detector zones always trigger an 'ALARM', even O yes
when the detector zone is switched off O no
Maximum operation time without mains supply ____ hours
Building plan handed over on _________
by _________
92
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System functions
6
Operating condition
93
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
6 System functions
Operation modes
'Manned operation'
In the 'Manned operation' operating mode, events can be processed via 'AVC' or
'IC'.
The remote transmission of an 'ALARM' may be delayed, for example, and an
operator may verify 'ALARMS' or 'Faults' that have occurred.
'Unmanned operation'
In 'Unmanned operation' operating mode events are directly handled in accordance
with the configuration, without taking into account the 'AVC' or 'IC'.
This means e.g. that remote transmission of an 'ALARM' is effected without delay.
Global alarming is activated immediately.
6.3.2 Test
The fire detection installation is in operating mode 'Test' if one of the following test
modes is activated:
'Detector test mode'
'Control test mode'
'Install. test mode'
Test variants
Existing sounder bases are equally activated when the corresponding detector is
tested.
In 'Detector test mode' test mode the fire detection installation has the following
properties:
The automatic detectors are set to high sensitivity.
Alarm devices and controls are active as in normal operation.
No danger messages or fault messages are generated.
Test activations are indicated as test activation messages, logged in the event
memory and printed out if need be.
After the detector test the detectors are set to normal sensitivity again, like before
the test.
94
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System functions
6
Operation modes
Test variants
As a test variant it is possible to switch e.g. the control to test before performing the
installation test.
See also
Testing [➙ 64]
6.3.3 Isolation
You can switch off 'Zones' with automatic or non-automatic detectors in special
situations, e.g. during construction work.
When parts of the fire detection installation are switched off, the fire detection
installation is in 'ISOLATION' condition and operating mode.
The 'ISOLATION' LED on the Person Machine Interface is on.
In 'ISOLATION' operating mode neither 'ALARMS' nor 'Faults' from the parts that
have been switched off can be evaluated.
See also
Switching off / Switching on [➙ 37]
95
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
6 System functions
Access level and access rights
6.3.4 Renovation
In '--Renovation mode' operating mode the detector parameter sets are changed
as follows:
No evaluation possible by the optical part of the detector.
A static evaluation by the thermal part of the detector is possible, however,
without the evaluation of the temperature difference.
The 'ISOLATION' LED on the PMI is on as soon as a part of the installation has
been set to '--Renovation mode'.
A list of all commands and the required access levels can be found in the
corresponding chapter.
The following table shows examples of main menu items and the access levels
needed for execution
96
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System functions
6
Access level and access rights
When the key switch is in position 'On', the logout timeout function is deactivated.
See also
Logout timeout [➙ 97]
List of all commands and required access levels [➙ 100]
The PIN input dialog is indicated automatically if the activation of a button on the
PMI requires a higher access level.
See also
Log in / Change access level [➙ 49]
See also
Enabling / disabling Cerberus Remote [➙ 80]
97
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
6 System functions
Visibility
6.5 Visibility
Several fire control panels and fire terminals ('Stations') can be integrated into a fire
detection installation. The visibility defines which part of a fire detection installation
is visible and can be operated on a 'Station'.
The visibility for a fire control panel can be configured in the following topology
levels of a fire detection installation:
'Site'
'Station'
'Area'
The visibility for this 'Station' is configured by selecting and assigning event
categories from the topology to the visibility for this 'Station'.
For example, all the 'ALARMS' for the 'Site' or just the 'Faults' for the 'Area' of a
'Station' are indicated.
Two other modes are available for configuring the visibility:
'PMI standby visibility'
'PMI expanded visibility'
See also
Changing visibility [➙ 51]
Event categories [➙ 142]
See also
Deactivating standby [➙ 51]
Expanded visibility [➙ 99]
98
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System functions
6
Sabotage ALARM [DE]
Possible dependencies
'PMI expanded visibility' can only be activated if a monitored 'Station' fails.
See also
Activating / deactivating expanded visibility [➙ 51]
See also
Opening the control panel [DE] [➙ 149]
Switching off sabotage evaluation [DE] [➙ 48]
99
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
7 List of all commands and required access levels
'Switching on/off' command group
100
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
List of all commands and required access levels
7
Command zone 'Test'
101
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
7 List of all commands and required access levels
'Activating/deactivating' command group
102
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
List of all commands and required access levels
7
Command group 'Information'
103
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
7 List of all commands and required access levels
'Maintenance' command group
104
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
List of all commands and required access levels
7
Other commands
105
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
8 List of elements
8 List of elements
Element Definition
(short text
long text)
'Area' Highest level in the 'Detection tree', alarm organisation level
'Area'
'Section' 2. level in the 'Detection tree', building section (e.g. room, staircase, floor)
'Section' serving for the unambiguous identification and location of a fire alarm
'Zone' 3. level of the 'Detection tree'; decision on alarm is taken on this level
'Zone'
'Detect.' Lowest level in 'Detection tree'
'Detector'
'Control' General control
'Control'
'Evac ct' 3. level in 'Control tree'
'Evac control'
'Evac gr' 2. level in 'Control tree'
'Evac control group'
'Fire ct' 3. level in 'Control tree'
'Fire control'
'Fire gr' 2. level in 'Control tree'
'Fire control group'
'RT fire' 3. level in 'Control tree'
'RT fire control'
'RTfault' 3. level in 'Control tree'
'RT fault control'
'RT 1' … 'RT 8' 3. level in 'Control tree'
'RT 1 control' … 'RT 8 control'
'Alarmg.' 2. level in 'Control tree'
'Alarming control group'
'Sounder' 3. level in 'Control tree'
'Sounder control'
'Sounder' 2. level in 'Control tree'
'Sounder'
'Phased' Lowest level in 'Control tree'
'Phased sounder '
'Evac' Lowest level in 'Control tree'
'Evac sounder'
'Sounder' Lowest level in 'Control tree'
'Sounders' alarming control
'Sounders' fire control Lowest level in 'Control tree'
106
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
List of elements
8
Element Definition
(short text
long text)
'Station' Highest level in 'Hardware tree'
'Station'
'Station' 'Station' network
'Station'
'Printer' 'Station' printer
'Printer'
'Station' Highest level in 'Hardware tree', control panel
'Station'
'Module' 2. level in 'Hardware tree'
'Module'
'Line' 3. level in 'Hardware tree', primary detection line
'Line'
'Device' Lowest level in 'Hardware tree', functions of the physical device
'Device'
'Supply' Mains / Battery
'Power supply'
'FRT' Object display with operation function
'FRD' Object display without operation function
'Phys.ch' Lowest level in 'Hardware tree'
'Physical channel'
'PMI' 'Station' operating unit
'PMI'
'Mimic' LED indication unit on the P2 periphery bus
'Mimic display driver'
'Keydep.' Fire department key depot
'Key depot'
'BN dev.' 'BN dev.' device connection
'BACnet device object'
'FAT Fire brigade indication panel
'FAT
'FAT/FBF' Fire brigade indication panel with integrated fire brigade operating panel
'FAT with FBF'
107
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Overview
9 System description
This part of the document includes information on the setup and functions of the
fire detection installation.
9.1 Overview
Acquisition ►► Evaluation ►► Alarming and control
Acquisition
Fire detectors detect fire phenomena, e.g. smoke, heat or carbon monoxide, and
transmit signals to the control panel in the form of different danger levels.
108
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Overview
'Manned operation'
operation mode
109
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Topology
Alarming
The different fire alarms and system events are verified independently from one
another. Depending on the configuration, local alarming or direct or delayed global
alarming is actuated.
Local alarming:
Local alarming equipment (e.g. acoustic or optical alarm devices) is actuated in
order to call up immediately available intervention personnel (e.g. in-house
staff) and to alert people of a possible fire hazard.
Global alarming:
Global alarming equipment (e.g. remote transmission) is actuated and external
intervention forces (e.g. the fire department) are alerted.
The following points influence the type of alarming:
Configuration of the alarming process
Position of 'Manned operation'/'Unmanned operation' operation mode
– 'Manned operation': Personnel present on site
– 'Unmanned operation': No personnel present on site
Type of alarm activation (automatic or manual)
Control
In the event of fire it makes sense to initiate first, decisive actions automatically.
Automatic measures are carried out by controls, e.g. by the control of building
services, evacuation or extinguishing.
9.2 Topology
The configuration of an 'FS720' fire detection installation is shown in the following
structure trees:
'Hardware tree'
'Detection tree'
'Control tree'
'Operation tree'
'Network tree'
The structure is created by installing in the building and configuring the fire
detection installation. The elements of the individual structure trees are linked with
one another via channels.
Thanks to a hierarchical topology and arrangement into zones, events can be
assigned geographically and shown accordingly. This enables commands to be
given to consolidated parts of the site, for example.
110
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Topology
1 'Station' 3 'Device'
2 'Module' Dotted line 'Line'
111
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Topology
1 'Area' 3 'Zone'
2 'Section' 4 'Channel'/ 'Detector'
112
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Topology
'Area'
'Area' typically corresponds to a building.
'Area' combines 'Sections' which are subject to the same 'Manned
operation'/'Unmanned operation' operation mode.
'Area' actuates the alarming equipment (acoustic and optical alarming devices
as well as remote transmission).
'Area' is assigned the following functions:
– 'Manned operation'/'Unmanned operation' operation mode
– Switching assigned 'Sections' on/off
Several 'Areas' are possible per control panel:
FC722, FC724: up to four 'Areas'
FC726 up to eight 'Areas'
There is an 'Area' that groups together the functions of alarm verification(AVC), e.g.
collective alarms and degraded mode operation.
'Section'
'Section' is optional and does not exist in some countries.
'Section' combines 'Zones' to form logical units. Such a unit can be e.g. a floor
or a staircase.
'Section' is assigned the following function:
– Switching assigned 'Zones' on/off
'Zone'
'Zone' generally combines the detectors in a room.
'Zone' evaluates the danger levels transmitted by the detectors. The configured
combination of different danger levels defines the conditions upon which an
'ALARM' is triggered.
The following fire alarm zone types exist:
– 'Automatic zone'
– 'Manual zone'
– 'Technical zone'
– 'FSE zone'
– 'Flow switch zone' (sprinkler)
– 'Sub-system zone'
The following extinguishing zone types exist:
– 'Sprinkler zone'
– 'XC10 zone'
'Channel'
The 'Channel' in 'Detection tree' represents the functionality of the inputs and
outputs of an C-NET device.
113
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Topology
'Area'
'Manned operation'
In 'Manned operation' operating mode, operating personnel are present and
can investigate the fire location. The detectors are set to normal sensitivity, in
accordance with the selected parameter set.
'Unmanned operation'
In the 'Unmanned operation' operating mode, there are no operating personnel
present to investigate the fire location. The sensitivity level of the detectors or
their parameter sets are typically increased by switching to 'Unmanned
operation' operating mode.
The settings for the 'Manned operation'/'Unmanned operation' operation modes are
defined in the chapter Alarm Verification Concept (AVC).
'Zone'
Switched on (normal operation)
Danger levels are evaluated and 'ALARMS' produced in normal operation. The
detectors have a normal sensitivity level, in accordance with the selected
parameter set.
Switched off
If a 'Zone' is switched off, the channels assigned to the 'Zone' are isolated. No
signals are evaluated, neither danger levels nor 'Faults'.
There are two isolation functions:
– Isolation without time limits
– Isolation with time limits
'--Renovation mode'
This operating mode is not assigned a function.
'Detector test'
In the 'Detector test' operating mode, detectors can be actuated for test
purposes. When a detector is triggered, a test activation message is generated.
Alarm devices or controls are not activated.
The following devices are activated:
– Internal alarm indicators
– External alarm indicators in accordance with the configuration
– Base sounders if they are in the base of the activated detector
During testing the detectors must react quickly so that the holding times are
short. During the 'Detector test', the detectors are switched to increased
sensitivity with the 'Test' parameter set for this purpose.
After terminating the 'Detector test' operating mode, the detectors and
'Zones'are reset to the condition they were in before the 'Detector test'.
114
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Topology
'Installation test'
An 'Installation test' can be performed during normal operation. The alarm
devices and controls are activated.
In the test the detectors must react quickly so that the holding times are short.
During the 'Installation test', the detectors are switched to increased sensitivity
with the 'Test' parameter set for this purpose.
After terminating the 'Installation test' operating mode, the detectors and
'Zones'are reset to the condition they were in before the 'Installation test'
operating mode.
'Channel'
Switched on (normal operation)
In the normal operation, the danger levels of the detector as well as any 'Faults'
are transmitted to the 'Zone' for evaluation.
Switched off
If a 'Channel' is switched off, no signals are forwarded to the 'Zone', neither
danger levels nor 'Faults'.
115
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Topology
116
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Topology
117
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Topology
118
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Topology
Mimic display
There are two possible ways of configuring the LED indicator (internal) FTO2002:
Visibility of the 24 LED groups (red/yellow) on a Section or Zone.
Visibility of each of the 48 LEDs on any event.
Event printer
The event printer logs all system events in the configured view.
119
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Topology
Networking types
The stations in the fire detection system can be networked in the following ways:
SAFEDLINK (system bus)
SAFEDLINK, extended: coupling of several SAFEDLINK sub-nets via C-
WEB/LAN (optical Ethernet)
electric Ethernet (does not comply with EN-54)
SAFEDLINK and Ethernet mixed (does not comply with EN-54)
Connection types/functions
The stations in the network can have the following connection types/functions:
Stand-alone station: stand-alone station
SAFEDLINK station: station in the SAFEDLINK network
Router station: station in the SAFEDLINK sub-net connected to the C-
WEB/LAN
Ethernet station: station in the Ethernet sub-network to which no more stations
are connected via SAFEDLINK
GAP station: station in the network for connecting to a management station
(BACnet client)
– The GAP station has the function of a DHCP server (configurable)
– The DHCP server automatically issues IP addresses to the clients from a
defined IP address space. This enables a PC to receive local access, for
example
A route to an external IP router can be defined for the GAP station
Extended networking
Extended networking is the merging of several SAFEDLINK sub-nets via C-
WEB/LAN, which is managed as optical Ethernet in loop topology.
The sub-networks communicate via the router stations.
Private/external network
Private network: FS720 fire detection installations have their own cabling. The
IP addresses come from a reserved range for private networks
External network: Fire detection installations can be incorporated in an existing
IT infrastructure as sub-nets
Integration in an external network does not comply with EN-54
120
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Topology
Geographical allocation
Each device in the 'Hardware tree' has a unique address. In 'Detection tree', it is
possible to allocate room x on floor y to the device, for example.
The physical and the logical channel of a device are linked between the 'Detection
tree' and 'Hardware tree'.
The physical channel is the lowest level in the 'Hardware tree' and maps the
physical function of a device.
The logical channel is the lowest level in the 'Detection tree' and maps the logical
function of a device.
121
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Topology
122
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Acquisition
9.3 Acquisition
The detectors detect the fire phenomenon, e.g. smoke, heat or carbon monoxide,
and transmit the danger level to the 'Zone'.
Danger levels
123
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Evaluation
9.4 Evaluation
The evaluation of the danger level and the decision to trigger an 'ALARM' or not
takes place on 'Zone'.
The danger levels of several alarming detectors are combined in the 'Zone'. The
following zone types exist:
'Manual zone'
'Automatic zone'
'Technical zone'
'FSE zone'
'Sprinkler zone'
'XC10 zone'
124
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Evaluation
'Manual zone'
A 'Manual zone' combines the 'Manual call points'. Danger signals are evaluated by
means of an OR relation. Each detector of a 'Manual zone' can generate 'ALARM',
but not 'Pre-ALARM'.
'Automatic zone'
A 'Automatic zone' combines 'Automatic detectors'. The 'Automatic zone' can
generate 'Pre-ALARM' and 'ALARM'. A distinction is made between the following
detector dependencies:
Multi-detector dependency
With multi-detector dependency, the danger levels of several detectors are
linked (AND relation) and evaluated. A 'Pre-ALARM' or 'ALARM' is generated
when the defined danger levels have been reached.
Several evaluation variants are possible in multi-detector dependency.
Single-detector dependency
With single-detector dependence the danger levels are linked (OR relation) by
one or more detectors. A 'Pre-ALARM' or 'ALARM' is generated as soon as at
least one detector has reached the defined danger level.
Alarm levels
'Technical zone'
In a 'Technical zone', inputs for technical messages are combined, e.g. fault or
danger by extraneous equipment.
'FSE zone'
A release element is assigned to this zone. With the release element, a fire alarm
is generated manually, which in turn releases the lock to the 'Key depots' with the
keys for the building. A key is required to operate the release element and this is
held in the exclusive possession of the fire department.
125
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Evaluation
'Sprinkler zone'
A sprinkler system is a piping system that is terminated at several locations with
sprinkler heads. It is normally fed by the public network of hydrants.
The sprinkler station is installed directly after the house feed. It separates the
sprinkler network from the hydrant network due to overpressure in the sprinkler
network.
The sprinkler station signalizes when the sprinkler network is opened somewhere
and water begins to flow. This condition is reported to the fire control panel via a
contact (or two as an option) and triggers an alarm with immediate response from
the fire brigade.
In larger sprinkler systems, the piping system is distributed over several floors and
the line network has an outlet on every floor. Flow rate indicators are built into each
outlet.
The flow rate indicators generate a signal when there is a flow.
126
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Evaluation
'XC10 zone'
Extinguishing is actuated and monitored by the autonomous extinguishing control
unit XC10.
An interface to the extinguishing control unit makes it possible to send
extinguishing control unit functions to the fire control panel, and to transmit
commands from the fire control panel to the extinguishing control unit.
D 'Detection tree'
XC10 Extinguishing control unit
I Extinguishing control unit inputs: 'Extinguishing activated', 'Fault', 'Pre-
alarm', 'Autom. + manual extinguishing OFF'
O Extinguishing control unit outputs: 'Reset', 'Autom. Blocking extinguishing
activation, 'Autom. + manual extinguishing activation blocked'
Z 'XC10 zone'
127
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Control
9.5 Control
Alarm events and system events may occur in a fire detection installation. It is the
task of the fire control unit to alert people and/or initiate appropriate actions based
on the different event categories. This is achieved with the different control types:
Alarming control
'Fire control'
'Evac control'
Extinguishing control
The alarming control is described in the chapter "Alarm Verification Concept
(AVC)".
Sample control
Causes are any events such as 'ALARM', 'Fault', 'Isolation', test mode as well as
signal inputs (contacts).
The control has an "OR / AND / NOT" combination of the causes that have
occurred.
The effects of the control are the activation or deactivation of outputs. The actuated
outputs can be combined with inputs for confirmation.
Effects are also commands within the fire detection system, e.g. for the isolation of
a 'Zone' or for changing a detector parameter set.
128
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Control
129
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Control
130
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Control
3 'Alert' → → → 'Evac' → → →
2 'Alert' → → → 'Evac' → → →
1 'Alert' → → → 'Evac' → → →
EG 'Alert' → → → 'Evac'
UG 'Alert' 'Evac' → → →
131
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Control
132
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Control
133
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Alarm verification concept (AVC)
134
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Alarm verification concept (AVC)
If the 'ALARM' is not reset within the given time t2, 'Immediate global alarming' is
activated.
135
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Alarm verification concept (AVC)
mx m
t1.. q t2.. r
?
qx rx
..t1 X ..t2 X
GA
Alarm verification
136
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Alarm verification concept (AVC)
Alarm devices
For local and global alarming, acoustic alarm devices, strobes, digital outputs, etc.
can be used. The tone of the alarm devices can be configured differently for local
and global alarming (the alarm devices must be suitable for this).
Remote transmission
The alarm message is transmitted to an intervention station. In the case of local
alarming, this is usually the company fire brigade and for global alarm usually the
state fire brigade. A remote transmission device must be used to transmit alarm
messages via the public telephone network.
137
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Intervention concept (IC)
Operating mode:
– 'Manned operation'
– 'Unmanned operation'
Alarming type:
– 'Local alarming only'
– 'Delayed alarming'
– 'Global alarming only'
The 'Intervention Concept' ('IC') is an integral part of the fire control panel and
takes into account the interaction of the operating personnel. The 'Intervention
Concept' can be used to define an intervention process which is initiated should an
event occur or once a particular delay time has lapsed.
138
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Intervention concept (IC)
For each of the following event categories the behavior can be defined separately:
'Fault'
'Isolation'
Test
'Technical message'
'Activation'
'Information'
The 'Intervention Concept' has two independent, parallel intervention processes:
Attendance check (t1)
Intervention monitoring (ts)
The intervention process can be configured according to the 'Manned
operation'/'Unmanned operation' operating mode.
139
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Intervention concept (IC)
The figure below shows an exemplary intervention process for the 'Fault' event
category.
Attendance check Intervention monitoring
A B
t1.. ts..
! !
..t1 X ..ts X
G S
140
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Intervention concept (IC)
Alarm devices
Alarm devices, strobes, digital outputs, etc. can be used for local and global
alarming. The tonality of the alarm devices can be configured differently for local
and global alarming.
Remote transmission
For service intervention the event message is transmitted to intervention forces, in
general the maintenance personnel. A remote transmission device must be to
transmit event messages via the public telephone network.
Intervention alarming
141
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Events
The alarm devices and the remote transmission can be separately configured for:
Operating mode:
– 'Manned operation'
– 'Unmanned operation'
Immediate intervention:
– 'Local intervention only'
– 'Delayed intervention'
– 'Global intervention only'
Service intervention:
– 'Delayed intervention'
– 'Direct intervention'
9.8 Events
See also
Event memory [➙ 144]
142
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Events
Identification Meaning
! Message not acknowledged
i Cause of message no longer available
no identification Message acknowledged
+ More than one detector is active
143
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
Events
See also
Select events [➙ 58]
In the 'Message summary' main menu item only those message categories in
which messages (events) have actually occurred are indicated.
After pressing the short-cut button (2) the detailed view of the 'Pre-ALARM'
message category is indicated:
144
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
List representation and types of lists
In the 'Message summary' main menu item only those event categories are
indicated in which events have actually occurred.
In accordance with the event categories, there are the following event lists:
'ALARM'
'Pre-ALARM'
'Fault'
'Isolation'
Test
'Technical message'
'Activation'
'Information'
All events are also included in the event list in the 'Event memory'. This 'Event
memory' list has a different layout as well as additional functions. For this reason,
a separate chapter 'Event memory' is included.
145
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
9 System description
List representation and types of lists
See also
Event memory [➙ 144]
025 Elements
Station 1
Area 1
PMI 1
Network 1
Execute Execute commands
Commands Topology
Details of Station 1
146
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System description
9
Version indication station / Configuration data
Select command
Set customer text (1)
ON (2)
OFF (3)
OFF/timer (4)
Activate (5)
See also
Show version [➙ 91]
147
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
10 Faults / Troubleshooting
10 Faults / Troubleshooting
If the site is indicating 'Fault', the table below provides a list of possible 'Faults',
including information on the possible causes.
If a 'Fault' cannot be eliminated with the help of these operation instructions, please
contact the service engineer.
With all other 'Faults', the service provider in account must be contacted.
See also
Inserting printing paper [➙ 88]
148
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
System maintenance
11
Maintenance recommendation
11 System maintenance
Regular maintenance of the 'Site' is necessary in order to ensure the system will
function reliably.
The fire detection installation has a reminder function that informs you of imminent
maintenance. When the service reminder is displayed, regular maintenance by the
service technician is required.
NOTICE
Sabotage ALARM by opening the control panel
Measures for 'Sabotage ALARM' are triggered unnecessarily.
Switch off sabotage evaluation before you open the control panel.
See also
Switching off sabotage evaluation [DE] [➙ 48]
149
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
12 Glossary
12 Glossary
Term Definition
A
Addressable detector line Detector line technique which gives each device its unique address. → Collective
detector line
Alarm device One component of a → Fire detection system, which is used for acoustic and/or optical
alarming, e.g. → Alarm sounder, beacon.
Alarm indicator Visual display to signal an alarm or pre-alarm
Alarm organization Covers all measures which are used for alarming, rescue, preventing a fire from
spreading, fire fighting and orientation in the event of a fire. Alarm organization may
differ depending on the → 'Manned' or → 'Unmanned' operating mode. → Alarm
verification concept
Alarm verification concept Concept for preventing false alarms which takes into account the interaction of the
operating personnel in the alarming sequence
Alarming control Monitoring and controlling the alarming equipment
Alarming equipment Alarm devices and transmission equipment
Area Topmost level in the → Detection tree. Assigned to the area are → Sections and →
Zones
Automatic configuration A zone is created for each sensor channel (automatic detector and manual call point).
A control is created for each alarm sounder. IO-modules, FT2010, FT2011 and
external alarm indicators are not configured automatically.
Automatic fire detector Device which measures a physical parameter (e.g. warmth) in order to detect a fire
AVC Abbreviation for Alarm Verification Concept → Alarm verification concept
B
BACnet Abbreviation for 'Building Automation and Control Networks'. Network protocol for
building automation, such as communication between one → Management-Station
(MMS) and one fire detection installation.
BDV Abbreviation for 'Basis Data Variant'
C
CAP CAP = Central Access Point. Term valid up to MP2.1. >MP2.1 is also used in the tool
for corresponding systems. Connection station between the SAFEDLINK and Ethernet
sub-nets.
C-NET Addressed → Detector line for C-NET devices
C-NET device A device to which the C-NET detector line is connected.
Collective detector line Detector line technique which gives one address to all detectors on a detector line.
This makes it impossible to identify individual detectors.
Control group Combination of several similar → Controls
Control tree Structure tree with → Control group and → Control
150
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Glossary
12
Term Definition
CPU Abbreviation for 'Central Processing Unit'. The computing unit of the → Fire control
panel. → CPU module
C-WEB Protocol which is used in the SAFEDLINK → SAFEDLINK → System bus
C-WEB/Ethernet FS720-specific term for networking with electric Ethernet → C-WEB/LAN
C-WEB/LAN FS720-specific term for loop-shaped networking with optical Ethernet → C-
WEB/Ethernet
C-WEB/SAFEDLINK FS720 system bus → C-WEB → SAFEDLINK
D
Danger level A fire detector signal which expresses the probability of a fire. Automatic fire detectors
have e.g. danger levels 0 to 3. Manual call points only have danger levels 0 and 3. 0 =
no danger, 1 = possible danger, 2 = probable danger, 3 = very probable danger
Degraded mode Defined reduced mode of operation which occurs when part of the fire detection
installation (e.g. main CPU) fails.
Detection tree Diagram of the geographical and organizational arrangements for → Sensors in a
building. This is a hierarchical structure comprising → Area, → Section, → Zone
Detector line Electrical connection between the detectors and the fire control panel. There are
collective detector lines and addressed detector lines.
Detector line topology Arrangement of devices on the detector line. Depending on the detector line, up to
three topology types are possible: → Loop, → Stub, stub on loop
E
Effect An impact caused by a control, e.g. activation of a hardware output or a → Command.
→ Cause
Emergency power operation → Fire detection installation is supplied by the second source of power, e.g.
→ Batteries.
Ethernet station Participant in the Ethernet sub-net without local connection for the PC
Extended networking Connection between several SAFEDLINK networks → C-WEB/SAFEDLINK → C-
WEB/LAN
External alarm indicator Optical element for indicating the site of the fire which is positioned at some distance
from the detector. Is usually fitted at point at which the room where the detector is
alarming is accessed.
Extinguishing control → Control which controls a connected extinguishing system and evaluates and
displays its statuses
Extinguishing control group Level in the → Control tree of the → Fire detection system. The extinguishing control
group contains the → Extinguishing controls.
F
False alarm Alarm based on no danger
Fire control → Control which is activated in the event of a → Fire alarm
Fire control group Level in the → Control tree of the → Fire detection system. The fire control group
contains the → Fire controls
151
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
12 Glossary
Term Definition
Floor repeater display A display device without operating elements.
Floor repeater terminal A display device with operating elements for acknowledging and resetting alarms and
faults.
G
GAP Abbreviation for Global Access Point. Participant in the Ethernet sub-net for the
connection between the Ethernet sub-net and a management station (BACnet client)
and/or for remote access with the Cerberus engineering tool or Cerberus Remote. If
there is a → Secondary GAP, the GAP becomes the main GAP. Can be operated as a
DHCP server in the Ethernet sub-net.
Gateway Network bridges which link two different systems/networks with one another and
transfer the different communication and transmission standards/protocols.
Global alarming Global alarming equipment (e.g. remote transmission) is actuated and external
intervention forces (e.g. the fire brigade) are alerted. → Local alarming
H
Hardware tree Depiction of the hardware of a → Fire detection installation
I
IC Abbreviation for Intervention Concept → Intervention concept
Intervention concept Concept with two independent verifications: Presence check for rapid local
intervention and intervention check for service intervention.
Isolation Status of one part of the → Fire detection installation, which suppresses the evaluation
of all signals
L
License key Hardware modules for activating functions.
Line card Umbrella term for module bus cards for connecting detectors
Line driver Hardware: Driver (repeater) for the detector lines.
Line separator An electronic switch in devices on the detector line which automatically disconnects
the defective part of the line in the event of a short-circuit.
Link Creating a reference between two elements, e.g. logical channel and physical channel
Local alarming Local alarming equipment (e.g. acoustic or optical) is actuated in order to call up
intervention personnel and to alert people of a possible fire hazard. → Global alarming
Logical channel Depiction of a device's logical function in the → Detection tree or control tree. The
logical channel is always the bottom level in the structure tree.
Logical horn channel Control element. Activates a → Horn output.
Logical input channel Represents a digital input.
Logical output channel with Control element. Activates the 'Output' channel in the hardware tree. An input which
feedback monitors whether the output has switched is assigned to this.
Logical tree In FS720 split into → Detection tree and → Control tree
152
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Glossary
12
Term Definition
Loop → Detector line topology which runs from the → Fire control panel via the → Fire
detectors and back to improve operational reliability (UL864 Class A Wiring). This type
of wiring allows all detectors to communicate with the control panel even in the event
of an open line or short-circuit. → Stub.
Loop line Expression for → Loop
M
Main GAP GAP = Global Access Point. Participant in the Ethernet sub-net for the connection
between the Ethernet sub-net and a management station (BACnet client) and/or for
remote access with the Cerberus engineering tool or Cerberus Remote. If there is a
secondary GAP, the GAP becomes the main GAP.
Management station A superordinate system for monitoring and operating safety-related sites and
buildings, e.g. fire, intrusion, access, heating, ventilation
Manned Switching status of the → Alarm organization, if operating personnel are present and
can intervene should an event arise (alarm, fault)
Maximum current connection Calculation unit for planning the detector lines → Outline quantities. Maximum current
factor value that a device obtains from the detector line.
Minor incident Alarm situation which the operating personnel can handle themselves and does not
therefore trigger → Global alarming. → Major incident
Multi-detector dependency When using multi-detector dependency, the → Danger levels of several detectors are
included in the alarm decision. Measures such as → Alarming or closing the fire doors
are only initiated when the defined dependencies occur (e.g. two detectors detect
→ Danger level 3). → Single-detector dependency
N
Network module (SAFEDLINK) FS720 network card
Network tree Figure of the network in a → Fire detection installation
Networked fire detection system Site with more than one fire control panel and at least two sub-nets
Non-stationary C-NET devices Devices mounted with a base (exception: alarm sounders and radio detectors).
Normally closed contact (NC) Opens a power circuit when activated. → Normally open contact (NO)
Normally open contact (NO) Closes a power circuit when activated → Normally closed contact (NC)
O
Outline quantities Defines the number of permissible elements of one type in a system. For example,
maximum number of devices on a → Detector line.
P
Parameter set Defined detector behavior, e.g. in terms of sensitivity, resistance to deceptive
phenomena, response time. Detectors can be operated with different parameter sets.
Physical channel Depiction of a device's physical function in the → Hardware tree. The physical channel
is the bottom level in the hardware tree.
Physical output channel A6V10211076_Bedienung_de_to_en.xml.ttxElement of the hardware tree.
153
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
12 Glossary
Term Definition
Corresponds to the output of a device.
Pre-alarm Stage before an → Alarm for information early on should an event occur.
Pre-configuration A sub-configuration of the → Hardware tree, → Detection tree and → Control tree
produced before commissioning the → Fire detection installation.
Q
Quiescent current connection Factor for the current that a device obtains from the detector line when in quiescent
factor condition
R
Radio gateway Interface converter for converting from detector line protocol to radio
Remote transmission → Remote transmission
Renovation mode Mode of operation of the → Zone for maintaining a minimum detection ability during
renovation work. In renovation mode, the detectors are operated at low sensitivity.
Router station Participant in the SAFEDLINK sub-net for the connection between the SAFEDLINK
sub-net and the Ethernet sub-net (C-WEB/LAN) via the Ethernet switch (MM)
FN2008-A1.
RT Abbreviation for → Remote transmission
RT The abbreviation for → Remote transmission equipment
S
SAFEDLINK Physical network of an FS720 fire detection system with the → Network module
(SAFEDLINK) and the network cable
SAFEDLINK station Participant in the SAFEDLINK sub-net with local connection for the PC
Secondary GAP GAP = Global Access Point. Participant in the Ethernet sub-net, in redundancy to the
main GAP, for the connection between the Ethernet sub-net and a standby
management station (BACnet client) and/or for remote access with the Cerberus
engineering tool or Cerberus Remote. Cannot be operated as a DHCP server in the
Ethernet sub-net.
Section Level in the → Detection tree of the → Fire detection system. The → Section is
assigned to the → Area. It is used to combine → Zones.
Separator connector factor Specifies whether a device on the detector line features a line separator.
Single-detector dependency With single-detector dependency, the alarm decision depends on the → Danger level
of one detector. The first detector in the → Zone which detects the corresponding
→ Danger level, triggers a → Fire alarm. → Multi-detector dependency
Site Representation of the → Fire detection installation: The top level in the figure showing
the installed system. Includes → Hardware tree, → Detection tree and → Control tree.
Stand-alone station Standalone station with local connection for the PC only
Standard operation The → Fire detection installation is supplied with mains voltage.
154
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Glossary
12
Term Definition
Standby router station Participant in the SAFEDLINK sub-net, in redundancy to the router station, for the
connection between the SAFEDLINK sub-net and the Ethernet sub-net (C-WEB/LAN)
via the Ethernet switch (MM) FN2008-A1.
station Fire control panel or fire terminal
Stationary C-NET devices Devices that are directly installed without a base, e.g. manual call points, input/output
modules and alarm sounders or radio detectors.
Stub Detector line which is only connected to the fire control panel on one side. In the event
of an open line or short-circuit, not all the → Fire detectors can still communicate with
the → Fire control panel. → Loop
System bus Loop-shaped, redundant networking via C-WEB/SAFEDLINK → C-WEB
→ SAFEDLINK
T
Technical message Events (e.g. from third-party systems) evaluated via sensors or contacts which are
forwarded to the → Fire control panel.
Test activation Activation of → Fire detectors in the → Detector test or → Effects in the → Control test.
Test timeout After a configurable time, the system automatically exits 'Test' mode of operation (→
Detector test, → Control test, → Installation test).
U
Unmanned Switching status of the → Alarm organization, if operating personnel are not present
and cannot intervene should an event arise (alarm, fault)
V
VdS Abbreviation for 'Vertrauen durch Sicherheit', a company in the Gesamtverband der
Deutschen Versicherungswirtschaft e.V. (GDV). Inspection and certification body for
fire detection systems in Germany.
Visibility Defines which part of a → Site can be seen and operated on a → Station
Z
Zone Level in the → Detection tree. A zone has at least one detector. The alarm decision is
made on the zone. The zone is assigned to a → Section or the → Area.
155
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Index
Index
Alarm verification concept
Symbols AVC, 134
universal control Example of verification process, 135
Activating / deactivating , 73 AVC
Alarm verification concept, 134
A Example of verification process, 135
Access level
Levels, Access rights, 96 B
List of all commands and required access levels, Buttons
100 Buttons on the PMI, 17
Logout, 49 Buzzer
PIN, log in, release, 49 'Buzzer off' button, 17
Access rights Volume setting, 86
Access level, stages, 96
Acknowledge C
Button / Functions, 17 Cerberus Remote
Acoustic signals enabling / disabling , 81
Button / functions, alarm devices, 18 General function, 29
Deactivating / activating alarm devices, 69 License key, 81
Activate operating, 83
Alarm indicator (AI), 67 Operating modes, 33
CAUTION note, 66 permanent enabling, 81
Activating Visibility, 81
Activating / deactivating fire control group , 74 Change language, 84
Activating / resetting zone, 70 Command
Evac control, 75 Window command response, 27
ALARM Command confirmation
What to do? Procedure, 34 Hide, 58
Alarm counter Commands
Show information, 76 Command entry Basics, Execute, function-
Alarm delay oriented / object-oriented, 53
Switch off alarm delay, 34 List of all commands and required access levels,
Alarm delay off 100
156
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Index
157
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Index
auto-configuration, 78 Scrolling, 31
Numeric key
Shortcut, Menu selection, Command execution,
S
32 Sabotage ALARM
Opening the control panel, 149
O Sabotage monitoring, 48
Opening the control panel Scroll bar
Maintenance, 149 Indication of position and list length, 31
Sabotage ALARM, 149 Scrolling
Operating Indication of position and list length, 31
Cerberus Remote, 83 Scrolling in option lists, command lists, element
Operating modes category lists, 31
Operation modes, Normal operation, Test, Numeric key, Menu selection, Command
Isolation, 93 execution, 32
158
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Index
Show information
Alarm counter, remote transmission, 76
Cerberus-Remote
connect, 81, 81
Standby
Visibility, 98
Summer time
Setting date and time, 87
Switching off / Switching on
DANGER-Note, 37
Detector, 40
Remote transmission, fire, 44
Temporary switching-off, 42
System maintenance
Service reminder, 149
System test
CAUTION note, 65
T
Temporary switching-off
Section, duration, 42
Time and date
Set, 87
Topology, 110
Select element, hardware tree, detection tree,
control tree, 60
V
Version
Displaying station version, 91
Visibility
Definition, 98
extended visibility, 99
standby, 98
Z
Zone
Activating / resetting , 70
159
Building Technologies A6V10211076_d_en
Fire Safety & Security Products 02.07.2010
Issued by © 2008-2010 Copyright Siemens Switzerland Ltd
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Industry Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
Fax +41 41-724 35 22
www.siemens.com/buildingtechnologies