METHOD STATEMENT For Kitchen
METHOD STATEMENT For Kitchen
METHOD STATEMENT For Kitchen
Description
Technical afire Method of statement
N.C.C.
Method of Statement
Document control
1
Projects Department
Description
Technical afire Method of statement
Document information
Document History
Document Approvals
Table of contents
2
Projects Department
Description
Technical afire Method of statement
1. Introduction
2. Method Statements
1. Introduction :
3
Projects Department
Description
Technical afire Method of statement
This Method Statement describes the management arrangements and systems of work to
be adopted by AL NOUR Construction Co. during civil and electromecanical engineering works.
2. Method Of Statements :
HSSE dept. PTW to be issued with necessary requirements such tool box
4
Projects Department
Description
Technical afire Method of statement
5
Projects Department
Description
Technical afire Method of statement
2.2.1 EXCAVATION
1- The following specific site conditions should be taken into accounts for safe
excavations:
a- Traffic
c- Soil
6
Projects Department
Description
Technical afire Method of statement
f- Weather
2- Before any excavation actually begins, the standard requires the employer to
determine the estimated location of utility installations: Sewer, telephone, fuel,
electric, water lines or any other underground installations that may be
encountered during digging.
6- Workers must be supplied with and wear any personal protective equipment
deemed necessary to assure their protection.
7- All spoil piles will be stored a minimum of two (2) feet from the sides of the
excavation. The spoil pile must not block the safe means of egress.
10- A competent person will inspect all excavations and trenches daily, prior to
employee exposure or entry, and after any rainfall, soil change, or any other time
needed during the shift. The competent person must take prompt measures to
eliminate any and all hazards.
7
Projects Department
Description
Technical afire Method of statement
11- Excavations and trenches 4 feet or deeper that have the potential for toxic
substances or hazardous atmospheres will be tested at least daily. If the
atmosphere is inadequate, protective systems will be utilized.
The OSHA standards define soil classifications within the simplified soil classification
systems, which consist of four categories:
a- Stable Rock
b- Type A Soil
c- Type B Soil
d- Type C Soil
Stability is greatest in stable rock and decreases through type A and B to type C, which
is the least stable.
Stable Rock: is defined as natural solid mineral matter that can be excavated with
vertical sides and remain intact while exposed. (Example: granite or sandstone).
Type A Soil: are cohesive soils with unconfined compressive strength of 1.5 tons per
square foot or greater. (Example: clay, silty clay, sandy clay, clay loam)
Type B Soil: are cohesive soils with an unconfined compressive strength greater than
0.5 tons per square foot but less than 1.5 (tsf)
Type C Soil: are cohesive soils with an unconfined compressive strength of 0.5 tsf or
less.(Example: gravel, sand and loamy sand, submerged soil, soil from which water is
freely seeping.
There are two basic protective systems for an excavation and trenches:
The protective systems shall have the capacity to resist without failure all loads that are
intended or could reasonably be expected to be applied to or transmitted to the system.
8
Projects Department
Description
Technical afire Method of statement
Type C 1½ : 1 34 deg.
Shoring Systems:
Shoring is the provision of a support system for trench faces used to prevent movement
of soil, underground utilities, roadways, and foundations. Shoring is used when the location or
depth of the cut makes sloping back to the maximum allowable slope impractical. Shoring
systems consist of posts, wales, struts, and sheeting
9
Projects Department
Description
Technical afire Method of statement
Spoil:
Temporary spoil must be placed no closer than 2 ft. (0.61 m) from the surface edge of
the excavation
Soil replacement will be from the bottom of excavation to the foundation level with thickness
50 cm with using sand and dolomyte breaks.
Replacement will be in two layers, every layer 25 cm.
All replacement layers will rolled and uniformly copmacted to 95% of the maximum
laboratory density.
10
Projects Department
Description
Technical afire Method of statement
2.2.2 BACKFILLING:
NCC shall not begin backfilling until approval has been obtained from
2. Backfill Material
a. All backfill material shall meet latest edition of ASTM D2321 unless otherwise
there is a deficiency due to a rejection of part thereof, the contractor shall provide
11
Projects Department
Description
Technical afire Method of statement
3. Do not leave trenches open overnight without backfilling to the natural ground level.
Steel plates (1/2” in thickness) may be used to cover open trenches only with the
2.2.3 DEWATERING:
At locations where the excavation extends below ground water table, a
dewatering system is to be provided .The resulting ground water level
shall be at a depth below the excavation level so as to allow the safe
and proper execution of works.
**MATERIALS
**PREPARATORY WORKS
**WORK METHODOLOGY:
12
Projects Department
Description
Technical afire Method of statement
the connection between the new semells and existing columns/semells (including
chisel concrete cover of the contact area, cleaning the steel bars with steel
brush/sand blasting to remove any concrete remains, rust to ensure proper
bonding, dowels plantation, approved epoxy material....etc)
13
Projects Department
Description
Technical afire Method of statement
The Waterproofing System shall be applied over clean, dry and smooth concrete surface.
The Waterproofing System shall be fully torched over 3 coats of hot
oxides bitumen paints on walls, footings, columns neck
1- Purchase the correct size of paintbrush. Foam brushes come in 1, 2 and 3 inch
widths. They have a beveled end for cut-in work and a wooden handle.
2- Prepare a can of polyurethane by stirring it so it is smooth. Prepare the surface of the
project by sanding and wiping with a tack cloth to remove dust and grit.
3- Dip the foam paintbrush into the polyurethane. Fill it only half way up. Overloading
will cause drips. Begin painting the surface with long, smooth strokes. When the
polyurethane is almost out of the brush, lift the tip to a 45-degree angle and pull off
the board so that there are no lines.
4- Continue until the project is completed. Either dispose of the brush or if you desire,
wash the brush under cold water. Squeeze the polyurethane from the foam until the
water runs clear. Dry and use another day.
14
Projects Department
Description
Technical afire Method of statement
Mortar mixes shall be accurately gauged by volume using approved gauge boxes.
The ingredients shall first be mixed dry until thoroughly mixed to a
uniform color before water is added to the mix.
For work below floor slab level and work in contact with the ground: 1 part sulphate-
resisting cement: 3parts sand.
15
Projects Department
Description
Technical afire Method of statement
***MOVEMENT JOINTS:
The movement joints to be 12mm wide in the places between the existing and the
extension building.
The joints shall be straight vertical and formed with uncut faces of the
blocks to each side.
16
Projects Department
Description
Technical afire Method of statement
**MATERIAL REQUIREMENT:
Material approval for Sand, cement and water has to be obtained from
QC prior to take up the plastering work.
Cement shall be of Portland cement conforming to BS 12, SRC shall comply with BS 4027.
Sand for mortar shall be from khatatba or dune sand washed clean free
from clay, chalk, shells organic materials and other impurities. The sand
shall comply with BS 1200.
Water shall be potable.
** RENDERING:
Mortar mix shall be accurately gauged by volume using approved gauge boxes.
The ingredients shall first be mixed dry thoroughly to obtain a uniform
color before water is added to the mix.
Rendering shall be composed of one part cement to three parts sand by volume.
Only sufficient material shall be prepared which can easily be applied
within the initial setting time of the material and no water shall be added
after the initial mix. Unset plaster shall be discarded when initial set
occurs and no reconstituted mix shall be allowed.
Surfaces to receive plasterwork shall be brushed down to remove dust
loose flecking material shall be removed and the projections of mortar
and the like shall be clipped off or ground away. Surfaces shall be
dampened sufficiently to ensure uniform absorption.
Backgrounds shall be prepared as required to suit the finish being
applied. Dense, smooth concrete shall be keyed with PVA emulsion
bonding agent, block work shall be hacked if necessary.
17
Projects Department
Description
Technical afire Method of statement
**SURFACE PREPARATION:
18
Projects Department
Description
Technical afire Method of statement
**APPLICATION:
19
Projects Department
Description
Technical afire Method of statement
Gypsum Ceiling
1- Measure the ceiling starting the one end along a wall perpendicular to the joists.
2- Find the joist that's closest to being 8 feet from the wall, without being further than
that.
3- Measure from the middle of the joist to the wall.
4- Use your razor knife to score and snap a piece of gypsum board at that length, running
the blade alongside your t-square to keep it straight.
5- Set up two ladders, one by the starting wall, the other under the joists to which you
measured.
6- With an assistant, hold the gypsum board up to the ceiling, with the cut end facing the
wall and the uncut end lining up with the middle of the joist.
7- Shoot drywall screws every six inches or so along the edge of the board where it is
under the joist.
8- Do the same for the rest of the joists above the board. (You will be able to judge the
positions of the joists behind the board based on where they come out from the side of
it.) Make sure to completely sink the screw heads below the surface.
9- Hang the rest of the boards in the same manner, positioning them end to end, in
courses, always meeting at the joists.
10- Stagger the positions of the board between courses, so there are no four-way
intersections.
20
Projects Department
Description
Technical afire Method of statement
11- Press meshes dry walling tape over all the seams between the boards. Use a drywall
knife to spread joint compound over the tape, making a smooth line about 4 inches
wide.
12- Spread a little compound over the sunken screw holes and Let it dry for about 4 hours.
13- Sand the seams and screw holes by hand to smooth out the dried joint compound.
14- Apply another layer of joint compound over the first along the seams, making the seams
a little wider.
15- Let it dry, sand it, and apply a third, very thin final coat.
21
Projects Department
Description
Technical afire Method of statement
a. Open an approved shop drawings. These shop drawings consist of approved Toilet
details and mechanical pipe sleeves location for both indoor unit refrigeration pipes and
sanitary fixtures ventilation.
b. Gypsum partitions outer side and water proofing activity should be done first before
installation.
c. Waiting pipes, stub pipes and fittings from risers and underground pipes should be
present before starting inside the toilet.
d. Assign the location of pipes in the wall or floor that is exactly as mention on the
approved toilet details shop drawing. Mark with the line corresponds to the total area
to bury the pipe in the wall or floor (for lavatory and A/C drain).
e. Use block cutter or simply portable grinder to cut a side of partition side continuously
along the line that had been marked. Absolute care should be done not to cut or
damaged the pre-installed pipe sleeves of fixture vents and A/C indoor unit.
f. Standard fittings and materials must be used and all pipes and fittings must be joined
using the approved glue. Sanitary tee fittings for vent are fixed inclined 45° or slope
from center line of pipe it serve.
g. Level of the slab should be identified by surveyor before proceeding installation. Also
locate points as alternative reference point for pipe and pipe fittings installation.
h. Install / layout the pipes at designated height, location and slopes (1% slope for sanitary
fixtures and 0.5% slope for A/C drain).
i. Sanitary fixtures outlet location should also be installed and identified.
22
Projects Department
Description
Technical afire Method of statement
j. Connection of drainage pipes other than water closet drain (i.e. A/C drain, lavatory
drain, bidet drain, bathtub drain) should be slope toward gully trap floor drain based on
the approved toilet details shop drawings.
k. Pipes and pipe fittings connection should be on the compacted fine sand and partly
small of cement mortar as its support. Height distance between gully trap bottom and
slab should be two (2) centimeter for all toilets.
l. Absolute care should be imposed not to damage the water proofing upon installation.
m. Install sleeves for pipes passing through the concrete or masonry walls Put sealant in
between the pipes and sleeves.
n. Check the pipes securely fixed, joint and capped before leak testing.
o. Leak test for the installed pipes is to be carried-out with presence of inspector Engineer.
p. After the approval of Inspector Engineer, cover the pipes with the internal side of the
gypsum partition.
a. Open an approved toilet detail shop drawing. This drawing should be accompanied with
the approved location of mechanical pipe sleeves for both A/C indoor unit refrigeration
tubes/pipes and sanitary fixtures ventilation.
b. Gypsum partitions outer side and water proofing activity should be done first before
installation.
c. Locate the pipe locations in the wall and mark with the line corresponds to the total
area to bury the pipe in the wall.
d. Use approved pipes, pipe fittings, and joining compound.
e. For solvent cement joints:
23
Projects Department
Description
Technical afire Method of statement
24
Projects Department
Description
Technical afire Method of statement
n. Leak test the pipes and proved tight under a water pressure not less than 1½ its working
pressure under which it is to be used. Leak test the pipes for four (4) hours. Do not test
the pipes without the presence of inspection Engineer.
o. After the approval of Inspector Engineer, cover the pipes with the internal side of the
gypsum partition.
Preparation:
a. Sand Bed under Floor Tiles, thickness should be maintained as necessary to obtain finish
floor levels indicated on Approved Shop Drawings.
b. Manual spreading and compaction to obtain uniform depth and distribution remove
stones and foreign materials.
c. Background to receive wall tiles on vertical surfaces to finished with ceramic wall tiles
are to be coated with dash coat to be wet cured for a minimum of 2 days prior to setting
of tiles.
d. Lightly Rinse with water prior to setting tiles.
e. Perform cutting and drilling of tile without marring visible surfaces.
f. Fit tile to electrical outlet, piping, fixtures and other penetration as shown in the shop
drawing.
g. Ceramic tiles are to be soaking in water for one hour prior to setting in place.
25
Projects Department
Description
Technical afire Method of statement
a. Obtain center lines for both axes as per approved shop drawing.
b. Floor tiles are to be set using thick wet mortar bedding on uniformly distributed sand
beds. Mortar mix shall be 1:3 (1 part Portland cement and 3 part sand) Thickness of
bedding shall be between (20-25mm). Each tile is to be beaten to ensure bedding of
tiles.
c. Start installing tiles in 1 direction alongside of the centerline
d. Install tile on floor with 3mm paver tile. In wet areas provide slope to drains.
e. Install stone threshold as per approved shop drawing at location indicated.
Grouting
a. Clean joint by brush to ensure that thickness of tile is clear and free of foreign material.
b. Add 5 kg of grout to 1.8 liter of water and mix until thick creamy paste is produced;
allow standing for 10 minutes.
c. Apply grout to the joint spaces between tiles using a sponge or soft cloth.
d. Work the mixture into the joints grouting the ceramics tile thickness and around the
edges.
e. Remove surplus from the face of the tiles with dry cloth and run the tip as a gloves
finger or a rounded piece of wood along the grouting.
f. When the grout is dry, clean the tiles with a damp sponge.
a. On completion of placement and grouting, clean all ceramic tile surfaces. Remove
cement grout residue from tile as soon as possible.
26
Projects Department
Description
Technical afire Method of statement
b. Leave finished installation clean and free of cracked, chipped, broken, unbounded and
otherwise defective tile work.
c. Prohibit foot and wheel traffic from tiles floors at least 7 days after grouting is
completed.
d. Provide fixed protection or other heavy covering during construction period to prevent
staining, damage and wear.
Terminating the phase, neutral and earth wires to the internal devices block at
respective terminals it is installed.
Locations: Drawings generally show approximate locations of outlets and equipment.
Exact locations shall be determined from interior finishing and detail drawings. Any
condition that would place an outlet in an unsuitable location shall be referred to the
Engineer switches ,will be at strike sides of doors ,In location outlets allow for
overhead pipes, ducts, variations in arrangements, thickness of finishing, window
trim, paneling and other engineering features.
Mounting heights for outlet boxes and similar equipment will be uniform within the
same or similar areas.
Lighting switches and socket outlets; general]y at 1250 mm and 450 mm from
finished floor level respectively. Switches for long dimensions vertical and operating
handle, if the toggle type, up when in the on position.
Additional Outlets to those shown: on the drawings will be provided as required
equipment manufacturers for control or other wiring.
Recessed Outlet Boxes Make neat openings, to the satisfaction of the Engineer,
allowing for thickness of finishing, and use extension rings if required. Damaged
finishing to original condition before installation of fittings or plates.
27
Projects Department
Description
Technical afire Method of statement
Grouped Outlets arrange neatly so that use of fitting is convenient and clear.
** CONNECTION OF Appliances:-
PANEL BOARDS:-
**INSTALLATION:-
a) Fixing Generally:
Align level and securely fasten panel boards to structure.
Do not use connecting conduits to support panel boards.
Close unused openings in the panel board cabinets.
b) Panel board interiors: Do not install in cabinets until all conduit connections to
cabinet have been completed.
c) Wiring inside Panel boards: Neatly arranged, accessible and strapped to prevent
tension on circuit breaker terminals. Tap-off connections are to be split and bolted
type, fully insulated.
d) Trim: fix plumb and square prior to painting. Fix trim for flush mounted cabinets Flush
with wall surface finish.
e) Mounting Heights: Top of trim 1800 mm above finished floor, unless otherwise
indicated.
f) Circuit Directory: Create a directory to indicate installed circuit loads after balancing
panel boards’ loads. Obtain approval before installing directories.
28
Projects Department
Description
Technical afire Method of statement
**IDENTIFICATION:-
**CONNECTION:-
29
Projects Department
Description
Technical afire Method of statement
Supply, install and test fire alarm outlets using (2 x 1.5 mm² screened fire retardant cables
105ºC) inside EMT conduits 20 mm for exposed installation and inside medium gauge
RPVC conduits with outer diameter 20 mm for embedded installation; the price includes
cables, conduits and all necessary accessories(boxes, fittings, fixation base, flexible
conduits, back box for detector fixation .....etc.) and ancillary works as specified and as
shown in the drawings .
Supply, install and test telephone outlet using 2 pairs (2x0.6) cables inside heavy gauge
RPVC conduits with outer diameter 20 mm for exposed installation from outlet to telephone
box ; the price includes cables, conduits, boxes and all required accessories, fittings and
material to complete the work and according to specifications and drawings.
supply, install and test TV system outlet using RG6 and RG11 cables inside heavy gauge
RPVC conduits with outer diameter 20 mm for exposed installation to achieve at minimum
65 DB at outlet; the price includes cables, conduits, boxes and all required accessories,
fittings and material to complete the work and according to specifications and drawings.
supply, install and test speaker outlet using shielded audio cables (2x1.5)mm² inside heavy
gauge RPVC conduits with outer diameter 20 mm for exposed installation ; the price
includes cables, conduits, boxes and all required accessories, fittings and material to
complete the work and according to specifications and drawings.
30
Projects Department
Description
Technical afire Method of statement
31
Projects Department
Description
Technical afire Method of statement
Professional sub contractor which supply equipment's will act this task with arrange with
NCC.
Insure that all facilities like electrical wire was installed and tested according to the required
voltage.
Water supply and sewage water also check to insure the proper connection.
32
Projects Department
Description
Technical afire Method of statement
Tests switch and outlet tests together with insulation resistance of wiring installations.
Operation: Devices will be tested for operation and intended at full load without sins of
heating.
Equipment will be insulation tested and observed, with respect to undue Heating and
performance in general.
Work will be inspected for correct fixing and workman shop , outlet device are tested for
voltages and polarity
** CLEANING:
33
Projects Department
Description
Technical afire Method of statement
2.2.14 Scaffolding:
34
Projects Department
Description
Technical afire Method of statement
APPLICABLE PUBLICATIONS:
35