PLC Connecting Ok
PLC Connecting Ok
PLC Connecting Ok
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi FX3U (Ethernet)
PLC I/F Ethernet
Port no. 5001(default) Refer to Module Setting
PLC sta. no. 0 (default) Refer to Module Setting
PLC Setting:
Fx3u-ENET module setting:
Before using Ethernet module, use GX Developer / FX Configurator-EN to set the Ethernet
module, the FX3u-ENET module setting steps are shown below.
Step3. Connect PLC via serial port for setting IP address first.
PLC Connection Guide
Step4. After finishing the PLC settings, select Tools/FX special function utility/FX
Configurator-EN.
Step7. In Ethernet open settings, press “End” after setting the parameters below.
(The first Protocol means using GX Developer to communicate with module, the max.
“Fixed buffer communication preocedure” is 4 units.)
PLC Connection Guide
Or
PLC Connection Guide
Step8. After setting the parameters of PLC, restart for Ethernet communication.
Device Address:
Bit/Word Device type Format Range Memo
B X OOO 0 ~ 571 Input
B Y OOO 0 ~ 571 Output Relay
B M DDDD 0 ~ 7999 Internal Relay
B T DDD 0 ~ 511 Timer Contacts
B C DDD 0 ~ 255 Counter Contacts
B SM DDDD 8000 ~ 8511 Special Int. Relays
B D_Bit DDDDDdd 0 ~ 1799915 Data Register Bit Access
B S DDDD 0 ~ 4095 Step Relays
W TV DDD 0 ~ 511 Timer Value
W CV DDD 0 ~ 199 Counter Value
W D DDDD 0 ~ 7999 Data Registers
W CV2 DDD 200 ~255 Counter Value
W SD DDDD 8000 ~ 8511 Special Data Registers
W R DDDDD 0 ~ 32767 File Register
PLC Connection Guide
Wiring Diagram:
Ethernet cable: