Biogas Safety Rules
Biogas Safety Rules
Biogas Safety Rules
Biogas Installations
Fachausschuss “Chemie”
(Technical Committee “Chemistry”)
Department Explosion Protection
Resp.: Dr. Dyrba
Kurfürsten-Anlage 62
69115 Heidelberg
Germany
TÜV Süddeutschland
Niederlassung Ulm
Benzstr. 17
89079 Ulm
Germany
2
Status 09/05/2002*
_______________
Work Document
69
_______________
Biogas Installations
3
TABLE OF CONTENTS
1. General.......................................................................................................................... 6
1.1 Definitions ............................................................................................................... 6
1.2 Gas Schematic of an Agricultural Biogas Installation .............................................. 7
1.3 Characteristics of Biogas ........................................................................................ 7
1.4 Dangers .................................................................................................................. 8
1.5 Note for Permits ...................................................................................................... 8
2. Facility Parts................................................................................................................. 9
2.1 General ................................................................................................................... 9
2.2 Fermentation Vessel/Fermenter/Reactor .............................................................. 10
2.3 Liquid Manure Storage.......................................................................................... 11
2.4 Gas Storage .......................................................................................................... 11
2.5 Facility Control and Process Control (PLT) ........................................................... 15
2.6 Gas Treatment ...................................................................................................... 16
2.7 Gas Pipes ............................................................................................................. 16
2.8 Armatures, Safety Systems, and Gas Carrying Facility Parts ............................... 17
3. Potentially Explosive Areas, Ex-Zone Classification .............................................. 19
3.1 Requirements/Marking .......................................................................................... 20
3.2 Classification of Zones .......................................................................................... 20
3.3 Requirements for Equipment In Explosive Areas .................................................. 25
3.4 Dimensioning of the Area of Zone 1...................................................................... 25
3.5 Dimensioning of the Area of Zone 2...................................................................... 26
4. Installation Rooms ..................................................................................................... 26
4.1 Gas Firings............................................................................................................ 26
4.2 CHP Plant ............................................................................................................. 26
5. Operation .................................................................................................................... 28
6. Fire Protection............................................................................................................ 29
Exhibit 1 Commissioning/Reoperation of a Biogas Facility .......................................... 30
Exhibit 2 Test Certificate for a Biogas Foil Storage Vessel .......................................... 31
Exhibit 3 Sample Operational Manual for a Biogas Facility in Normal Operation ...... 34
Exhibit 4 Operational Record (example)......................................................................... 36
Exhibit 5 Sample Operational Manual for a Biogas Installation during Malfunction .. 37
Exhibit 6 Shut-Off of a Biogas Installation ..................................................................... 38
Exhibit 7 Operational Instruction ..................................................................................... 39
Exhibit 8 Proposed Content of an Alarm and Hazard Protection Plan ........................ 40
Exhibit 9 Example of a Zoning Division.......................................................................... 41
Exhibit 10 Tightness of Equipment................................................................................. 42
Exhibit 11 Examples of Further Requirements and Regulations ................................. 44
4
Preliminary Remarks
The Safety Standards for Agricultural Biogas Installations (Work Document 69)
comment and substantiate the requirements for installation and operation of agricultural
biogas installations, in the sense of the Instruction for Implementation of § 1 of the
Health and Safety Regulation “Work Places, Edificial Facilities, and Installations” (VSG
2.1) of Agricultural Cooperative Associations.
They shall provide advice to the planning office, the construction company in charge of
the installation, and to the operator relative to the installation and operation of
agricultural biogas installations that are operated with an operating pressure of less than
0.1 bar.
The Safety Standards represent a summary of the most important regulations, and thus
provide references to applicable regulations. In addition, the generally accepted rules of
techniques are applicable; see Exhibit 11 for examples. Deviations are acceptable if the
safety can be ensured in a different manner.
5
1. General
1.1 Definitions
6
1.2 Gas Schematic of an Agricultural Biogas Installation
Gas
Storage CHP
Fermentation
Vessel
Necessary components Optional components
AV Shut-off valve FF Gas fine filter
AL Blow-off pipe GF Gas torch
HKW CHP Plant GZ Gas counter
DS Over/under press’ protection LD Air dosing pump
O Access opening MA U-Pipe manometer
S Flame return safety RV Return valve
KA Condensate separator SG Observation window
NA Emergency switch
VS Automatic shut-off valve
UW Low pressure monitor
7
1.4 Dangers
The following dangers and risks can arise when using biogas:
• Danger for life and health by suffocation or poisoning in ducts or containers,
e.g., H2S, CH4, CO2
• Health hazards by co-fermentation matters
• Explosion of ignitable gas/air mixtures
• Development of fires
• Freezing of gas or substrate pipes, causing consequently an unintended
blockage of pipes
• Development of condensates, particularly through cooling of water saturated
gases, with the danger of freezing and blocking of pipes
• Plugging of pipes, particularly of gas and substrate pipes
2. Facility Parts
2.1 General
Biogas facility parts are facilities, structures, buildings, and rooms that are necessary
for operation and safety of the biogas facility.
2.1.1 Those parts of the biogas facility that are installed above ground outside have to
have safe foundations. They have to be installed in a way that they are well
accessible. Sufficient stability has to be ensured.
2.1.2 In order to avoid the appearance of differences of electrical potential, all facility parts
that are electrically conductive have to be connected with each other, as well as with
the protective conductor and the ground conductor (potential equalization).
2.1.3 Gas transporting parts of the biogas facility have to be protected against chemical
influences, as well as against mechanical damage in risk areas (e.g., protection
against collision in driving areas).
9
2.1.4 Maintenance and operation stands, as well as operational panels, for stirring
machines, pumping devices, and rinsing devices should be installed above ground. If
that is not possible, a fixed forced ventilation system has to be existent. Before
accessing the area, sufficient air exchange has to be ensured (user manual and
markings have to be observed).
10
- Self-closing flaps for vertical openings
- Fill channels with covered vertical openings
If the above measures cannot be used because of the consistence of the
decomposition material, other protective measures with the same safety for
personnel against falling into the facility have to be used.
2.2.6 Safety Installations against Gas Hazards at Fill Openings
Fill openings should be located relative to the main wind direction in a way that gases
are led away from the operating area.
For locations inside buildings, fermentation gases have to be forced to exit. The
installation for conducting gases off has to be automatically switched on during filling.
If necessary, an operation stand has to be foreseen for filling funnels for safe control
of the rinsing hose.
The gas dangers in the close proximity of the filling device have to be pointed out.
2.2.7 Discontinuous Fermentation (e.g., batch)
No gas dangers shall develop during charging or removal of containers for
discontinuous fermentation.
2.4.4 Doors
Doors have to open toward the outside and be lockable.
2.4.5 Safety Distances (a)
In order to reduce the interaction in an event of damage, or in case of fire to prevent
encroaching on close-by installations, as well as for the protection of a gas tank from
an event of damage such as heating caused by fire, safety distances (fire breaks)
according to Tables 2.4.5.2 to 2.4.5.4 have to be foreseen between the gas tanks
and neighboring facilities, installations, buildings, or traffic ways not belonging to the
biogas facility. Inside the biogas facility, safety distances of at least 6 meters are to
be foreseen between gas tank and rooms for installation of combustion engines or
electrical switching installations (see Section 2.4.5.5).
Remark
If several gas tanks of a facility have to be recognized as a unit because of their
arrangement, the safety distances (a) result from the addition of the individual gas
volumes.
2.4.5.1 Dimensioning of the Safety Distances
For above ground installations, the safety distance is measured from the vertical
projection of the rim of the storage container. For safety distance (a) see Sections
2.4.5.2 to 2.4.5.5.
2.4.5.2 Above Ground Fixed Gas Storage
These include also foil storage in fixed containers or installation rooms, e.g., in former
fermentation food silos or containers.
12
Gas volume in To 300 More than More than More than Material selection for outer
m3 per tank 300 to 1,500 to 5,000 walls
1,500 5,000
Safety 3 3 6 10 Not flammable,
Distance (a) in construction material class
meters A, fire-retardant (F30),
smoke protected
Safety 3 6 10 15 Not flammable,
Distance (a) in construction material class
meters A, smoke protected
Safety 6 10 15 20 Other, from flammable
Distance (a) in materials of construction
meters material class B
2.4.5.4 Balloon and Pillow Storage as well as Foil Storage above Liquid Manure Storage or
Fermentation Vessels
Safety Distances
Gas volume in m3 To 300 More than 300 to More than 1,500 to More than 5,000
per tank 1,500 5,000
Safety Distance 4.5 10 15 20
(a) in meters
13
Picture: Protection Wall Arrangement
Biogas Storage
Building
Biogas Storage
Protection Wall
Building
Biogas Storage
Protection Wall
Building
14
2.4.5.6 Requirements within the Safety Distances
Within the safety distances:
- No combustible materials in quantities above 200 kg may be stored without
additional protection measures, and there may be no other buildings, public
streets, or roads located. Additional protection measures may include, for
example, fire prevention, fire protection, or fire fighting measures (see, e.g.,
Section 2.4.5.5).
- Traffic routes are permissible if necessary for the operation of the facility.
- Machines and activities that could lead to an endangerment for the gas tank (e.g.,
welding, cutting) are forbidden without additional protection measures.
- Fire, open light, and smoking are forbidden.
2.4.5.7 Marking
Areas in which safety distances have to be respected, including, as case may be,
also access to gas tanks, must be marked according to VSG 1.5.
Examples for Marking
15
Central Emergency Shut-off System and Shut-Off Criteria
Both quick acting gate valves in the gas safety line have to be controlled in a way
that the gas supply to the engines is not released until start of operation and
interrupted during operation under the following conditions:
- Exceeding of rpm
- Falling below the minimum gas pressure
- Exceeding the maximum gas pressure
- Activation of the temperature limiter in the cooling circuit
- Use of the emergency stop switch
- Failure of control power
- Activation of the gas alert and fire detection systems, or the temperature
monitoring system of the air in the room
- Failure of the ventilation system
Control devices with safety function have to be designed to be safe themselves,
unless they are secured by means of a redundant system, e.g., a mechanical over
pressure safety device or a free level overflow pipe against overfill.
17
2.8.3 It shall be possible to operate armatures from a safe stand. Armatures for gas
extraction have to be secured against unauthorized or inadvertent opening, e.g., by
securing the handle.
2.8.4 Condensate separator and safety systems have to be accessible at all times.
Pressure control units with sealing liquid in over or under pressure safety devices, as
well as condensate and dirt separators, must be controllable and maintainable easily
and safely, without having to enter into pits or shafts.
Pressure control units with sealing liquid have to be designed in a way that in case of
actuation the sealing liquid cannot exit but rather flows back automatically. In order to
avoid emission of gas, the pressure of water seals that function as a condensate
separator rather than as an over/under pressure safety device has to be at least five
times the actuation pressure of the over pressure safety device.
2.8.5 In front of gas consumption devices, such as heating boilers and CHP facilities, flame
traps have to be installed as closely as possible to the consumer in accordance with
the instructions by the manufacturer. Only certified armatures have to be used.
Gravel pits have to be type certified.
Recommendation
Existing facilities with gravel pits without type certification should be refurbished with
type certified gravel pits or type certified flame filters when major changes of the gas
system or an exchange of an aggregate are implemented. It is recommended that the
refurbishment be executed within five (5) years of the publication of these safety
regulations.
The arrangement of components has to be done in accordance with Schematic 1.2.
2.8.6 Arrangement of Over and Under Pressure Safety Devices
2.8.6.1 Each gas tight vessel in which biogas is being produced has to be equipped with
at least one safety device against exceeding or under-running of the pressure.
The gas escaping in case of actuation has to be led off safely. The reliability and
suitability of the safety device has to be proven by component marking and
individual test. It has to be ensured by means of a separate under pressure
sensor or a similar device in the gas system that a forced shutdown of the gas
consumption equipment and a malfunction message are initiated before actuation
of the under pressure safety device.
The over and under pressure safety devices within the facility have to be
designed, arranged, and monitored, and the biogas facility as a whole has to be
operated in a way that all operational states of the fermenters can be safely
controlled. The formation of foam represents a malfunction and has to be
prevented by means of operational measures within the facility. Damage by the
formation of foam has to be prevented, e.g., by a burst safety device, a pressure
relief safety device, or sufficient storage volume. The suitability of the over/under
pressure safety device has to be proven by means of a comprehensible
calculation and a functional description. If designed for submersion, it has to be
ensured that it does not run empty or dry and does not freeze.
18
The operational manual has to point out that the function of safety devices has to
be verified always after facility malfunctions, and once a week during normal
operation.
Note
Safety devices may become ineffective, for example, by sluggishness caused by
dirt or corrosion, by plugging, or by freezing.
A change of the interior pressure can be caused by:
- gas production without discharging,
- addition or discharging of gas or substrate by means of pumps.
Liquid seals as a safety device have to be designed so that the sealing liquid
flows back automatically with over or under pressure.
The feeding pipes for over or under pressure safety devices must not have the
possibility for manual shut-off.
Over and under pressure safety devices have to safe against freezing.
2.8.6.2 Relief pipes for over or under pressure safety devices have to:
- open at least 3 meters from the ground, and
- open one meter above the roof or the rim of the vessel, or
- be away from buildings and traffic ways by at least 5 meters.
Alternately, free flow off has to be proven. The one-meter area around the
opening of the relief pipes is Zone 1.
The blow off of biogas in case of malfunctions of the gas consumption facilities is
not admissible without limitations. If the gas volumes to be expected in such
cases exceed a volume flow of 20 m3/h, the blow off volumes have to be limited to
such value by appropriate measures, or gas burn off has to be used.
Appropriate measures are, e.g.:
- Existence of a second gas consumption facility, independent from each other,
and corresponding reduction of the substrate supply. Not later than 48 hours
after the malfunction event, the remaining gas consumption has to be in a
position to reduce the residual blow off gas volume to 20 m3/h.
- Proof of a suitable location for positioning the connection possibility and the
availability of a mobile burn off facility within 24 hours.
The exhaust gases of the gas burn off have to be conducted away over the roof
or through an exhaust pipe, which has to be away from buildings or traffic routes
by at least 5 meters, and the opening has to be located at least 3 meters above
ground.
19
3.1 Requirements/Marking
Since one has to consider the existence of explosive gas/air mixtures in the vicinity of
gas tanks and fermentation vessels, zones have to be implemented in accordance
with Section 3.2. Measures for the avoidance of ignition sources have to be taken in
accordance with BGR 104 Section E 2, “Measures that Prevent the Ignition of a
Dangerous Explosive Atmosphere” in explosive areas, e.g., prevention of sparking,
interdiction of fire and smoking.
Explosive areas have to be marked by using appropriate signage with black letters on
yellow background, e.g.:
Zone 0 contains areas in which the dangerous explosive atmosphere, which consists of a
mixture of air and gases, vapors or mists, is present continuously, long-term, or
often.
Remarks
The term “often” has to be understood as “most of the time”.
Explanations
During normal operation of biogas facilities, Zone 0 is practically non-existent. In
addition, the fermentation vessel does not contain explosive mixtures. At most, the
intake manifold of the combustion engine or the combustion chamber for the gas
burn off contains, in accordance with their purpose, an explosive mixture. This area is
sealed off from the remaining gas system by flame traps.
Zone 1 contains areas in which it has to be taken into account that a dangerous explosive
atmosphere consisting of gases, vapors, or mists develops occasionally.
Explanations
20
Occasionally, an explosive mixture develops in biogas facilities around the openings
of blow off pipes of gas over pressure safety devices and of gas burn off installations
(see Section 3.4).
Zone 2 contains areas for which the development of a dangerous explosive atmosphere
consisting of gases, vapors, or mists does not have to be considered, but if it
develops anyway, then only with a low probability and short term.
Explanations
The rare appearance of explosive gas mixtures can generally develop during a
malfunction or during service activities.
In the area of the fermentation vessel, this is valid for the maintenance and cleaning
openings and the interior of a continuously operated fermenter. For gas storage, this
concerns the gas tank and the vicinity of the ventilation inlets and outlets (see
schematic drawing).
21
Examples for Ex-Zones
Observation glass,
technically tight
Stirring machine,
service opening
Prep pit
Fermentation
Vessel Over pressure
Safety device
Protection wall,
smoke protected
F 90
22
Outside Foil Gas Storage
Top View
Biogas storage
Protection wall
Building
Protection wall
Building
Biogas storage
23
Example Ex-Zones
Fermentation vessel with foil cap
Protection wall
Opening
ventilation
Building
Biogas storage
Protection wall
Opening
ventilation
Building
Biogas
storage
24
Top View
Biogas storage
Ventilation intake
Ventilation
outlet
Building
Protection walls
25
as an operational exit of biogas has to be accounted for, as well as around the
opening of blow off pipes (see BGR 104 Section E 1.3.2.3, Exhibits 9 and 10).
The distance of one meter is valid for free ventilation. A distance of 4.5 meters has to
be respected in enclosed rooms.
4. Installation Rooms
4.1 Gas Firings
The Technical Regulations for Gas Installations (DVGW-TRGI 1986, edition 1996) is
applicable for installation rooms for gas installations.
26
4.2.1.1 Installation rooms have to be dimensioned so that the CHP Plants can be
installed, operated, and maintained orderly. That is normally the case if the CHP
is accessible from three sides. Doors have to open in direction of escape.
4.2.1.2 Floor drains must have oil separators. Alternately, an oil collection tank has to be
installed below the engine that is able to receive the total oil volume of the engine.
4.2.1.3 Installation rooms must have intake and outlet openings for ventilation that cannot
be closed and that allow lateral ventilation. When using technical ventilation, it has
to be ensured that the outgoing air is drawn from the vicinity of the ceiling. In such
case, it is irrelevant whether the air intake is located low or high in the room.
When using natural ventilation, the air intake has to be located in the vicinity of
the floor, the opening for air exit at the opposing wall near the ceiling.
Note
The free minimum cross section ”A” of the opening for air intake or outlet results
from the following equation:
4.2.1.4 It must be possible to shut the CHP off at any time by means of an illuminated
switch located at the outside of the installation room. The switch has to be marked
well visibly and permanently by “Emergency Switch CHP”.
4.2.1.5 It shall be possible to shut the gas supply for the CHP off from outside the
installation room as closely as possible to the CHP room. The open and closed
positions must be marked.
4.2.1.6 In case of engines that use a turbo charger for compressing the gas-air mixture,
the following precautions have to be taken to prevent explosive mixtures in case
of emergencies:
a) monitoring of the air in the installation room using type certified equipment and
automatic shut-off of the aggregate and the electrical installations, or
b) monitoring of the air in the installation room using type certified equipment and
automatic shut-off of the aggregate and simultaneous switch-on of a forced
ventilation installation, which is dimensioned according to c) so that no
explosive mixtures can develop, or
c) forced ventilation of the aggregate room with at least an air exchange that
effects sufficient dilution for the maximum possible gas volumes. The
necessary minimum air exchange is 35 m3/h of air for each one kilowatt
electrical power installed. This results in a maximum gas concentration of
maximum 1.5 vol%, which corresponds to about 25% of the lower gas
explosion limit (biogas 6 to 12 vol%).
27
With open shut-off valves, the ventilator must operate, and its function has to
be monitored by a flow guard.
4.2.1.7 Two shut-off valves have to be installed before each engine aggregate, which
shut off automatically with standstill of the engine. The leak tightness of this pipe
portion has to be verified on a regular basis. If the supply line to the engine is
operated continuously with an over pressure of > 5 mbar even with engine
standstill, an automatic supply line monitoring is necessary.
Recommendation
Existing installations have to be refurbished in case of essential modifications of
the gas system or the exchange of an aggregate. It is recommended to execute
the refurbishment within five (5) years after publishing of these safety guidelines.
4.2.1.8 Rooms into which gas can intrude and that have to be accessible on a regular
basis for the operation of the facility have to be ventilated in a way that no
dangerous gas mixture can develop. Exit from such rooms shall be possible
without entering into the CHP room. If these rooms cannot be ventilated
accordingly, an explosion protection has to be foreseen. In addition, the MAK
values have to be complied with safely and permanently.
Explanation
Such rooms are considered Zone 2 (see Section 3).
4.2.2 Installation in Residential Buildings
4.2.2.1 The regulations of Sections 4.2.1.1 to 4.2.1.8 are applicable.
4.2.2.2 Walls and columns, as well as ceilings above and below installation rooms, have
at least to be fire protected according to F 90 A DIN 4102 and consist of
noncombustible materials. Claddings and insulation layers made from
combustible materials may not be used for walls, ceilings, or columns.
4.2.2.3 Doors in fire resistant walls have to be at least fire retardant, according to T 30
DIN 4102, and have to be self-closing; this is not applicable for doors that lead to
the outside.
4.2.2.4 Ventilation ducts and other pipes may only be installed across walls and ceilings if
the pipes themselves cannot transfer fire or if preventive measures against
transfer of fire have been taken (e.g., insulation of cables with general
construction certification, fire protection flaps).
Open areas in the opening have to be filled with noncombustible materials that
are resistant to deformation.
5. Operation
An operational manual has to be available for initial operation (see sample in Exhibit
1). The initial operation of the installation has to be done by the specialized
professional (see the Acceptance Protocol in Exhibit 2).
Operation and maintenance of biogas facilities may only be assigned to reliable
persons who are familiar with the tasks. Attention has to be paid to the operational
manuals with the safety instructions (see Exhibit 3).
28
The operational instructions have to be placed permanently in the operation room
(see, e.g., Exhibit 7).
It is recommended to maintain an operational record (see Exhibit 4) that contains all
daily measurements, control and maintenance activities, as well as malfunctions.
In case of a malfunction of the gas consumption equipment, the gas production of the
facility has to be reduced by means of appropriate measures in order to keep the
blow off volumes as small as possible.
Appropriate measures for the reduction of the gas production are, e.g.:
- Interruption of the supply of substrate
- Shut-off of heat supply to the fermenter
In case of malfunctions and for a shut down of the biogas facility, the measures
according to Exhibits 5 and 6 have to be taken.
6. Fire Protection
A fire extinguisher with 12 kg powder and a protection cap, for fire classification A, B,
and C according to DIN EN 3, has to be attached outside at the operation building
well visible, easy to access in case of fire, and ready for use.
For the equipment with fire extinguishers, reference is made to BGR 133 “Equipment
of Work Places with Fire Extinguishers”. Farther reaching fire protection measures
(see Exhibit 8 - Proposal For The Content of an Alarm and Danger Protection Plan)
have to be coordinated with the regionally responsible fire department.
For fire protection reasons, storage of engine oils, used oils, or other combustible
materials in quantities above 200 kg is not permitted in the CHP room. For CHPs with
up to 50 kW electrical power, the storage of up to 5,000 liters of ignition oil is
permitted.
29
Exhibit 1 Commissioning/Reoperation of a Biogas Facility
Sample for Facility according to Section 1.2
Commissioning/Reoperation of a Biogas Facility
1. During the commissioning, explosive gas mixtures may be present in the gas space in
the fermentation vessel. Spark formation has to be avoided, e.g., operation of the
stirring machines submerged.
2. Attention has to be paid to zones according to Section 3.2.
3. Initially, empty fermentation vessels have to be separated from the gas collection
system.
4. The fermentation vessels are connected to the atmosphere through over pressure
safety devices, in open position, and blow off pipes.
5. The fermentation vessels are being filled with as much as possible active substrate
until all inlets and outlets (liquid seal) are sealed by substrate.
6. Heating of the fermentation substrate.
7. During the start up/heating of the facility, no further filling shall take place.
8. During the start up of the fermentation process, the developed gases pass through the
blow off pipe (gas over pressure safety device) in the open air and replace the air in
the fermenter.
9. After verification of the gas quality, the gas system and the gas tank will be filled with
biogas. The over/under pressure safety device is put into operation. The gas quality is
sufficient and not explosive if the methane content of the gas is higher than 45% or the
gas continues to burn without ignition flame.
10. The CHPs are put into operation. They draw the gas automatically from the gas tank.
Acceptable gas quality to be verified by gas measurement.
Note: A flame test shall only be done if a flame trap is installed in front of the opening!
The opening shall not be located in enclosed rooms.
30
Exhibit 2 Test Certificate for a Biogas Foil Storage Vessel
Sample
Operator of Facility:
Manufacturer of Facility:
Material:
Dimensions:
Gas tightness: For Methane: cm3/m2 • d • bar
Mechanical strength: Tear strength: N/5 cm
Tensile strength: N/5 cm
Temperature resistance:
Seals:
Installation type:
Tightness Test
Test area:
Test method:
Test medium:
Test result:
Remarks:
Location/Date: Seal/Signature
31
Sample
Operator of Facility:
Manufacturer of Facility:
Tightness Test
Test line from - to
Test method: According to Technical Regulations for Gas Installations
DVGW-TRGI 86 “Test of Pipes with Operational Pressure of
Up To 100 mbar”
Test pressure: Pre-Test: 1 bar, main test: 110 mbar
Test duration: Pre-Test: 10 min., main test: 10 min.
Test medium: Air
Test result:
Remarks:
Location/Date: Seal/Signature
32
Test Report No. Order No.:
VSG 1.4/BGV 2 A
Test executed according VBG 4
DIN VDE 0100 T. 610 DIN VDE 0829/EN 50 090
Reason for test: New Installation Expansion Modification Repair
Visual Inspection: Heat generating equipment Main potential equalizing
Correct selection of equipment Target destination of pipes in distributor Additional (local) potential equalization
Damage of equipment Pipe installation
Protection against direct touching Low voltage with safe switch-off
Safety devices Protection disconnector Arrangement of bus equipment in distr.
Fire protection walls Protection insulation Bus lines/actuators
Test: Remark:
Function of protection and Right orientation of 3-phase plug-ins Function of bus installation E:B
monitoring devices
Function of high voltage installation Turning direction of motors
Measurement:
Grounding resistance Ω Connectivity protective conductor/potential equalization
Insulation resistance of bus line kΩ Connectivity/polarization bus lines
Used instruments Manufacturer Type Manufacturer Type Manufacturer Type
according to
DIN VDE Manufacturer Type Manufacturer Type Manufacturer Type
Circuit Location Line/cable Over current Z8 Fault current ULS…
No. Facility part Protection Ω Protection device V
Type No. Cross Type/ /n Or R n/Art /∆mess /∆mess Umess
wires section Charac /n
2
mm t A A MΩ A A A V
Main line
Distributor
33
Exhibit 3 Sample Operational Manual for a Biogas Facility in Normal Operation
General Part:
- Pay attention to pressure variations and to good accessibility during filling and emptying.
Daily:
- Note gas counter reading and operational hours of engine
- Verify oil level of engine
- Verify functioning of alarm lamps in the switching cabinet in the electrical room
- Verify water pressure of heating installation
- Verify the functioning of the air dosage installation of the desulphurization facility
- Monitor fermentation temperature
- Select stirring intervals so that there is no formation of a swimming or a sinking layer
- Ensure for all intakes and outlets that the liquid manure/substrate flow required by the
process is maintained
- The set up desulphurization airflow has to be adjusted to the actual gas production rate
(max. 12 vol%)
- Verify fill levels of the fermenter and the final storage
- Verify the foil connections (e.g., clamp tube at the foil gas storage vessel)
Weekly:
- Verify fill levels of the submerged cups of the over or under pressure safety device and
of the condensate separator
- Verify functioning of the submerged propeller; verify appearance of vibrations
- Visually inspect motors and electrical lines
- Verify functioning and dirt of gas magnet valves
- Verify tightness of automatically closing gas shut off valves
Monthly:
- Move all sliders several times so that they do not become stuck
6-monthly:
- Verify the air intake and outflow of the engine room of the CHP
- Inspect electrical installations for damage
- Verify functioning of the under pressure detectors
- Control function of gas sensors, fire alarm (if available)
Yearly:
- Verify all gas carrying facility parts for damage, tightness, and corrosion
- Verify fire extinguishers
34
- Verify prevention of freezing of seal liquids
In the zones according to Section 3.2, ignition sources have to be avoided, e.g.:
- Smoke, fire
- Non-explosion protected electrical equipment
35
Exhibit 4 Operational Record (example)
Sample
Date Gas Gas Con- Hours of Electricity Ferment. Substrate Mainten. Special
Meter sumption Operation Meter Temp. Supply Work Events
Reading [m3/day] [h] Reading [°C] [m3]
[m3] [kWh]
36
Exhibit 5 Sample Operational Manual for a Biogas Installation during Malfunction
Sample Operational Manual for a Biogas Installation
during Malfunction
Heating
- Attention: Danger of scalding by exiting heating water
Electrical Installation
- Work at the electrical installation must be done only by tradesmen
37
Exhibit 6 Shut-Off of a Biogas Installation
1. Shut-off of the substrate supply to the fermentation vessels, while removal continues.
The removal volume of the substrate may not exceed the volume of the produced gas.
2. If the removal volume of the substrate can exceed the volume of produced gas, the
fermentation vessel will be shut off from the gas collection system and the connection to
the atmosphere is established, e.g., by emptying the liquid from the liquid seal.
3. Separate the gas tank from the gas storage vessel in order to avoid gas backflow.
4. Pumps and stirring machines have to be shut off and secured against switch-on.
5. Ignition sources have to be avoided within the protection distance around the
fermentation vessel.
6. Before accessing and during stay in pits and channels, it has to be ensured that no
danger of suffocation and poisoning exists, and that sufficient air for breathing is
available. Facility equipment has to be secured reliably against switch-on. Sufficient
ventilation has to be ensured. In case of insufficient ventilation, there is danger of
suffocation, poisoning, fire, and explosion.
38
Exhibit 7 Operational Instruction
Operational Instruction
Designation of Hazardous Materials
Liquid Manure and Biogases
(Hydrogen Sulphide, Methane, Carbon dioxide, Ammonia)
Work Area: Biogas facility, liquid manure pits, liquid manure channels, liquid manure storage, channels,
etc.
Activities: Stirring, rinsing, pumping, transfer pumping, removal of liquid manure or substrate, repair and
First Aid
After breathing of liquid manure and biogases: Fresh air supply.
Unconscious persons: Verification of breathing and stable side position.
Secure medical assistance immediately. Indicate poisoning by hydrogen sulphide.
First Aid Assistance: Doctor:
Tel.: Emergency Call: 112
__________________ ___________________________________
Date Signature Business Owner
39
Exhibit 8 Proposed Content of an Alarm and Hazard Protection Plan
Proposed Content of an Alarm and Hazard Protection Plan
A biogas facility is a construction facility that necessitates a detailed review during the
planning stage, relative to the factual assessment of the fire risk, and a close coordination
with the management of the deployment forces of the local fire department, relative to the
requirements for tactical deployment.
This requires normally the joint development of a common concept for the tactical
deployment of the fire department in case of fire incidences and for other technical
assistance (fire protection concept).
The Fire Protection Concept has to be drafted by the operator of the facility, and then
coordinated with the responsible fire department relative to their tactical requirements for
tactical deployment. The Fire Protection Concept has to be submitted in final form to the
authorization agency at least one week before commissioning of the facility.
In accordance with the individual requirements, the Fire Protection Concept will normally
have to include facts and descriptions relative to the following issues:
1. Access and transit ways, as well as positioning and operation areas for the fire
department.
2. Proof of the necessary fire water volume and proof of fire water supply.
4. The system of outer and inner sealing in fire sectors or fire fighting sectors, as well as
the system of smoke sectors with details about positioning and arrangement of the
components.
5. Position, arrangement, and marking of rescue routes on the property and inside of
buildings, with indication of safety illumination.
8. Position and arrangement of air ventilation systems, if case be, with details relative to fire
protection instructions.
10. Position, arrangement, and, if case be, dimensions of facilities, installations, and
equipment for fire fighting (e.g., fire extinguishers) with details relative to protection areas
and storage of special fire fighting matters.
40
Exhibit 9 Example of a Zoning Division
Around:
Foil storage outside 3 meters upwards
41
Exhibit 10 Tightness of Equipment
Tightness of Equipment
1. Tightness of Equipment
The exit of combustible gases, vapors, or dusts in hazardous quantities into the
environment can be avoided by tight equipment.
The construction materials for equipment shall be selected for the design of equipment in a
way that they withstand the mechanical, thermal, and chemical conditions to be expected.
Danger by reaction of wall materials with combustible mixtures must be excluded. When
selecting materials, the potential for corrosion has to be considered.
Equipment is permanently technically tight (BGV B6 formerly VBG 61, TRB 600 No. 5), if:
Relative to a)
Permanently technically tight facility and equipment parts are, e.g., welded equipment with
- removable components, whereby the necessary detachable connections have only to be
operationally released very rarely, and the construction of which is designed in the same
way as the following detachable pipe connections (exception: metallically tightening
connections)
- connecting pieces for the detachable attachment of pipes, armatures, or blind covers,
whereby the necessary detachable connections have only to be operationally released
very rarely, and the construction of which is designed in the same way as the following
detachable pipe connections (exception: metallically tightening connections)
Permanently technically tight connections for the connection of equipment, as far as they
are rarely operationally detached, are, e.g.:
- pipe connections as mentioned above, and
42
- NPT-thread (National Pipe Paper Thread, cone type pipe thread) or other conical pipe
threads with sealing the thread until DN 50, as far as they are not exposed to changing
thermal loads (∆t > 100 °C).
Relative to b)
Beside pure design measures, technical measures combined with organizational measures
can also lead to permanently technically tight equipment.
The extent and frequency of verification and maintenance depend in detail on the type of
design, operational mode, and the loads and shall ensure permanent technical tightness.
Attention has to be paid that extent and frequency of verification and maintenance,
necessary to maintain permanent technical tightness, shall be determined in the operational
instructions.
- Walk through and observation, e.g., for streaks, formation of ice, smell, and noise
caused by leakages.
- Walk through the facility with mobile leak detectors or mobile gas warning equipment.
- Continuous or periodic monitoring of the atmosphere by automatic fixed measurement
equipment with warning function.
Suitable preventive maintenance can reduce the extent and frequency of the verification of
tightness.
- Pumps whose technical tightness cannot be ensured permanently (e.g., with a simple
sliding ring seal.
- Detachable connections according to Item 1.1, which are rarely not detached.
43
Exhibit 11 Examples of Further Requirements and Regulations
Examples of Further Requirements and Regulations
Source for ordering: The VSWGen can be requested from the proper Agricultural
Cooperative Association (see second to last page).
Ordinances:
Ordinance for safety and occupational health relative to the appropriation of means for work
and their use for work, relative to the safety during operation of facilities which have to be
monitored during operation, and relative to the organization of operative occupational health
and safety (Operational Safety Ordinance – BetrSichV).
DVGW-Regulations
G 469 “Pressure Test Method for Pipes and Installations of Gas Supply”
G 462 Part 2 “Steel Gas Pipes from 4 Bar to 16 Bar Operational Pressure;
Installation”
Source for ordering: Wirtschafts- und Verlagsgesellschaft Gas und Wasser mbH,
45
Postfach 14 01 51, 53111 Bonn, Germany
Masthead
Editor:
Reference: Through the regional Agricultural Cooperative Associations, see (next page)
addresses
46
List of Agricultural Cooperative Associations
47
48