FINAL Hydraulic Calculation
FINAL Hydraulic Calculation
FINAL Hydraulic Calculation
12/14/2022
20121182632
Hydraulic Calculation
The presentation deals with hydraulic calculations of the wet pipe fire sprinkler system of
a commercial building under Ordinary Hazard Group 1 (OH1) occupancy.
The Sample Design Layout (above) has a floor area of 30 m by 50 m (1,500 m2), one-
story commercial building which served by a 4-inch riser and believed to be within 52,000 ft2
(4,831 m2) maximum fire sprinkler system protection coverage per riser.
The design area of protection is 1,500 ft2 (139.4 m2) with a water density of 0.15 gpm/ft2.
Each sprinkler covers 129.17 ft2 (12 m2). Using area/density method to compute for the Design
Area (Area of Protection).
𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟𝑠 𝑡𝑜 𝐶𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒
𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟 𝐶𝑜𝑣𝑒𝑟𝑎𝑔𝑒 = 4 𝑚 × 3 𝑚 = 12 𝑚2 = 129.17 𝑓𝑡 2
𝐷𝑒𝑠𝑖𝑔𝑛 𝐴𝑟𝑒𝑎 1,500 𝑓𝑡 2
𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟𝑠 = =
𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟 𝐶𝑜𝑣𝑒𝑟𝑎𝑔𝑒 129.17 𝑓𝑡 2
𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟𝑠 = 11.61 ≈ 12
𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟𝑠 𝑎𝑙𝑜𝑛𝑔 𝐵𝑟𝑎𝑛𝑐ℎ 𝐿𝑖𝑛𝑒
𝑆 = 4 𝑚 = 13.12 𝑓𝑡 𝑎𝑝𝑎𝑟𝑡
PASCUA, PAUL DANIELLE S. 12/14/2022
20121182632
𝑄 = 𝑘√𝑃
𝑊ℎ𝑒𝑟𝑒: 𝑘 = 𝑆𝑝𝑟𝑖𝑛𝑘𝑒𝑟 𝑘 − 𝑓𝑎𝑐𝑡𝑜𝑟, 𝑁𝐹𝑃𝐴 13
𝑃 = 𝑆𝑝𝑟𝑖𝑛𝑘𝑙𝑒𝑟 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑛𝑔 𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒, 𝑃𝑆𝐼
𝑇ℎ𝑒𝑛,
Hydraulic Calculation
for
AUTOMATIC FIRE SPRINKLER SYSTEM of ONE-STOREY COMMERCIAL BUILDING
Nozzle Fittings Pipe Friction Required
Step Flow Pipe Size C k
Ident. & & Equivalent Loss Pressure
No. (GPM) (Schedule 40) Factor Factor
Location Devices Length (ft) (psi/ft) (psi)
q Nominal 1" Length 13.12 Pt 11.96
1 1 BL-1 None Fittings 0 120 0.1226 Pe 0 5.6
Q 19.37 Act. 1.049
Total 13.12 Pf 1.61
1
q 20.63 Nominal Length 13.12 Pt 13.57
1/4"
2 2 BL-1 None 120 0.1233 5.6
Fittings 0 Pe 0
Q 39.99 Act. 1.38
Total 13.12 Pf 1.62
1
q 21.82 Nominal Length 13.12 Pt 15.18
1/4"
3 3 BL-1 None 120 0.2760 5.6
Fittings 0 Pe 0
Q 61.81 Act. 1.38
Total 13.12 Pf 3.62
1
q 24.28 Nominal Length 6.56 Pt 18.81
BL-1 1/2"
4 4 Tee 120 0.2405 5.6
to RN Fittings 8 Pe 0
Q 86.10 Act. 1.61
Total 14.56 Pf 3.50
q Nominal 2" Length 1 Pt 22.31
5 RN Tee Fittings 10 120 0.0712 Pe 0.43 5.6
Q 86.10 Act. 2.067
Total 11 Pf 0.78
2
BL-1 q Nominal Length 9.84 Pt 23.52
1/2"
6 to BL- None 120 0.0300 16.67
Fittings 0 Pe 0
2 Q 86.10 Act. 2.469
Total 9.84 Pf 0.29
2
BL-2 q 86.64 Nominal Length 9.84 Pt 23.82
1/2"
7 to BL- None 120 0.1087 16.67
Fittings 0 Pe 0
3 Q 172.73 Act. 2.469
Total 9.84 Pf 1.07
2
BL-3 q 83.17 Nominal Length 139.4 Pt 24.89
1/2" 1-Std.
8 to 120 0.2249 16.67
Elbow Fittings 6 Pe 0
TOR Q 255.90 Act. 2.469
Total 145.4 Pf 32.70
q Nominal 3" 1-Std. Length 13.12 Pt 57.59
TOR
Elbow, Fittings 40 Pe 5.68
9 to 120 0.0781 16.67
Q 255.90 Act. 3.068 1-GV,
BOR Total 53.12 Pf 4.15
2-CV
q Nominal 3" 5-Std. Length 59.04 Pt 67.42
BOR
Elbow, Fittings 52 Pe 1.42
10 to 120 0.0781 16.67
Q 255.90 Act. 3.068 1-GV,
PUMP Total 111 Pf 8.67
1-CV
q 250 Nominal n/a Length n/a Pt 77.51
11 HOSE n/a Fittings n/a 120 n/a Pe n/a n/a
Q 505.90 Act. n/a
Total n/a Pf n/a