ITYS ES

Solution for electrical substations


from 1000 to 3000 VA - Electrical Substation

The solution for

> Control devices


> Electric lines
Prime

Compliance with standards

> IEC 62040-1


> IEC 62040-2
> IEC 62040-3

Certifications

gamme_850.psd

High protection and high­ Operating efficiency and


availability versatility
Tech info
•T  he ITYS ES series is a range of compact •T  he versatility of these models makes them
UPS systems available in 1000, 2000 suitable for protecting critical devices in the The CEI 016 STANDARD for
and 3000 VA models with on-line double industrial field. auxiliary cabin equipment requires
conversion technology (VFI) with sinusoidal • The standard equipment and an uninterrupted power supply to
absorption. communication accessories have been the control circuits for the General
• ITYS ES guarantees permanent regulation specially designed to satisfy the typical Protection and Medium Voltage
of the output voltage and frequency. needs of installation or use in transformer Switch.
This technology is compatible with all IT cabins (i.e. tropicalized boards). The control circuits for the General
and industrial applications and operating • In situations where automatic power Protection, Medium Voltage Switch
environments, installations with generator management procedures are required, and coil must be powered by the
sets included. the communication software can be used same auxiliary voltage when there is
• Wide tolerance on input voltage ensures to programme scheduled start-up and no power. The power supply must
that switchovers to battery mode are shutdown times. be guaranteed for a back-up time of
infrequent, significantly prolonging battery • Restarting the UPS from the battery to 1 hour, either by the UPS or by buffer
lifetime. power the DG before closing the main batteries.
• Wide operating ambient temperature up to isolator.
45°C. The Medium Voltage Switch must
• Standard Over Voltage Control Device be powered up by skilled personnel
(OVCD) protects the UPS and the load from if out of service for a long time due to
dangerous mains peak-voltages. maintenance or failure.
• UPS models with tropicalised (Conformal It is necessary to power the General
Coating) boards. Protection before closing the Medium
Voltage Switch.
Straightforward to install and
easy to use The required protection comprises:
- Mains power cuts due to poor
•T  he UPS is shipped ready for connection
maintenance of the user’s system.
with internal batteries connected and
charged. - Inappropriate tripping of the Medium
Voltage Switch because of faults in
• ITYS ES, with the manual bypass option
the trip circuit.
is easy to install without any special plant
engineering preparation, as it is equipped - Alert signalling if the Medium Voltage
with built-in thermal protection. Switch trips due to a power failure
(system with regular maintenance).
• The LCD monitoring/control panel and a
buzzer make the equipment extremely easy
and intuitive to use. The graphic indicating
the power distribution path shows at a
glance whether or not the system is working
as it should.
• Battery efficiency can be tested via the
control panel or using dedicated software.

2 Catalogue 2022
ITYS ES
Single-phase UPS systems
from 1000 to 3000 VA - Electrical Substation

UPS - Technical data Standard communication features


ITYS ES •  mbedded dry-contact interface.
E
Model ITY3-TW010B-ES ITY3-TW020B-ES ITY3-TW030K-ES • Input mains switch breaker.
Sn [VA] 1000 2000 3000 • Power off the UPS remotely.
Pn [W] 1000 2000 3000 • Internal temperature sensor.
Input / output 1/1 • 1 slot for communication options.
INPUT
• USB port for UPS management based on
Rated voltage 230 V (1ph) 110÷300 V; (160÷300 V @100% load)
HID protocol.
Rated frequency 40-70Hz (50/60 Hz +/-5% Auto-Selectable)
Power factor >0,99 • MODBUS RTU (RS232).
OUTPUT • LOCAL VIEW software for local UPS
Rated voltage 220 / 230 / 240 V (± 1 %) monitoring and shutdown for Windows,
Rated frequency 50/60 Hz (± 0.1 Hz in battery mode) Linux and MAC Osx.
Overload up to 105% continuously; 125% x 3 min; 150% x 30 sec • Clear and uncluttered LCD interface
Crest factor 3:1 for easy UPS monitoring, even for less
Connections 4 x IEC 320 (C13) 8 x IEC 320 (C13) 8 x IEC 320 (C13) + 1 (C19) specialist users.
BATTERIES
Type sealed lead-acid maintenance free - expected lifetime 3-5 years Communication options
Back-up time(1) 12 minutes 16 minutes 23 minutes
Sized for a back-up time of 108 minutes @ 50 W 130 minutes @ 150 W 156 minutes @ 300 W • Dry-contact card.
Back-up time(2) + switching back on 60 minutes @ 50 W 60 minutes @ 150 W 60 minutes @ 300 W • NET VISION: professional WEB/SNMP
Battery test • • • Ethernet interface for secure UPS monitoring
COMMUNICATION and remote automatic shutdown.
Interfaces RS232 - USB - Dry contact • Environmental Monitoring Device (EMD).
Ethernet adapter NET VISION (TCP / IP & SNMP) optional card
• REMOTE VIEW PRO supervision software.
Local communication software Local View
EFFICIENCY
Online mode up to 93% Manual bypass (option)
ENVIRONMENT
• Specially designed for ITYS ES, the manual
Ambient service temperature from 0 °C to +40 °C (up to 45 °C (4))
bypass option enables:
Relative humidity < 95 % non-condensing
Maximum altitude 1000 m without de-rating
• simplified installation: connection to the
Noise level at 1 m < 50 dBA
system is made with industrial grade
UPS
terminals, while connection to the UPS is via
Dimensions W x D x H 145 x 404 x 224 mm 192 x 428 x 322 mm 384 x 428 x 322 mm
the pre-wired plug and socket supplied.
Weight 14,4 kg 26 kg 49,3 kg • easy maintenance and uninterrupted
Degree of protection IP20 operation: thanks to the manual bypass
COMPLIANCE WITH STANDARDS isolator it is possible to service or replace
Safety IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 the UPS while maintaining the power supply
EMC IEC/EN 62040-2, AS 62040.2 to the devices downstream in complete
Product declaration CE, RCM (E2376), UKCA safety for the operator. This operation has
ITYS ES - Manual bypass (3) been specially devised to be simple to carry
Sn [VA] 1000 2000 3000 out, even in an emergency.
INPUT • increased level of equipment immunity
Type of terminals CBD6 to surge voltages, typical for this type
Wire size 6 mm2 max of application, thanks to suitable surge
BYPASS arrestors included in addition to standard
Switching positions 1: UPS - 2: MAINS UPS protection.
Switching time 6 ms max
LOAD OUTPUT
Type of terminals CBD6
Wire size 6 mm2 max
UPS SUPPLY OUTPUT
Type of socket IEC 320 10 A IEC 320 16 A
SURGE ARRESTORS (on request)
Type "L" in compliance with CEI EN 61643-11
L/N pulse current 40 kA (8/20) max
VAC N/GND 255 V max
VAC L/N 320 V max
ITYS_025_A.EPS

(1) @75 % of rated load (models with internal batteries) PF 0.7.


(2) Factory setting: back-up time limited to 60 minutes to permit subsequent restarting with battery.
(3) Upon request.
(4) Conditions apply.