OPERATOR’S MANUAL
( &*%"#) #')( *(( # # ') '$ '&*#. #'.
# #$) #()!! # *( # $'# ,) ) #()'*)$# "#*! ".
*( #)''# )$ '$ $""*#)$#( 0 / "$! ( #
)() # $*# )$ $"%!. ,) ) !")( $' !(( $"%*)# +(
%*'(*#) )$ *%') $ ') $ ) '*!( , ' (# )$
%'$+ '($#! %'$))$# #() (* #)''# ,# $%') #
$""'! #+'$#"#) %')$# $ )( &*%"#) # '(#)! '
( ! !. )$ *( #)''# # , ( ) *(' ) ( $,# -%#(
,!! '&*' )$ ) ,)+' "(*'( ". '&*' )$ $'') )
#)''#
©Copyright 1992, 1995 Exide Electronics Corporation, Raleigh, NC. All rights
reserved. No part of this document may be reproduced in any way without the
expressed written approval of Exide Electronics Corporation.
Safety Considerations
The UPS contains LETHAL VOLTAGES. All repairs should be performed
by trained service personnel. There are no userĆserviceable parts inside the UPS.
The UPS contains its own energy source (battery). The output
receptacles may be live even when the UPS is not connected to an AC supply.
There is high voltage present at terminals 9 and 10 (terminals for remote battery
connection) when a battery cabinet is connected to the UPS.
To fully deĆenergize the UPS, turn off the output breaker. Then turn off the
input breaker and the battery breaker.
All cabinets must be secured to keep them from moving after installation
is complete. Secure the cabinets by bolting the cabinets to the cabinet mounting
plate. Failure to do so violates safety rules and results in the unit losing its safety
agency approvals.
!
Special Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Estimated Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Special Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Control Keys and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Using the Front Panel Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
The Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
The System Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
UPS Control Panel Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
OnĆBattery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Overload Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Load PowerĆOff Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Audible Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Bypass Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Automatic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Local/Remote Emergency PowerĆOff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
!
!
Obtaining Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Powerware® Plus 12 Operator's Manual (164200090 Rev E) # iii
Plus 12 UPS Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Plus 12 UPS Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Plus 12 UPS Battery Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Installing the UPS and Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Final Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Bypass Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Input Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Installing the Power Distribution Module (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Installing Remote Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Determining the Battery Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Remote Battery Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Remote Battery Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Special Features
All Plus 12 UPS models come with the following special features:
True online, doubleĆpower conversion operation for complete load protection
Reliable, highĆquality power whether operating from utility, battery, or generator
Local/Remote Emergency PowerĆOff (EPO/REPO) feature that can disconnect
your protected equipment from all power sources
Automatic and maintenance bypass
Easy access to input, output, and battery circuit breakers
Latching lid protects circuit breakers
Sturdy, lineĆup and match cabinets are attractive enough for any office or
computer room
Sealed, maintenanceĆfree batteries
Casters for easy installation and mobility
Digital front panel allows userĆprogrammable output voltage and frequency
Rectifier, inverter, and I/O modules are housed in factoryĆsealed field replaceable
units for safety, easy repair, and quick upgrades
20% additional output kVA for nonlinear load applications
OneĆyear Powercare® limited warranty and extended warranty service (USA
and Canada)
System Overview
During normal operation, incoming commercial power is filtered to reduce noise and
spikes. The rectifier provides isolated, regulated, and filtered DC power to the inverter.
A portion of the input power to the rectifier is used to charge the battery. The inverter
provides further regulated and filtered AC power to the load. In the event of a severe
overload or unit failure, the Auto Bypass feature (if enabled) switches the load to the
filtered input power. If bypass is not available, the inverter can still support difficult loads
for a short period of time.
If utility power falls out of tolerance, the UPS remains online, deriving power from the
battery. During extended power outages, the battery supplies power until nearly
discharged at which time the UPS shuts off power to the load. When the utility power
returns within tolerance, the UPS automatically restarts and supplies power to your
protected equipment while recharging the battery.
System Requirements
Determine the total load requirements, in voltĆamperes, of the equipment you intend to
protect with your UPS. The UPS load should not exceed the UPS rating. See Figure 1
and the following procedure to determine the total load requirements:
. Obtain the load ratings from either the nameplate or operator's manual of the
equipment you intend to protect. The ratings are listed in either watts (W),
amperes or amperes max (A), or voltĆamperes (VA).
. If the rating is in watts, multiply by 1.4 to obtain the VA requirement (this is the
typical relationship between watts and voltĆamperes ratings in most computing
equipment).
If the rating is in amperes or amperes max, multiply by the input voltage (200, 208,
220, 230, or 240 VAC) to obtain the VA requirement.
. Add all of the resultant VA ratings together to obtain the total load
requirements of the equipment to be protected.
Special Symbols
These common symbols may be found on your UPS:
LCD Display
Horn Silence
UPS Off
UPS On
Menu Button Select Button
Press the EPO switch to turn off the load power during an emergency condition.
The UPS must be restarted after an EPO.
Press to start up the UPS.
Press to silence the audible alarm, to perform a lamp test, or to test audible alarm.
Press the Horn Silence button for approximately 12 seconds to perform the Horn and
Lights test. During the first four seconds, the panel indicators illuminate. During the
next four to six seconds, one or more of the indicators go out. During the last few
seconds, the alarm sounds. The test ends when you release the Horn Silence button
after the alarm sounds.
Press to shut down the UPS.
!' '&&"!
Press the Menu button to return to previous menu level. If you are not sure which
menu is currently displayed, press the Menu button repeatedly until the Main Menu
displays &&'%.
& '&&"!
Selects the currently displayed item shown on the second line of the LCD Display or
enters the next menu level. For example, if the display shows on the top
line and &$% on the second line, pressing the Select button enters the Meters
menu and shows the option.
See UPS Control Panel Functions" on page 15 for information on the Normal, Bypass,
Battery, and Overload indicators.
,,-+
The UPS Status option displays the number of currently active alarms and the
conditions. The following table describes the different UPS conditions.
/&"& ' /(++ Inverter has ramped, but load is still on bypass
-,(-, *#* (& Output breaker open (O); UPS not supplying power to the load
,*+
The Meters option displays system meter values obtained through the serial
communications network or calculated from the values obtained through the network.
Use the up and down arrow buttons to view the following metered values:
&(-, '$,+ , input voltage (each phase and lineĆtoĆneutral)
&(-, '$,+ , input voltage (each phase and lineĆtoĆline)
-,(-, '$,+ , output voltage (each phase and lineĆtoĆneutral)
-,(-, '$,+ , output voltage (each phase and lineĆtoĆline)
.* ,,*/ '$,
"&# '$,
&.*,* *)-&/
&(-, *)-&/
-,(-, # , shown as bar graphs with each block representing approximately
10% of capacity
!+ ' -**&,, load currents (phase A, B, and C) are shown as bar graphs
with each block representing approximately 10% of capacity
"% ,, displayed in the MM/DD/YY; HH:MM:SS or the DD/MM/YY;
HH:MM:SS format
$*% --
The Alarm Queue option displays the 200 most recent alarms and events in
chronological order (most recent first). Use the right and left arrow buttons to pan
across the screen and view entire descriptions. Use the up and down arrow buttons to
scroll through the queue. The alarms are displayed in the following format: sequence
number, date, time, and description of the alarm.
The Active Alarms option displays a description of each active alarm.
The Battery Data option displays information about the battery. If the UPS is running
with normal utility, the Battery Charge bar chart is displayed. If the UPS is running on
battery, the Battery Time Remaining bar chart is displayed. Each block on the bar chart
represents approximately 10% of the total time. This calculation assumes a constant
load on the UPS. If custom batteries are selected, the battery voltage is displayed.
The S. W. Versions option displays the software versions for the front panel, inverter,
and rectifier.
Select the System Setup option to enter the System Setup Menu. This menu is
passwordĆprotected and prompts you for the System Setup password. After entering a
valid password, the System Setup Menu appears.
The default password is MEMORY. It is recommended to change the default
password to ensure security (see page 13). Contact your field service
representative if you have misplaced your password.
Use the Select Type option to select the output voltage, output phase, and output
frequency type for the UPS. The UPS kVA rating is displayed for information only, it
cannot be changed.
Use the right and left arrow buttons to display all options for each category. Press the
Select button to save an option. In this submenu, pressing the Menu button does not
cancel changes; it returns the cursor to the previous menu.
The UPS must be off and the output breaker must be open (O) in order to change the
Select Type setting; otherwise, you can only view the type setting.
After selecting a new type option, press the Menu button to exit the Select Type
submenu before turning on the UPS.
The Select Type submenu contains the following options:
Output Voltage
100V
105V
110V
115V
120V
125V
Output Phase
120°
180°
240°
Output Frequency
50 Hz
60 Hz
Model Number
Use the H. W. Modules option to view and change the present system hardware
configuration. This option contains the following entries:
Bypass Installed
Number of Output Phases
Inverter Installed
Rectifier Installed
Comm Board Installed
Use the up and down arrow buttons to view the entries. Only the Comm Board Installed
option can be changed by the user. Use the left and right arrow buttons to change the
value. Press the Select button to save your changes.
The UPS must be off and the output breaker must be open (O) in order to change the
H. W. Modules setting. If the UPS is not off and the output breaker is closed ( I ), you
can only view the H. W. Modules.
After selecting a new value, press the Menu button to exit the H. W. Modules submenu
before turning on the UPS.
Use the Sync Range option to select a deviation of the utility frequency from the
nominal inverter frequency. The inverter tracks the utility within the range entered in
this option. If the utility is outside of range, the inverter operates at nominal frequency.
The ranges are:
0.5 Hz
1.0 Hz
1.5 Hz
2.0 Hz
2.5 Hz
3.0 Hz
Use the up and down arrow buttons to view the entries. Use the left and right arrow
buttons to change the value. Press the Select button to save your changes.
The UPS must be off and the output breaker must be open (O) in order to change the
Sync Range setting. If the UPS is not off and the output breaker is closed ( I ), you can
only view the Sync Range submenu.
After selecting a new value, press the Menu button to exit the Sync Range submenu
before turning on the UPS.
Use the Adjust Output Volts option to adjust the output voltage to ±5% of the nominal
output voltage. The UPS must be in Normal mode while adjusting the output voltage.
Use the up arrow button to increase the percentage; the down arrow button to
decrease the percentage. The changes are made in realĆtime and remain effective after
you exit the Adjust Output Volts submenu. The Menu button does not cancel changes
within this submenu.
Use the Comm Setup option to set up the serial port for communication with a terminal
and printer or in a computer mode. Output modes are for ASCII computer, binary
computer, terminal, and printer. The I/O port must have the following parameters
correctly set to establish and maintain communication: baud rate, data size, hardware
handshake, software handshake, and parity. Two standard sets of I/O port parameters
are available for twoĆwire terminal (no handshaking) and terminal with software
handshake. All I/O port parameters can be customized.
Use the up or down arrow buttons to view the list of setup parameters. Use the right
and left arrow buttons to view other settings. See Chapter 5, UPS Communications"
on page 25 for more information on the communication interface.
Use the Relay Setup option to display and change the LAN Relay Interface
configuration. Standard configurations include: AS/400,® Novell,® and AT&T®/Default 1.
All relays can also be customized. Use the up and down arrow buttons to view the list
of options. Refer to the Powerware Plus Communications Manual for more information
on the relay setup.
Use the Set Language option to select a language for the display. You can select
English, French, German, Portuguese, or Spanish. Use the up and down arrow buttons
to view the options.
! %#$%
Use the Contrast Adjust option to change the contrast on the display. This option may
not be available for some Plus 12 models. Use the up and down arrow buttons to
adjust the contrast. Press the Select button to save the setting.
%%#'
Use the Battery Cfg option to set your battery configuration or set up the system
for custom batteries. See page 51 to use this option for configuring remote batteries.
The following configurations are available for the Battery Cfg option:
No Battery
Custom Battery
1 EBC2
2 EBC2s
3 EBC2s
4 EBC2s
1 EBC1 & 1 EBC2
2 EBC1 & 1 EBC2
1 EBC1 & 2 EBC2
1 EBC1
2 EBC1s
3 EBC1s
1 EBC18
2 EBC18s
3 EBC18s
4 EBC18s
Use the up and down arrow buttons to change the value. To save the value, press the
Select button.
Operating Modes
After you install and startup the Plus 12 UPS, the UPS filters and regulates incoming AC
power, eliminating noise and voltage spikes, and provides consistent power to your
equipment (see Figure 3).
BYPASS LINE
BYPASS
AC PLUS
SURGE
INPUT AC OUTPUT
SUPPRESSION
RECTIFIER INVERTER TO LOAD
TO UPS EMI/RFI
FILTERS
FRONT
PANEL
EMERGENCY
POWER
OFF TERMINAL BOARD
BATTERY CABINETS FOR REPO
LEGEND
ST SHUNT TRIP
BATTERY BATTERY BATTERY
F FREQUENCY METER
A AM METER
V VOLT METER
REMOTE BATTERY VA VOLTĆAMP METER
CONNECTION W WATT METER
T TEMPERATURE
Normal Mode
In Normal mode, incoming AC commercial power is filtered to reduce spikes and noise.
A portion of the utility power is automatically redirected to charge the battery, and the
battery charge condition is monitored. If the utility AC fails or falls out of specified limits,
the UPS automatically goes to OnĆBattery mode. The UPS automatically returns to
Normal mode when the utility power returns to within specified limits.
If Automatic Bypass is enabled and the utility goes out of specified limits, the Normal
indicator flashes and Bypass is not available.
On-Battery Mode
In OnĆBattery mode, the battery system provides DC power that is converted to
conditioned AC by the UPS. Depending upon the battery capacity, the system operates
in the OnĆBattery mode until the battery is fully drained. Output power is then no longer
available to the load. If incoming power returns within specified parameters, the UPS
automatically returns to Normal mode.
When the utility fails and the unit transfers to OnĆBattery mode, the Normal indicator
goes off, the Battery indicator illuminates, and the alarm sounds. Press the Horn
Silence button to turn off the alarm. The Battery indicator flashes and the alarm sounds
again when the battery is almost discharged. When the battery reserves are depleted,
the Battery indicator goes off and the UPS no longer provides power.
Overload Mode
The Overload indicator illuminates when the system goes into an overload condition
due to one of the following conditions: overload current is between 106% to 124% of
rating for 10 minutes, 125% to 149% for 30 seconds, or greater than 150% of the output
current rating for 10 cycles. The alarm sounds. Push the Horn Silence button to turn off
the alarm. If the Bypass feature is disabled or not available, the unit shuts down. If
Bypass is enabled, the unit transfers to Bypass mode in an overload condition.
Bypass Mode
In the Bypass mode, the UPS transfers the critical load directly to the filtered utility
power, provided the bypass source is available. The transfer occurs due to one of the
following conditions:
Load current is between 106% to 124% of the rating for 10 minutes, 125% to 149%
for 30 seconds, or greater than 150% for 10 cycles. (The UPS attempts three
restarts.)
UPS internal temperature exceeds safe operating range. (The UPS does not
attempt a restart.)
UPS output falls out of the specified voltage limits. (The UPS does not attempt a
restart.)
Output real power exceeds specified limits. (The UPS does not attempt a restart.)
Load current inrush (surge) exceeds peak current capability. (The UPS
continuously tries to restart.)
When the unit is in Normal mode and automatically transfers to Bypass due to a load
current overload condition, the UPS attempts to return to Normal mode. If three
autoĆstart attempts fail (due to a load current) within a 10Ćminute period, the UPS
remains on Bypass. When the unit transfers to Bypass due to an overtemp, realĆpower
overload, or inverter failure, the UPS remains on Bypass and does not attempt a restart.
When a surge current causes the unit to transfer to Bypass, the UPS continuously tries
to restart.
To switch to Bypass (with Bypass Configuration switch enabled), hold the UPS Off
button for three seconds. The Normal indicator goes off and the Bypass indicator
illuminates.
If the alarm sounds when the UPS Off button is pressed, then Bypass is
not available. If the UPS Off button is pressed for three seconds with Bypass not
available, the UPS enters Load PowerĆOff mode.
If the Bypass mode was entered from Normal mode, wait approximately one minute
before trying to return to Normal mode. The UPS waits for internal voltages to bleed
down before proceeding to Normal mode of operation. Press the UPS On button once
to return to the Normal mode.
Load Power-Off Mode
To switch to Load PowerĆOff from Bypass mode, hold the UPS Off button for three
seconds. The alarm sounds while the UPS Off button is held, and the Bypass indicator
goes off when the bypass voltage is removed from the load. Press the UPS On button
once to return to Bypass mode.
If Bypass is not enabled or the Bypass indicator is blinking (indicating that Bypass is
not available), the UPS enters Load PowerĆOff mode from Normal mode. To switch to
Load PowerĆOff from Normal mode, hold the UPS Off button for three seconds. The
alarm sounds while the UPS Off button is held, and the Normal indicator goes off when
the voltage is removed from the load. The UPS waits for internal voltages to bleed
down before proceeding to Normal mode of operation. Press the UPS On button once
to return to the Normal mode.
Load PowerĆOff can also be entered by turning off (O) the output breaker.
Audible Alarm
An audible alarm sounds a pulsing tone when the UPS is in Overload or OnĆBattery
mode. When there is one minute or less of battery time remaining, a constant tone
sounds. The alarm also sounds a constant tone if the UPS is on battery and the
UPS battery is disconnected (battery breaker is open or battery disconnected).
Bypass Plus
The UPS Bypass Plus feature contains two features in one: Automatic Bypass and
Maintenance Bypass. The UPS Bypass Plus features are available only when the
Bypass Configuration switch is enabled; this switch is factoryĆconfigured according to
your order.
Bypass operation requires that input and output voltage, frequency, and phase
displacement are the same. If the UPS is operating as a voltage and/or frequency
converter, bypass must be disabled. See Final Configuration" on page 45.
Automatic Bypass
The UPS automatically transfers the protected equipment directly to the utility AC
power, provided the bypass source is available, when one of the following conditions is
true:
Load current is between 106% to 124% of rating for 10 minutes, 125% to 149% for
30 seconds, or greater than 150% for 10 cycles.
UPS internal temperature exceeds safe operating range.
UPS output falls outside of the specified limits of voltage.
Output real power exceeds specified limits.
Load current inrush (surge) exceeds peak current capability.
Powerware® Plus 12 Operator's Manual (164200090 Rev E) 17
3 UPS Operations
When the unit is in Normal mode and automatically transfers to Bypass mode due to an
overload condition, the UPS attempts to return to Normal mode. After output
realĆpower overload failure or any other abnormal condition, return to Normal mode
must be done manually (system startup). The UPS remains in Bypass mode if three
autoĆstart attempts fail within a 10Ćminute period.
Maintenance Bypass
The Maintenance Bypass switch is located under the top cover of the UPS (see
Figure 10 on page 37). When activated, this switch allows for onsite servicing of the
UPS. Be sure that the output breaker is turned on ( I ).
This equipment is always electrically live. Users must remove utility power
by external means.
Initial Power-on
Since the system type is factoryĆset according to your order, it is not mandatory that
you set the type. See the label on the rear of the unit for type information. If you want to
verify or change the system type, perform the following steps:
. Open the top cover of the UPS. Verify that all three breakers input breaker,
battery breaker, and output breaker are in the OFF (O) position.
. Apply AC input power and close ( I ) the input breaker in the UPS cabinet.
The front panel indicators come on and then go off. The alarm sounds, indicating
that the battery breaker is open (O). Press the Horn Silence button to turn off the
alarm.
. Press the Menu button to display &&'%
. Press the down arrow button until )%& &'# appears.
Press the Select button. The prompt %%("$ appears.
The default password is MEMORY. It is recommended to change the
default password to ensure security (see page 13). Contact your field
service representative if you have misplaced your password.
. Enter the password by using the up and down arrow buttons to scroll through
the letters; press the right and left arrow buttons to move to other character
positions.
. Press the Select button after entering the password. The display shows
& )#.
. Press the Select button to display the '&#'& "& option. Figure 4 shows
the unit types and possible configurations provided by the '&#'& "&
option.
You can press the down arrow button to scroll through all of the menu
options. The selected voltage is indicated with an asterisk (*).
. Press the right and left arrow buttons to view the possible settings for the
option. Press the Select button to select an Output Voltage
setting. The lineĆtoĆneutral (l-n) and lineĆtoĆline (l-l) voltages are displayed on
the menu.
. Press the down arrow button to view the option. Use the
right and left arrow buttons to view the settings. Press the Select button to
select an Output Frequency setting.
If an asterisk does not appear to the left of the newly selected output
voltage or frequency setting, verify that the UPS is off and that the output
breaker is off (O).
. Press the down arrow button to view the option. Use the right
and left arrow buttons to view the settings (240 DEG, 120 DEG, 180 DEG).
Press the Select button to select an Output Phase setting.
Select a new output phase if you receive a phase rotation error on the
front panel.
. Press the down arrow button to display the UPS Model number. This is a view
only option; you cannot change this selection.
. Wait 15 seconds for the UPS configuration to complete; then press the Menu
button four times to return to normal operation. Press the Select button once
to return to the menu.
System Startup
Make sure that the UPS is off (all indicators are off). Start up your system according to
one of the following procedures, depending on whether the Bypass feature is disabled
or enabled.
System Shutdown
Shut down your system according to one of the following procedures, depending on
whether the Bypass feature is disabled or enabled.
If the utility input voltage is removed from the UPS or the input breaker is
left open for an extended period, the batteries will be discharged. The batteries
must be disconnected from the UPS, opening the battery breaker will remove
all load from the batteries.
Power is applied to the UPS, but Output type set incorrectly. Reset the output voltage and
the UPS does not start up and frequency to match the inputs
the Bypass indicator is flashing. (see page 11).
Power is applied to the UPS, but Improper voltage applied to the Check the utility input voltage.
the UPS does not start up and unit.
no indicators
i di t are on.
Output breaker is open (O). Close ( I ) the output breaker.
UPS starts, enters Normal Battery not connected. Contact qualified service
mode, and then turns off; personnel.
or Battery indicator flashes and
alarm sounds while UPS is Battery breaker is not Close ( I ) the battery breaker.
on battery. closed (O).
Normal indicator flashing Input (bypass) out of frequency Check set type and sync range.
(bypass not available). or voltage limits.
Obtaining Service
If you have any questions or problems with your UPS, call for service at one of the
following telephone numbers and ask for a UPS technical representative.
In the United States
In Canada
All other countries
Please have the following information ready when you call for service:
Model number
Serial number
Version number (if available)
Date of failure or problem
Symptoms of failure or problem
Customer return address and contact information
For any warranty claim to be valid, the Warranty Registration Card must be on
file, or Proof and Date of Purchase must be available.
Model 12/8: 120/208 VAC 36A
Model 12/10: 120/208 VAC 42A
Model 12/12: 120/208 VAC 48A
Model 12/8: 120/208 VAC 34A
Model 12/10: 120/208 VAC 42A
Model 12/12: 120/208 VAC 50A
Floor Loading 1.48 lb/in2 (.12 kg/cm2) 2.43 lb/in2 (.17 kg/cm2) for 7 AH
2.88 lb/in2 (.20 kg/cm2) for 8 AH
*Power processor with one 7ĆAH battery cabinet: 475 lb (215 kg)
*Power processor with one 18ĆAH battery cabinet: 530 lb (240 kg)
Site Preparation
For optimum system operation, be sure that your site conforms to the following
specifications and requirements:
The maximum elevation for normal operation is 5000 ft (1500 m). Derating is
required for higher elevations.
Equipment weights are provided for typical configurations (see page 30). Contact
your local sales representative if additional information is needed.
Additional battery cabinets may be added for extended battery time.
The unit should be installed with these environmental specifications: operating
temperature of 0° to 40°āC and humidity of 5% to 95% (noncondensing).
Important Safeguards
Do not tilt the cabinet more than 12 degrees; the unit may tip over.
Do not connect more than three battery cabinets to the UPS unit to avoid fire and
electrical shock hazard.
To perform the Plus 12 installation, you need the following tools: a 5/16I and a 1/4I
hexĆnut driver. Make sure that you read all of the caution and warning statements in
Safety Considerations" beginning on page before performing the installation.
If your UPS is connected to a remote battery provided by another manufacturer,
disregard all references to battery cabinets in this section and see Installing Remote
Batteries" on page 49 for more information on installation and configuration.
The following instructions assume you have already removed the UPS and battery
cabinets from the pallets according to the unloading instructions on the outside of the
shipping box.
Use the following procedure to set up the UPS and battery cabinets:
. Place the UPS and battery cabinets near the operating site. Make sure the air
vents and exhausts are free of obstructions and the UPS is not near a heat
source or in direct sunlight.
It is recommended to allow a minimum of 24I of space on the left side of
the unit for access by qualified service personnel and a minimum of 8I of
space on the rear side for proper ventilation.
. Remove the joining kit hardware from the shipping carton. The hardware kit
should contain four joining brackets (one notched) and eight #10Ć32 .50
large hexĆhead screws.
. Remove the mounting plates from the pallets (see Figure 5).
Pallet
. Using the 5/16I bolts you took out when unloading each cabinet, bolt each
cabinet to the mounting plate as shown in Figure 7.
Mounting Screws
Service Plate
. Remove the two screws located at the top rear of the battery cabinet
(see Figure 9). Retain the screws.
Removable
Conduit
Plate
Communications Port
Air Exhausts
Battery
Spring
Latch
. Open the top cover of the UPS cabinet by sliding the cover latch forward and
lift up as shown in Figure 11.
UPS Cover Latch
Step 9
Figure 11. Removing the Top Cover from the UPS Cabinet
. Remove the right side cover of the UPS cabinet by removing the mounting
screws (four each) as shown in Figures 9 and 10.
. Pull the right side cover out from the top and then detach it from the system.
Retain the side cover and mounting hardware.
. Find the two interconnect cables secured to the top of the battery tray.
. Select either one of the cables. Cut the retaining straps.
. Connect the UPS to the first battery cabinet through the top cutout in the
battery cabinet (Figure 12).
Interconnect
Cables
Figure 12. Connecting the UPS and Battery Cables (Top View)
. Mate the connector with the mating half located in the I/O module as shown in
Figure 13. If the cabinets are not permanently mounted to the floor, you can
slide them apart to make the connection.
See Figure 14
I/O Module
Inverter Module
Rectifier Module
Figure 13. Connecting the UPS and Battery Cables (Right Side View)
. To connect a second battery cabinet, select either one of the two interconnect
cables located in the second battery cabinet. Cut and remove the retaining
straps. Connect to mating connector in the first battery cabinet.
Step 16
1st Battery Cabinet 2nd Battery Cabinet
See Figure 13
. Join the cabinets together in four places as shown in Figure 15.
Mounting Screws
Top View
Mounting Screws
Front View
Mounting Screws
Rear View
Mounting Screws
Figure 15. Joining the Cabinets (Top, Front, and Rear View)
. Remount the right side cover that was removed from the UPS cabinet in
Step 10 to the right side of the last battery cabinet. Use the original hardware
provided in the joining kit.
. Remount the top cover of the battery cabinet by offsetting the cover toward
the back. Push it forward so that the spring latch engages the frame top.
Secure the cover using the original hardware.
. Close the top cover of the UPS unit.
. Continue to Electrical Installation" on page 42.
If you are installing an optional PDM, continue to page 46.
All cabinets must be secured to keep them from moving after installation
is complete. Secure the cabinets by bolting the cabinets to the cabinet mounting
plate. Failure to do so violates safety rules and results in the unit losing its safety
agency approvals.
Electrical Installation
Refer to your national and local electrical codes for acceptable external wiring
practices. Material and labor for the external wiring are customerĆsupplied. An external
protective device for the input source must be provided and sized for the currents
indicated on the UPS nameplates.
NOTE: Upstream protection must be coordinated with the load current requirements
under nominal as well as lowĆline and overload conditions. The recommended
input stream service protection is 60 amps.
The UPS must be grounded at the input terminal block to a singleĆpoint local or utility
earth ground. The ground conductor should be sized according to your national and
local electrical codes. In the United States, the output is a separatelyĆderived source.
If you are using remote batteries, a DC breaker suitable for branch circuit protection
is required. The DC breaker is customerĆsupplied and must be rated at 250V, 75A.
The maximum fault current from a remote battery cannot be more than 4500 amps.
See Figure 16 for the location of the power cable terminal block and the conduit
access. Use the following procedure to perform the electrical installation for your UPS:
Battery Cabinet UPS Cabinet
Power Cable
Terminal Block
Removable
Conduit
Plate
. Hardwire the input and output terminations for the UPS. See the following
table for specifications. Refer to the label located on the inside of the UPS
cabinet for terminal block torque requirements. See the Oneline Drawing
(110719208) for terminal block diagrams.
*) %$ The UPS contains its own energy source (battery). There is high
voltage present at terminals 8 and 9 (terminals for remote battery connection)
when a battery cabinet is connected to the UPS.
. As part of the branch circuit that supplies this unit, install an insulated
grounding conductor. Use the following specifications for the grounding
conductor that connects to the input terminal block:
S )' " $ $(*") %$ ) !$(( must be identical to the grounded and
ungrounded branchĆcircuit supply conductors
S %"%' should be green with or without a yellow stripe(s)
S '%*$ should be grounded to the earth ground in the service equipment
or in the supply transformer (if supplied by a separatelyĆderived system)
All attachment plugĆreceptacles on or connected to your UPS or system
equipment must be a grounding type. The grounding conductors serving
these receptacles must be connected to the earth ground in the service
equipment.
. For 120V output, continue to Step 6. For 220, 230, or 240V output skip to
Step 11. See the Oneline Drawing (110719208) for the connection locations of
your particular Plus 12 model.
Grounding Jumper
Neutral Bonding
Jumper Grounding
Jumper
The REPO wires are at highĆvoltage potential (240V). Refer to your
local electrical code for proper installation of the highĆvoltage REPO wires.
. Replace the terminal block plate and the conduit plate on the UPS rear panel.
. Continue to the following section, Final Configuration."
Final Configuration
After you have installed the UPS, perform the following steps for the bypass and input
configuration.
Bypass Configuration
#" Any change to the bypass configuration must be made when there is no
power to the unit. Failure to do so may result in damage to the load.
. Locate the Bypass Configuration switch on the rear panel of the UPS
(see Figure 9 on page 37) and Maintenance Bypass switch on the top panel
of the UPS (see Figure 10 on page 37).
ENABLE
I ON I
S1 S3
O OFF O
DISABLE
S2
To perform the PDM installation, you need the following tools: a 1/4I hexĆnut driver, a
small flatĆhead screwdriver, and a 1 3/8I wrench. Make sure that you read all of the
caution and warning statements in Safety Considerations" beginning on page before
performing the installation.
The following instructions assume you have already installed the UPS and battery
cabinets according to the procedure in Installing the UPS and Battery Cabinets" on
page 34.
The critical load is deĆenergized during the PDM cabinet installation.
Make sure your UPS is shut down before performing any steps in this section
(see page 23).
. Make sure all of the PDM circuit breakers are in the OFF (O) position.
. Hang the PDM on the PDM mounting bracket, aligning the mounting holes on
the PDM with the holes on the mounting bracket. Using the four hexĆhead
screws provided in the hardware kit, secure the PDM to the top and bottom
frame of the battery cabinet.
. Remove the PDM terminal block access plate and retain the screws.
. Attach the strain relief connected to each end of the output cable to the
conduit mounting plate by removing the nut and placing it on the back side of
the conduit mounting plate. Secure tightly.
To ensure proper strain relief of the cable, do not loosen or remove the strain relief
clamp from the cable during installation.
Output Terminals
PDM Terminal
Block Access
Plate
PDM Terminal
Block
(optional)
Conduit
Mounting
Plate
. Connect the wires from the PDM to the UPS output terminal block as shown in
Figure 22. Refer to the label located on the inside of the PDM for terminal
block torque requirements. Use only #6ĆAWG 75°āC copper wire (minimum).
If you are using the optional hardwired PDM, connect the wiring to the terminal
block according to the label located on the inside of the PDM for the UPS output.
Use the conduit plate for conduit landing.
The UPS contains its own energy source (battery). There is high
voltage present at terminals 8 and 9 (terminals for remote battery connection)
when a battery cabinet is connected to the UPS.
. Nominal battery voltage is 240 Vdc (120 cells @ 2.0 Vdc). Float voltage should
not exceed 270 Vdc.
. Determine the desired backup time and the operating temperature.
. The lowĆbattery shutdown voltage is customerĆselectable. It can be set
between 1.67 Vdc/cell and 1.85 Vdc/cell. Select a value suitable for your
application to size your battery and make sure you set the value when
configuring the UPS.
. Follow the battery manufacturer's application notes and charts to calculate the
battery capacity necessary for your application.
. The UPS has a cyclic battery charger (turn on = 265 Vdc, turn off = 285 Vdc)
that delivers a maximum current of 5 amps. The internal charger must be
disabled when an external charger is used. For battery sizes above 75 AH, an
external charger is recommended.
Mounting Screws
Service Plate
. Press the down arrow button until appears. Press the
Select button.
. Using the up and down arrow buttons, scroll to . Press the
Select button.
. A menu appears that allows you to select the lowĆbattery
shutdown level.
Use the left and right arrow buttons to scroll through the different options. Press
Select to choose the desired level. An asterisk appears to the left of the
newly selected option.
If the Custom DCUV selection does not appear after selecting Custom
Battery, verify that the UPS is off or on bypass.
. Press the Menu button four times to exit System Setup.