Logamatic 2107 Controls Applications Manual 06.2018 Us
Logamatic 2107 Controls Applications Manual 06.2018 Us
Logamatic 2107 Controls Applications Manual 06.2018 Us
2 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
Table of Contents
1 Introduction 4
2 Terms 5
3 Control Programming 7
5 Setting Parameters 10
6 Troubleshooting 12
8 Application Drawings 20
9 Burner/Boiler Wiring 52
11 Mixing 67
12 Tables/Formulas 70
|3
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
1 Introduction
This manual addresses some of the many applications that are
possible using Buderus outdoor reset controls. Applications
depicted in the manual are presented with both hydraulical and
electrical outlines. The drawings contained in this manual are
intended to be used as an aid to system installers and
designers and are conceptual in nature. Auxiliary equipment
depicted in this manual does not necessarily represent any one
particular manufacturer or specific model number. There are a
wide variety of techniques, practices and piping arrangements
possible with hydronic heating systems and it is the
responsibility of the installing contractor to determine which of
these is best suited for a specific application.
4 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
2 Terms
Outdoor Reset: Outdoor reset is a control method that takes The constant circulation zone will only be interrupted under the
outdoor air temperature into consideration when determining the following conditions:
system water temperature. Instead of a fixed high limit • Domestic hot water priority.
temperature (i.e. 180°F (82°C)), the high limit is reset to a • Certain setback modes (See the control Service Manual for
temperature high enough to satisfy the heat loss at any given information on various setback modes).
outdoor temperature. • Condensate protection. If boiler water temperature falls below
the condensate protection temperature while the burner is
In designing a heating system the first requirement is an accurate firing, the space heating circulator(s) will be shut off. Once the
heat loss calculation. Several factors are used in determining heat boiler temperature reaches a safe level, circulator operation
loss; the volume of space being heated, type of materials being will resume.
used in construction, insulation values and a design temperature. • When the outdoor temperature rises above the WWSD (warm
The design temperature represents the coldest day of the year. weather shut down) setting.
The heat loss calculation is then used to determine the output
requirements for the boiler, baseboard, panel radiators, etc. In WWSD: Warm weather shut down or summer-winter changeover,
short the system is sized to heat the house on the coldest day of is the outdoor air temperature at which the space heating function
the year. of the system shuts down. With the Buderus control system this
temperature is adjustable from 49°F to 87°F (9°C to 31°C). When
However, a building‘s heat loss is ever changing; and is largely the outdoor temperature rises above the WWSD set point, the
dependent on outdoor temperature. As the outdoor temperature system will only operate for domestic hot water production. (For
drops, the heat loss increases and as it rises the heat loss detailed operation of the WWSD feature refer to the control
decreases. The fact is that approximately 98% of the heating Service Manual).
season the boiler and radiators are oversized. With
outdoor reset controlling you can more accurately match the BFU Room sensor: The Buderus room sensor is similar to a
output from the heating system to the current heat loss. For thermostat although it will not turn a circulator on or off. The
example, it may require 180°F (82°C) water temperature function of the room sensor is to continually monitor room
circulating through the system in order to have enough output to temperature and relay this information back to the control system.
maintain a 70°F (21°C) indoor temperature on a 10°F (-12°C) day. This information is used to compensate for variations in room
Yet, at a 40°F (5°C) outdoor temperature it may only require temperature due to internal heat gains (or losses) such as solar
135°F (57°C) water temperature to satisfy the heat loss. By gain, fireplaces, wood stoves, appliances, lighting, people, open
resetting the system water temperature, a lower average water doors or windows, etc. The control compensates for these
temperature is used throughout the heating season and maximum variations by adjusting the system water temperature (up or down)
temperature is used only on the coldest days of the year. in order to maintain the desired room temperature. Buderus room
sensors also allow the occupant to manually override
Among the many benefits to this type of controlling is optimum programmed setback periods.
fuel economy. By only heating the water to the minimum
temperature needed, fuel economy is maximized (as much as The control system allows you to limit the amount of
30% in fuel savings!). Lower standby losses during “off” cycles compensation that the room sensor has over the selected
(due to a lower boiler temperature) also reduce fuel consumption. heating curve. This setting is referred to as “ROOM COMP” and
In addition, the room comfort level is significantly increased by can be adjusted at the programming level of the control. This
matching the heat output to the current heat loss. Less room setting is only available when using a room sensor.
temperature fluctuation is realized. System noise caused by
expansion of piping is significantly reduced due to lower system You may want to limit compensation if secondary zones are under
water temperatures. radiated.
Example: The main heating zone (continuous circulation) zone is
Constant circulation zone: A constant or continuous circulation experiencing solar heat gain. The room sensor senses the rise in
zone is just what the term implies, water continuously circulates room temperature and lowers the system water temperature in
through a given zone when the heating system is in operation. order to keep the zone from over heating. In this scenario, the
The water temperature in this zone is modulated so that the heat system water temperature could be lowered enough so that the
output from the distribution units (i.e., fin-tube baseboard, panel output from a secondary zone was insufficient to satisfy that zone.
radiators, radiant floors, etc.) matches the rate of heat loss for that
zoned area. A constant circulation zone is typically the main Only one Buderus room sensor can be used for high temperature
heating zone. In multi-zone systems, the constant circulation zone space heating (a second room sensor can be added when using
must require the highest system water temperature. With this an FM241 module for motorized mixing of a lower water
method of controlling, a room sensor is required in order to temperature).
monitor room temperature. All secondary zones will have standard
room thermostats to intermittently operate a zone valve or zone Careful consideration must be given to placement of room
circulator. sensors. Keep in mind that not all applications are suitable for
using a constant circulation zone. Avoid using a room sensor in a
small baseboard zone as overheating may occur during DHW
|5
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
6 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
3 Control Programming
The following will allow access to the service side of the control: and want to do the temp set back by it, you will need to
change it to RMSETBACK.
1. Push and hold the turn page button " " while inserting
a pen or wire into the hole " " on the display. 13. Turn the blue dial one more time and OFFSET will appear.
The setting will be at 0°F (0°C) and is okay with normal
2. The word AMERICAN will be displayed. radiation, but if you have an air handler, you will need to
raise the offset to 9°F (5°C). This will raise the beginning of
3. Turn blue dial once to the right, BLR TEMP will be displayed. the curve and supply enough temperature on milder days.
This is a main category.
14. Push and release the return button " " again.
4. Push and release return button to access sub menu.
FREEZE TEMP will be displayed. If the outdoor 15. Turn the blue dial one more time and DHW PROD will
temperature drops beneath the frost protection limit, the appear. The factory setting is ON. If no DHW tank is
heating system pump (contacts 61/63) will be started. installed, hold down the " " button and turn until it says
Factory default: 41°F (5°C). OFF and release.
5. Turn blue dial one more time and BUILD RESP will be 16. Turn the blue dial one more time and RECIRPUMP will
displayed. The current setting will be 2, change that to 1 by appear. The setting is 2, it can be changed to OFF,
holding the " " button and turning the blue dial until 1,2,4,5,6,ON. The pump will run 3 minute cycles depending
you get to the number 1 and release. This will let the boiler on the number of cycles you choose per hour. If you do not
respond faster to outside air temp changes. have a recirc pump turn it to OFF.
6. Turn the dial one more time and PUMPLOGIC will be 17. Turn the blue dial one more time and HTG CURVE1 will
displayed. The current setting is 104°F (40°C). This will not appear. Hold the " " button and turn the blue dial. It
let the burners and the pump run at the same time below will show you three points on the curve so you can see what
104°F (40°C) to protect from condensation. the water temp will be at 3 different points, then release.
7. Turn the dial one more time and MAXTEMP1 will be 18. Turn the blue dial one more time and RELAYS will appear.
displayed. The current setting for this is 176°F (80°C). To This will allow you to test all the components that are wired
change this to 194°F (90°C), hold down the " " button to the 2107 control.
and turn the blue dial until 194°F (90°C) appears, then
release. (this may not be necessary unless under radiated) 19. Push the " " button and BURNER will appear. Hold
the " " button and turn the blue dial and the LCD will
8. Now push the return button " " once. read ON, release and the burner will start. Hold the " "
button and turn the blue dial and the LCD will read OFF,
9. Now you are back to the main categories. Turn the blue dial release and the burner will turn OFF.
once to the right and it will read CIRCUIT1.
20. Test the Heating Pump (constant circulation pump),
10. Push and release the " " button and REF TEMP will DHW Tank Pump, and DHW Recirc Pump the same way.
be displayed which represents the boiler water temperature
at 14°F (-10°C). Default is 167°F (75°C). Refer to page 20 21. When you are done with the RELAY tests push the return
in the service manual for graphing REF TEMP changes. button " ".
11. Turn the blue dial one more time and REMOTE1 will appear. 22. Turn the blue dial one more time and LCD-TEST will
The factory setting is off, and the only time you have to turn appear. To test the LCD display, hold the " " button
this on is if you are using a BFU room sensor. Use a BFU and turn the blue dial, release and it should read
room sensor for constant circulation on one zone and power LCD-TEST.
the pump off of 61 and 63.
23. Turn the blue dial one more time and RESET should
Once REMOTE1 setting is turned „on“, the ROOM COMP appear. To reset the control back to factory settings, hold
parameter will be displayed. Use ROOM COMP to adjust the the " " button until all of the 8‘s disappear and release.
room influence on the heating curve. The first thing you will need to do is go back to the language
and it will read DEUTSCH. Hold the " " button and
12. Turn the blue dial one more time and OASETBACK will turn the blue dial until you read AMERICAN on the LCD.
appear. Hold the " " and turn the blue dial to The control is now back to factory setting.
SETBACK. On the OASETBACK mode, the pumps will
turn off in the night setback mode if the temp outside is Now push the AUT button and you will be back in Automatic
above the freezetemp. In the SETBACK mode the curve mode.
will drop back for fuel savings. If you have a room sensor
|7
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
Notice:
8 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
G215
Figure 1 Logabracket installation
It is necessary to bend down the tabs on the rear jacket panel
to prevent interference between bracket and jacket panel. 1 Logabracket
2 2107 Logamatic control
3 Screws
G234X, G334X
Simply cut off the tabs of the bracket and mount on the rear
panel by drilling an additional hole for a second mounting screw.
GA124, GA244
|9
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
+ Press the ‘Display’ key and ‘Install’ key at the same time to call up the
service level. Alternatively press (1....7), clock, and return arrow button
simultaneously. See Chapter 3 for extended functions.
Display
10 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
Display
SOLAR7
RESET Reset
6 Only if FM 241 module is installed and if heating circuit 2 is selected as an "FLOOR HTG" or "PERIM HTG" heating system.
| 11
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
6 Troubleshooting
6.1 "NO HEAT" call
LT GRY
ZM1
“BRENNER” (burner) wiring block Example: Outdoor temperature at 32°F, based on heating curve
the water temperature required is 140°F with a 26°F burner
– Terminal 4 – 120V Neutral differential.
– Terminal 8 – 120V input clocks hours run meter The differential (26°F) is split (13°F) above & (13°F)
(must be field wired) below the target temperature.
– Terminal 9 – 120V input displays “BURNER ERR” 140°F target + 13°F = 153° high limit
message (must be field wired)
140°F target - 13°F = 127° low limit
– Terminal 10 / 11 – “dry” contacts close to energize
burner This 127°F to 153°F becomes the range of temperature that the
boiler will maintain. As zones call and pull heat from the boiler,
– Terminal 12 – 120V power (drops out when manual eventually the temperature in the boiler drops. Once the
reset limit is tripped) temperature in the boiler hits the low limit (127°F) the R2107
control closes a switch (dry contacts) between terminals 10 & 11
to fire the boiler (this is indicated by a flame symbol displayed
on the LDC screen of the R2107). When the boiler temperature
reaches the high limit (153°F), the contacts open and the boiler
Burner operation stops firing.
The R2107 is not a cold start control. It does not reply on a call Once the outdoor temperature drops below the WWSD setting,
for heat from an end switch or thermostat to fire the boiler. the boiler begins to maintain temperature. Above WWSD the
boiler will only fire on a call for DHW.
The boiler will maintain a range of water temperature based on
outdoor temperature. The differential of this range is dynamic,
meaning that it is not fixed, and will adjust based on outdoor
temperature and current system load. The starting point of the
differential is 27°F (15°C) and will adjust from there. The
differential will generally be wider at milder outdoor
temperatures and narrower at colder outdoor temperatures.
12 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
Oil burners – factory jumper between terminals 12 & 10, brings Gas burners – remove factory installed jumper between
120V from 12 to 10. When contacts close between terminals 10 terminals 10 & 12. The contacts between terminals 10 & 11 are
& 11, 120V power is sent from terminal 11 to Hot on the burner now “dry” (no voltage present) and switching to the burner is
(terminal 4 is the neutral). now low voltage between terminals 10 & 11 on the R2107 and
TT (or RW) on the boiler aquastat.
| 13
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
18
11
18
14 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
For example: Customer says they can’t get the house above 65°F.
We need to increase the room temperature by 5°F
…5 x 2.5 = 12.5.
| 15
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
DHW ERR - when the tank temperature drops to the low limit
(7°F below the set point), the R2107 goes into DHW priority
mode.
At this point, the control will go back to space heating mode and
lock out the DHW to avoid freezing the building. This message
is general in nature and the R2107 control is essentially telling
you, “I tried to make domestic hot water but nothing happened”.
The R2107 will again try to make DHW. Check terminals 24 &
25 for 120V. If power is present and boiler fires the R2107 is
o.k.
1 - bad circulator
4 - closed valve
16 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
7 Description of wiring
terminals
LT GRY
ZM1
Note: Power to terminals 61 and 63 are interrupted when the system is in domestic water production. Therefore, there will
never be power on terminals 24/25 and 61/63 at the same time, while operating in automatic mode
| 17
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
18 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
Optional modules:
FM241 Mixing module
Brown (SH/PH-HK2) Mixing and Space heating circuit #2:
Terminal 41 Power input for mixing motor
Terminal 43 “OPEN” output to mixing motor
Terminal 44 “CLOSE” output to mixing motor
Terminals 61/63 Power output for circuit #2 pump(s) (2 amp max)
(refer to section 7 of this manual for detailed wiring information for FM241)
| 19
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
8 Application drawings
Description (page#)
Single temperature systems
Multi-Temperature Systems
Boiler/Burner Wiring
20 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
Mechanical/Electrical Symbols
| 21
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
• Boiler temperature is maintained based on the selected • The boiler temperature rises on a call for DHW for fast
heating curve and inputs from both the outdoor sensor and recovery.
indoor room sensor.
• The control powers the domestic pump (PS) and the heating
• During setback periods, the boiler temperature will be reduced circuit (PH) is shut down.
based on the night setback setting on the room sensor.
• After the DHW recharging and intelligent purge cycle is
• The space heating pump (PH) runs continuously with the completed, the PS pump will be shut down and PH circuit will
following exceptions: be turned on.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
4) Initial part of setback period
22 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
PH
| 23
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
• Boiler temperature is maintained based on the selected • The boiler temperature rises on a call for DHW for fast
heating curve and input from the outdoor sensor. recovery.
• During setback periods, the boiler temperature will be reduced • The control powers the domestic pump (PS) and the heating
based on the DAY TEMP and NIGHT TEMP settings on the circuit (PH) is shut down.
Logamatic control.
• After the DHW recharging and intelligent purge cycle is
• The space-heating pump (PH) requires a switching relay to completed, the PS pump will be shut down and PH circuit will
operate on a call for heat from a room thermostat. be turned on.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
24 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
| 25
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
Space Heating Operation: • This application requires a room sensor for constant
circulation.
• Boiler temperature is maintained based on the selected
heating curve and inputs from both the outdoor sensor and DHW Heating Operation:
indoor room sensor.
• The boiler temperature rises on a call for DHW for fast
• During setback periods, the boiler temperature will be reduced recovery.
based on the night setback setting on the room sensor.
• The control powers the domestic pump (PS) and the heating
• The constant circulation zone pump (P1) will be wired directly circuit (PH-HK1) is shut down.
to the PH-HK1 circuit on the Logamatic control. Additional
zone pumps require a multi-zone switching relay to operate on • After the DHW recharging and intelligent purge cycle is
a call for heat from a room thermostat. completed, the PS pump will be shut down and PH-HK1 circuit
will be turned on.
• Power to the PH-HK1 circuit is interrupted under the
following conditions:
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
4) Initial part of setback period
26 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
Space Heating Operation: • This application requires a room sensor for constant
circulation.
• Boiler temperature is maintained based on the selected
heating curve (REF TEMP and OFFSET) and inputs from the • End switch (XI - X2) on multi-zone relay panel is not used.
outdoor sensor (FA), boiler sensor (FK) and room sensor (BF)
.
• This application requires a multi-zone pump relay (not DHW Heating Operation:
supplied by Buderus). 120V output from terminal 63 (PH-HKl)
will energize the relay. However, the PH-HK1 circuit is limited • The tank sensor (FB) monitors domestic water temperature.
to a 5 amp maximum load. Therefore, multi-pump applications
require an additional source of 120V power to the pump relay. • 120V output from terminals 24 & 25 (PS) powers the DHW
Generally the #63 terminal is wired to the ZC terminal on the pump.
relay panel, however relay circuitry can vary. Refer to wiring
diagrams provided in this manual for specific manufacturer • During a call for DHW production the domestic pump (PS) is
and model of the relay being used. If the model being used is turned on and the space-heating circuit (PH-HK1) is turned off.
not listed, contact Buderus for assistance.
• After the DHW recharging and intelligent purge cycle is
• The constant circulation pump (PI) shall run continuously (see completed, the PS pump will be shut down and PH-HK1 circuit
following exceptions). All other zone pumps are energized on will be turned on.
a call for heat from a room thermostat.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
4) Initial part of setback period
| 27
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
• Boiler temperature is maintained based on the selected • The boiler temperature rises on a call for DHW for fast
heating curve and input from the outdoor sensor. recovery.
• During setback periods, the boiler temperature will be reduced • The control powers the domestic pump (PS) and the heating
based on the DAY TEMP and NIGHTTEMP settings on the circuit (PH-HK1) is shut down .
Logamatic control.
• After the DHW recharging and intelligent purge cycle is
• Space heating pumps require a multi-zone switching relay completed, the PS pump will be shut down and PH-HK1 circuit
to operate on a call for heat from a room thermostat. will be turned on.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
4) This application does not require a room sensor.
28 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
• Boiler temperature is maintained based on the selected • The tank sensor (FB) monitors domestic water temperature.
heating curve (REF TEMP and OFFSET) and inputs from the
outdoor sensor (FA) and boiler sensor (FK). • 120V output from terminals 24 & 25 (PS) powers the DHW
pump.
• This application requires a multi-zone pump relay (not
supplied by Buderus). • During a call for DHW production the domestic pump (PS) is
turned on and the space-heating circuit (PH-HK1) is turned off.
• 120V output from terminal 63 (PH-HK1) will energize the
relay. However, the PH-HK1 circuit is limited to a 5 amp • After the DHW recharging and intelligent purge cycle is
maximum load. Therefore, multi-pump applications require an completed, the PS pump will be shut down and PH-HKl circuit
additional source of 120V power to the pump relay. Generally will be turned on.
the #63 terminal is wired to the ZC terminal on the relay panel,
however relay circuitry can vary. Refer to wiring diagrams
provided in this manual for specific manufacturer and model of
the relay being used. If the model being used is not listed,
contact Buderus for assistance.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
| 29
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
• Boiler temperature is maintained based on the selected • The boiler temperature rises on a call for DHW for fast
heating curve and inputs from the outdoor sensor and indoor recovery.
room sensor.
• The control powers the domestic pump (PS) and the heating
• During setback periods, the boiler temperature will be reduced circuit (PH-HK1) is shut down.
based on the night setback setting on the BFU room sensor.
• After the DHW recharging and intelligent purge cycle is
• Constant circulation zone (Z1): Zone valve will be powered completed, the PS pump will be shut down and PH-HK1 circuit
open when the PH-HK1 circuit is on. will be turned on.
• Additional zone valves will open on a call for heat from their
respective room thermostats.
• The PH-HK1 circuit and space heating pump (PH) shall have
continuous power with following exceptions:
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
4) Initial part of setback period
30 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
BOILER
• Boiler temperature is maintained based on the selected • The tank sensor (FB) monitors domestic water temperature.
heating curve (REF TEMP and OFFSET) and inputs from the
outdoor sensor (FA), boiler sensor (FK) and room sensor • 120V output from terminals 24 & 25 (PS) powers the DHW
(BFU). pump.
• This application requires a 24V transformer to power zone • During a call for DHW production the domestic pump (PS) is
valves (not supplied by Buderus). Transformer must be sized turned on and the space-heating circuit (PH-HKl) is turned off.
per manufacturer‘s instructions.
• After the DHW recharging and intelligent purge cycle is
• 120V output from terminal 61 & 63 (PH-HK1) will provide completed, the PS pump will be shut down and PH-HK1 circuit
power to both the space heating pump (PH) and the 24V will be turned on.
transformer.
• The PH-HK1 circuit and space heating pump (PH) shall have
continuous power with the following exceptions:
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
4) Initial part of setback period
• Boiler temperature is maintained based on the selected • The boiler temperature rises on a call for DHW for fast
heating curve and input from the outdoor sensor. recovery.
• During setback periods, the boiler temperature will be reduced • The control powers the domestic pump (PS) and the heating
based on the DAY TEMP and NIGHT TEMP settings on the circuit (PH-HK1) is shut down.
Logamatic control.
• After the DHW recharging and intelligent purge cycle is
• All zones require a call for heat from their respective room completed, the PS pump will be shut down and PH-HK1 circuit
thermostats to open zone valve and operate space-heating will be turned on.
pump (PH).
• All zone valves will close when the PH-HK1 circuit is turned
off.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
32 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
BOILER
Space Heating Operation: • The PH-HK1 circuit shall have continuous power with the
following exceptions:
• Boiler temperature is maintained based on the selected
heating curve (REF TEMP and OFFSET) and inputs from the 1) DHW priority
outdoor sensor (FA) and boiler sensor (FK). 2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
• This application requires a 24V transformer to power zone
valves (not supplied by Buderus). Transformer must be sized • This application does not require a room sensor.
per manufacturers instructions.
• This application requires a pump-switching relay (not supplied DHW Heating Operation:
by Buderus).
• The tank sensor (FB) monitors domestic water temperature.
• 120V output from terminal 61 & 63 (PH-HK1) will provide 120V output from terminals 24 & 25 (PS) powers the DHW
power to both the space heating pump relay and the 24V pump.
transformer.
• During a call for DHW production the domestic pump (PS) is
• Zone valves will open on a call for heat from their respective turned on and the space-heating circuit (PH-HKl) is turned off.
room thermostats. Zone valve end switches will pull in pump
relay to operate space-heating pump (PH). • After the DHW recharging and intelligent purge cycle is
completed, the PS pump will be shut down and PH-HK1 circuit
will be turned on.
| 33
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
34 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
• The boiler temperature rises on call for DHW for fast recovery.
• The control powers the domestic pump (PS) and the heating
circuit (PH-HK1) is shut down.
| 35
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
ZM1
LT GRY
36 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
HK1 circuit (high temperature) • The tank sensor (FB) monitors domestic water temperature.
• Boiler temperature is maintained based on the selected
heating curve (REF TEMP 1 and OFFSET 1) and inputs from • 120V output from terminals 24 & 25 (PS) powers the DHW
the outdoor sensor (FA) and boiler sensor (FK). pump.
• This application requires a multi-zone pump relay (not • During a call for DHW production the domestic pump (PS) is
supplied by Buderus). turned on and the space-heating circuit (PH-HK1) is turned off.
• 120V output from terminal 63 (PH-HK1) will energize the • After the DHW recharging and intelligent purge cycle is
relay. However, the PH-HK1 circuit is limited to a 5 amp completed, the PS pump will be shut down and PH-HK1 circuit
maximum load. Therefore, multi-pump applications require an will be turned on.
additional source of 120V power to the pump relay. Generally
the #63 terminal is wired to the ZC terminal on the relay panel, • During the DHW cycle the PH-HK2 circuit remains on. The
however relay circuitry can vary. Refer to wiring diagrams mixing valve can be set to either continue normal operation or
provided in this manual for specific manufacturer and model of fully close to prioritize DHW production. (Refer to the
the relay being used. If the model being used is not listed, Logamatic Service Manual for setting options)
contact Buderus for assistance.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
| 37
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
38 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
Space Heating Operation: Note: 8.8 Electrical diagram on the following page.
1) Condensate protection
2) Outdoor temperature exceeds WWSD setpoint
3) DHW priority
• The system pump may also shut down during the initial part of
night setback period if a BF room sensor is being used for high
temperature space heating.
• The control powers the domestic pump (PS) and the heating
circuit (PH-HK1) is shut down.
• The PH-HK2 circuit will remain on during the DHW cycle. The
mixing valve can be set to either continue normal operation or
fully close to prioritize DHW production. (Refer to the
Logamatic Service Manual for setting options)
| 39
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
ZM1
BOILER
LT GRY
40 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
1) Condensate protection
2) Outdoor temperature exceeds WWSD setpoint
• During the DHW cycle the PH-HK2 circuit remains on. The
mixing valve can be set to either continue normal operation or
fully close to prioritize DHW production. (Refer to the Logamatic
Service Manual for setting options)
| 41
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
SENSOR
• Boiler temperature is maintained based on the selected • The boiler temperature rises on a call for DHW for fast
heating curve and input from the outdoor sensor. recovery.
• During setback periods, the boiler temperature will be reduced • The control powers the domestic pump (PS) and the heating
based on the DAY TEMP and NIGHT TEMP settings on the circuit (PH-HK1) is shut down.
Logamatic control.
• After the DHW recharging and intelligent purge cycle is
• Power to the PH-HK1 circuit shall be interrupted under the completed, the PS pump will be shut down and PH-HK1 circuit
following conditions: will be turned on.
42 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
SENSOR
BOILER
LT GRY
ZM1
| 43
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
• The control will stage either one or two boilers to maintain the
desired set point. Refer to control Service Manual for wiring
information for burners.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
44 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
• The primary loop temperature is maintained based on the • The boiler temperature rises on a call for DHW for fast
selected heating curve and input from the outdoor sensor. recovery.
• During setback periods, the boiler temperature will be reduced • The control powers the domestic pump (PS) and the heating
based on the DAY TEMP and NIGHT TEMP settings on the circuit (PH-HK1) is shut down.
Logamatic control.
• After the DHW recharging and intelligent purge cycle is
• Boiler pumps (P1,P2) shall be wired to the Honeywell L8148 completed, the PS pump will be shut down and PH-HK1 circuit
aquastat (L8148 (oil) or L7148 (gas)) and will operate on a will be turned on.
demand signal from the Logamatic control.
Notes:
• Power to the PH-HK1 circuit shall be interrupted under the 1. Boilers shall be piped in a primary/secondary arrangement
following conditions: with recommended spacing of 4 pipe diameters with a
maximum of 8" between the supply and return to the
1) DHW priority primary loop.
2) Condensate protection 2. A small thermal bypass shall be installed immediately after
3) Outdoor temperature exceeds WWSD setpoint the FK supply sensor in order to create flow past the
sensor when the system pump (PH) is off.
3. 8.10 Electrical diagram is on the following page
| 45
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
ZM1
LT GRY
46 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
• The control will stage either one or two boilers to maintain the
desired set point. Refer to control Service Manual for wiring
information for burners.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
| 47
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
P4
P3
SENSOR
• Boiler temperature is maintained based on the selected • On-demand zone requires a separate switching relay in order
heating curve and input from the outdoor sensor. to fire the boiler on a call for heat.
• Boiler will run to high limit on call from on-demand heat zone. • Power to the PH-HK1 circuit shall be interrupted under the
following conditions:
• During setback periods, the boiler temperature will be reduced
based on the DAY TEMP and NIGHT TEMP settings on the 1) DHW priority
Logamatic control. 2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
• Space heating pumps require a multi-zone switching relay to
operate on a call for heat from a room thermostat.
Note - As shown, the on-demand zone is interrupted during
DHW priority, WWSD and condensate protection. For year
round, 24-hour operation of the on-demand zones, disconnect
the PH-HK1 connection from ZC on the pump relay. This will
allow the on-demand zone to operate during DHW recharging
cycles. Consideration to boiler sizing must be given.
48 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
• The control powers the domestic pump (PS) and the heating
circuit (PH-HK1) is shut down.
| 49
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
ZM1
LT GRY
50 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
• Boiler temperature is maintained based on the selected • The tank sensor (FB) monitors domestic water temperature.
heating curve (REF TEMP and OFFSET) and inputs from the
outdoor sensor (FA) and boiler sensor (FK). • 120V output from terminals 24 & 25 (PS) powers the DHW
pump.
• Boiler will run to limit set on L8148 aquastat on a call for heat
from on-demand zone(s). • During a call for DHW production the domestic pump (PS) is
turned on and the space-heating circuit (PH-HK1) is turned off.
• This application requires a multi-zone pump relay (not
supplied by Buderus). The on-demand zone also requires a • After the DHW recharging and intelligent purge cycle is
separate pump relay to fire the boiler on a call for heat. When completed, the PS pump will be shut down and PH-HK1 circuit
using a heat exchanger as shown, pumps P3 and P4 must run will be turned on.
simultaneously. The demand signal from the on-demand
zone(s) (aquastat, thermostat or end switch) must be wired to
turn both pumps on.
1) DHW priority
2) Condensate protection
3) Outdoor temperature exceeds WWSD setpoint
| 51
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
9 Burner/Boiler wiring
Description
52 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
black
QRC
blue
brown
BURNER CONTROLLER
blue
black
BURNER CONTROL UNIT LMO
brown
blue
BURNER CABLE
MOTOR
black
M
4 10 11 9 8
yellow/green
blue IGNITOR
black
yellow/green
12
blue
VALVE
black
yellow/green
ZM1
| 53
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
ZM1
LT GRY
54 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
| 55
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
ZM1
RIELLO F40 SERIES
N
X
L
RED WIRE
JUMPER
INSTALLED
FACTORY
AL 1009 Control
RIELLO
LT GRY
56 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
| 57
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
ZM1
LT GRY
58 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
BV
BV
A
A
70200 CONTROL
CARLIN EZ-66
IGNITION
MOTOR
L1 OUT
VALVE
LIMIT
L1 IN
L2
L1
ZM1
| 59
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
IGNITER
IGNITER
L2 (IGN)
REMOVE
JUMPER
MOTOR
MOTOR
L2 (MTR)
VALVE
OIL VALVE
L2 (VLV)
CAD
TW
TR
CAD CELL
CELL
ZM1
60 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
| 61
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
ZM1
LT GRY
62 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
| 63
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
Description
64 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
ZM1
H
LT GRY
| 65
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
LT GRY
ZM1
66 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
11 Mixing
Description (page #)
| 67
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
68 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
(CLOSE)
(OPEN)
| 69
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Logamatic 2107 Controls
Applications Manual
12 Tables/Formulas
Flow Rate Calculations for Water Table 1 Flow Rate Calculations for Water Table 2
Temperature Drop Temperature Drop
BTU/H BTU/H
10 20 30 10 20 30
GPM GPM
5,000 1 0.5 0.33 200,000 40 20 13.0
60,000 12 6 4
70,000 14 7 4.7
Mixing Valve Sizing Table 3
75,000 15 7.5 5
GPM ESBE ESBE
80,000 16 8 5.3 (Radiant System) 3-Way 4-Way
85,000 17 8.5 5.7
1 to 8 ¾" ¾"
90,000 18 9 6 9 to 14 1" 1"
95,000 19 9.5 6.3 15 to 22 1¼" 1¼"
100,000 20 10 6.7 23 to 40 1½" 1½"
110,000 22 11 7.3 41 to 60 2" 2"
120,000 24 12 8 61 to 125 2½" * 2½" *
130,000 26 13 8.7 126 to 200 3" * 3" *
140,000 28 14 9.3 * Requires VM83 motor and VL800 linkage
150,000 30 15 10
160,000 32 16 10.7
170,000 34 17 11.3
180,000 36 18 12
190,000 38 19 12.7
70 |
Technical specifications are subject to change without prior notice Logamatic 2107 Controls applications manual | 06.2018
Applications manual Logamatic 2107 Controls
Applications Manual
Approx. Heat Output for Fin-Tube Baseboard Table 4 Conversion Formulas Table 6
Average Water Temperature BTU/Hr Per Lineal Ft @ Unit of Measure Formula
(°F) 1GPM Flow Rate
110 156
* Q(Load) = 8.31 (lbs/gal water) x Delta T x Gallons
120 209
| 71
Logamatic 2107 Controls applications manual | 06.2018 Technical specifications are subject to change without prior notice
Bosch Thermotechnology Corp.
65 Grove Street BTC 463001101 C | 06.2018
Watertown, MA 02472
Tel.: 866-642-3198
Fax: 603-965-7581
www.boschheatingandcooling.com