Nothing Special   »   [go: up one dir, main page]

Devicenet Armorblock™ Network Powered 16-Input Module: Installation Instructions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Installation Instructions

DeviceNet ArmorBlock™ Network


Powered 16-input Module
Catalog number 1732D-IBDPM12MND, Series A

Table of Contents

Topic Page
Important User Information 2

Environment and Enclosure 3

Preventing Electrostatic Discharge 3

About the Module 4

Catalog Number Explanation 5

Install the Module 5

Set the Node Address 5

Mount the Module 6

Connect the Cordsets 8

Communicate with the Module 9

Interpret Status Indicators 10

Specifications 12
2 DeviceNet ArmorBlock™ Network Powered 16-input Module

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical


equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1 available from your local Rockwell Automation sales office or online
at http://www.rockwellautomation.com/literature/) describes some important differences between
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an


explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to


personal injury or death, property damage, or economic loss. Attentions help you
identify a hazard, avoid a hazard and recognize the consequences.

SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of
the product.

Publication 1732D-IN007B-EN-E - November 2011


DeviceNet ArmorBlock™ Network Powered 16-input Module 3

Environment and Enclosure

ATTENTION: This equipment is intended for use in overvoltage Category II


applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft)
without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR 11. Without appropriate precautions, there may be difficulties
with electromagnetic compatibility in residential and other environments due
to conducted and radiated disturbances.
This equipment is supplied as enclosed equipment. It should not require
additional system enclosure when used in locations consistent with the
enclosure type ratings stated in the Specifications section of this publication.
Subsequent sections of this publication may contain additional information
regarding specific enclosure type ratings, beyond what this product provides,
that are required to comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1, for additional installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the
degrees of protection provided by enclosures.

Preventing Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic discharge, which can


cause internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.

Publication 1732D-IN007B-EN-E - November 2011


4 DeviceNet ArmorBlock™ Network Powered 16-input Module

About the Module


The DeviceNet 1732D ArmorBlock I/O family consists of standalone 24V DC I/O
modules that communicate via the DeviceNet network. The sealed IP67 housing of these
modules requires no enclosure. Note that environmental requirements other than IP67
may require an additional appropriate enclosure. I/O connectors are sealed M12-style.
The 1732D-IBDPM12MND module is shown here.
DeviceNet ArmorBlock Network Powered 16-input Module

Mini-style
D
DeviceNet N
e
connectors MOD
t
NET
In

I-0 I - 15

I-1 I - 14
I-2 I - 13

12 mm I/O 12 mm I/O
connectors I-3 I - 12
connectors
I-4 I - 11

I-5 I -10

I-6 I-9

I-7 I-8

0 0

8 2 8 2
Node address
Protective 6 4 6 4
X10 X1
earth
44773

Ground Conductors

Conductor Description
Protective earth Provides the grounding of field devices and is internally
connected to each Pin 5 of the M12 I/O connectors.

Publication 1732D-IN007B-EN-E - November 2011


DeviceNet ArmorBlock™ Network Powered 16-input Module 5

The DeviceNet network uses advanced network technology, producer/consumer


communication, to increase network functionality and throughput. Visit our web site
at www.ab.com/networks for producer/consumer technology information and updates.

Catalog Number Explanation


The catalog number 1732D-IBDPM12MND refers to a DeviceNet 24V DC 8-port,
16-input mini-style network connector module.

Install the Module


To install the module:
• Set the node address.
• Mount the module.
• Connect the cordsets.

Set the Node Address


Valid node addresses are 00…63.
Set the node address using either the rotary switches, RSNetWorx for DeviceNet,
DeviceNetManager, or another software configuration tool. Setting the switches at 64…99
lets the software have address control.
Each module is shipped with their node address set at 63. Remove the caps on the front of
the module to access the switches. The two switches are:
• X10 (most significant digit) – left side of module
• X1 (least significant digit) – right side of module
To reset the node address:

1. Rotate the switches using a small-bladed screwdriver.


2. Line up the small black dot on the switch with the number setting you wish
to use.
3. Cycle power.

Publication 1732D-IN007B-EN-E - November 2011


6 DeviceNet ArmorBlock™ Network Powered 16-input Module

Node Address Default Setting

This example shows


the default node
address set at 63.

43968

The rotary switches are read periodically. If the switches have been changed since the last
time they were read and no longer match the online address, a minor fault occurs, which is
indicated by the module indicator flashing red.
Settings of 64…99 cause the module to use the last valid node address stored internally. For
example, if the last setting internally was 40 and the setting is changed to 68, when you
power up, the address defaults back to 40.
The module is equipped with AutoBaud detect. AutoBaud lets the module read the
settings already in use on your DeviceNet network and automatically adjusts to
those settings.

Mount the Module


Use the two sets of mounting holes to mount the module directly to a panel or machine.
Mounting holes accommodate #6 (M3) pan-head screws. The torque specification is
0.64 Nm (6 lb-in.).
Refer to the mounting dimensions diagram to help you mount the module.

Publication 1732D-IN007B-EN-E - November 2011


DeviceNet ArmorBlock™ Network Powered 16-input Module 7

Module Dimensions
65 (2.56) 43.25 (1.70) Millimeters
26.5 (inches)
(1.04)

D
N
e
t
MOD NET
In

I-0 I - 15

I-1 I - 14
179 (7.05) I-2 I - 13

I-3 I - 12

I-4 I - 11

169 (6.64)
I-5 I -10

I-6 I-9

I-7 I-8

0 0

8 2 8 2

6 4 6 4
X10 X1
44774
Front view Side view

Mount the Module in High Vibration Areas

If you mount the module in an area that is subject to shock or vibration, we recommend
you use a flat and a lock washer to mount the module. Mount the flat and the lock washer
as shown in the mounting diagram. Torque the mounting screws to 0.64 Nm (6 lb-in.).

High Vibration Area Mounting

Lock washer

Flat washer
44766

Publication 1732D-IN007B-EN-E - November 2011


8 DeviceNet ArmorBlock™ Network Powered 16-input Module

Connect the Cordsets


The ArmorBlock DeviceNet family has 5-pin micro-style connectors. We provide caps to
cover the unused connectors on your module. Connect the quick-disconnect cordsets you
selected for your module to the appropriate ports.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connected
I/O must be powered from a source compliant with the following: Safety Extra
Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

Network Connector

Refer to the pinout diagram for the network connector.

Mini-style Input Male Connector


(View into connector)
Pin 1 Drain
1 5
Pin 2 V+
Pin 3 V-
2 4
Pin 4 CAN_H
3 Pin 5 CAN_L
43901

I/O Connectors

Refer to the pinout diagram for the I/O connector.

Micro-style 5-pin Female Input Connector


(View into connector)
Pin 1 Sensor source voltage
1 2
Pin 2 Input B
5 Pin 3 Return
4 3 Pin 4 Input A
Pin 5 PE
41452

Publication 1732D-IN007B-EN-E - November 2011


DeviceNet ArmorBlock™ Network Powered 16-input Module 9

Refer to Cordsets and Field Attachables, publication M117-CA502A, or visit the


Connection Devices website, http://www.ab.com/connectionsystems.

ATTENTION: Make sure all connectors and caps are securely tightened to
properly seal the connections against leaks and maintain IP enclosure
type requirements.

Communicate with the Module


This module’s I/O is exchanged with the master through a cyclic, polled, or
change-of-state connection.
• Cyclic: Allows configuration of the block as an I/O client. The block will
produce and consume its I/O cyclically at the rate configured.
• Polled: A master initiates communication by sending its polled I/O message to
the module. The module consumes the message, updates outputs, and produces a
response. The response has input data.
• Change-of-state: Productions occur when an input changes or a fault condition
occurs. If no input or fault condition change occurs within the expected packet
rate, a heartbeat production occurs. This heartbeat production tells the scanner
module that the I/O module is alive and ready to communicate. Consumption
occurs when data changes and the master produces new output data to the
I/O block.
Refer to the Module Data Definitions table for more information.

1732D-IBDPM12MND Data Definitions

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0


Produce 0 I7 I6 I5 I4 I3 I2 I1 I0

Produce 1 I15 I14 I13 I12 I11 I10 I9 I8

Produce 2 In short

Where: I = Input data; 0 = Off, 1 = On


In short 0 = Working, 1 = Sensor source voltage fault

Publication 1732D-IN007B-EN-E - November 2011


10 DeviceNet ArmorBlock™ Network Powered 16-input Module

Interpret Status Indicators


This module has the following indicators:
• Network and module status indicators for DeviceNet
• Auxiliary power indicator
• Individual I/O status indicators for inputs and outputs

1732D-IBDPM12MND

D
N
Module e
t
Network
MOD NET
status In status
indicator I-0 I - 15 indicator

I-1 I - 14
I-2 I - 13

I/O status I/O status


indicators I-3 I - 12 indicators
I-4 I - 11

I-5 I -10
I-6 I-9

I-7 I-8

0 0

8 2 8 2

6 4 6 4
X10 X1

44773

Publication 1732D-IN007B-EN-E - November 2011


DeviceNet ArmorBlock™ Network Powered 16-input Module 11

Indicator Status for Modules


Status Description
Module status Off No power applied to the device.
Green Device is online and has one or more I/O connections in
established state.
Flashing green Device needs commissioning due to missing, incomplete, or
incorrect configuration.
Red Critical fault – device timed out or has an unrecoverable fault.
Flashing red Recoverable fault – input or output short circuit.
Network status Off Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Green Device operating normally. As a Group 2 module, it means that the
module is allocated to a master.
Flashing green Device is online with no connections in the established state.
Red Critical link failure – failed communications module.
Flashing red Recoverable fault – an I/O connection has timed out.
I/O status Off I/O is not energized or is not valid.
Yellow I/O is energized and valid.

Publication 1732D-IN007B-EN-E - November 2011


12 DeviceNet ArmorBlock™ Network Powered 16-input Module

Specifications
General Specifications
Attribute Value
Number of inputs 16
Input type 61131-2 Type 3 compatible
Off-state input voltage, max 5V DC
On-state input voltage, min 11V DC
On-state input voltage, nom 24V DC
On-state input voltage, max 25V DC
Sensor source voltage, min 11V DC
Sensor source voltage, max 25V DC
Off-state input current, max 1.5 mA @ 5V DC
On-state input current, max 5 mA @ 25V DC
Input delay time(1)
Off to On 0…16,000 s
On to Off
DeviceNet power 11…25V DC
voltage range
Sensor source current 500 mA
per module, max
DeviceNet current 75 mA plus sum of sensor currents
Indicators 1 green/red – module status
1 green/red – network status
16 yellow – input status
Isolation voltage 50V (continuous), Basic Insulation Type, inputs to network
No isolation between individual inputs
Type tested @ 707V DC for 60 s
Communication rate 125 Kbps @ 500 m (1640 ft) for thick cable, flat media length 375 m (1230 ft)
250 Kbps @ 200 m (600 ft) for thick cable, flat media length 150 m (492 ft)
500 Kbps @ 100 m (330 ft) for thick cable, flat media length 75 m (246 ft)
Dimensions (HxWxD), 179 x 65 x 43.25 mm
approx. (7.05 x 2.56 x 1.70 in)
Enclosure type rating Meets IP65/66/67/69K (when marked), and NEMA 4X/6P with receptacle
dust caps or cable termination
Wiring category(2)(3) 1 – on signal ports
2 – on communication ports
Weight, approx. 0.392 kg (0.864 lb)

Publication 1732D-IN007B-EN-E - November 2011


DeviceNet ArmorBlock™ Network Powered 16-input Module 13

(1)
Input Off-to-On or On-to-Off delay is time from a valid input signal to recognition by the module.

(2) Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.

(3) Refer to Connection Systems, publication C116-CA508.

Environmental Specifications
Attribute Value
Temperature, operating IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, surrounding air, max. 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
ESD immunity IEC 61000-4-2:
8 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±3 kV @ 5 kHz on signal ports
±2 kV @ 5 kHz on communication ports

Publication 1732D-IN007B-EN-E - November 2011


14 DeviceNet ArmorBlock™ Network Powered 16-input Module

Environmental Specifications
Attribute Value
Surge transient immunity IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
±2 kV line-earth (CM) on communication ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Emissions CISPR 11:
Group 1, Class A

Certifications

Certification (when Value


product is marked)(1)
c-UL-us UL-listed Industrial Control Equipment, certified for US and Canada. See
UL File E322657.

CE European Union 2004/108/EC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

ODVA ODVA conformance tested to DeviceNet specifications

(1)
See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other
certification details.

Publication 1732D-IN007B-EN-E - November 2011


DeviceNet ArmorBlock™ Network Powered 16-input Module 15

Notes:

Publication 1732D-IN007B-EN-E - November 2011


Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs,
technical and application notes, sample code and links to software service packs, and a MySupport feature
that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.

United States or Canada 1.440.646.3434


Outside United States or Use the Worldwide Locator at
Canada http://www.rockwellautomation.com/support/americas/phone_en.html, or
contact your local Rockwell Automation representative.

New Product Satisfaction Return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow
these procedures.

United States Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete
the return process.
Outside United States Please contact your local Rockwell Automation representative for the return
procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002, available at
http://www.rockwellautomation.com/literature/.

Allen-Bradley, Rockwell Automation, ArmorBlock, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1732D-IN007B-EN-E - November 2011 PN-126462


Supersedes Publication 1732D-IN007A-EN-E - April 2009 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

You might also like