VRE Grid Compliance NGCP Testing Guidelines
VRE Grid Compliance NGCP Testing Guidelines
VRE Grid Compliance NGCP Testing Guidelines
OUTLINE
03 – PHOTOVOLTAIC TESTING
REQUIREMENTS
Procedure:
1. Operate PV inverter under test at rated Active Power, Voltage in nominal frequency.
2. Modify the frequency at an increment of 0.1Hz per minute to reach 59.7Hz and 60.3Hz.
Performance Criteria:
1. Active and Reactive Power should not change at any variation of frequency within 5 minutes
without any signs of abnormal conditions in the inverter.
2. PV inverter should not disconnect during/upon frequency change.
GCR 4.4.4.1 GENERATING POWER
OUTPUT
B. PVS facilities shall be capable of continuously supplying its Active Power Output depending on the
availability of primary resource, and Reactive Power at the connection point within voltage
variations ±5% during normal operating conditions and outside this range, up to a voltage variation
of ±10%.
Procedure:
1. Operate PV inverter under test at rated Active Power, Voltage in nominal frequency.
2. Modify the nominal voltage at an increment of 2.5% per minute to reach 95%, 90%, 105% and 110%
respectively.
Performance Criteria:
1. Active and Reactive Power should not change within ±5% variation of voltage within 5 minutes without
any signs of abnormal conditions in the inverter.
2. Reduction of Active and Reactive Power is allowed within ±10% variation of voltage. Provided that this
reduction does not exceed 5% of the generator’s declared data.
3. PV inverter should not disconnect during/upon voltage change from 95%, 90%, 105% and 110%.
GCR 4.4.4.2 FREQUENCY
WITHSTAND CAPABILITY
Performance Criteria:
1. The inverter shall maintain stable operation 95% of the time, provided the voltage at the connection
point is with ±5% of the nominal values
2. PVS shall be connected for at least 5 minutes for frequencies greater than 61.8 Hz – 62.4 Hz.
3. PVS shall be connected for at least 1 hour for frequency range of 58.2 Hz – 61.8 Hz.
4. PVS shall be connected for 60 minutes for frequency range of 57.6 Hz - < 58.2 Hz.
5. For frequencies less than or equal to 57.6 Hz, PVS shall be allowed to disconnect after 5 seconds.
GCR 4.4.4.3 REACTIVE POWER
CAPABILITY
A. PVS shall be capable of supplying Reactive Power output, at its connection point, within the limits of
Power Factor 0.95 lagging and 0.95 leading.
Procedure:
1. Operate PV inverter under test at rated Active Power, Voltage in nominal frequency.
2. Maintain the Active Power Constraint Mode depending on availability of primary resource.
3. Modify the Power Factor with increments of ±0.1 per 5 minutes until reaching Reactive Power Limits
0.95 lagging and 0.95 leading.
Performance Criteria:
1. Validation of the Reactive Capability of the PVS from 0.95 lagging to 0.95 leading.
2. Measured values are within ±5% percent of the capability as registered
3. PVS should not disconnect during/upon Power Factor change.
GCR 4.4.4.4 PERFORMANCE DURING
NETWORK DISTURBANCES (LVRT)
A. PVS shall be able to withstand, without disconnection, Voltage Sags at the connection point, produced
by faults or disturbances in the network;
Procedure:
1. Using a simulator tool/program, introduce voltage sags at the connection point to determine the time
of disconnection of the PVS.
2. Observe/log the inverter disconnection time.
GCR 4.4.4.4 PERFORMANCE DURING
NETWORK DISTURBANCES (LVRT)
GCR 4.4.4.4 PERFORMANCE DURING
NETWORK DISTURBANCES (LVRT)
Performance Criteria:
A. PVS shall be capable of supplying Reactive Power output at its connection point, within the limits of
Power Factor 0.95 lagging and 0.95 leading.
Procedure:
1. Operate PV inverter under test at rated Active Power, Voltage in nominal frequency.
2. Maintain the Active Power Constraint Mode depending on availability of primary resource.
3. Modify the Power Factor with increments of ±0.1 per 5 minutes until reaching Reactive Power Limits
0.95 lagging and 0.95 leading.
GCR 4.4.4.5 VOLTAGE CONTROL
SYSTEM
B. PVS shall be capable of supplying Reactive Power output at its connection point, within the limits of
terminal voltage of 0.95pu to 1.05pu.
Procedure:
1. Operate PV inverter under test at rated Active Power, Voltage in nominal frequency.
2. Maintain the Active Power Constraint Mode depending on availability of primary resource.
3. Modify the terminal voltage with increments of ±0.1pu per 5 minutes until reaching Limits 0.95pu and
1.05pu.
GCR 4.4.4.5 VOLTAGE CONTROL
SYSTEM
Performance Criteria:
1. Validation of the Reactive Capability of the PVS from 0.95 lagging to 0.95 leading.
Voltage Control Mode: control of voltage at the connection point with a margin not greater than 0.01pu
and no greater than 5% of the maximum reactive power
Voltage response time of 5 seconds, reaching the final value within 30 seconds
Power Factor Control Mode: power factor at the connection point within the required reactive power
range, with a target power factor in steps not greater than 0.01 pu.
A. PVS should be equipped with an Active Power regulation control system able to operate, at least, in
the following control modes, provided that System Frequency is within the range of 59Hz to 61Hz.
a. Free Active power production (no Active Power control): The PVS operates producing maximum
Active Power output depending on the availability of the primary resource.
b. Active Power Constraint: The PVS should operate producing Active Power output equal to the
value specified by the System Operator (set point) provided the availability of the primary
resource is equal or higher than the prescribed value; or producing the maximum possible Active
Power in case the primary resource availability is lower than the prescribed set-point.
GCR 4.4.4.6 ACTIVE POWER
SYSTEM
Procedure:
1. Operate PV inverter under test at Free Active Power Mode for at least an hour depending on the available
resource.
2. From Free Active Power Mode set the power plant controller to Active Power Constraint Mode. Set the
Active power to 20% of its rated/available capacity depending on the available resource.
3. Adjust Power output in 20% per step until achieving the maximum available capacity of the PV plant.
Performance Criteria:
1. PVS should not disconnect during/upon Active Power change.
2. For Active Power Constraint the change output should respond after 2 seconds and completed up to 30
seconds.
3. Measured response is within ±5% percent of the required level of response
GCR 4.4.4.6 ACTIVE POWER
SYSTEM
B. If the Frequency exceeds 61.0Hz the Active Power control system should reduce according to the
following formula:
61.0 − 𝑓𝑛
Δ𝑃 = 45 • 𝑃𝑚 •
60
Where:
Δ𝑃 = is the variation of the Active Power output that should be achieved
Procedure:
1. Operate PV inverter under test at Free Active Power Mode for at least an hour depending on the
available resource.
2. Set the initial Frequency at 60.0Hz as start point and adjust to 61.0Hz to 61.8Hz with increments of
+0.2Hz per step.
Performance Criteria:
1. PVS should not disconnect during/upon Active Power change.
2. For Active Power Gradient the change output should respond after 2 seconds and completed up to 30
seconds.
GCR 4.4.4.6 ACTIVE POWER
SYSTEM
C. If the System Frequency drops below 59.0Hz the Active Power control system should change to Free
Active Power production mode, generating the maximum Active Power output, compatible with the
availability of Primary Resource.
Procedure:
1. On Active Power Control system, reduce the frequency from the initial set point of 60Hz with
decrements of -0.2Hz per step until reaching 59.0Hz.
2. Gradually decrease frequency with same step decrements until reaching 58.8Hz.
Performance Criteria:
1. PVS should not disconnect during/upon frequency change.
2. Observe the change of Active Power Control to Free Active Power production mode below frequency
of 59Hz.
GCR 4.4.4.7 POWER QUALITY
A. With the system on Normal State, upon connection of the PVS, the Flicker severity at the Connection
Point shall not exceed the values established in PST 3.2.6.6 of the PGC.
B. Upon the connection of PVS, the Total Harmonic Distortion (THD) of the voltage and the Total Demand
Distortion (TDD) of the current at the Connection Point shall not exceed the limits established in PST
3.2.4.4 of the PGC.
Procedure:
1. Install the PQ analyzer at the Connection Point/s and measure Power Quality parameters (Flicker, THD
& TDD).
2. Monitor Power Quality for a minimum of one (1) week for quality data sampling.
GCR 4.4.4.7 POWER QUALITY
Performance Criteria:
1. Total Harmonic Distortion (THD)
Individual
Voltage Level THD
Odd Even
500kV 1.5% 1.0% 0.5%
115kV – 230kV 2.5% 1.5% 1.0%
69kV 3.0% 2.0% 1.0%
GCR 4.4.4.7 POWER QUALITY
Performance Criteria:
2. Total Demand Distortion (TDD)
Individual
Voltage Level TDD
Odd Even
500kV 1.5% 1.0% 0.5%
115kV – 230kV 2.5% 2.0% 0.5%
69kV 5.0% 4.0% 1.0%
GCR 4.4.4.7 POWER QUALITY
Performance Criteria:
3. Flicker Severity