XS2000 - BE /beg: Electronic MCCB

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

658

Circuit Breakers > TemBreakPRO MCCBs > XS2000_BE /BEG

XS2000_BE
/BEG
Electronic MCCB
MCCBs

✔ General purpose power distribution, motor starting General


✔ Current limiting device, reduces fault let through Electronic LSI (BE Type) or
energy for increased installation safety Trip Unit Protection Type
LSIG (BEG Type) 1)

✔ Direct opening and indication of main contact status – Trip Unit Rating 2000 A
maximising machine and user safety
Number of Poles 3/4
✔ Complies to AS / NZS 60947-2, IEC 60947-2 and CE

✔ Panel mount standard, with other mounting options Switching Poles 3P / 3P + N

✔ Full range of accessories for application flexibility


Short Circuit
✔ 3 or 4 pole versions
Short-Circuit Capacity
HL 85 kA
✔ Front or rear connect option (Ultimate) @415 V AC

✔ 450 mm (H), 185 mm (D), 105 mm pole centres


Voltage
✔ Fault rating; 85 kA Icu @ 415 V AC
Utilisation Voltages 24 V AC to 690 V AC
✔ Electronic trip unit: Individual dial setting adjustments
of LSI settings Rated Frequency 50 / 60 Hz
✔ Options include GF or PTA

✔ Trip unit; 2000 A


Connections
Front Connection (Option)
Connection Mode
Rear Connection (Standard)

Notes: 1) When ordering MCCBs with Ground Fault, an optional Neutral


GF CT can be ordered for 3 or 4 pole MCCBs for when it’s
installed in a 3P+N system. For PTA - contact NHP.
659

Circuit Breakers > TemBreakPRO MCCBs > XS2000_BE /BEG

Quick Reference Dimensions – Rear Connect

MCCBs
2000 A Frame 3 Pole 85 kA BE (LSI)
In Rated Current at 45 °C Ir Adjustable Icu @ 400 / 415 V Poles Catalogue No.
(A @ 45 °C) (A) (kA)

2000 1000 - 2000 85 3 XS2000HL32000BE

2000 A Frame 3 Pole 85 kA BEG (LSIG)


In Rated Current at 45 °C Ir Adjustable Icu @ 400 / 415 V Poles Catalogue No.
(A @ 45 °C) (A) (kA)

2000 1000 - 2000 85 3 XS2000HL32000BEG

2000 A Frame 4 Pole 85 kA BE (LSI)


In Rated Current at 45 °C Ir Adjustable Icu @ 400 / 415 V Poles Catalogue No.
(A @ 45 °C) (A) (kA)

2000 1000 - 2000 85 4 XS2000HL42000BE

2000 A Frame 4 Pole 85 kA BEG (LSIG)


In Rated Current at 45 °C Ir Adjustable Icu @ 400 / 415 V Poles Catalogue No.
(A @ 45 °C) (A) (kA)

2000 1000 - 2000 85 4 XS2000HL42000BEG


660

Circuit Breakers > TemBreakPRO MCCBs > XS2000_BE /BEG

Ratings Environmental
Vibration Frequency, Operational
Component Type MCCB 16.7 Hz
(Max.)

Selectivity Category B Vibration Acceleration (Max.) 19 m/s²

Number of Poles 3/4 Vibration Duration (Max.) 12 min

Altitude, Operating
Switching Poles 3P / 3P + N 2000 m
(No Derating)
MCCBs

Frame Size 2000 AF Storage Temperature -10 to +70 min/max °C

Trip Unit Rating 2000 A Operating Temperature -5 to +70 min/max °C

In, Rated Current (A) Relative Humidity, Max 85 % RH

2000
45⁰C 2000
50⁰C 2000 Connection
70⁰C -

Ue, Rated Operational Voltage, Terminal Bar Connection Cable or Busbar


690 V AC
AC, max
Front Connection
Ui, Rated Insulation Voltage 800 V (rms) (Option)
Connection Mode
Rear Connection
Uimp, Impulse Withstand Voltage 8 kV (Standard)

Extension Bar With Bolt


Supply Voltage Type AC Terminal Type
holes

Rated Frequency 50 / 60 Hz Connection Torque 22.5 - 37.2 Nm

Pollution Degree 3

Installation Types
Trip Unit Rating (A) - Power Loss Per Pole (W)
(A) 2000 Suitable for Panel Mounting No
(W) 76
DIN rail mounting
No
with optional adapter
Dielectric Strength 2500 V AC
Suitable for mounting on chassis No

Suitable for Distribution


Standards Switchboard or MCC
Yes

Withdrawable No
IEC 60947-2
Standards Compliance
AS/NZS 60947-2
Plug-in PM Base No
RCM (Regulatory Compliance Mark) Compliant
Plug-in UPX Type No
CE Mark Compliant
Suitable for angle
Mounting
bracket mounting
Shipping Approvals Contact NHP

Contact NHP for standards compliance and approvals not


listed here
661

Circuit Breakers > TemBreakPRO MCCBs > XS2000_BE /BEG

Physical Trip Unit


Height 450 mm Over Current Protection Function Yes

3P 320 mm Electronic LSI


Width Trip Unit Protection Type (BE Type) or
4P 429 mm LSIG (BEG Type)

Depth (less toggle) 185 mm Rated Temperature 50 °C

Depth (toggle included) 245 mm

MCCBs
Weight
3P 54 kg Other Features
4P 67 kg
Pre-trip alarm (PTA) Refer NHP
Electrical Life 500 cycles
ZSI Zone Selective Interlocking No
Mechanical Life 2500 cycles

ACIP Auxiliary Communications Port No

Short-Circuit Capacity CIP Communications Interface Port No


kA Rating
MIP Maintenance Interface Port No
MCCB Type
Voltage HL OAC Optional Alarm Contact No

220 / 240 V AC 125


Icu (Ultimate Breaking Capacity)

380 V AC 100

400 / 415 V AC 100/85


General Accessories
440 V AC 85 Auxiliary Switches Yes
690 V AC 45
Alarm Switch Yes
1000 V AC -

1100 V AC - Shunt Trip Yes


Based On AS/NZS 60947.2 and IEC 60947-2

125 V DC -
Under Voltage Trip Yes
250 V DC -

220 / 240 V AC 94 Handle Operators Yes


Ics (Service Breaking Capacity)

380 / 400 V AC 75
Motor Operator Yes
415 V AC 65
Mechanical Interlock Yes
440V AC 65

690 V AC 42 Mechanical Interlock -


Yes
rear walking beam or cable type
1000 V AC -
Locking Devices Yes
1100 V AC -

125 V DC - Terminal Covers No


250 V DC -
Interpole Barriers No
Icw (Short Time

External Panel Display No


Withstand)

0.3 Seconds 42
662

Circuit Breakers > TemBreakPRO MCCBs > XS2000_BE /BEG

Time Current Characteristic Curve, XS2000HL, Basic Electronic


MCCBs

Curves Based on Standard Settings


Tripping Time

XS2000HL32000BE_dOPCH-S01
[Ict] x % % Percent Rated Current of Base Current (I1)

XOS Over Current Tripping Characteristics: XS2000HL, XS2500HL

CT rated current (A) (In) 2000, 2500


Base current setting (A) (IO) (In) x (0.63-0.8-1.0)
(IO) x (0.8 - 0.85 - 0.9 - 0.95 - 1.0). Non-trip at (I1) setting x 105 % and below.
Long time-delay pick-up current (A): (I1)
Trips at 125 % and above
Long time-delay time settings (S) (T1) (5 - 10 - 15 - 20 - 30) at (I1) x 600 % current. Setting tolerance ± 20 %
Short time-delay pick-up current (A): (I2) (IO) x (2 - 4 - 6 - 8 - 10). Setting tolerance ± 15 %
Opening time (0.1, 0.15, 0.2, 0.25, 0.3) in the definite time-delay.
Short time-delay time settings (S) (T2)
Total clearing time is +50 ms and resettable time - 20 ms for the time-delay setting
Instantaneous trip pick-up current (A) (I3) Continuously adjustable from (Io) x (3 to 12). Setting tolerance ± 20 %
• Pre-trip alarm pick-up current (A) (IP) (I1) x (0.7, 0.8, 0.9, 1.0). Setting tolerance ±10 %
• Pre-trip alarm time setting (S) (TP) 40 fixed definite time-delay. Setting tolerance ±10 %
• Ground fault trip pick-up current (A) (IG) Continuously adjustable from (IN) x (0.1 to 0.4). Setting tolerance ± 15 %
Opening time (0.1 - 0.2 - 0.3 - 0.4 - 0.8) in the definite time-delay.
• Ground fault trip time setting (S) (TG)
Total clearing time is +50 ms and resettable time is - 20 ms for the time-delay settings

Notes
• Optional.
• BOLD values represent factory default settings.