TEST REPORT OF MV12 UNDER/OVER VOLTAGE RELAY

TEST REPORT FOR UNDER/OVER


VOLTAGE RELAY

DOT- 16/04/2023
CLIENT : P&G , MANDIDEEP TOTAL SHEETS-2

NAME OF THE FEEDER : PCC-8 – TR11 INCOMER BAY

DETAILS OF THE EQUIPMENT - VOLTAGE PROTECTION RELAY


MAKE: L&T
MODEL NO. MV12
Equipment used - Numerical relay test set Make: Omicron Model: CMC256 Plus Sr.No. – NDM709M

ADOPTED SETTINGS
 OVERVOLTAGE RELAY
Setting – 440 V , Delay – 5 sec
Operating voltage - 415 phase to phase

MEASURED OPERATING TIME IN SEC


INJECTED PHASE EXPECTED OPERATING TIME IN SEC
INJECTED VOLTAGE (440V)
R PH-YPH 5.010 5.000

 UNDERVOLTAGE RELAY
Setting – 390V , Delay – 5 sec
Operating voltage - 415 phase to phase type

MEASURED OPERATING TIME IN SEC


INJECTED PHASE EXPECTED OPERATING TIME IN SEC
INJECTED VOLTAGE (390V)
Y PH-BPH 5.010 5.000

 UNDERVOLTAGE RELAY
Setting – 390V , Delay – 5 sec
Operating voltage - 415 phase to phase type

1
MEASURED OPERATING TIME IN SEC
INJECTED PHASE EXPECTED OPERATING TIME IN SEC
INJECTED VOLTAGE (390V)
B PH-RPH 5.010 5.000

REMARKS:
DIP switch found wrong in relay, due to which relay not operating in under voltage or overvoltage as
per setting , same was corrected & then tested the relay.

ALL INDICATION LED'S – OK


GENERAL REMARKS - RELAY FOUND HEALTHY

Tested By: NDL POWER


Name : Abhishek Rajput
Designation : Testing engineer