PCC8 - MV12 Report
PCC8 - MV12 Report
PCC8 - MV12 Report
DOT- 16/04/2023
CLIENT : P&G , MANDIDEEP TOTAL SHEETS-2
ADOPTED SETTINGS
OVERVOLTAGE RELAY
Setting – 440 V , Delay – 5 sec
Operating voltage - 415 phase to phase
UNDERVOLTAGE RELAY
Setting – 390V , Delay – 5 sec
Operating voltage - 415 phase to phase type
UNDERVOLTAGE RELAY
Setting – 390V , Delay – 5 sec
Operating voltage - 415 phase to phase type
1
MEASURED OPERATING TIME IN SEC
INJECTED PHASE EXPECTED OPERATING TIME IN SEC
INJECTED VOLTAGE (390V)
B PH-RPH 5.010 5.000
REMARKS:
DIP switch found wrong in relay, due to which relay not operating in under voltage or overvoltage as
per setting , same was corrected & then tested the relay.