Manual-SITRAM Multisense Software - v1.0
Manual-SITRAM Multisense Software - v1.0
Manual-SITRAM Multisense Software - v1.0
Copyright Note:
Privileged Business Information – Do Not Release
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Page 2 of 115
SITRAM® Multisense Software Installation and Operation Manual
Revision History
Revision ID Changes
Bold = Does apply for this document / Not Bold = Does not apply for this document
Preface
Main Focuses Themes
Bold = Does apply for this document / Not Bold = Does not apply for this document
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Page 3 of 115
SITRAM® Multisense 5 Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Page 4 of 115
SITRAM® Multisense Software Installation and Operation Manual
Technical Support
E-Mail:
support.energy@siemens.com
Training Centers
E-Mail :
transformer.academy.energy@siemens.com
Web : http://www.energy.siemens.com/nl/en/services/power-
transmission/transformer-lifecycle-management/
E-Mail:
PowerAcademy@siemens.com
Web:
https://product-training.siemens.com/power-academy/
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Page 5 of 115
SITRAM® Multisense 5 Installation and Operation Manual
Contents
3.3.2 Working Area Transformer ............................ 30
REVISION HISTORY ............................................................ 3 3.3.3 Context Menu Transformer ............................ 31
3.4 CONNECTION SETTINGS ...................... 32
PREFACE ............................................................................ 3 3.4.1 Modem Settings ............................................. 32
LEGAL PROVISIONS ............................................................ 4 3.4.2 Serial Interface Settings ................................. 33
3.4.3 Network Settings ............................................ 33
WARNING NOTICE CONCEPT .................................................... 4 3.4.4 Bridge Settings ............................................... 33
QUALIFIED PERSONNEL ............................................................ 4 3.4.5 Common Settings ........................................... 33
USE OF SYSTEM ..................................................................... 4 3.5 SITRAM MULTISENSE DEVICE SETTINGS .................... 34
TRADEMARKS ........................................................................ 4 3.5.1 Alert Setup .......................... 36
DISCLAIMER OF LIABILITY ......................................................... 4 3.5.2 Sensor Setup .................... 39
TECHNICAL SUPPORT ......................................................... 5 3.5.3 Alert SMS Setup............. 43
3.5.4 DGA Level Adjust ....... 45
CUSTOMER SUPPORT CENTER ................................................... 5 3.5.5 Analog Outputs ..... 47
BUSINESS SEGMENT TLM™ ..................................................... 5 3.5.6 Digital Outputs ....... 48
TRAINING CENTERS................................................................. 5 3.5.7 Settings .................................... 48
1. SITRAM MULTISENSE SOFTWARE ............................ 8 3.5.8 Transformer Setup ..... 52
3.6 DIAGNOSTICS ............................. 56
1.1 PURPOSE OF THE PROGRAM .......................................... 8
1.2 ADVICE FOR USE OF THIS OPERATION MANUAL ................. 8 3.6.1 Duval Triangle ................ 56
1.3 PC-REQUIREMENTS ..................................................... 8 3.6.2 Rogers (3D) ........................... 64
1.4 INSTALLATION ............................................................. 8 3.7 COMMUNICATION WITH SITRAM
1.4.1 SITRAM Multisense Software – InstallShield MULTISENSE DEVICES......................................................... 72
Wizard 8 3.7.1 SITRAM MULTISENSE Communication ........... 72
1.4.2 Start Program .................................................. 9 3.7.2 SITRAM MULTISENSE Connection Scheduler .. 72
1.4.3 Adjust the Installation ..................................... 9 3.7.3 Windows Task Scheduler with SITRAM
Multisense Software Connection scheduler.................. 76
2. USER INTERFACE AREAS .......................................... 9 3.7.4 Lock Data Folder ............................................ 77
2.1 MENU BAR ............................................................... 10 3.8 VIEW MEASUREMENT VALUES (HISTORY) 77
2.1.1 File - Menu ..................................................... 10 3.8.1 Sensor Selection Window ............................... 78
2.1.2 Edit - Menu .................................................... 16 3.8.2 Time Span Selection Window Measurement
2.1.3 View - Menu .................................................. 19 Values 79
2.1.4 Transformer - Menu ...................................... 21 3.8.3 Result Window ............................................... 81
2.1.5 Extra - Menu .................................................. 22 3.8.4 Further Processing of the displayed
2.1.6 Help - Menu ................................................... 23 measurement values .................................................... 85
2.2 TREE STRUCTURE....................................................... 25 3.9 VIEW ALARMS ..................................... 87
2.3 WORKING AREA ........................................................ 25 3.9.1 Alarm Selection Window ................................ 88
2.4 MESSAGE AREA ........................................................ 26 3.9.2 Alarm Time Span Window .............................. 88
2.5 CONTEXT MENU........................................................ 26 3.9.3 Alarm Window ............................................... 89
3.9.4 Further Processing of the displayed Alerts ..... 93
3. WORKING WITH SITRAM MULTISENSE SOFTWARE 27
3.10 ONLINE SENSORS ................... 94
3.1 CUSTOMER .......................................... 27 3.10.1 Sensor Selection Window Online Sensors ... 95
3.1.1 Rename the Customer Directory ................... 27 3.10.2 Time Span Selection Window Online Sensors
3.1.2 Working Area Customer ................................ 27 96
3.1.3 Context Menu Customer ................................ 27 3.10.3 Result Window Online Sensors ................... 97
3.2 STATION .............................................. 28 3.10.4 Further Processing of the Online Values ..... 99
3.2.1 Set up a New Station ..................................... 28 3.11 EXTRACTION STATUS ........ 102
3.2.2 Working Area Station .................................... 28 3.11.1 Result Selection Window Extraction Status
3.2.3 Context Menu Station .................................... 28 103
3.3 TRANSFORMER ............................. 29 3.11.2 Result Window Extraction Status ............. 103
3.3.1 Set up a New Transformer ............................. 29
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Page 6 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 8 of 115
SITRAM® Multisense Software Installation and Operation Manual
SITRAM Multisense Software can also be operated by the context menu (right mouse click):
Context menu (2.5)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 9 of 115
SITRAM® Multisense Software Installation and Operation Manual
The simplest way to work with SITRAM Multisense Software is to use the computer-mouse. With it the corresponding menu or
the corresponding entry in the tree structure can easily be selected. However it is possible to operate the program with the
computer-keyboard only.
Exit (2.1.1.11)
Note: Depending on the position of the cursor or which view (2.1.3.4) is selected, the particular menu items are active (black)
or inactive (grayed out).
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 10 of 115
SITRAM® Multisense Software Installation and Operation Manual
2.1.1.2 Customer ►
By selecting the menu item „Customer ►
“ the following selection window appears:
Rename ... :
By selecting this menu item the input window „Rename Customer” will open:
Any name can be entered (3.1.1). With the button the entered name will be saved and with the
button it will be aborted.
Any name can be entered (3.2.1). With the button a station is created and saved under the entered name
and with the button it will be aborted. Arbitrary stations can be created and managed.
2.1.1.3 Station ►
By selecting the menu item „Station ►
“ the following selection window appears:
Rename ... :
By selecting this menu item the input window „Rename Station” will open:
The input window „Rename Station” opens and any name can be entered (3.2.1).
With the button the entered name will be saved and with the button it will be aborted.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 11 of 115
SITRAM® Multisense Software Installation and Operation Manual
Delete ... :
By selecting the menu item „Delete …” the marked station will be deleted. The information window „Station deleted”
opens.
Note: The station can only be deleted, when there are no more transformers available in that station.
New Transformer ... :
By selecting this menu item the input window „New Transformer” will open:
2.1.1.4 Transformer ►
By selecting the menu item „Transformer ►
” the following selection window appears:
Rename ... :
By selecting this menu item the input window „Rename Transformer” opens:
Any name can be entered (3.3.1). With the button the entered name will be saved and with the
button it will be aborted.
Delete ... :
By selecting this menu item the confirmation window opens:
The action will be cancelled by pressing the button. The transformer will be deleted by pressing the
button and confirmed by the information window.
2.1.1.5 Export ►
By selecting the menu item „Transformer ►
” following selection window appears:
Excel ... :
By selecting this menu item the input window „Save As“ opens:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 12 of 115
SITRAM® Multisense Software Installation and Operation Manual
The system automatically assigns the path under which the Excel file should be saved. It can be changed by hand. Any
name can be entered. By pressing the button the file will be saved under the entered name and with the
button the export will be aborted.
CSV ... :
By selecting this menu item the input window „Save As” opens:
Any name can be inserted (3.2). With the button the entered in name is saved and aborted with the
button.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 13 of 115
SITRAM® Multisense Software Installation and Operation Manual
The export separators (List/Decimal/String) and the export format (Date/Time) are defined in the input window „CSV Export
Setup“. By pressing the button the separators and the export format will be taken from the system settings of the
used computer. In this way the import into an appropriate analysis program can be simplified. With the button the
inputs are saved and aborted with the button.
2.1.1.7 Save
After the input of detail information (values) into the station- or transformer settings, the menu items „Save” and „Revert”
become active (black). By selecting the menu item „Save” the entries will be saved. It is also possible to save the entries by
pressing the key combination [Ctrl+S] on the computer-keyboard. Exit the entries without saving, a confirmation window
opens automatically:
With the button the entries will be saved and with the button aborted.
By pressing the button the entries have to be saved by hand. In this case the confirmation window will close and
will not reappear (it appears again only after a restart of SITRAM Multisense Software).
2.1.1.8 Revert
After the input of detail information (values) into the station- or transformer settings, the menu items „Save” and „Revert”
become active (black). By selecting the menu item „Revert” the entered settings will be aborted.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 14 of 115
SITRAM® Multisense Software Installation and Operation Manual
The default setting for the print out can be done here. The „Orientation” and the „Margins” (millimeter) can be chosen
respectively adjusted in the corresponding field. The settings „Paper” are predetermined. The default printer with paper size A4
is used.
Further features (e.g. print command, zoom, page view and close) are available in this window.
Note: The feature „Print …” can also be selected by using the context menu (3.8.4.2)
2.1.1.11 Exit
This menu item will close the SITRAM Multisense Software program.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 15 of 115
SITRAM® Multisense Software Installation and Operation Manual
Undo (2.1.2.11)
The input window „New Property” opens and any name can be entered. With the button the new user defined
attribute will be saved under the typed name and aborted with the button.
The input window „Edit Property” opens and any name (for the value) can be entered. With the button the new
name will be saved and aborted with the button.
The input window „Rename Customer” opens and any description (for the property) can be entered.
With the button the inserted name will be saved and aborted with the button.
Note: Only user defined properties can be renamed!
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 16 of 115
SITRAM® Multisense Software Installation and Operation Manual
2.1.2.4 Delete
By selecting the Menu item „Delete” the following confirmation window appears:
The selected property will be deleted with the button. The action will be canceled by pressing the
button.
Note: Only user defined properties can be deleted!
...
Alert Properties (3.5.1)
Sensor Properties (3.5.2)
...
The corresponding alert or sensor will be disabled and the settings will be deleted.
2.1.2.7 Cut
By selecting the menu item „Cut” the selected part will be cut out and put into the Windows
clipboard.
2.1.2.8 Copy
By selecting the menu item „Copy” the selected part will be copied and put into the Windows
clipboard.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 17 of 115
SITRAM® Multisense Software Installation and Operation Manual
2.1.2.9 Paste
By selecting the menu item „Paste” the Windows clipboard will be inserted to the cursor position.
2.1.2.10 Insert ►
Depending on the selection in the tree structure and what is selected in the working area the following selection window
appears by selecting the menu item „Insert ►
“:
The message text (SMS/e-mail) can be made up with any {place holder} or real alphanumeric text. You’ll find more information
under (3.5.3) or (2.1.5.2).
2.1.2.11 Undo
After an input in one of the fields of the Alert SMS Setup the menu item „Undo” will be activated (black). By selecting the menu
item „Undo” the input will be aborted.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 18 of 115
SITRAM® Multisense Software Installation and Operation Manual
View as ► (2.1.3.4)
Alert ► (2.1.3.6)
Sensor ► (2.1.3.7)
2.1.3.4 View as ►
Depending on which entry is selected in the tree structure, the following selection window appears by selecting the menu item
„View As ►“:
By selecting / in the tree structure
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 19 of 115
SITRAM® Multisense Software Installation and Operation Manual
2.1.3.6 Alerts ►
If the tree structure entry is selected and an alert is chosen in the alert selection window of the working area the
following selection window (3.9.3.2) appears by selecting the menu item
„Alert ►
“:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 20 of 115
SITRAM® Multisense Software Installation and Operation Manual
2.1.3.7 Sensors ►
If the tree structure entry is selected and an active sensor is chosen in the sensor
selection window of the working area the following selection window (Error! Reference source not found.) appears by
electing the menu item „Sensors ►
“:
Add to Left Y-Axis: The scaling will be shown on the left Y-Axis of the result window.
Add to right Y-Axis: The scaling will be shown on the right Y-Axis of the result window.
Remove: The display of the sensor will be deactivated in the result window.
Set Color: The window „Set Sensor Color“ will be opened.
The first three menu items (blue frame) refer to manually controlled data read & write.
2.1.4.2 Disconnect
By selecting the menu item „Disconnect” the established connection will be terminated immediately (3.7.1). This should be
avoided during the login procedure.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 21 of 115
SITRAM® Multisense Software Installation and Operation Manual
2.1.5.1 Language ►
By selecting the menu item „Language ►
” the following selection window appears:
SITRAM Multisense Software supports the following languages: English, German, Russian, Turkish, French, Chinese, Spanish,
Polish and Korean.
Remark: Sending an e-mail at communication error alarms is enabled and parameterd in the
SITRAM MULTISENSE input window communication timing (3.7.1).
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 22 of 115
SITRAM® Multisense Software Installation and Operation Manual
SMTP Server
Server: Name of the exchange server
Port-Number: Port number for the e-mail communication
Use SSL: Data encryption
User Name: Domain name of the user
Password: User password
Device Alerts
E-Mail Content
Subject: Subject line
Message text: Entry of the message by using text or place holders (3.5.3)
From, To
From: Sender
To: Recipient ( a semicolon (;) separates more than one recipient)
Send Button: By pressing this button, a test e-mail will be sent.
Communication Error Alerts
E-Mail Content
Subject: Subject line
Message text: Entry of the message by using text or place holders (3.5.3)
From, To
From: Sender
To: Recipient ( a semicolon (;) separates more than one recipient)
Send Button: By pressing this button, a test e-mail will be sent.
Note: This function only makes sense if the „SITRAM MULTISENSE Connection scheduler” is activated on each transformer
(3.7.2.2).
There is the possibility to display the data for gas and moisture in oil with a fixed position after decimal point. 0 … 6 positions
after decimal point could be entered. In case the input field is empty the
original values will be shown.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 23 of 115
SITRAM® Multisense Software Installation and Operation Manual
By selection of the button the information window will be extended by the contact data:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 24 of 115
SITRAM® Multisense Software Installation and Operation Manual
History (3.8)
Level 3: Transformer (3.3) Alerts (3.9)
Connection (3.4)
One SITRAM MULTISENSE device will be Online Sensors (3.10)
assigned automatically to each Extraction Status (Error! Reference
transformer. The type has to be applied ource not found.)
during creation. Alarm Setup (3.5.1)
Sensor Setup (3.5.2)
Alert SMS Setup (3.5.3)
Level 4: SITRAM MULTISENSE (3.5) DGA Level Adjust (3.5.4)
Analog Output Setup (3.5.5)
The properties are associated to each
SITRAM MULTISENSE device. Digital Output Setup (3.5.6)
Settings (3.5.7)
Transformer Setup (Error! Reference
ource not found.)
Level 4: Diagnostics (3.6) Duval Triangle (3.6.1)
Rogers (3D) (3.6.2)
The SITRAM MULTISENSE 1008 device
has additional diagnostic functions.
Remark: For a better presentation of the overview, the tree structure in the upper image has been modified. Detailed
explanations refer to chapter (3.5).
The type of the SITRAM MULTISENSE device has to be set during the creation of the transformer (3.3.1).
Note: The tree structure of the different SITRAM MULTISENSE types varies in the amount of entries. By selecting the individual
entries in the tree structure the content in the working area will change accordingly.
2.3 Working Area
The working area is on the right side of the SITRAM Multisense Software program window. The content of the working area
changes according to the selected entry in the tree structure. The working areas and their
settings will be explained in chapter (3.1).
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 25 of 115
SITRAM® Multisense Software Installation and Operation Manual
It is used to display system messages. These are mainly messages when an error occurs in the database. For example, if the
database of a transformer cannot be open or close. These messages are written into a log-file. In case of a problem the log-file
can be sent together with the database to the SIEMENS Service Department.
Note: In case of a serious system error the message area will be opened automatically!
Here is an example of the context menus for the tree structure levels:
- Level 1(Connection scheduler on/off)
- Level 2
- Level 3
The particular context menus will not be listed here in detail. They will be explained in the corresponding chapters.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 26 of 115
SITRAM® Multisense Software Installation and Operation Manual
Level 1: Customer
In both cases the input window „Rename Customer” appears. The chosen name is user defined and can be changed at any time.
It can be renamed to your needs (3.1.1). By pressing the button the entered name will be saved and
aborted by pressing the button.
Set Customer Icon ... :
This menu item has to be included.
Connection scheduler:
Master off-/on switching of the connection scheduler for all activated automatic data readouts. The actual status
appears right to the text ( switched on / switched off) and changes when this context menu item is selected.
Note: When SITRAM Multisense Software is started, the connection scheduler (Run communication
scheduler) is always switched on.
New Station ... :
By selecting this menu item the input window „New Station“ opens:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 27 of 115
SITRAM® Multisense Software Installation and Operation Manual
Any name can be entered (3.2.1). By pressing the button the entered station name will be saved and by
pressing the button the entry will be aborted.
Note: Any number of stations can be created and managed.
3.2 Station
The station is located on level 2 in the tree structure:
Level 2: Station
The input window „New Station” appears. Any name can be entered.
Note: Any numbers of stations can be created and managed in SITRAM Multisense Software.
Any name can be entered. By pressing the button the entered name will be saved and aborted by pressing
the button.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 28 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: The station can only be deleted, if there is no transformer present in this station.
3.3 Transformer
The transformer is located on level 3 in the tree structure and contains 4 sub entries:
History (3.8)
Level 3: Transformer Alerts (3.9)
Connection (3.4)
Online Sensors (3.10)
Extraction Status (3.11)
3.3.1 Set up a New Transformer
To set up a new transformer an existing station has to be selected. Then a new transformer can be created in a known manner
as transformer station:
By menu item „File ► Station ► New Transformer ...“
By context menu with the right mouse button
The input window „New Transformer“ appears. Any name can be entered. Additionally the type of the SITRAM MULTISENSE
device (SITRAM MULTISENSE 5 & 9) has to be chosen.
Note: Any numbers of transformers can be added to a station!
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 29 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: These detail information can only be entered and managed in SITRAM Multisense Software.
Additionally to the existing standard property fields
Name
Manufacturer
Type
Year
Prim. Voltage
Sec. Voltage
Prim. Current
Sec. Current
Additionally user defined fields can be added by a right mouse click out of the context menu or by the menu item „Edit►
New”. The property description can be changed by „Rename“ and the value
description by choosing „Edit“. The settings can be completely undone by choosing „Undo“ and single fields can be deleted by
selecting „Delete“. Changes have to be saved with the entry „Save“ or by choosing another entry in the tree structure.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 30 of 115
SITRAM® Multisense Software Installation and Operation Manual
Any name can be entered. By pressing the button the entered name will be saved and aborted by pressing
the button.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 31 of 115
SITRAM® Multisense Software Installation and Operation Manual
First determine how the connection to the SITRAM MULTISENSE device has to be done. Via Modem (option),
Com-Port, Network or Bridge. Mark the corresponding selection field.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 32 of 115
SITRAM® Multisense Software Installation and Operation Manual
There is the possibility to generate a so called send/receive-protocol. In this protocol, connection specific data is stored, which
contains useful information for the Siemens-service department in case of an error.
The following selections are possible:
log disabled (protocol off)
log send/receive (protocol on)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 33 of 115
SITRAM® Multisense Software Installation and Operation Manual
SITRAM MULTISENSE 9
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 34 of 115
SITRAM® Multisense Software Installation and Operation Manual
The SITRAM MULTISENSE settings can be configured and saved with SITRAM Multisense Software.
The SITRAM MULTISENSE tree structure entry contains the following information that is read-out from the device during a
connection:
Serial number of the SITRAM MULTISENSE device
Firmware version of the SITRAM MULTISENSE device
Path of the data directory in which the data will be saved on the PC
Date of last data readout
Customer entry line 1
Customer entry line 2
Customer entry line 3
Customer entry line 4
Numeric password to change the settings (Default 999)
String password for modem login (Default KWA).
User name for modem login (Default Siemens).
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 35 of 115
SITRAM® Multisense Software Installation and Operation Manual
The selection is carried out as usual either through the context menu by activation with the right mouse button or through the
menu item „View ►View as ► ...“.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 36 of 115
SITRAM® Multisense Software Installation and Operation Manual
The following dialog window opens in the views „List” and „Symbols” by a double click on an alarm icon and in the view „Details”
by a double click on the row header:
At first the appropriate alarm mode has to be selected under „Alert Mode”. The following modes are available:
Hi: A single-stage alarm is triggered when the threshold value „Level 1” is exceeded.
Hi - Hi: A double-stage alarm is triggered. The first stage of the alarm is triggered when the threshold value „Level 1” is
exceeded. The second stage of the alarm is triggered when the threshold value „Level 2” is exceeded.
Low: A single-stage alarm is triggered when the threshold value “Level 1” is not achieved.
Low - Low: A double-stage alarm is triggered. The first stage of the alarm is triggered when the threshold value “Level
1” is not achieved. The second stage of the alarm is triggered when the threshold value “Level 2” is not achieved.
Out Range (Low – Hi): A double-stage alarm is triggered when the measurement value is outside of the range. The
first stage of the alarm is triggered when the threshold value “Level 1” is not achieved. The second stage of the alarm is
triggered when the threshold value “Level 2” is exceeded.
In Range: A single-stage alarm is triggered when the measurement value is inside the range, which is defined by the
threshold values “Level 1” and “Level 2”.
The next step is to select a sensor that serves as alarm source. All above mentioned internal sensors are available. If additional
sensors are connected and setup correctly (3.5.2) these will be
selectable as well. Depending on the SITRAM MULTISENSE type the following measurements are available:
SITRAM MULTISENSE 5
H2 - C2H2 - C2H4 - CO - H2O concentration
H2 - C2H2 - C2H4 - CO daily trend
H2 - C2H2 - C2H4 - CO weekly trend
T1 temperature (gas temperature measurement cell)
T2 temperature (oil temperature extraction chamber)
All under additional sensors defined measurements
SITRAM MULTISENSE 9
H2 - C2H2 - C2H4 - CO - CO2 - C2H6 - CH4 - H2O concentration
H2 - C2H2 - C2H4 - CO - CO2 - C2H6 - CH4 daily trend
H2 - C2H2 - C2H4 - CO - CO2 - C2H6 - CH4 weekly trend
T1 temperature (gas temperature measurement cell)
T2 temperature (oil temperature extraction chamber)
All under additional sensors defined measurements
For clear alarm identification an appropriate description can be entered in the input field „Name“.
The alarm threshold values are entered in the input fields „Level 1” and if applicable „Level 2”. The device „ppm” is used for gas
concentrations, the device „°C” for temperatures and for additional sensors the individual defined devices (e.g. volt, ampere …).
The alarm threshold values must be within the corresponding measurement range. These are e.g. 0 ... 2000/5000 ppm for gas
concentrations,
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 37 of 115
SITRAM® Multisense Software Installation and Operation Manual
0 ... 100 ppm for moisture in oil and -20 ... 100°C for temperatures. For additional sensors defined minimal and maximal
threshold values.
The delays (Delay 1 and 2) can be entered to suppress alarms that exceed or not achieve their thresholds only for a short
period. As the measurement cycle for gas sensors takes max. 20 minutes the delay time should not be less than 1 hour. The
entry of the delay time is in seconds or directly in [days]-[hours]:[minutes]:[seconds]. After confirmation by pressing the OK
button the value is shown in the format [days]-[hours]:[minutes]:[seconds
The following actions can be chosen in the selection fields „Action 1” and „Action 2”:
Log-entry: A change of the status is stored into the alarm history. The alarm has to be acknowledged.
Output: Depending on the selected mode an output is set in case of exceeding or not achieving the level. This output
will be reset as soon as the alarm isn´t present any longer.
Output Hold: Depending on the selected mode an output is set in case of exceeding or not achieving. When leaving
the alarm state the output remains switched on until the alarm is acknowledged by hand.
Log-entry & SMS: A change of the status is stored into the alarm history. The alarm has to be acknowledged.
Additionally a SMS is send to the defined addresses.
Output & SMS: Depending on the chosen mode an output is set in case of exceeding or not achieving the level and
additionally a SMS is send to the defined addressees.
Output Hold & SMS: Depending on the chosen mode an output is set in case of exceeding or not achieving the level.
When leaving the alarm state the output is lasting until the alarm is acknowledged by hand. Additionally a SMS is send
to the defined recipients.
Note: As soon as an alarm is defined the entry in the alarm history is always active!!!
It is possible to assign the same output to different alarms, to create a so called collective alarm.
After a change of the alarm settings an asterisk appears right to the icon , which indicates that the settings still
has to be transferred to the device. The settings are not synchronized at the moment and will be updated to the SITRAM
MULTISENSE device on the next connection (3.7), if the selection field “Update Configuration” is selected.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 38 of 115
SITRAM® Multisense Software Installation and Operation Manual
List
Symbol
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 39 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 40 of 115
SITRAM® Multisense Software Installation and Operation Manual
The selection is carried out as usual either through the context menu by activation with the right mouse button or through the
menu item „View ►View as ► ...“.
The following dialog window opens in the views „List” and „Symbols” by a double click on an sensor icon and in the view
„Details” by a double click on the row header. The settings for the internal sensors cannot be changed and therefore they are
grayed out:
Input Signal
In the selection field „Input Signal” the output signal type (current/voltage) and the signal range of the corresponding sensor
can be selected. These differ for external and virtual sensors by SITRAM MULTISENSE type and optional equipment as follows:
Input
SITRAM MULTISENSE 5 / SITRAM MULTISENSE 9
signal
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 41 of 115
SITRAM® Multisense Software Installation and Operation Manual
Device
The following device for the measurement of the sensor can be selected:
- no device
°C: temperature sensors
ppm: moisture in oil sensor or other sensors for chemicals
%: moisture in oil sensor or other sensors for chemicals
V: voltage measurement
KV: voltage measurement
mA: current measurement
A: current measurement
kA: current measurement
ppm/d: Trend ppm / day
ppm/w: Trend ppm / week
#: Number, quantity, position etc.
Sample Interval [s]
The sample interval specifies how often the sensor value (measurement value) is stored in the SITRAM MULTISENSE device. The
default setting for internal sensors is 1200 seconds (20:00).
Sensor Name
For ease of use, each sensor should be assigned with a unique name.
Minimum Value / Maximum Value
The measurement range is scaled with these entries. This means, the measurement range is assigned to the signal range of the
sensor. e.g. 4...20 mA DC corresponds to 0 ... 120 °C
0% 100 %
Signal range 4 mA DC 20 mA DC
Measurement range 0 °C 120 °C
Minimum Value 0
Maximum Value 120
Minimum Display / Maximum Display
These minimum and maximum values refer to the bar graph in the main menu (additional sensor status) of the display. If you
know in advance that the observed range of the measurement value is only in a segment of the measurement range, this can
be narrowed down (zoom), so a change of the measurement value on the bar graph is more apparent.
e.g. The measurement range is 0 ... 120°C, but the measured temperature is between 60 ... 70 °C.
Measurement range 0 °C 120 °C
Minimum Display 60
Maximum Display 70
Smooth
The function „Smooth“ can be activated by setting a check in the related field.
Note: The grayed out entries Sensor ID and Sensor Type are purely informative and cannot be changed.
After a change of the sensor settings an asterisk appears right to the icon , which indicates that the settings
still has to be transferred to the device. The settings are not synchronized at the moment and will be updated to the SITRAM
MULTISENSE device on the next connection (3.7), if the selection field “Update Configuration” is selected.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 42 of 115
SITRAM® Multisense Software Installation and Operation Manual
The telephone number of the short message service center has to be entered in the input field
„Service Center”. Normally this number is preprogrammed on the SIM card. Therefore it has only to be entered in case it is no t
on the SIM card.
The alarm message, which is defined in the input field „Message” (max. 63 characters), can be send to up to 5 recipients
simultaneously. The numbers of these recipients have to be entered in the input fields „Recipient” to „Recipient #5”.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 43 of 115
SITRAM® Multisense Software Installation and Operation Manual
By performing a right mouse click on the input field „Message”, the content of the alarm message can be combined with pre
defined wild-cards as follows:
To add pre-defined text the corresponding wild-cards have to be selected. The following text is available in this form:
{#} - Serial number
{1} - Customer data row 1
{2} - Customer data row 2
{3} - Customer data row 3
{4} - Customer data row 4
{T} - System time long: „hh:mm:ss”
{t} - System time short: „hh:mm”
{D} - System date long: „YYYY:MM:DD”
{d} - System date short: „YY:MM:DD”
{A} - Alert name
{a} - Alert number
{l} - Alert level
Value of the “Alert level” {l}
Mode Condition Value
„All“ No alert 0
Hi > Hi 1
> Hi 1
Hi - Hi
> Hi - Hi 2
Low < Low 1
< Low 1
Low - Low
< Low - Low 2
< Low 1
Out Range
> Hi 2
> Low 1
In Range
< Hi 1
Example: {#}{1}{T}{D}{A}{l}
The following message text is the result: Serial number, Customer data row 1, System time long,
System date long, Alarm name, Alarm level
The content of the message text can be defined freely as well without using the wild-cards.
Note: Either „Log-entry & SMS”, „Output & SMS” or „Output Hold & SMS” must be selected in the selection field „Alert Setup”
(3.5.1) to alarm via SMS. Also the optional GSM modem must be installed and configured.
Settings which has been newly created or modified must be saved with the button afterwards. The asterisk right to
the icon indicates that the settings still has to be transferred to the device. The settings are not
synchronized at the moment and will be updated to the
SITRAM MULTISENSE device on the next connection (3.7), if the selection field “Update Configuration” is selected.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 44 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 45 of 115
SITRAM® Multisense Software Installation and Operation Manual
Before entering the laboratory results, the appropriate date on which the oil sample was taken, has to be selected in the
selection field „Sample Date”. The average values of the gas concentration on the indicated date will be calculated and shown
in the information fields „SITRAM MULTISENSE - History-Value”. After the laboratory values were entered into the corresponding
input fields „Laboratory - Value” (H2, C2H2, C2H4 and CO), they must be confirmed with the button. In the mask
„Active Adjustment” the information fields „Active since” and „Sample Date” change from „- not set -” to „- new -” .
The device will now use these correction factor values as base for the gas concentration calculation. The device is able to s ave
up to 8 DGA level adjustments at which only the last one is active. If 8 DGA level adjustments are already present on the device
and a new one is added and the oldest will be replaced by the new one. The DGA level adjustments can only be disabled, but
not deleted anymore:
Settings which has been newly created or modified must be saved with the button afterwards. The asterisk right to
the icon indicates that the settings still has to be transferred to the device. The settings are not
synchronized at the moment and will be updated to the SITRAM MULTISENSE device on the next connection (3.7), if the
selection field “Update Configuration” is selected.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 46 of 115
SITRAM® Multisense Software Installation and Operation Manual
Output #1 4 … 20 mA H2 4 … 20 mA H2
Output #4 4 … 20 mA CO 4 … 20 mA CO
Output #6 - - 4 … 20 mA CO2
Output #7 - - 4 … 20 mA C2H6
Output #8 - - 4 … 20 mA CH4
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 47 of 115
SITRAM® Multisense Software Installation and Operation Manual
3.5.7 Settings
The settings in the menu are distributed in three tabs:
Real time clock RTC (3.5.7.1)
Ethernet (3.5.7.2)
Modbus RS485 (3.5.7.3)
LED Bar Levels (Error! Reference source not found.)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 48 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: „None” means that no time shift in relation to the real time clock (local time) is available. This setting is recommended.
Settings which have been newly created or modified must be saved with the button afterwards. The asterisk right
to the icon indicates that the settings still has to be transferred to the device. The settings are not synchronized
at the moment and will be updated to the SITRAM MULTISENSE device on the next connection (3.7), if the selection field
“Update Configuration” is selected.
Date and time of the SITRAM MULTISENSE device can be synchronized by use of the connected PC. Therefore select the
selection field „Synchronize with PC Clock” (3.7.1) that is shown after connection to the PC and pressing the button
in the transformer menu:
3.5.7.2 Ethernet
Ethernet related settings can be done for each SITRAM MULTISENSE device in the tab „Ethernet” of the menu.
It can be chosen out of the following two variants:
Static IP (3.5.7.2.1)
DHCP Client (3.5.7.2.2)
3.5.7.2.1 Static IP
The network settings can be obtained from your corresponding system administrator!
IP Address
Mask The setting 255.255.255.0 can be used in general.
Gateway Normally the automatic assigned setting can be used.
TCP Port Number The TCP port number should be determined by the system administrator as
well. The free range for TCP port numbers is: 49152 ... 65535. Theoretically the device allows the
following settings: 1 ... 65535. However several TCP port numbers are reserved for other
applications for example HTTP, FTP, Mail, etc.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 49 of 115
SITRAM® Multisense Software Installation and Operation Manual
By using this setting, the device obtains the network settings from the DHCP server which is responsible for the network
administration. In this case only the port number can be entered. The network administrator must allow the automatic TCP/IP
address assignment for SITRAM MULTISENSE in the network.
Settings which have been newly created or modified must be saved with the button afterwards. The asterisk right
to the icon indicates that the settings still has to be transferred to the device. The settings are not synchronized
at the moment and will be updated to the SITRAM MULTISENSE device on the next connection (3.7), if the selection field
“Update Configuration” is selected.
3.5.7.3 Modbus RS485
RS485 or MODBUS® serial related settings can be done for each SITRAM MULTISENSE device in the tab
„Modbus RS485“ of the menu.
RS485 serial (3.5.7.3.1)
MODBUS® RTU/ASCII serial (3.5.7.3.2)
MODBUS® TCP (3.5.7.3.3)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 50 of 115
SITRAM® Multisense Software Installation and Operation Manual
Point-to-Point connection for one device Bus connection for multiple devices
Address: 0,1 ... 254 (as Bus Node with Address 1…254)
Answer Delay: 0 ... 2550 ms
Baud rate 2400, 4800, 9600, 19200, 38400 or 57600
Data bits, parity and stop bits of the serial interface are set permanent to 8-N-1.
Note: Each device has to have a unique address (0, 1 … 254). Currently up to 32 devices can be in the same RS485 bus
network.
Settings which have been newly created or modified must be saved with the button afterwards. The asterisk right
to the icon indicates that the settings still has to be transferred to the device. The settings are not synchronized
at the moment and will be updated to the SITRAM MULTISENSE device on the next connection (3.7), if the selection field
“Update Configuration” is selected.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 51 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: Each device has to have a unique address (1 … 254). Currently up to 32 devices can be in the same MODBUS® serial
network.
Settings which have been newly created or modified must be saved with the button afterwards. The asterisk right
to the icon indicates that the settings still has to be transferred to the device. The settings are not synchronized
at the moment and will be updated to the SITRAM MULTISENSE device on the next connection (3.7), if the selection field
“Update Configuration” is selected.
3.5.7.3.3 MODBUS® TCP
The MODBUS® communication can be implemented into a network. MODBUS ® TCP is available on the SITRAM MULTISENSE
devices 5 and 9 and uses the default port number 502. These are independent from the serial MODBUS ® configuration.
MODBUS® TCP is not supported by SITRAM Multisense Software but for the sake of completeness it is
mentioned here.
3.5.8 Transformer Setup
The settings in the menu are distributed in three tabs:
Hot Spot Calculation (3.5.8.1)
Ageing Rate / Loss-of-Life (3.5.8.2)
Bushing Monitoring (3.5.8.3)
3.5.8.1 Hot Spot Calculation
The SITRAM MULTISENSE device can calculate the hot spot temperature of a transformer. For this calculation the SITRAM
MULTISENSE device requires additional sensors.
The tab „Hot Spot Calculation“ contains the selection of the required sensors and has additional 1 … 3 sub tabs, depending on
how many cooling stages were selected.
Note: If the required sensors are not available in the selection, they must be defined previously in the menu
(3.5.2).
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 52 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: The assignment of the calculated values to the virtual sensors must be defined previously in the
menu (3.5.2).
First of all, you must define the selection- and input fields with required information. Followings information must be selected
respectively entered:
Kind of Insulation (Paper): Normal / Thermally Updated
Hot-Spot Temperature Sensor: Select sensor
Transformer Loss-of-Live: Enter hours
Transformer Time into Service: Enter hours or select date
… into Service since: Select date (DD.MM.YYYY)
Note: The value for “Transformer Time into Service” is set automatically when the date “… into Service since” is selected. The
date is selected in three steps (day – month –year) with the cursors on the right hand side of the field.
Note: If the required sensor is not available in the selection, it must be defined previously in the menu
(3.5.2).
Settings which have been newly created or modified must be saved with the button afterwards. The asterisk right
to the icon indicates that the settings still has to be transferred to the device. The settings are not
synchronized at the moment and will be updated to the SITRAM MULTISENSE device on the next connection (3.7), if the
selection field “Update Configuration” is selected.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 54 of 115
SITRAM® Multisense Software Installation and Operation Manual
For detailed information regarding the sensors, refer to the Siemens bushing monitoring documentation.
Settings which have been newly created or modified must be saved with the button afterwards. The asterisk right
to the icon indicates that the settings still has to be transferred to the device. The settings are not
synchronized at the moment and will be updated to the SITRAM MULTISENSE device on the next connection (3.7), if the
selection field “Update Configuration” is selected.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 55 of 115
SITRAM® Multisense Software Installation and Operation Manual
3.6 Diagnostics
The SITRAM MULTISENSE 9 device has additional measuring data diagnoses. This can help to interpret the measuring data. The
measuring data are represented according to Duval (type 1) and Rogers (3D). Different algorithms can be selected.
The three settings for the two diagnosis methods appear in the menue :
The properties can be selected as follows:
Duval Regions: - standard - / Biotemp / FR3 / IEC 60599 / Midel / Silicone
Remark: The sort of oil for the Duval-triangle can be selected here. Different oil has different boundaries and fault zones.
The selection ’standard’ corresponds to the type of oil IEC 60599.
Duval threshold: - standard - / 10-10-10
Remark: The selection 10-10-10 means, that the measurement is only visualized in the triangle, when a minimum
concentration of at least 10 ppm for the gases C 2H2, CH4 and C2H4 is present.
Rogers threshold: - standard - / 10-10-10-10-10
Remark: The selection 10-10-10-10-10 means, that the measurement is only visualized in the 3D grafic, when a minimum
concentration of at least 10 ppm for the gases H2, C 2H2, C2H4, C2H6 and CH4 is present.
3.6.1 Duval Triangle
To view the read out measuring data as a Duval triangle (defined according IEC 60599 type 1 with C 2H2[%], CH4[%] and
C2H4[%]), the entry has to be selected in the corresponding transformer in the tree structure. Three
different operation windows are available (see graphic):
Duval
Sensor
Window
Result
Window
Timerange
Selection
Window
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 56 of 115
SITRAM® Multisense Software Installation and Operation Manual
Sensor name
Status display
This is for the overview only and presents the sensor colour of the legend from the Result Window in the “Display as Graphic”
view.
Remark: The settings are fixed. The status display as well as the corresponding colours can not be changed.
3.6.1.2 Timerange Selection Window (Duval):
The timerange for the display in the Result Window is selected in this window:
Average Timerange
Timerange
Start-Date
Calendar
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 57 of 115
SITRAM® Multisense Software Installation and Operation Manual
The following time values are available for the average value generation:
automatic 2 hours 1 day
4 hours 2 days
6 hours 4 days
12 hours 7 days
If "automatic" is selected the following average value generation is deposited at the corresponding time span:
Remark: The average value generation is displayed in square brackets in the header in table view of the Result
Window
Time Span
The time span in the Result Window can be changed by means of the selection box or with selected time span (blue
background) with the arrow keys of the computer keyboard.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 58 of 115
SITRAM® Multisense Software Installation and Operation Manual
Preceding month
Remark: The calendar appears in the standard language of the operating system.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 59 of 115
SITRAM® Multisense Software Installation and Operation Manual
Beside of the data columns the table consists of a column containing the time of the measurement. It is named Date/Time. By
default the sequence of the data is ordered by Date/Time (oldest first).
Context Menu
The following settings can be done via the context menu in the table view:
Remark: The settings in the red frame are only possible, if the Graphic- or the Duval Triangle View are active. When
changing to Table View they will be grayed out and can not be selected anymore. The blue marked settings can be
selected at any time.
Show Alarm-, Date- Timerange: With this function the sensor- and the time range selection window can be faded in
or out. The Result Window will be displayed bigger or smaller accordingly.
Remark: This function can be switched ON or OFF with a double click in the Result Window as well.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 60 of 115
SITRAM® Multisense Software Installation and Operation Manual
Context Menu
The following settings can be done via the context menu in the graphic view:
Remark: The settings in the red frame are only possible, if the Graphic- or the Duval Triangle View are active. When
changing to Table View they will be grayed out and can not be selected anymore. The blue marked settings can be
selected at any time
Show Alarm-, Date- Timerange: With this function the sensor- and the time range selection window can be faded in
or out. The Result Window will be displayed bigger or smaller accordingly.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 61 of 115
SITRAM® Multisense Software Installation and Operation Manual
Remark: This function can be switched ON or OFF with a double click in the Result Window as well.
3.6.1.3.3 Result Window Duval Triangle View
In the illustration Duval Triangle View, the data points are displayed in the selected time range with the appropriate averaging
as a Duval Triangle (according typ 1):
Context Menu
The following settings can be done via the context menu in the graphic view:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 62 of 115
SITRAM® Multisense Software Installation and Operation Manual
Remark: The settings in the red frame are only possible, if the Graphic- or the Duval Triangle View are active. When
changing to Table View they will be grayed out and can not be selected anymore. The blue marked settings can be
selected at any time
Show Alarm-, Date- Timerange: With this function the sensor- and the time range selection window can be faded in
or out. The Result Window will be displayed bigger or smaller accordingly.
Remark: This function can be switched ON or OFF with a double click in the Result Window as well.
The sort of oil for the Duval-triangle can be selected here.
The sort of oil for the Duval-triangle (Duval Region) can be selected in the workin area of the Menu (3.6).
Different oil has different boundaries and fault zones. The selection ’standard’ corresponds to the type of oil IEC 60599.
Here the overview of the 6 different settings with the same data points:
Standard Biotemp FR3
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 63 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rogers
Sensor
Window
Result
Window
Timerange-
Selection
Window
The five gases are shown as relations in a 3D graphic (according IEC 60599 Relations: X-Axis (Ratio1)=C2H4/C2H6; Y-Axis
(Ratio2)=CH4/H2; Z-Axis (Ratio3)=C2H2/C2H6)
The individual operation windows have the following designation:
Rogers Sensor Window (3.6.2.1)
Timerange Selection Window (3.6.2.2)
Result Window (3.6.2.3)
The Result Window offers the following options in the context menu (right mouse click):
Continue processing the displayed measuring data (3.6.2.4)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 64 of 115
SITRAM® Multisense Software Installation and Operation Manual
Sensor name
Status display
Timerange
Start-Date
Calendar
The following time values are available for the average value generation:
automatic 2 hours 1 day
4 hours 2 days
6 hours 4 days
12 hours 7 days
If "automatic" is selected the following average value generation is deposited at the corresponding time span:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 65 of 115
SITRAM® Multisense Software Installation and Operation Manual
Remark: The average value generation is displayed in square brackets in the header in table view of the Result
Window.
Time Span
The time span in the Result Window can be changed by means of the selection box or with selected time span (blue
background) with the arrow keys of the computer keyboard.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 66 of 115
SITRAM® Multisense Software Installation and Operation Manual
Preceding month
Remark: The calendar appears in the standard language of the operating system.
3.6.2.3 Result Window (Rogers)
In the Result Window, the data points are displayed in the selected time range with the appropriate averaging. Activate the
context menu in the Result Window with a right mouse click and choose the desired display type.
Remark: The selection of the view can also be done via the View Menu in the Menubar.
The individual display types have the following designations:
Result Window Rogers Tabel View (3.6.2.3.1)
Result Window Rogers Graphic View (3.6.2.3.2)
Result Window Rogers 3D View (3.6.2.3.3)
3.6.2.3.1 Result Window Rogers Table View
In the illustration Table View, the data points are displayed in a table within the selected time range with the appropriate
averaging.
Beside of the data columns the table consists of a column containing the time of the measurement. It is named Date/Time. By
default the sequence of the data is ordered by Date/Time (oldest first).
Context Menu
The following settings can be done via the context menu in the table view:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 67 of 115
SITRAM® Multisense Software Installation and Operation Manual
Remark: The settings in the red frame are only possible, if the Graphic- or the Rogers 3 View are active. When
changing to Table View they will be grayed out and can not be selected anymore. The blue marked settings can be
selected at any time.
Show Alarm-, Date- Time range: With this function the sensor- and the time range selection window can be faded in
or out. The Result Window will be displayed bigger or smaller accordingly.
Remark: This function can be switched ON or OFF with a double click in the Result Window as well.
3.6.2.3.2 Result Window Rogers Graphic VIew
In the illustration Graphic View, the data points are displayed in the selected time range with the appropriate averaging in a
graphical curve progression:
Context Menu
The following settings can be done via the context menu in the graphic view:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 68 of 115
SITRAM® Multisense Software Installation and Operation Manual
Remark: The settings in the red frame are only possible, if the Graphic- or the Rogers 3D View are active. When
changing to Table View they will be grayed out and can not be selected anymore. The blue marked settings can be
selected at any
Show Alarm-, Date- Timerange: With this function the sensor- and the time range selection window can be faded in
or out. The Result Window will be displayed bigger or smaller accordingly.
Remark: This function can be switched ON or OFF with a double click in the Result Window as well.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 69 of 115
SITRAM® Multisense Software Installation and Operation Manual
DX Intersection of D1 and D2
D1 Discharges of low energy
D2 Discharges of high energy
DT Combination thermal faults & discharges
PD Partial discharges
T1 Thermal faults, t < 300°C
T2 Thermal faults,300°C < t < 700°C
T3 Thermal faults, t > 700°C
Context Menu
The following settings can be done via the context menu in the Rogers 3D View:
Remark: The settings in the red frame are only possible, if the Graphic- or the Rogers 3 View are active. When
changing to Table View they will be grayed out and can not be selected anymore. The blue marked settings can be
selected at any time.
Show Alarm-, Date- Timerange: With this function the sensor- and the time range selection window can be faded in
or out. The Result Window will be displayed bigger or smaller accordingly.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 70 of 115
SITRAM® Multisense Software Installation and Operation Manual
Remark: This function can be switched ON or OFF with a double click in the Result Window as well.
In order to clarify whether certain data points are located in a bad sector, the display of the Rogers 3D Ratio View can be rotated
in a limited area around the Z axis. Once the mouse cursor is in the workspace, the icon changes to . The rotation can be
performed by clicking with the left mouse button in the relevant side of the workspace. In the left side of the work area (red)
the rotation is clockwise. In the right side of the work area (blue) the rotation is counterclockwise. The closer the position of
the cursor is to middle of the work area, the smaller the rotation steps become. The end positions are indicated by the symbols
(clockwise end position) and (counterclockwise end position). Through a left mouse click in the middle of the working
area the graph jumps back to the home position.
Context menu
Table View Graphic View Rogers 3D View
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 71 of 115
SITRAM® Multisense Software Installation and Operation Manual
By pressing the button the dialog window „SITRAM MULTISENSE Communication“ opens:
The following selection- and input fields are available in the dialog window:
Read Configuration: Reads the configuration of the SITRAM MULTISENSE device. That means that changes done in
SITRAM Multisense Software (marked with a star) will be over written with the configuration from the SITRAM
MULTISENSE device.
Read History & Alerts: All measurement and alarm values which have not already read out at that time, will be read
and stored into the SITRAM Multisense Software database.
Update Configuration: Writes all changes done in SITRAM Multisense Software to the SITRAM MULTISENSE device and
activates them. The numeric password (default 9999) is needed for this action.
Reset Alerts: With this command all actual alarms which haven’t been acknowledged at that time will be
acknowledged. The numeric password (default 999) is needed for this action.
Auto-disconnect when done: Automatically closes the connection when the data transfer is completed. This transfer
option is especially recommended when using a modem. As a result, connection costs can be reduced to a minimum.
Synchronize with PC Clock: Automatically synchronizes the date and the time of the SITRAM MULTISENSE device with
the one set up on the PC. The numeric password (default 9999) is needed for this action.
Password: Serves as security and is needed for several actions. Numeric default password: 9999.
Timeout [s]: The default timeout is 5 seconds. When a modem is used an timeout of 20 seconds is recommended.
After the Start button is pressed, the content of the working area changes. Now the log window with the connection- and data
transfer status is shown.
By pressing the button the connection will be terminated immediately. This should
be prevented during the login to the device. After termination or abortion of the communication the log window can be closed
with this button. The transformer properties will be shown again in the working area. In case problems occur with
the communication the diagnostic data (log data) (3.4.1) can be used for trouble shooting.
3.7.2 SITRAM MULTISENSE Connection Scheduler
3.7.2.1 General
Up to SITRAM Multisense Software version 1.0.16 the read out of SITRAM MULTISENSE data had to be initialized manually.
With the version 1.0.18 an automatic read out is available. The automatic data read out is realized with the Windows based
connection scheduler and is integrated in SITRAM Multisense Software.
3.7.2.2 Description of the Connection Scheduler
Following you find a detailed description of the connection scheduler (the „italic written terms” relate to descriptions in the
dialog window of the connection scheduler).
The connection scheduler is a separate process and runs, if active, in the back ground of SITRAM Multisense Software. When
„Scheduled Data Read-Out” is active the transformers will be checked every 15 seconds if any data read out is available. As soon
a transformer is active, it will be checked if the actual time is greater than the point of time „Next Connect at:”. On this way an
internal list with open data read outs will be generated.
In case the list is not empty it will be processed step by step until all transformers are read out before a new list is being
generated.
On each transformer data read out, information will be supplied. On every successful read out the „Connect Fail Count:” will be
set to zero and the „Next Connect at:” is updated (actual time and „Connect Interval:” will be added – optional synchronized to
the „Connect Time [s]:” if available).
In case of an error, the „Connect Fail Count:” will be increased by one and the point of time „Next Connect at:” will be
overwritten by the actual time plus a delay. If the „Connect Fail Count:” is less than 3 a new connection with a delay of 5
minutes will be initialized. If the „Connect Fail Count:” is less than 5 a new connection with a delay of 10 minutes will be
initialized. When the „Connect Fail Count:” reaches the value 5, the „Next Connect at:” is updated (actual time and „Connect
Interval:” will be added – optional synchronized to the „Connect Time [s]:” if available. The same as with
successful connections.).
By the time the connection scheduler notices that the length of time since the moment „Next Connect at:” is 3 times bigger
than the „Connect Interval:”, the „Connect Fail Count:” will be set to 4. On transformers with error status, this leads to a double
connection attempt if the application was not active for a longer period of time.
The following points should be noticed:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 72 of 115
SITRAM® Multisense Software Installation and Operation Manual
Changes which were created by the connection scheduler need some time until they are visualized in the tree
structure.
Even if the read out status of a transformer is bad, a connection attempt based on the „Connect Interval:” will always
be initiated.
A manual data read out will not change the moment „Next Connect at:”. Even if a manual data read out is directly
before the moment „Next Connect at:” the planed data read out will be executed as well.
A log file ´Scheduler.log´ will be generated in the SITRAM Multisense Software data folder. In case of problems with the
connection scheduler a view in this file can help finding the error. The entries in the log file are English.
Note: It is not possible to write the configuration or to acknowledge alerts with the connection
scheduler. Still these actions are to be performed manually. Only setting the time is possible using the connection scheduler
and the corresponding password.
To open the dialog window SITRAM MULTISENSE connection scheduler the corresponding transformer has to be selected in the
tree structure. Afterwards the dialog window can be opened with the button.
Note: There is also the possibility to open the dialog window via the transformer menu (2.1.4.4) or the context menu (3.3.3).
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 73 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 74 of 115
SITRAM® Multisense Software Installation and Operation Manual
The connection scheduler has established the connection to transformer 4 in station 1. The communication buttons in the
working area are deactivated. The changed background color (light pastel yellow) of the buttons indicates that the data read
out is actually running.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 75 of 115
SITRAM® Multisense Software Installation and Operation Manual
The connection to transformer1 in station 1 was interrupted more than 5 times or could not be
established. The transformer as well as the station is shown with the corresponding error symbol (red station, red transformer).
3.7.3 Windows Task Scheduler with SITRAM Multisense Software Connection scheduler
The automatic data read out with the SITRAM Multisense Software connection scheduler can be retrieved via the
Windows task scheduler.
Windows contains an assistant that guides you step by step through the creation of a new task.
Follow these instructions to create a task for SITRAM Multisense Software. The task scheduling depends on the personal
necessity and the data read out with SITRAM Multisense Software. If, for example, you want to perform a daily data read out
with SITRAM Multisense Software, you have to invoke the Windows task scheduler daily as well.
When the task input with the Windows task scheduler is finished, the SITRAM Multisense Software task can be optimized with
the command line parameters (3.7.3.1).
Note: Communication settings and the connection to the device should be checked before a SITRAM Multisense Software task
is initiated via the Windows task scheduler.
3.7.3.1 Command Line Parameters for the Windows Task Scheduler
By invoking the data read out from SITRAM Multisense Software via the Windows task scheduler two command line
parameters can be used.
Example: <Path>\SITRAM Multisense Software -IdleClose 0:15:00 –Minimized
3.7.3.1.1 Parameter „IdleClose“
The command line parameter „Idle Close” closes the application as soon all data has been read out from SITRAM MULTISENSE
device. This command has to be set with a time which defines the closing delay. This closing delay must have the following
format: [hh:mm:ss].
The SITRAM Multisense Software connection scheduler scans the transformers in regard to the next data read out and
determines so the starting point. In case the rest time until the next data read out is greater than the „Idle Close”-time the
application will be closed. If a data read out should take place every day the default „Idle Close”-time should be set to 15
minutes. This leaves the possibility to repeat the dial-up in case of a failure and closes the application within a reasonable time
if a communication error occurs.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 76 of 115
SITRAM® Multisense Software Installation and Operation Manual
Sensor
selection
window
Result
window
Time span
selection
window
The individual operation windows in the working area have the following labels:
Sensor selection window (3.8.1)
Time span selection window (3.8.2)
Result window (3.8.3)
By the context menu (right mouse click) in the result window the following options arise:
Further processing of the shown data (3.8.4)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 77 of 115
SITRAM® Multisense Software Installation and Operation Manual
Sensor device
Last transferred value
Sensor name
Activation mark with status display
Beside of the sensor name the last transferred data, the device and the time span (from / to), in which measurement values ar e
available, will be displayed. There is an activation mark in front of the sensor name (i. e.: : H2 Sensor is activated and
therefore shown in the result window). With a double click on the sensor name or the associated activation mark, the view in
the result window of the corresponding sensor can be changed. In this case the scaling of the active sensor will automatically
be projected on the Y-Axis.
Activation mark with Status Display
Sensor view active – Scaling is displayed on the left Y-Axis
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 78 of 115
SITRAM® Multisense Software Installation and Operation Manual
If the color is already assigned to a sensor, the corresponding name will be displayed on the right side of the color
icon. However if you want to assign a color that is already allocated, you have the possibility to overwrite the color
assignation. Therefore the message „Overwrite ‘XX’ Color assignment?” has to be confirmed by pressing OK.
Time Span
Selection field
Scrollbar (1 ... 12 hours)
Start Date
Calendar
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 79 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: The scroll bar appears only when selecting 1, 2, 3, 6 or 12 hours, with a resolution of
1 hour. The scroll bar can be moved with the arrow keys or selected and moved with the left mouse button.
Start Date
The start date is set with a mouse click on the desired date in the calendar dialog. The previous or next month can be
selected with the arrow keys in the calendar dialog.
Previous month
Note: The calendar appears in the default language of the operating system.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 80 of 115
SITRAM® Multisense Software Installation and Operation Manual
Beside of the measurement value columns the table contains a column with the time stamp. This column is named with
Date/Time. By default the order of the measurement value is sorted by Date/Time (oldest data first).
Context Menu
In the table view the following settings can be done via the context menu:
Note: The red marked settings are only available in active table view. On a change to graph view they will be grayed
out and cannot be selected anymore. The blue marked settings are always available.
Show Date- & Span-Panel: The sensors- and the time span selection window can be switched on or off with this
function. The result window will be displayed smaller or bigger accordingly.
Note: With a double click of the left mouse button in the result window this function can also be switched on or off.
Export to Excel: (3.8.4.1)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 81 of 115
SITRAM® Multisense Software Installation and Operation Manual
By moving the cursor to a desired position on the graph, the corresponding measurement value will be displayed as decimal
value with date and time in a light yellow pop up window.
Context Menu
In the graph view the following settings can be done via the context menu:
Note: The red marked settings are only available in active graph view. On a change to table view they will be grayed
out and cannot be selected anymore. The blue marked settings are always available.
Set Axis Scaling ... : By selecting „Set Axis Scaling …” the input window „Axis Scaling” opens:
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 82 of 115
SITRAM® Multisense Software Installation and Operation Manual
The scale setting of both axis (left Y-axis and right Y-axis) can be done independently from each other. By selecting
„Auto” the range will be adjusted automatically related to the active sensors. If the relation between the individual
sensors becomes too big, the assignment of the sensors (3.7.1) to both Y-axes can be selected manually.
Mark Curve Points: Every single measurement value is displayed with a cross marker in the curve shape.
Show Measure Gaps: Here you can choose whether missing data will be displayed with a gap or if the gap between
the measurement values will be interpolated.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 83 of 115
SITRAM® Multisense Software Installation and Operation Manual
Full Detail for long Time Periods: To ensure a fast presentation over long time spans,
average values will be displayed over the curve shape. By activating this function, all measurement values will be
displayed on the curve shape.
Show Date- &Span-Panel: The sensor- and the time span selection window can be switched on or off with this
function. The result window will be displayed smaller or bigger accordingly.
Note: With a double click of the left mouse button in the result window the sensor- and the time span selection
window can be switched on or off as well.
Print Graph ... : (3.8.4.2)
Screenshot -> Clipboard: (3.8.4.3)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 84 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 85 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: The function „Print Graph …” can be activated via the menu bar entry (2.1.1.10) as well.
Paste
Ctrl + V
Note: As soon an additional copy- or cut command is being performed the clipboard will be
overwritten and the content of the result window will not be available any longer!
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 86 of 115
SITRAM® Multisense Software Installation and Operation Manual
Alarm
selection
window
Alarm
window
Time span
selection
window
The individual operation windows in the working area have the following labels:
Alarm selection window (3.9.1)
Time span selection window (3.9.2)
Alarm window (3.9.3)
By the context menu (right mouse click) in the alert window the following options arise:
Further processing of the shown alerts (3.9.4)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 87 of 115
SITRAM® Multisense Software Installation and Operation Manual
The alarms which were configured in the alarm setup (3.5.1) or directly on the device are displayed in the alarm selection
window. On the SITRAM MULTISENSE types 5 and 9 the alarm “extraction error” will be displayed by default. Beside of the alarm
name the last alarm state is displayed, that means after the read out of the data it represents the actual condition.
Add: The display of the alarm in the alarm window will be activated.
Remove: The display of the alarm in the alarm window will be deactivated.
3.9.2 Alarm Time Span Window
In this window the time span to be shown in the alarm window will be selected.
Time span
Selection field
Scroll bar (1 ... 12 hours)
Start Date
Calendar
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 88 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: The scroll bar appears only when selecting 1, 2, 3, 6 or 12 hours, with a resolution of
1 hour. The scroll bar can be moved with the arrow keys or selected and moved with the left mouse button.
Start Date
The start date is set with a mouse click on the desired date in the calendar dialog. The previous or next month can be
selected with the arrow keys in the calendar dialog.
Previous month
Note: The calendar appears in the default language of the operating system.
3.9.3 Alarm Window
The results for all activated alarms will be displayed in the alarm window for the chosen time span. A right mouse click in the
alarm window activates the context menu. Choose the desired display view:
The individual display formats have the following label:
Alarm window table view (3.9.3.1)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 89 of 115
SITRAM® Multisense Software Installation and Operation Manual
Device
Value
Date / Time
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 90 of 115
SITRAM® Multisense Software Installation and Operation Manual
Context Menu
In the table view the following settings can be done via the context menu:
Note: The red marked settings are only available in active table view. On a change to graph view they will be grayed
out and cannot be selected anymore. The blue marked settings are always available.
Show Date- &Span-Panel: The alarm- and the time span selection window can be switched on or off with this
function. The alarm window will be displayed smaller or bigger accordingly.
Note: With a double click of the left mouse button in the alarm window this function can also be switched on or off.
Export to Excel: (3.9.4.1)
Visible alarms
Alarm legend
Graphical trend
Alarms
Y-Axis scaling
State legend
In the graph view as well as in the table view 5 different alarm states are displayed. The meaning of the different
states is as follows:
0->None
No alarm active. I.e. the threshold “level 1” of the alarm was not exceeded in the past or the pending alarm was
acknowledged in the past.
1->Level 1*
The defined threshold “level 1” for a Hi - alarm was exceeded in the past. The threshold “level 1” was underrun again.
2-> Level 2*
The defined threshold “level 2” for a Hi - Hi - alarm was exceeded in the past. The thresholds “level 2” and “level 1”
were underrun again.
3-> Level 1
The defined threshold “level 1” for a Hi - alarm is currently exceeded.
4-> Level 2
The defined threshold “level 2” for a Hi - Hi - alarm is currently exceeded
Following an example of the same alarm trend in both display formats:
Context menu
In the graph view the following settings can be done via the context menu:
Note: The red marked settings are only available in active table view. On a change to graph view they will be grayed
out and cannot be selected anymore. The blue marked settings are always available.
Show Date- &Span-Panel: The alerts- and the time span-panel can be switched on or off with this function. The result
window will be displayed smaller or bigger accordingly.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 92 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: With a double click of the left mouse button in the alarm window the alarm- and time span selection window
can be switched on or off as well.
Print Graph ... : (3.9.4.2)
Context menu
Table View Graph View
Note: The functions „ Export ►„ (2.1.1.5) and „Print Graph …” (2.1.1.10) can be
selected via the menu bar as well.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 93 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: The function „Print Graph …” can be activated via the menu bar entry (2.1.1.10) as well.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 94 of 115
SITRAM® Multisense Software Installation and Operation Manual
Sensor
selection
window
Result
window
Time Span
selection
window
The individual operation windows on the working area have the following labels:
Sensor selection window online sensors (Error! Reference source not found.)
Time span selection window online sensors (3.10.2)
Result window online sensors (3.10.3)
By the context menu (right mouse click) in the result window the following options arise:
Further processing of the online values (3.10.4)
3.10.1 Sensor Selection Window Online Sensors
All sensors which are available in the SITRAM MULTISENSE device (related to the device type) are displayed in the sensor
selection window (Visible Sensors). Basically all sensors will be recorded, even if they are not displayed active in the result
window.
Sensor device
Sensor name
Activation mark with status display
The sensor device is displayed on the right side of the sensor name. There is an activation mark in front of the sensor name
(i.e.: : H2 Sensor is activated and therefore shown in the result window). The color for the displayed sensor is assigned
automatically. With a double click (left mouse button) on the sensor name or the associated activation mark the view in the
result window of the corresponding sensor can be changed.
Activation mark with Status Display
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 95 of 115
SITRAM® Multisense Software Installation and Operation Manual
Communication connection
Start / Stop / Online Status
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 96 of 115
SITRAM® Multisense Software Installation and Operation Manual
Note: When a data recording is not finished within the defined time span, the already recorded data will be
overwritten continuously.
Communication connection with Online Status
To ensure the communication connection to the device the correct connection settings (3.4) for the desired device
have to be defined first.
The data recording will start.
Offline Establish connection Data read out active Cancel connection Offline
Note: There is no context menu for the time span connection window.
3.10.3 Result Window Online Sensors
The actual data of the online sensors will be shown as a curve progression in the result window. The desired detail of the curve
progression can be chosen via the zoom function and the „visible time span”. Further processing of the data is possible from
here.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 97 of 115
SITRAM® Multisense Software Installation and Operation Manual
Visible Sensors
Color Legend
Visible Sensors
The color legend for the active sensors in the sensor selection window is being displayed here again.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 98 of 115
SITRAM® Multisense Software Installation and Operation Manual
The chosen interval can be hold by mark the selection field (freeze):
Freeze the displayed interval: switched ON
Start time: Time on which the data recording was started [hh:mm:ss]
Visible Interval: Start- and End time of the visible interval [hh:mm:ss]
3.10.4 Further Processing of the Online Values
Out of the result window online sensors the data can be further processed. The different options can be selected via the
context menu.
Context menu
Graph -> Clipboard (3.10.4.1)
Export Data to ► (3.10.4.2)
Print Graph ... (3.10.4.3)
Unzoom Graph (3.10.4.4)
Delete Data (3.10.4.5)
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 99 of 115
SITRAM® Multisense Software Installation and Operation Manual
Paste
Ctrl + V
With the command “paste” or with the shortcut [Ctrl + V] the content of the clipboard can be pasted into the desired program.
3.10.4.2 Export
The actual data will be exported with the function „Export Data to ►
” into an Excel- or CSV-file. The export contains the values of
all existing sensors in its corresponding cycle time.
Excel ...
CSV ...
Note: Depending on the used operating system and the Excel version installed on your PC, it can rarely happens, that the
communication to the device will be interrupted when an Excel export is being
performed during an active data read out.
3.10.4.3 Print
By selecting the context menu entry „Print Graph ... „ the following preview window opens:
More functions are available in this window (e.g. print command, zoom, page view and close)
Note: The function „Print Graph …” can be activated via the menu entry (2.1.1.10) as well.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 100 of 115
SITRAM® Multisense Software Installation and Operation Manual
Unzoom Graph
Delete data
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 101 of 115
SITRAM® Multisense Software Installation and Operation Manual
Result
Selection Result
Window Window
SITRAM MULTISENSE 9
Result
Selection Result
Window Window
In online mode, all sensors are ideally recorded every second. However, the cycle time depends upon the used communication
interface (modem, serial interface or network) and its settings. In worst case, the cycle time increases to 5 ... 10 seconds.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 102 of 115
SITRAM® Multisense Software Installation and Operation Manual
Result selection
Here the selection between the two result views can be done (view Extraction Status or Prozess Flow in the result
window). The selection can be changed at any time.
Establish Communication with Online Status
To ensure the communication connection to the device, the correct connection settings (3.4) for the desired device
have to be done first.
The online connection will be started.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 103 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 104 of 115
SITRAM® Multisense Software Installation and Operation Manual
Status information
Time bar graph
Device status
Measurement- and
extraction components
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 105 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 106 of 115
SITRAM® Multisense Software Installation and Operation Manual
SITRAM MULTISENSE 9
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 107 of 115
SITRAM® Multisense Software Installation and Operation Manual
Sub step 1
Sub step 2
Sub step 3
Sub step 4
Sub step 5
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 108 of 115
SITRAM® Multisense Software Installation and Operation Manual
Status information
Time bar graph
Process information
Process steps
In case of an error or a not installed device an additional step (red) will be displayed in the upper right area of the
result window.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 109 of 115
SITRAM® Multisense Software Installation and Operation Manual
Status Information
The status information displays the progress within the process flow and is presented with up to 5 time bar graphs (3
dark and 2 light green). Each time bar graph depicts the degree of fulfillment of a partial step within the process step.
Sub step 1
Sub step 2
Sub step 3
Sub step 4
Sub step 5
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 110 of 115
SITRAM® Multisense Software Installation and Operation Manual
3.11.2.3.3 Depression
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 111 of 115
SITRAM® Multisense Software Installation and Operation Manual
3.11.2.3.6 Circulate
3.11.2.3.9 Measurement
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 112 of 115
SITRAM® Multisense Software Installation and Operation Manual
3.11.2.3.10 Purging
3.11.2.3.12 Ready
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 113 of 115
SITRAM® Multisense Software Installation and Operation Manual
3.11.2.3.14 Draining
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 114 of 115
SITRAM® Multisense Software Installation and Operation Manual
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Author: Fleischhauer, Vitalij Page 115 of 115
Siemens AG
Energy Management
Humboldtstrasse 59
90459 Nuremberg,
Germany
Printed on elementary chlorine-free bleached paper. Subject to change without prior notice.
Rev. 1.0, 3/27/2018 © Siemens AG 2018. All rights reserved. Page 7 of 115