Nothing Special   »   [go: up one dir, main page]

Untitled

Download as pdf or txt
Download as pdf or txt
You are on page 1of 47

STANDARD SPECIFICATION NO.

KPC-C-01
REVISION 4 Sheet 1 of 50

STANDARD SPECIFICATION NO. KPC-C-01

STANDARD SPECIFICATION FOR


CIVIL AND STRUCTURAL DESIGN CRITERIA

FOR

P.T. KALTIM PRIMA COAL PROJECT


AT EAST KALIMANTAN, INDONESIA

Revision 1 2 3 4

D a t e 02/03/89 17/03/89 27/04/89 21/06/89

Prepared by S.S-J S.S-J S.S-J S.S-J

Checked by

Contracts
Approved
Approved by
Proj. Mgr.

TABLE OF CONTENTS
Page No.

SECTION 1 - GENERAL 4

1.1 Introduction 4
1.2 Definitions 4
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 2 of 50

1.3 Abbreviations 4
1.4 Governing Codes, Standards, Regulations
and Reference Documents 4
1.5 Contractor's Obligation 5
1.6 Site Data 5

SECTION 2 - EARTHWORKS 6

2.1 General 6
2.2 Site Earthworks 6
2.3 Grassing and Slope Protection 6
2.4 Roadworks 6

SECTION 3 - DRAINAGE 8

3.1 General 8
3.2 Runoff Classification 8
3.3 Design Hydrology 8
3.4 Culvert Installation 9
3.5 Open Channel Drainage 9
3.6 Sedimentation Dams & Silt Traps 9

SECTION 4 - WATER 11

4.1 General 11
4.2 Raw Water 11

SECTION 5 - SEWERAGE 15

5.1 General 15
5.2 Sewer Lines 15
5.3 Sewage Treatment 16

SECTION 6 - STRUCTURAL - GENERAL 17

6.1 Design Loads 17


6.2 Structural Steelwork 21
6.3 Concrete Structures 25
6.4 Masonry/Blockwork 26
6.5 Foundations 26
6.6 Piles 26
6.7 Earth Pressure 28

SECTION 7 - BUILDINGS 29

7.1 Scope 29
7.2 General 29
7.3 Switch Rooms 30
7.4 Stockyard Control Room (SCR) 30
7.5 Portsite Amenities Building 30
7.6 Cribroom and Toilet at the Jetty Head 30
7.7 Pumphouse (Portsite) 31
7.8 Coal Washing Building 31
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 3 of 50

7.9 Minesite Laboratory 31


7.10 Central Control Building (Minesite) 31

SECTION 8 - AIRCONDITIONING & VENTILATION 33

SECTION 9 - MARINE WORKS 34

9.1 General 34
9.2 Standards and Codes of Practice 34
9.3 Design Criteria 34
Fig. 9.3.4(ii)(a) 40
9.4 Design Load Combinations 47

Attachment A - List of Standards and


Reference Documents 45

Attachment B - Seismic Design Criteria for


(Revision 2) Civil Engineering Works

Attachment C - Design Flood Estimation Manual

Attachment D - Design Load Combinations for


Marine Structures

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 4 of 50

SECTION 1 - GENERAL

1.1 INTRODUCTION

These criteria shall govern the design of the structures and


facilities included in the Scope of Work.

The metric system (SI) of measurement and calculation shall


be used throughout.

1.2 DEFINITIONS

"Submit", "submitted" and "submittal" shall mean written


submission to the Engineer requesting his approval.

"Approved" and "approval" shall mean approved by the


Engineer in writing.

"Instructed", "directed" and "ordered" shall mean ordered by


the Engineer in writing.

"Acceptable" shall mean acceptable to and approved by the


Engineer as advised by him in writing.

1.3 ABBREVIATIONS

The abbreviations listed below shall, where used in this


Specification, have the following meanings:

AS Australian Standard
SAA Standards Association of Australia
BS British Standard
KPC PT Kaltim Prima Coal
NAASRA National Association of Australian State Road
Authorities
ISO International Standards Organisation
NI Indonesian Code

1.4 GOVERNING CODES, STANDARDS, REGULATIONS AND REFERENCE


DOCUMENTS

Except as varied by this Specification or otherwise


specifically approved or ordered, the design of all
structures and facilities shall, as a minimum requirement,
be based on the codes, standards and reference documents
listed in Attachment A to this Specification as well as all
relevant Indonesian codes, standards and regulations and the
Site Data collected and listed in the Appendices.

In case of conflict between any of the listed codes,


standards, reference documents and regulations, the more
stringent requirement shall govern.
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 5 of 50

1.5 CONTRACTOR'S OBLIGATION

In addition, the Contractor shall in every instance satisfy


himself as to the completeness and adequacy of the site data
presented, and where necessary for the proper design of the
facility or structure in question, carry out such further
investigations and determinations as he deems necessary.
The results of such further investigations and
determinations shall be made available to the Engineer.

All designs shall be carried out and checked by fully


qualified engineers experienced in the type of work being
undertaken, and all design computations shall be clearly and
methodically set out with all references noted.

1.6 SITE DATA

The available site data have been collected and are


available for perusal in KPC's offices in Jakarta. For
further details, including a listing of the available
reports, refer:

o Appendix I Meteorological, Oceanographic and


Hydrological Data
o Appendix J Geotechnical Data for the Pinang
Coal Mine Project

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 6 of 50

SECTION 2 - EARTHWORKS

2.1 GENERAL

The design of earthworks, roads and accessways, embankments,


etc. shall generally be based upon the data collected in the
geotechnical investigations (Appendix J), the details
specified herein and any additional investigations and
determinations carried out by the Contractor to fully
satisfy himself of the site conditions pertaining to the
Works.

2.2 SITE EARTHWORKS

Maximum batter slopes shall generally be as follows:-

(a) In cut 2H:1V


(b) In fill 2H:1V for Terrain Units IV & V
2.5H:1V for Terrain Unit III
3H:1V for Terrain Unit II

Batter slopes may be steepened where it can be shown by


approved slope stability analyses for the particular soils,
that such slopes will be stable.

Flatter slopes may be necessary for slope stability of


particular in-situ batters or fill batters, depending on
Terrain Unit, depth of cut, dip and strength of soil strata
and height of fill. The Contractor shall assess the
appropriate stability requirements for all batters and shall
submit slope stability analyses as and when requested by the
Engineer.

2.3 GRASSING AND SLOPE PROTECTION

Grassing or other appropriate slope protection shall be


provided to all cut and fill batters and drainage channels,
and their design shall be submitted.

The types of grasses used shall be suitable for the region.

2.4 ROADWORKS

Access roads shall be provided to all areas of both the


minesite and portsite coal preparation and handling
facilities including all buildings, conveyors, stockpiles,
marine facilities, and to, as well as along, the overland
conveyor.

Minimum road dimensions shall be as follows:-

Single lane: - 3500mm minimum along overland conveyor


- 3700mm elsewhere
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 7 of 50

Double lane: - 6000mm minimum along overland conveyor


- 8000mm elsewhere

Shoulders: - 1500mm minimum.

Pavement design shall be based upon the geotechnical


conditions at the particular locations, the available
pavement materials for base and sub-base courses, and the
traffic and vehicular loads imposed.

Painted marker posts shall be provided along all roads and


accessways, complete with reflectors at maximum spacings of
100m on straights, and and at spacings of 0.6R for curve
radius R to maximum 100m spacing.

Minimum 3% crossfalls shall be allowed on road surfaces.

Design speed of roads around the Site shall be 60km/hr.

Generally, the maximum grade shall be 10%. However, for


infrequently travelled roads the grade may exceed 10% for
limited stretches.

For the service road alongside the Overland Conveyor


(CO-01), the design vehicular traffic shall be the same as
specified in section 9.3.4(ii) of this Specification. Other
roads, including any roads and overpasses within the
stockpile area, shall be designed for the following design
vehicles in addition to those specified in Section
9.3.4(ii):

(i) a 140t mobile crane,


(ii) the standards specified by the relevant Indonesian
regulations for that class of road,
(iii) the construction traffic generated by the
development and construction of KPC's mine and
facilities, including the transport by road of coal
to the interim stockpile at the portsite.

Transition slabs shall be designed and installed between any


bridge or overpass and the adjoining embankments, and shall
be minimum 3m long.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 8 of 50

SECTION 3 - DRAINAGE

3.1 GENERAL

Drainage design shall be based upon the site data listed in


Appendix I for meteorology, oceanography and hydrology, the
details specified herein and any additional investigations
and determinations carried out by the Contractor to fully
satisfy himself of the site conditions pertaining to the
Works.

3.2 RUNOFF CLASSIFICATION

Runoff shall be collected in drainage facilities that


separates contaminated from uncontaminated water.

Contaminated water - from catchments disturbed by


mining operations, coal handling
facilities, and infrastructure
areas and roads.

Uncontaminated water - from natural, undisturbed or fully


vegetated catchments.
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 9 of 50

3.3 DESIGN HYDROLOGY

All drainage collection facilities, water diversion


facilities, bridge structures, culverts and other hydraulic
structures shall be designed for flows appropriate to the
following requirements for probabilities of occurrence
expressed as "average recurrence intervals" (ARI) in years.

Description Design storm ARI (Years)

Major drainage works: 300


- bridges over rivers/streams
- floodways for overland
conveyor
- drainage where flooding may
disrupt production.

Open channels:
- normal flow with freeboard 25
- for overtopping where plant
facilities may be damaged 100

Culverts:
- flowing full 5
- 1 metre head at the inlet 10
- overtopping road 25

Peak flow calculations shall be computed using the


parameters recommended in Attachment C to this
Specification.

3.4 CULVERT INSTALLATION

The culverts shall be installed at slopes that will provide


self cleansing velocities of 0.6m/s minimum for 1/3 depth of
full flow. In areas where such grades cannot be achieved,
silt traps shall be provided at the culvert inlets.

The minimum culvert diameter shall be 375mm.

All culverts shall have reinforced concrete headwalls and


wingwalls with minimum concrete thickness of 150mm.

Guardrails or guide posts shall be provided at culvert


headwalls.

Culverts shall be designed for the maximum loading


configuration of plant and vehicles that will pass over
them.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 10 of 50

Culverts may be reinforced concrete pipes (RCP) of the


appropriate class or corrugated metal pipes (CMP) with
appropriate protection against corrosion.

Scour and erosion protection shall be provided at the inlets


and outlets to culverts.

Roughness coefficients for hydraulic flow calculations shall


be in accordance with Australian Standard AS2200.

3.5 OPEN CHANNEL DRAINAGE

All open channels shall have scour and erosion protection


facilities.

Manning's roughness coefficients for hydraulic calculations


shall be to the approval of the Engineer.

Batter slopes to drains shall be as appropriate to the soil


conditions such that erosion and undermining are minimised.

Minimum channel velocities at 0.08m depth shall be 0.2m/s.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 11 of 50

3.6 SEDIMENTATION DAMS AND SILT TRAPS

All contaminated runoff shall run through sedimenta-


tion storages, also referred to as "settlement ponds".

The design criteria for settlement ponds shall be as


follows:-

(i) particle sizes for settling during the 3 hours


design storm with ARI of 5 years:

. Coal particles: 0.07mm and larger

. Sand and silt particles: 0.03mm and larger

(ii) minimum storage volume equivalent to rainfall over a


24 hour period with an ARI of 5 years.

Silt traps shall be provided at locations adjacent to coal


handling facilities for collection of coal sediment before
entering drainage systems. Silt traps shall also be
provided at other locations where excessive silt can be
retained from runoff prior to entering major drainage
systems.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 12 of 50

SECTION 4 - WATER

4.1 GENERAL

Water for raw water and potable water will be reticulated by


KPC to a connection point within 100m of the eastern
boundary of the portsite stockpile area.

The Contractor shall base all design work on the details


specified herein and any additional investigations and
determinations carried out by the Contractor to fully
satisfy himself of the site conditions pertaining to the
Works.

4.2 RAW WATER

Raw water shall be used for washdown, fire protection and


dust suppression facilities.

4.2.1 Reticulation Mains

Water reticulation mains and fittings shall be of


materials appropriate for buried or above ground
application as detailed in Standard Specifications
KPC-C-06 and KPC-M-16 respectively.

Hydraulic calculations shall be carried out with


appropriate roughness coefficients as detailed in
Australian Standard AS2200, or approved equivalent
for pipes in the "aged" condition, with checks for
higher flows for pipes in new condition.

Installation details for reticulation mains shall be


in accordance with the Standard Specifications
referred to in this Clause.

The minimum depth of cover over all buried pipes


shall be 600mm.

4.2.2 Washdown

Outlets for washdown hoses shall be provided at all


transfer stations, at regular intervals along
conveyors (not more than 100m apart), at truck
washdown facilities, and any other locations
requiring washdown facilities.
In addition, washdown connection points shall be
provided for the shiploader(s) and for the stockpile
machines (stackers and reclaimers). For the latter,
the connection points shall be maximum 100m apart.

4.2.3 Fire Protection


[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 13 of 50

Fire protection facilities shall be serviced from


either a separate reticulation supply or a joint
supply system with dust suppression and washdown
facilities, provided pressure and flow requirements
can be maintained.

Provision shall be made for augmenting the fire


water supply in cases of emergency and/or a major
fire, with sea water.

If it is proposed to use the same reticulation


system for both fresh water and sea water, then the
system shall be designed such that each and every
part of the system can be thoroughly flushed clean
with fresh water after each emergency, and the
flushing procedure, complete with diagrams, shall be
incorporated into an approved manual.

The pumps for the emergency fire water supply shall


be located off the trestle to the shiploader(s)
together with the pumps for the Power Station
cooling water intake. See also Section 7.7.

Each longitudinal row of stockpiles shall be


encircled by the fire watering main(s), which shall
not be less than 150mm diameter.

Fire service outlets shall be located adjacent to


all ground run conveyors, transfer stations, drive
heads, switchrooms, electric substations, oil
depots, amenities buildings, and the central control
room building.

Fire hydrants shall be located such that the


possibility of accidental damage from mobile
equipment is minimised.

Hydrant spacing along conveyor lengths and coal


stockpiles shall be a maximum of 100m.

Fire hydrant specification shall be as detailed in


Standard Specification KPC-C-06.
Flow and pressure requirements shall be in
accordance with the requirements of Australian
Standard AS2419.1 and the requirements of KPC's
insurance policies for the Project.

In addition to hydrant installations, small bore


hose reels and fire extinguishers shall be used.
The former shall be 20mm solid bore hoses with
bayonet fittings to fit 25mm diameter outlet valves.
Portable hose reels shall be 36m long; and along
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 14 of 50

each conveyor, fire hose outlets shall be spaced


maximum 100m apart.

Fire protection within buildings shall comply with


all relevant Codes, Standards and Regulations, as
well as the requirements of KPC's insurance
policies.

In addition, permanently connected hose reel units


shall be installed close to any fire hazardous
equipment and any storage area for fire hazardous
materials.

4.2.4 Dust Suppression

The design of all dust suppression systems,


including their associated water reticulation and
reagent injection systems, shall be submitted.

Where the Scope of Work calls only for the design


and installation of the associated reticulation
systems; the design shall still be submitted, and
shall be based on the criteria set out below for the
complete dust suppression system, such that the
future extension is limited to the simple addition
of the requisite monitors, nozzles, hoses and
instrumentation.

Water sprays shall be provided for all coal


stockpiles. The sprays shall consist of appropriate
spray nozzles along each side of the stockpiles such
that all the surface area of the stockpile will be
covered by the sprays.

Sprays shall be automatically activated when wind


velocity exceeds a set point, and shall also be
capable of being operated manually.

Provision shall also be made for spraying the coal


before stockpiling with water to which a surfactant
agent has been or can be added.

Manually operated dust suppression monitors shall be


spaced such that complete coverage of the coal
stockpiles is guaranteed, and located such that the
possibility of accidental damage from mobile
equipment is minimised.

In addition, fog sprays shall be installed in the


head chute of each conveyor.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 15 of 50

SECTION 5 - SEWERAGE

5.1 GENERAL

Sewerage collection, treatment and disposal facilities shall


be provided for all amenities included in the Scope of Work.

The Contractor shall determine the appropriate loadings


based upon the staffing requirements set by KPC.

5.2 SEWER LINES

All internal wastewater/sewerage collection facilities shall


be in accordance with Standard Specification KPC-A-10 for
Plumbing.

Buried sewer lines shall be vitrified clay or PVC for


nominal diameters of 150mm and under, and vitrified clay,
PVC, cast iron or ductile iron for diameters greater than
150mm. All jointing will be with rubber rings.

Minimum depth of cover over buried pipes shall be 750mm.


Pipe sections, other than cast or ductile iron, under
roadways shall be encased in concrete if cover is less than
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 16 of 50

1200mm. Concrete encasing shall commence and finish at


flexible couplings in the pipelines.

Manholes shall be provided at all changes of direction,


changes of grade and at maximum distances of 100m on
straights. The fall across manholes shall be 30mm minimum.

Manhole covers in areas accessible to vehicular traffic


shall be cast iron of suitable load bearing capacity.
Manhole covers in areas not accessible to traffic shall be
light duty cast iron.

The design flows in reticulation pipelines shall be based


upon the fixture units connected to the sewers and the
population load on the sewers. In addition, an allowance
for infiltration shall be added to the above flows
equivalent to 100 cubic metres per day per kilometre per
metre diameter.

Minimum grades shall be such as to maintain adequate self


cleansing velocities without scouring the pipes.

5.3 SEWAGE TREATMENT

Sewerage treatment facilities shall comprise septic tank


systems or other approved disposal/treatment facilities.

It shall be the Contractor's responsibility to determine,


subject to approval, the appropriate treatment facilities
and disposal suitable for the Site conditions.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 17 of 50

SECTION 6 - STRUCTURAL

6.1 DESIGN LOADS

The design loads for all structures shall generally be as


detailed below. However, the Contractor shall be
responsible for assessing all specified loadings and load
combinations which may be applied to any particular
structure.

6.1.1 Dead Loads

The design dead load shall be in accordance with


AS1170 and shall include the weight of all
structural components and insulation, the empty
weight of equipment and piping, and all
miscellaneous permanent loads. For the maximum
loading condition, the total weight of the process
material or test fluid in the equipment and piping,
whichever is applicable, shall be included.

6.1.2 Live Loads

(a) General

Except where otherwise specified, live loads


shall comply with Section 3 of AS1170, Part
1. The provision for occasional loading on
roof trusses or frames shall be applied in
accordance with Clause 3.8.3 of AS1170, Part
1.

(b) Elevated Floors

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 18 of 50

Except where equipment loads produce more


severe loading, the following live loads
shall be applied:

Operating Floors and


Light Storage 7.5kPa

Heavy Equipment
Lay Down Areas 12.0kPa

Plant Maintenance Walkways 5.0kPa

Stairs and Landings 5.0kPa

Office and Laboratory


Areas 3.0kPa

Walkways alongside Conveyors 2.5kPa

Storage Areas - to be calculated, but not


less than 2.4kPa per metre
of clear height.

In addition to the above a concentrated load


of 10kN shall be applied mid-span to all
major floor beams and girders, but these
loads shall not be cumulatively added to
supporting members.

(c) Ground Floor Slabs and Pavements

Ground floor slabs and pavements shall be


designed to support the equipment and live
loads specified for that particular area.
The minimum thickness shall be 150mm, unless
otherwise approved.

6.1.3 Wind Loads

(a) General

Wind loads shall be calculated in accordance


with AS1170, Part 2.

The design wind velocity shall be taken as


35m/s, in combination with:

o Terrain Category 1 for the coastal area,


including wharf and portsite stockpile
area, and the terminal transfer tower
for the Overland Conveyor, and

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 19 of 50

o Terrain Category 2 for the mine area and


Overland Conveyor generally.

(b) Operating Conditions


For the limits of operating conditions a
maximum wind speed of 20m/sec shall be
adopted for design purposes.

6.1.4 Impact Loads

Static loads shall be increased by the following


percentages to allow for impact:

Reciprocating machinery,
crushers and pumps 100%

Rotating machinery 20%

Mobile equipment and Shiploaders 20%

Hangers supporting floors and


balconies 35%

6.1.5 Seismic Loads

For structures falling within the scope of volume 5:


Draft Code of Practice for Seismic Design of
Buildings in Indonesia, of the Indonesian Earthquake
Study, the design procedure, requirements and
assessment of earthquake forces shall be in
accordance with that Draft Code.

For civil engineering works the seismic design


criteria shall be as set forth in Attachment B to
this Specification and further elaborated in section
9.3.2(v).

For unusual buildings or other types of structures


the seismic design criteria shall be as submitted to
and approved by the Engineer.

6.1.6 Thermal Loads

Forces caused by expansion or contraction of


structures, pipes and/or equipment, shall be taken
into account.

The following coefficients of static friction shall


be used to determine forces at sliding surfaces:

Teflon on Stainless Steel 0.05


Steel on Steel 0.30
Steel on Concrete 0.45
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 20 of 50

A minimum ambient temperature range of 20?C shall be


adopted for the design of all structures whether
enclosed and shielded from sunlight or not.

The effects of temperature gradients induced by the


sun and the cooling effects of either wind, shade or
wash down activities shall also be taken into
account.

6.1.7 Dynamic Loads

Dynamic loads, such as those resulting from


vibrating equipment and from surging fluids in
piping and equipment, shall be considered.

Design parameters and operating frequencies for


vibrating equipment shall be obtained from the
manufacturers for each piece of equipment.

6.1.8 Temporary Loads due to Construction

The method of construction and erection shall for


each facility be investigated and any possible extra
loadings applicable during the course of
construction ascertained.

If more severe than the normal operating loads, then


these shall be taken into account in the design of
that facility.

6.1.9 Vehicular Loads

These shall not be less than those specified in


section 9.3.4(ii) of this Specification, and shall
wherever specified and/or directed be combined with
any one or all of the following additional design
vehicles:

(i) a 140t mobile crane,

(ii) the standards specified by the relevant


Indonesian regulations for that class of road
and/or bridge,

(iii) the construction traffic generated by the


development and construction of KPC's mine
and facilities, including the transport by
road of coal to the interim stockpile at the
portsite.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 21 of 50

Any road, accessway, bridge and overpass forming


part, or likely to be part, of the main transport
route between the port area and the mine shall be
designed for all of the additional design vehicles
listed above; while any road, accessway, parking
area and overpass leading to and being part of the
maintenance area for the stacker and the
stacker/reclaimer shall be designed also for the
140t mobile crane.

6.1.10 Bin and Silo Pressures

These shall be determined based on the properties


and characteristics, including flow characteristics,
of the material to be stored, as evidenced by actual
tests performed at an approved laboratory.

Any effect due to the shape and size of the bin or


silo proposed, including the proposed reclaim
arrangements and equipment, shall also be taken into
account.

6.1.11 Load Combinations

Any or all of the following loads shall be combined


to produce the most severe stresses in the
structure:

. Dead loads
. Roof and floor live loads
. Equipment loads
. Crane loads
. Material loads
. Wind loads
. Temperature effects
. Seismic effects
. Wave loads
. Current loads
. Buoyancy effects
. Accident loads

In each combination of loads considered, the various


classes of loads and/or effects shall be combined
using the relevant combination factors.

6.2 STRUCTURAL STEELWORK

6.2.1 General

The design shall generally conform to AS1250 or


AS1538 and the referenced standards, unless
otherwise approved.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 22 of 50

For any specific structure, reference should also be


made to the relevant Project Specification for any
particular requirements.

6.2.2 Design and Stresses

Load combinations examined shall generally, as a


minimum, include those listed in Clause 3.3.1 of
AS1250.

In addition, and where relevant, the load


combinations examined shall include those listed in
Attachment D and in ISO5049, Part 1. For the latter
load combinations the permissible stresses shall be
as specified for the equipment in question.

For conveyor trusses see subsection 6.2.2(a)


following.

Particular attention shall be paid to steelwork that


is supporting dynamic loads or vibrating machinery.
It shall be checked for fatigue as per the
requirements of the referenced codes and it shall be
ensured that resonance does not occur.

All bolted connections of members subject to dynamic


loads or reversal of stresses shall be bolted with
grade 8.8 high strength bolts and be fully tensioned
conforming to AS1511 to form a friction type joint.
Load indicating washers or bolts designed for
special tightening procedures shall not be used
unless otherwise approved.

The minimum bolt diameter for primary structural


members shall be 20mm and each individual member
shall be connected with at least two bolts per
connection.

Connections for purlins, girts, door and window


frames, handrails, ladders, stairs and other minor
members may be designed using commercial class mild
steel bolts. Commercial class bolts shall be
minimum 16mm in diameter unless otherwise approved.

All connection plates shall be minimum 10mm thick,


with small cleats etc. being minimum 6mm thick
plates.

Where purlins and girts are used to provide lateral


restraint to supporting members, the adequacy of
such support shall be proven to the satisfaction of
the Engineer.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 23 of 50

Roof and wall cladding shall not be considered as


effectively restraining the supporting members.

Walkway grids shall minimum be "Forgeline" type


FA325, Series 2, with a mass of 35.4 kg/m2, by Johns
Perry Industries Pty. Ltd., or approved equivalent.

(a) Conveyor Trusses and Supporting Trestles

The load combinations examined for conveyor


trusses and their supporting trestles shall
include the following, each with maximum
stresses not greater than the permissible
stresses to AS1250.

(i) Conveyor Trusses with Two Walkways

. (SW+ID+BL)+LL+PL+MN

. (SW+ID+BL)+LL+PL+MN+WS

. (SW+ID+BL)+0.5(LL)+PL+MF

. (SW+ID+BL)+0.5(WS)+PL+MF

. (SW+ID+BL)+LL*+LL*+PL+EL+MN [* live
load on both walkways]

. (SW+ID+BL)+PL+WD

. [(SW+ID+BL)+PL+EQ+MN]0.75

. [(SW+ID+BL)+PL+WD+MN]0.75

Longitudinal wind drag on rising


conveyors shall be considered in the
appropriate load combinations as
applicable.

(ii) Conveyor Trusses with one Walkway

The following load combinations shall be


considered in the design of conveyor
trusses with only one side walkway.

. (SW+ID+BL)+LL+PL+EL+MN

. (SW+ID+BL)+LL+PL+EL+MN+WS

. (SW+ID+BL)+0.5(LL)+PL+EL+MF

. (SW+ID+BL)+0.5(WS)+PL+EL+MF

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 24 of 50

. (SW+ID+BL)+PL+EL+WD

. [(SW+ID+BL)+PL+EL+EQ+MN]x0.75

. [(SW+ID+BL)+PL+EL+WD+MN]x0.75

Longitudinal wind drag on rising


conveyors shall be considered in the
appropriate load combinations as
applicable.

(iii) Conveyor Trestles

The load combinations shall be the


same as for the supported trusses.

In the preceding load case definitions the


following notation has been used:

SW Self Weight of Steelwork


ID Idlers Load
BL Belt Loads
LL Live Load on Walkway per Walkway
WS Wind Load at Shutdown (20m/sec)
WD Wind Load at Maximum Design Wind
MN Normal Operating Material Weight
MF Flooded Belt Material Weight
EL Electrical Cable Design Load
PL Piping Load
EQ Earthquake Load

The vertical and horizontal deflections of


conveyor trusses shall not exceed SPAN/500
for any load combination except those
including WD or EQ, in which case deflection
shall not exceed SPAN/250.

The horizontal lateral deflection at the top


of a conveyor trestle shall be limited to the
following:

(a) For WS: HEIGHT OR 50mm maximum


500

(b) For WD or EQ: HEIGHT


250

Conveyor trusses shall be given a vertical


precamber equal to the deflection caused by
SW+ID+BL+PL+EL.

Belt clearances from steelwork shall be 175mm

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 25 of 50

6.2.3 Materials

All structural steel shall be Grade 250 unless


otherwise approved.

All bolted structural steelwork connections shall be


made with hot dipped galvanised bolts.

For cladding to conveyors refer section 2.1(b) of


Standard Specification KPC-A-07.

For cladding and roofing of buildings, including


conveyor transfer towers, refer sections 2.1(a) and
2.3 respectively of Standard Specification KPC-A-07.

6.2.4 Welding
Welding shall conform to the requirements of AS1554.
Minimum welds shall be 6mm fillet welds.

All hollow sections shall be sealed to prevent


corrosion.

6.2.5 Fabrication and Erection

Fabrication and erection procedures shall comply


with AS1250 and the SAA Manual on Steel Structures,
Sections MA1.8 and MA1.9 respectively. Where the
approved design is based on a specific or
specialised fabrication or erection technique, full
details shall appear on the drawings.

6.2.6 Corrosion Protection

Generally, no specific allowances for corrosion


shall be made in the selection of structural member
sizes. However, where erected steelwork is
inaccessible and also subject to corrosive
atmosphere, such steelwork shall be protected by one
of the specified surface protection systems, or the
members selected shall be subject to reduced
allowable stresses, or additional thickness
provided, all as agreed with the Engineer.

6.2.7 Wear Protection

Structural members exposed to wear due to the motion


of coal or reject material, shall be protected by
wear plates or similar devises.

6.3 CONCRETE STRUCTURES

The design shall generally conform to AS3600 - 1988 and


referred standards, unless otherwise approved.
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 26 of 50

For any specific structure, reference should also be made to


the relevant Project Specification for any particular
requirements.

Characteristic concrete strength shall be minimum 30MPa for


the overland conveyor and minesite and minimum 35MPa for the
portsite and marine works.
Reinforcing bars shall be deformed bars either Grade 400Y or
Grade 250S to AS3600 unless otherwise specified or approved,
except that 10mm diameter plain round bar Grade 250R may be
used for ties and ligatures.

Except where otherwise specified, the minimum cover to


reinforcement shall be :-

Pad Footings 60mm


Columns 50mm
Elevated Beams and Slabs 40mm
Retaining Walls 50mm
Structures in Contact with
Ground Water 60mm
Precast Slabs and Wall Panels 40mm
Marine Structures See Section 9.3.9
Elsewhere 50mm

6.4 MASONRY/BLOCKWORK

Design shall generally conform to AS1475.

6.5 FOUNDATIONS

All foundations shall be founded on undisturbed soil unless


otherwise approved.

All foundation designs shall take cognizance of all of the


site data, and geotechnical and other reports that provide
the requisite information on geotechnical structure, soil
type, bearing capacity etc.

Adjacent foundations at different levels shall be designed


and built in such a way that the vertical angle between the
two adjacent foundations edges is not steeper than 45?.

Under operating conditions (excluding earthquake and


erection conditions) the maximum eccentricity of the
resultant shall be: e max = B/6, where e max is measured
from the centre of the underside of the foundation in
question.

For earthquake loading and erection conditions the maximum


eccentricity of the resultant shall be: e max = B/3.
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 27 of 50

All foundations supporting vibrating machines shall be


checked for resonance and amplitude of vibration.

6.6 PILES

6.6.1 General

The design shall generally conform to AS2159 unless


otherwise approved.

For piles forming part of the Marine Works see also


section 9.0 following as well as Standard
Specification KPC-C-10 and Project Specification
KPC-MA1.

6.6.2 Design Pile Capacities

Unless otherwise determined by the detailed design,


the estimated ultimate load capacity to be used in
the design of tubular steel piles shall be taken
from the following table:

Description Ultimate Resistance Diameter


of Pile

----------------------------------------------------
Onshore piles 1000kN 610mm
----------------------------------------------------

Marine piles:

Trestle 0-12m
water depth 1500kN 762mm

Trestle 12m-17m
water depth 1500kN 914mm

Jetty head
vertical piles 3500kN 914mm

Jetty head
raking piles 4000kN 914mm
___________________________________________________

Notes:

(a) Depth of water is measured below LAT.

(b) The above tabulated design values shall be


proven by tests as specified in Specification
KPC-C-10.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 28 of 50

(c) The design capacity of steel piles not listed


in the above table and of piles of other
materials, eg. timber piles, shall be as
approved.

(d) The factor of safety on the working loads of


piles shall be not less than two (2). This
factor of safety shall be maintained
notwithstanding the ultimate load capacities
quoted in the table above.

6.7 EARTH PRESSURE

Lateral earth pressures shall be calculated using the soil


data established in the geotechnical reports plus any
additional investigations deemed necessary and shall be done
in conformity with best available and accepted international
practice as agreed with the Engineer.

Seismic effects and "overpressures" due to any applied


compactive effort shall all be taken into account.

SECTION 7 - BUILDINGS

7.1 SCOPE

The buildings covered by this specification are the:

o Electrical substations with switchrooms

o Stockyard Control Room (SCR)


[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 29 of 50

o Portsite Amenities Building

o Cribroom and Toilet at the Jetty Head.

o Pumphouse (Portsite)

o Coal Washing Building

o Minesite Laboratory

o Central Control Building (Minesite)

o Conveyor Transfer Towers

7.2 GENERAL

All buildings shall be designed to comply with all relevant


Indonesian regulations as well as the criteria set forth in
this specification.

Except as otherwise specified or approved, all onshore


buildings shall be of concrete blockwork type construction,
reinforced as and if necessary, with steel roof and steel
roof sheeting and R.C. floors; while Conveyor Transfer
Towers and any buildings on the Trestle and Jetty Head shall
be of steel frame construction with steel cladding and roof.
The Coal Washing Building shall be an open steel framed
building with steel roof sheeting.

For further details regarding roofing and cladding materials


refer Sections 2.1, 2.2 and 2.3 of Standard Specification
KPC-A-07.

All buildings including transfer towers shall have an R.C


floor at ground level. Floors above ground level shall
generally be reinforced concrete except that for conveyor
transfer towers and the Coal Washing Building open steel
floor grids may, subject to approval, be used as and where
appropriate.

All air conditioned buildings and/or rooms shall have foil


insulation between roofing and purlins, batt insulation over
suspended ceilings, and, where necessary, perimeter wall
insulation with vapour barrier.

For further particular requirements refer the standard


architectural specifications nos. KPC-A-07 and KPC-A-10.

7.3 SWITCH ROOMS

These shall be pressurised to 25mm w.g. static pressure and


provided with adequate ventilation, and insulation as
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 30 of 50

necessary, to offset internal heat gain. Exhaust air shall


be released by barometric type dampers.

For further requirements refer the relevant project


specifications: ie. KPC-CP for minesite and KPC-CO1 for
portsite.

7.4 STOCKYARD CONTROL ROOM (SCR)

This shall be airconditioned as well as pressurised to 25mm


w.g. static pressure, and shall contain toilet and wash
facilities for the operators stationed in that building.

For further requirements refer project specification


KPC-CO1.

7.5 PORTSITE AMENITIES BUILDING

This building shall provide:

o change room, toilet and shower facilities for


25 people plus lockers for 40 people.

o airconditioned lunchroom facilities for 25


people.

o an airconditioned prayer room

7.6 CRIBROOM AND TOILET AT THE JETTY HEAD

This building shall provide lunchroom and toilet facilities


for up to 8 people. The lunchroom shall be airconditioned.

7.7 PUMPHOUSE (PORTSITE)

It is anticipated that this will house the pumps, including


standby pumps and associated control gear, for both the
Power Station cooling water and the emergency fire water
supply and that the water depth at the pump intakes will be
approx. 6m.

It is further anticipated that:

(i) the platforms supporting this equipment and its


shelter will be a concrete slab not less than
2
approximately 55m in area and supported on not less
than 4 nos. 762mm diameter steel piles.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 31 of 50

(ii) the platform will be integral with one of the


passing bays along the trestle.

The pumphouse shall be so designed as to permit the removal


of any of the pumps and their intake pipes; and the
forecourt or roadway in front of the pumphouse, or the
platform supporting the pumps and pumphouse as the case may
be, shall be designed to withstand the loads imposed by the
15 tonne mobile crane being used to both place and remove
any of this equipment.

The pumphouse shall be pressurised and ventilated similar to


the switch rooms, see Section 7.3.

7.8 COAL WASHING BUILDING

For detailed requirements refer project specification


KPC-CP.

7.9 MINESITE LABORATORY

For detailed requirements refer project specification


KPC-CP.

7.10 CENTRAL CONTROL BUILDING (MINESITE)

This shall be separate from the Coal Washing Plant, but


connected to the latter with a walkway at first floor level.

The building shall contain all electrical switchgear and


controls, with the transformers housed in suitable "pens"
integral with the building.

In addition, the building shall also contain the control


room for the minesite coal preparation and handling
facilities as well as change rooms, crib room, prayer room,
toilets and management offices for the nominated number of
people. These latter facilities shall all be located on the
first floor, unless otherwise approved.

The cribroom, prayer room and management offices shall all


be airconditioned.

For further requirements refer project specification KPC-CP.

SECTION 8 - AIRCONDITIONING AND VENTILATION

The buildings and/or rooms designated to be


[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 32 of 50

air-conditioned shall be cooled and ventilated by mechanical means


designed to maintain 24?C Dry Bulb Temperature and 55% relative
humidity in the designated areas as well as providing an adequate
rate of air change.

Change rooms, toilets and showers shall be provided with natural


ventilation plus a primary mechanical exhaust system giving 10 air
changes per hour.

SECTION 9 - MARINE WORKS

9.1 GENERAL

This section sets out the particular design criteria to be


used for the marine facilities defined in Project
Specification No. KPC-MA1: Marine Works.

9.2 STANDARDS AND CODES OF PRACTICE

Design of the marine facilities shall be carried out in


accordance with the latest editions of the codes of practice
and design standards referenced in this Specification.

The abbreviated titles for codes, standards and design


practices have been used for convenience.

The principal design codes shall be:

AS1170, Part 1 Dead and Live Loads


Part 2 Wind Loads
AS1250 SAA Steel Structures Code
AS1554 SAA Structural Steel Welding Code
AS1720 SAA Timber Engineering Code
AS2159 SAA Piling Code
AS3600-1988 SAA Concrete Structures Code

BS6349 Draft Code of Practice for Maritime


Structures

Where there is no applicable Code nominated herein, the


design shall be carried out in accordance with the
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 33 of 50

applicable Australian, British or United States Code of


Practice or Standard as agreed with the Engineer.

9.3 DESIGN CRITERIA

9.3.1 General

The depth of water at the berthing line shall be


17.8 below LAT. LAT is defined as 1.21m below mean
sea level (MSL), and MSL is 2.42m below bench mark
DAS 6010.

The structures and embankments shall be designed to


resist design loads derived from the criteria given
in this Specification unless otherwise approved.

Structures shall be checked for both service and


ultimate limit states.
Where alternative maximum and minimum factors are
given for imposed loads, the ultimate limit state
shall be checked separately for each alternative.
For further details see Section 9.4 and Attachment
D.
The various loadings are summarised in the
following.

9.3.2 Environmental Loads

Environmental Loads are those imposed upon the


structure by thermal, wind, sea, seismic or other
natural effects. The effect of these loads upon
ships moored to and vehicles and equipment parked on
the structures shall be included.

Loads imposed by the sea include those resulting


from waves, currents and buoyancy effects.

Environmental loads other than seismic shall be


separately computed for extreme and normal
conditions.

Concrete structures shall also be designed to resist


forces and effects caused by their own creep and
shrinkage.

(i) Deformation

The structures shall be designed to resist


all forces and effects caused by their own
thermal expansion and contraction and that of
pipelines, equipment and buildings supported
by the structures.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 34 of 50

Coefficients of thermal expansion shall be


taken as:
-5
o Steel 1.15 x 10 /?C
-5
o Concrete 1.1 x 10 /?C
-5
o Timber 0.6 x 10 /?C

A minimum ambient temperature range of 20?C


shall be adopted for design purposes.

The effect of temperature gradient induced by


the sun and the cooling effects of sea spray
shall be included in the loading cases
considered. It is noted that under specific
circumstances the effects of temperature
gradients will be superimposed on to gravity
and other loads.

(ii) Wind

Refer Section 6.1.3 of this specification.

(iii) Wave

Extreme wave loads for design purposes shall


be quasi-static loads imposed by a maximum
single occurrence wave (H max) of 7 seconds
period.

The design wave shall be:

Hsig. = 2.5m Hmax. = 4.0m

The design wave shall be assumed concurrent


with a tide level of
RL + 2.5 metres.

Waves shall be assumed to approach the


structures from any direction between
north-east and south.

(iv) Current

The structures shall be designed to resist


forces imposed by currents with velocities
evaluated by the Contractor.

However, for the purposes of this Contract


said velocities shall not be taken into
account at values less than the following:

o All structures (both extreme and normal


conditions):
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 35 of 50

- parallel to berth 0.30m/sec


- perpendicular to berth 0.15m/sec

o On tubular structural members, current


forces shall be calculated using the
following formulae:

FL = 0.5 CLSV A and FD =0.5 CDSV A

Where FL and FD = lift and drag force per


unit length,
S = mass density of
seawater,
CL = lift coefficient = 1.2
CD = drag coefficient = 1.0

Allowances made for protruding fins, etc.


shall be stated in the design submission. In
addition, 50mm of marine growth shall be
allowed for in the design (ie. D nom > D +
100mm).
=

No allowance shall be made for variation in


current forces with depth.

Non-circular members shall be designed using


the above formulae with revised CL and CD
(which shall be stated).

Lift and drag forces due to currents shall be


assumed to act simultaneously, shall be added
vectorially, and shall be added to the wave
forces.

(v) Seismic

Structures shall be designed to resist all


lateral and vertical seismic forces, which
shall be assessed in accordance with
Attachment B.

For piled marine structures the value of


EQ(=KCD) shall be increased by 50% as
required for bridge type structures founded
in weak deep soils, and shall be a minimum of
0.07D.

The structures shall be designed to be


ductile in accordance with AS2121 Appendix
4(a), 4(b) or 4(c) as appropriate.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 36 of 50

Should a value of K less than 1.0 (minimum


0.67) be proposed for the design, then the
adoption of that K-value for design purposes
shall be contingent upon the required
ductility of the proposed design being proven
to the satisfaction of the Engineer.

The design forces for the vertical direction


shall be taken as 50% of the horizontal
design forces, and shall be applied
simultaneously with the horizontal forces.

Lateral seismic design of the piles shall


include consideration of the likely movement
of any reclamation or embankment as a result
of earthquakes.

The wharf and trestle structures as a whole


shall be designed to withstand without
distortion or damage the forces likely to be
generated by earth movements caused by the
code level earthquake. Prediction as to the
likely behaviour of these structures in a
more severe event is required.

(vi) Buoyancy

Structures shall be designed to accommodate


the uplifts due to submergence in seawater.
For the purposes of calculation of uplift
forces the specific gravity of seawater may
be take as 1.025.

(vii) Tidal Variations

For available data refer Appendix I.

9.3.3 Dead Load of Structures

The dead loads of the structures shall include the


weights of all structural components, using the
following material densities:
3
o Structural steel 7850kg/m
o Normal weight reinforced
concrete including
3
reinforcement 2600kg/m
o Lightweight reinforced
concrete including
reinforcement 2100kg/m3
3
o Cement grout 1900kg/m

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 37 of 50

Where necessary, values for other components shall


be taken from AS1170 Part 1.

9.3.4 Other Imposed Loads on Structures

(i) General

Imposed loads are those due to equipment


which can be removed, conveyed materials,
traffic and equipment live loads,
construction loads, mooring and berthing
loads, and loads imposed by the shiploader,
jetty conveyor, transfer tower, and crib room
and other buildings.

(ii) Vehicular Loads

Apart from any construction loads, the


causeway, approach trestle and loading
platform deck structures shall also be
designed to accommodate the following design
vehicles:

o 15 tonne mobile crane

o NAASRA H20 - 44 truck

o 1 tonne light passenger vehicle

The plan arrangement of axles and wheel


spacings is shown in Figure 9.3.4(ii)(a).
For impact allowances see Section 6.1.4.

The following vehicle live load combinations


for the approach trestle shall be adopted for
design:

(a) A single mobile crane or NAASRA truck


plus up to one (1) full span of light
passenger vehicles, with vehicles either
on same span or on two (2) adjacent
spans.

Note: If the inclusion of the light


passenger vehicles produces a
more severe loading situation,
then that situation shall be
treated as an exceptional or
extreme load case; while the
loading situation formed by
excluding the light passenger
vehicles shall be treated as a
normal load case.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 38 of 50

(b) Mobile crane and NAASRA truck on


adjacent spans or within the same span.

(c) One (1) span of light passenger vehicles


only.

In addition, the approach trestle including


the superstructure and roadway shall also be
designed for the loads imposed by using the
15 tonne mobile crane for maintenance and
repairs of the trestle conveyor, CT-04. For
these operations the maximum lift is expected
to be no more than 5 (five) kN.

(iii) Other Live Loads

In addition to the vehicle loads given above,


and combined therewith where appropriate, the
structures shall be designed to also
withstand the following loads:

o Walkways 2.5kPa
o Dolphin Decks 5kPa
o Service Areas

(a) Service Deck at Transfer Tower:

10kPa and/or a 200kN point load on a


bearing area of 0.4m x 0.4m

(b) Shiploader Repair and Storage Area:

12kPa and/or a 200kN point load on a


bearing area of 0.4m x 0.4m

(c) Service Deck at Conveyor Return Unit:

10kPa or a 200kN point load on a bearing


area of 0.4m x 0.4m

(iv) Construction Loads

Where construction equipment is supported on


the permanent works, any loads and effects,
including dynamic effects, imposed on any
part of the permanent works, whether fully
assembled or in parts, as a result of the
chosen method(s) of construction and erection
shall be examined and allowed for in the
design. The combined effect of various wind,
wave, and other loads on the equipment, and
on the structures shall also be allowed for.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 39 of 50

(v) Berthing Dolphins

Breasting and berthing dolphins shall be


designed to safely absorb the berthing energy
from the following vessels under normal
serviceability conditions:

180,000 DWT 25,000 DWT


VESSEL VESSEL
______________________________________________

Ballast Displacement
(Tonnes) 60,000 10,000

Maximum Displacement
(Tonnes) at Berthing 200,000 35,000

Length Overall (m) 300 175


Beam (m) 50 25
Length Overall on
Hatches (cm) 220 130
Width of Hatches (m) 22 12

Berthing Velocity
(m/sec) 0.15 0.19
Point of Impact 1/4 Point 1/4 Point
Angle of Vessel to
Fender Face up to 10? up to 10?
_______________________________________________

The lateral forces on the structures,


imparted at right angles to the berthing
line, shall be calculated from the above data
and the characteristics of the fender system.

The longitudinal and vertical berthing loads


shall be taken as 30% of the lateral load.

(vi) Mooring Dolphins

Mooring bollards for the vessels listed in


sub-section (v) preceding have been nominated
in Project Specification No. KPC-MA1. The
Contractor shall calculate the loads on
mooring points imposed by moored vessels
under the action of wind, waves and currents
and compare these with the nominated bollard
capacities. If the calculated bollard
capacity is greater than that nominated,
then, subject to approval, a mooring bollard
of the required greater capacity shall be
substituted.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 40 of 50

Mooring bollards and support structures shall


be designed for a bollard pull which can act
in any direction within an arc of 150
degrees, the centreline of which is
perpendicular to the berthing face of the
loading platform. The bollard pull shall
also be assumed to act at an inclination to
the horizontal of up to 30 degrees to produce
the maximum effects on the bollard and/or
support structures.

(vii) Accident Loads

In addition to the normal serviceability


loads, the structures shall be checked for
the effects of accidental loads as defined
below.

(a) Approach Trestle

An accidental point blow of 50kN at


water level arising from the collision
of a barge or tug with either of the
piles in the trestle. The blow may be
absorbed by plastic deformation but the
trestle should remain in place.

(b) Berthing Dolphins

An accidental point blow transversely to


the dolphin of 7,500kN with damage or
destruction of fenders and buckling and
distortion of dolphin above MSL but pile
loads not exceeding ultimate.

(c) Mooring Dolphins

The maximum accident limit for mooring


dolphins shall be taken as breakage of
ships mooring ropes imposing a load of
2,500kN in any of the directions defined
in Clause 9.3.4(v).

(viii) Operational Loads due Shiploader and Feed


Conveyors

The support structures including running


rails for the shiploader, shall be designed
for the operational loads. These loads
include:

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 41 of 50

o Dead load of shiploader, feed conveyors


and coal.

o Live load on the walkways.

o Inertial loads of shiploader, shiploader


boom and boom carriage.

o Inertial loads of belt conveyors.

o Start up and braking loads for


shiploader and conveyors.

o Skewing loads during rotation of


shiploader, and travelling of boom
carriage.

o Loads due to luffing of shiploader boom.

The environmental effects of wind and seismic


loadings on the shiploader structure reacting
against the trestle support structure shall
also be designed for.

(ix) Loads from Service Pipes

The gravity loads from the cooling water


intake pipes, when full, shall be taken as
5.2kN/m per pipe.

In addition, the design of the trestle


structure(s) shall take into account the
expansion and contraction of all the service
pipe supported by the trestle(s).

9.3.5 Deformation of Structures

The differential lateral deflection between, on the


one hand the shiploader support structure(s) or the
trestle from shore, and on the other hand the
structure supporting the transfer tower TT-03, shall
be checked and shown to be within acceptable limits
for the satisfactory operation of the respective
conveyors.

The deflection of the dolphins, particularly the


berthing dolphins, shall likewise be checked, also
in the extreme load cases, and shown to be less than
the clear distance to any adjacent structure by an
acceptable margin.

9.3.6 Causeway

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 42 of 50

(i) Imposed Loads

In addition to the dead load of the


structures and conveyed materials, the
causeway shall be designed for the
following loads:
o The environmental loads specified in
section 9.3.2 of this specification.

o The live loads specified in section


9.3.4(ii) of this specification.

(ii) Stability

While the causeway alignment is given, the


longitudinal position of the causeway head is
not. The actual location of the causeway
head shall be determined by the Contractor
having regard to the requirements for
stability and his responsibilities under the
Contract.

The available geotechnical data indicate that


the soil conditions at the site are weak and
compressible. Therefore, particular care
shall be taken in the stability analyses and
in developing the requisite construction
techniques, the latter of which may need
inclusion of one or more methods for
improving the strength of the in-situ soils.

In addition to the Site Data, the Contractor


shall also study the records of the 1987
slippage failure of the existing reclamation
at the nearby service wharf, to assist in
deriving suitable parameters for the design
of the proposed causeway.

Stability design shall as a minimum include


analyses of both the total stress state for
short term considerations, and the effective
stress state for long term considerations.

The stability analyses shall furthermore take


into account:

o any layering of the subsoils, and

o the pore pressures and their variation


during construction,

and define the potential failure surface with


minimum margin of safety.
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 43 of 50

The factors of safety to be achieved when


considering short term loading using total
stress parameters shall not be less than 1.3.

Limiting pore pressures shall be established


based on effective stress analyses.

The long term factor of safety shall not be


less than 1.5 under the most adverse tidal
conditions and maximum live loading, while
for earthquake with one third of live load in
place the factor of safety shall not be less
than 1.1.

(iii) Settlement

In designing the causeway works, the


Contractor shall:

o calculate the settlement which will


occur in the short term (1-3 months), at
1, 2 and 5 years, and the total
settlement expected;

o assess the pore pressures likely to be


generated and determine a method of
controlling these pore pressures such
that the specified minimum factors of
safety are maintained at all times.

The Contractor shall design and install a


minimum 3m long transition slab between the
trestle and the head of the causeway to
maintain traffic access. The slab shall be
constructed of reinforced concrete and
provided with lifting eyes to allow
readjustment.

9.3.7 Fenders

Fenders, their frontal frames, and appurtenances,


shall be designed to safely withstand and absorb at
least the forces and berthing energies defined in
Section 9.3.4(vi), as well as the effects of:

o angular approach of vessels,

o variations in vessel size and tidal levels at


time of berthing,

o shear distortion of fenders, and

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 44 of 50

o variation in the nominal design properties of


fender material.

In addition, the frontal frame of the fenders shall


project below the deck of a laden ship of 25,000 DWT
berthing at lowest astronomical tide.

9.3.8 Navigation Beacons and Buoys

The type, number and locations of navigational aids,


including beacons, buoys, leading lights, channel
markers, daymarks and land fall mark shall be in
accordance with Project Specification MA1.

These navigational aids, their fittings and


attachments shall be designed to safely withstand
the environmental loads given in section 9.3.2, the
dead load arising from batteries, solar cell arrays,
lamps, daymarks and ladders, and, for navigational
aids located at sea: the berthing loads from a 50
tonne displacement vessel berthing at 0.3m/second
against the structure in normal environmental
conditions.

9.3.9 Cover to Reinforcement

The cover to steel reinforcement for all marine


concrete structures shall be as follows:

- In-situ beams, soffit and sides 75mm


- In-situ slabs, top 60mm
- In-situ slabs, sides and soffit 65mm
- Precast slabs 65mm
- Pile caps 75mm
- Elsewhere 75mm

9.4 DESIGN LOAD COMBINATIONS AND FACTORS

Combinations of loads calculated in accordance with Section


9.3 shall be multiplied by the load factor stated in
Attachment D.

Structures shall be checked for both service and ultimate


limit states.

Where alternative maximum and minimum factors are given for


imposed loads, the ultimate limit state shall be checked for
each alternative - ie. all minimum factors in combination
and all maximum factors in combination. The minimum factors
generally will relate to ultimate loads in tension piles and
similar effects.

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 45 of 50

ATTACHMENT A

LIST OF STANDARDS

AND REFERENCE DOCUMENTS

[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 46 of 50

CODES AND STANDARDS

NI 2 Indonesian Reinforced Concrete Code

NI 18 Indonesian Loading Code, Chapters 1 to 4 inclusive


and Chapter 6.

AS1170 SAA Loading Code

AS1221 Fire Hose Reels

AS1250 SAA Steel Structures Code

AS1302 Steel Reinforcing Bars for Concrete

AS1418 SAA Crane Code

AS1475 SAA Blockwork Code

AS1504 SAA Formwork Code

AS1511 SAA High Strength Structural Bolting Code

AS1523 Elastomeric Bearings for use in Structures

AS1538 SAA Cold-formed Steel Structures Code

AS1554 SAA Structural Steel Welding Code

AS1657 SAA Code for Fixed Platforms, Walkways, Stairways


and Ladders

AS1720 SAA Timber Engineering Code

AS2121 SAA Earthquake Code

AS2159 SAA Piling Code

AS2200 Design Charts for Water Supply and Sewerage

AS2419 Installation of Fire Hydrants

AS3600-1988 SAA Concrete Structures Code

MA1 SAA Manual on Steel Structures


Section MA1.8: Fabrication
Section MA1.9: Erection

BS5337 Code of Practice for the Structural Use of Concrete


for Retaining Aqueous Liquids
BS6349 Code of Practice for Maritime Structures
[70/KPCCOAL2]
STANDARD SPECIFICATION NO. KPC-C-01
REVISION 4 Sheet 47 of 50

Part 1: General Criteria


Part 4: Design of Fendering and Mooring Systems

BS8004 Code of Practice for Foundations

ISO5049 Mobile Continuous Bulk Handling Equipment


Part 1: Rules for the Calculation of Frameworks

REFERENCE DOCUMENTS

1. Indonesian Earthquake Study, by Beca Carter, Hollings &


Ferner Ltd. and the Indonesian Counterpart Team

Volume 5: Draff Code of Practice for Seismic Design of


Building in Indonesia.

2. NAASRA: Bridge Design Specification

[70/KPCCOAL2]

You might also like