Basement Presentation
Basement Presentation
Basement Presentation
No basement shall be constructed within the prescribed setbacks and prescribed building lines and
shall not exceed in area the maximum
coverage of floor 1 (entrance floor):
(e) The walls and floor of the basement shall be water-tight and be so designed
that the effect of surrounding soil and moisture , if any, are taken into account in design
and adequate damp roofing treatment is given.
(f) The access to the basement shall be separate from the main and alternate
staircase providing access and exit from higher floors. Where the staircase is
continuous in case of building served by more than one staircase the same shall be of
enclosed type serving as a fire separation from the basement floor and higher floors.
Open ramps shall be permitted if they are constructed within the building line
BASEMENTS IN PRACTISE
BASEMENTS IN PRACTISE
STAIRCASE AND LIFTS FOR BASEMENTS
In case of single staircase it shall terminate at the ground floor level and the access
to the basement shall be by a separate staircase.
Wherever the building is served by more than one staircase one of the staircases may
lead to basement level provided the same is separated at ground level by either a ventilated
lobby or a out off screen wall without opening having a fire resistance of not less than
2 hours with discharge point at two different ends or through enclosures.
It shall also be cut-off from the basement area at various basement levels by a protected
and ventilated lobby/lobbies.
The staircase shall be lighted and ventilated and the minimum size of opening on walls
abutting to open spaces shall be 0.3 sq.m. per landing.
Lift shall not normally communicate with the basement. However, one of the lifts
may be permitted to basement level is pressurised and separated from the best of the basement
areas, by smoke actuated fire resisting door of two hours fire resistance.
These doors can also be kept in hold-open position by an Electromagnet devise to be linked
with smoke detector.
FIRE PROTECTION FOR BASEMENTS
Each basement shall be separately ventilated. Vents with cross sectional area
(aggregate )not less than 2.5% of the floor area spread evenly round the perimeter of
the basement and shall be provided in the form of grills or breakable stall boards lights
or pavement light or by way of shafts.
Alternatively, a system of air inlets shall be provided at basement floor level and smoke
outlets at basements ceiling level. Inlets and extracts may be terminated at ground
level with stall boards or pavement lights as before but ducts to convey fresh air to the
basement floor level have to be laid.
Stall-boards and pavement lights should be in positions easily accessible to the Fire
Brigade and clearly marked “SMOKE OUTLET” or “AIR INLET” with an indication of
area severed at or near the opening.
In multi-storeys basements, intake ducts may serve all basement levels but each basement and
compartment shall have separate smoke outlet duct or ducts.
Mechanical extractors for smoke venting system from lower basement levels shall also be
provided. The system shall be of such design as to operate on actuation of heat sensitive detector
of sprinklers if installed and shall have the standard units.
It should also have an arrangement to start it manually and shall be designed to function at a
temperature not less than 50ºC.
Kitchens working on gas fuel, departmental stores, and shops shall not be permitted in basement/
sub-basement.
FIRE PROTECTION FOR BASEMENTS
FIRE PROTECTION FOR BASEMENTS
Transformers :
a) If transformers are housed in the building below the ground level it shall be necessarily in the first
basement in separate fire resisting room of 4 hours rating.
The rooms shall necessarily be at the periphery of the basement. The entrance to the room shall be
provided with a steel door of 2 hours fire rating.
A curb (sill) of a suitable height shall be provided at the entrance in order to prevent the flow
of oil from ruptured transformer into other parts of the basement. The direct access to the transformer
room shall be provided preferably from outside. The switch gears shall be housed in a separate room
separated from the transformer bays by a fire resisting wall with fire resistance not less than four
hours.
b) The transformer if housed in basement shall be protected by an automatic high pressure water
spray system (Mulsifyre System).
c) In case the transformer housed in the basements totally segregated from other area of the
basements by 4 hours fire resisting wall/walls with an access directly from outside it may be protected
by carbon-dioxide or B.C.F. fixed installation system.
RAMPS FOR BASEMENTS
(a) Ramps with as slope of not more than 1 to 10 may be substituted for and
shall c omply with all this applicable requirements of required stairways as to enclosure,
Capacity and limited dimensions, Ramps shall be surfaced with approved non-slipping material.
Provided that in the case of public office, hospitals,assembly halls etc. the slope of the ramp shall not
be more than 1 in 12.
In the case of parking spaces provided in basement at least two ramps of adequate width and slope
(not less than 1:8 or more than 1:12) shall be provided, located preferably at opposite ends.
WATERPROOFING FOR BASEMENTS
WATERPROOFING FOR BASEMENTS
WATERPROOFING FOR BASEMENTS
WATERPROOFING FOR BASEMENTS
WATERPROOFING FOR BASEMENTS
UPLIFT WATER PRESSURE IN BASEMENT
BASEMENT SECTION