PICKUP - Vip 400
PICKUP - Vip 400
PICKUP - Vip 400
The other possible phase protection settings are common to both setting groups (harmonic 2 restraint,
reset time, phase Cold Load Pick-Up). Setting group A applies by default.
The setting groups can be switched:
from the keypad on the front panel. Refer to the Use section (see page 39).
from the communication interface via a remote control order. Refer to the Communication section
(see page 143).
72 NRJED311206EN 03/2013
VIP400, VIP410 - Functions and Parameters
Settings
NOTE:
In is the phase CT primary rated current:
In = 200 A for the CUa sensors
In = 630 A for the CUb sensors
NOTE: The INST setting for the Io>> set point can only be accessed if the VIP is configured without a
minimum tripping time. This parameter setting is defined by customizing the VIP associated with the
circuit breaker (see page 137).
NRJED311206EN 03/2013 73
VIP400, VIP410 - Functions and Parameters
I
extrait de CT192
t
I(t) = I(0).e t
Measurement of the VIP currents is not affected by the presence of an aperiodic component (50 Hz or
60 Hz), which allows a significant reduction in the ANSI 51 protection function settings.
In instantaneous protection (ANSI 50), the I>>> set point should be set to at least 37% of the peak value
of the inrush current stated by the transformer manufacturer.
With delayed protection (ANSI 51), the same rule applies, taking account of the current attenuation
according to the time constant stated by the transformer manufacturer.
If the protection plan requirements impose settings that do not comply with the above rules, it is advisable
to activate the phase protection harmonic 2 restraint.
74 NRJED311206EN 03/2013