Rated Windows Atria Window Sprinklers - A Comparison Chart
Rated Windows Atria Window Sprinklers - A Comparison Chart
Rated Windows Atria Window Sprinklers - A Comparison Chart
CODE REFERENCES
APPLICATION RATED WINDOWS CLOSELY-SPACED FOR ATRA TYCO WS SPRINKLERS
Fire Partitions (IBC 708), Fire
In lieu of Atrium 1-hour Enclosure Barrier (IBC 707), or Exterior
Where Applied? Fire Partitions & Fire Barriers [IBC 2000-06 404.5, 2009-18 404.6, Wall (IBC 705) for up to 2-hour
or NFPA 101 2003-18 8.6.7(c)] fire-resistance rating
[ICC-ES ESR-2397 3.1, 5.3]
No. Yes; alternate method.
Alternative to Code? No; rated glazing can meet
[IBC 2000-06 404.5, [IBC 2003-18 104.11]
Requires AHJ prescriptive code
2009-18 404.6, [ICC-ES ESR-2397 3.3]
Approval? requirements.
or NFPA 101 2003-18 8.6.7(c)] [NFPA 101 2003-18 1.4.3]
Supporting ICC-ES ESR-2397 Report
- -
Documentation [ICC-ES Link]
Building Code
Yes. Yes. N/A
Criteria Apply?
No. Yes.
NFPA 13 Criteria
N/A [NFPA 13 2016 A.8.15.26(3), 2019 [NFPA 13 2016 A.8.15.26(3),
Apply?
A.9.3.15(3)] 2019 A.9.3.15(3)]
IBC 2006: 5-ft (1524 mm) min
Fire Separation
IBC 2009-15: 10-ft (3048 mm)
Distance for Exterior N/A N/A
min.
Wall Use
[ICC-ES ESR-2397 5.7]
No.
No.
In Lieu of Firewall? - [IBC 2000-06 404.5, 2009-18 404.6,
[ICC-ES ESR-2397 5.9]
or NFPA 101 2003-18 8.6.7(c)]