MiCOM P741

Numerical Busbar Protection


Software Version D2.2, D2.3 and D2.5
Hardware Version K

PICS & MICS

P741/EN PM/I75
Note: The technical manual for this device gives instructions for its installation, commissioning, and
operation. However, the manual cannot cover all conceivable circumstances or include detailed
information on all topics. In the event of questions or specific problems, do not take any action
without proper authorization. Contact the appropriate AREVA technical sales office and request
the necessary information.

Any agreements, commitments, and legal relationships and any obligations on the part of AREVA
including settlements of warranties, result solely from the applicable purchase contract, which is
not affected by the contents of the technical manual.

This device MUST NOT be modified. If any modification is made without the express permission of
AREVA, it will invalidate the warranty, and may render the product unsafe.

The AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.

MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered
or not, are the property of their owners.

This manual is provided for informational use only and is subject to change without notice.

© 2008, AREVA. All rights reserved.


PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 1

CONTENTS

1. PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS) .........3

1.1 INTRODUCTION ....................................................................................................3

1.2 ACSI BASIC CONFORMANCE STATEMENT ...............................................................3

1.3 ACSI MODELS CONFORMANCE STATEMENT ...........................................................4

1.4 ACSI SERVICE CONFORMANCE STATEMENT ...........................................................5

2. MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) ................9

2.1 INTRODUCTION ....................................................................................................9

2.2 OBJECTIVE ..........................................................................................................9

2.3 LOGICAL DEVICE DEFINITIONS...............................................................................9

2.4 LOGICAL NODE DEFINITIONS ...............................................................................12

2.5 COMMON DATA CLASS DEFINITIONS ....................................................................21

2.6 COMMON DATA ATTRIBUTE TYPE DEFINITIONS ......................................................26

2.7 ENUMERATED TYPE DEFINITIONS.........................................................................26

2.8 MMS DATA-TYPE CONVERSIONS .........................................................................28


P741/EN PM/I75 PICS & MICS

(PM) 2 MiCOM P741


PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 3

1. PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS)

1.1 Introduction
This specification is the Protocol Implementation Conformance Statement (PICS) and
presents the ACSI conformance statements as defined in Annex A of Part 7-2 of the
IEC61850 standard specifications.
1.2 ACSI basic conformance statement
The basic conformance statement shall be as defined in Table A.1.
Table A.1 - Basic conformance statement

Client/ Server/ Value/


Subscriber Publisher Comments

Client-Server Roles

B11 Server side ⎯ ⎯ c1 Y


(of TWO-PARTY-APPLICATION-ASSOCIATION)
B12 Client side c1 N ⎯ ⎯
(of TWO-PARTY-APPLICATION-ASSOCIATION)

SCSMs Supported

B21 SCSM: IEC 61850-8-1 used N Y


B22 SCSM: IEC 61850-9-1 used N N
B23 SCSM: IEC 61850-9-2 used N N
B24 SCSM: Other

Generic Substation Event Model (GSE)

B31 Publisher side ⎯ ⎯ O Y


B32 Subscriber side O Y ⎯ ⎯

Transmission of Sampled Value Model (SVC)

B41 Publisher side ⎯ ⎯ O N


B42 Subscriber side O N ⎯ ⎯
c1 - Shall be ‘M’ if support for LOGICAL-DEVICE model has been declared
O - Optional
M - Mandatory
Y - Yes (supported)
N - No (not supported)
P741/EN PM/I75 PICS & MICS

(PM) 4 MiCOM P741

1.3 ACSI models conformance statement


The ACSI models conformance statement shall be as defined in Table A.2.
Table A.2 - ACSI models conformance statement

Client/ Server/ Value/


Subscriber Publisher Comments

If Server Side (B1) Supported

M1 Logical device c2 N c2 Y
M2 Logical node c3 N c3 Y
M3 Data c4 N c4 Y
M4 Data set c5 N c5 Y
M5 Substitution O N O N
M6 Setting group control O N O N
Reporting
M7 Buffered report control O N O N
M7-1 sequence-number
M7-2 report-time-stamp
M7-3 reason-for-inclusion
M7-4 data-set-name
M7-5 data-reference
M7-6 buffer-overflow
M7-7 entryID
M7-8 BufTim
M7-9 IntgPd
M7-10 GI
M8 Unbuffered report control O N O Y
M8-1 sequence-number N Y
M8-2 report-time-stamp N Y
M8-3 reason-for-inclusion N Y
M8-4 data-set-name N Y
M8-5 data-reference N Y
M8-6 BufTim N Y
M8-7 IntgPd N Y
M8-8 GI N Y
Logging O N O N
M9 Log control O N O N
M9-1 IntgPd N N
M10 Log O N O N
M11 Control M N M N

If GSE (B31/32) is Supported

GOOSE O Y O Y
M12-1 entryID N N
M12-2 dataRefInc N N
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 5

Client/ Server/ Value/


Subscriber Publisher Comments
M13 GSSE O N O N

If SVC (41/42) is Supported

M14 Multicast SVC O N O N


M15 Unicast SVC O N O N
M16 Time M Y M N Time source
with required
accuracy shall
be available
M17 File Transfer O N O Y
c2 - Shall be ‘M’ if support for LOGICAL-NODE model has been declared
c3 - Shall be ‘M’ if support for DATA model has been declared
c4 - Shall be ‘M’ if support for DATA-SET, Substitution, Report, Log Control, or Time model has been
declared
c5 - Shall be ‘M’ if support for Report, GSE, or SMV models has been declared

1.4 ACSI service conformance statement


The ACSI service conformance statement shall be as defined in Table A.3 (depending on the
statements in Table A.1).
Table A.3 - ACSI service conformance statement

AA: Client/ Server/


Services Comments
TP/MC Subscriber Publisher
Server (clause 6)
S1 ServerDirectory TP N M Y

Application association (clause 7)


S2 Associate M N M Y
S3 Abort M N M Y
S4 Release M N M Y

Logical device (clause 8)


S5 LogicalDeviceDirectory TP M N M Y

Logical node (clause 9)


S6 LogicalNodeDirectory TP M N M Y
S7 GetAllDataValues TP O N M Y

Data (clause 10)


S8 GetDataValues TP M N M Y
S9 SetDataValues TP O N O Y
S10 GetDataDirectory TP O N M Y
S11 GetDataDefinition TP O N M Y
P741/EN PM/I75 PICS & MICS

(PM) 6 MiCOM P741

AA: Client/ Server/


Services Comments
TP/MC Subscriber Publisher
Data set (clause 11)
S12 GetDataSetValues TP O N M Y
S13 SetDataSetValues TP O N O N
S14 CreateDataSet TP O N O N
S15 DeleteDataSet TP O N O N
S16 GetDataSetDirectory TP O N O Y

Substitution (clause 12)


S17 SetDataValues TP M N M N

Setting group control (clause 13)


S18 SelectActiveSG TP O N O N
S19 SelectEditSG TP O N O N
S20 SetSGValues TP O N O N
S21 ConfirmEditSGValues TP O N O N
S22 GetSGValues TP O N O N
S23 GetSGCBValues TP O N O N

Reporting (clause 14)


Buffered report control block (BRCB)
S24 Report TP c6 N c6 N
S24-1 data-change (dchg)
S24-2 qchg-change (qchg)
S24-3 data-update (dupd)
S25 GetBRCBValues TP c6 N c6 N
S26 SetBRCBValues TP c6 N c6 N
Unbuffered report control block (URCB)
S27 Report TP c6 N c6 Y
S27-1 data-change (dchg) N Y
S27-2 qchg-change (qchg) N N
S27-3 data-update (dup N N
S28 GetURCBValues TP c6 N c6 Y
S29 SetURCBValues TP c6 N c6 Y
c6 - Shall declare support for at least one (BRCB or URCB)

Logging (clause 14)


Log control block
S30 GetLCBValues TP M N M N
S31 SetLCBValues TP O N M N
Log
S32 QueryLogByTime TP c7 N M N
S33 QueryLogAfter TP c7 N M N
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 7

AA: Client/ Server/


Services Comments
TP/MC Subscriber Publisher
S34 GetLogStatusValues TP M N M N
c7 - Shall declare support for at least one (QueryLogByTime or QueryLogByEntry)

Generic substation event model (GSE) (clause 14.3.5.3.4)


GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage MC c8 N c8 Y
S36 GetGoReference TP O N c9 Y
S37 GetGOOSEElementNumber TP O N c9 Y
S38 GetGoCBValues TP O N O N
S39 SetGoCBValues TP O N O N
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage MC c8 N c8 N
S41 GetGsReference TP O N c9 N
S42 GetGSSEElementNumber TP O N c9 N
S43 GetGsCBValues TP O N O N
S44 SetGsCBValues TP O N O N
c8 - Shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage)
c9 - Shall declare support if TP association is available

Transmission of sampled value model (SVC) (clause 16)


Multicast SVC
S45 SendMSVMessage MC c10 N c10 N
S46 GetMSVCBValues TP O N O N
S47 SetMSVCBValues TP O N O N
Unicast SVC
S48 SendUSVMessage TP c10 N c10 N
S49 GetUSVCBValues TP O N O N
S50 SetUSVCBValues TP O N O N
c10 - Shall declare support for at least one (SendMSVMessage or SendUSVMessage)

Control (clause 17.5.1)


S51 Select M N O N
S52 SelectWithValue TP M N O N
S53 Cancel TP O N O N
S54 Operate TP M N M N
S55 Command-Termination TP M N O N
S56 TimeActivated-Operate TP O N O N

File transfer (clause 20)


S57 GetFile TP O N M Y
S58 SetFile TP O N O N
S59 DeleteFile TP O N O Y
P741/EN PM/I75 PICS & MICS

(PM) 8 MiCOM P741

AA: Client/ Server/


Services Comments
TP/MC Subscriber Publisher
S60 GetFileAttributeValues TP O N M Y

Time (5.5)
T1 Time resolution of internal clock 1ms Nearest
negative power
of 2 in seconds
T2 Time accuracy of internal clock 1ms T0
T1
T2
T3
T4
T5
T3 Supported TimeStamp resolution 1ms Nearest value
of 2**-n in
seconds
according to
5.5.3.7.3.3
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 9

2. MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)

2.1 Introduction
This specification is the Model Implementation Conformance Statement (MICS) and presents
the top-level IEC61850 data model that has been implemented. The definitions of all used
Logical Nodes and their associated Common Data Classes, components and associated
enumerated values are also included for completeness.
The reader is expected to be conversant with the terminology presented within the IEC61850
part 7 series of specifications.

2.2 Objective
To provide comprehensive details of the standard data object model elements supported by
the device. The MICS is conformant to the devices associated ICD (Substation Configuration
Language) file, according to part 6 of the IEC61850 standards. The layout of the presented
tables within this document are conformant to the part 7 series of the IEC61850 standard
specifications with the following exceptions:

• The "Trigger Options" field is not presented.

• The "M/O" field is not present as the definitions are as deployed within the model.

• An additional column "X" is used to signify AREVA custom attributes.

2.3 Logical Device definitions


The MiCOM relay implements an IEC61850 server that can contain one or more Logical
Devices. Each Logical Device contains a data model built from instances of specific Logical
Nodes and must consist of at least an instance of the LPHD Logical Node (which is
responsible for providing physical device information) and an instance of the LLN0 Logical
Node (for addressing common issues across the Logical Device).
The IEC61850 data model is contained within the Logical Devices detailed in the table
below. All MiCOM devices will name the supported Logical Devices consistently to ensure
that data model variables with the same purpose will have the same name within each
MiCOM server.

Logical Device Comment / Usage


Protection Protection Elements
Records Recording Data
System Global System Data
2.3.1 IEC61850 Logical Device data model
The IEC61850 Logical Device top-level data model consists of instances of Logical Nodes.
The data model name for a Logical Node instance is constructed from an optional prefix
(known as the wrapper), the Logical Node name, and an instance ID (or suffix).
The presented data model is in an alphabetically sorted order, rather than a logical order,
because this is the natural order of the data when presented by a native MMS browser.
(Higher level browsers can of course impart any ordering that they desire.)
P741/EN PM/I75 PICS & MICS

(PM) 10 MiCOM P741

LD LN Instance LN Type Description


Protection
CftCzNPDIF1 PDIF_NEU P740 : circuitry fault for SEF check zone
CftCzPPDIF1 PDIF_STR_OP_SEG P740 : circuitry fault supervision for each phase of the
check zone
CftPhsPDIF1 PDIF_STR_OP_SEG Differential phase protection : Circuitry fault supervision
for each phase of the zone 1
CftPhsPDIF2 PDIF_STR_OP_SEG Differential phase protection : Circuitry fault supervision
for each phase of the zone 2
CftPhsPDIF3 PDIF_STR_OP_SEG Differential phase protection : Circuitry fault supervision
for each phase of the zone 3
CftPhsPDIF4 PDIF_STR_OP_SEG Differential phase protection : Circuitry fault supervision
for each phase of the zone 4
CftPhsPDIF5 PDIF_STR_OP_SEG Differential phase protection : Circuitry fault supervision
for each phase of the zone 5
CftPhsPDIF6 PDIF_STR_OP_SEG Differential phase protection : Circuitry fault supervision
for each phase of the zone 6
CftPhsPDIF7 PDIF_STR_OP_SEG Differential phase protection : Circuitry fault supervision
for each phase of the zone 7
CftPhsPDIF8 PDIF_STR_OP_SEG Differential phase protection : Circuitry fault supervision
for each phase of the zone 8
CftSefPDIF1 PDIF_NEU P740 : circuitry fault for SEF zone 1
CftSefPDIF2 PDIF_NEU P740 : circuitry fault for SEF zone 2
CftSefPDIF3 PDIF_NEU P740 : circuitry fault for SEF zone 3
CftSefPDIF4 PDIF_NEU P740 : circuitry fault for SEF zone 4
CftSefPDIF5 PDIF_NEU P740 : circuitry fault for SEF zone 5
CftSefPDIF6 PDIF_NEU P740 : circuitry fault for SEF zone 6
CftSefPDIF7 PDIF_NEU P740 : circuitry fault for SEF zone 7
CftSefPDIF8 PDIF_NEU P740 : circuitry fault for SEF zone 8
FltCzNPDIF1 PDIF_FLT_CZ_SEF P740 : SEF check zone fault
FltCzPPDIF1 PDIF_OP_SEG_NO_STR P740 : Fault on the check zone for each phase
LLN0 LLN0_PROT_P741 Protection Logical Device for P741
LPHD1 LPHD_STANDARD Physical Device Information
TrpCupPTRC1 PTRC_CU_TRIP P740 : central trip zone 1
TrpCupPTRC2 PTRC_CU_TRIP P740 : central trip zone 2
TrpCupPTRC3 PTRC_CU_TRIP P740 : central trip zone 3
TrpCupPTRC4 PTRC_CU_TRIP P740 : central trip zone 4
TrpCupPTRC5 PTRC_CU_TRIP P740 : central trip zone 5
TrpCupPTRC6 PTRC_CU_TRIP P740 : central trip zone 6
TrpCupPTRC7 PTRC_CU_TRIP P740 : central trip zone 7
TrpCupPTRC8 PTRC_CU_TRIP P740 : central trip zone 8
TrpNeuPDIF1 PDIF_TRP_NEU P740 : Trip zone 1 for SEF
TrpNeuPDIF2 PDIF_TRP_NEU P740 : Trip zone 2 for SEF
TrpNeuPDIF3 PDIF_TRP_NEU P740 : Trip zone 3 for SEF
TrpNeuPDIF4 PDIF_TRP_NEU P740 : Trip zone 4 for SEF
TrpNeuPDIF5 PDIF_TRP_NEU P740 : Trip zone 5 for SEF
TrpNeuPDIF6 PDIF_TRP_NEU P740 : Trip zone 6 for SEF
TrpNeuPDIF7 PDIF_TRP_NEU P740 : Trip zone 7 for SEF
TrpNeuPDIF8 PDIF_TRP_NEU P740 : Trip zone 8 for SEF
TrpPhsPDIF1 PDIF_STR_SEG_OP_NOS Differential phases protection : Trip zone 1 for the three
EG phases.
TrpPhsPDIF2 PDIF_STR_SEG_OP_NOS Differential phases protection : Trip zone 2 for the three
EG phases.
TrpPhsPDIF3 PDIF_STR_SEG_OP_NOS Differential phases protection : Trip zone 3 for the three
EG phases.
TrpPhsPDIF4 PDIF_STR_SEG_OP_NOS Differential phases protection : Trip zone 4 for the three
EG phases.
TrpPhsPDIF5 PDIF_STR_SEG_OP_NOS Differential phases protection : Trip zone 5 for the three
EG phases.
TrpPhsPDIF6 PDIF_STR_SEG_OP_NOS Differential phases protection : Trip zone 6 for the three
EG phases.
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 11

LD LN Instance LN Type Description


Protection
TrpPhsPDIF7 PDIF_STR_SEG_OP_NOS Differential phases protection : Trip zone 7 for the three
EG phases.
TrpPhsPDIF8 PDIF_STR_SEG_OP_NOS Differential phases protection : Trip zone 8 for the three
EG phases.
TrpPhsRBRF1 RBRF_87BB_TRIP_PHS P740 : central breaker failure busbar 1
TrpPhsRBRF2 RBRF_87BB_TRIP_PHS P740 : central breaker failure busbar 2
TrpPhsRBRF3 RBRF_87BB_TRIP_PHS P740 : central breaker failure busbar 3
TrpPhsRBRF4 RBRF_87BB_TRIP_PHS P740 : central breaker failure busbar 4
TrpPhsRBRF5 RBRF_87BB_TRIP_PHS P740 : central breaker failure busbar 5
TrpPhsRBRF6 RBRF_87BB_TRIP_PHS P740 : central breaker failure busbar 6
TrpPhsRBRF7 RBRF_87BB_TRIP_PHS P740 : central breaker failure busbar 7
TrpPhsRBRF8 RBRF_87BB_TRIP_PHS P740 : central breaker failure busbar 8
Records
LLN0 LLN0_STANDARD Records Logical Device
LPHD1 LPHD_STANDARD Physical Device Information
RDRE1 RDRE_BASIC Disturbance Recorder
System
AlmGGIO1 GGIO_ALM_96 Alarms
CbfOrdGGIO1 GGIO_IND_16 P740 : 50BF order from PU and opto
FnkGGIO1 GGIO_IND_10 Function Keys
GosGGIO1 GGIO_IND_32 GOOSE Input Signals
GosGGIO2 GGIO_IND_32 GOOSE Output Signals
LckCbfGGIO1 GGIO_IND_8_WD Breaker Failure protection locked on the CU for each
zone
LckDifGGIO1 GGIO_IND_8_WD 87BB differential protection locked for each zone
LedGGIO1 GGIO_IND_18 Red LED Signals
LedGGIO2 GGIO_IND_18 Green LED Signals
LLN0 LLN0_STANDARD System Logical Device
LPHD1 LPHD_STANDARD Physical Device Information
OptGGIO1 GGIO_IND_8 P740 : Opto Inputs CU
OptVirGGIO1 GGIO_IND_16_WD P740 : virtual opto
PloGGIO1 GGIO_IND_32 PSL Control Inputs
PueAlmGGIO GGIO_IND_8_WD Alarm PU Error for each zone
1
PueLckGGIO1 GGIO_IND_8_WD Locking PU Error for each zone
RlyGGIO1 GGIO_IND_8 P740 : Outputs Contacts CU
RlyVirGGIO1 GGIO_IND_16_WD P740 : virtual relay
TrpManGGIO1 GGIO_IND_8_WD P740 : Manual trip order
P741/EN PM/I75 PICS & MICS

(PM) 12 MiCOM P741

2.4 Logical Node definitions


The definition tables for each of the Logical Nodes in the top-level data model are presented
in the following sub-sections.
The following table presents a summary of the Logical Node templates used across the
Logical Devices within the overall IEC61850 product data model:
LN Type (LN Class) Description Name Space
GGIO_IND_10 (GGIO) Generic Process I/O (w.r.t 10 Indication Elements) IEC61850-7-4:2003
GGIO_IND_16 (GGIO) Generic process I/O IEC61850-7-4:2003
GGIO_IND_16_WD (GGIO) Generic process I/O IEC61850-7-4:200
GGIO_IND_18 (GGIO) Generic Process I/O (w.r.t 18 Indication Elements) IEC61850-7-4:2003
GGIO_IND_32 (GGIO) Generic Process I/O (w.r.t 32 Indication Elements) IEC61850-7-4:2003
GGIO_IND_8 (GGIO) Generic process I/O IEC61850-7-4:2003
GGIO_IND_8_WD (GGIO) Generic process I/O IEC61850-7-4:2003
GGIO_ALM_96 (GGIO) Generic Process I/O (w.r.t 96 Alarm Elements) IEC61850-7-4:2003
LLN0_STANDARD (LLN0) General Logical Node 0 IEC61850-7-4:2003
LLN0_PROT_P741 (LLN0) Protection Domain Logical Node 0 for P741 AREVA-SII:PCS-Px40
LPHD_STANDARD (LPHD) Px40 Physical Device Information IEC61850-7-4:2003
PDIF_FLT_CZ_SEF (PDIF) Differential AREVA-SII:PCS-Px40
PDIF_NEU (PDIF) Differential (w.r.t Neutral) IEC61850-7-4:2003
PDIF_OP_SEG_NO_STR (PDIF) Differential AREVA-SII:PCS-Px40
PDIF_STR_OP_SEG (PDIF) Differential IEC61850-7-4:2003
PDIF_STR_SEG_OP_NO (PDIF) Differential AREVA-SII:PCS-Px40
SEG
PDIF_TRP_NEU (PDIF) Differential AREVA-SII:PCS-Px40
PTRC_CU_TRIP (PTRC) Protection trip conditioning IEC61850-7-4:2003
RBRF_87BB_TRIP_PHS (RBRF) Breaker Failure IEC61850-7-4:2003

RDRE_BASIC (RDRE) Disturbance Recorder function (w.r.t Mandatory IEC61850-7-4:2003


Attributes only)
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 13

2.4.1 Logical Node: GGIO_ALM_96

Description: Generic Process I/O (w.r.t 96 Alarm Elements)


LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Alm1 SPS_D General single alarm
Alm2 SPS_D General single alarm
Alm3 SPS_D General single alarm
Alm4 SPS_D General single alarm
Alm5 SPS_D General single alarm
Alm6 SPS_D General single alarm
Alm7 SPS_D General single alarm
Alm8 SPS_D General single alarm
Alm9 SPS_D General single alarm
Alm10 SPS_D General single alarm
Alm11 SPS_D General single alarm
Alm12 SPS_D General single alarm
Alm13 SPS_D General single alarm
Alm14 SPS_D General single alarm
Alm15 SPS_D General single alarm
Alm16 SPS_D General single alarm
Alm17 SPS_D General single alarm
Alm18 SPS_D General single alarm
Alm19 SPS_D General single alarm
Alm20 SPS_D General single alarm
Alm21 SPS_D General single alarm
Alm22 SPS_D General single alarm
Alm23 SPS_D General single alarm
Alm24 SPS_D General single alarm
Alm25 SPS_D General single alarm
Alm26 SPS_D General single alarm
Alm27 SPS_D General single alarm
Alm28 SPS_D General single alarm
Alm29 SPS_D General single alarm
Alm30 SPS_D General single alarm
Alm31 SPS_D General single alarm
Alm32 SPS_D General single alarm
Alm33 SPS_D General single alarm
Alm34 SPS_D General single alarm
Alm35 SPS_D General single alarm
Alm36 SPS_D General single alarm
Alm37 SPS_D General single alarm
Alm38 SPS_D General single alarm
Alm39 SPS_D General single alarm
Alm40 SPS_D General single alarm
Alm41 SPS_D General single alarm
Alm42 SPS_D General single alarm
Alm43 SPS_D General single alarm
P741/EN PM/I75 PICS & MICS

(PM) 14 MiCOM P741

Attribute Attr. Type Explanation T X


Alm44 SPS_D General single alarm
Alm45 SPS_D General single alarm
Alm46 SPS_D General single alarm
Alm47 SPS_D General single alarm
Alm48 SPS_D General single alarm
Alm49 SPS_D General single alarm
Alm50 SPS_D General single alarm
Alm51 SPS_D General single alarm
Alm52 SPS_D General single alarm
Alm53 SPS_D General single alarm
Alm54 SPS_D General single alarm
Alm55 SPS_D General single alarm
Alm56 SPS_D General single alarm
Alm57 SPS_D General single alarm
Alm58 SPS_D General single alarm
Alm59 SPS_D General single alarm
Alm60 SPS_D General single alarm
Alm61 SPS_D General single alarm
Alm62 SPS_D General single alarm
Alm63 SPS_D General single alarm
Alm64 SPS_D General single alarm
Alm65 SPS_D General single alarm
Alm66 SPS_D General single alarm
Alm67 SPS_D General single alarm
Alm68 SPS_D General single alarm
Alm69 SPS_D General single alarm
Alm70 SPS_D General single alarm
Alm71 SPS_D General single alarm
Alm72 SPS_D General single alarm
Alm73 SPS_D General single alarm
Alm74 SPS_D General single alarm
Alm75 SPS_D General single alarm
Alm76 SPS_D General single alarm
Alm77 SPS_D General single alarm
Alm78 SPS_D General single alarm
Alm79 SPS_D General single alarm
Alm80 SPS_D General single alarm
Alm81 SPS_D General single alarm
Alm82 SPS_D General single alarm
Alm83 SPS_D General single alarm
Alm84 SPS_D General single alarm
Alm85 SPS_D General single alarm
Alm86 SPS_D General single alarm
Alm87 SPS_D General single alarm
Alm88 SPS_D General single alarm
Alm89 SPS_D General single alarm
Alm90 SPS_D General single alarm
Alm91 SPS_D General single alarm
Alm92 SPS_D General single alarm
Alm93 SPS_D General single alarm
Alm94 SPS_D General single alarm
Alm95 SPS_D General single alarm
Alm96 SPS_D General single alarm
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 15

2.4.2 Logical Node: GGIO_IND_10

Description: Generic Process I/O (w.r.t 10 Indication Elements)


LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General indication (binary input)
Ind2 SPS_D General indication (binary input)
Ind3 SPS_D General indication (binary input)
Ind4 SPS_D General indication (binary input)
Ind5 SPS_D General indication (binary input)
Ind6 SPS_D General indication (binary input)
Ind7 SPS_D General indication (binary input)
Ind8 SPS_D General indication (binary input)
Ind9 SPS_D General indication (binary input)
Ind10 SPS_D General indication (binary input)

2.4.3 Logical Node: GGIO_IND_16

Description: Generic process I/O


LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General indication (binary input)
Ind2 SPS_D General indication (binary input)
Ind3 SPS_D General indication (binary input)
Ind4 SPS_D General indication (binary input)
Ind5 SPS_D General indication (binary input)
Ind6 SPS_D General indication (binary input)
Ind7 SPS_D General indication (binary input)
Ind8 SPS_D General indication (binary input)
Ind9 SPS_D General indication (binary input)
Ind10 SPS_D General indication (binary input)
Ind11 SPS_D General indication (binary input)
Ind12 SPS_D General indication (binary input)
Ind13 SPS_D General indication (binary input)
Ind14 SPS_D General indication (binary input)
Ind15 SPS_D General indication (binary input)
Ind16 SPS_D General indication (binary input)

2.4.4 Logical Node: GGIO_IND_16_WD

Description: Generic process I/O


LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
P741/EN PM/I75 PICS & MICS

(PM) 16 MiCOM P741

Attribute Attr. Type Explanation T X


Ind1 SPS_WD General indication (binary input)
Ind2 SPS_WD General indication (binary input)
Ind3 SPS_WD General indication (binary input)
Ind4 SPS_WD General indication (binary input)
Ind5 SPS_WD General indication (binary input)
Ind6 SPS_WD General indication (binary input)
Ind7 SPS_WD General indication (binary input)
Ind8 SPS_WD General indication (binary input)
Ind9 SPS_WD General indication (binary input)
Ind10 SPS_WD General indication (binary input)
Ind11 SPS_WD General indication (binary input)
Ind12 SPS_WD General indication (binary input)
Ind13 SPS_WD General indication (binary input)
Ind14 SPS_WD General indication (binary input)
Ind15 SPS_WD General indication (binary input)
Ind16 SPS_WD General indication (binary input)

2.4.5 Logical Node: GGIO_IND_18

Description: Generic Process I/O (w.r.t 18 Indication Elements)


LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General indication (binary input)
Ind2 SPS_D General indication (binary input)
Ind3 SPS_D General indication (binary input)
Ind4 SPS_D General indication (binary input)
Ind5 SPS_D General indication (binary input)
Ind6 SPS_D General indication (binary input)
Ind7 SPS_D General indication (binary input)
Ind8 SPS_D General indication (binary input)
Ind9 SPS_D General indication (binary input)
Ind10 SPS_D General indication (binary input)
Ind11 SPS_D General indication (binary input)
Ind12 SPS_D General indication (binary input)
Ind13 SPS_D General indication (binary input)
Ind14 SPS_D General indication (binary input)
Ind15 SPS_D General indication (binary input)
Ind16 SPS_D General indication (binary input)
Ind17 SPS_D General indication (binary input)
Ind18 SPS_D General indication (binary input)

2.4.6 Logical Node: GGIO_IND_32

Description: Generic Process I/O (w.r.t 32 Indication Elements)


LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 17

Attribute Attr. Type Explanation T X


Ind1 SPS_D General indication (binary input)
Ind2 SPS_D General indication (binary input)
Ind3 SPS_D General indication (binary input)
Ind4 SPS_D General indication (binary input)
Ind5 SPS_D General indication (binary input)
Ind6 SPS_D General indication (binary input)
Ind7 SPS_D General indication (binary input)
Ind8 SPS_D General indication (binary input)
Ind9 SPS_D General indication (binary input)
Ind10 SPS_D General indication (binary input)
Ind11 SPS_D General indication (binary input)
Ind12 SPS_D General indication (binary input)
Ind13 SPS_D General indication (binary input)
Ind14 SPS_D General indication (binary input)
Ind15 SPS_D General indication (binary input)
Ind16 SPS_D General indication (binary input)
Ind17 SPS_D General indication (binary input)
Ind18 SPS_D General indication (binary input)
Ind19 SPS_D General indication (binary input)
Ind20 SPS_D General indication (binary input)
Ind21 SPS_D General indication (binary input)
Ind22 SPS_D General indication (binary input)
Ind23 SPS_D General indication (binary input)
Ind24 SPS_D General indication (binary input)
Ind25 SPS_D General indication (binary input)
Ind26 SPS_D General indication (binary input)
Ind27 SPS_D General indication (binary input)
Ind28 SPS_D General indication (binary input)
Ind29 SPS_D General indication (binary input)
Ind30 SPS_D General indication (binary input)
Ind31 SPS_D General indication (binary input)
Ind32 SPS_D General indication (binary input)

2.4.7 Logical Node: GGIO_IND_8

Description: Generic process I/O


LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General indication (binary input)
Ind2 SPS_D General indication (binary input)
Ind3 SPS_D General indication (binary input)
Ind4 SPS_D General indication (binary input)
Ind5 SPS_D General indication (binary input)
Ind6 SPS_D General indication (binary input)
Ind7 SPS_D General indication (binary input)
Ind8 SPS_D General indication (binary input)

2.4.8 Logical Node: GGIO_IND_8_WD

Description: Generic process I/O


P741/EN PM/I75 PICS & MICS

(PM) 18 MiCOM P741

LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_WD General indication (binary input)
Ind2 SPS_WD General indication (binary input)
Ind3 SPS_WD General indication (binary input)
Ind4 SPS_WD General indication (binary input)
Ind5 SPS_WD General indication (binary input)
Ind6 SPS_WD General indication (binary input)
Ind7 SPS_WD General indication (binary input)
Ind8 SPS_WD General indication (binary input)

2.4.9 Logical Node: LLN0_PROT_P741

Description: Protection Domain Logical Node 0 for P741


LN Class: LLN0
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LLN0 Name Plate
PhsDifMod INC_MODE_PRIVA phases differential protection Mode
TE
PhsDifBeh INS_BEH_PRIVATE Phases differential protection Behaviour
NeuDifMod INC_MODE_PRIVA Neutral differential protection Mode
TE
NeuDifBeh INS_BEH_PRIVATE Neutral differential protection Behaviour
PhsCftMod INC_MODE_PRIVA circuitry fault protection Mode
TE
PhsCftBeh INS_BEH_PRIVATE circuitry fault protection Behaviour
NeuCftMod INC_MODE_PRIVA neutral circuitry fault protection Mode
TE
NeuCftBeh INS_BEH_PRIVATE neutral circuitry fault protection Behaviour
BFMod INC_MODE_PRIVA Breaker failure Mode
TE
BFBeh INS_BEH_PRIVATE Breaker failure Behaviour

2.4.10 Logical Node: LLN0_STANDARD

Description: General Logical Node 0


LN Class: LLN0
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LLN0 Name Plate

2.4.11 Logical Node: LPHD_STANDARD

Description: Px40 Physical Device Information


LN Class: LPHD
Attribute Attr. Type Explanation T X
PhyNam DPL_STANDARD Physical device name plate
PhyHealth INS_HEALTH Physical device health
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 19

Attribute Attr. Type Explanation T X


Proxy SPS_D Indicates if this LN is a proxy
PwrUp SPS_D Power up detected

2.4.12 Logical Node: PDIF_FLT_CZ_SEF

Description: Differential
LN Class: PDIF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
CftBeh INS_BEH_PRIVATE Behaviour
PueBeh INS_BEH_PRIVATE Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Op ACT_NEU Operate T
DifAClc WYE_NEU Differential current
RstA WYE_NEU Restraint current

2.4.13 Logical Node: PDIF_NEU

Description: Differential (w.r.t Neutral)


LN Class: PDIF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_NEU Start
Op ACT_NEU Operate T
DifAClc WYE_NEU Differential current
RstA WYE_NEU Restraint current

2.4.14 Logical Node: PDIF_OP_SEG_NO_STR

Description: Differential
LN Class: PDIF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
CftBeh INS_BEH_PRIVATE circuitry fault blocked information
PueBeh INS_BEH_PRIVATE PU error blocked information
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Op ACT_SEG Operate T
DifAClc WYE_SEG Differential current
RstA WYE_SEG Restraint current

2.4.15 Logical Node: PDIF_STR_OP_SEG

Description: Differential
LN Class: PDIF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
P741/EN PM/I75 PICS & MICS

(PM) 20 MiCOM P741

Attribute Attr. Type Explanation T X


NamPlt LPL_LN Name Plate
Str ACD_SEG Start
Op ACT_SEG Operate T
DifAClc WYE_SEG Differential current
RstA WYE_SEG Restraint current

2.4.16 Logical Node: PDIF_STR_SEG_OP_NOSEG

Description: Differential
LN Class: PDIF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
CftBeh INS_BEH_PRIVATE Circuitry Fault Blocking
PueBeh INS_BEH_PRIVATE PU error blocking
CzBeh INS_BEH_PRIVATE Check zone confirmation
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_SEG Start
Op ACT_NO_SEG Operate T
DifAClc WYE_SEG Differential current
RstA WYE_SEG Restraint current

2.4.17 Logical Node: PDIF_TRP_NEU

Description: Differential
LN Class: PDIF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
CftBeh INS_BEH_PRIVATE circuitry fault Behaviour
PueBeh INS_BEH_PRIVATE PU Error blocking
CzBeh INS_BEH_PRIVATE Check zone status
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_NEU Start
Op ACT_NO_SEG Operate T
DifAClc WYE_NEU Differential current
RstA WYE_NEU Restraint current

2.4.18 Logical Node: PTRC_CU_TRIP

Description: Protection trip conditioning


LN Class: PTRC
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Tr ACT_NO_SEG Trip

2.4.19 Logical Node: RBRF_87BB_TRIP_PHS

Description: Breaker Failure


LN Class: RBRF
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 21

Attribute Attr. Type Explanation T X


Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
OpEx ACT_NO_SEG Breaker failure trip ("External trip") T

2.4.20 Logical Node: RDRE_BASIC

Description: Disturbance Recorder function (w.r.t Mandatory Attributes only)


LN Class: RDRE
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
RcdMade SPS_WD Recording made
FltNum INS_BASIC Fault number

2.5 Common Data Class definitions


The definition tables for each of the Common Data Classes used in the Logical Node
definitions are presented in the following sub-sections.
From an application point-of-view the data attributes of a Common Data Class are classified
according to their specific use. The characterization of data attributes, and the services that
they support/provide, will be through the use of 'Functional Constraints'. The Functional
Constraints are specified by the table below:
FC Name Semantic Source Definition
BR Buffered reports IEC61850-7-2
CF Configuration IEC61850-7-2
CO Control IEC61850-7-2
DC Description IEC61850-7-2
EX Extended Definition IEC61850-7-2
GO GOOSE Control IEC61850-7-2
GS GSSE Control (UCA2 GOOSE) IEC61850-7-2
LG Logging IEC61850-7-2
MS Multicast sampled value control IEC61850-7-2
MX Measurands (Analogue values) IEC61850-7-2
RP Unbuffered reports IEC61850-7-2
SE Setting Group Editable IEC61850-7-2
SG Setting Group IEC61850-7-2
SP Set Point IEC61850-7-2
ST Status Information IEC61850-7-2
SV Substitution Values IEC61850-7-2
US Unicast sampled value control IEC61850-7-2
XX Data attribute service parameters IEC61850-7-2

2.5.1 Common Data Class: ACD_NEU

Description: Directional Protection Activation Information (w.r.t Neutral)


CDC Class: ACD
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
dirGeneral ENUMERATED8*(MMS Type: ST dir General direction (unknown,
INT8) forward, backward or both)
neut BOOLEAN ST Trip or start event with earth
P741/EN PM/I75 PICS & MICS

(PM) 22 MiCOM P741

Attribute Type FC Enumeration Comment X


current has happened
dirNeut ENUMERATED8*(MMS Type: ST dir Earth current direction
INT8) (unknown, forward or backward)
q Quality ST Quality of the protection
activation information
t TimeStamp ST Timestamp of the last change in
state of protection activation
information

2.5.2 Common Data Class: ACD_SEG

Description: Directional Protection Activation Information (w.r.t Phase Segregation)


CDC Class: ACD
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
dirGeneral ENUMERATED8*(MMS Type: ST dir General direction (unknown,
INT8) forward, backward or both)
phsA BOOLEAN ST Trip or start event of Phase A
has happened
dirPhsA ENUMERATED8*(MMS Type: ST dir Phase A direction (unknown,
INT8) forward or backward)
phsB BOOLEAN ST Trip or start event of Phase B
has happened
dirPhsB ENUMERATED8*(MMS Type: ST dir Phase B direction (unknown,
INT8) forward or backward)
phsC BOOLEAN ST Trip or start event of Phase C
has happened
dirPhsC ENUMERATED8*(MMS Type: ST dir Phase C direction (unknown,
INT8) forward or backward)
q Quality ST Quality of the protection
activation information
t TimeStamp ST Timestamp of the last change in
state of protection activation
information

2.5.3 Common Data Class: ACT_NEU

Description: Protection Activation Information (w.r.t Neutral)


CDC Class: ACT
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
neut BOOLEAN ST Trip or start event with earth
current has happened
q Quality ST Quality of the protection
activation information
t TimeStamp ST Timestamp of the last change in
state of protection activation
information

2.5.4 Common Data Class: ACT_NO_SEG

Description: Protection Activation Information (w.r.t No Phase Segregation)


CDC Class:
ACT
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
q Quality ST Quality of the protection
activation information
t TimeStamp ST Timestamp of the last change in
state of protection activation
information
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 23

2.5.5 Common Data Class: ACT_SEG

Description: Protection Activation Information (w.r.t Phase Segregation)


CDC Class: ACT
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
phsA BOOLEAN ST Trip or start event of Phase A
has happened
phsB BOOLEAN ST Trip or start event of Phase B
has happened
phsC BOOLEAN ST Trip or start event of Phase C
has happened
q Quality ST Quality of the protection
activation information
t TimeStamp ST Timestamp of the last change in
state of protection activation
information

2.5.6 Common Data Class: CMV_MAG_FLOAT

Description: Complex Measured value (w.r.t Floating Point Magnitude)


CDC Class: CMV
Attribute Type FC Enumeration Comment X
cVal Vector_Magnitude_Float MX Deadbanded complex
measured vector. Updated to
the current value of instCVal
when the value has changed
according to the configuration
parameter db.
q Quality MX Quality of the measurement
value
t TimeStamp MX Time deadbanded magnitude
last exceeded its db
configuration parameter
units Unit_No_Multiplier CF Unit of the attribute
representing the data
db INT32U CF Measurement deadband

2.5.7 Common Data Class: DPL_STANDARD

Description: Standard Device Name Plate


CDC Class: DPL
Attribute Type FC Enumeration Comment X
vendor VISIBLE_STRING255 DC Name of the vendor
hwRev VISIBLE_STRING255 DC Hardware revision
swRev VISIBLE_STRING255 DC Software revision
serNum VISIBLE_STRING255 DC Serial Number
model VISIBLE_STRING255 DC Model Number
location VISIBLE_STRING255 DC Physical location of device

2.5.8 Common Data Class: INC_MOD

Description: Controllable Integer Status (w.r.t Mode)


CDC Class: INC
Attribute Type FC Enumeration Comment X
stVal INT32*(MMS Type: INT8) ST Mod Status value of the data
q Quality ST Quality of the status value
t TimeStamp ST Timestamp of the last change
in state of status value
ctlModel ENUMERATED8*(MMS Type: CF ctlModel Control model (Corresponding
INT8) to the behaviour of the data)
P741/EN PM/I75 PICS & MICS

(PM) 24 MiCOM P741

2.5.9 Common Data Class: INC_MODE_PRIVATE

Description: Controllable Integer Status


CDC Class: INC
Attribute Type FC Enumeration Comment X
stVal INT32*(MMS Type: INT8) ST Mod Status value of the data
q Quality ST Quality of the status value
t TimeStamp ST Timestamp of the last change
in state of status value
ctlModel ENUMERATED8*(MMS Type: CF ctlModel Control model (Corresponding
INT8) to the behaviour of the data)
dataNs VISIBLE_STRING255 EX Data name space

2.5.10 Common Data Class: INS_BASIC

Description: Integer Status (w.r.t Mandatory Options Only)


CDC Class: INS
Attribute Type FC Enumeration Comment X
stVal INT32 ST The element status
q Quality ST The quality of the status value
t TimeStamp ST Timestamp of the last change
in state

2.5.11 Common Data Class: INS_BEH

Description: Integer Status (w.r.t Behaviour)


CDC Class: INS
Attribute Type FC Enumeration Comment X
stVal INT32*(MMS Type: INT8) ST Beh The element status
q Quality ST The quality of the status value
t TimeStamp ST Timestamp of the last change in
state

2.5.12 Common Data Class: INS_BEH_PRIVATE

Description: Integer Status


CDC Class: INS
Attribute Type FC Enumeration Comment X
stVal INT32*(MMS Type: INT8) ST Beh The element status
q Quality ST The quality of the status value
t TimeStamp ST Timestamp of the last change
in state
dataNs VISIBLE_STRING255 EX Data name space

2.5.13 Common Data Class: INS_HEALTH

Description: Integer Status (w.r.t health)


CDC Class: INS
Attribute Type FC Enumeration Comment X
stVal INT32*(MMS Type: INT8) ST Health The element status
q Quality ST The quality of the status value
t TimeStamp ST Timestamp of the last change
in state

2.5.14 Common Data Class: LPL_LLN0

Description: Logical Node 0 Name Plate


PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 25

CDC Class: LPL


Attribute Type FC Enumeration Comment X
vendor VISIBLE_STRING255 DC Name of the vendor
swRev VISIBLE_STRING255 DC Software revision
d VISIBLE_STRING255 DC Description
configRev VISIBLE_STRING255 DC Uniquely identifies the
configuration of a local device
instance
ldNs VISIBLE_STRING255 EX Logical Device name space

2.5.15 Common Data Class: LPL_LN

Description: Standard Logical Node Name Plate


CDC Class: LPL
Attribute Type FC Enumeration Comment X
vendor VISIBLE_STRING255 DC Name of the vendor
swRev VISIBLE_STRING255 DC Software revision
d VISIBLE_STRING255 DC Description

2.5.16 Common Data Class: SPS_D

Description: Standard Single Point Status (with Description)


CDC Class: SPS
Attribute Type FC Enumeration Comment X
stVal BOOLEAN ST The element status (TRUE or
FALSE)
q Quality ST The quality of the status value
t TimeStamp ST Timestamp of the last change
in state
d VISIBLE_STRING255 DC Description of the status
element

2.5.17 Common Data Class: SPS_WD

Description: Single Point Status (without Description)


CDC Class: SPS
Attribute Type FC Enumeration Comment X
stVal BOOLEAN ST The element status (TRUE or
FALSE)
q Quality ST The quality of the status value
t TimeStamp ST Timestamp of the last change
in state

2.5.18 Common Data Class: WYE_NEU

Description: Phase to ground measurements (w.r.t Neutral)


CDC Class: WYE
Attribute Type FC Enumeration Comment X
neut CMV_MAG_FLOAT -- Measurement values for neutral
input

2.5.19 Common Data Class: WYE_SEG

Description: Phase to ground measurements for a 3-Phase system (w.r.t Phase Seggregation)
CDC Class: WYE
Attribute Type FC Enumeration Comment X
phsA CMV_MAG_FLOAT -- Measurement values for Phase
A
phsB CMV_MAG_FLOAT -- Measurement values for Phase
B
P741/EN PM/I75 PICS & MICS

(PM) 26 MiCOM P741

phsC CMV_MAG_FLOAT -- Measurement values for Phase


C

2.6 Common data attribute type definitions


Common data attribute types, known herein as components, are defined for use in the
Common Data Classes defined in the sections above.

2.6.1 Component: AnalogueValue_Float

Comment: General analogue value (w.r.t Floating Point value)


Parent Type: AnalogueValue
Attribute Type Enumeration Comment X
f FLOAT32 Floating point value

2.6.2 Component: Unit_No_Multiplier

Comment: SI Unit definitions


Parent Type: Unit
Attribute Type Enumeration Comment X
SIUnit ENUMERATED16 SIUnit SI Unit

2.6.3 Component: Vector_Magnitude_Float

Comment: Complex vector (w.r.t Floating Point Magnitude value)


Parent Type: Vector
Attribute Type Enumeration Comment X
mag AnalogueValue_Float The magnitude of the complex value

2.7 Enumerated type definitions


The following sub-sections specify the enumerations that are associated to some Common
Data Class attributes. The definition of the enumerations are according to IEC61850-7-3
and IEC61850-7-4 unless otherwise stated.

2.7.1 Enumerated type: Beh

Description: Behaviour
Ordinal Semantic
1 on
2 blocked
3 test
4 test/blocked
5 off

2.7.2 Enumerated type: ctlModel

Description: Control Model


Ordinal Semantic
0 status-only
1 direct-with-normal-security
2 sbo-with-normal-security
3 direct-with-enhanced-security
4 sbo-with-enhanced-security

2.7.3 Enumerated type: dir

Description: Direction
Ordinal Semantic
0 unknown
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 27

Ordinal Semantic
1 forward
2 backward
3 both

2.7.4 Enumerated type: Health

Description: Health
Ordinal Semantic
1 Ok
2 Warning
3 Alarm

2.7.5 Enumerated type: Mod

Description: Mode
Ordinal Semantic
1 on
2 blocked
3 test
4 test/blocked
5 off

2.7.6 Enumerated type: SIUnit

Description: SI Units derived from ISO/IEC 1000


Ordinal Semantic
1 none
2 m
3 kg
4 s
5 A
6 K
7 mol
8 cd
9 deg
10 rad
11 sr
21 Gy
22 q
23 °C
24 Sv
25 F
26 C
27 S
28 H
29 V
30 ohm
31 J
32 N
33 Hz
34 lx
35 Lm
36 Wb
37 T
38 W
P741/EN PM/I75 PICS & MICS

(PM) 28 MiCOM P741

Ordinal Semantic
39 Pa
41 m²
42 m³
43 m/s
44 m/s²
45 m³/s
46 m/m³
47 M
48 kg/m³
49 m²/s
50 W/m K
51 J/K
52 ppm
53 1/s
54 rad/s
61 VA
62 Watts
63 VAr
64 theta
65 cos(theta)
66 Vs
67 V²
68 As
69 A²
70 A²t
71 VAh
72 Wh
73 VArh
74 V/Hz

2.8 MMS data-type conversions


The following table shows the relationships between the Part 7 and Part 8-1 data types. The
definitions presented above use Part 7 data types, however these are subject to 'translation'
when exposed over an MMS (Part 8-1) interface:
Part 7 Type MMS Type Part 7 Description
BOOLEAN Bool Logical TRUE/FALSE value
BVstring13 BVstring13 Variable bit string (upto 13 bits)
CODED_ENUM Byte Coded enumeration
CODED_ENUM2 Byte Coded enumeration (2)
EntryTime Btime6 8.1 Section 8.1.3.7
ENUMERATED16 Short 16 bit enumerated value
ENUMERATED8 Byte 8 bit enumerated value
FLOAT32 Float 32 bit floating point value
FLOAT64 Double 64 bit floating point value
INT128 Long 128 bit signed integer value
INT16 Short 16 bit signed integer value
INT16U Ushort 16 bit unsigned integer value
INT24U Ulong 24 bit unsigned integer value
INT32 Long 32 bit signed integer value
INT32U Ulong 32 bit unsigned integer value
INT8 Byte 8 bit signed integer value
INT8U Ubyte 8 bit unsigned integer value
PICS & MICS P741/EN PM/I75

MiCOM P741 (PM) 29

Part 7 Type MMS Type Part 7 Description


OCTET_STRING6 Ostring6 6 character string (8 bits per character)
OCTET_STRING64 Ostring64 64 character string (8 bits per character)
OCTET_STRING8 Ostring8 8 character string (8 bits per character)
Quality BVstring13 IEC61850 Quality
TimeStamp Utctime IEC61850 Time stamp
UNICODE_STRING255 UTF8Vstring255 255 character string (16 bits per
unicode character)
UTC_TM Utctime UTC Timestamp
VISIBLE_STRING255 Vstring255 255 character string
VISIBLE_STRING64 Vstring64 64 character string
VISIBLE_STRING65 Vstring65 65 character string
VISIBLE_STRING97 Vstring97 97 character string
Publication: P741/EN PM/I75

AREVA T&D's Automation & Information Systems Business www.areva-td.com


T&D Worldwide Contact Centre online 24 hours a day: +44 (0) 1785 25 00 70 http://www.areva-td.com/contactcentre/