Operating and Installation Conditions
Operating and Installation Conditions
Operating and Installation Conditions
com
Installation recommendations
Operating and installation conditions
Doing the setting or calculating the tripping time for a given 10 000
5 000
temperature: 2 000
$IWHUKDYLQJGHWHUPLQHWKHFRUUHFWHGUDWLR,,QWKHWULSSLQJWLPHDW&LVGH¿QHG 1 000
with the tripping curves (see page E-2 to page E-3). 500
7RREWDLQWKHULJKWVHWWLQJRUWKHWULSSLQJWLPHDWDGLႇHUHQWWHPSHUDWXUHWKHUDWLR,,Q
has to be corrected with the correction factor below:
200
100
B
50
Correction factor table for thermal magnetic (TM-D) NSXm 20
DB423008.eps
to determine setting or tripping time at In 10
5 TM125D : Im = 10 x In
Rating Temperature °C t(s)
2
(A) In 10 15 20 25 30 35 40 45 50 55 60 65 70 1
16 1.16 1.13 1.11 1.08 1.05 1.03 1.00 0.97 0.94 0.91 0.88 0.85 0.81 .5 TM160D :
Im = 8 x In
25 1.13 1.11 1.09 1.07 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.88 0.85 .2
.1
32 1.14 1.11 1.09 1.07 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.87 0.84
.05
40 1.15 1.12 1.10 1.08 1.05 1.03 1.00 0.97 0.95 0.92 0.89 0.86 0.83
.02
50 1.13 1.11 1.09 1.07 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.87 0.85 .01 t < 10 ms
63 1.14 1.12 1.10 1.07 1.05 1.02 1.00 0.97 0.95 0.92 0.89 0.86 0.83 .005
80 1.21 1.18 1.14 1.11 1.07 1.04 1.00 0.96 0.92 0.88 0.83 0.80 0.75 .002
.001
100 1.18 1.16 1.12 1.10 1.06 1.04 1.00 0.96 0.94 0.90 0.87 0.83 0.80 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
125 1.17 1.14 1.11 1.08 1.06 1.03 1.00 0.96 0.93 0.90 0.87 0.84 0.80 I / Ir
160 1.17 1.15 1.12 1.09 1.06 1.03 1.00 0.97 0.93 0.90 0.87 0.83 0.79
For Ir = 0.7 to 0.9 In, additional correction factor need to be applied - please consult us.
B-5