Installation recommendations
Operating and installation conditions

Doing the setting or calculating the tripping time for a given 10 000
5 000
temperature: 2 000
$IWHUKDYLQJGHWHUPLQHWKHFRUUHFWHGUDWLR,,QWKHWULSSLQJWLPHDWƒ&LVGH¿QHG 1 000
with the tripping curves (see page E-2 to page E-3). 500
7RREWDLQWKHULJKWVHWWLQJRUWKHWULSSLQJWLPHDWDGLႇHUHQWWHPSHUDWXUHWKHUDWLR,,Q
has to be corrected with the correction factor below:
200
100
B
50
Correction factor table for thermal magnetic (TM-D) NSXm 20

DB423008.eps
to determine setting or tripping time at In 10
5 TM125D : Im = 10 x In
Rating Temperature °C t(s)
2
(A) In 10 15 20 25 30 35 40 45 50 55 60 65 70 1
16 1.16 1.13 1.11 1.08 1.05 1.03 1.00 0.97 0.94 0.91 0.88 0.85 0.81 .5 TM160D :
Im = 8 x In
25 1.13 1.11 1.09 1.07 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.88 0.85 .2
.1
32 1.14 1.11 1.09 1.07 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.87 0.84
.05
40 1.15 1.12 1.10 1.08 1.05 1.03 1.00 0.97 0.95 0.92 0.89 0.86 0.83
.02
50 1.13 1.11 1.09 1.07 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.87 0.85 .01 t < 10 ms
63 1.14 1.12 1.10 1.07 1.05 1.02 1.00 0.97 0.95 0.92 0.89 0.86 0.83 .005

80 1.21 1.18 1.14 1.11 1.07 1.04 1.00 0.96 0.92 0.88 0.83 0.80 0.75 .002
.001
100 1.18 1.16 1.12 1.10 1.06 1.04 1.00 0.96 0.94 0.90 0.87 0.83 0.80 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
125 1.17 1.14 1.11 1.08 1.06 1.03 1.00 0.96 0.93 0.90 0.87 0.84 0.80 I / Ir

160 1.17 1.15 1.12 1.09 1.06 1.03 1.00 0.97 0.93 0.90 0.87 0.83 0.79

Doing the right setting depending of the temperature:


Example: What is the setting to obtain a real Ir of 105 A, taking into account the
temperature, for a Compact NSXm 125 A?
The necessary dial setting, in amperes, is shown below.
b At 40 °C, Ir = 105 / 1 = 105 A
b At 20 °C, Ir = 105 / 1.11 = 95 A
b At 60 °C, Ir = 105 / 0.87 = 121 A.

Calculating the tripping time at Ir = In for a given temperature:


Example: What is the tripping time of a Compact NSXm 100A at Ir = In for an
overload of 500 A?
b At 40 °C, I/Ir = 5, tripping time is between 6 and 60 seconds
b At 20 °C, I/Ir = 5 / 1.12 = 4.46, tripping time is between 8 and 80 seconds
b At 60 °C, I/Ir = 5 / 0.87 = 5.75, tripping time is between 5 and 50 seconds

For Ir = 0.7 to 0.9 In, additional correction factor need to be applied - please consult us.