Liquiphant M FTL50 (H), FTL51 (H) : Technical Information
Liquiphant M FTL50 (H), FTL51 (H) : Technical Information
Liquiphant M FTL50 (H), FTL51 (H) : Technical Information
TI328F/00/en
71114953
Liquiphant M FTL50(H), FTL51(H)
Table of contents
Electronic insert FEL51 (AC 2-wire) . . . . . . . . . . . . . . 6 Electronics FEL58 (NAMUR H-L edge,
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 in compact housing). . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Connectable load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Connectable load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electronics FEL51 (AC, in compact housing). . . . . . . . 7
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Electronic insert FEL57 (PFM). . . . . . . . . . . . . . . . . . 16
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Connectable load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Connectable load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electronic insert FEL52 (DC PNP) . . . . . . . . . . . . . . . . 8
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Electronic insert FEL50A (PROFIBUS PA) . . . . . . . . . 18
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Connectable load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electronics FEL52 (DC PNP, in compact housing) . . . . 9 Electronic insert FEL50D (density) . . . . . . . . . . . . . . 20
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Connectable load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Operating principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Light signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Electronic insert FEL54 (AC/DC with relay output) . 11
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Connection and function . . . . . . . . . . . . . . . . . . . . . . 22
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Connecting cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Safety mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Switching time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Connectable load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Switch-on behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Medium conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Medium temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Thermal shock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Medium pressure pe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Test pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
State of aggregation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Viscosity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Solids content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Lateral loading capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 27
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Dimensions (in mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Electronic inserts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Compact housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 41
Liquiphant M FTL50, FTL51 product structure . . . . . . . . . . . . . . 41
Liquiphant M FTL50H, FTL51H product structure . . . . . . . . . . . 46
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Welding neck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
G¾, d=55 with flange for flush-mounted installation . . . . . . . . . 51
G1, d=60 with flange for flush-mounted installation with sealing
surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
G1, Sensor can be positioned . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
RD52, Sensor can be positioned . . . . . . . . . . . . . . . . . . . . . . . . . 53
DRD DN50 (65 mm), for flush-mounted installation of devices
with DRD flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Application
Point level detection Maximum or minimum detection in tanks or pipes containing all kinds of liquids, including use in hazardous
areas, food and pharmaceuticals.
L00-FTL5xxxx-11-05-xx-xx-000
L00-FTL5xxxx-15-05-xx-xx-000
EX EX
L00-FTL5xxxx-15-05-xx-en-000
4 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Input
Measured variable Level (limit value)
Density Adjustment on the electronic insert > 0.5 g/cm3 or > 0.7 g/cm3 (other on request)
Endress+Hauser 5
Liquiphant M FTL50(H), FTL51(H)
IL
1 2
IL = load current Max.
(switched through)
< 3.8 mA
1 2
< 3.8 mA = residual current
(blocked)
IL
1 2
= lit
Min.
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 3.8 mA
Connectable load • For relays with a minimum holding power/rated power > 2.5 VA at 253 V AC (10 mA) or
> 0.5 VA at 24 V AC (20 mA)
• Relays with a lower holding power/rated power can be operated by means of an RC module connected in
parallel.
• For relays with a maximum holding power/rated power < 89 VA at 253 AC or < 8.4 VA at 24 V AC
• Voltage drop across FEL51 max. 12V
• Residual current with blocked electrical switch: max. 3.8 mA.
• Load switched directly into the power supply circuit via the thyristor.
Transient (40 ms) max. 1.5 A, max. 375 VA at 253 V or max. 36 VA at 24 V (not short-circuit proof)
6 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
PE L1 N PE L1 N
(Ground) (Ground)
L00-FTL5xxxx-04-05-xx-en-008
• That a relay cannot de-energize with holding power below 3.8 mA.
If this is the case, a resistor should be connected parallel to the relay (RC module available on request).
IL
1 3
IL
= load current Max.
(switched through) < 3.8 mA
1 3
< 3.8 mA
= residual current
(blocked) IL
1 2
= lit Min.
L00-FTL5xxxx-04-05-xx-xx-001a
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 3.8 mA
Connectable load • For relays with a minimum holding power/rated power > 2.5 VA at 253 V AC (10 mA) or
> 0.5 VA at 24 V AC (20 mA)
• Relays with a lower holding power/rated power operated by means of an RC module connected in parallel.
• For relays with a maximum holding power/rated power < 89 VA at 253 AC or < 8.4 VA at 24 V AC
• Voltage drop across FEL51 max. 12V
• Residual current with blocked electrical switch: max. 3.8 mA.
• Load switched directly into the power supply circuit via the thyristor.
Transient (40 ms) max. 1.5 A, max. 375 VA at 253 V or max. 36 VA at 24 V (not short-circuit proof)
Endress+Hauser 7
Liquiphant M FTL50(H), FTL51(H)
0.5 A
e.g.
Relay
PLC
–
L+ L–
U–
... 10…55 V DC
L00-FTL5xxxx-04-05-xx-en-001
L+ IL +
1 3
IL = load current Max.
(switched through)
< 100 µA
1 3
< 100 μA = residual current
(blocked)
L+ IL +
1 3
= lit Min.
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 100 A
Connectable load • Load switched via the transistor and separate PNP connection, max. 55 V DC
• Load current max. 350 mA (pulsed overload and short-circuit protection)
• Residual current < 100 A (with transistor blocked).
• Capacitance load max. 0.5 F at 55 V, max. 1.0 F at 24 V
• Residual voltage < 3 V (with transistor switched through);
8 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
R R
FTL5#(H)- #######N3#
(M12x1)
52010285 / 52024216 0.5 A 0.5 A
L– L+ L– L+
FTL5#(H)- #######D3#
(Pg11) 1 1
or
2 2
FTL5#(H)- #######E3#
(NPT ½") 3 + 3
+
R
– R
–
0.5 A 0.5 A
PE L– L+ PE L– L+
(Ground) (Ground)
3 + 3
(BN) (BN) +
R
– R
–
0.5 A 0.5 A
PE L– L+ PE L– L+
(Ground) (Ground)
L00-FTL5xxxx-04-05-xx-en-010
L+ IL +
3 2
IL = load current Max.
(switched through)
L+ < 100 µA +
3 2
< 100 μA = residual current
(blocked)
L+ IL +
2 3
= lit
Min.
Endress+Hauser 9
Liquiphant M FTL50(H), FTL51(H)
L00-FTL5xxxx-16-05-
xx-xx-002
L+ IL –
1 2
Max.
IL = load current
L+ < 100 µA –
(switched through) 1 2
L00-FTL2xxxx-07-05-
xx-xx-000
ye 2 gn
Safety mode Level Output signal LEDs
L00-FTL5xxxx-16-05-
xx-xx-001
L+ IL –
1 2
Max.
IL = load current
L+ < 100 µA –
(switched through) 1 2
L00-FTL2xxxx-07-05-
xx-xx-000
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 100 A
Connectable load • Load switched via the transistor and separate PNP connection, max. 55 V DC
• Load current max. 350 mA (pulsed overload and short-circuit protection)
• Residual current < 100 A (with transistor blocked).
• Capacitance load max. 0.5 F at 55 V, max. 1.0 F at 24 V
• Residual voltage < 3 V (with transistor switched through);
10 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Output:
When connecting an instrument with 1 2 3 4 56 7 8
high inductance, provide a spark arrester
to protect the relay contact.
A fine-wire fuse (depending on the
load connected) protects the relay contact
on short-circuiting.
Both relay contacts switch simultaneously.
*
0.5 A
* When jumpered, the relay
output works with NPN logic.
NO C NC NO C NC
a u r a u r
L1 N PE ** **
L+ L– (Ground)
L00-FTL5xxxx-04-05-xx-xx-002
3 4 5 6 7 8
Max.
= relay energized 3 4 5 6 7 8
= relay de-energized
3 4 5 6 7 8
= lit
Min.
= unlit
3 4 5 6 7 8
L00-FTL2xxxx-07-05-
xx-xx-001 L00-FTL5xxxx-04-05-xx-xx-005
Signal on alarm Output signal on power failure or in the event of damaged sensor: relay de-energized
Endress+Hauser 11
Liquiphant M FTL50(H), FTL51(H)
EEx ia
EX
EX
– +
U–
... 11…36
11…36 V DC
e.g. PLC
L00-FTL5xxxx-04-05-xx-en-000
+ ~16 mA
2 1
Max.
+ ~8 mA
~ 16 mA = 16 mA ± 5 % 2 1
~ 8 mA = 8 mA ± 6 %
+ ~16 mA
2 1
= lit
Min.
= unlit + ~8 mA
2 1
L00-FTL2xxxx-07-05-
L00-FTL5xxxx-04-05-xx-xx-006
xx-xx-000
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 3.6 mA
12 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Connecting to multiplexer:
Set clock time to min. 2 s.
EEx ia
EX
I
EX
L
– +
Isolating amplifier
to IEC 60947-5-6
(NAMUR)
L00-FTL5xxxx-04-05-xx-en-004
0.6 …
+ 1.0 mA
2 1
Max.
2.2 …
+ 2.8 mA
2 1
= lit 0.6 …
+ 1.0 mA
2 1
= flashes
Min.
2.2 …
= unlit + 2.8 mA
2 1
L00-FTL5xxxx-07-05-
L00-FTL5xxxx-04-05-xx-xx-003
xx-xx-002
Signal on alarm Output signal in the event of damaged sensor: > 2.2 mA
Connectable load See Technical Data of the isolating amplifier connected according to IEC 60947–5–6 (NAMUR)
Endress+Hauser 13
Liquiphant M FTL50(H), FTL51(H)
Additional function:
Test key on the electronic insert.
EEx ia
Pressing the key breaks the connection
to the isolating amplifier.
EX
! Note!
H
In Ex–d applications, the additional function
can only be used if the housing is not exposed I
to an explosive atmosphere. EX
L
Connecting to multiplexer:
Set clock time to min. 2 s.
– +
Isolating amplifier
to IEC 60947-5-6
(NAMUR)
L00-FTL5xxxx-04-05-xx-en-002
= lit 2.2 …
+ 3.5 mA
2 1
= flashes
Min.
0.6 …
= unlit + 1.0 mA
2 1
L00-FTL5xxxx-07-05- L00-FTL5xxxx-04-05-xx-xx-007
xx-xx-002
Signal on alarm Output signal in the event of damaged sensor: < 1.0 mA
Connectable load • See Technical Data of the isolating amplifier connected according to IEC 60947–5–6 (NAMUR)
• Connection also to isolating amplifiers which have special safety circuits (I > 3.0 mA)
14 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
FTL5#(H)- #######C3#
Thus, it is not possible to use 1 1 2
(BU) (BU) (BK)
the M12 connector with an
integrated LED (52018763)
3
(BN)
+ – + –
L00-FTL5xxxx-04-05-xx-en-009
= lit 2.2…
+ 3.5 mA –
1 2
= flashes Min.
0.6…
= unlit + 1.0 mA –
1 2
L00-FTL5xxxx-07-05- L00-FTL5xxxx-04-05-xx-xx-007a
xx-xx-002
Signal on alarm Output signal in the event of damaged sensor: < 1.0 mA
Connectable load • See Technical Data of the isolating amplifier connected according to IEC 60947–5–6 (NAMUR)
• Connection also to isolating amplifiers which have special safety circuits (I > 3.0 mA)
Endress+Hauser 15
Liquiphant M FTL50(H), FTL51(H)
16 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Please note this switching response and function of the plant especially when replacing a
Liquiphant with an EL17Z or FEL37 electronic insert with a Liquiphant M with an FEL57 electronic insert.
150 Hz
= lit
= unlit 50 Hz
L00-FTL2xxxx-07-05-
xx-xx-000
L00-FTL5xxxx-04-05-xx-xx-008
Signal on alarm Output signal on power failure or in the event of damaged sensor: 0 Hz
Connectable load • Floating relay contacts in the connected switching device Nivotester FTL320, FTL325P,
FTL370, FTL372, FTL375P
• For contact load, see the Technical Data of the switching unit
Endress+Hauser 17
Liquiphant M FTL50(H), FTL51(H)
Electrical connection Two-wire connection for power supply and data transfer
PA– PA+
–
–
PROFIBUS PA
U–
... 9…32 V DC
–
Segment coupler
–
L00-FTL5xxxx-04-05-xx-en-005
PC with Commuwin II
Proficard or Profiboard
PLC
Segment coupler
PROFIBUS DP
EX
PROFIBUS PA
EX
L00-FTL5xxxx-04-05-xx-en-006
18 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
OUT_D = 1
PA bus signal
= lit inverted
OUT_D = 0
= unlit PA bus signal
L00-FTL2xxxx-07-05-
xx-xx-000 L00-FTL5xxxx-04-05-xx-xx-009
Signal on alarm • Failure information can be opened using the following interfaces:
Yellow LED flashing, status code, diagnostic code; see BA198F
Endress+Hauser 19
Liquiphant M FTL50(H), FTL51(H)
" Caution!
Operation with other switching units, EEx ia
such as FTL325P, is not permitted.
This electronic insert cannot be installed in EX
devices that were originally used as a point level switch.
pulse
EX
– +
FML621
10 82 On
Endress+Hauser
FML621
112 182
TI420Fde004
Signal on alarm Output signal on power failure or in the event of damaged sensor: 0 Hz
Adjustment In the Liquiphant M modular system, the option of adjustment is also provided in addition to the electronics
(see feature 60: "Accessories").
There are three types of adjustment:
Standard adjustment (see ordering information for additional options, basic version A)
• Here, two fork parameters are determined to describe the sensor characteristics, indicated in the adjustment
report and provided with the product.
These parameters must be transmitted to the Density Computer FML621.
Special adjustment (see ordering information for additional options, special adjustment, density H2O (K) or
special adjustment, density H2O with 3.1 certificate (L))
• Here, three fork parameters are determined to describe the sensor characteristics, indicated in the
adjustment report and provided with the product.
These parameters must be transmitted to the Density Computer FML621.
Greater accuracy is achieved with this type of adjustment (see also "Performance characteristics").
Field adjustment
• During field adjustment, a density value actually determined by the customer is entered and the system is
automatically adjusted to this value (wet adjustment).
! Note!
Further information on Liquiphant M Density is available in Technical Information TI420F. This document is
available for download at www.endress.com => Download.
20 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Operating principle Measuring the density of a liquid medium in pipes and tanks. Also suitable for use in hazardous areas, and
preferably for applications in the chemical and food industry.
EX EX
* *
Endress+Hauser
RMM621
On
FML621
PLC/SPS
Endress+Hauser
RMM621
1. 2. 3. 4.
On
FML621
PLC/SPS
TI420Fxx016
Maintenance required
Green Power on
Power off
Red No fault
Maintenance required
Device failure
Endress+Hauser 21
Liquiphant M FTL50(H), FTL51(H)
Switch-on behavior When switching on the power supply, the output assumes the alarm signal.
After max. 3 s it assumes the correct switching mode (exception: FEL57)
Performance characteristics
Reference operating Ambient temperature: 23 °C
conditions
Medium temperature: 23 °C
Medium density: 1 g/cm3 (water) Switchpoint
13 mm
2 for
Viscosity: 1 mm /s reference conditions
Repeatability 0.1 mm
Hysteresis Approx. 2 mm
22 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Operating conditions
Installation Installation instructions
Switch points on the sensor depend on the mounting position, with reference to water,
Density 1 g/cm3, 23 °C, pe 0 bar.
4 mm
4 mm
13 mm
L00-FTL5xxxx-06-05-xx-xx-001
Mounting from above Mounting from below Mounting from the side
! Note!
The switch points of the Liquiphant M are at other positions to those of the previous version Liquiphant II.
Examples of mounting Examples of mounting with regard to the viscosity ν of the liquid and the tendency to form buildup
L00-FTL5xxxx-11-05-xx-xx-001
Endress+Hauser 23
Liquiphant M FTL50(H), FTL51(H)
*
*
L00-FTL5xxxx-11-05-xx-xx-002
Vertical from above Protruding into the tank from the side
*
* min. 25
(min. 1 in)
L00-FTL5xxxx-11-05-xx-en-003
L00-FTL5xxxx-11-05-xx-xx-004
24 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
L00-FTL5xxxx-11-05-xx-xx-005
.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
Ensure adequate space outside the .................................................................................................................................
.. .. .. .. .. .. .. .. .. .. .. .. .
L00-FTL5xxxx-11-05-xx-xx-006
Orientation FTL50(H) and FTL51(H) with short pipe (up to approx. 500 mm) - any position,
FTL51(H) with long pipe - vertical
Environment
Ambient temperature range Permitted ambient temperature Ta at the housing depending on the medium temperature Tp in the tank:
Ta
Ta ** *
70 °C
50 °C
0 °C
Tp
–50 °C 0 °C 50 °C 100 °C 150 °C Tp
90 °C
–50 °C
L00-FTL5xxxx-05-05-xx-xx-001
* Additional temperature range for devices with a temperature spacer or Pressure tight feed through.
** Maximum ambient temperature with FEL50D/FEL50A in hazardous areas.
Endress+Hauser 25
Liquiphant M FTL50(H), FTL51(H)
Degree of protection Types of housing IP65 IP66* IP67* IP68* IP69k NEMA4X**
Compact housing with valve connector X – – – – –
Pf11/NPT ½
Compact housing with 5 m cable tail – X – X – –
Compact housing with M12x1 connector – X – X – –
(52010285) 316L (metal)
Compact housing with elbowed connector – X – X X –
(52024216) / L= 5 m, without integrated
LEDs
Compact housing with elbowed connector – X – X X –
(52018763) / L= 5 m, with integrated
LEDs
Polyester housing F16 – X X – – X
Stainless steel housing F15 – X X – – X
Aluminum housing F17 X X X – – X
Aluminum housing F13 X X – X*** – X
Stainless steel housing F27 – X – X – 4x/6P
Aluminum housing T13 with separate X X – X*** – 4x/6P
connection compartment (EEx d)
* As per EN60529
** As per NEMA 250
*** Only with M20 cable entry or G1/2 thread
Vibration resistance To IEC 68, Part 2-6 (10 to 55 Hz, 0.15 mm, 100 cycles)
In the event of increased vibrations, we recommend the additional fitting feature "060" version "P" 100 bar
process pressure.
Medium conditions
Medium temperature –50 to +150 °C; see "Process connections" for exceptions
Medium pressure pe
pe
bar
(psi)
(psi)
*
100
(1450)
64
(928)
Tp
–1 °C
–50 (–14.5) 0 (°F)
150
(–58) (32) (300)
L00-FTL5xxxx-05-05-xx-xx-003
* Allowed pressure rating when the "100 bar" option is selected (see "Product structure FTL51", feature 060,
→ ä 41ff.). See "Process connections" for exceptions.
26 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Please refer to the standards listed for the permitted pressure values of the flanges at higher temperatures:
• pR EN 1092-1: 2005
With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are identical and are
grouped together under 13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can be
identical.
• ASME B 16.5a - 1998 Tab. 2-2.2 F316
• ASME B 16.5a - 1998 Tab. 2.3.8 N10276
• JIS B 2220
The lowest value from the derating curves of the device and selected flange applies in each case.
Mechanical construction
Design Summary of all electrical and mechanical versions
Endress+Hauser 27
Liquiphant M FTL50(H), FTL51(H)
Housing
Bushings (optional)
Temperature spacer and pressure tight feed through
L00-FTL5xxxx-03-05-xx-xx-005
Process connections
G ¾, DIN ISO 228/I G 1, DIN ISO 228/I Diverse Flanges to DIN, ANSI,
R ¾, EN10226 R 1, EN10226 hygienic and JIS
NPT ¾, ANSI B 1.20.1 NPT 1, ANSI B 1.20.1 aseptic from DN 25 / 1"
(AF 32) (AF 41) connections
L00-FTL5xxxx-03-05-xx-xx-018
28 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
166
141
133
ø40 ø40 ø40
232
206
199
32 AF 32 AF 32 AF
*
1. 5 m cable
2. M12 connector
3. Pg11/NPT ½ connector L00-FTL5xxxx-06-05-xx-en-008
max. 155
max. 40.7
*
17.5
L00-FTL5xxxx-06-05-xx-xx-004
~25
*
L00-FTL5xxxx-06-05-xx-xx-005
ø21.5
*
10
L00-FTL5xxxx-06-05-xx-xx-006
Endress+Hauser 29
Liquiphant M FTL50(H), FTL51(H)
max. 190
*
L00-FTL5xxxx-06-05-xx-xx-007
! Note!
The switch points of the Liquiphant M are at other positions to those of the previous version Liquiphant II.
supplied
30 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
R¾
EN10226 GE2
L00-FTL5xxxx-06-05-xx-en-004
GE5
GE6
R1
EN10226 GF2
L00-FTL5xxxx-06-05-xx-en-005
GF5
GF6
L00-FTL5xxxx-06-05-xx-xx-008
AlloyC4/C22 -plated flanges are available for higher chemical-resistance. The flange carrier
material comprises 316L and is welded with a 2 to 3 mm thick AlloyC4/C22 disk.
Tri-Clamp 66.5
Clamping ring and Max. 16 bar
1 ½" = ø50.5 mm TC2 front seal Max. 120 °C
2" = ø64.0 mm TE2 installed on site
ISO 2852 Max. 2 bar
In conformity with
Max. 150 °C
FDA*
L00-FTL5xxxx-06-05-xx-xx-009
Mounting with NA connector (as per ASME, TUBE Standard ASTM A276) only in conjunction
with T13, F13 and compact housing. Other housings on request.
Threaded pipe joint Sealing ring with collar, DN 32, DN 40:
DN 32 MA2 66.5 installed on site Max. 40 bar to 100 °C
DN 40 MC2 Max. 25 bar to 140 °C
In conformity with
DN 50 ME2
FDA*
DIN 11851 DN 50:
Max. 25 bar
With thread adapter nut Max. 140 °C
L00-FTL5xxxx-06-05-xx-xx-010
Endress+Hauser 31
Liquiphant M FTL50(H), FTL51(H)
See "Accessories"
L00-FTL5xxxx-06-05-xx-xx-012
L00-FTL5xxxx-06-05-xx-xx-014
FDA*
Max. 150 °C
L00-FTL5xxxx-06-05-xx-xx-015
32 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
L
L
ø21.5
L00-FTL5xxxx-06-05-xx-xx-017 L00-FTL5xxxx-06-05-xx-xx-018
L00-FTL5xxxx-06-05-xx-xx-016
Any length L:
148 mm to 3000 mm (6 to 115 in); special version (TSP) on request up to 6000 mm (235 in)
! Note!
The switch points of the Liquiphant M are at other positions to those of the previous version Liquiphant II.
Special length "L II":
With vertical mounting from above the same switchpoint as for the Liquiphant II
FTL360, FTL365, FDL30, FDL35
Endress+Hauser 33
Liquiphant M FTL50(H), FTL51(H)
Process connections • Parallel thread G ¾, G 1 to DIN ISO 228/I with flat seal to DIN 7603
• Tapered thread R ¾, R 1 to EN10226
• Tapered thread ¾ -14 NPT, 1 - 11½ NPT to ANSI B 1.20.1
• Flush-mounted installation with welding neck to factory standard Endress+Hauser (G ¾, G 1)
• Flush-mounted installation with welding neck to factory standard Endress+Hauser (1"),
sensor can be positioned
• Tri-Clamp 1½", 2" to ISO 2852
• Threaded pipe joint DN 32, 40, 50 to DIN 11851
• Aseptic connection DN 50 to DIN 11864-1 Form A for pipe DIN 11850
• SMS connection 2" (DN 51)
• DRD flange
• Varivent® DN 50 (50/40) to factory standard Tuchenhagen
• Flanges to EN/DIN from DN 25, for standards see "Product structure," to ANSI B 16.5 from 1",
to JIS B2220 (RF)
• Ingold DN25 fitting length 46 mm with thread adapter nut G1 ¼
34 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Human interface
Electronic inserts With FEL51, FEL52, FEL54, FEL55:
• 2 switches for safety mode and density change,
FEL51
• green LED to indicate operational status, L1 N U~
19...253V AC
• red LED to indicate the switching status, 50/60Hz
1 Max >0,7
I max : 350mA
With FEL56: 1 2
With FEL50A:
• 8 switches for configuring the device address
FEL50A
• green LED to indicate operational status, Address
L00-FTL5xxxx-03-05-xx-en-002
With FEL50D:
• yellow LED: to indicate the validation of the measurement
• green LED: to indicate the operational status
FEL50D
• red LED: to indicate faults
Impuls
– +
YE
GN RD
TI328Fxx004
Endress+Hauser 35
Liquiphant M FTL50(H), FTL51(H)
L00-FTL5xxxx-19-05-xx-xx-001
Light signals
AC/DC NAMUR
rd ye
gn gn
L00-FTL5xxxx-07-05-xx-xx-005
36 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
ye rd
gn
L00-FTL5xxxx-07-05-xx-xx-003
ye 1
ye 2 gn
L00-FTL5xxxx-07-05-xx-xx-004
Endress+Hauser 37
Liquiphant M FTL50(H), FTL51(H)
Green light (gn) lights up, both yellow lights (ye 1+2) do not light up:
Liquiphant M has detected a fault.
38 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Ra (μm)
Aseptic HE2 X X X X
DRD PE2 X - - X
SMS UE2 X X X X
®
Varivent WE2 X X X X
Ingold TT2 X - X -
! Note!
• For CIP (Clean in Place) and SIP (Sterilize in Place) processes the pressure and temperature specifications of
the process connections must be observed.
• Suitable fittings and seals must be used to ensure hygiene-compliant design according to 3A, EHEDG,
ASME BPE etc.
• Surface Ra < 0.38 μm (< 15 μin) electropolished; surface Ra < 1.5 μm (59 μin) mechanically polished.
# Warning!
To avoid risk of contamination, install according to the "Hygienic Equipment Design Criteria (HDC)" as stated
in the Subgroup Design Principles of the EHEDG, Doc. 8, July 1993.
The flow of liquid during cleaning is important and should be in compliance with the HDC.
CRN approval Versions with a CRN approval (Canadian Registration Number) are marked with a "*" in ordering information
feature 20 "process connection" (see Page 41 ff.). CRN-approved devices are fitted with a separate plate bearing
the registration number 0F10525.5C.
! Note!
Wetted device components are listed in the "Mechanical construction“ (see Page 27 ff.) and "Ordering
information" (see Page 41 ff.) sections.
Combinations Based on the various certificates, permissible combinations of housings * ) and electronic inserts are given in
of housings and the following table.
electronic inserts *) Abbreviations: Polyester = PBT, Stainless steel 316L = St., Aluminum = Alu
Aluminum housing with separate connection compartment = Alu/sep
Endress+Hauser 39
Liquiphant M FTL50(H), FTL51(H)
B ATEX II 3G EEx nC IIC T6, WHG PBT, St., Alu, Alu/sep. FEL54
F ATEX II 1/2 G, EEx ia IIC T6, WHG PBT, St., Alu, Alu/sep. FEL55/56/57/58/50A/50D
ATEX II 1/2 G, EEx ia IIC T6, WHG St., Alu, Alu/sep. FEL55/56/57/58/50A/50D
ATEX II 1/2 D, T80°C
Q FM, XP, Cl. I, II, III, Div. 1, Gr. A–G Alu FEL51/52/54
with NPT cable entry FEL55/56/57/58/50D/50A
R FM, NI, Cl. I, Div. 2, Gr. A–D St., Alu, Alu/sep. FEL51/52/54,
with NPT cable entry FEL55/56/57/58/50D
PBT FEL55/56/57/58/50D/50A
with NPT cable entry
PBT FEL51/52,
with NPT cable entry FEL55/56/57/58/50D/50A
S CSA, IS, Cl. I, II, III, Div. 1, Gr. A–G PBT, St., Alu, Alu/sep. FEL55/56/57/58/50D/50A
with NPT cable entry
T CSA, XP, Cl. I, II, III, Div. 1, Gr. A–G Alu FEL51/52/54,
with NPT cable entry FEL55/56/57/58/50D/50A
*** In preparation!
40 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
! Note!
With polyester housing (PBT), electric connecting cables run in pipes:
Do not screw cable entries firmly to the piping. Use flexible connections (e.g. with armored hose).
If piping is used for grounding, then ensure that there is a continuous electrical connection.
! Note!
Despite the additional dust ignition-proof certificates, the FTL5x(H) is to be used as a liquid point level switch
only.
Ordering information
! Note!
Versions that are mutually exclusive are not indicated in this list.
10 Approval:
A Non-hazardous area
B ATEX/NEPSI II 3 G/ EEx nC II T6 Overfill protection to WHG (Germany)
ATEX/NEPSI II 3 D T 85 °C*
C ATEX/NEPSI II 3 G EEx nA II T6 Overfill protection to WHG (Germany)
ATEX /NEPSI II 3 D T 85 °C*
D Non-hazardous area Overfill protection to WHG (Germany)
E ATEX II 1/2 G EEx de IIC T6 Overfill protection to WHG (Germany)
F ATEX II 1/2 G EEx ia IIC T6 Overfill protection to WHG (Germany)
ATEX II 1/2 D T 80 °C*
G ATEX II 1/2 G EEx ia IIC T6
ATEX II 1/2 D T 80 °C*
H ATEX II 1 G EEx ia IIC T6
I ATEX II 1/2 G EEx de IIC T6
J ATEX II 1 G EEx ia IIC T6 Overfill protection to WHG (Germany)
K ATEX II 1/2 G EEx d IIC T6
L ATEX II 1/2 G EEx d IIC T6 Overfill protection to WHG (Germany)
M NEPSI Ex ia IIC T6
N NEPSI Ex d IIC T6
P FM IS, Class I, II, III Division 1, Group A–G
Q FM XP, Class I, II, III Division 1, Group B–G, for E5 housing Group A–G
R FM NI, Class I Division 2, Group A–D
S CSA IS, Class I, II, III Division 1, Group A–G
T CSA XP, Class I, II, III Division 1, Group A–G
U CSA General Purpose
V TIIS Ex ia IIC T3
W TIIS Ex d IIB T3
X TIIS Ex ia IIC T6
7 TIIS Ex d IIC T3
8 TIIS Ex d IIC T6
Y Special version
Endress+Hauser 41
Liquiphant M FTL50(H), FTL51(H)
42 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
FTL51
BB ....... mm; 316L** Ra <3.2 μm/80 grit
BE ....... mm; Alloy** Ra <3.2 μm/80 grit
CB ....... inch; 316L** Ra <3.2 μm/80 grit
CE ....... inch; Alloy** Ra <3.2 μm/80 grit 2.3 kg/100 in
DB Length: type II*; 316L Ra <3.2 μm/80 grit 0.1 kg
DE Length: type II*; Alloy Ra <3.2 μm/80 grit 0.1 kg
JB ....... mm; 316L** + Temperature spacer 0.9 kg/m
+0.6 kg
JE ....... mm; Alloy** + Temperature spacer 0.9 kg/m
+0.6 kg
Endress+Hauser 43
Liquiphant M FTL50(H), FTL51(H)
40 Electronics; output:
A FEL50A PROFIBUS PA
D FEL50D Density/concentration
1 FEL51* 2-wire, 19 to 253 V AC
2 FEL52* 3-wire PNP, 10 to 55 V DC
4 FEL54 Relay DPDT, 19 to 253 V AC, 19 to 55 V DC
5 FEL55 8/16 mA, 11 to 36 V DC
6 FEL56 NAMUR (L-H signal)
7 FEL57 2-wire PFM
8 FEL58* NAMUR + test keys (H-L signal)
9 Special version
*) Also available in compact housing
44 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
60 Additional options
A Basic version
B Cleaned for silicone-free service, max 2000mm
C EN 10204 - 3.1 material (316L wetted) inspection certificate
K Special adjustment, density H20
L Special adjustment, density H20, EN10204-3.1
N EN 10204 - 3.1 material, NACE MR0175 (316L wetted)
Inspection certificate
P 100 bar process pressure (FTL51)
R 100 bar process pressure, EN 10204 - 3.1 material,
NACE MR0175 (316L wetted) (FTL51)
Inspection certificate
S GL/ABS marine approval (FTL51: max. 1600 mm)
Y Special version
! Note!
The basic weight includes the compact sensor, thread adapter G ¾, electronic insert,
polyester housing
Endress+Hauser 45
Liquiphant M FTL50(H), FTL51(H)
10 Approval:
A Non-hazardous area
B ATEX/NEPSI II 3 G EEx nC II T6 Overfill protection to WHG (Germany)
ATEX/NEPSI II 3 D T 85 °C*
C ATEX/NEPSI II 3 G EEx nA II T6 Overfill protection to WHG (Germany)
ATEX/NEPSI II 3 D T 85 °C*
D Non-hazardous area Overfill protection to WHG (Germany)
E ATEX II 1/2 G EEx de IIC T6 Overfill protection to WHG (Germany)
F ATEX II 1/2 G EEx ia IIC T6 Overfill protection to WHG (Germany)
ATEX II 1/2 D T 80 °C*
G ATEX II 1/2 G EEx ia IIC T6
ATEX II 1/2 D T 80 °C*
H ATEX II 1 G EEx ia IIC T6
I ATEX II 1/2 G EEx de IIC T6
J ATEX II 1 G EEx ia IIC T6 Overfill protection to WHG (Germany)
K ATEX II 1/2 G EEx d IIC T6
L ATEX II 1/2 G EEx d IIC T6 Overfill protection to WHG (Germany)
M NEPSI Ex ia IIC T6
N NEPSI Ex d IIC T6
P FM IS, Class I, II, III Division 1, Group A–G
Q FM XP, Class I, II, III Division 1, Group B–G, for E5 housing Group A–G
R FM NI, Class I Division 2, Group A–D
S CSA IS, Class I, II, III Division 1, Group A–G
T CSA XP, Class I, II, III Division 1, Group A–G
U CSA General Purpose
V TIIS Ex ia IIC T3
W TIIS Ex d IIB T3
X TIIS Ex ia IIC T6
7 TIIS Ex d IIC T3
8 TIIS Ex d IIC T6
Y Special version
*) Not for PBT
46 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Endress+Hauser 47
Liquiphant M FTL50(H), FTL51(H)
40 Electronics; output:
A FEL50A PROFIBUS PA
D FEL50D Density/concentration
1 FEL51* 2-wire, 19 to 253 V AC
2 FEL52* 3-wire PNP, 10 to 55 V DC
4 FEL54 Relay DPDT, 19 to 253 V AC, 19 to 55 V DC
5 FEL55 8/16 mA, 11 to 36 V DC
6 FEL56 NAMUR (L-H signal)
7 FEL57 2-wire PFM
8 FEL58* NAMUR + test keys (H-L signal)
9 Special version
60 Additional options
A Basic version
B* CoC, EN 10204 - 3.1 material (316L wetted)
Inspection certificate
C EN 10204 - 3.1 material (316L wetted),
Inspection certificate
K Special adjustment, density H20
L Special adjustment, density H20, EN10204-3.1 (316L wetted) inspection certificate
S GL/ABS marine approval (FTL51H: max. 1600 mm)
Y Special version
* In preparation.
! Note!
Basic weight = compact sensor, thread adapter G ¾, electronic insert, stainless steel housing
48 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Accessories
! Note!
• All dimensions in mm
• For more detailed information on welding necks, please refer to TI426F/00.
• The tolerance of the defined thread start between the welding neck and sensor is ± 15°.
G1
G¾, d=29 G¾, d=50 with G¾, d=55 G1, d=53 G1, d=60
can be
without flange flange with flange with flange with flange
positioned
Silicone
Silicone O-ring Silicone O-ring Silicone O-ring Silicone O-ring Silicone O-ring
Seal (set of 5) profile gasket
520217173) 520217173) 520144733) 520144723) 520144723)
520144243)
FTL50 GQ2
FTL5x GW2 GW2 GW2
020
FTL50H GQ2
1) This welding neck replaces the welding neck with the order number 917969-1000.
2) This welding neck replaces the welding neck with the order number 215159-0000.
3) A seal is included in the delivery.
Endress+Hauser 49
Liquiphant M FTL50(H), FTL51(H)
DRD DN50
RD52 Uni D85 Uni D65 M24 D65 (65 mm)
(welding flange)
Liquiphant M
1) This welding neck replaces the welding neck with the order number 942329-0001.
50 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
G¾, d=55
with flange for Dimensions Version Order number
flush-mounted installation
26 • AISI 316L (1.4435) 52001052
• Roughness: Ra <0.8 μm
21
Ø 55 –0.4
ISO 228
Ø 32
G¾
Silicone O-ring, ∅ 21.89 x 2.62 52014473
Material: VMQ70, FDA (set of 5)
• Max. 25 bar / max. 150 °C FDA-compliant material in accordance with 21 CFR Part 177.1550/2600
• Max. 40 bar / max. 100 °C Approval: 3A, EHEDG
Endress+Hauser 51
Liquiphant M FTL50(H), FTL51(H)
G1, d=60
with flange for flush-mounted Dimensions Version Order number
installation with sealing
surface 29.6
• AISI 316L (1.4435) 52001051
• Roughness: Ra <0.8 μm
24.6
ISO 228
Ø 60 –0.4
Silicone O-ring, ∅ 28.17 x 3.53
Ø 41
52014472
G1
G1
Sensor can be positioned Dimensions Version Order number
• Roughness: Ra <0.8 μm
52 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
RD52
Sensor can be positioned Dimensions Version Order number
RD 52 x 1 6
Ø 42.3
Ø 65
Silicone profile gasket 29 x 36 x 3.7 52014424
Material: SI-60, FDA (set of 5)
• The seal can be easily replaced with
this version.
a0008271
FDA-compliant material in accordance with 21 CFR Part 177.1550/2600
• Max. 25 bar / max. 150 °C Approval: 3A, EHEDG
• Max. 40 bar / max. 100 °C
Alternative seals 29 x 39 x 3.7 Order number
Ø 125
Ø 105
Ø 66
13
4 x 90° (= 360°)
16
4 x M10
a0008263
Endress+Hauser 53
Liquiphant M FTL50(H), FTL51(H)
14
Pressure up to 40 bar
92
Material: corrosion-resistant steel
92
1.4301 (AISI 304)
Weight: 0.54 kg
G1 12
L00-FTL5xxxx-06-05-xx-xx-024
M6 (3x)
Weight for G 1, NPT 1: 0.21 kg
Weight for G 1½, NPT 1½: 0.54 kg G1A
(1 NPT)
55 AF
19
pe =
0 bar
22
M6 (3x)
G 1½ A
(1½ NPT)
L00-FTL5xxxx-06-05-xx-en-006
G1 DIN ISO 228/I 1.4435 (AISI 316 L) 52011888 3.1 inspection certificate
EN 10204 - 3.1 material
NPT1 ANSI B 1.20.1 1.4435 (AISI 316 L) 52011889 3.1 inspection certificate
EN 10204 - 3.1 material
G 1½ DIN ISO 228/I 1.4435 (AISI 316 L) 52011890 3.1 inspection certificate
EN 10204 - 3.1 material
NPT1½ ANSI B 1.20.1 1.4435 (AISI 316 L) 52003981
54 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
NPT1½ ANSI B 1.20.1 1.4435 (AISI 316 L) 52011891 3.1 inspection certificate
EN 10204 - 3.1 material
~70
(ATEX, NEPSI).
Material: corrosion-resistant steel 50 AF
1.4435 (AISI 316L) or AlloyC4
Weight for G 1, NPT 1: 1.13 kg
18
2
Weight for G 1½, NPT 1½: 1.32 kg
G1A
Seal package made of graphite (1 NPT)
ø60
~72
50 AF
22
G 1½ A
(1½ NPT)
L00-FTL5xxxx-06-05-xx-en-007
NPT1 ANSI B 1.20.1 1.4435 (AISI 316 L) 52011881 3.1 inspection certificate
EN 10204 - 3.1 material
G 1½ DIN ISO 228/1 1.4435 (AISI 316 L) 52011882 3.1 inspection certificate
EN 10204 - 3.1 material
NPT1½ ANSI B 1.20.1 1.4435 (AISI 316 L) 52011883 3.1 inspection certificate
EN 10204 - 3.1 material
* AlloyC22 in preparation.
Endress+Hauser 55
Liquiphant M FTL50(H), FTL51(H)
pe
bar
(psi) Liquiphant M FTL51*
100 Liquiphant S
(1450)
80
(1160)
64
(928)
Liquiphant M
Tp
°C
–60 –50 –1 0 150 230 280 (°F)
(–76) (–58) (–14.5) (32) (300) (440) (540)
L00-FTL5xxxx-05-05-xx-xx-002
* FTL51 with high-pressure sliding sleeve (100 bar). See "Additional fitting" → ä 41 option "P" or "R".l
L00-FTL5xxxx-03-05-xx-xx-016
56 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
27.5
Body: PVC (transparent)
Thread adapter nut: 316L min. 40
Degree of protection: IP69K (fully locked)
L00-FTL20Hxx-07-05-xx-xx-005
Temperature range: –25 to +70 °C
Documentation
! Note!
You can find supplementary documentation on the product pages at www.endress.com
Endress+Hauser 57
Liquiphant M FTL50(H), FTL51(H)
Functional safety (SIL) Liquiphant M/S with electronic insert FEL51 (MAX)
SD164F/00/en
Liquiphant M/S with electronic insert FEL51 (MIN)
SD185F/00/en
Liquiphant M/S with electronic insert FEL52 (MAX)
SD163F/00/en
Liquiphant M/S with electronic insert FEL52 (MIN)
SD186F/00/en
Liquiphant M/S with electronic insert FEL54 (MAX)
SD162F/00/en
Liquiphant M/S with electronic insert FEL54 (MIN)
SD187F/00/en
Liquiphant M/S with electronic insert FEL55 (MAX)
SD167F/00/en
Liquiphant M/S with electronic insert FEL55 (MIN)
SD279F/00/en
Liquiphant M/S with electronic insert FEL57 + Nivotester FTL325P (MAX)
SD111F/00/en
Liquiphant M/S with electronic insert FEL57 + Nivotester FTL325P (MIN)
SD231F/00/en
Liquiphant M/S with electronic insert FEL57+ Nivotester FTL375P (MAX)
58 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
SD113F/00/en
Liquiphant M/S with electronic insert FEL56 + Nivotester FTL325N (MAX)
SD168F/00/en
Liquiphant M/S with electronic insert FEL56 + Nivotester FTL325N (MIN)
SD188F/00/en
Liquiphant M/S with electronic insert FEL58 + Nivotester FTL325N (MAX)
SD161F/00/en
Liquiphant M/S with electronic insert FEL58 + Nivotester FTL325N (MIN)
SD170F/00/en
Control Drawings Liquiphant M/S (IS and NI) Current output PFM, NAMUR Entity installation
Class I, Div. 1, 2, Groups A, B, C, D
Class I, Zone 0
Class II, Div. 1, 2, Groups E, F, G
Class III
ZD041F-I/00/EN
Endress+Hauser 59
Liquiphant M FTL50(H), FTL51(H)
Class III
ZD240F/00/EN
Liquiphant M/S (IS and NI) PROFIBUS PA, FOUNDATION FieldbusClass I, Zone 0, IIC
Class I, Division 1, 2, Groups A, B, C, D
Class II, Division 1, 2, Groups E, F, G
Class III
ZD244F/00/EN
60 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Endress+Hauser 61
Liquiphant M FTL50(H), FTL51(H)
62 Endress+Hauser
Liquiphant M FTL50(H), FTL51(H)
Endress+Hauser 63
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
TI328F/00/en/05.10
71114953
SL/FM+SGML6.0 ProMoDo 71114953