R 438 A.V.R.: R 438 For Shunt, Arep or PMG Alternators

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

R 438 A.V.R.

R 438 FOR SHUNT, AREP or PMG ALTERNATORS

1 - Description

R 438 is an analog A.V.R.


It is designed for alternators with a
AREP or PMG excitation.
R 438 controls the excitation current in order
to maintain the output voltage of the alternator.
R 438 is performant in terms of voltage
regulation, simple to set , to use and is reliable.
It can run without LAM (U/f), or with LAM, selection
is done by strap ST5.

It is in compliance with I.E.C. 60034-1 standard


and U.L. 508 / C.S.A. approved

2 - Operation range
LSA 40 42.3 44.3 46.3 47.2 49.3 50.2 51.2 53.1 54

Shunt - - - - - - - - - -

AREP - - - - - - - - - -

PMG - - - - - - - - - -

Operation mode : Standalone

3 - Main feature and characteristics


Voltage
- Voltage regulation : ± 0.5 %. 60 Hz
Knee 57 Hz

- U/F function (1).


Knee
- LAM function (2). 48 Hz
- Response time : 500 ms. 100 %
U/UN 50 Hz
- Nominal excitation current : 5A.
- Maximum excitation current : 8A during 10 s.
- Supply range and voltage détection : Frequency
95 to 520 V. 50 Hz 60 Hz Hz

- Protection : fuse 8A. (1) U/F function

Transient voltage drop


UN Max. speed drop with
LAM
fN LAM
the shaft (kW)

0,9
Load on

(U/f) 0,9 Variation in the load


without LAM without
0,8 with LAM LAM Load shedding due to LAM
Time 0,8 Time Time

0 1s 2s 3s 0 1s 2s 3s
0 1s 2s 3s
(2) LAM Function

Ref : 4549en-2015.11/d Page 1


R 438 A.V.R.

4 - Opération conditions
- Operating temperature range : - 40° C à + 70° C.
- Storage temperature range : - 55° C à + 85° C.
- Hygrometry : 98%.
- Maximum choc : 9 g on 3 axis.
- Vibrations : less than 10 Hz , 2 mm peak magnitude.
From 10 Hz to 100 Hz : 100 mm/s, below 100 Hz : 8g.

Optional modules compatible


- R 731 : three phase voltage sensing.
- R 734 : 3-phase current and voltage sensing for parallel operation.
- R 726 : regulation system changed to “4 - function”.

5 - Connexion and setting


Settings are done through the A.V.R.

- Potentiometer P1 : Quadrature droop setting.


- Potentiometer P2 : Voltage setting.
- Potentiometer P3 : Stability setting.
- Potentiometer P5 : Excitation ceiling setting.

140 mm

X2 Z1 X1 Z2 E+ E- 0V 110 220 380 4 x holes Ø 5.8 x


Slow fuse
F1
125 mm

250V 8 A 115 x 100 mm

ST5
Quad
with LAM without LAM
P1 droop

ST3 AREP
Frequency 50Hz 60Hz ST9 PMG

R 438
ST10 T.I. S2 P2
LAM 13 % 25 %
Option
Ph.1
S1
P1
Excitation
P5 ceiling
ST4 Option
open
ST11 knee-point: 65 Hz
External potentiometer
for adjusting the voltage

normal
ST2 Response
time fast ST1 P2 Option

Single- R731 3-ph. detection


P3 Stability phase
detection Voltage in 3-ph. detection ST1 open