2001 Standard For: Air Diffusers and Air Diffuser Assemblies
2001 Standard For: Air Diffusers and Air Diffuser Assemblies
2001 Standard For: Air Diffusers and Air Diffuser Assemblies
STANDARD for
AIR DIFFUSERS
AND AIR
DIFFUSER
ASSEMBLIES
Standard 890
SAFETY RECOMMENDATIONS
It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with
nationally recognized safety requirements appropriate for products covered by this standard.
ARI, as a manufacturers' trade association, uses its best efforts to develop standards employing state-of-the-art and
accepted industry practices. However, ARI does not certify or guarantee safety of any products, components or
systems designed, tested, rated, installed or operated in accordance with these standards or that any tests conducted
under its standards will be non-hazardous or free from risk.
Note:
Price $10.00 (M) $20.00 (NM) ©Copyright 2001, by Air-Conditioning and Refrigeration Institute
Printed in U.S.A. Registered United States Patent and Trademark Office
TABLE OF CONTENTS
SECTION PAGE
Section 4. Classifications..................................................................................................3
FIGURES
APPENDICES
1.1.1 Intent. This standard is intended for the 3.2.3 Grille. A louvered or perforated face over
guidance of the industry, including manufacturers, an opening which is generally located in the sidewall,
engineers, installers, contractors and users. sill, or floor.
1.1.2 Review and Amendment. This standard is 3.2.4 Register. A combination Grille and damper
subject to review and amendment as technology assembly.
advances.
3.2.5 Slot Diffuser or Slot. A long narrow air
outlet (aspect ratio generally greater than 10:1).
Section 2. Scope
3.3 Air Stream Patterns. These are characterized by the
2.1 Scope. This standard applies to Diffusers and following terms (see Figure 1):
Diffuser Assemblies used in air distribution systems which
are duct connected to a remote forced air source, as defined
in Section 3. DIFFUSER
3.1 Air Inlet. A device through which air is removed or Plan View
returned from a conditioned space. (Grilles, Registers,
Diffusers, and Slots may be used as Air Inlets.)
1
ARI STANDARD 890-2001
3.3.1 Angle of Discharge. The largest included where An is the nominal area, ft2 [m2], of the duct connection
angle between centerlines of principal jets of the to the Diffuser or Diffuser Assembly.
primary air stream.
3.10 Octave Band. A frequency band of sound covering a
3.3.2 Drop. The vertical distance that the lower range of frequencies such that the highest frequency is twice
edge of a horizontally projected air stream drops the lowest. The Octave Bands used in this standard are
between the outlet and the end of its throw. defined in ANSI Standard S1.11.
3.3.3 Envelope (ISOVEL). The boundary surface 3.11 Pressure. The force per unit area, in H2O [kPa],
of points of equal velocity which describe the air exerted by a homogeneous liquid or gas.
distribution profile (see Figure 1).
3.11.1 Static Pressure (SP). The pressure that
3.3.4 Spread. The maximum distance, in ft [m], would be exerted by a moving fluid on a body
measured parallel to the plane of the outlet between immersed in it if the body were carried along with the
the extremes of the Terminal Velocity Envelope (see fluid. Practically, it is the normal force per unit area
Figure 1). at a small hole in a wall of the duct through which the
fluid flows.
3.3.5 Terminal Velocity (Vt). The highest
sustained velocity in the air stream from an outlet, 3.11.2 Total Pressure (TP). The sum of the
fpm [m/s], which is arbitrarily specified and used to Static and Velocity Pressures, in H2O [kPa].
determine throw (T).
3.11.3 Velocity Pressure (VP). The pressure in a
3.3.6 Throw (T). The distance, ft [m], from the moving fluid, in H2O [kPa], capable of accelerating
center of the outlet to a point in the air stream where the same fluid from rest to the velocity of the fluid
the highest sustained velocity of the air stream has with complete conversion of pressure into kinetic
been reduced to a specified Terminal Velocity (see energy. In this standard, Velocity Pressure is a
Figure 1). Pressure calculated from duct area and flow rate, at
the point of Static Pressure measurement.
3.4 Area Factor (A k). An empirical factor of an outlet or
inlet, ft2 [m2], determined from the discharge or intake 3.12 Published Rating. A statement of the assigned values
velocity (Vk) and the volume flow rate, Q, cfm [m3/s]. of those performance characteristics, under stated Rating
Conditions, by which a unit may be chosen to fit its
Q ⎡ L s⎤ application. These values apply to all units of like nominal
Ak = ⎢ Ak = ⎥ size and type (identification) produced by the same
Vk ⎣ Vk ⎦
manufacturer. As used herein, the term Published Rating
includes the rating of all performance characteristics shown
3.5 Aspect Ratio. Ratio of the length/width of a on the heat pump or published in specifications, advertising
rectangular air outlet. or other literature controlled by the manufacturer, at stated
Rating Conditions.
3.6 Discharge or Intake Velocity (Vk). The average of the
velocities of the air stream, fpm [m/s], of an outlet or inlet, 3.12.1 Application Rating. A rating based on tests
measured at specified locations relative to the face of the performed at Application Rating Conditions (other
outlet or inlet with a specified instrument. than Standard Rating Conditions).
3.7 Flow Rate. The volume of standard air per unit of 3.12.2 Standard Rating. A rating based on tests
time, cfm [m3/s], which moves past a given plane. performed at Standard Rating Conditions.
3.8 Hertz (Hz). A unit of frequency equal to one cycle per 3.13 Rating Conditions. Any set of operating conditions
second. under which a single level of performance results and which
causes only that level of performance to occur.
3.9 Neck Velocity (Vn). This is measured in fpm [m/s] and
is calculated as follows: 3.13.1 Standard Rating Conditions. Rating
Conditions used as the basis of comparison of
Q ⎡ L s⎤ performance characteristics.
Vn = ⎢Vn = ⎥
An ⎣ An ⎦
3.14 "Shall" or "Should". "Shall" or "should" shall be
interpreted as follows:
2
ARI STANDARD 890-2001
1. Fixed
3.14.1 Shall. Where "shall" or "shall not" is used 2. Adjustable
for a provision specified, that provision is mandatory
if compliance with the standard is claimed.
Section 5. Test Requirements
3.14.2 Should. "Should" is used to indicate
provisions which are not mandatory but which are 5.1 Test Requirements. Diffusers and Diffuser
desirable as good practice. Assemblies shall be verified by tests conducted in
accordance with the provisions set forth in ASHRAE
3.15 Sound Power Level, Lw. This is ten times the Standard 70. One exception is that the single stationary
logarithm to the base ten of the ratio of the sound power microphone provision, as defined in 5.2 of ASHRAE
radiated by the source to a reference sound power, expressed Standard 70, shall be disallowed and the room qualification
in decibels (dB). The reference sound power used in this shall be in accordance with ANSI Standard 12.31.
standard is 1 picowatt (pW).
For the purposes of this standard, the highest sustained
3.16 Standard Air. Air weighing 0.075 lb/ft3 [1.2 kg/m3] velocity shall be the average velocity determined for a
which approximates dry air at 70°F [21°C] and at a period of not less than 30 seconds.
barometric pressure of 29.92 in Hg [101.3 kPa].
5.2 The procedures of Section 6 shall be used where
calculation procedures are required to develop the Standard
Section 4. Classifications Rating.
3
ARI STANDARD 890-2001
Exception: Where this velocity is outside the manufacturer's Octave Band Center Rating Tolerance,
recommended velocity, the unit shall be tested at the Frequencies, Hz dB
manufacturer's rated point. 125 6
250 4
Terminal Velocity.......………................150 fpm [0.76 m/s] 500 3
1000 3
6.3.1 Air flow rate shall be determined at the 2000 3
Standard Rating Conditions. 4000 3
4
ARI STANDARD 890-2001
A1.1 ANSI Standard S1.11-1986 (R1993), A1.4 ASHRAE Standard 70-1991, Method of
Octave- Band and Fractional Octave-Band Analog Testing for Rating the Performance of Air Outlets
and Digital Filters, 1993, American National and Inlets, 1991, American Society of Heating,
Standards Institute, 25 West 43rd Street, 4th Fl., New Refrigerating and Air-Conditioning Engineers, Inc.,
York, NY 10036, U.S.A. 1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A.
The following Recommendations have been made by the ISHRAE Standard Committee to
be incorporated in the Standard:-
------------X-----------