Make sure of the follow describe before start an engine fire pump.
Fuel lines (both supply and return) connected to fuel tank and engine
During an engine run, check instrument panel i.e. Oil pressure, Water
temperature gauge, Tachometer ( engine speed ) / Hour meter
SPENCO LIMITED
1000/31 Udomsuk 27, Sukhumvit 103 Bangna Banga Bangkok 10260 Thailand
1000/31 ซอยอุดมสุ ข 27, ถนนสุ ขมุ วิท 103 แขวงบางนา เขตบางนา กรุ งเทพฯ 10260
Tel : 02-383-9163 (10 Lines) Fax : 02-383-9162 E-mail : spenco@spenco.co.th
Check suction and discharge pipe, sensing line, vent pipe and priming pipe ( if
need )
Prime water in suction side and water level reservoir are prompt
SPENCO LIMITED
1000/31 Udomsuk 27, Sukhumvit 103 Bangna Banga Bangkok 10260 Thailand
1000/31 ซอยอุดมสุ ข 27, ถนนสุ ขมุ วิท 103 แขวงบางนา เขตบางนา กรุ งเทพฯ 10260
Tel : 02-383-9163 (10 Lines) Fax : 02-383-9162 E-mail : spenco@spenco.co.th
FIRE PUMP SYSTEM CHECK LIST
The fire pump is always ready to run in case of fire or emergency. Necessary inspection
procedure shall be done. These are describe certainly to prevent serious damage the
firefighting pump system.
Check both Heat Exchanger Auto loop line & Manual by-pass cooling line
Check the piping leaks if jockey pump start exceed 5 times per day
SPENCO LIMITED
1000/31 Udomsuk 27, Sukhumvit 103 Bangna Banga Bangkok 10260 Thailand
1000/31 ซอยอุดมสุ ข 27, ถนนสุ ขมุ วิท 103 แขวงบางนา เขตบางนา กรุ งเทพฯ 10260
Tel : 02-383-9163 (10 Lines) Fax : 02-383-9162 E-mail : spenco@spenco.co.th
FIELD FAILURE ALARM SIMULATION
Battery 1 failure : Turn breaker (CB1) in OFF or disconnect cable battery # 1 alarm will
sound. To reset alarm go to OFF mode
Battery 2 failure : Turn breaker (CB2) in OFF or disconnect cable battery # 2 alarm will
sound. To reset alarm go to OFF mode
Charger failure : Remove AC power from the diesel controller panel after
30 seconds delay, alarm will sound. To reset alarm go to OFF mode
Engine Overspeed : Jumper 3 & 6 or 3 & 8 alarm will sound To silence alarm, place
controller in the OFF mode.
Low oil pressure : Disconnect field wire 2, 9 & 10 and initial automatic start then an
engine will running. Jumper 2 & 6 or 2 & 8 after 15 seconds
delay alarm will sound. To silence alarm, place controller in the
OFF mode.
Fail to start :
a) Disconnect field wire 9 & 10 on fire pump controller & initial automatic start (place
controller in “TEST” mode)
b) Allow pressure to drop and begin cranking sequence
c) Wait for 180 seconds to allow for 3 cranks per battery (15 sec. cranking, 15 sec.
rest, 6 times)
d) Alarm will sound. To silence alarm, place controller in the OFF mode.