1) Open Function Chart Builder, click on PC section and click NEW.
6) Click on CONTRM block and Follow step 4 to select create. Select move and click on parameter
to set the number of Input/output to 8. Click OK x2 to create the Move Block. Double click the
Move block terminal 1-8 to assign the input and 21-28 to assign output. Double click on Move
block terminal 1 and click DB to select the Data Base Input DI800_1.1 and click OK. Same for
terminal 21, click on DB and select Data Base Output DO800_1.1. Follow the same for the rest
for DI800_1.2 to DI800_1.8 and DO800_1.2 to DO800_1.8 for terminal 2 to 8 and terminal 22 to
28.
Figure 10: Create Move Block
7) Save the PC Program and goto file\Generate source. Uncheck DB source and click ok to generate
the PC source.
Figure 18: Generate PC Source
8) Close the Function Chart Builder and go to Application Builder File\Convert. Select PC source
Code (*.AAX) from left and convert to right PC Source Code (*.AA).
Figure 20: Application builder\ convert
9) Open On-Line Builder and use command TRPCS srce:Test0101 to translate the PC source code to
controller.
Note: To Translate all the PC source code in the SRCE: Folder, use command #TRPCS SRCE:
Figure 23: TRPCS Command
11) Use command LSS to check the PC1 Special Status. The PC1 is in Build Mode after first Translate
from source code. Use DIBM PC1 to disable the PC1 build Mode and DBL PC1 to Deblock PC1
program. Only After DIBM and DBL the PC1 program then it is ready to use.