Nothing Special   »   [go: up one dir, main page]

Ba222pen 0608

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

Operating Instructions

Cerabar M PMC41/45, PMP41/45/46/48


Process pressure measurement

8
0,753
Zero Span
1 2 3
on address
Display

off

+ –

BA222P/00/en/06.08
71064505
Valid from software version:
1.1/1.2
Overview of documentation Cerabar M mit PROFIBUS PA

Overview of documentation

Device Documentation Contents

Cerabar M PROFIBUS PA Technical Information TI399P Technical data

Operating Instructions BA222P – Identification


– Installation
– Wiring
– Operation
– Commissioning
– Maintenance
– Troubleshooting and spare parts
– Appendix: illustration of menus

2 Endress+Hauser
Cerabar M mit PROFIBUS PA Table of contents

Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 4 9 Troubleshooting . . . . . . . . . . . . . . . . . 47
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 9.1 Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
1.2 Installation, commissioning and operation . . . . . . . . 4 9.2 Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 4 9.3 Error codes in V2H0 and V2H1 . . . . . . . . . . . . . . . 48
1.4 Notes on safety conventions and icons . . . . . . . . . . . 5 9.4 Simulation (Commuwin II only) . . . . . . . . . . . . . . . 49
1.5 Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . 6 9.5 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9.6 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
2 Identification . . . . . . . . . . . . . . . . . . . . 7 9.7 Repair of Ex-certified devices . . . . . . . . . . . . . . . . . 51
9.8 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 7 9.9 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 9.10 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.3 CE mark, Declaration of Conformity . . . . . . . . . . . . 9 9.11 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.4 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . 9
10 Technical data . . . . . . . . . . . . . . . . . . . 53
3 Installation . . . . . . . . . . . . . . . . . . . . . 10
3.1 Incoming acceptance and storage . . . . . . . . . . . . . . 10 11 Operating matrix . . . . . . . . . . . . . . . . . 54
3.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Installation instructions . . . . . . . . . . . . . . . . . . . . . 10 11.1 Matrix for Analog Input Block (AI Transmitter) . . . 55
3.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 18 11.2 Description of parameters . . . . . . . . . . . . . . . . . . . 55

4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 19 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.1 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 Connecting the device . . . . . . . . . . . . . . . . . . . . . . 20
4.3 Connecting the measuring unit . . . . . . . . . . . . . . . 22
4.4 Potential equalization . . . . . . . . . . . . . . . . . . . . . . 22
4.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 23

5 Operation . . . . . . . . . . . . . . . . . . . . . . 24
5.1 Onsite display (optional) . . . . . . . . . . . . . . . . . . . . 24
5.2 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3 Operation via Endress+Hauser operating program . 26

6 PROFIBUS-PA interface . . . . . . . . . . . 27
6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.2 Device address configuration . . . . . . . . . . . . . . . . . 27
6.3 Device master and type files (GSD) . . . . . . . . . . . . 28
6.4 Cyclic data exchange (Data_Exchange) . . . . . . . . . 30
6.5 Acyclic data exchange . . . . . . . . . . . . . . . . . . . . . . 32
6.6 Data format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.7 Configuration of parameter profiles . . . . . . . . . . . . 38

7 Commissioning. . . . . . . . . . . . . . . . . . 40
7.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.2 Onsite commissioning . . . . . . . . . . . . . . . . . . . . . . 40
7.3 Commissioning and operation . . . . . . . . . . . . . . . . 41
7.4 Locking/unlocking operation . . . . . . . . . . . . . . . . . 45
7.5 Information on the measuring point . . . . . . . . . . . 46

8 Maintenance. . . . . . . . . . . . . . . . . . . . 47
8.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Endress+Hauser 3
Safety instructions Cerabar M mit PROFIBUS PA

1 Safety instructions

1.1 Designated use


The Cerabar M is a pressure transmitter for measuring pressure and level.
The manufacturer accepts no liability for damages resulting from incorrect use or use other than that
designated.

1.2 Installation, commissioning and operation


The device is designed to meet state-of-the-art safety requirements and complies with applicable
standards and EC regulations. If used incorrectly or for anything other than the designated use, the
device can, however, be a source of danger e.g. product overflow due to incorrect installation or
configuration. Consequently, installation, connection to the electricity supply, commissioning,
operation and maintenance of the measuring system must be carried out by trained, qualified
specialists authorized to perform such work by the facility's owner-operator. The specialists must
have read and understood these Operating Instructions and must follow the instructions they
contain. Modifications and repairs to the device are permissible only if they are expressly approved
in the manual. Pay particular attention to the information and instructions on the nameplate.

1.3 Operational safety

1.3.1 Hazardous areas (optional)


Devices for use in hazardous areas are fitted with an additional nameplate (→ see from Page 7,
Section 2.1.1 "Nameplates"). If the measuring system is to be used in hazardous areas, applicable
national standards and regulations must be observed. The device is accompanied by separate
"Ex documentation", which is an integral part of this documentation. The installation regulations,
connection values and safety instructions listed in this Ex document must be observed. The
documentation number of the related safety instructions is also indicated on the additional
nameplate.
• Ensure that all personnel are suitably qualified.

4 Endress+Hauser
Cerabar M mit PROFIBUS PA Safety instructions

1.4 Notes on safety conventions and icons


In order to highlight safety-specific or alternative operating procedures in the manual, the following
conventions have been used, each indicated by a corresponding icon in the margin.

Symbol Meaning

#
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to
serious personal injury, a safety hazard or the destruction of the device.

"
Caution!
A caution highlights actions or procedures which, if not performed correctly, may lead to
personal injury or the incorrect operation of the device.

!
Note!
A note highlights actions or procedures which, if not performed correctly, can have an
indirect effect on operation or trigger an unexpected response on the part of the device.

0
Explosion-protected, type-examined equipment
If the device has this symbol embossed on its nameplate, it can be used in a hazardous area
or a non-hazardous area, depending on the approval.

Hazardous area

- Symbol used in drawings to indicate hazardous areas.


– Devices used in hazardous areas must possess an appropriate type of protection.

Safe area (non-hazardous area)

. Symbol used in drawings to indicate non-hazardous areas.


– Devices used in hazardous areas must possess an appropriate type of protection. Cables
used in hazardous areas must meet the necessary safety-related characteristic quantities.

% Direct current
A terminal to which DC voltage is applied or through which direct current flows.

&
Alternating current
A terminal to which alternating voltage (sine-wave) is applied or through which alternating
current flows.

)
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded by means of a
grounding system.

* Protective ground terminal


A terminal which must be connected to ground prior to establishing any other connections.

Equipotential connection

+ A connection that has to be connected to the plant grounding system: this may be a
potential equalization line or a star grounding system depending on national or company
codes of practice.

Endress+Hauser 5
Safety instructions Cerabar M mit PROFIBUS PA

1.5 Measuring system

1 4

3
ENDRESS + HAUSER
5

P01-PMx4xxxx-14-xx-xx-xx-000

Fig. 1: Cerabar M measuring system with PROFIBUS-PA protocol


1 Personal computer with operating program, e.g. FieldCare or Commuwin II
2 PROFIBUS-DP
3 Cerabar M pressure transmitter
4 PLC
5 Segment coupler
6 Fieldbus with PROFIBUS-PA

The complete measuring point in a simple application consists of:


• Cerabar M transmitter with PROFIBUS-PA protocol
• PLC or personal computer with an operating program, e.g. FieldCare or Commuwin II
• Segment coupler
• PROFIBUS-PA terminating resistor

1.5.1 Number of devices


The maximum number of transmitters on one bus segment is determined by their current
consumption, the power of the bus coupler and the required bus length, see Operating Instructions
BA198F/00/en. In general, however, the maximum number of transmitters that can be operated
on one bus segment is as follows:
• Max. 9 Cerabar M for hazardous area applications
• Max. 32 Cerabar M for non-hazardous area applications
Cerabar M has a max. current consumption of 11 mA ± 1 mA per device.

Refer also to:


PROFIBUS-PA Specification EN 50170 (DIN 19245), for Ex areas: EN 50 020, FISCO model or visit
http://www.PROFIBUS.com.

6 Endress+Hauser
Cerabar M mit PROFIBUS PA Identification

2 Identification

2.1 Device designation

2.1.1 Nameplates

! Note!
• The MWP (maximum working pressure) is specified on the nameplate. This value refers to a
reference temperature of 20°C (68°F), or a temperature of 100°F for ANSI flanges.
• The pressure values permitted at higher temperatures can be found in the following standards:
– EN 1092-1: 2001 Tab. 181)
– ASME B 16.5a – 1998 Tab. 2-2.2 F316
– ASME B 16.5a – 1998 Tab. 2.3.8 N10276
– JIS B2230
• The test pressure corresponds to the overpressure limit (OPL) of the device = MWP x 1.52).
• The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The
abbreviation "PS" corresponds to the MWP (maximum working pressure) of the measuring
device.

Nameplate of the aluminum housing

Made in Germany,
Cerabar M D-79689 Maulburg
Order Code: 1
Ser.-No.: 2
p 3
Span 4
M.W.P.: 5
6
7
Mat. 8 10
9
Bei Sauerstoffeinsatz 11
for oxygen service 12
16
14 15 17
13

P01-PMx4xF18-18-xx-xx-xx-000

Fig. 2: Nameplate for Cerabar M with aluminium housing


➀ Order code
See the specifications on the order confirmation for the meanings of the individual letters and digits.
➁ Serial number
➂ Nominal measuring range
➃ Minimum/maximum span
➄ MWP (Maximum working pressure)
➅ Electronic version (output signal)
➆ Supply voltage
➇ Wetted materials
➈ Wetted materials
➉ Wetted materials
Maximum pressure for oxygen applications (optional for devices, suitable for oxygen applications)
Maximum temperature for oxygen applications (optional for devices, suitable for oxygen applications)
ID number of notified body with regard to Pressure Equipment Directive (optional)
ID number of notified body with regard to ATEX (optional)
5 SIL-symbol for devices with SIL2/IEC 61508 Declaration of conformity (optional)
6 Degree of protection
7 CRN number (optional)

1) With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO in EN 1092-1 Tab. 18. The chemical
composition of the two materials can be identical.
2) The equation does not apply for PMP41, PMP45 and PMP48 with a 100 bar measuring cell.

Endress+Hauser 7
Identification Cerabar M mit PROFIBUS PA

Nameplate of the stainless steel housing

Mat. 8 9
10
Made in Germany,
Cerabar M D-79689 Maulburg Bei Sauerstoffeinsatz
Order Code: 1 for oxygen service
Ser.-No.: 2 11 12
p 3 13
Span 4 14
M.W.P.: 5
6 15 17 18
7 16

P01-PMx4xF15-18-xx-xx-xx-000

Fig. 3: Nameplate for Cerabar M with stainless steel housing


➀ Order code
See the specifications on the order confirmation for the meanings of the individual letters and digits.
➁ Serial number
➂ Nominal measuring range
➃ Minimum/maximum span
➄ MWP (maximum working pressure)
➅ Electronic version (output signal)
➆ Supply voltage
➇ Wetted materials
➈ Wetted materials
➉ Wetted materials
Maximum pressure for oxygen applications (optional for devices, suitable for oxygen applications)
Maximum temperature for oxygen applications (optional for devices, suitable for oxygen applications)
Degree of protection
CRN number (optional)
5 ID number of notified body with regard to ATEX (optional)
6 ID number of notified body with regard to Pressure Equipment Directive (optional)
7 A3 symbol for devices with A3 (optional)
8 SIL-symbol for devices with SIL2/IEC 61508 Declaration of conformity (optional)

Additional nameplate
Devices for use in hazardous areas are fitted with an additional nameplate.

8 Endress+Hauser
Cerabar M mit PROFIBUS PA Identification

2.2 Scope of delivery


The scope of delivery comprises:
• Cerabar M pressure transmitter
• Optional accessories
Documentation supplied:
• Operating Instructions BA222P (this document)
• Final inspection report
• Optional: factory calibration certificate
• Devices that are suitable for use in hazardous areas:
additional documentation such as Safety Instructions, Control or Installation Drawings

2.3 CE mark, Declaration of Conformity


The devices are designed to meet state-of-the-art safety requirements, have been tested and left the
factory in a condition in which they are safe to operate. The devices comply with the applicable
standards and regulations as listed in the EC Declaration of Conformity and thus comply with the
statutory requirements of the EC Directives. Endress+Hauser confirms the successful testing of the
device by affixing to it the CE mark.

2.4 Registered trademarks

KALREZ, VITON, TEFLON


Registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA
PROFIBUS PA
Registered trademark of the PROFIBUS Trade Organisation, Karlsruhe, D
TRI-CLAMP
Registered trademark of Ladish & Co., Inc., Kenosha, USA
GORE-TEX®
Registered trademark of W.L. Gore & Associates, Inc., USA

Endress+Hauser 9
Installation Cerabar M mit PROFIBUS PA

3 Installation

3.1 Incoming acceptance and storage

3.1.1 Incoming acceptance


• Check the packaging and the contents for damage.
• Check the shipment, make sure nothing is missing and that the scope of supply matches your
order.

3.1.2 Storage
The device must be stored in a dry, clean place and protected against damage from impact
(EN 837-2).
Storage temperature range:
• –40 to +100°C (–40 to +212°F)
• Onsite display: –40 to +80°C (–40 to +176°F)

3.2 Installation conditions

3.2.1 Dimensions
→ For dimensions, please refer to the Technical Information for Cerabar M TI399P, "Mechanical
construction" section.

3.3 Installation instructions


! Note!
• Due to the orientation of the Cerabar M, there may be a shift in the zero point, i.e. when the
container is empty, the measured value does not indicate zero. The position-dependent zero point
shift can be corrected directly at the device via 2 keys → see Page 44, Section 7.3.8 "Position
adjustment - only display (bias pressure)" (onsite operation) or via communication → see Page 45,
Section 7.3.9 "Zero point correction".
• For PMP46 and PMP48, please pay attention to Page 14, Section 3.3.2 "Installation instructions
for devices with diaphragm seals – PMP46, PMP48".
• The onsite display can be rotated in 90° stages.
• Endress+Hauser offers a mounting bracket for installation on pipes or walls.
→ See Page 17, Section 3.3.4 "Wall and pipe-mounting (optional)".

10 Endress+Hauser
Cerabar M mit PROFIBUS PA Installation

3.3.1 Installation instructions for devices without a diaphragm seal –


PMC41, PMC45, PMP41, PMP45

! Note!
• If a heated Cerabar M is cooled during a cleaning process (e.g. by cold water), a vacuum develops
for a short time, whereby moisture can penetrate the sensor through the pressure compensation
➀. If this is the case, mount the Cerabar M with the pressure compensation ➀ pointing
downwards.


• Keep the pressure compensation and GORE-TEX filter ➀ free from dirt.
®

• Cerabar M devices without diaphragm seals are mounted as per the norms for a manometer
(DIN EN 839-2). We recommend the use of shutoff devices and siphons. The orientation depends
on the measuring application.
• Do not clean or press the diaphragm with hard or pointed objects.

Pressure measurement in gases

P01-PMx4xxxx-11-xx-xx-xx-002

Fig. 4: Measuring arrangement for pressure measurement in gases


➀ Cerabar M
➁ Shutoff device

• Mount Cerabar M with shutoff device above the tapping point so that the condensate can flow
into the process.

Endress+Hauser 11
Installation Cerabar M mit PROFIBUS PA

Pressure measurement in steam




P01-PMx4xxxx-11-xx-xx-xx-003

Fig. 5: Measuring arrangement for pressure measurement in steam


➀ Cerabar M
➁ Shutoff device
➂ U-shaped siphon
➃ Circular siphon

• Mount Cerabar M with siphon above the tapping point.


The siphon reduces the temperature to almost ambient temperature.
• Fill the siphon with liquid before commissioning.

Pressure measurement in liquids

P01-PMx4xxxx-11-xx-xx-xx-004

Fig. 6: Measuring arrangement for pressure measurement in liquids


➀ Cerabar M
➁ Shutoff device

• Mount Cerabar M with shutoff device below or at the same level as the tapping point.

12 Endress+Hauser
Cerabar M mit PROFIBUS PA Installation

Level measurement

P01-PMx4xxxx-11-xx-xx-xx-005

Fig. 7: Measuring arrangement for level

• Always mount Cerabar M below the lowest measuring point.


• Do not mount the device at the following positions:
In the filling curtain, in the tank outlet or at a point in the tank which could be affected by pressure
pulses from an agitator.
• Do not mount the device in the suction area of a pump.
• The calibration and functional test can be carried out more easily if you mount the device after a
shutoff device.

PMP41 mounting
PMP41 is available with a flush-mounted diaphragm or an adapter and an internal diaphragm. The
adapter can be screwed on or welded in. A seal is enclosed depending on the version and material
used.

Threaded version: Welded version:

SW 27

SW 25
SW 32

P01-PMP41xxx-06-09-xx-xx-004 P01-PMP41xxx-06-09-xx-xx-005

Fig. 8: The flush-mounted version is screwed together Fig. 9: Screw the complete device into the process
with the adapter using a torque of 50 Nm. Screw thread with max. 80 Nm (at AF 25).
the complete device into the process thread with
max. 80 Nm (at AF 32).

Endress+Hauser 13
Installation Cerabar M mit PROFIBUS PA

Threaded connection, flush-mounted diaphragm

– Einschweißadapter
Bestell-Nr.: 52002643
– mit 3.1 Abnahmeprüfzeugnis
Bestell-Nr.: 52010172
SW 27

21
Viton-Dichtung

13

21
ø26
ø50

max. Druckfestigkeit
100 bar
O-Ring 14 x 1,78
Viton oder NBR
P01-PMP41xxx-06-09-xx-xx-001

Fig. 10: The flush-mounted version is screwed into the process thread with max. 50 Nm ± 5 Nm (at AF 27).

3.3.2 Installation instructions for devices with diaphragm seals –


PMP46, PMP48

! Note!
• The Cerabar M with a diaphragm seal is screwed in, flanged or clamped, depending on the type
of diaphragm seal.
• Together, a diaphragm seal and the pressure transmitter form a closed, calibrated system which
is filled with oil. The filling hole is sealed and should not be opened.
• Do not clean or press the diaphragm of the diaphragm seals with hard or pointed objects.
• Do not remove diaphragm protection until shortly before installation.
• When using a mounting bracket, sufficient strain relief must be ensured for the capillaries in order
to prevent the capillary from buckling (bending radius ≥ 100 mm).
• Please note that the hydrostatic pressure of the liquid columns in the capillaries can cause zero
point shift. The position-dependent zero point shift can be corrected directly at the device via
2 keys → see Page 44, Section 7.3.8 "Position adjustment - only display (bias pressure)" (onsite
operation) or via communication → see Page 45, Section 7.3.9 "Zero point correction".
• Please note the application limits of the diaphragm seal filling oil as detailed in the Technical
Information for Cerabar M TI399P, "Planning instructions for diaphragm seal systems" section.
In order to obtain more precise measurement results and to avoid a defect in the device, mount the
capillaries as follows:
• Vibration-free (in order to avoid additional pressure fluctuations)
• Not in the vicinity of heating or cooling pipes
Insulate if the ambient temperature is below or above the reference temperature
• With a bending radius of ≥ 100 mm.

14 Endress+Hauser
Cerabar M mit PROFIBUS PA Installation

Vacuum application
For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter
below the diaphragm seal. This prevents a vacuum load of the diaphragm seal caused by the
presence of filling oil in the capillaries.
When the pressure transmitter is mounted above the diaphragm seal, the maximum height
difference H1 - as illustrated in the diagram below left - must not be exceeded. The maximum
height difference depends on the density of the filling oil and the lowest pressure that is permitted
to occur at the diaphragm seal (empty tank), see the following illustration.

H1

P01-PMP4xxxx-11-xx-xx-xx-001 P01-PMx7xxxx-05-xx-xx-xx-011

Fig. 11: Installation above the diaphragm Fig. 12: Diagram of maximum installation height above the
seal diaphragm seal for vacuum applications as a function of
the pressure at the diaphragm seal

Mounting with temperature isolator

max. 115

P01-PMP4xxxx-11-xx-xx-xx-006

Endress+Hauser recommends the use of temperature isolators in the event of constant extreme fluid
temperatures which lead to the maximum permissible electronics temperature of +85°C (+185°F)
being exceeded. To minimize the influence of rising heat, Endress+Hauser recommends the device
be mounted horizontally or with the housing pointing downwards.
The additional installation height also brings about a zero point shift of approx. 21 mbar due to the
hydrostatic column in the temperature isolator. The position-dependent zero point shift can be
corrected directly at the device using 2 keys → see Page 44, Section 7.3.8 "Position adjustment -
only display (bias pressure)" (onsite operation) or via communication → see Page 45, Section 7.3.9
"Zero point correction".

Endress+Hauser 15
Installation Cerabar M mit PROFIBUS PA

Mounting with capillary tube


The housing of the Cerabar M can be mounted with a capillary tube to one side of the measuring
point to protect from high temperatures, moisture or vibration, or in cases where the mounting
point is not easily accessible.
A bracket for mounting on a wall or pipe is available for this purpose.

184.5

101 (121)
60.3
81
70

26

119.5

167
101 (121)

3
26

102.5

P01-PMx4xxxx-11-xx-xx-xx-006

Fig. 13: Mounting with capillary tube and bracket away from the measuring point. Values in brackets apply to devices
with a raised cover.
➀ Mounting location away from the measuring point.
➁ Measuring point: very humid, hot, with strong vibrations or difficult to access

16 Endress+Hauser
Cerabar M mit PROFIBUS PA Installation

3.3.3 Seal for flange mounting

➀ ➁

P01-FMD7xxxx-11-xx-xx-xx-002

Fig. 14: Mounting the versions with flange or diaphragm seal


➀ Diaphragm
➁ Seal

# Warning!
The seal is not allowed to press down on the diaphragm as this could affect the measurement result.

3.3.4 Wall and pipe-mounting (optional)


Endress+Hauser offers a mounting bracket for installing on pipes or walls for PMC41, PMP41,
PMP46 and PMP48. You can order the mounting brackets either via the order code or separately
as an accessory.
PMC41
• Order number: 919806-0000
• Material: AISI 304 (1.4301)
PMP41, PMP46 and PMP48
• Order number: 52001402
• Material: AISI 304 (1.4301)

176
159 179.2
162.2 106 (126)
115 (129)
115 (135)
125 (140)

3
6

60.3
81
70

29
20

94 111

P01-PMC41xxx-17-xx-xx-xx-000

Wall and pipe-mounting PMC41

Endress+Hauser 17
Installation Cerabar M mit PROFIBUS PA

167.5
170.7 184.5
187.6

108 (122)
99 (119)

108 (122)
99 (119)
3

6
60.3

81
70

26
26

102.5 119.5

P01-PMP41xxx-17-xx-xx-xx-000

Wall and pipe-mounting PMP41

The dimensions in brackets apply to housings with a raised cover (for optional display). Dimensions written in
italics apply to devices with an aluminum housing.

167.5 184.5
170.7 187.6
108 (122)
99 (119)

108 (122)
99 (119)
3

60.3
81
70

26
26

102.5 119.5

P01-PMP4xxxx-17-xx-xx-xx-000

Wall and pipe-mounting PMP46/PMP48

The dimensions in brackets apply to housings with a raised cover (for optional display). Dimensions written in
italics apply to devices with an aluminum housing.

3.4 Post-installation check


After installing the device, carry out the following checks:
• Are all the screws firmly tightened?
• Are the housing covers screwed down tight?

18 Endress+Hauser
Cerabar M mit PROFIBUS PA Wiring

4 Wiring

4.1 Electrical connection


! Note!
Cerabar M with a PROFIBUS-PA output is a two-wire transmitter. Note the following before
connecting the device:
• Turn off the power supply.
• Ground the device using the external ground terminal.

4.1.1 Power supply


The Cerabar M has the following connection values:

I = 11 mA ± 1 mA
Non-hazardous area: U = 9 to 32 V DC
Hazardous area: U = 9 to 24 V DC

4.1.2 Bus cable


Endress+Hauser recommends you use a twisted, shielded twin-core cable. The following values
must be observed for installation in Ex areas (EN 50020, FISCO model):

Loop-resistance (DC): 15 to 150 W/km


Inductance per unit length: 0.4 to 1 mH/km
Capacitance per unit length: 80 to 200 nF/km

The following are examples of suitable cable types:

Non-hazardous area:

• Siemens 6XV1 830-5BH10 (gray)


• Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL (gray)
• Belden 3076F (orange)
Hazardous area:
• Siemens 6XV1 830-5AH10 (blue)
• Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL (blue)

4.1.3 Shielding
For maximum EMC protection, e.g. near frequency convertors, it is advisable to connect the
housing and cable shielding using a potential matching line (PML). (Max. wire cross-section:
2.5 mm², fixed conductor)

Please pay attention to the following points:

• Ground the device using the external ground terminal.


• The bus cable shield may not be interrupted.
• Ground the shield at each end of the cable, and always try to keep the connecting cable between
the shielding and ground as short as possible.
• If there are large potential differences between the individual grounding points, you only need to
connect one point to the reference ground. Connect all the other ends of the shield via a
HF-enabled capacitor with reference potential (e.g. ceramic capacitor 10 nF/250 V~).

Endress+Hauser 19
Wiring Cerabar M mit PROFIBUS PA

" Caution!
Multiple protective shield grounding is only permitted under specific conditions in applications
subject to explosion protection, see EN 60079-14.
Further information on the layout and grounding of the network is provided in Operating
Instructions BA198F "PROFIBUS-PA: Guidelines for planning and commissioning" and in the
PROFIBUS-PA Specification EN 50170 (DIN 19245).

4.2 Connecting the device


! Note!
• When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings.
• Protective circuits to prevent reverse polarity, HF influences and overvoltage peaks are installed.
• The shield or grounding (if present) must always be connected to the internal ground terminal o
in the housing.
• The supply voltage must match the power supply on the nameplate (→ see Page 7ff.,
Section 2.1.1 "Nameplates").
• Switch off the supply voltage before connecting the device.
• Unscrew the housing cover.
• If present, remove the retaining ring with the onsite display.
– Push up the latch with the arrow until the grip of the retaining ring is audibly released.
– Release the retaining ring carefully to prevent damage to the display cables. The connector of
the display can remain plugged in.
• Guide the cable through the gland. Preferably use twisted, shielded two-wire cable.
• Connect the device in accordance with the following diagram.
• Where applicable, refit the retaining ring with the onsite display. The grip of the retaining ring
clips in with an audible click.
• Screw down housing cover.
• Switch on supply voltage.

➀ ➁
+ -

Zero Span
1 2 3
on address
Display

off

+ –

P01-PMx4xxxx-04-xx-xx-xx-012

Fig. 15: PROFIBUS PA electrical connection


➀ Disassembling the onsite display: To release the retaining ring from the electronic insert, push up the latch with
the arrow.
➁ The terminal n on the electronic insert is for grounding and is already wired internally. If the connecting cable
also has a shielding or ground cable within it, then this may only be connected to the internal ground terminal o
of the housing, not to terminal n. The terminals are designed to take one wire each.

20 Endress+Hauser
Cerabar M mit PROFIBUS PA Wiring

4.2.1 Connecting devices with Harting connector Han7D

Cerabar M
+
7
+ – – 8 6
1
2 5
3 4
Han7D

+ –
P01-PMx4xxxx-04-xx-xx-xx-003

Fig. 16: Left: electrical connection for devices with Harting connector Han7D
Right: view of the connector at the device

4.2.2 Connecting devices with M12 connector

Cerabar M

+ –
– +

M12

+ –
P01-PMx4xxxx-04-xx-xx-xx-004

Fig. 17: Left: electrical connection for devices with M12 connector
Right: view of the connector at the device

4.2.3 Connecting the cable version

rd +
+
bk –

gnye
PE
4...20 mA

P01-PMx4xxxx-04-xx-xx-xx-010

Fig. 18: rd = red, bk = black, gnye = green-yellow

Endress+Hauser 21
Wiring Cerabar M mit PROFIBUS PA

4.2.4 Connecting the valve connector M16, ISO4400

Cerabar M 3
1 2 3 4...20 mA
2 1
+
4...20 mA
-
BN BU GNYE

1 2
+ -

4...20 mA
P01-PMx4xxxx-04-xx-xx-xx-009

Fig. 19: BN = brown, BU = blue, GNYE = green/yellow

4.3 Connecting the measuring unit

4.3.1 Supply voltage

! Note!
• When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings.
• All explosion protection data are given in separate documentation which is available upon
request. The Ex documentation is supplied as standard with all devices approved for use in
hazardous areas.
Supply voltage
• For non-hazardous areas: 9...32 V DC

4.3.2 Cable specification


• Endress+Hauser recommends using twisted, shielded two-wire cables.
• Terminals for wire cross-sections: 0.14 to 2.5 mm2
• Cable outer diameter: 5 to 9 mm

4.3.3 Shielding/potential matching


• You achieve optimum shielding against interference influences if the shielding is connected on
both sides (in the cabinet and at the device). If potential equalization currents are expected in the
plant, only ground the shielding on one side, preferably at the transmitter.
• When using in hazardous areas, you must observe the applicable regulations.
Separate Ex documentation with additional technical data and instructions is included with all
Ex devices as standard.

4.4 Potential equalization


Ex applications: Connect all devices to the local potential equalization system.
Observe the applicable regulations.

22 Endress+Hauser
Cerabar M mit PROFIBUS PA Wiring

4.5 Post-connection check


Perform the following checks after completing electrical installation of the device:
• Does the supply voltage match the specifications on the nameplate?
• Is the device connected as per → Section 4.2?
• Are all the screws firmly tightened?
• Are the housing covers screwed down tight?
The connected onsite display lights up as soon as voltage is applied to the device.

Endress+Hauser 23
Operation Cerabar M mit PROFIBUS PA

5 Operation

5.1 Onsite display (optional)


A plug-in onsite display is used as the display unit. The display can be rotated in 90° stages.

0% 50% 100%

0…1 bar

P01-PMx4xxxx-07-xx-xx-xx-000

Fig. 20: Onsite display


➀ 4-digit display of measured values and input parameters
➁ Bar graph, display of current measured value
➂ Nominal measuring range

5.1.1 Function of the onsite display


The onsite display has two display modes:
• Display in measurement mode: This is shown as standard.
• Display in calibration mode: This is shown after pressing the Zero or Span key once. It returns
automatically to measurement mode display after 2 seconds.
The bar graph displays the current value (4 to 20 mA) belonging to the pressure value.

A:
0.753
0.753 ➀ ➁
B:

0…1 bar ➃ S
Z 0.250

P01-PMx4xxxx-07-xx-xx-xx-001

Fig. 21: Function of the onsite display


A Display in measuring mode
B Display in calibration mode
➀ Lower-range value
➁ Upper-range value
➂ Set measuring range in measuring limits
➃ Display of calibration point (Z (Zero) = lower-range value (LRV) or S (Span) = upper-range value (URV))

24 Endress+Hauser
Cerabar M mit PROFIBUS PA Operation

5.2 Operating elements

5.2.1 Position of the operating elements on the electronic insert


The onsite display is supplied ready-mounted if it is ordered with the device. In such instances, the
onsite display with the retaining ring must be released from the electronic insert before operating.
Removing the display:
• Push up the latch with the arrow until the grip of the retaining ring on the electronic insert is
audibly released.
• Release the retaining ring and lift off carefully to prevent damage to the display cables.
• During operation, you can fit the display onto the edge of the housing.


Zero Span
1 2 3
on address
Display ➂
off

+ –

Fig. 22: Position of operating elements


➀ Key for setting the lower-range value
➁ Position adjustment
➂ Key for setting the upper-range value
➃ Address switch

5.2.2 Function of the operating elements


Use the "Zero" and "Span" keys to set the lower-range value and upper-range value of the bar graph
in the display module. These settings do not have any effect on the digital output value (OUT value)
and the "measured value" in the matrix field V0H0.

No. Operating element Function

➀ Key for lower-range value The value currently saved for the lower-range value
(zero point) is displayed and the pressure present is
accepted as the lower-range value.

➁ Key for upper-range value The value currently saved for the upper-range value
is displayed and the pressure present is accepted as the
upper-range value.

➂ Bias key combination: The value currently saved for the bias pressure is
Key for lower-range value and key for upper-range displayed and the pressure present is accepted as the
value bias pressure.

➃ Address switch Set device address in the bus (→ see Page 27,
Section 6.2 "Device address configuration")

If the display does not show zero after calibrating the lower-range value at zero operating pressure
(position-dependent), it can be corrected to zero by adopting a bias pressure.

Endress+Hauser 25
Operation Cerabar M mit PROFIBUS PA

5.3 Operation via Endress+Hauser operating program

5.3.1 FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare,
you can configure all Endress+Hauser devices as well as devices from other manufacturers that
support the FDT standard.
FieldCare supports the following functions:
• Configuration of transmitters in online operation
• Loading and saving device data (upload/download)
• Documentation of the measuring point
Connection options:
• PROFIBUS PA via segment coupler and PROFIBUS interface card

! Note!
For more information, see → www.endress.com.

5.3.2 Commuwin II
With the Commuwin II display and operating program, Cerabar M can be configured and operated
as follows:
• Via matrix operation or
• Via graphic operation
For this, the corresponding server (e.g. HART or ZA672) must be activated. For a description of the
Commuwin II operating program, see Operating Instructions BA124F.

Matrix operation (Device parameter menu)


You can access the extended functions of the
Cerabar M using the "Device parameter/matrix
operation" menu.
• Each row is assigned to a function group.
• Every field represents a parameter.
• The setting parameters are entered in the
appropriate fields and confirmed with ↵ .

P01-PMx4xxxx-20-xx-xx-en-001

Graphic operation
Commuwin II offers graphic templates for
certain configuration procedures which you can
access via the "Device parameter/graphic
operation" menu. The parameter changes are
entered directly here and confirmed with ↵.

P01-PMx4xxxx-20-xx-xx-en-002

26 Endress+Hauser
Cerabar M mit PROFIBUS PA PROFIBUS-PA interface

6 PROFIBUS-PA interface

6.1 Overview

FieldCare/
Commuwin II
1

RS485 PROFIBUS-DP

5
IEC61158-2
31,25 kbit/s

6 PROFIBUS-PA IEC 61158-2


31,25 kbit/s

P01-PMx4xxxx-14-xx-xx-xx-002

Fig. 23: PROFIBUS-PA schematic diagram


➀ PLC
➁ Process control system
➂ RS485 up to 12 Mbit/s
➃ Segment coupler
➄ Non-Ex area
➅ Ex area

! Note!
Additional planning information for PROFIBUS-PA can be found in the Operating Instructions
BA198F/00/en.

6.2 Device address configuration


An address must be assigned to every PROFIBUS-PA device. If the address is not set correctly, the
device will not be recognized by the process control system.
• Valid device addresses are in the range from 0 to 126. All devices are delivered with the software
address 126 on leaving the factory.
• A device address may appear only once within a particular PROFIBUS-PA network. Please refer
also to the Operating Instructions BA198F for further information.

Endress+Hauser 27
PROFIBUS-PA interface Cerabar M mit PROFIBUS PA

The address 126 set at the factory can be used to check the function of the device and to connect
to a PROFIBUS-PA network already in operation. Afterwards the address should be changed to
allow other devices to be connected to the network.
There are two ways of assigning an address to a Cerabar M:
• With software using an operating program, (DP Class 2 master e.g. Communwin II or
• Locally via DIP switches. The DIP switches are located on the electronic insert.

Zero Span
1 2 3
on address
Display

off

2 + 8 = 10
SW
1 2 4 8 16 32 64 HW Value

ON
OFF
1 2 3 4 5 6 7 8 Switch No.

P01-PMx4xxxx-19-xx-xx-xx-040

Fig. 24: Example for setting the device address via the address switches: set to address 10

6.2.1 Setting the address mode


Set the address mode via switch 8:
• ON = Software addressing via the bus system
(default setting, SW)
• OFF = Hardware addressing, the device address must then be set via DIP switches 1-7.

6.2.2 Hardware addressing


Proceed as follows to set a hardware address:
1. Set DIP switch 8 to OFF.
2. Set address using DIP switches 1-7 in accordance with the table below.
3. You have to wait 10 seconds for a change in address to take effect.

Switch no. 1 2 3 4 5 6 7

Weighting in "ON" position 1 2 4 8 16 32 64


Weighting in "OFF" position 0 0 0 0 0 0 0

6.2.3 Software addressing


Please refer to Operating Instructions BA198F for the procedure for addressing devices via software.

6.3 Device master and type files (GSD)


A device master file (GSD) contains a description of the properties of a PROFIBUS-PA device, e.g.
what data transmission rate the device supports or what digital information the PLC gets from the
device and in what format. Bitmap files also belong to the GSD files. These allow the measuring
points to be represented as a graphic. The device master file and corresponding bitmaps are required
to plan the PROFIBUS-DP network.

28 Endress+Hauser
Cerabar M mit PROFIBUS PA PROFIBUS-PA interface

Every device is allocated an ID number by the PROFIBUS User Organization (PNO). The name of
the device master file (GSD) is derived from this. For Endress+Hauser, this ID number always starts
with "15XX", where "XX" stands for the device name.

Name of device ID No. GSD Type file Bitmaps

Cerabar M 151C (hex) EH3x151C.gsd EH3151Cx.200 EH151C_d.bmp


EH151C_n.bmp
EH151C_s.bmp

The full set of GSD files for all Endress+Hauser devices can be obtained as follows:
• Internet:
– Endress+Hauser È http://www.de.endress.com
Products Product program È Process Solutions È PROFIBUS GSD files
– PNO È http://www.de.PROFIBUS.com (GSD library)
• CD-ROM
– Directly from Endress+Hauser: order no. 56003894

! Note!
The PNO provides a universal database file called PA_x9700.gsd for devices with one Analog
Output Block. This file supports the transmission of the primary measured value. This database file
does not support the transmission of a second measured value (2nd cyclic value) or a display value
(Display value). The universal profile must be selected via matrix field V6H0 in Commuwin II.

6.3.1 Working with GSD files


The GSD files must be loaded into a specific subdirectory in the PROFIBUS-DP network design
software of your PLC.
• GSD files and bitmaps that are located in the "Extended" directory are used, for example, for the
configuration software STEP7 of the Siemens S7-300/400 PLC family.
• x.200 files and bitmaps that are located in the "Typdat5x" directory are used for the configuration
software COM ET200 with Siemens S5.
• GSD files that are located in the "Standard" directory
are for PLCs that support the "identifier byte" (0x94) but not the "identifier format". They can be
used with an Allen-Bradley PLC5, for example.
More details about the directories used for storing the GSD files can be found in the Operating
Instructions BA198F.

Endress+Hauser 29
PROFIBUS-PA interface Cerabar M mit PROFIBUS PA

6.4 Cyclic data exchange (Data_Exchange)

Messgröße Display
Sensor Physical Block
mit Skalierung
Signalanpassung Gerätespezifische
Eigenschaften,
z. B. Softwareversion z. B. SPS
V6H5
1 0
Transducer
Block Analog Input Block
Messwert- V0H0 Bearbeitung der Messgröße OUT
anpassung für das Prozessleitsystem, value status

V6H6 z. B. Skalierung, Statuszuweisung


E+H Matrix
V0H0
V0H0 V6H6 0 = Sensor value (V7H8)
1 = Trimmed value (V9H7) V6H4 OUT SV
2 = Biased value (V9H8) value status

Display value to V6H6 IN


value status

P01-PMx4xxxx-02-xx-xx-en-000

Fig. 25: Block model for Cerabar M with PROFIBUS-PA Profile 3.0
The values in brackets indicate the matrix position in the operating program.

6.4.1 Block model


The block model of a Cerabar M is shown in → Fig. 25. The primary measured value V0H0 is
transferred from the Transducer Block to the Analog Input Block. Here, the measured value is scaled
and limit values added before being output to the PLC as the variable OUT during cyclic data
communication. A value and the related status is transmitted with the variable OUT.

The onsite display and the matrix field V0H0 normally show the same value. However, a cyclic
output value (Display value) can also be made available to the onsite display via a PLC. For this, the
matrix field V6H5 in Commuwin II must be set to "Display Value" or "1". Example: Two Cerabar
M transmitters measure the pressure drop across a filter. The differential pressure is registered in
the PLC and then allocated to the matrix field V6H6.

A Cerabar M can output a secondary value to the PLC. A value can be selected via the field V6H4
in Commuwin II.

6.4.2 Configuration
The data exchange must be configured via a network design tool and a operating program.
1. Use the network design tool for your PLC and add the Cerabar M to the network. Ensure that
the address assigned corresponds to the set device address.
2. Select Cerabar M and start the configuration program. Four options appear: "Main process
value", "2nd cyclic value", "Display value" and "FREE PLACE".
3. Select "Main process value". If no other values are required, close the configuration window,
otherwise
4. Select "2nd cyclic value" or "FREE PLACE" (= function disabled) and select "Display value" or
"FREE PLACE" (= function disabled). Then close the configuration window.
5. Start operating program and establish the connection to the bus using the server PA-DPV1
(Commuwin II) or PROFIdtmDPV1 (FieldCare). Then generate a live list, locate the device
address and click Cerabar M.
6. Open the device menu. Select the operating matrix (Commuwin II only).
7. If required, select a secondary measured value via the matrix field V6H4:

30 Endress+Hauser
Cerabar M mit PROFIBUS PA PROFIBUS-PA interface

0 = Sensor value, 1 = Trimmed value, 2 = Biased value.


8. To display a cyclic output value (Display value) on the onsite display, set V6H5 = "Display
value" (or "1").
9. The data exchange is now configured for this Cerabar M.

6.4.3 Cerabar M È PLC (input data)


With the Data_Exchange service, a PLC can read the input data from a Cerabar M in the response
telegram. The cyclic data telegram has the following structure.

Input data Data Access Data format/comments


index

0, 1, 2, 3 Pressure primary value Read 32-bit floating point number


(IEEE-754)

4 Status code for primary value Read See status codes

5, 6, 7, 8 Secondary value, Sensor value, Read 32-bit floating point number


Trimmed value or Biased value (IEEE-754)

9 Status code for secondary value Read See status codes

6.4.4 PLCÈ Cerabar M (output data)


The output data from the PLC to the onsite display have the following structure:

Output data index Data Access Data format/comments


0, 1, 2, 3 Display value Write 32-bit floating point number
(IEEE-754)

4 Status code Write See status codes for secondary value

6.4.5 Status codes


The following status codes are supported by the Cerabar M for the measured value and secondary
measured value:

Status code Device status Meaning Primary Secondary


value measured
value

0F Hex BAD Non-specific x x

1F Hex BAD Out of service (target mode) x

47 Hex UNCERTAIN Last valid value (failsafe mode active) x

4B Hex UNCERTAIN Substitute quantity (failsafe mode active) x

4F Hex UNCERTAIN Initial value (failsafe mode active) x

5C Hex UNCERTAIN Configuration error x


(limits not set correctly)

80 Hex GOOD OK x x

84 Hex GOOD Active block alarm x


(static revision has been increased)

89 Hex GOOD LOW:LIM (alarm active) x

8A Hex GOOD HI_LIM (alarm active) x

8D Hex GOOD LOW_LOW_LIM (alarm active) x

8E Hex GOOD HI_HI_LIM (alarm active) x

0F Hex BAD Non-specific x x

Endress+Hauser 31
PROFIBUS-PA interface Cerabar M mit PROFIBUS PA

6.5 Acyclic data exchange


The device parameters in the Physical Block, Transducer Block and Analog Input Block, see
→ Fig. 25, and in the device management PROFIBUS-DP Class 2 master can be accessed using the
acyclic service. → Fig. 26 and → Fig. 27 show block models of the Transducer Block and Analog
Input Block. A full description of the device management, standard parameters and the Physical
Block can be found in the Operating Instructions BA198F.

BIAS PRESSURE (V0H5/V0H6)


MEAS BEGIN (V0H1/V0H3)
CAL POINT HIGH (V7H5)

MEAS END (V0H2/V0H4)


CAL POINT LOW (V7H4)

SENSOR UNIT (V0H9)


DAMPING (V0H7)

SCALE IN

SCALE IN

STATUS
SENSOR TRIMMED PRIMARY
VALUE VALUE VALUE

t
(V7H8) P' (V9H7)
D (V0H0)

PD

P01-PMx4xxxx-02-xx-xx-xx-000

Fig. 26: Schematic diagram of the Cerabar M Transducer Block


Parameters with information on a matrix position (in brackets) can also be accessed using Commuwin II.

! Note!
As standard, the OUT value is transmitted in the unit specified on the nameplate.
PERMITTED_MODE
OUT_SCALE_UNIT

OUT_SCALE_MAX
OUT_SCALE_MIN
PV_SCALE_MAX

OUT_SCALE_DP

NORMAL_MODE
PV_SCALE_MIN

TARGET_MODE
FSAFE_VALUE
FSAFE_TYPE
ALARM_HYS
SIMULATION

OUT_SCALE

LO_LO_LIM

MODE_BLK
PV_SCALE
CHANNEL

HI_HI_LIM
ON_OFF
STATUS

LO_LIM
HI_LIM
VALUE

MAN

MODE/
STATUS
MAN
1
FAIL O/S OUT
SAFE
0
0 1
AUTO
PV OUT
ACTUAL_MODE
LO_LO_ALM
HI_HI_ALM

LO_ALM
HI_ALM

P01-PMx4xxxx-02-xx-xx-xx-001

Fig. 27: Schematic diagram of the Cerabar M Analog Input Block

32 Endress+Hauser
Cerabar M mit PROFIBUS PA PROFIBUS-PA interface

6.5.1 Slot/index table


The device parameters are listed in the following tables. The parameters are accessed via the slot
and index number. The Analog Input Block, Transducer Block and Physical Block contain standard
parameters, block parameters and manufacturer-specific parameters.

If Commuwin II is the operating program used, then the matrix field and the graphic operation are
available as the user interface. As soon as the standard operating parameters are made available to
a device block, every parameter change is automatically displayed in the block parameters. The
dependencies are listed in the "E+H matrix" column. See also → Fig. 26 and → Fig. 27.

6.5.2 Device management

Parameter E+H matrix/ Slot Index Size (bytes) Type Read Write Storage
parameter class

Directory object header 1 0 12 Array of UNSIGNED16 X C

Composite list directory 1 1 24 Array of UNSIGNED16 X C


entries

GAP directory continuous 1 2-8


GAP reserved 1 9-15

6.5.3 Analog Input Block

Parameter E+H matrix/ Slot Index Size (bytes) Type Read Write Storage class
parameter

AI Block data 1 16 20 DS-321) X C

Static revision 1 17 2 UNSIGNED16 X N

Device tag VAH0 1 18 32 OSTRING X X S

Strategy 1 19 2 UNSIGNED16 X X S

Alert key 1 20 1 UNSIGNED8 X X S

AI Target mode 1 21 1 UNSIGNED8 X X S


AI Mode block 1 22 3 DS-371) X D/N/C
1)
AI Alarm summary 1 23 8 DS-42 X D
1)
Batch 1 24 10 DS-67 X X S

Gap 1 25

Block parameters

OUT V6H2/3 1 26 5 DS-331) X D


PV scale 1 27 8 Array of FLOAT X X S
1)
OUT scale 1 28 11 DS-36 X X S

Linearization type 1 29 1 UNSIGNED8 X X S

Channel 1 30 2 UNSIGNED16 X X S

Gap 1 31

PV FTIME 1 32 4 FLOAT X X S
Fail safe type 1 33 1 UNSIGNED8 X X S

Fail safe value 1 34 4 FLOAT X X S

Alarm Hysteresis 1 35 4 FLOAT X X S

Gap 1 36

HI HI Limit 1 37 4 FLOAT X X S

Endress+Hauser 33
PROFIBUS-PA interface Cerabar M mit PROFIBUS PA

Parameter E+H matrix/ Slot Index Size (bytes) Type Read Write Storage class
parameter

Gap 1 38

HI Limit 1 39 4 FLOAT X X S

Gap 1 40

LO Limit 1 41 4 FLOAT X X S

Gap 1 42

LO LO Limit 1 43 4 FLOAT X X S

Gap 1 44-45
HI HI Alarm 1 46 16 DS-391) X D
1)
HI Alarm 1 47 16 DS-39 X D
1)
LO Alarm 1 48 16 DS-39 X D

LO LO Alarm 1 49 16 DS-391) X D
1)
Simulate 1 50 6 DS-50 X X S

OUT unit text 1 51 16 OSTRING X X S

Gap reserved 1 52-60

Gap 1 61-65

1) → See Page 37 ff., Section 6.6.2 "Data strings"


C = constant, N = nonvolatile (remains stored), S = static (revision counter incremented by 1), D = dynamic

6.5.4 Physical Block

Parameter E+H matrix/ Slot Index Size (bytes) Type Read Write Storage
parameter class

Standard parameters

PB Block data 1 66 20 DS-361) X C

Static revision 1 67 2 UNSIGNED16 X N


Device tag VAH0 1 68 32 OSTRING X X S

Strategy 1 69 2 UNSIGNED16 X X S

Alert key 1 70 1 UNSIGNED8 X X S

PB Target mode 1 71 1 UNSIGNED8 X X S


1)
PB Mode block 1 72 3 DS-37 X D/N/C
1)
PB Alarm summary 1 73 8 DS-42 X D

Block parameters

Software revision V6H2/3 1 74 16 OSTRING X C

Hardware revision 1 75 16 OSTRING X C


Device manufacturer identity 1 76 2 UNSIGNED16 X C

Device identity 1 77 16 OSTRING X C

Device serial number VAH2 1 78 16 OSTRING X C


Diagnosis 1 79 4 OSTRING X D

Diagnosis extension 1 80 6 OSTRING X D

Diagnosis mask 1 81 4 OSTRING X C

Diagnosis mask extension 1 82 6 OSTRING X C

Device certification 1 83 32 OSTRING X N

Security locking V9H9 1 84 2 UNSIGNED16 X X N

34 Endress+Hauser
Cerabar M mit PROFIBUS PA PROFIBUS-PA interface

Parameter E+H matrix/ Slot Index Size (bytes) Type Read Write Storage
parameter class

Factory reset V9H2 1 85 2 UNSIGNED16 X S

Descriptor 1 86 32 OSTRING X X S

Device message VAH1 1 87 32 OSTRING X X S

Device installation date 1 88 16 OSTRING X X S

Gap reserved 1 89

Identification V6H0 1 90 1 UNSIGNED8 X X S


number

HW write 1 91 1 UNSIGNED16 X D
protection

Gap reserved 1 92-98

Gap 1 99-103

Matrix error code V2H0 1 104 2 UNSIGNED16 X D

Matrix last error code V2H1 1 105 2 UNSIGNED16 X X D

UpDown features supported 1 106 1 OSTRING X C

UpDown control 1 107 1 UNSIGNED8 X D

UpDown data 1 108 20 OSTRING X X D

Bus address V9H4 1 109 1 UNSIGNED8 X D

Matrix device V2H2 1 110 2 UNSIGNED16 X C


software number

PA set unit to bus V6H1 1 111 1 UNSIGNED8 X X S


PA input value V6H6 1 112 6 FLOAT+U8+U8 X D

PA select V0H0 V6H5 1 113 1 UNSIGNED8 X X S

PA profile revision V6H7 1 114 16 OSTRING X C


Gap 1 115-119

PA select second cyclic value V6H4 1 120 1 UNSIGNED8 X X S

PA identity 1 121 2 UNSIGNED16 X D


number

PA identity string 1 122 32 OSTRING X C

PA DP status 1 123 1 UNSIGNED8 X D

Gap 1 124-128 X

1) See Section 6.6, "Data strings" section or PROFIBUS-PA Specification Part 1


C = constant, N = nonvolatile (remains stored), S = static (revision counter incremented by), D = dynamic

6.5.5 View_1 parameters

Parameter E+H matrix/ Slot Index Size (bytes) Type Read Write Storage
parameter class
View 1 Physical block 1 205 17 OSTRING X D/N/C

Gap reserved 1 206-210

View 1 Transducer block 1 211 22 OSTRING X D/N/C

Gap reserved 1 212-216

View 1 Analog Input block 1 217 18 OSTRING X D/N/C

Gap reserved 1 218-222 18

Endress+Hauser 35
PROFIBUS-PA interface Cerabar M mit PROFIBUS PA

6.5.6 Transducer Block

Parameter E+H matrix Slot Index Size (bytes) Type Read Write Storage class

Standard parameters

TB Block data 1 129 20 DS-321) X C

Static revision 1 130 2 UNSIGNED16 X N

Device tag VAH0 1 131 32 OSTRING X X S


Strategy 1 132 2 UNSIGNED16 X X S

Alert key 1 133 1 UNSIGNED8 X X S

TB Target mode 1 134 1 UNSIGNED8 X X S

TB Mode 1 135 3 DS-371) X D/N/C


1)
TB Alarm summary 1 136 8 DS-42 X D

Block parameters

Sensor value V7H8 1 137 4 FLOAT X D

Sensor high limit V7H7 1 138 4 FLOAT X N

Sensor low limit V7H6 1 139 4 FLOAT X N

Calibration point high V7H5 1 140 4 FLOAT X X S

Calibration point low VAH4 1 141 4 FLOAT X X S

Calibration minimum span 1 142 4 FLOAT X N

Sensor unit V0H9 1 143 2 UNSIGNED16 X X N


Trimmed value V9H7 1 144 5 DS-331) X D

Sensor type 1 145 2 UNSIGNED16 X N

Sensor serial number VAH3 1 146 4 UNSIGNED32 X N

Primary value V0H0 1 147 5 DS-331) X N

Primary value unit V0H9 1 148 2 UNSIGNED16 X X S

Primary value type 1 149 2 UNSIGNED16 X X S

Gap 1 150-157 S
1)
Secondary value 1 1 158 5 DS-33 X S

Secondary value 1 unit V0H9 1 159 2 UNSIGNED16 X X


Secondary value 2 1 160 5 DS-331) X S

Secondary value 2 unit V0H9 1 161 2 UNSIGNED16 X X D

Linearization 1 162 1 UNSIGNED8 X X

Scale in V0H1/2 1 163 2*4 Array of FLOAT X X

Gap 1 164-177 D

Gap reserved 1 178-187 D


Endress+Hauser parameters

Measure begin V0H1 1 188 4 FLOAT X X S

Measure end V0H2 1 189 4 FLOAT X X S

Automatically measure begin V0H3 1 190 1 UNSIGNED8 X X S

Automatically measure end V0H4 1 191 1 UNSIGNED8 X X S

Bias pressure V0H5 1 192 4 FLOAT X X S

Automatically bias pressure V0H6 1 193 1 UNSIGNED8 X X S

Damping V0H7 1 194 4 FLOAT X X S

Sensor tab index V2H7 1 195 1 UNSIGNED8 X X S

36 Endress+Hauser
Cerabar M mit PROFIBUS PA PROFIBUS-PA interface

Parameter E+H matrix Slot Index Size (bytes) Type Read Write Storage class

Sensor tab value V2H8 1 196 4 FLOAT X X S

Sensor trim off V9H5 1 197 4 FLOAT X S

Sensor trim off value V9H6 1 198 4 FLOAT X S

Biased pressure V9H8 1 199 4 FLOAT X D

Gap VAH6 1 200-204

1) → See Page 37 ff., Section 6.6.2 "Data strings"


C = constant, N = nonvolatile (remains stored), S = static (revision counter incremented by 1), D = dynamic

6.6 Data format

6.6.1 IEEE 754 format


The measured value is transmitted as an IEEE -754 floating point number, whereby:

Measured value = (-1)sign x 2(E - 127) x (1+F)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0


Sign Exponent (E) Fraction (F)

27 26 25 24 23 22 21 20 2-1 2-2 2-3 2-4 2-5 2-6 2-7

Fraction (F)

2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2-16 2-17 2-18 2-19 2-20 2-21 2-22 2-23

Example
40 F0 00 00 hex = 0100 0000 1111 0000 0000 0000 0000 0000 binary

Value = (-1)0 x 2 (129-127) x (1 + 2-1 x 2-2 x 2-3)


= 1 x 22 x (1 + 0.5 x 0.25 x 0.125)
= 1 x 4 x 1.875
= 7.5

! Note!
• Not all PLCs support the IEEE 754 format. If this is the case, a conversion module must be used
or written.
• Depending on the type of data storage used in the PLC (master) - (most significant
byte or low significant byte) - the byte sequence might have to be altered (byte swapping routine).

6.6.2 Data strings


Some data types, e.g. DS-36, are marked with an asterisk in the slot/index table (→ see Page 33,
Section 6.5.1 "Slot/index table"). These data types are data strings that are structured according to
the PROFIBUS-PA Specification Part 1, Version 3.0. They comprise several elements that are
addressed via the slot, index and subindices, as shown in the following two examples:

Parameter Slot Index Element Subindex Type Size


type

DS-33 1 26 OUT Value 1 FLOAT 4

OUT Value 1 FLOAT 4

Endress+Hauser 37
PROFIBUS-PA interface Cerabar M mit PROFIBUS PA

Parameter Slot Index Element Subindex Type Size


type

DS-36 27 OUT Scale Max. 1 FLOAT 4

OUT Scale Min. 5 FLOAT 4

OUT Scale Unit. 9 UNSIGNED16 2


OUT Scale DP 11 INTEGER8 1
(decimal point.)

6.7 Configuration of parameter profiles


You can access the block parameters via a PROFIBUS-DP Class 2 master, such as Commuwin II/
FieldCare. Commuwin II/FieldCare runs on an IBM-compatible computer or laptop. The computer
must be equipped with a PROFIBUS interface, i.e. PROFIBOARD for PCs and PROFICARD for
laptops. During the system integration, the computer is registered as a Class 2 master.

6.7.1 Operation via FieldCare


The operating of FieldCare are described in the integrated FieldCare online help.
The PROFIdtmDPV1 server has to be installed for operation.

6.7.2 Operation via Commuwin II


The PA-DPV1 server has to be installed for operation. Then establish the connection to
Commuwin II via this server.
• Generate a live list with "tags".
• Select the E+H device operation by clicking the device name, e.g. Cerabar M.
• Select profile operation by clicking the appropriate tag, e.g. AI: PIC 209 = Analog Input Block
Cerabar M or by selecting the related device profile in graphic operation.
• The settings are then entered in the "Device parameter" menu.

Device parameter menu


The "Device parameter" menu in Commuwin II offers you two operating modes, namely "Matrix
operation" and "Graphic operation".
• During matrix operation, the device or profile parameters are loaded to a matrix. A parameter can
be changed when the corresponding matrix field is selected.
• In the case of graphic operation, the operating sequence is shown in a series of graphics with
parameters. For profile operation, the Diagnosis, Scaling, Simulation and Block graphics are of
interest.

Output scaling
The Cerabar M onsite display and the digital output operate completely independently of each
other. As standard, the output value (OUT value) is transmitted in the unit specified on the
nameplate.

38 Endress+Hauser
Cerabar M mit PROFIBUS PA PROFIBUS-PA interface

Digital output value (Out value) = display value of the onsite display
The following operating options are available so that the display and the digital output produce the
same value:
• Set the values for the lower and upper limit of PV scale and OUT scale in the Analog Input Block
as equal; PV Scale min. = OUT Scale min. and PV Scale max. = OUT Scale max. See also (→ see
Page 33, Section 6.5.1 "Slot/index table") and Section 11.1 "Matrix for Analog Input Block (AI
Transmitter)",
• Scale the limits of PV scale and OUT scale in Commuwin II in the graphic mode, see illustration
below or
• Confirm the "Set unit to bus" parameter in accordance with Section 7.3, "Selecting a pressure
unit" section. Confirming this parameter automatically sets the PV scale and OUT scale limits to
the same value.

Digital output value (Out value) ≠ display value of the onsite display
If you require an output value for your PLC that is scaled differently than the display value on the
onsite display, the following operating options are available:
• Set the values for the lower and upper limit for PV scale and OUT scale in the Analog Input Block
as per the requirements, (→ see Page 33, Section 6.5.1 "Slot/index table") and Section 11.1
"Matrix for Analog Input Block (AI Transmitter)" or
• Scale the limits of PV scale and OUT scale in Commuwin II in the graphic mode, see illustration
below.

! Note!
If you wish to perform position adjustment using bias pressure for the value indicated on the onsite
display (see Section 7.3 "Position adjustment - only display (bias pressure)") this must be done before
changing the values for OUT scale min. and OUT scale max.

Fig. 28: Scaling the Out value via graphic operation in Commuwin II

Endress+Hauser 39
Commissioning Cerabar M mit PROFIBUS PA

7 Commissioning
The Cerabar M is ready for measurement immediately. The measuring range corresponds to the
information on the nameplate. As standard, the pressure applied is transmitted via PROFIBUS-PA
in the unit specified on the nameplate. The measured value is transmitted in the unit "bar" following
a "5140" reset in the V2H9 matrix field (→ see Page 50, Section 9.5 "Reset").
There is no turndown in the conventional sense for PROFIBUS-PA digital signal transmission. The
measured value is transmitted with a resolution corresponding to an accuracy of 0.2 %.

7.1 Function check


Carry out a post-installation and a post-connection check as per the checklist before commissioning
the device.
• "Post-installation check" checklist (→ see Page 18, Section 3.4 "Post-installation check")
• "Post-connection check" checklist (→ see Page 23, Section 4.5 "Post-connection check")

7.2 Onsite commissioning

7.2.1 Preparatory work


• Connect the Cerabar M, → see Page 19, Section 4.1 "Electrical connection".
• Ensure that a pressure can be specified within the required measuring range.

Zero Span
1 2 3
on address
Display

off

+ –

Fig. 29: ➀ Position of keys for calibrating lower and upper-range value
Example:
Zero key 1 x = display lower-range value, 2 x = accept lower-range value
Span key 1 x = display upper-range value, 2 x = accept upper-range value

! Note!
Use the "Zero" and "Span" keys to set the lower-range value and upper-range value of the bar graph
in the display module. These settings do not have any effect on the digital output value (OUT value)
and the "measured value" in the matrix field V0H0.

40 Endress+Hauser
Cerabar M mit PROFIBUS PA Commissioning

7.2.2 Lower-range value calibration


Calibration of the lower-range value is carried out using the "Zero" key.
Proceed as follows when calibrating the lower-range value:
• Specify the exact pressure for the lower-range value.
• Press the Zero key twice.
The acting pressure is adopted as the lower-range value.
By pressing the Zero key once the value saved as the lower-range value
can be output on the onsite display.

7.2.3 Upper-range value calibration


Calibration of the upper-range value is carried out using the "Span" key.
Proceed as follows when calibrating the upper-range value:
• Specify the exact pressure for the upper-range value.
• Press the Span key twice.
The acting pressure is adopted as the upper-range value.
By pressing the Span key once the value saved as the upper-range value
can be output on the onsite display.

7.3 Commissioning and operation

7.3.1 Preparatory work


Connect the Cerabar M, see Section 4.1Electrical connection.

7.3.2 Endress+Hauser operating program


The calibration is performed via parameters with FieldCare or operating matrix with Commuwin II:

Matrix field/ Meaning


parameter

V0H1 Entry of pressure for lower-range value (only affects the bar graph in the display module)

V0H2 Entry of pressure for upper-range value (only affects the bar graph in the display module)

V0H3 Acting pressure is taken as lower-range value, (only affects the bar graph in the display module)

V0H4 Acting pressure is taken as upper-range value, (only affects the bar graph in the display module)

V0H5 Entry of bias pressure (only affects the display module and the matrix fields V0H0, V0H1 and V0H2)

V0H6 Acting pressure is taken as bias pressure


(only affects the display module and the matrix fields V0H0, V0H1 and V0H2)

V0H7 Enter damping τ (0 to 40 s)

V0H9 Pressure unit can be selected: mbar, bar, Pa, hPa, kPa, MPa, mm H2O, m H2O, in H2O,
ft H2O, psi, g/cm2, kg/cm2, kgf/cm2, atm, lb/ft2, torr, mm Hg, in Hg

V6H1 Various pressure units can be selected via V0H9. The pressure-specific parameters are converted and
displayed with the selected unit in Commuwin II/FieldCare. V6H1 must be confirmed to transfer the
converted values on the bus, see "Selecting pressure unit" section.

V9H5 Position adjustment, see "Zero point correction" section.

Endress+Hauser 41
Commissioning Cerabar M mit PROFIBUS PA

7.3.3 Reset to factory setting (reset)


By entering a certain code, the entries in the matrix are reset partially or completely to the factory
settings. Further information on the various types of reset and their effects is given in Section 9.5
"Reset".

# Matrix (VH position)/ Meaning Entry


parameter

V2H0 Reset to e.g. 2380


factory values

7.3.4 Damping τ (integration time)


The damping τ affects the speed at which the output signal and the onsite display react to changes
in pressure.

# Matrix (VH position)/ Meaning Entry I


parameter ➀
100 %
V0H7 Damping (s) e.g. 30 63 %
(0 to 40 s) ➁

0 t 2t 3t
P01-PMx4xxxx-19-xx-xx-xx-036

Fig. 30: ➀ Jump in pressure. ➁ Output signal.

7.3.5 Selecting a pressure unit


You can select a pressure unit using the "Select pressure unit" parameter (V0H9), (see table below).
If you select a new pressure unit in V0H9, all pressure-specific parameters are converted and
displayed in Commuwin II with the new pressure unit.

# Matrix (VH position)/ Meaning Entry


parameter

1 All pressure-specific parameters are given in pressure unit "bar", e.g.


measured value V0H0 = 1 bar.

2 V0H9 Select new pressure unit e.g. psi

3 All pressure-specific parameters are given in pressure unit "psi", e.g.


measured value V0H0 = 14.5 psi.

Unit Unit Unit Unit Unit


2
mbar kPa in H2O kg / cm Torr
2
bar MPa ft H2O kgf / cm mm Hg

Pa mm H2O psi atm in Hg

hPa m H2O g/ cm2 lb / ft2

! Note!
As standard, the measured value is transferred via the bus in the pressure unit given on the
nameplate. For the digital output value and the measured value in the matrix field V0H0 to display
the same value - even after selecting a new pressure unit - you must confirm the "Set unit to bus"
parameter in V6H1 once. Note that a change of the digital output value can influence the controller.

42 Endress+Hauser
Cerabar M mit PROFIBUS PA Commissioning

# Matrix (VH position)/ Meaning Entry


parameter

1 e.g. measured value V0H0 = 1 bar

2 V0H9 Select new pressure unit e.g. psi

3 Display measured value V0H0 = 14.5 psi


Value 1 is still transmitted via the bus.
V6H2 displays: 1.0 UNKNOWN

4 V6H1 V6H2 displays: Press Enter to


14.5 psi confirm "Set
unit to
bus"

5 Value 14.5 is now transmitted via the bus.

! Note!
The "Lower-range value" (V0H1/V0H3) and "Upper-range value" (V0H2/V0H4) parameters set the
bar graph in the display module. These settings do not have any effect on the digital output value
(OUT value) or the "measured value" in the matrix field V0H0.

7.3.6 Calibration without reference pressure


A pressure is entered for the lower-range value and upper-range value. No particular pressure must
be acting.

# Matrix (VH position)/ Meaning Entry


parameter

1 V0H9 Select pressure unit e.g. bar

2 V3H0 Select "Pressure" "Pressure"


operating mode

3 V0H1 Lower-range value e.g. 0.0

4 V0H2 Upper-range value e.g. 1.0

5 e.g. current measured value (V0H0) = 0.7 bar

P01-PMx4xxxx-19-xx-xx-xx-033

Fig. 31: ➀ No reference pressure

Endress+Hauser 43
Commissioning Cerabar M mit PROFIBUS PA

7.3.7 Calibration with reference pressure


A reference or process pressure present is accepted as the lower-range or upper-range value.

# Matrix (VH position)/ Meaning Entry


parameter

1 V0H9 Select pressure unit e.g. bar

2 V3H0 Select "Pressure" "Pressure"


operating mode

3 Specify the exact pressure for the lower-range value.

4 V0H3 Accept the Confirm with


pressure applied "Enter".
for the lower-range value

5 Specify the exact pressure for the upper-range value.



6 V0H4 Accept the Confirm with
pressure applied "Enter". P01-PMx4xxxx-19-xx-xx-xx-034
for the upper-range value Fig. 32: ➀ No reference pressure
7 e.g. current measured value (V0H0) = 0.7 bar

7.3.8 Position adjustment - only display (bias pressure)


If the display does not show zero after calibrating the zero point at zero operating pressure (position-
dependent), the display value can be corrected to zero by entering or adopting a bias pressure
(position adjustment).

# Matrix (VH Meaning Entry


position)/
p e=0 p
parameter

1 V0H5 Enter bias pressure e.g. 0.1

p Bias
2 Where necessary, set the display value and output
value (OUT value) as equal.

V6H1 Set the display value Confirm p+p Bias


and output value with
as equal "Enter".

Accept a bias pressure present


1 V0H6 Accept the Confirm
pressure applied with
as the bias pressure "Enter".
2 Where necessary, set the display value and output
value (OUT value) as equal.
P01-PMx4xxxx-19-xx-xx-xx-031

V6H1 Set the display value Confirm


and output value with
as equal "Enter".

44 Endress+Hauser
Cerabar M mit PROFIBUS PA Commissioning

7.3.9 Zero point correction


The "Zero offset" (V9H5) parameter offers a further possibility of carrying out position adjustment.
In contrast to position adjustment using bias pressure (V0H5/V0H6), the digital output value (OUT
value) is also corrected in addition to the display value on the onsite display (measured value
(V0H0)). When carrying out a zero offset, an applied pressure is assigned a correction value via "Zero
offset" (V9H5). This shifts the sensor characteristic curve according to the diagram and the "Low
sensor cal" (V7H4) and "High sensor cal" (V7H5) values are recalculated. The "Zero offset value"
(V9H6) matrix field indicates the value by which the sensor characteristic curve was shifted.
The value is calculated as follows for "Zero offset value" (V9H6):
• Zero offset value (V9H6) = Sensor pressure (V7H8) - Zero offset (V9H5)
The "Sensor pressure" (V7H8) displays the pressure currently applied.

Main group: Basic calibration

# Matrix (VH Meaning Entry


position)/ ➀
parameter

1 • Display measured value (V0H0) = 0.03 bar 1.03 ➂


(position-dependent pressure)
• OUT value (V6H2) = 0.03 1
• Lower-range value (V0H1) is set to 0.0 bar

2 Pressure for zero point correction is applied:
Sensor pressure (V7H8) = 0.03 bar
(corresponds to the pressure-dependent pressure) ➃
➆ 0.03
3 V9H5 The value 0.0 is
assigned to the
pressure present.
0.0
{ 0
➅ ➄
4 After entering information for the "Zero
offset" (V9H5) parameter, the parameters
show the following values:
P01-PMx4xxxx-05-xx-xx-xx-004
• Zero offset value (V9H6):
V9H6 = V7H8 – V9H5 Fig. 33:
V9H6 = 0.03 bar – 0.0 bar ➀ Pressure e.g. [bar]
V9H6 = 0.03 bar ➁ Before zero point correction
• Measured value (V0H0) = 0.0 bar ➂ Sensor characteristic curve
V6H2 = 0.0 ➃ After zero point correction
➄ High sensor cal (V7H5)
➅ Low sensor cal (V7H4)
➆ Value for zero point correction (V9H6)

7.4 Locking/unlocking operation


After calibrating or entering all the parameters, the operation can be locked by entering a code. As
the code, enter any number from 1 to 9998, (except 130 and 2457).

# Matrix (VH position)/ Meaning Entry


parameter

1 V9H9 Lock operation e.g. 131

2 V9H9 Unlock operation 130 or 2457

Endress+Hauser 45
Commissioning Cerabar M mit PROFIBUS PA

7.5 Information on the measuring point


The following information about the measuring point can be read via Commuwin II/FieldCare:

Matrix field/ Display or entry


parameter

Measured values

V0H0 Primary value: pressure


V6H2/V6H3 OUT value, OUT status (Analog Input Block)

V7H8 Sensor pressure (unit in V0H9) can be selected

V9H7 Current damped pressure without bias correction

Sensor data

V7H4 Low sensor calibration


Lower calibration pressure (unit can be selected in V0H9)
V7H5 High sensor calibration
Upper calibration pressure (unit can be selected in V0H9)

V7H6 Low sensor limit (unit can be selected in V0H9)


V7H7 High sensor limit (unit can be selected in V0H9)

Information on the transmitter

V2H2 Software number

V2H7 Sensor data number:


Number of the entry in the sensor table (1 to 11).
Please take from sensor pass.

V2H8 Sensor data value:


Entry in sensor table, contains all sensor-specific data.
Please take from sensor pass.

Error response mode


V2H0 Current diagnostic code

V2H1 Last diagnostic code

7.5.1 User information


The VAH0 and VAH1 fields give you the option of saving additional information on the measuring
point and measuring device. The serial number of the device and that of the sensor are saved in the
VAH2 and VAH3 matrix fields/parameters.

Matrix field/parameter Display


VAH01) Name of the measuring point.

VAH1 1) User text (Physical Block)

VAH2 1) Device serial number


VAH3 1) Sensor serial number

1) Enter up to 32 characters (ASCII)

46 Endress+Hauser
Cerabar M mit PROFIBUS PA Maintenance

8 Maintenance
Keep the pressure compensation and GORE-TEX® filter ➀ free from dirt.

P01-PMx4xxxx-17-xx-xx-xx-001

8.1 Exterior cleaning


Please note the following points when cleaning the device:
• The cleaning agents used should not corrode the surface and the seals.
• Mechanical damage to the diaphragm, e.g. due to pointed objects, must be avoided.
• Observe the degree of protection. Where applicable, see → Page 7, Section 2.1.1, "Nameplates".

9 Troubleshooting

9.1 Fault
If the Cerabar M detects an error, the following occurs:
• An error code is generated and flashes on the onsite display
• When the onsite display is connected, the bar graph accepts the selected value for the error
message (MIN, MAX, CONTINUE)
• The display value and the bar graph flash
• Error codes can be read in the "Transmitter information" main group or in matrix fields V2H0 and
V2H1

9.2 Warning
If the Cerabar M detects a warning, the following occurs:
• An error code is generated: Cerabar M continues to measure
• The scale flashes when the onsite display is connected
• Error codes can be read in the transmitter information main group or in matrix fields V2H0
and V2H1.

Endress+Hauser 47
Troubleshooting Cerabar M mit PROFIBUS PA

9.3 Error codes in V2H0 and V2H1


If several errors occur simultaneously, the sequence in which they are displayed corresponds to their
order of priority.

Code Type Cause and remedial action Priority

E101 Fault Sensor table checksum error 4


• Appears when the sensor data are being entered.
The error message disappears when the sensor data are entered completely
and correctly.
• The checksum is not correct.
Check sensor data - see "Sensor data no." (V2H7) and "Sensor data value"
(V2H8) parameters.

E102 Warning • Electronic device error for maximum indicator display 12


Perform reset (5140 code), recalibrate sensor.
• Electronic insert defective.
Replace electronic insert.

E103 Warning Initialization active 10


• The electronics are initialized after connecting the device.
Wait for the initialization process to complete.

E104 Warning Sensor calibration 11


• The values in V7H4 and V7H5 (Low sensor cal and High sensor cal) are too
close to one another, e.g. following sensor recalibration.
Perform a reset (code 2509) and recalibrate the sensor.

E106 Fault • Download active 7


Wait for download to complete

E110 Fault Checksum error 9


• The power supply is disconnected when writing to the processor.
Reestablish power supply. Perform a reset (code 5140) and recalibrate the
sensor.
• EMC effects are greater than specifications in → see Page 53, Section 10
"Technical data".
Block off EMC effects
• Electronic insert defective.
Replace electronic insert,
reenter sensor data.

E111 Fault No connection to the sensor EEPROM 1


• Cable connection between sensor electronics - main electronics - display
(internal bus) disconnected or sensor electronics defective.
Check connector for sensor. Check cable connection.
Replace sensor.

E114 Fault Electronics error 2


• Electronic insert defective
Replace electronic insert

E115 Fault Sensor overpressure 2


• Overpressure present.
Reduce pressure until message disappears.
• Cable connection sensor – electronic insert disconnected.
Check cable connection.
• Sensor defective
Replace sensor.

E116 Fault Download error (PC-transmitter) 2


• During the download, the data are not correctly transmitted to the processor,
e.g. because of open cable connections, spikes (ripple) on the supply voltage or
EMC effects.
Check cable connection PC – transmitter. Perform a reset (code 5140) and
restart download.

48 Endress+Hauser
Cerabar M mit PROFIBUS PA Troubleshooting

Code Type Cause and remedial action Priority

E120 Fault Sensor low pressure 2


• Pressure too low.
Increase pressure until message disappears.
• Cable connection sensor – electronic insert disconnected.
Check cable connection.
• Sensor defective.
Replace sensor.
• For small measuring ranges, screwing down the cover may cause the error
"E120" to be shown for a short while.
The error message disappears as soon as the overpressure in the housing is
reduced.

E121 Fault Checksum error 2


• Main electronics defective
Replace main electronics.

9.4 Simulation (Commuwin II only)


You have the option of simulating either the output value (OUT value) or the function of the Analog
Input Block. In the following sections, the matrix fields in brackets indicate the matrix position in
the Analog Input Block display in the operating program. See also Section 11.1 "Matrix for Analog
Input Block (AI Transmitter)".

9.4.1 OUT value simulation


You can simulate the output value (OUT value) as follows:
1. Where necessary, unlock the matrix using code 130 or 2457 in matrix field VAH9.
2. Using matrix field V9H9, switch from the standard to the Analog Input Block display.
3. Set the mode of the "Target mode" parameter (V8H0) to "manual".
– You can now enter a simulation value directly for the "OUT value" (V0H0).
– Afterwards, check the change to the OUT value, e.g. at the PLC.
4. Set the "Target mode" parameter back to "automatic".

! Note!
The operating program offers a further option of specifying an OUT value using the graphic
operation in the "Simulation AI-Block" menu.

9.4.2 Analog Input Block simulation


You can simulate the function of the Analog Input Block as follows:
1. Where necessary, unlock the matrix using code 130 or 2457 in matrix field V9H9.
2. Using matrix field VAH9, switch from the standard to the Analog Input Block
display.
3. Set the "Simulation" parameter in the Analog Input Block (V7H2) to "on".
– You can now enter a simulation value directly for "Simulation value" (V7H0).
– Afterwards, check the change to the OUT value (V0H0) and at the PLC.
4. Set the "Simulation" parameter back to "off".

Endress+Hauser 49
Troubleshooting Cerabar M mit PROFIBUS PA

9.5 Reset
By entering a certain code, the entries are reset partially or completely to the factory settings. Please
note that in the event of a reset, customer-specific calibration carried out by the factory is also reset
to the default values.

# Matrix field/ Meaning Entry


parameter

1 V2H9 Reset to factory setting e.g.

The Cerabar M differentiates between different reset codes with different effects. See the following
table to find out which parameters are reset by reset codes 5140 or 1, 2380 and 731.

Other reset codes have the following effects:


• 2506: Device warm start
• 2509: This reset sets the lower and upper sensor calibration limits and the zero offset value to the
factory setting, i.e.:
Low sensor cal = low sensor limit (V7H4 = V7H6),
High sensor cal = high sensor limit (V7H5 = V7H7),
Zero offset value (V9H6) = 0.0
• 2712: The device address set via the bus is reset to the default value 126.

Reset H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
codes

V0 Measured Lower- Upper- Set lower Set upper Set bias Bias Set output Select
value range range value value pressure pressure damping pressure
value value autom. unit

1/5140 0.0 = V7H7 0.0 0.0 bar


2380 0.0 = V7H7 0.0 0.0
731 0.0 = V7H7 0.0 0.0

V1

V2 Diag- Last Software Sensor Sensor Default


nostic diagnostic number data no. data value values
code code

1/5140 0 = V7H7
2380 0 = V7H7
731 0 = V7H7

V3 to V5

V6 Manufact- Set unit to OUT value OUT 2nd cyclic Select OUT value Profile
urer ident. bus status value V0H0 PLC version
number
1)
1/5140 Prim. val. 0.0
2380 1) Prim. val. 0.0
731 0.0

V7 Low High Lower Upper Sensor


sensor sensor range limit range limit pressure
calibration calibration

1/5140 = V7H6 = V7H7


2380 = V7H6 = V7H7
731

V8

V9 Zero offset Zero offset Unbiased Bias Security


value pressure pressure locking

50 Endress+Hauser
Cerabar M mit PROFIBUS PA Troubleshooting

Reset H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
codes

1/5140 0.0 = V7H82) = V7H82)


2380 0.0 = V7H82) = V7H82)
731

VA Set tag Set user


number text

1/5140 deleted deleted


2380 deleted deleted
731

1) Following a "5140" or "2380" reset, the V6H2 field displays the current digital output value.
UNKNOWN is displayed here since the unit is not known.
2) After a reset, the matrix fields V9H7 and V9H8 show the
pressure currently applied.

9.6 Repair
The Endress+Hauser repair concept provides for measuring devices to have a modular design and
that the customer may also carry out repairs.
The "Spare parts" section contains all the spare parts, and their order numbers, which you can order
from Endress+Hauser to repair the Cerabar M. Where necessary, the spare parts also include
replacement instructions.

! Note!
• For certified devices, please refer to the "Repair of Ex-certified devices" section.
• For more information on service and spare parts contact Endress+Hauser Service.
→ See www.endress.com/worldwide.
• Only the process connection on the PMC41 can be exchanged by the customer. For all other
models, a device without a display and housing can be ordered. → See Technical Information
TI399P, "Ordering information" section.

9.7 Repair of Ex-certified devices


# Warning!
When repairing Ex-certified devices, please note the following:
• Only specialist personnel or Endress+Hauser may undertake repairs to certified devices.
• Relevant standards, national hazardous area regulations and safety instructions and certificates
must be observed.
• Only use genuine spare parts from Endress+Hauser.
• When ordering spare parts, please check the device designation on the nameplate. Identical parts
may only be used as replacements.
• Electronic inserts or sensors already in use in a standard device may not be used as spare parts for
a certified device.
• Carry out repairs according to the instructions. After a repair, the device must fulfill the
requirements of the specified individual tests.
• A certified device may only be converted to another certified version by Endress+Hauser.
• All repairs and modifications must be documented.

Endress+Hauser 51
Troubleshooting Cerabar M mit PROFIBUS PA

9.8 Spare Parts


An overview of the spare parts for your device is available in the internet at www.endress.com.
To obtain information on the spare parts, proceed as follows:
1. Go to "www.endress.com" and select your country.
2. Click "Instruments".

3. Enter the product name into the "product name" field.

4. Select the device.


5. Click the "Accessories/Spare parts" tab.

6. Select the required spare parts (You may also use the overview drawing on the right side of the
screen.)
When ordering spare parts, always quote the serial number indicated on the nameplate. As far as
necessary, the spare parts also include replacement instructions.

52 Endress+Hauser
Cerabar M mit PROFIBUS PA Technical data

9.9 Return
Before you send in a device for repair or inspection, perform the following:
• Remove all traces of the fluid. Pay special attention to the grooves for seals and crevices which
could contain fluid residues. This is especially important if the fluid is hazardous to health. Please
refer also to the "Declaration of Hazardous Material and Decontamination".
Please enclose the following when returning the device:
• The duly completed and signed "Declaration of Hazardous Material and Decontamination".
Only then can Endress+Hauser inspect or repair the returned device.
• The chemical and physical properties of the fluid.
• A description of the application.
• A description of the error which occurred.
• Special instructions on handling, if necessary, e.g. safety data sheet as per EN 91/155/EEC.

9.10 Disposal
When disposing, separate and recycle the device components based on the materials.

9.11 Software history

Date Software version Changes to software Operating Instructions

12.2000 1.0 Original software. BA222P/00/en/07.00


Compatible with: 52006534
– Commuwin II
– FieldCare
– PDM

06.2001/ 1.1/1.2 Transducer block adaption/Communication BA222P/00/en/06.02


05.2002 service adaption 52014606
BA222P/00/en/12.03
52022185

BA222P/00/en/03.05
52027748

BA222P/00/en/06.08
71064505

10 Technical data
For technical data, please refer to the Technical Information TI399P for Cerabar M.

Endress+Hauser 53
Operating matrix Cerabar M mit PROFIBUS PA

11 Operating matrix

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9

V0 Basic Measured Lower Upper-range Set Set Set Bias pressure Set output Select
calibration value range-value value lower value upper value bias pressure autom. damping pressure unit

V1

V2 Diagnostic Last Software Sensor data Sensor data Default


Trans- code diagnostic No. No. value values
mitter code
information

V3…V5

V6 Manufacture Set Out value Out 2nd Select Profile


PROFIBUS r ident unit status cyclic V0H0 version
parameter number to bus value

V7 Low High Lower Upper Sensor


Sensor data sensor sensor range limit range limit pressure (P)
calibration calibration

V8

V9 Instrument Zero Zero Unbiased Bias Security


Service address offset offset value pressure pressure locking 1)

VA Set tag Set user text Serial Serial Device


Communi- number number number profile
cation sensor

= display field

1) Security locking ≠ 130/2457, unlocking = 130/2457


Security locking = 333, all parameters apart from "Sensor data No." (V2H7) and "Sensor data value" (V2H8) are locked.

The following matrix gives an overview of the factory settings.


You can also enter your values here.

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9

V0 — 0.0 V7H7 — — 0.0 — 0.0 bar

V1

V2 0 0 xxxx 1 0 0

V3 to V5

V6 xxxx — UNKNOWN — — 3.0


V7 = V7H6 = V7H7 — — —

V8

V9 xxx 0.0 0.0 — — 130/2457


VA ————— ———— ————— —————

54 Endress+Hauser
Cerabar M mit PROFIBUS PA Operating matrix

11.1 Matrix for Analog Input Block (AI Transmitter)

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9

V0 OUT OUT OUT OUT Sub OUT Limit Fail Safe Fail Safe
OUT Value Status Status Status Action Value

V1 PV Scale PV Scale Type of OUT OUT OUT Unit User Unit Decimal Rising
Scaling Min Max Linearization Scale Min Scale Max Point OUT Time

V2 Alarm
Alarm Hysteresis
Limits

V3 HI HI Limit Value Alarm Switch-on Switch-off


HI HI State Point Point
Alarm

V4 HI Limit Value Alarm Switch-on Switch-off


HI Alarm State Point Point

V5 LO Limit Value Alarm Switch-on Switch-off


LO Alarm State Point Point
V6 LO LO Value Alarm Switch-on Switch-off
LO LO Limit State Point Point
Alarm

V7 Simulation Simulation Simulation


Simulation Value Status Mode

V8 Target Actual Permitted Normal Channel Unit Mode


Block Mode
Mode

V9 Current Disable Static


Alarm Revision
Config.

VA Set Tag Strategy Alert Key Profile Batch ID Batch Batch Batch Device
Block Number Version Rup Phase Operation Profile
Parameter

11.2 Description of parameters

Matrix field/ Description


parameter

Measured value This parameter indicates the value currently measured. V0H0 corresponds to the onsite display.
(V0H0) Select a pressure unit via the "Select pressure unit" (V0H9). The measured value is converted
and displayed in the pressure unit you selected.
Note: As standard, the measured value is transmitted via the bus in the pressure unit indicated
on the nameplate. To transmit the converted measured value via the bus, the
"Set unit to bus" must be confirmed once in the V6H1 matrix field/parameter.
See also Matrix/Parameter description for "Set unit to bus" (V6H1).

Lower-range value Enter a pressure value for the lower-range value (calibration without reference pressure).
(V0H1) Use this parameter to set the lower-range value for the bar graph on the onsite display.
This parameter has no effect on the digital output value (OUT value).
See Section 7.3, "Calibration without reference pressure".
Factory setting: 0.0

Upper-range value Enter a pressure value for the upper-range value (calibration without reference pressure).
(V0H2) Use this parameter to set the upper-range value for the bar graph on the onsite display.
This parameter has no effect on the digital output value (OUT value).
See Section 7.3, "Calibration without reference pressure".
Factory setting: "Upper range limit" (V7H7)

Endress+Hauser 55
Operating matrix Cerabar M mit PROFIBUS PA

Matrix field/ Description


parameter

Set lower value If you confirm this parameter, the current pressure value is set as the lower-range value
(V0H3) (calibration with reference pressure). The lower-range value only refers to the bar graph on the
onsite display. It has no effect on the digital output value (OUT value).
The value is displayed in the "Lower-range value" parameter (V0H1).
This is equivalent to pressing the Zero key twice during onsite operation.

Set upper value If you confirm this parameter, the current pressure value is set as the
(V0H4) upper-range value (calibration with reference pressure). The lower-range value
only refers to the bar graph on the onsite display. It has no effect on the
digital output value (OUT value).
The value is displayed in the "Upper-range value" parameter (V0H2).
This is equivalent to pressing the Span key twice during onsite operation.

Set bias pressure If the onsite display does not show zero after calibrating the lower-range value at zero operating
(V0H5) pressure (position-dependent), you can correct the display value of the onsite display to zero by
entering a pressure value (bias pressure)
(position adjustment). The "Measured value" (V0H0), "Lower-range value" (V0H1) and
"Upper-range value" (V0H2) parameters are corrected by the bias pressure.
Note: In the "Pressure" operating mode, position adjustment via a bias pressure
has no effect on the digital output value ("OUT value" parameter) which is
transmitted via the bus. For the onsite display and the "OUT value" (V6H2)
to display the same value, the "Set unit to bus" must be confirmed in
Matrix field/Parameter V6H1. See also Section 7.3, "Position adjustment - only display (bias
pressure)".
Factory setting: 0.0

Bias pressure If you confirm this parameter, the current pressure value is adopted as the bias pressure.
autom. The value is displayed in the "Set bias pressure" (V0H5).
(V0H6) This is equivalent to pressing the Zero and Span key twice simultaneously during onsite
operation.
See also parameter description for "Set bias pressure" (V0H5).

Set output damping The damping (integration time) affects the speed at which the output signal and the
(V0H7) display value react to a change in the pressure.
Damping is adjustable from 0 to 40 s. Factory setting: 0.0

Select Select a pressure unit.


pressure unit If a new pressure unit is selected, all the pressure-specific parameters
(V0H9) are converted and displayed in the new pressure unit.
Note: As standard, the measured value is transmitted via the bus in the pressure unit
indicated on the nameplate. To transmit the converted measured value via the bus, the
"Set unit to bus" must be confirmed once in the V6H1 Matrix field/Parameter.
See also parameter description for "Set unit to bus" (V6H1).
See Section 7.3, "Selecting a pressure unit".
Factory setting: see information on the nameplate

Diagnostic code The pressure transmitter outputs an error code if it detects a fault or a warning.
(V2H0) This parameter indicates the current error code.
For a description of the error codes, see Section 9.3.

Last diagnostic Indicates the last error code.


code For a description of the error codes, see Section 9.3.
(V2H1) Factory setting: 0

Software number Indicates the device and software number.


(V2H2) The first two digits represent the device number and digits 3 and 4 the
software version. Example: Cerabar M PROFIBUS-PA SW 1.2 = 8212

Sensor data no. A sensor pass with 11 items of sensor data is provided with each device.
(V2H7) If the electronics are replaced, these data must be reentered via the "Sensor data no."
(V2H7) and "Sensor data value" (V2H8).

Sensor data value See "Sensor data no." (V2H7).


(V2H8)

Default values Enter a reset code. Possible reset codes are: 5140 or 1, 2380, 731,
(V2H9) 2506, 2509 and 2712. The parameters that are reset to the
factory setting by the specific reset codes are indicated in Section 9.5.

56 Endress+Hauser
Cerabar M mit PROFIBUS PA Operating matrix

Matrix field/ Description


parameter

Manufacturer ident. For selecting the ID number. Options:


number – Profile: General ID number of the PNO (PROFIBUS User Organization):
(V6H0) "9700 (hex)". To configure the PLC, the device master file (GSD) of the
PNO (Profibus User Organization) must be used.
– Manufacturer: Device ID number for Cerabar M PROFIBUS-PA: "151C (hex)".
To configure the PLC, the device-specific GSD must be used.
See also Section 6.3 "Device master and type files (GSD)".

Set unit In the following instances, the digital output value (OUT value) and the onsite display or the
to bus "Measured value" parameter (V0H0) do not show the same value:
(V6H1) – If you have selected a new pressure unit via the "Select pressure unit" (V0H9) and/or
– If you have performed position adjustment in the "Pressure" operating mode by entering a
bias pressure (V0H5/V0H6).
To make the digital output value display the same value as the onsite display or V0H0 in
such instances, the "Set unit to bus" in Matrix field/Parameter V6H1 must be confirmed
after calibration. Note that a change of the digital output value can influence the controller.
See also Section 7.3, "Selecting a pressure unit" and "Position adjustment - only display (bias
pressure)".

V6H2 This parameter shows the OUT value of the Analog Input Block (digital
OUT value output value that is transmitted via the bus).
(V6H2) As long as Matrix field/Parameter V6H2 continues to display UNKNOWN,
"Set unit to bus" in Matrix field/Parameter V6H1 has not yet been confirmed.

OUT status This parameter shows the status of the OUT value (digital output value).
(V6H3) For the description of the status codes, see Section 6.4, "Status codes".

2nd cycl. value This field can be used to select a second parameter that is output cyclically to the PLC.
(V6H4) Options: Sensor value (V7H8), Trimmed value (V9H7) and Biased value (V9H8).
See also Section 6.4, Fig. 25.
Factory setting: measured value (V0H0)

Select The onsite display and Matrix field/Parameter V0H0 normally show the same value.
V0H0 However, a cyclic output value can also be made available to the onsite display
(V6H5) via a PLC. For this purpose, this parameter has to be set to "display value" (or 1).
See also Section 6.4.

OUT_value Displays a cyclic OUT value of the PLC. See also Section 6.4, Fig. 25.
from PLC
(V6H6)

Profile version Displays the PROFIBUS-PA profile version.


(V6H7)

Low sensor For entering the lower point of the sensor characteristic curve during a sensor calibration.
calibration Use this parameter to assign a new value to a reference pressure applied to the device.
(V7H4) The pressure value present and the value entered for "Low sensor cal" corresponds to
the lower point of the sensor characteristic curve.
Factory setting: "Lower range limit" (V7H6)

High sensor For entering the upper point of the sensor characteristic curve during a sensor calibration.
calibration Use this parameter to assign a new value to a reference pressure applied to the device.
(V7H5) The pressure value present and the value entered for "High sensor cal" corresponds to
the upper point of the sensor characteristic curve.
Factory setting: "Upper range limit" (V7H7)

Lower Displays the lower measuring limit.


range limit (V7H6)

Upper Displays the upper measuring limit.


range limit (V7H7)
Sensor pressure Displays the pressure currently present.
(V7H8)

Instrument address Displays the instrument address set in the bus. The address can either be set on site,
(V9H4) via DIP switches or via software. See also Section 6.2.
Factory setting: 126

Endress+Hauser 57
Operating matrix Cerabar M mit PROFIBUS PA

Matrix field/ Description


parameter

Zero You can use this parameter to perform a calibration (zero point correction) simultaneously
offset for the display value of the onsite display ("Measured value" (V0H0)) and for the
(V9H5) digital output value (OUT value).
By entering a value for this parameter, you can assign a new value to a pressure
applied at the device. The sensor characteristic curve is shifted by this value and the
"Low sensor calibration" (V7H4) and "High sensor calibration" (V7H5) parameters are
recalculated.
See Section 7.3, "Zero point correction".
Factory setting: 0.0

Zero Displays the value by which the sensor characteristic curve has been moved during zero
offset value point correction.
(V9H6) See also parameter description for "Zero offset"
(V9H5) and Section 7.3, "Zero point correction".
Factory setting: 0.0

Unbiased pressure This parameter indicates the pressure currently present and damped without bias correction.
(V9H7) See also parameter description for "Set bias pressure" (V0H5).

Bias This parameter indicates the pressure currently present and damped after
pressure bias correction. See also parameter description for "Set bias pressure" (V0H5).
(V9H8) Calculation: "Bias pressure" (V9H8) = "Unbiased pressure" (V9H7) – "Set bias pressure" (V0H5)
In the "Pressure" operating mode, this parameter and the "Measured value" parameter
(V0H0) display the same value.

Security locking For entering a code to lock or unlock the operating matrix and local operation.
(V9H9) Locking operation:
– via the "Security locking" parameter (V9H9): enter a number from 1 to 9998,
apart from 130 and 2457.
Unlocking operation:
– via the "Security locking" parameter (V9H9): enter 130 or 2457.
See also Section 7.4.

Set tag number Enter a text for the name of the measuring point (up to 32 ASCII characters).
(VAH0)

Set user text Enter a text for additional information (up to 32 ASCII characters).
(VAH1)
Serial no. Displays the serial number of the device.
(VAH2)

Serial no. sensor Displays the serial number of the sensor.


(VAH3)

58 Endress+Hauser
Cerabar M mit PROFIBUS PA Operating matrix

Endress+Hauser 59
Operating matrix Cerabar M mit PROFIBUS PA

60 Endress+Hauser
Cerabar M mit PROFIBUS PA Index

Index
A T
Alarm messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Temperature isolator, installation instructions. . . . . . . . 15–16
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
C
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 U
Unlocking operation . . . . . . . . . . . . . . . . . . . . . . . . . . 45–46
D
Diaphragm seals, installation instructions . . . . . . . . . . . . . . 14 W
Diaphragm seals, vacuum application. . . . . . . . . . . . . . . . . 15 Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

E
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Ersatzteile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

F
FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

H
Hazardous areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

I
Incoming acceptance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation instructions for devices with diaphragm seals . . 14
Installation instructions for devices without diaphragm seals .
11

L
Locking operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45–46

M
Measuring arrangement for level measurement . . . . . . . . . 13
Measuring arrangement for pressure measurement . . . . . . 12

N
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

O
Onsite display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Operating elements, position . . . . . . . . . . . . . . . . . . . . . . . 25
Operating keys, position . . . . . . . . . . . . . . . . . . . . . . . . . . 25

P
Pipe mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

R
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Repair of Ex-certified devices. . . . . . . . . . . . . . . . . . . . . . . 51

S
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Shielding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Supply voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Endress+Hauser 61
Cerabar M mit PROFIBUS PA Index

62 Endress+Hauser
Declaration of Hazardous Material and De-Contamination
Erklärung zur Kontamination und Reinigung
Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA#
clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
RA No. Bitte geben Sie die von E+H mitgeteilte Rücklieferungsnummer (RA#) auf allen Lieferpapieren an und vermerken Sie diese
auch außen auf der Verpackung. Nichtbeachtung dieser Anweisung führt zur Ablehnung ihrer Lieferung.

Because of legal regulations and for the safety of our employees and operating equipment, we need the "Declaration of Hazardous Material
and De-Contamination", with your signature, before your order can be handled. Please make absolutely sure to attach it to the outside of the
packaging.
Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, benötigen wir die unterschriebene
"Erklärung zur Kontamination und Reinigung", bevor Ihr Auftrag bearbeitet werden kann. Bringen Sie diese unbedingt außen an der
Verpackung an.

Type of instrument / sensor Serial number


Geräte-/Sensortyp ____________________________________________ Seriennummer ________________________

Used as SIL device in a Safety Instrumented System / Einsatz als SIL Gerät in Schutzeinrichtungen

Process data/Prozessdaten Temperature / Temperatur_____ [°F] _____ [°C] Pressure / Druck _____ [psi] _____ [ Pa ]
Conductivity / Leitfähigkeit ________ [μS/cm] Viscosity /Viskosität _____ [cp] _____ [mm2/s]

Medium and warnings


Warnhinweise zum Medium

harmful/
Medium /concentration Identification flammable toxic corrosive irritant other * harmless
Medium /Konzentration CAS No. entzündlich giftig ätzend gesundheits- sonstiges* unbedenklich
schädlich/
reizend
Process
medium
Medium im
Prozess
Medium for
process cleaning
Medium zur
Prozessreinigung
Returned part
cleaned with
Medium zur
Endreinigung
* explosive; oxidising; dangerous for the environment; biological risk; radioactive
* explosiv; brandfördernd; umweltgefährlich; biogefährlich; radioaktiv
Please tick should one of the above be applicable, include safety data sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen.

Description of failure / Fehlerbeschreibung __________________________________________________________________________


______________________________________________________________________________________________________________
______________________________________________________________________________________________________________

Company data /Angaben zum Absender

Company /Firma ___________________________________ Phone number of contact person /Telefon-Nr. Ansprechpartner:


_________________________________________________ ____________________________________________
Address / Adresse Fax / E-Mail ____________________________________________
_________________________________________________
_________________________________________________ Your order No. / Ihre Auftragsnr. ____________________________

“We hereby certify that this declaration is filled out truthfully and completely to the best of our knowledge.We further certify that the returned
parts have been carefully cleaned. To the best of our knowledge they are free of any residues in dangerous quantities.”
“Wir bestätigen, die vorliegende Erklärung nach unserem besten Wissen wahrheitsgetreu und vollständig ausgefüllt zu haben. Wir bestätigen
weiter, dass die zurückgesandten Teile sorgfältig gereinigt wurden und nach unserem besten Wissen frei von Rückständen in gefahrbringen-
der Menge sind.”
P/SF/Konta XIV

(place, date / Ort, Datum) Name, dept./Abt. (please print /bitte Druckschrift) Signature / Unterschrift
www.endress.com/worldwide

BA222P/00/en/06.08
71064505
CCS/FM+SGML6.0 71064505

You might also like