Ba00298fen 1417 PDF
Ba00298fen 1417 PDF
Ba00298fen 1417 PDF
Operating Instructions
Liquicap M FMI51, FMI52
FEI50H HART
Capacitive level measurement
Liquicap M FMI51, FMI52
Serial number
2. www.endress.com/deviceviewer Endress+Hauser
Operations App
3.
A0023555
Make sure the document is stored in a safe place such that it is always available when
working on or with the device.
To avoid danger to individuals or the facility, read the "Basic safety instructions" section
carefully, as well as all other safety instructions in the document that are specific to working
procedures.
The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser Sales Center will supply you with current information and updates to these
Instructions.
2 Endress+Hauser
Liquicap M FMI51, FMI52
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . . . 4 7 Maintenance . . . . . . . . . . . . . . . . . . . . . 78
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Installation, commissioning and operation . . . . . . 4 8 Accessories . . . . . . . . . . . . . . . . . . . . . . . 79
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
8.1 Protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
1.4 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
8.2 Shortening set for FMI52 . . . . . . . . . . . . . . . . . . . 79
1.5 Notes on safety conventions and icons . . . . . . . . . 5
8.3 Commubox FXA195 HART . . . . . . . . . . . . . . . . . . 79
8.4 HAW56x surge arrester . . . . . . . . . . . . . . . . . . . . . 79
2 Identification . . . . . . . . . . . . . . . . . . . . . . 6 8.5 Weld-in adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 9 Troubleshooting . . . . . . . . . . . . . . . . . . 80
2.3 Trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
9.1 Error messages at electronic insert . . . . . . . . . . . 80
9.2 System error messages . . . . . . . . . . . . . . . . . . . . . 80
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . 8 9.3 Possible measuring errors . . . . . . . . . . . . . . . . . . . 83
3.1 Quick installation guide . . . . . . . . . . . . . . . . . . . . . . 8 9.4 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
3.2 Incoming acceptance, transport, storage . . . . . . . . 8 9.5 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
3.3 Planning instructions . . . . . . . . . . . . . . . . . . . . . . . . 9 9.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
3.4 Measuring condition . . . . . . . . . . . . . . . . . . . . . . . 10 9.7 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
3.5 Minimum probe length for nonconductive media
(<1s/cm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 10 Technical data . . . . . . . . . . . . . . . . . . . . 85
3.6 Installation examples . . . . . . . . . . . . . . . . . . . . . . 11
10.1 Technical data: probe . . . . . . . . . . . . . . . . . . . . . . . 85
3.7 With separate housing . . . . . . . . . . . . . . . . . . . . . 16
10.2 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
3.8 Installation instructions . . . . . . . . . . . . . . . . . . . . 19
10.3 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
3.9 Post-installation check . . . . . . . . . . . . . . . . . . . . . 21
10.4 Performance characteristics . . . . . . . . . . . . . . . . . 86
10.5 Operating conditions: Environment . . . . . . . . . . . 88
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 10.6 Operating conditions: Process . . . . . . . . . . . . . . . . 89
4.1 Recommendations for connection . . . . . . . . . . . 22 10.7 Certificates and approvals . . . . . . . . . . . . . . . . . . . 92
4.2 Wiring and connecting . . . . . . . . . . . . . . . . . . . . . 24 10.8 Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
4.3 Post-connection check . . . . . . . . . . . . . . . . . . . . . 26
11 Operating menu. . . . . . . . . . . . . . . . . . . 95
5 Operation. . . . . . . . . . . . . . . . . . . . . . . . . 27 11.1 "Basic setup" menu
5.1 Operating options . . . . . . . . . . . . . . . . . . . . . . . . . 27 Commissioning with display and operating module
5.2 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 95
5.3 Locking/unlocking configuration . . . . . . . . . . . . 40 11.2 "Safety setting" menu . . . . . . . . . . . . . . . . . . . . . . . 96
5.4 Resetting to factory setting (reset) . . . . . . . . . . . 40 11.3 "Linearization" menu . . . . . . . . . . . . . . . . . . . . . . . . 97
5.5 Operation via FieldCare Device Setup . . . . . . . . . 41 11.4 "Output" menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
5.6 Operation via HART handheld terminal DXR375 . . 11.5 "Device properties" menu . . . . . . . . . . . . . . . . . . . . 99
42
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
6 Commissioning . . . . . . . . . . . . . . . . . . . . 43
6.1 Installation and function check . . . . . . . . . . . . . . 43
6.2 Basic setup without the display/operating module
43
6.3 "Basic setup" menu
Commissioning with display and operating module
48
6.4 "Safety setting" menu . . . . . . . . . . . . . . . . . . . . . . 54
6.5 "Linearization" menu . . . . . . . . . . . . . . . . . . . . . . . 58
6.6 "Output" menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
6.7 "Device properties" menu . . . . . . . . . . . . . . . . . . . 68
6.8 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6.9 FieldCare: operating program from Endress+Hauser
72
Endress+Hauser 3
Safety instructions Liquicap M FMI51, FMI52
1 Safety instructions
1.3.1 Ex area
When using the measuring system in Ex-areas, the appropriate national standards and
regulations have to be observed. Separate Ex documentation, which constitutes an integral
part of this documentation, is supplied with the device. The installation procedures,
connection data and safety instructions it contains must be observed.
• Make sure that the technical staff has adequate training.
• The special measuring and safety-related requirements for the measuring points must be
observed.
1.4.1 CE mark
The measuring system meets the legal requirements of the applicable EC guidelines. These
are listed in the corresponding EC Declaration of Conformity together with the standards
applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
4 Endress+Hauser
Liquicap M FMI51, FMI52 Safety instructions
Safety instructions
Warning!
# Draws attention to activities or procedures that can result in serious injuries to persons, a
safety risk or the destruction of the device if not carried out properly.
Caution!
" Draws attention to activities or procedures that can result in injuries to persons or the
defective operation of the device if not carried out properly.
Note!
! Draws attention to activities or procedures that have an indirect effect on operation, or can
trigger an unforeseen device reaction if not carried out properly.
Type of protection
Ex area
- This symbol in the drawings in these Operating Instructions indicates Ex-areas. Devices
located in Ex-areas, or cables for such devices, must have appropriate explosion protection.
Electrical symbols
% Direct current
A terminal to which direct voltage is applied or through which the direct current flows.
Alternating current
& A terminal to which alternating voltage (sine wave) is applied or through which the
alternating current flows.
) Ground connection
A grounded terminal which, from a user's point of view, is grounded via a grounding system.
Equipotential connection
+ A connection that has to be connected to the grounding system of the plant. This can be a
potential matching line or a star grounding system, depending on national or company codes
of practice.
Endress+Hauser 5
Identification Liquicap M FMI51, FMI52
2 Identification
2.1.1 Nameplate
You can take the following technical data from the nameplate of the device:
Order number
(see ordering information)
Z 65.13.xxx
Safety information
-40°C £ Ta £ +60°C MWP: 25bar XA327F Dat.:10/04
SIL 250002075 - -
! Note!
The product structure is used to identify the alphanumeric order number (see nameplate:
Order Code).
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is
displayed.
For an overview of the technical documentation provided, enter the serial number from the
nameplates in the W@M Device Viewer (www.endress.com/deviceviewer).
6 Endress+Hauser
Liquicap M FMI51, FMI52 Identification
2.3 Trademarks
Tri-Clamp®
Registered trademark of Ladish & Co., Inc., Kenosha, USA
Endress+Hauser 7
Installation Liquicap M FMI51, FMI52
3 Installation
1.
< 80 Nm (G½)
< 100 Nm (G¾)
< 180 Nm (G1)
< 500 Nm (G1½)
2. a b c
2
1
1 2
1 2
... 270°
L00-FMI5xxxx-17-06-xx-xx-001
3.2.2 Storage
For storage and transportation, pack the device in such a way as to protect it reliably against
impact. The original packaging offers the best protection for this.
The permitted storage temperature is –50°C to +85°C.
8 Endress+Hauser
Liquicap M FMI51, FMI52 Installation
3.3.1 Installation
The Liquicap M FMI51 (rod probe) can be installed from above and from below.
The Liquicap M FMI52 (rope probe) can be installed vertically from above.
! Note!
• The probe may not come into contact with the container wall!
• Recommended distance from the container floor: 10 mm.
• If multiple probes are mounted next to each other, a minimum distance of 500 mm
(19.7 in) between the probes must be observed.
• Do not install probes in the area of the filling curtain!
• If using the probe in agitator tanks, make sure the probe is at a sufficient distance from the
agitator.
• Rod probes with a ground tube must be used in the event of severe lateral load.
≥500 (19.7)
L00-FMI5xxxx-11-06-xx-xx-003
Dimensions mm (in)
Endress+Hauser 9
Installation Liquicap M FMI51, FMI52
! Note!
• Rod probes with a diameter of 10 mm and 16 mm have to be supported with a length 1
m (see drawing).
L/4
L/2
L
300 mm
L00-FMI5xxxx-06-05-xx-xx-077
100 %
• Use a ground tube for nonconductive
media.
≥500 (19.7)
Note!
L1
Dimensions mm (in)
10 Endress+Hauser
Liquicap M FMI51, FMI52 Installation
! Note!
• A fully insulated rod probe may be neither shortened nor extended.
• If the insulation of the probe rod is damaged, this results in an incorrect measurement
result.
• These application examples show vertical installation for continuous level measurement.
L00-FMI5xxxx-11-06-xx-xx-004
Endress+Hauser 11
Installation Liquicap M FMI51, FMI52
L00-FMI5xxxx-11-06-xx-xx-005
FMI51: rod probe with inactive length (e.g. for insulated tanks)
L00-FMI5xxxx-11-06-xx-xx-006
12 Endress+Hauser
Liquicap M FMI51, FMI52 Installation
FMI51: rod probe with ground tube and inactive length (for mounting nozzles)
L00-FMI5xxxx-11-06-xx-xx-007
FMI51: fully insulated probe with clad flange for aggressive media
L00-FMI5xxxx-11-06-xx-xx-011
Endress+Hauser 13
Installation Liquicap M FMI51, FMI52
! Note!
These application examples show the installation of rope probes for continuous level
measurement.
L00-FMI5xxxx-11-06-xx-xx-008
FMI52: rope probe with inactive length (e.g. for insulated tanks)
L00-FMI5xxxx-11-06-xx-xx-009
14 Endress+Hauser
Liquicap M FMI51, FMI52 Installation
FMI52: rope probe with fully insulated inactive length (for mounting nozzles)
L00-FMI5xxxx-11-06-xx-xx-010
! Note!
See Operating Instructions, rope shortening kit KA061F/00.
To avoid too high a tensile load the rope should be loose or guyed with a spring. The
maximum tensile load may not exceed 200 Nm.
L00-FMI5xxxx-11-06-xx-xx-012
Endress+Hauser 15
Installation Liquicap M FMI51, FMI52
EX
Zone 1
EX
Zone 0
L1
L4 ≤ 6 m
L00-FMI5xxxx-14-00-06-xx-002
! Note!
• The maximum cable length between probe and separate housing is 6 m (L4). The required
cable length must be indicated in the ordering process of a Liquicap M with separate
housing.
• The total length L = L1 + L4 should not exceed 10 m (e.g. for rope probes).
• If the cable connection has to be shortened or led through a wall, it must be separated from
the process connection.
Housing side: wall mounting Housing side: pipe mounting Sensor side
r ³ 100 mm
~61 mm B ~75 mm B H5
D
H1
H1
H3
~41 mm
~41 mm
r ³ 100 mm
L00-FMI5xxxx-06-05-xx-xx-049
! Note!
• The cable has a bending radius of r 100 mm. This must be observed as a minimum!
• Connecting cable: ø10.5 mm
• Outer jacket: silicone, notch resistance
16 Endress+Hauser
Liquicap M FMI51, FMI52 Installation
H5 (mm) D (mm)
Probes Ø10 mm rod 66 38
Probes Ø16 mm rod or rope G¾", G1", NPT¾", NPT1", Clamp 1", 66 38
(without fully insulated Clamp 1½", Universal Ø44,
inactive length) flange <DN 50, ANSI 2", 10K50
G1½", NPT1½", Clamp 2", 89 50
DIN 11851, flanges DN 50, ANSI
2", 10K50
Probes Ø 22 mm rod or rope 89 38
(with fully insulated inactive
length)
! Note!
• The wall bracket forms part of the scope of delivery.
• The wall bracket first has to be screwed to the separate housing before you can use it as a
drilling template. The distance between the holes is reduced by screwing it to the separate
housing.
86
6.2
28
3 70
TI418F20
L00-FMI5xxxx-03-05-xx-xx-010
Endress+Hauser 17
Installation Liquicap M FMI51, FMI52
L00-FMI5xxxx-03-05-xx-xx-011
! Note!
The maximum connection length between the probe and the separate housing is 6 m. When
ordering a device with a separate housing, the desired length must be specified.
If the cable connection has to be shortened or led through a wall, it must be separated from
the process connection. Please proceed as follows:
1. Pressing screw
2. Insert seal RD
YE
25. Solder the red (RD) strand
with the central core of the
3. Cone GN/YE coaxial cable (probe)
24. Solder the yellow (YE) strand
4. Heatshrinking sleeve with the screening of the
coaxial cable (ground)
5. Cabel gland 23. Strand yellow/green (YE/GN)
with a ring terminal
6. Seal
7. Adapter disk
8. Seal
9. Plug M3 22. Coaxial cable with central core
10. Split washer and screening
11. Strand yellow/green (YE/GN) with ring terminal 21. Strand black (BK)
12. Strand yellow (YE) with ring terminal and (not required)
heatshringking sleeve 20. External screening
13. Snap ring (not required)
14. Nut M4
15. Split washer
16. Strand red (RD) with ring terminal and
heatshringking sleeve
17. Blade plug
18. Tube
L00-FMI5xxxx-03-05-xx-en-005
18 Endress+Hauser
Liquicap M FMI51, FMI52 Installation
• Loosen the pressing screw (1) with an open-end wrench (AF22). If necessary, hold the
process connection. Please make sure that neither the connecting cable nor the probe is
turning with the pressing screw.
• Pull the insert seal (2) out of the cable gland (5).
• Using an open-end wrench (AF22), disconnect the cable gland (5) from the adapter disk.
If necessary, hold it against the adapter disk (7) using an open-end wrench AF34.
• Loosen the adapter disk (7) from the tube (18).
• Remove the snap ring (13) with a pair of snap ring pliers.
• Clutch the nut (M4) of the blade plug with a pair of pliers and pull this out.
! Note!
• If you are shortening the connecting cable, we recommend to reuse all strands with ring
terminals.
• If the strands are not to be reused, the crimp connections of the new ring terminals fitted
must be isolated with a heat shrinking sleeve (risk of short-circuiting).
• All soldered joints must be insulated. Use heat-shrink tubes to do so.
L00-FMI5xxxx-17-00-00-xx-003
! Note!
The following applies for probes with a parallel thread and supplied seal:
Endress+Hauser 19
Installation Liquicap M FMI51, FMI52
! Note!
Use spring washers (1).
It is recommended to retighten the flange bolts periodically, depending on process
temperature and
pressure. Recommended torque: 60 to 100 Nm.
spring washers
L00-FMI5xxxx-17-00-00-en-005
! Note!
For housing type T13 with a separate connection compartment, the Phillips screw for
aligning the housing is also located in the electronics compartment.
20 Endress+Hauser
Liquicap M FMI51, FMI52 Installation
1. 2. 3.
2
1
1 2
1 2
... 270°
4.
L00-FMI5xxxx-04-00-00-xx-002
Endress+Hauser 21
Wiring Liquicap M FMI51, FMI52
4 Wiring
" Caution!
Before connecting the supply voltage, note the following:
• The supply voltage must match the data specified on the nameplate (1).
• Switch off the supply voltage before connecting the device.
• Connect the potential equalization to the ground terminal on the sensor.
! Note!
• When using the probe in hazardous areas, the relevant national standards and the
information in the safety instructions (XA) must be observed.
• Use the specified cable gland only.
" Caution!
In Ex-applications, the screen may only be grounded on the sensor side.
Connect the potential equalization to the outer ground terminal of the housing (T13, F13,
F16, F17, F27). In the case of the stainless steel housing F15, the ground terminal
(depending on the version) can also be located in the housing.
For further safety instructions, please refer to the separate documentation for applications
in hazardous areas.
22 Endress+Hauser
Liquicap M FMI51, FMI52 Wiring
3 mm
(1/8 in)
FEI..
max. 2.5 mm²
(max. AWG 14)
M20x1.5 *
max. 4 mm²
ød
(max. AWG 12)
L00-FTI5xxxx-04-05-xx-xx-011
* Cable entries
Nickel-plated brass: d = 7 to 10.5 mm (0.28 to 0.41 in)
Synthetic material: d = 5 to 10 mm (0.2 to 0.38 in)
Stainless steel: d = 7 to 12 mm (0.28 to 0.47 in)
Endress+Hauser 23
Wiring Liquicap M FMI51, FMI52
4.1.4 Connector
For the version with a connector M12, the housing does not have to be opened for
connecting the signal line.
1 +
4 3
2 not used
3 –
1 2
4 ground
L00-FTI5xxxx-04-06-xx-xx-015
Connection compartment
Determining the explosion protection:
Housing Standard EEx ia EEx d Gas-tight
process seal
Polyester housing F16 X X - -
Stainless steel housing F15 X X - -
Aluminum housing F17 X X - -
Aluminum housing F13 X X X X
Stainless steel housing F27 X X X X
Aluminum housing T13 X X X X
(with separate connection
compartment)
FEI5x
4...20 mA – +
FEI5x –x+
FEI5
– +
FEI5x 1 2
IS - Ground
+ –
1 2
L00-FMI5xxxx-04-00-00-xx-001
24 Endress+Hauser
Liquicap M FMI51, FMI52 Wiring
a. b.
1
I=16mA
7 3
FEI55
8/16mA – 5 +
11...36V DC
– +
1 2
L00-FTI5xxxx-04-06-xx-xx-003
a. + b.
2 – +
1 2
– +
1 2
IS - Ground
IS - Ground
1
1 2
L00-FTI5xxxx-04-06-xx-xx-004
Endress+Hauser 25
Wiring Liquicap M FMI51, FMI52
PML
1 2
– +
L00-FMI5xxxx-04-00-00-en-002
Gleichspannungs-
quelle
oder
2 (+)
1 (–) 4...20 mA SPS
250 Ώ
dsdmdm
df das.
asdas fa
asas la.
FMP40: LIC0001
ONLINE
1 GROUP SELECT
2 PV 8.7 m
HELP SAVE
6
9 Page
Up
Bksp
#%&
1
Page
On
ABC
2
Delete
DEF
3
- ToF Tool -
FieldTool
Copy Paste Hot Key
PQRS TUV W XY Z
7 8 9
,()‘ _<> +*/
Package
. 0 -
Display - + 375
FIELD COMMUNICATOR
+ -
- FieldCare
5 -
4...20m
FEI50H
A HART Commubox
+
3
7
DXR375 FXA195
1
L00-FMI5xxxx-04-00-00-en-015
" Caution!
If the HART communication resistor is not integrated in the supply unit, a 250
communication resistor must be included in the 2-wire line.
26 Endress+Hauser
Liquicap M FMI51, FMI52 Operation
5 Operation
PLC
FieldCare
Commubox FXA195
EX EX
Transmitter power
Measured Value
e.g. RMA422 + ¿
or RN221N
(with integrated dsdmdm
Display and
df das.
asdas fa
asas la.
DELTABAR: * * * * * * * *
ONLINE
communication
1 QUICK SETUP
2 OPERATING MENU
3 PV 352 mbar
4 SV 0 °C
resistor)
HELP SAVE
operating module
6
9
Bksp
Page
Page
Up
Delete (optional)
On
PQRS TUV W XY Z
7 8 9
ENDRESS + HAUSER
RMA 422
FXA195 ,()‘
.
_<>
0
+*/
-
HART handheld terminal
or
375
FIELD COMMUNICATOR
DXR375/475
L00-FMI5xxxx-14-00-06-en-001
Endress+Hauser 27
Operation Liquicap M FMI51, FMI52
Function switch
– Key 7 3 + Key
FEI50H
4...20mA - 5 +
- +
+ -
Display
Current pick-off
4...20 mA
4.0 mA
V= V~
L00-FMI5xxxx-07-05-xx-en-100
28 Endress+Hauser
Liquicap M FMI51, FMI52 Operation
(d)
L00-FMI5xxxx-19-05-xx-en-012
(a): Name of what is being displayed, e.g. Main menu view; (b): Item code of function displayed; (c): Softkey symbols;
(d): Keys
Display symbols
Symbol Meaning
User
User parameters can be edited.
Locked
All parameters are locked.
Scrollbar
This symbol tells you whether you can scroll up or down to get to more functions other than
those shown on the display.
Display parameter
The parameter cannot be edited in the current operating mode of the device.
Write parameter
The parameter can be edited.
Endress+Hauser 29
Operation Liquicap M FMI51, FMI52
Symbol Meaning
Down
Moves the bar downwards in a picklist.
Up
Moves the bar upwards in a picklist.
Enter
• Enter the selected submenu or selected function.
• Confirm the edited function value.
Previous function
Go to the previous function within the function group.
Next function
Go to the next function within the function group.
Confirm selection
From the picklist, select the option the bar is currently on.
Increase value
Increases the selected position of an alphanumeric function.
Decrease value
Decreases the selected position of an alphanumeric function.
Error list
Opens the list of the errors currently present.
The symbol is inverted and flashes if a warning is present.
The symbol appears constantly if an alarm is present.
Increase contrast
Increases the contrast of the display module.
Decrease contrast
Decreases the contrast of the display module.
Locking
Locks the device against parameter changes.
Locking can only be reversed by entering a release code.
30 Endress+Hauser
Liquicap M FMI51, FMI52 Operation
Function codes
The functions of Liquicap M are arranged in an operating menu. A 5-digit item code is
shown on the display for every function to aid orientation within the menu.
CX001
main menu
basic setup
safety settings
linearisation
↑
CX001
↑ ↵ A B C
L00-FMI5xxxx-07-05-xx-en-001
1) The function groups available depend on the device version, the installation environment and the operating mode selected.
Endress+Hauser 31
Operation Liquicap M FMI51, FMI52
Measured Value
64.50 %
+ ↵
CX001
main menu
basic setup
safety settings
linearisation
↑
↑ ↵ basic setup CLX00
medium : no build up
cal. type : wet
↑
↑
medium : no build up
cal. type : wet
↑
↑ ↵ medium property CLX01
no build up
build up
CLX00
basic setup
medium : no build up ↑
cal. type : wet ↑ Â
↑
↑ ↵ Abgleichart CLX03
dry
wet
CLX04
empty calibr. ↑
↑ Â
value empty : 0.000 %
measure capacity: 1.79 pF
confirm cal. : yes
↵
↑
↑
CLX04
empty calibr.
value empty : 0.000 %
measure capacity: 1.79 pF
confirm cal. : yes
↑
↑ ↵ empty calibr. CLX04
value
value empty
empty : 0.000 %
0.000 capacity: 1.79 % pF
measure
CLX04
empty calibr. confirm cal. : yes
value empty : 0.000 %
measure capacity: 1.79 pF – + ↵
confirm cal. : yes
↑
↑ ↵
CLX04
empty calibr.
value empty : 0.000 %
measure capacity: 1.79 pF
confirm cal. : yes
↑
full calibr. CLX05
↑ ↵
value full : 100.000 %
measure capacity : 1.85 pF
confirm cal. : yes
↵
↑
↑
CLX05
full calibr.
value full : 100.000 %
measure capacity : 1.85 pF
confirm cal. : yes
↑
↑ ↵ full calibr. CLX05
value
value fullfull
: 100.000 %
100.000
measure capacity : 1.85 % pF
CLX05
full calibr. confirm cal. : yes
value full : 100.000 %
measure capacity : 1.85 pF – + ↵
confirm cal. : yes
↑
↑ ↵
CLX05
full calibr.
value full : 100.000 %
measure capacity : 1.85 pF
confirm cal. : yes
↑
output damping CLX06 ↑ ↵
output damping : 1.0 s
↵
↑
↑
CLX06
output damping
output damping : 1.0 s
output
output damping
damping : 1.0 s
1.0 s
– + ↵
L00-FMI5xxxx-05-06-xx-en-002
32 Endress+Hauser
Liquicap M FMI51, FMI52 Operation
Launching menus
! Note!
If you are within a submenu and do not press a key for 15 minutes, the display automatically
switches to the main screen (measured value).
Navigation always starts with the main screen (measured value display). From here, you can
go to the following menus with the aid of the keys:
Measured Value
64.50 %
+ ↵
Measured Value
1040.00 pF
+ ↵ actual error
Warning 103
Alarm 101
...
...
L00-FMI5xxxx-19-05-xx-en-011
• Measured value
Displays the measured value in %, mA or pF.
• Main menu
The main menu contains all the parameters of Liquicap M. It is split into submenus. Some
of the submenus themselves have additional submenus.
An overview of the submenus and the functions they contain is provided in the
"Commissioning" section.
• Actual errors
If the automatic monitoring function of Liquicap M detects an error, the related softkey
symbol appears over the center key.
If the softkey symbol is flashing, only "Warning"-type errors are present2).
If the symbol is displayed continuously, at least one "Alarm"-type error is present.
Once you press the key, a list appears with all the errors currently pending.
2) See Section 9.2, "System error messages" for information on the difference between a "Warning" and an "Alarm".
Endress+Hauser 33
Operation Liquicap M FMI51, FMI52
Selecting a submenu
CX001
main menu
basic setup
safety settings
linearisation
↑
↑ ↵
1. Press W or V until the desired submenu is
selected.
1.
CX001
main manu
safety settings
linearisation
output
↑
↑ ↵
2. Press to enter the selected submenu.
2.
L1008
linearisation
type : none
mode : level
simulation : sim. off
L1008
linearisation
type : none
mode : level
simulation : sim. off
↑
↑ ↵
L00-FMI5xxxx-19-05-xx-en-001
! Note!
You can return to the next-highest menu level any time by pressing .
34 Endress+Hauser
Liquicap M FMI51, FMI52 Operation
CLX00
basic setup
medium : no build up
cal. type : wet
↑
↑
1. Press U or T until you reach the desired
function.
1.
CLX04
empty calibr.
value empty : 0.000 %
measure capacity: 1.79 pF
confirm cal. : yes
↵
↑
↑
2.
CLX18
empty calibr.
value empty : 0.000 %
measure capacity: 1.79 pF
confirm cal. : yes
↑
↑ ↵ 3. Use W and V to select the desired subfunction.
(This step is not necessary if the function only
has one subfunction.)
3.
CLX18
empty calibr.
value empty : 0.000 %
measure capacity: 1.79 pF
confirm cal. : yes 4. Press to enter the subfunction.
↑
↑ ↵ The editing process that follows depends on
the type of subfunction selected (picklist,
numeric function or alphanumeric function).
Details are explained in the following sections.
4.
L00-FMI5xxxx-19-05-xx-en-002
! Note!
You can leave the function at any time and return to the next-highest menu level by pressing
.
Endress+Hauser 35
Operation Liquicap M FMI51, FMI52
CLX02
unit level
%
m
mm
↑
↑ Â
1. Press W or V until the bar is on the desired
option
(here: "m").
1.
CLX02
unit level
%
m
mm
↑
↑ Â
2. Press ¬ to select this option.
The new value is now transferred to the device.
If required, you can edit another subfunction in
2. the same way.
CLX00
basic setup
medium : no build up
unit level : m
cal. type : wet
↑
↑ ↵
L00-FMI5xxxx-19-05-xx-en-003
! Note!
You can leave the function at any time and return to the next-highest menu level by pressing
.
36 Endress+Hauser
Liquicap M FMI51, FMI52 Operation
CLX04
empty calibr.
value
value empty
empty : 0.000 %
5.000 capacity : 1.79 % pF
measure
confirm cal. : yes
– + ↵
2. Press to enter the value and go to the next
position.
2.
CLX04
empty calibr.
value
value empty
empty : 0.000 %
5.000 capacity : 1.79 % pF
measure
confirm cal. : yes
– + ↵
3. Follow the same procedure for the positions
3.
that follow.
CLX04
empty calibr.
value
value empty
empty : 0.000 %
5.500 capacity : 1.79 % pF
measure
confirm cal. : yes
– + ↵
4. Once all the necessary positions have been
entered, press S or O until appears at the
marker.
4.
CLX04
empty calibr.
value
value empty
empty : 0.000 %
↵ capacity : 1.79 % pF
5.500
measure
confirm cal. : yes
– + ↵
5. Press to transfer the entire value to the
device.
5.
CLX04
empty calibr.
value empty : 5.500 %
measure capacity : 1.79 pF
confirm cal. : yes
↑
↑ ↵
L00-FMI5xxxx-19-05-xx-en-004
Endress+Hauser 37
Operation Liquicap M FMI51, FMI52
CLX04 CLX04
↵
empty calibr. empty calibr.
value
value empty
empty : 0.000 % value empty : 5.500 %
↵ capacity : 1.79 % pF
5.500
measure measure capacity : 1.79 pF
confirm cal. : yes confirm cal. : yes
↑
– + ↵ ↑ ↵
L00-FMI5xxxx-19-05-xx-en-005
Enter: The number to the left of the marker is transferred to the device.
CLX04 CLX04
empty calibr. empty calibr.
value
value empty
empty : 0.000 % value empty : 5.500 %
5.800 capacity : 1.79 % pF
measure measure capacity : 1.79 pF
confirm cal. : yes confirm cal. : yes
↑
– + ↵ ↑ ↵
L00-FMI5xxxx-19-05-xx-en-006
Escape: You exit the editor. The old function value remains.
CLX04 CLX04
empty calibr. empty calibr.
value
value empty
empty : 0.000 % value
value empty
empty : 0.000 %
5.500 capacity : 1.79 % pF
measure 5.500 capacity : 1.79 % pF
measure
confirm cal. : yes confirm cal. : yes
– + ↵ – + ↵
L00-FMI5xxxx-19-05-xx-en-007
CLX04 CLX04
empty calibr. empty calibr.
value
value empty
empty : 0.000 % value
value empty
empty : 0.000 %
5.500 capacity : 1.79 % pF
measure 5.500 capacity : 1.79 % pF
measure
confirm cal. : yes confirm cal. : yes
– + ↵ – + ↵
L00-FMI5xxxx-19-05-xx-en-008
38 Endress+Hauser
Liquicap M FMI51, FMI52 Operation
CLX04 CLX04
empty calibr. empty calibr.
value
value empty
empty : 0.000 % value
value empty
empty : 0.000 %
5.500 capacity : 1.79 % pF
measure 5.5
measure capacity : 1.79 % pF
confirm cal. : yes confirm cal. : yes
– + ↵ – + ↵
L00-FMI5xxxx-19-05-xx-en-009
Delete: The current position and all positions to the right of this position are deleted.
↑
↑
L00-FMI5xxxx-19-05-xx-en-010
Pressing the left and center key simultaneously has the following effect:
• Takes you from the editing mode to the display mode of the functions
• Takes you from the display mode of the functions to the submenu
• Takes you from the submenu to the main menu
• Takes you from the main menu to the measured value display.
3) See Section 9.2, "System error messages" for information on the difference between a "Warning" and an "Alarm".
Endress+Hauser 39
Operation Liquicap M FMI51, FMI52
Locking
Go to the "Safety settings" function.
In the menu, the current locking status of the device is displayed in the "Status" subfunction
under "Safety settings" (SAX01). The following values can appear:
• Unlocked
All parameters can be modified.
• Locked
The device has been locked by means of the operating menu. It can only be enabled again
by entering "100" in the "Safety settings" function.
If an attempt is made to change a parameter, the device goes to the "Safety settings"
function. "Key locking" is displayed in the "Status" subfunction. Press all the keys
simultaneously. The device then goes back to the original function and all the parameters
can be changed again.
• Key locked
The device has been locked by means of the operating keys. It can only be enabled again
by pressing all three keys simultaneously.
! Note!
A key symbol is shown on the display when locked.
Effects of a reset
• All parameters are reset to the factory setting.
• The linearization is reset to "linear". However, any linearization table available is retained
and can be activated again where necessary.
! Note!
The factory setting of the parameters is marked in bold in the menu overview (see the "Basic
setup" menu ff.).
Performing a reset
To carry out a reset, enter the value "333" in the "Device properties/Diagnosis/Password
reset/Reset" function.
40 Endress+Hauser
Liquicap M FMI51, FMI52 Operation
! Note!
Further information on FieldCare is provided on the CD-ROM which is supplied with the
device.
Menu-guided commissioning
Basic setup2_de
Connection options:
• HART with Commubox 195
Endress+Hauser 41
Operation Liquicap M FMI51, FMI52
dsdmdm
df das.
asdas fa
asas la.
dsdmdm
df das.
asdas fa
asas la.
FMI51: LIC0001
FMR231: LIC0001 ONLINE
ONLINE
1 GROUP SELECTION
1 GROUP SELECT
2 PV 8.7 m 2 PV 8.7 m Delete
HELP SAVE
H dsdmdm
df das.
asdas fa
asas la.
1 BASIC SETUP
Bksp Delete 2 SAFETY SETTINGS Delete
3 LINEARISATION
Page 4 EXTENDED CALIB.
On Bksp 5 OUTPUT
#%& ABC DEF
1 2 3
Copy
GHI
Paste
JKL
Hot Key
MNO
H dsdmdm
df das.
asdas fa
asas la.
L00-FMI5xxxx-07-00-00-xx-007
! Note!
• Further information on the HART handheld terminal can be found in the associated
Operating Instructions which can be found in the carrying case for the device.
42 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
6 Commissioning
! Note!
The device is operated via the electronic insert, the display or with FieldCare. If a display is
attached to the electronic insert, the function keys (- key/ + key) and the Mode switch at the
electronic insert are deactivated. All other settings can be made using the function keys on
the display or with FieldCare.
! Note!
• On leaving the factory, Liquicap M devices are calibrated for media with a conductivity of
100 μS/cm (e.g. for all water-based liquids, acids, alkalis ...). A recalibration is only
necessary if the 0 %-value or the 100 %-value should be adjusted to suit customer-specific
requirements, the distance to the tank wall is < 250 mm or if the liquid is not conductive.
• Only the "Wet" type of calibration can be carried out without the display and operating
module.
During wet calibration ("Wet" operating mode), the 0 %-value and/or the 100 %-value is
adjusted to customer-specific requirements. This calibration can be carried out if the tank is
empty, full or partially full. During full calibration, the probe must be covered by liquid in the
installed state.
An empty and full calibration must be performed.
Function switch
– Key 7 3 + Key
FEI50H
4...20mA - 5 +
- +
+ -
Display
Current pick-off
4...20 mA
4.0 mA
V= V~
L00-FMI5xxxx-07-05-xx-en-100
Endress+Hauser 43
Commissioning Liquicap M FMI51, FMI52
! Note!
Before carrying out empty and full calibration, the medium properties must be configured. If
the medium is conductive and tends to form buildup, the "Buildup" operating mode must be
selected.
In this operating mode, the buildup on the probe rod is compensated.
The "No buildup" operating mode is set at the factory.
Proceed as follows to chose between media forming buildup (e.g. yoghurt) and media not
forming buildup (e.g. water):
• Turn the function switch to position 4
• "Buildup" operating mode
=> Press the + key for media that tend to form buildup.
=> The green LED confirms your entry by flashing three times.
• "No buildup" operating mode
=> Press the – key for media that do not form buildup.
=> The green LED confirms your entry by flashing three times.
44 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
Too high a level reduces the accuracy of the zero point (corresponds to the empty tank). An
ammeter must be connected to the current pick-off at the electronic insert.
Let us presume that the level was determined for 15 %. Now the current value that
corresponds to the level of 15 % must be determined. The lower current value can be
adjusted with the +/– keys. The + key increases the value, the – key reduces the value. The
following must also be considered:
1. The lower current value (= empty tank, 0 %) is 4 mA.
2. The upper current value (= full tank, 100 %) is 20 mA.
3. This results in a measuring range of 16 mA for a change from 0 % to 100 %,
i.e. 0.16 mA increase in the current for every 1 % increase in the level.
4. For a 15 % level, this is 15 % x 0.16 mA/% which equals 2.4 mA. This must be added to
the 4 mA to obtain the current value to be set: 2.4 mA + 4 mA = 6.4 mA.
Endress+Hauser 45
Commissioning Liquicap M FMI51, FMI52
4. For a 90 % level, this is 90 % x 0.16 mA/% which equals 14.4 mA. This must be added
to the
4 mA to obtain the current value to be set: 14.4 mA + 4 mA = 18.4 mA. (You can also
take
the upper current value and then subtract 10 % x 0.16 mA/% = 1.6 mA from 20 mA.)
! Note!
• From version FW: V 01.03.00
• Before and after the automatic proof test, it is essential to check whether the level value
displayed corresponds to the actual level value.
When the self-test is activated, the current output is set to 4 mA and follows a ramp function
up to 22 mA. This test is completed after approx. 40 s.
! Note!
After the self-test, the device automatically returns to the operating mode.
" Caution!
The reset can affect the measurement as the current values are overwritten by those of the
factory calibration (0 % (4 mA) and 100 % (20 mA)).
Proceed as follows to restore the factory settings:
• Disconnect the electronic insert from the power supply
• Turn the function switch to position 7
46 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
• Press and hold the – and + keys together while the device is being reconnected to the
power supply
=> red LED flashes slowly and then starts to flash quickly
• The device reset is complete when the red LED goes out
• Release the – and + keys again
Proceed as follows to transfer the calibration values from the sensor to the electronic insert:
Upload
• Turn the function switch to position 8
• Press the + key to start uploading from the sensor to the electronic insert
=> The green LED flashes for approx. 2 s, thereby confirming your entry.
=> The device now restarts.
Endress+Hauser 47
Commissioning Liquicap M FMI51, FMI52
! Note!
If a reset is performed at the device and if the power supply is switched off and on again, the
language of the display texts has to be selected again.
Menu structures: Main menu
The main menu is activated by means of the right Enter key .
The following menu headings appear. These are explained in more detail over the following
pages:
• "Basic setup"
• "Safety setting " ( ä 54)
• "Linearization" ( ä 58)
• "Output" ( ä 64)
• "Device properties" ( ä 68)
! Note!
• Liquicap M devices are calibrated on leaving the factory for media with a conductivity of
100 μS/cm (e.g. for all water-based liquids, acids, alkalis ...). A recalibration is only
necessary if the 0 %-value or the 100 %-value should be adjusted to suit customer-specific
requirements, the distance to the tank wall is < 250 mm or if the liquid is not conductive.
• A distinction is generally made between two types of calibration:
Wet calibration:
During wet calibration ("Wet" operating mode), the probe must be covered by liquid in the
installed state. This calibration can be carried out if the tank is empty, full or partially full.
Empty and full calibration must be performed.
• Dry calibration
During dry calibration, empty and full calibration can be carried out without the probe
being in contact with the liquid. The calibration values can be entered directly in units of
length (e.g. m, mm, ...) for example.
48 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
100 %
(on leaving factory)
100 % / 20 mA
(customer specific)
^
0%= 4.0 mA
(customer specific)
^
0%= 4.0 mA 0 % / 4 mA
(on leaving factory)
L00-FMI5xxxx-15-05-xx-en-000
You can make the following settings in the "Basic setup" menu:
Endress+Hauser 49
Commissioning Liquicap M FMI51, FMI52
CLX00
basic setup
medium : no build up
cal. type : wet
Medium : no buildup
Cal. type: Wet
↵
↑
↑
L00-FMI5xxxx-07-05-xx-en-003
! Note!
This function is only displayed if the function value "Dry" was selected under the subfunction
"Cal. type".
! Note!
This subfunction is only displayed if the function value "Nonconductive" was selected under
the subfunction "Medium property".
The dielectric constant for the liquid to be measured is entered here (e.g. 3.4)
50 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
! Note!
This subfunction is only displayed if the function value "Conductive" or "Nonconductive" was
selected under "Medium property".
The desired level unit for Basic setup is entered here.
! Note!
The calibration data can be calculated with CapCalc.xls ä 74.
With "Empty calibration", the 0 % value or the 4 mA value is assigned to the level value.
! Note!
The procedure applies to the "Wet" type of calibration. Information on "Dry" calibration is
provided further below.
! Note!
To keep the calibration error to a minimum, the level should be between 0 % and 30 %.
! Note!
The procedure applies to the "Wet" type of calibration. Information on "Dry" calibration is
provided further below.
! Note!
To keep the calibration error to a minimum, the level should be between 70 % and 100 %.
Endress+Hauser 51
Commissioning Liquicap M FMI51, FMI52
Thread length: L1 E
H4 for G1½ = 25 mm
H4 for G 1½ = 19 mm
Plug: 4 mA
10 mm rod = 10 mm 0%
16 mm rod = 15 mm L00-FMIxxxxx-19-00-00-xx-013
22 mm rod = 15 mm
"Value full"
F E "Value empty" ( ä 52)
L1 F
4 mA
0%
L00-FMIxxxxx-19-00-00-xx-014
52 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
Endress+Hauser 53
Commissioning Liquicap M FMI51, FMI52
L00-FMI5xxxx-07-05-xx-en-004
You can make the following settings in the "Safety settings" menu.
↑
↑
"Code" subfunction
With this subfunction, you can lock the device against unpermitted or unintentional
changes.
• Enter a number 100 to lock the device. Parameters can then no longer be modified.
• Enter "100" to unlock the device. Parameters can then be modified again.
54 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
"Status" subfunction
This subfunction displays the current locking status of the device. The following values can
appear:
• "Unlocked"
All writeable parameters can be modified.
• "Locked"
The device has been locked via the operating menu ("Code" subfunction). It can only be
unlocked by entering "100" in the "Code" subfunction.
! Note!
The "Parameter okay" subfunction has to be confirmed with "Yes" so the device can be locked
for the SIL/WHG operating mode. In addition, the SIL/WHG function value has to be selected
for the "Operating mode" subfunction and "Locked" must be set for the "Status" subfunction.
The device can be unlocked using the special release code. The release code is "7452".
Endress+Hauser 55
Commissioning Liquicap M FMI51, FMI52
! Note!
The "Parameter okay" subfunction has to be confirmed with "Yes" so the device can be locked
for the SIL/WHG operating mode. In addition, the SIL/WHG function value has to be selected
for the "Operating mode" subfunction and "Locked" must be set for the "Status" subfunction.
The device can be unlocked using the special release code. The release code is "7452".
"Status" subfunction
This subfunction displays the current locking status of the device. The following values can
appear:
• "Unlocked"
All writeable parameters can be modified.
• "Locked"
The device has been locked via the operating menu ("Code" subfunction). It can only be
unlocked by entering "100" in the "Code" subfunction.
56 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
! Note!
The "Parameter okay" subfunction has to be confirmed with "Yes" so the device can be locked
for the SIL/WHG operating mode. In addition, the SIL/WHG function value has to be selected
for the "Operating mode" subfunction and "Locked" must be set for the "Status" subfunction.
The device can be unlocked using the special release code. The release code is "7452".
"Output" subfunction
This function determines the value the output in question assumes when an alarm condition
occurs.
Options:
• "Max"
22 mA
• "Hold"
The last value is retained
• "User-spec."
As defined in the "Output value" subfunction
22 22 22
A C
B
3.8
t t t
L00-FMI5xxxx-19-05-xx-xx-006
! Note!
• From version FW: V 01.03.00
• Before and after the automatic proof test, it is essential to check whether the level value
displayed corresponds to the actual level value.
• After the self-test, the device automatically returns to the operating mode.
Endress+Hauser 57
Commissioning Liquicap M FMI51, FMI52
linearisation L1008
Linearization L1008 ! Note!
Type: None The number and type of subfunctions depend on the
type : none
mode : level
simulation : sim. off
Mode: Level type of linearization selected.
↵
Simulation: Sim. off Only the "Type" and "Mode" subfunctions are
↑
↑
always available.
L00-FMI5xxxx-07-05-xx-en-005
58 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
4) This function is only displayed if the "Sim. off" option was not selected under the "Simulation" subfunction.
5) This function is only displayed if the "User-spec." option was selected under the "Customer unit" subfunction.
6) This function is only displayed if the "Horizontal cyl" or "Sphere" option was selected under the "Type"
subfunction.
7) This function is only displayed if the "Pyramid bottom", "Conical bottom" or "Angled bottom" option was
selected under the "Type" subfunction.
8) This function is only displayed if the "Table" option was selected under the "Type" subfunction.
9) This function is not displayed if the "Table" option was selected under the "Type" subfunction.
"Type" subfunction
Select the type of linearization in this subfunction.
Options:
• "None"
In this type of linearization, the measured level is not converted but instead is output
linearly in the level unit selected (see "Unit level" function).
• "Linear"
In this type of linearization, the measured value output is linear to the measured level.
20 mA
100 %
L00-FMI5xxxx-19-05-xx-xx-001
Endress+Hauser 59
Commissioning Liquicap M FMI51, FMI52
Options:
• "Horizontal cyl."
• "Sphere"
In these types of linearization, the volume in a spherical tank or in a horizontal cylindrical
tank is calculated from the level.
20 mA
100 %
ø
(D)
L00-FMI5xxxx-19-05-xx-xx-002
Options:
• "Pyramid bottom"
• "Conical bottom"
• "Angled bottom"
In these types of linearization, the volume in the tank in question is calculated from the
level measured.
20 mA
100 %
H
4 mA kg, m³, ft³, ...
0% (a)
L00-FMI5xxxx-19-05-xx-xx-003
60 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
Options:
• "Table"
In this type of linearization, the measured value is calculated using a linearization table.
The table can comprise up to 32 "Level - Volume" value pairs. The table must be monotone.
20 mA
100 %
L00-FMI5xxxx-19-05-xx-xx-004
"Mode" subfunction
In this function, specify whether
the measurement should refer to level A or to
the empty area B.
20 mA
100 %
4 mA
0%
L00-FMI5xxxx-19-05-xx-xx-005
"Simulation" subfunction
In this subfunction, you can simulate the level or the volume by entering a level under "Sim.
level value" or a volume under "Sim. vol. value".
Endress+Hauser 61
Commissioning Liquicap M FMI51, FMI52
"Diameter" subfunction
In this subfunction, specify the diameter of the horizontal cylindrical tank or the spherical
tank (only for the "dry" type of basic setup).
"Edit" subfunction
Use this function to enter, modify or read the linearization table.
The following options are available:
• "Read"
The table editor is opened. The existing table can be read but not edited.
• "Manual"
The table editor is opened. Table values can be entered or modified.
• "Semi-automat."
The table editor is opened. The level value is read in automatically.
The related measured value (volume, weight or flow) must be entered by the user.
• "Delete"
The linearization table is deleted.
! Note!
The linearization table can only be edited if it is disabled (
"Status" subfunction)
Row function
Delete row
Insert row (before current row)
Return to the previous Move row Query: new position
step by this
key combination.
L00-FMI5xxxx-19-05-xx-en-013
62 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
Endress+Hauser 63
Commissioning Liquicap M FMI51, FMI52
output/calculat 01302
Output/calculat. O1302
Extended calibr.
extended calibr.
HART settings
simulation
↑
HART setting
↵
Simulation
↑
L00-FMI5xxxx-07-05-xx-en-006
↑
↑
Output Extended calibr. Extended calibr. Measuring range 2000 pF1)
4000 pF
Sensor DAT Stat. OK
Sensor DAT Upload
Download
Output/Calculat Curr. turn down On
Off
Turn down 4 mA2) 0%
Turn down 20 mA2 100 %
4 mA threshold On
Off
HART setting HART setting HART address 0
No. of preambles 5
Short TAG HART TAG
Output/Calculat Current span 4 to 20 mA
Fix. curr. HART
mA value3) 4 mA
Simulation Simulation Off
On
Simulation value4) xx.xx mA
! Note!
At the factory, the measuring range is always calibrated to the probe length ordered. If the
electronic insert is used in another probe, the measuring range must be configured in
accordance with the probe length.
64 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
"Output/Calculat." function
"Curr. turn down" subfunction (not available for "Current span", "Fix. curr. HART")
With this function, you can switch on the current turn down. The current output then only
refers to a (freely definable) part of the measuring range. This is then magnified when
displayed.
"Turn down 4 mA" subfunction (only for "Curr. turn down", "On")
In this function, enter the measured value at which the current should be 4 mA.
"Turn down 20 mA" subfunction (only for "Curr. turn down", "On")
In this function, enter the measured value at which the current should be 20 mA.
[mA]
20
Endress+Hauser 65
Commissioning Liquicap M FMI51, FMI52
[mA] [mA]
20 20
A B
4 4
3.8 3.8
! Note!
In multidrop operation, the output current is 4 mA as standard. However, it can be changed
in the "mA value" function.
Output/Calculat" function."
66 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
[mA] [mA]
20 20
A B
C
4
3.8
0
–10 0 100 [%, ...] 0 100 [%, ...]
L00-FMI5xxxx-19-05-xx-xx-011
"Simulation" function
"Simulation" subfunction
With this function, you can switch the simulation of an output current on and off.
Options:
• "Off"
Simulation does not take place. Instead, the device is in the measuring mode.
• "On"
The device is in the simulation mode. A measured value is not output. Instead, the current
output assumes the value defined in the "Simulation value" subfunction.
Endress+Hauser 67
Commissioning Liquicap M FMI51, FMI52
↑
↑
Device properties Display Language English
Deutsch
Francais
Espanol
Italiano
Nederlands
Display format Format Decimal
ft-in-1/16"
No of decimals x
x.x
x.xx
x.xxx
Sep. character . (dot)
,
Back to home 900 s
Diagnostics Actual error Actual error 1 ....
Actual error 2 ....
Actual error 3 ....
Last error reset errorlist Keep
Delete
Last error 2 ...
Last error 3 ...
Password/reset Reset 12345
Status Unlocked
Electronic temp. Electronic temp. xx.x °C
Max. temp. xx.x °C
Min. temp. xx.x °C
Temperature unit °C
°F
K
Min/Max temp. Keep
Delete
Reset Min.
Reset Max.
Measure capacity Measure capacity xxxx.xx pF
Max. capacity val xxxx.xx pF
Min. capacity val xxxx.xx pF
Min/Max capacity Keep
Delete
Reset Min.
Reset Max.
System parameters Device information Device designation Liquicap-FMI5x
Serial No. ...
EC Serial No. xxxxxxxxxxx
Device marking FMI51-
OrderCode
Device information Dev. rev x
Software version V01.xx.xx.xxx
DD version xx
Device information Working hour xxxxx h
Current run time 000d00h00m
Probe length Probe length xxx mm
Sensitivity 0.0
68 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
"Language" function
In this function, select the language for the display and operating module.
Options:
• "English"
• "Deutsch"
• "Français"
• "Español"
• "Italiano"
• "Nederlands"
"Format" subfunction
In this subfunction, select the display format for displaying numbers.
Options:
• "Decimal"
• "ft-in-1/16"
Endress+Hauser 69
Commissioning Liquicap M FMI51, FMI52
"Password/reset" function
With this function, you can restore the factory settings. All parameters are reset to their
factory setting.
"Reset" subfunction
In this subfunction, enter the reset code ("333" or "7864") to reset all the parameters to their
factory setting.
• The factory settings of the parameters are marked in bold in the menu overview.
• During a "333" reset, linearization is reset to "linear". However, any linearization table
available is retained and can be activated again where necessary.
The following subfunctions (marked with an asterisk (*)) are also reset.
• During a "7864" reset, linearization is reset to "linear" and the linearization table deleted.
70 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
! Note!
All functions listed below can be viewed only.
"Sensitivity" subfunction
You can read off the current sensitivity in mm/pF in this subfunction.
Endress+Hauser 71
Commissioning Liquicap M FMI51, FMI52
6.8 Operation
After Basic setup, Liquicap M outputs the measured value via
• the display and operating module
• the current output
(the entire measuring range (0 % to 100 %) is then mapped to the range (4 to 20 mA) of
the current output.
• the digital HART signal.
! Note!
After reinstalling FieldCare, or by clicking a link in the Help menu, a video can be activated
that explains the possible applications of the program in just a few minutes.
Startup_screen_de.tif
72 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
6.9.1
Menu-guided commissioning:
Basic setup:
Endress+Hauser 73
Commissioning Liquicap M FMI51, FMI52
3.)
2.)
1.)
L00-FMI5xxxx-15-05-xx-xx-000
The program calculates the calibration values on the basis of the data entered (e.g. probe
length, probe type, medium properties etc.). The secure functioning of interface
measurement can already be determined at this time.
The calculated calibration values can be transmitted to the FEI50H electronic insert via the
display or Fieldcare.
! Note!
Generally speaking, capacitance interface measurement is also suitable for very pronounced
emulsion layers. The emulsion layer average is always measured.
74 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
L00-FMIxxxxx-20-00-00-en-018
In the window that follows, click the [Next] button in the top right.
L00-FMIxxxxx-20-00-00-en-019
Endress+Hauser 75
Commissioning Liquicap M FMI51, FMI52
L00-FMIxxxxx-20-00-00-en-020
76 Endress+Hauser
Liquicap M FMI51, FMI52 Commissioning
"Empty calibration"
1. Fill the container with the top medium and perform "Empty calibration" 0 % (see basic
setup ä 48)
If it is not possible to fill with medium, "Empty calibration" can also be performed with
the probe exposed (in the air). A calibration inaccuracy of approx. 2.5 % per meter
should be expected here (oil and water are the reference media).
"Full calibration"
2. Fill the container with the bottom medium and perform "Full calibration" 100 % (see
basic setup ä 48)
You have now performed basic setup.
Endress+Hauser 77
Maintenance Liquicap M FMI51, FMI52
7 Maintenance
No special maintenance work is required for the Liquicap M level transmitter.
External cleaning
When externally cleaning Liquicap M, make sure that the cleaning agent used does not
attack or corrode the housing surface or seals.
Seals
The process seals of the sensor should be replaced periodically, especially when using
molded seals (aseptic version)! The intervals between seal replacement depend on the
frequency of the cleaning cycles and on the fluid and cleaning temperature.
Repair
The Endress+Hauser repair concept is devised in such a way that the devices have a modular
design and repairs can be carried out by the customers.
Spare parts are grouped into handy kits with related replacement instructions. The "Spare
parts" section lists all the spare part kits, including the order numbers, which you can order
from Endress+Hauser for repairing Liquicap M. For further information on service and spare
parts, please contact Endress+Hauser Service.
Replacement
After replacing a Liquicap M or the electronic insert, the calibration values must be
transferred to the replacement device.
• When the probe is replaced, the calibration values in the electronic insert can be
transferred to the sensor DAT (EEPROM) module via a manual download.
• When the electronic insert is replaced, the calibration values of the sensor DAT (EEPROM)
module can be transferred to the electronics via a manual upload.
This means that you can restart the device without having to carry out a new calibration.
( ä 47 Sensor DAT (EEPROM) Upload/download.)
78 Endress+Hauser
Liquicap M FMI51, FMI52 Accessories
8 Accessories
Endress+Hauser 79
Troubleshooting Liquicap M FMI51, FMI52
9 Troubleshooting
The operating status of the device is indicated by the LEDs on the electronic insert.
! Note!
For more accurate error analysis, see ä 81 "Error codes".
80 Endress+Hauser
Liquicap M FMI51, FMI52 Troubleshooting
Flashing
A 116 • A: Alarm
• 116: Download error
W 103, W153 Initializing - please wait Replace the electronics if the message does not
disappear after a few seconds
A 426 Data of Sensor-DAT (EEPROM) not Repeat download from electronic insert or
consistent perform a total reset
A 427 Hardware not recognized after Repeat download or perform a total reset.
replacement
A 1121 Current output not calibrated Contact Endress+Hauser-Service
Endress+Hauser 81
Troubleshooting Liquicap M FMI51, FMI52
W 1662 Temperature at electronic insert too Lower ambient temperature by suitable measures
high (max. temp. at sensor exceeded)
W 430 Data of probe and electronic insert Check probe, perform a total reset
not compatible
W 1806 Current output is in simulation mode Set current output to normal mode
! Note!
If none of the proposed remedial measures achieves the desired result, perform reset 2
ä 46.
82 Endress+Hauser
Liquicap M FMI51, FMI52 Troubleshooting
F16 housing
2
8 6 4
1
7 5 3
1 = Guard
2 = SDA_TXD
3 = GND
4 = GND EEPROM
5 = GND
6 = DVCC (3V)
7 = Probe
8 = SCL RXD
1
7 5 3
2
8 6 4
BA298Fen080
9.5 Return
The measuring device must be returned if it is need of repair or a factory calibration, or if
the wrong measuring device has been delivered or ordered. Legal specifications require
Endress+Hauser, as an ISO-certified company, to follow certain procedures when handling
products that are in contact with the medium.
To ensure safe, swift and professional device returns, please refer to the procedure and
conditions for returning devices provided on the Endress+Hauser website at
http://www.endress.com/support/return-material
Endress+Hauser 83
Troubleshooting Liquicap M FMI51, FMI52
9.6 Disposal
When disposing of the device, make sure the device components are separated based on the
materials used and recycled where possible.
84 Endress+Hauser
Liquicap M FMI51, FMI52 Technical data
10 Technical data
10.2 Input
Endress+Hauser 85
Technical data Liquicap M FMI51, FMI52
L3
100 %
Note!
When installing in a nozzle, use inactive
≥500 (19.7)
length (L3).
L1
The 0 %, 100 % calibration can be
inverted.
0%
L00-FMI5xxxx-15-05-xx-xx-002
Dimensions mm (in)
10.3 Output
10.3.3 Linearization
The Liquicap M linearization function enables conversion of the measured value into any
desired length or volume units. Linearization tables for volume calculation of horizontal
cylindrical tanks and spherical tanks are pre-programmed. Any other tables with up to 32
value pairs can be input manually or semi-automatically.
86 Endress+Hauser
Liquicap M FMI51, FMI52 Technical data
t1 τ
L00-FMI5xxxx-05-05-xx-xx-009
= Output damping
t1= Dead time
! Note!
In an installed state, recalibration is only
necessary if:
L1
is < 250 mm
L00-FMI5xxxx-15-05-xx-xx-002
Endress+Hauser 87
Technical data Liquicap M FMI51, FMI52
10.4.8 Resolution
Analog in % (4 to 20 mA)
• FMI51, FMI52: 11 bit/2048 steps, 8 μA
• The resolution of the electronics can be directly converted to units of length of the probe
FMI51 or FMI52. For example, active probe rod 1000 mm.
Resolution = 1000 mm/2048 = 0.48 mm
10.5.6 Cleaning
Housing:
When cleaning, make sure that the cleaning agent used does not attack or corrode the
housing surface or seals.
Probe:
Depending on the application, buildup (contamination and soiling) can form on the probe
rod. A high degree of material buildup can affect the measurement result. If the medium
tends to create a high degree of buildup, regular cleaning is recommended. When hosing
down or during mechanical cleaning, it is important to make sure that the insulation of the
probe rod is not damaged.
88 Endress+Hauser
Liquicap M FMI51, FMI52 Technical data
! Note!
The temperature is restricted to Ta –40 °C if the polyester housing F16 is used or if additional
option B is selected (free from paint-wetting impairment substances, only FMI51).
Ta
°C
Ta 80 +80/
+70
60
TP +200/
40 +38
20
TP
0
–80 –60 –40 –20 0 20 40 60 80 100 120 140 160 180 200 °C
–20
–80/
–25 –40
–40/
–40
+20/
–60 –50
L00-FMI5xxxx-05-05-xx-xx-013
Endress+Hauser 89
Technical data Liquicap M FMI51, FMI52
Ta
°C +170/
+120
120
+200/
+100
* 100
Ta
80
60
TP
40
20
TP
0
–80 –60 –40 –20 0 20 40 60 80 100 120 140 160 180 200 °C
–20
–40
–60
L00-FMI5xxxx-05-05-xx-xx-011
Ta = Ambient temperature
TP = Process temperature
* The permitted ambient temperature at the separate housing is the same as indicated for the compact housing ä 89.
Refer to the following standards for the pressure values permitted at higher temperatures:
• EN 1092-1: 2005 Table, Appendix G2
With regard to its resistance/temperature property, the material 1.4435 is identical to
1.4404 (AISI 316L) which is grouped under 13E0 in EN 1092-1 Tab. 18. The chemical
composition of the two materials can be identical.
• ASME B 16.5a - 1998 Tab. 2-2.2 F316
• ASME B 16.5a - 1998 Tab. 2.3.8 N10276
• JIS B 2220
The lowest value from the derating curves of the device and the selected flange applies.
90 Endress+Hauser
Liquicap M FMI51, FMI52 Technical data
For process connections ½", ¾", 1", flanges DN50, ANSI 2", JIS 10K (10 mm rod)
For process connections ¾", 1", flanges DN50, ANSI 2", JIS 10K (16 mm rod)
Rod insulation: PTFE, PFA
Rope insulation: FEP, PFA
Pp
bar
40 +50/
+25
20
+200/
+2
TP
0
–80 –60 –40 –20 0 20 40 60 80 100 120 140 160 180 +200/ °C
–1
L00-FMI5xxxx-05-05-xx-xx-008
Pp : Process pressure
Tp : Process temperature
For process connections 1½", flanges DN50, ANSI 2", JIS 10K (16 mm rod)
Rod insulation: PTFE, PFA
Rope insulation: FEP, PFA
Pp
bar
+40/
+100
100
80
+80/
63 * +60
60
40
+200/
+20
20
TP
0
–80 –60 –40 –20 0 20 40 60 80 100 120 140 160 180 +200/ °C
–1
L00-FMI5xxxx-05-05-xx-xx-010
Pp : process pressure
Tp : process temperature
* For probes with an inactive length .
Endress+Hauser 91
Technical data Liquicap M FMI51, FMI52
Pp
bar
60 +50/
+50
40
20
+200/
+2
TP
0
–80 –60 –40 –20 0 20 40 60 80 100 120 140 160 180 +200/ °C
–1
L00-FMI5xxxx-05-05-xx-xx-012
Pp : Process pressure
Tp : Process temperature
10.8 Documentation
92 Endress+Hauser
Liquicap M FMI51, FMI52 Technical data
10.8.2 Certificates
Endress+Hauser 93
Technical data Liquicap M FMI51, FMI52
94 Endress+Hauser
Liquicap M FMI51, FMI52 Operating menu
11 Operating menu
The main menu is activated by means of the right Enter key .
The following menu headings appear. These are explained in more detail over the following
pages:
• "Basic setup"
• "Safety set."
• "Linearization"
• "Output"
• "Device properties"
You can make the following settings in the "Basic setup" menu.
Endress+Hauser 95
Operating menu Liquicap M FMI51, FMI52
↑
↑
Safety settings Safety settings I Code 1001)
Status Unlocked
Locked
Safety settings II Operating mode Standard
SIL/WHG
Output damping 1s
Output 1 MAX
Parameter okay no
Yes
Safety settings III Cap. empty x,xx pF
Value empty x,xxx %
Cap. full 2000.00 pF
Value full 100.000 %
Parameter okay no
Yes
Operating mode Operating mode Standard
SIL/WHG
SIL op. mode2) Unlocked
Locked
Status Unlocked
Locked
Output on alarm Output Max
Hold
User-spec.
Output value3) xx.xx mA
Proof test Proof test Off
On
96 Endress+Hauser
Liquicap M FMI51, FMI52 Operating menu
↑
↑
Linearization Linearization Type None
Linear1)
Horizontal cyl2)
Sphere2
Pyramid bottom3)
Conical bottom3)
Angled bottom3)
Table
Mode level
Ullage
Simulation Sim. off
Sim. level
Sim. volume
Sim. level value4) or xx.x %
Sim. vol. value4) xx.x %
Linearization Customer unit % (percentage), l, hl, m3, dm3, cm3, ft3, usgal,
igal, kg, t, lb, ton, m3, ft3, mm, inch, user-spec.
Customized text5) ...
Diameter6) xxxx m
Intermed. height7) xx m
Edit8) Read Table No.: 1
Input level: x m
Input volume: %
Manual Table No.: 1
Input level: x m
Input volume: %
Semi-automat. Table No.: 1
Input level: x m
Input volume: %
Delete
Status table7) Enabled
Disabled
Max. scale9) 100 %
Endress+Hauser 97
Operating menu Liquicap M FMI51, FMI52
↑
↑
Output Extended calibr. Extended calibr. Measuring range 2000 pF1)
4000 pF
Sensor DAT Stat. OK
Sensor DAT Upload
Download
Output/Calculat Curr. turn down On
Off
Turn down 4 mA2) 0%
Turn down 20 mA2 100 %
4 mA threshold On
Off
HART setting HART setting HART address 0
No. of preambles 5
Short TAG HART TAG
Output/Calculat Current span 4 to 20 mA
Fix. curr. HART
mA value3) 4 mA
Simulation Simulation Off
On
Simulation value4) xx.xx mA
98 Endress+Hauser
Liquicap M FMI51, FMI52 Operating menu
↑
↑
Device properties Display Language English
Deutsch
Francais
Espanol
Italiano
Nederlands
Display format Format Decimal
ft-in-1/16"
No of decimals x
x.x
x.xx
x.xxx
Sep. character . (dot)
,
Back to home 900 s
Diagnostics Actual error Actual error 1 ....
Actual error 2 ....
Actual error 3 ....
Last error reset errorlist Keep
Delete
Last error 2 ...
Last error 3 ...
Password/reset Reset 12345
Status Unlocked
Electronic temp. Electronic temp. xx.x °C
Max. temp. xx.x °C
Min. temp. xx.x °C
Temperature unit °C
°F
K
Min/Max temp. Keep
Delete
Reset Min.
Reset Max.
Measure capacity Measure capacity xxxx.xx pF
Max. capacity val xxxx.xx pF
Min. capacity val xxxx.xx pF
Min/Max capacity Keep
Delete
Reset Min.
Reset Max.
System parameters Device information I Device designation Liquicap-FMI5x
Serial No. ...
EC Serial No. xxxxxxxxxxx
Device marking FMI51-
OrderCode
Device information Dev. rev x
Software version V01.xx.xx.xxx
DD version xx
Device information III Working hour xxxxx h
Current run time 000d00h00m
Probe length Probe length xxx mm
Sensitivity 0.0
Endress+Hauser 99
Liquicap M FMI51, FMI52
Index
Numerics Editing numeric functions . . . . . . . . . . . . . . . . . . . . . . . . . 37
4 mA threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electromagnetic compatibility (EMC). . . . . . . . . . . . . . . . 22
A Electronic temp.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Empty calibr. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Actual error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Empty calibration ("Dry" operating mode) . . . . . . . . . . . . 52
Aligning the housing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Error signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
B Ex area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Basic setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43, 48, 50 Extended calibr.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
External cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
C
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 F
Cal. type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Fieldbus connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Calibration error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Full calibr.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Cap. empty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52, 55 Full calibration ("Dry" operating mode). . . . . . . . . . . . . . . 52
Cap. full . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Function and subfunction . . . . . . . . . . . . . . . . . . . . . . . . . 35
CapCalc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51, 74 Function switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Carrying out empty calibration . . . . . . . . . . . . . . . . . . . . 44
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . . . . 92 G
Code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Green LED flashing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Ground tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Commubox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Commubox FXA191/195 HART . . . . . . . . . . . . . . . . . . . 79 H
Confirm cal. Handheld terminal DXR375 . . . . . . . . . . . . . . . . . . . . . . . 42
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24, 26 HART - connecting with other supply units. . . . . . . . . . . 26
Curr. turn down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 HART address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Current run time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 HART handheld terminal DXR 375. . . . . . . . . . . . . . . . . . 42
Current span. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 HART settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Customer unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Customized text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 I
Inactive length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
D Incoming acceptance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DC value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Initial commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
DD version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Designated use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation and function check . . . . . . . . . . . . . . . . . . . . . 43
Dev. rev . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Intermed. height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Device designation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Device information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 K
Device marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Key combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Device properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48, 68 Key locking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Key unlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Diameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Keys (softkey operation) . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Display and operating elements (FEI50H) . . . . . . . . . . . 28
Display and operating module . . . . . . . . . . . . . . . . . . 29, 48
L
Display format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Display symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Last error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Last errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Download/upload sensor DAT . . . . . . . . . . . . . . . . . . . . . 47 Launching menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Dry calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48, 58, 61
Dry calibration for interface measurement . . . . . . . . . . 75 Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
E M
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
EC Serial No.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Edit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Marine approval (GL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Max. capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Editing functions with the picklist. . . . . . . . . . . . . . . . . . 36
100 Endress+Hauser
Liquicap M FMI51, FMI52
Endress+Hauser 101
W
Wall bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wet calibration
............................................. 48
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Working hour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
102
Index
103
71365416
www.addresses.endress.com