Experiment: Measurement of Power in Three Phase Balanced Load
Experiment: Measurement of Power in Three Phase Balanced Load
Experiment: Measurement of Power in Three Phase Balanced Load
Objective: To determine: (1) Relationship between phase and line voltage and current
Equipment: (1) Voltmeter: 150V, AC (2) Three phase balanced R-L Load (3) C-M Board
(4) AC Ammeter: 3 Amp (5) Three phase transformer (6) Wattmeter: 125V/5A
AR CAT
W
82 b2
2R1
3PHASE230 V SW FUSE
CR
c22 C.M. BOARD R2
Y L2
B
Circuit diagram
Theory:
Power measurement: The active power per phase in three
is the phase angle between phase voltage and
phase circuit is given by P=V,l,Cos6 Where
phase current.V, is phase voltage and I, is phase
current.Total power in three phase circuit is given by P=3 V, 1, Cos 0.
For star connections, V,=(V/W3) and I,= LP = 3(V/V3)( IL) Cos = N3 V, I,Cos .
(Ve-V,) Ic
P Instantaneous
reading of W,+ Instantaneous
reading of W2
Using phasor diagram, W, 13(VLX L) Cos (30° and
=
+0) W, =
V3v, I, Cos (30° -0)
Such that power in 3
phase circuit will be W=W+W=V3
load. (V)MCos 0, Where 0 is the phase angle of
Hence power=P=W=W+W=V3 (V)(NCos.
The Power factor
can be calculated as: cos =
cos [tan' {V3 (W-W,)/(W+W,)}]|
Procedure:
Connect the
experimental set up as shown in the circuit diagram.
Switch on the appropriate input
supply and measure the following,
Voltage across each phase (b) Voltage betvween line terminals
(C) Voltage across Rand L.(d)
Current in each phase by using the current measurement board.
Power: Wattmeter (W): keeping switch 1-2 open and closing switches 3-4& 5-6 closes.
(W): keeping switch 3-4 open and closing switches 1-2 &5-6 closed.
Record readings of all the instruments in the observations in table.
Observation:
Type of Voltage (V)
Circuit
Current V..L/A, Wattmeter Total Powe
(A) Readings Power Facte
Vp V V. V W W P=W+W Cos E
STAR
Report
>Discuss the discrepancies between calculated and
measured values.
Sketch the phasor diagràm in each case and calculate
reading of each watt meter.
Explain how sometimes a wattmeter reads negative reading in three phasc measurement.
Quiz questions:
1. The power taken by a three phase balanced load is given by.
2. The lcast number of
single phase watt meters required to mcasure total power consumed
unbalanced load feed from a three phase, four wire by an
system is .
3. In two-wattmeter method of
measuring three-phase power, one of the wattmeter shows
What will be the value of
power factor in this case?
zero reading.
4. If the power consumed
per phase by star connected balanced load is 200W, what will be the power
consumed per phase if the same load is connected in delta?