Fire Safety Compliance Report
Fire Safety Compliance Report
Fire Safety Compliance Report
COMPLIANCE REPORT:
FOUR-STOREY HOTEL
WITH ROOF DECK
1.0 Introduction 3
1.1 Scope 4
1.2 Short Project Description 5
1.3 Basis of Compliance 5
2.1 Hazard of Contents 6
2.2 Occupancy Classification 7
2.3 Fire Suppression 8
2.4 Design Criteria used for Sprinkler System/Standpipe 9
1.0 Introduction
The Fire Safety Compliance Report is submitted on behalf of our client, Mr. Jeffrey G.
Mercado. A report that includes all the necessary drawing and documentation in support of an
application for a Fire Safety Evaluation Clearance (FSEC) which is a requirement for
acquiring a Building Permit and an application for a Fire Safety Compliance and
Commissioning Report (FSCCR), a requirement for Fire Safety Inspection Certificate (FSIC)
for occupancy under the Republic Act 9514, The Fire Code of the Philippines of 2008 for the
proposed Four Storey Hotel with Roof Deck located in San Andres Manila.
1.1 Scope
Contents of the report are the documentation and drawings submitted for the application with
compliance of the requirements posted by The National Fire Prevention Association (NFPA).
Objective of this report is to satisfy the requirements and obligations set out by the RA 9514, The Fire
Code of the Philippines of 2008, which involves public safety, prevention and suppression of fire, and
promotion of fire service profession.
In this report it is demonstrated that the works, if carried out in accordance with the drawings and
documentation submitted with the application with performance requirements prescribed in this
report, will comply with the requirements of the National Fire Prevention Association (NFPA). It is
noted that the objective of the fire safety measures set out in this report is to satisfy the obligations of
the Republic Act 9514, The Fire Code of the Philippines of 2008, which are concerned with Health,
Safety and Welfare, and promote cost avoidance through fire suppression and prevention.
Additional measures may be necessary to protect against risk of property and consequential loss,
such measures are however a matter for the client and his insurers.
This report contains the following in accordance with the requirements of Section 9.0.3.2 of the
Republic Act of 9514, The Fire Code of the Philippines of 2008 as follows:
1. Short Project Description
2. Statement of the Codes and Standards used in the design
3. Discussion of Fire Protection and Life
i. Hazards of Contents
ii. Occupancy Classification
iii. Fire Suppression Description
iv. Design Criteria used for Sprinkler System/Standpipe
1. Suppression Systems
2. Portable Fire Extinguishers
3. Other Calculations
The project involves the design and computation on the installation of Fire protection
System of a Four-Storey Hotel with a Roof Deck, a residential occupancy, located at San Andres,
Manila and is currently owned by Engr. Jeffrey G. Mercado. The initial building plans suggests that
the building does not have any existing fire protection system which may deem to be Non-Compliant
if the building is constructed after the existence of National Fire Protection Association (NFPA). Thus,
an Automatic Fire Sprinkler System, a combined Standpipe System, and Portable Fire Extinguishers
that meet the standards of the current NFPA and codes of the RA 9514, The Fire Code of the
Philippines of 2008, shall be installed under the demands of the client . The Ground floor has a clear
area of approximately 116 m2 which includes the Fire Pump Room, EE Room, Linen Room, Reception
Area, Administration Office, and six bedrooms. The typical 2 nd to 4th floor has a total clear area of
approximately 504 m2 which includes eight bedrooms. The roof deck covers a clear area of
approximately 168 m2 which includes the covered laundry and ironing area.
● NFPA 10
3.3.3* Carbon Dioxide. A colorless, odorless, electrically nonconductive inert gas that is a
suitable medium for extinguishing Class B and Class C fires.
3.3.4 Chemical.
3.3.4.1* Dry Chemical. A powder composed of very small particles, usually
sodium bicarbonate-, potassium bicarbonate-, or ammonium phosphate-based with
added particulate material supplemented by special treatment to provide resistance
to packing, resistance to moisture absorption (caking), and the proper flow
capabilities. [17, 2017]
5.1 General Requirements. The selection of fire extinguishers for a given situation
shall be determined by the applicable requirements of Sections 5.2 through 5.6 and the
following factors:
(1) Type of fire most likely to occur
(2) Size of fire most likely to occur
(3) Hazards in the area where the fire is most likely to occur
(4) Energized electrical equipment in the vicinity of the fire
(5) Ambient temperature conditions
(6) Other factors (See Section H.2.)
5.1.1 Portable fire extinguishers shall be installed as a first line of defense to cope
with fires of limited size, except as required by 5.5.5.
5.1.2 The selection of extinguishers shall be independent of whether the building is
equipped with automatic sprinklers, standpipe and hose, or other fixed protection
equipment.
5.2 Classifications of Fires. Fires shall be classified in accordance with the
guidelines specified in 5.2.1 through 5.2.5.
5.2.1 Class A Fires. Class A fires are fires in ordinary combustible materials, such
as wood, cloth, paper, rubber, and many plastics.
5.2.2 Class B Fires. Class B fires are fires in flammable liquids, combustible liquids,
petroleum greases, tars, oils, oil-based paints, solvents, lacquers, alcohols, and flammable
gases.
5.2.3 Class C Fires. Class C fires are fires that involve energized electrical
equipment.
5.2.4 Class D Fires. Class D fires are fires in combustible metals, such as
magnesium, titanium, zirconium, sodium, lithium, and potassium.
5.2.5 Class K Fires. Class K fires are fires in cooking appliances that involve
combustible cooking media (vegetable or animal oils and fats).
● NFPA 13
4.1 Level of Protection. A building, where protected by an automatic sprinkler
system installation, shall be provided with sprinklers in all areas except where specific
sections of this standard permit the omission of sprinklers.
6.3.2* Steel Pipe —Welded or Roll-Grooved. When steel pipe referenced in Table
6.3.1.1 is used and joined by welding as referenced in 6.5.2 or by roll-grooved pipe and
fittings as referenced in 6.5.3, the minimum nominal wall thickness for pressures up to 300
psi (21 bar) shall be in accordance with Schedule 10 for pipe sizes up to 5 in. (125 mm),
0.134 in. (3.4 mm) for 6 in. (150 mm) pipe, 0.188 in. (4.8 mm) for 8 in. and 10 in. (200 mm
and 250 mm) pipe, and 0.330 in. (8.4 mm) for 12 in. (300 mm) pipe.
6.3.3 Steel Pipe — Threaded. When steel pipe referenced in Table 6.3.1.1 is joined
by threaded fittings referenced in 6.5.1 or by fittings used with pipe having cut grooves, the
minimum wall thickness shall be in accordance with Schedule 30 pipe [in sizes 8 in. (200
mm) and larger] or Schedule 40 pipe [in sizes less than 8 in. (200 mm)] for pressures up to
300 psi (21 bar).
6.3.4 Specially Listed Steel Pipe. Pressure limitations and wall thickness for steel
pipe specially listed in accordance with 6.3.10 shall be permitted to be in accordance with
the pipe listing requirements.
6.3.5* Copper Tube. Copper tube as specified in the standards listed in Table
6.3.1.1 shall have a wall thickness of Type K, Type L, or Type M where used in sprinkler
systems.
6.3.6 Brass Pipe. Brass pipe specified in Table 6.3.1.1 shall be permitted in the
standard weight in sizes up to 6 in. (150 mm) for pressures up to 175 psig (12 bar) and in the
extra strong weight in sizes up to 8 in. (200 mm) for pressures up to 300 psig (21 bar).
6.3.7 Stainless Steel Pipe. Stainless steel pipe as referenced in the standards listed
in Table 6.3.1.1 shall be in accordance with Schedules 10S or 40S pipe.
8.5.3.4 Minimum Distance Between Sprinklers.
8.5.3.4.1 A minimum distance shall be maintained between
sprinklers to prevent operating sprinklers from wetting adjacent sprinklers and to
prevent skipping of sprinklers.
8.5.3.4.2 The minimum distance permitted between sprinklers shall comply with the
value indicated in the applicable section for each type or style of sprinkler.
8.11.2.2.2 In any case, the maximum area of coverage of any sprinkler shall not
exceed 130 ft (12.1 m ).
2 2
8.15.3 Stairways.
8.15.3.1 Combustible Construction. Sprinklers shall be installed beneath all
stairways of combustible construction.
8.15.3.1.1 Sprinklers shall be installed at the top of combustible stair shafts.
8.15.3.1.2* Sprinklers shall be installed under the landings at each floor level.
8.15.3.1.3 Sprinklers shall be installed beneath the lowest intermediate landing.
8.15.3.2 Noncombustible Construction.
8.15.3.2.1 In noncombustible stair shafts having noncombustible stairs with
noncombustible or limited-combustible finishes, sprinklers shall be installed at the top of the
shaft and under the first accessible landing above the bottom of the shaft.
8.15.3.2.2 Where noncombustible stair shafts are divided by walls or doors,
sprinklers shall be provided on each side of the separation.
8.15.3.2.3 Sprinklers shall be installed beneath landings or stairways where the area
beneath is used for storage.
8.15.3.2.3.1 Sprinklers shall be permitted to be omitted from the bottom of the
stairwell when the space under the stairs at the bottom is blocked off so that storage cannot
occur.
8.15.3.2.4 Sprinklers shall be permitted to be omitted from exterior stair towers when
the exterior walls of the stair tower are at least 50 percent open and when the stair tower is
entirely of noncombustible construction.
8.15.3.3* Stairs Serving Two or More Areas. When stairs have openings to each side
of a fire wall(s), sprinklers shall be installed in the stair shaft at each floor landing with
multiple openings.
8.15.8.2* Closets and Pantries. Sprinklers are not required in clothes closets, linen
closets, and pantries within dwelling units in hotels and motels where the area of the space
does not exceed 24 ft2 (2.2 m2 ) and the walls and ceilings are surfaced with
noncombustible or limited-combustible materials.
8.15.11.2 Sprinklers shall not be required in electrical equipment rooms where all of
the following conditions are met:
(1) The room is dedicated to electrical equipment only.
(2) Only dry-type electrical equipment is used.
(3) Equipment is installed in a 2-hour fire-rated enclosure including protection for
penetrations.
(4) No combustible storage is permitted to be stored in the room.
9.1 Hangers.
9.1.1* General.
9.1.1.1 Unless the requirements of 9.1.1.2 are met, types of hangers shall be in
accordance with the requirements of Section 9.1.
9.1.1.2 Hangers certified by a registered professional engineer to include all of the
following shall be an acceptable alternative to the requirements of Section 9.1:
(1) Hangers shall be designed to support five times the weight of the water-filled pipe
plus 250 lb (115 kg) at each point of piping support.
(2) These points of support shall be adequate to support the system.
(3) The spacing between hangers shall not exceed the value given for the type of
pipe as indicated in Table 9.2.2.1(a) or Table 9.2.2.1(b).
(4) Hanger components shall be ferrous.
(5) Detailed calculations shall be submitted, when required by the reviewing
authority, showing stresses developed in hangers, piping, and fittings, and safety factors
allowed.
The Portable Fire Extinguisher selected for all areas is of the Multipurpose Dry Chemical
type. All areas have a sample of Class A, Class B, and Class C combustibles at the very least
which may propagate to the other larger quantity combustibles. To prevent this, the
Multipurpose Dry Chemical fire extinguisher is the most capable in extinguishing all three
classes of combustibles. A single fire extinguisher of this type will be placed inside each area
with accompanying signs.
Ground Floor
Pipe Length (mm) Computed No. of Pipe Hanger Actual No. of Pipe Hanger
Pipe Diamter:
Room 1
12345
12345