NFA2XSY-T (3 x 50/16 + 50 mm2 - 3 x 240/25 + 50 mm

2
2 ) 12/20 kV
2
NFA2XSY-T (3 x 50/16 + 50 mm - 3 x 240/25 + 50 mm ) 12/20 kV
Al / XLPE / CWS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Wire Screened, PVC Sheathed,
with Galvanized Steel Support Messenger )
Standard Specification : SPLN 43-5-2 : 1995
Phase Conductor :
Aluminium (AAC) with
Water Blocking Material
Construction Data Conductor Screen
Application : XLPE Insulation
Conductor Approximate For installation outdoors, in air
Insulation Screen
if no mechanical damage is likely to occur.
Nom. Overall Cable Semi Cond. Water
Cross Diameter Weight Blocking Tape
Section Special Features on Request
Copper Wire Screen
Area approx. approx. - Flame Retardant Cat A, B, C Copper Tape Screen
- UV Resistance Non Cond. Water
mm² mm kg/km - Anti Termite Blocking Tape
- Anti Rodent PVC Sheath
3 x 50/16 + 50 65.8 3208 - Low Smoke Zero Halogen
Messenger Conductor :
3 x 70/16 + 50 69.6 3549 Galvanized Steel Strand
PVC Insulation
3 x 95/16 + 50 73.2 3935

3 x 120/16 + 50 76.3 4273


Note :
Conductor Shaped
3 x 150/25 + 50 79.1 4827
50 - 240 sqmm supplied in compacted circular stranded conductor shape
3 x 185/25 + 50 84.0 5384
Standard Packing :
3 x 240/25 + 50 88.4 6008 50 - 240 sqmm will be supplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Current-Carrying Short
Calculated Capacity circuit current at 1 sec
DC AC Breaking Load at 30°C * of
Nom.
Resistance at Resistance of messenger in air
Cross Sect. Conductor Screen
20°C at 90°C
(mm²) (kA) (kA)
( Ω/km ) (Ω/km) ( kg ) (A)

3 x 50/16 + 50 0.641 0.822 6600 196 4.70 1.60

3 x 70/16 + 50 0.443 0.568 6600 245 6.58 1.60

3 x 95/16 + 50 0.320 0.411 6600 297 8.93 1.60

3 x 120/16 + 50 0.253 0.325 6600 343 11.28 1.60

3 x 150/25 + 50 0.206 0.265 6600 387 14.10 2.50

3 x 185/25 + 50 0.164 0.211 6600 448 17.39 2.50

3 x 240/25 + 50 0.125 0.161 6600 527 22.56 2.50


* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
24804-02 Rev. 0. 0 / 2013

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NFA2XSY-T (3xx50/16
NFA2XSY-T (3 50/16++95
95mm
mm2 2- -33xx240/25
240/25++9595mm
mm
2 ) 12/20 kV
2
) 12/20 kV
Al / XLPE / CWS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Wire Screened, PVC Sheathed,
with Galvanized Steel Support Messenger)
Standard Specification : SPLN 43-5-2 : 1995

Construction Data Phase Conductor :


Application : Aluminium (AAC) with
Conductor Approximate For installation outdoors, in air Water Blocking Material
if no mechanical damage
Nom. Overall Cable is likely to occur.
Conductor Screen
Cross Diameter Weight XLPE Insulation
Section Special Features on Request
Insulation Screen
Area approx. approx. - Flame Retardant Cat A, B, C
Semi Cond. Water
Blocking Tape
- UV Resistance
mm² mm kg/km - Anti Termite
Copper Wire Screen
Copper Tape Screen
- Anti Rodent
3 x 50/16 + 95 65.8 3540 Non Cond. Water
- Low Smoke Zero Halogen
Blocking Tape
3 x 70/16 + 95 69.6 3884 PVC Sheath
Messenger Conductor :
3 x 95/16 + 95 73.2 4262 Galvanized Steel Strand
PVC Insulation
3 x 120/16 + 95 76.3 4601
Note :
3 x 150/25 + 95 79.1 5182 Conductor Shaped
50 - 240 sqmm supplied in compacted circular stranded conductor shape
3 x 185/25 + 95 84.0 5661
Standard Packing
3 x 240/25 + 95 88.4 6319 50 - 240 sqmm will be supplied in wooden drum on available length
Length Tolerance per drum ± 2%

Electrical Data
Conductor Short
Calculated Current-Carrying
circuit current at 1 sec
Breaking Load Capacity
Nom. DC AC of
of messenger at 30°C *
Cross Resistance Resistance in air
Sect. at 20°C at 90°C Conductor Screen
(mm²) ( Ω/km ) (Ω/km) ( kg ) (A) (kA) (kA)

3 x 50/16 + 95 0.641 0.822 12161 196 4.70 1.60

3 x 70/16 + 95 0.443 0.568 12161 245 6.58 1.60

3 x 95/16 + 95 0.320 0.411 12161 297 8.93 1.60

3 x 120/16 + 95 0.253 0.325 12161 343 11.28 1.60

3 x 150/25 + 95 0.206 0.265 12161 387 14.10 2.50

3 x 185/25 + 95 0.164 0.211 12161 448 17.39 2.50

3 x 240/25 + 95 0.125 0.161 12161 527 22.56 2.50


* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
24804-03 Rev. 0. 0 / 2013

www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification