YR Chiller Point List
YR Chiller Point List
YR Chiller Point List
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
ENG ASCII YR Warning Code ENG ASCII YR Operational Code ENG ASCII YR Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P57 P55 WARNING.FLT P58 P56 OPER.CODE P59 P57 SAFETY.FLT
0 0 No Abnormal Condition 0 0 Unit Stopped - Ready To Start 0 0 No Abnormal Condition
1 1 Real-Time Clock Failure 1 1 Unit Stopped - Local Shutdown 1 1 Evaporator - Low Pressure
2 2 Default Setpoints Loaded 2 2 Unit Stopped - Remote Shutdown 2 2 Evaporator - Transducer Or Leaving Liquid Probe
3 3 Evaporator Or Condenser Transducer Error 3 3 Unit Stopped - Warning Active 3 3 Evaporator - Temperature Transducer
4 4 Evaporator - Low Pressure Limit 4 4 Unit Stopped - Cycling Shutdown 4 4 Condenser - High Pressure Contacts Open
5 5 Condenser - High Pressure Limit 5 5 Unit Stopped - Safety Shutdown 5 5 Condenser - High Pressure
6 6 Condenser Transducer Error 6 6 Unit Start Inhibit 6 6 Condenser - Pressure Transducer Out Of Range
7 7 Condenser - Freeze Threat 7 7 Unit Starting 7 7 Auxiliary Safety - Contacts Closed
13 13 Oil - High Temperature 8 8 Unit Running - No Abnormal Condition 8 8 Discharge - Low Temperature
14 14 Motor - High Current Limit 9 9 Unit Running - Warning Active 9 9 Discharge - High Temperature
20 20 Oil - Filter Dirty 10 10 Unit Running - Chiller Unload Before Shutdown 10 10 Oil - High Temperature
21 21 Maximum Load - Load Limit 11 11 Unit Lockout Delay 15 15 Oil- High Pressure
22 22 Minimum Load - Load Limit 16 16 Oil- Filter Clogged
23 23 Low Discharge Superheat Limit 17 17 Oil - Low Seal Differential Pressure
24 24 Low Discharge Superheat Detected 19 19 Oil - Low Separator Oil Level
27 27 Slide Valve Uncalibrated 21 21 Control Panel - Power Failure
28 28 Freeze Threat - Condenser Flow Switch 23 23 Motor Or Starter - Current Imbalance