Sonnenbatterie Hybrid 816
Sonnenbatterie Hybrid 816
Sonnenbatterie Hybrid 816
Publisher
sonnen GmbH
Am Riedbach 1
87499 Wildpoldsried
Service number +49 8304 92933 444
E-Mail info@sonnen.de
Document
Document number KD-421
Part no. 22136
Version X03
Valid for AU, NZ
Publication date 16/01/2019
Table of contents
1 Information about this document.................................................................6
1.1 Target group of this document............................................................................. 6
1.2 Designations in this document............................................................................ 6
1.3 Explanation of symbols........................................................................................ 6
2 Safety..............................................................................................................7
2.1 Intended Use......................................................................................................... 7
2.2 Requirements for the electrician........................................................................ 7
2.3 Operating the storage system............................................................................ 8
2.4 Product modifications or changes to the product environment.....................8
2.5 Voltage on and in the storage system................................................................8
2.6 Handling the battery modules............................................................................ 9
2.7 Conduct in case of a fire................................................................................... 10
3 Product description......................................................................................11
3.1 Technical data....................................................................................................... 11
3.2 System components.......................................................................................... 13
3.3 The function of the switches............................................................................. 14
3.4 Type plate........................................................................................................... 14
3.5 Symbols on the outside of the storage system................................................15
4 Transport and storage..................................................................................16
4.1 Storage................................................................................................................. 16
4.1.1 Ambient conditions during storage...........................................................16
4.1.2 Storing the battery modules.....................................................................16
4.2 Transport............................................................................................................. 16
4.2.1 Ambient conditions during transport.......................................................16
4.2.2 Transporting battery modules..................................................................17
4.2.3 Inspecting for transport damage..............................................................17
4.2.4 Transport to the installation location......................................................19
4.2.5 Temperature adjustment after transport................................................19
5 Installation...................................................................................................20
5.1 Scope of delivery................................................................................................ 20
5.2 Selecting the installation location.....................................................................21
5.2.1 Requirements for the installation location...............................................21
5.2.2 Observing minimum distances.................................................................21
5.3 Opening the doors of the main cabinet...........................................................21
5.3.1 Opening the door....................................................................................... 21
5.3.2 Removing the cover of the extension cabinet.......................................22
5.3.3 Removing the filter plates....................................................................... 22
► Read this document in its entirety before beginning the installation work.
► Keep this document in the vicinity of the sonnenBatterie.
DANGER
DANGER Extremely dangerous situation leading to certain death or serious injury if the
safety information is not observed.
CAUTION
CAUTION Dangerous situation leading to potential injury if the safety information is not
observed.
Notice
Notice Indicates actions that may cause material damage.
Symbol Meaning
► Work step
1. 2. 3. … Work steps in a defined order
• List
Table 1: Additional symbols
2 Safety
Failure to comply with the conditions of the warranty and the information
specified in this document invalidates any warranty claims.
In the event of a fire in the vicinity of the product or in the storage system itself,
proceed as follows:
Only firefighters with appropriate protective equipment (safety gloves, safety
clothing, face guard, breathing protection) are permitted to enter the room where
the burning storage system is located.
There is a danger of electrocution when extinguishing fire while the storage system
is switched on. Therefore, before starting to extinguish the fire:
► Switch off the storage system to electrically isolate it (see 8.2 – p. 62).
► Switch off the mains fuses in the building.
If the storage system and/or mains fuses cannot be safely switched off:
► Observe the minimum distances specified for the extinguishing agent used.
The storage system works with an output voltage of 400 V (AC) and is therefore
considered a low-voltage system. However, the voltage of the PV system that is
connected to the storage system (through the PV connectors on the top of the
storage system) can be up to 1,000 V (DC).
► A storage system fire can be extinguished using conventional extinguishing
agents.
► Water is recommended as an extinguishing agent in order to cool the battery
modules and therefore prevent thermal runaway in battery modules which are still
intact.
3 Product description
Safety
Protection class I / PE conductor
Required fault current monitoring Residual current device (RCD) | Type B | 30 mA
Degree of Protection IP30
Rated short-time withstand 10 kA
current (ICW)
Separation principle no galvanic isolation, transformer-less
Power meter
Voltage measurement inputs Nominal voltage (AC): 230 V (L-N), 400 V (L-L) |
max. connectible conductor cross-section: 1.5 mm2
Clamp-on current transformer Max. measurable current: 60 A (standard), optional up to 400 A
Ambient conditions
Environment indoor (conditional)
Ambient temperature range 5 °C … 30 °C
Storage temperature range 0 °C … 40 °C
Transport temperature range -15 °C … 40 °C
Max. rel. humidity 90 %, non-condensing
Permissible installation altitude 2,000 m above sea level
Pollution degree 2
Additional ambient conditions • The installation location must not be at risk of flooding.
• Installation room should be ventilated.
• The currently applicable building codes must be observed.
• Even floor, suitable for heavy loads.
• Observe fire control standards.
• Free from corrosive and explosive gases (ammonia content max. 20 ppm).
• Free from dust (especially flour dust or sawdust).
• Free from vibrations.
• Free access to the installation location.
• No direct sunlight.
Table 2: Technical data
1 XAC SPV
XDIO
XSO1
S1
S1
F1
XPVP
XPVM
XSO2
XRE1 XSO3
XETH
XSO4 F1
XMOD
3
Figure 1: System components of the storage system
The nominal power and battery capacity of the storage system differ depending on
the number of battery modules installed. For this reason the nominal power and
battery capacity must be entered on the type plate by the electrician installing the
system.
kg
4.1 Storage
Storage describes the condition when the storage system is not connected to the
public electrical mains and the battery modules cannot be automatically charged.
DANGER
4.1.1 Ambient conditions during storage
WARNING The ambient conditions specified in section 3.1 (p. 11) must be observed during
storage.
CAUTION
4.1.2 Storing the battery modules
► Do not disconnect the storage system from the public grid for long periods of
time.
► Never continue to operate battery modules which have been deep-discharged.
4.2 Transport
Lithium-ion batteries are hazardous goods. Therefore the following points must be
observed when transporting the battery modules:
► Observe the general transport regulations based on the mode of transport as
well as all legal regulations.
► Consult an external hazardous goods expert.
The battery module data relevant for transport is provided in the following:
• Hazardous goods class: 9
DANGER • UN number: UN3480 ‘lithium-ion batteries’
• Battery module mass (including packaging): 29 kg
The shipping company can only be held liable for transport damage if it can be
proven that the damage occurred during the course of transport. For this reason it
is important to follow the instructions given here as closely as possible.
Transport damage is divided into open and hidden damage. Open damage is
externally visible damage to the transported goods or their packaging. Hidden
damage occurs when the packaging is not damaged but the transported goods
inside are.
Open transport damage must be reported to the shipping company immediately.
The following time frames apply in the case of hidden transport damage:
• Deutsche Post / DHL / parcel services: report damage within 24 hours
• Shipping company: report damage within 7 days
Proceed as follows:
the shipper.
The storage system has not been transported properly if blue powder has been
transferred into the arrow of the transport indicator.
► Refuse to accept the goods if blue powder has been transferred into the arrow
of the transport indicator.
WARNING
Notice
► At least two people are necessary to carry the main cabinet of the storage
system.
CAUTION
4.2.5 Temperature adjustment after transport
Forming of condensation
Notice
Damage to the storage system!
► Check the inside of the storage system for condensation before installation.
► Only install the storage system if there is no condensation on the surfaces.
If the temperature of the storage system is lower than the ambient temperature of
the room when it is delivered, condensation may form inside the storage system.
5 Installation
3
1x Installationsanleitung sonnenBatterie eco 8.0
– für Elektrofachkräfte –
1x
+49 (0) 83 04 / 92 93 3 - 444 · i nf o@ so nn e n ba tte ri e .de · w ww.so n ne n b att er ie .d e
12 11 5 1x 10 9
K
L
K
L
L
1x
1x 1x Installationsanleitung sonnenBatterie eco 8.0
– für Elektrofachkräfte –
1x
+49 (0) 83 04 / 92 93 3 - 444 · i nf o@ so nn e n ba tte ri e .de · w ww.so n ne n b att er ie .d e
3x
1 2 3 4 5
B 1x 1x 1x
1x
1x
C 2 D 2 E
1
1 1x 1x
3 4 3 4
1
2x 2x 2x 2x
1x
5 5
2x 2x
1x 1x
A Scope of delivery for main B Scope of delivery for battery C Scope of delivery for big extension
cabinet module cabinet
1 Main cabinet 1 Battery module 1 Big extension cabinet
2 Numbering for battery modules 2 Fuse plug 2 Levelling mat
3 RJ-45 coupling 3 BMS communication line 3 Locking nut
4 Power meter WM 271 4 DC line red 4 Contact disc
5 Modbus line 5 DC line black 5 Edge protection
6 Current transformer KSW60-3
7 Mains line D Scope of delivery for small E Scope of delivery for Pedestal
8 Installation instructions extension cabinet (optional)
9 Operating instructions 1 Small extension cabinet 1 Pedestal
10 Miniature Circuit Breaker B16 2 Levelling mat
11 PV plug-in connector minus 3 Locking nut
12 PV plug-in connector plus 4 Contact disc
5 Edge protection
50 cm 100 cm
At least three battery modules (6 kWh) are required to operate the storage
Notice
system. This means the sonnenBatterie hybrid 8.1 needs to be mounted with an
extension cabinet (big or small).
8 mm max. 15 mm
• Screw head diameter: max. 15 mm
The screw lengths and the wall plugs used must be suitable for the nature of the
wall.
The levelling mat (1) is part of the scope of delivery for the extension cabinet. It is
used to compensate uneven floors. Alternatively the extension cabinet can be
placed on an optional pedestal (3) instead of the levelling mat. This is helpful if the
extension cabinet doesn’t meet flush with the wall (e.g. because a skirting board (2)
is mounted).
1 2 3 ► Place the levelling mat (1) or the
pedestal (3) at the preferred installation
location.
Figure 11: Levelling mat or pedestal
626
► Note that the storage system must
526
226
33 be placed on the levelling mat or the
1316
B pedestal (C).
916
723
690
► Drill the holes shown in red in figure
656
256
on the left.
A Main cabinet
C
B Small extension cabinet
Figure 12: Drill template for storage C Levelling mat (height: 10 mm)
systems with small extension cabinet or pedestal (optional, height:
(figure is not to scale – all specifications are 80 mm)
in millimetres)
1176
1142
on the left.
402
A Main cabinet
B Big extension cabinet
There are keyhole attachments on the rear of the main cabinet. The main cabinet is
mounted using these attachments.
2 mm ► Apply suitable screws and anchors
(see 5.4.1 – p. 23) to the previously
drilled holes.
The screw should not be completely
Figure 15: Distance between screw head
screwed in. The screw head should
and wall
protrude from the wall by approx.
2 mm.
6 Electrical Installation
Electrical work on the storage system and electrical distributor
DANGER
Danger to life due to electrocution!
DANGER
► Switch off the storage system to electrically isolate it (see 8.2 – p. 62).
WARNING ► Disconnect the relevant electrical circuits.
► Install residual current device (RCD | Type B | I∆n = 30 mA) upstream of the
WARNING storage system.
Notice connection of the storage system. Approx. 25 cm of free space on a mounting rail
is required for placing the components.
1 2 3 4
A1 A2 N L1 L2 L3
123
• The miniature circuit breaker (1) protect the mains line of the storage system.
• The power meter (2) and the transformer interfaces (3) are used to measure the
consumption and generation of power in the building.
• The inverter of the storage system can cause a current with DC components. The
RCD (4) protects against high touch voltage in the event of a fault. A RCD Type
B with a rated differential current of 30 mA must be installed.
1
6
2 L1 L2 L3 N PE
123
1 8
3 2
4 3
5 BN BK GY BU GNYE
A1 A2 9
N L1 L2 L3
11
12
10
kWh 3~
14
L1 L2 L3 N PE
13
• The lines connected to the voltage measurement terminal strip (3) must be
protected by suitable miniature circuit breakers. Additional miniature circuit
breakers do not have to be installed if the lines are already protected in
accordance to the relevant, currently applicable regulations and standards.
• The clamp-on current transformers
are clamped across the affected lines.
The energy flow direction of the
clamp-on current transformer must
K K be observed.
L L The energy flow in the line must run
from K to L.
► Connect the socket (4) of the public network to the (XAC) connection on the
storage system. Ensure that the stickers (1) and (2) face upwards.
1 2 3
4
XAC
1, 2 Sticker 3 Lock
4 Mains connection plug XAC Mains connection socket
► Connect the other end of the Ethernet cable to the router of the home
network (2).
XS03
It is essential to ensure that a screened patch cable is used and that the screen of
the Modbus line is earthed in order to ensure optimal data transmission.
► Use a patch cable with the following properties as the Modbus cable:
• the Patch cable is Cat 6,
• the Patch cable is shielded.
► Earth the screen (5) of the Modbus line for the power meter3.
► Connect the patch cable (1) as it is shown in the following figure.
1
2
A1 A2 13 14 15 16
1 2 3 4 5 6 7 8
XSO2
6 5
If there is no jumper (4) installed between the pins 6 and 8 on the plug of the
Modbus terminal strip (3):
► Install a jumper (4) between pins 6 and 8 on the Modbus terminal strip (3)
connector.
3 Install the supplied screen clamp for this purpose as described in the provided instructions.
CAUTION ► Check that the device is disconnected from the power supply.
► Only licensed electricians are permitted to carry out electrical work.
Notice
Overvoltage when switching off electromagnetic relays
Notice
Damage to components!
► Only use electromagnetic relays with a protective circuit (e. g. with a free-
wheeling diode) or semiconductor relays.
The wiring configurations described in this section are examples only and serve as
a guide for electricians working on the system.
The wiring configurations are not universal. The electricians working on the system
are responsible for the correct wiring of the system.
In some cases, the permission of the distribution grid operator or power supply
company may be required.
The signal line for using the digital inputs/outputs can be obtained from sonnen
GmbH4. Only this original signal line may be used.
The digital inputs and outputs (XDIO) are on the top side of the storage system.
These can be used to control external devices. The digital signals are transmitted via
the signal cable (4). We recommend connecting the signal cable to a terminal strip
(6). The individual cores of the signal cable from the terminal strip can then be
distributed to the corresponding downstream external components. The white wire
of the signal cable (4) represents the earth (GND). If more than one digital output
is used, then several wires must be connected to earth. For this reason we
recommend installing multiple terminals which are connected via a bridge (5) to
earth (GND).
4 Additional accessories ‘Digital input/output D-SUB’
1
4
2
3
24 VDC
GND
5 6
1, 2 Knurled screw
3 Signal line connector
4 Signal line (not included in scope of delivery)
5 Bridge to connect terminals (not included in scope of delivery)
6 Terminal strip (not included in scope of delivery)
XDIO Digital inputs and outputs
Function
3
The storage system software can be
► Adjust the switch-on threshold and minimum switch-on duration to suit the
consumers that are activated using the self-consumption switch.
Application example
GND + 24 VDC
In this case it is a good idea to set the
A1
nominal power of the heating element
K1
A2 as the switch-on threshold.
1 Heating element
K1 External contactor
Function
3
The storage system software can be
The switching behaviour of the min/max SoC digital output can be configured using
the commissioning assistant (see 7.4 – p. 59).
► Set suitable values for the min SoC and max SoC variables.
Application example
The CHP digital input may only be used in the way described here in combination
with a combined heat and power station (CHP) which provides a constant supply
of electrical power. Modulating combined heat and power stations, which supply a
variable amount of power, must not be connected like this.
Function
Using the storage system’s software the power produced by the combined heat and
power station, or some other constant source of power, can be set.
If the digital CHP input is activated, then the set power will be added to the power
currently being produced.
1 Signal line
2 Digital input CHP
L
3 CHP
4 Floating operating contacts for the
combined heat and power station
L
3 M (open if the station is not operating,
1 4 closed if it is)
N
N
Figure 33: CHP with operating contacts
A5
current-operated relay (K3)
6 detects
whether the station (3) is currently
active.
L 1 Signal line
M 3
2 Digital input CHP
1
N 3 CHP
K3 Current-operated relay
N
Residual current devices (RCDs) which are installed in the current path and / or in
the heat pump path have to be rebuilt. The new installation location is shown in
the circuit diagram on page 35.
The heat pump control can be used when the heat pump is billed using a separate
energy meter. In this case the heat pump is located in a separate current path (heat
pump current path) that is not recorded by the consumption measurement of the
power meter.
Using the heat pump control, the heat pump can be switched to the current path
(power meter current path) for which consumption is recorded by the power
meter. If this happens, the consumption of the heat pump is measured and included
in the storage system controls.
Function
If the self-consumption switch is activated, K230, K40 and then Q41 energise
(see Figure 35 - p. 43). The power meter current path is closed.
K30 energises two seconds after the self-consumption switch is activated. Then
Q31 energises. The heat pump current path is interrupted.
The auxiliary make contact 23/24 for Q31 can be used to activate the heat pump.
This requires a suitable interface for the heat pump.
When the self-consumption switch is deactivated, K30 de-energises immediately.
The heat pump current path is closed.
K40 de-energises two seconds after the self-consumption switch is deactivated.
Then Q41 de-energises. The power meter current path is interrupted.
The switch-on threshold and the minimum switch-on duration should be set
so that the current paths are not switched back and forth too frequently.
Designation Description
F50 Miniature circuit breaker
K30 Relay
K40 Relay
K230 Relay
Q31 Contactor
Q41 Contactor
Table 5: Content of the accessory heat pump control5
5 Included in “Additional accessories heat pump control”, available from sonnen GmbH.
3
xT=1 xT=1
1 1
GND + 24 VDC 2s 2s
T=2s T=2s
4
A1 F=RV F=AV
K230
A2 AV
RV (ESV) (AV+)
5 7
23
Q31
24
L1 L2 L3 N PE
PE N U V W
6
8
L
FI (16 und17) are part of the
F50 house wiring
16 17
11
15 15 Q41
K30 K40 9
18 18
KSW
1 2 3
L1 L2 L3 N PE
L
K
10
K
A1 A1
12
L
Q31 Q41
K
A2 A2 Q31
N
kWh 3~ kWh 3~
15 14
L1
13
L2
L3
N
PE
DANGER
CAUTION 6.8 Installing the battery modules
DANGER
Notice ► Do not open battery modules.
► Do not damage battery modules.
► The battery modules are only allowed to be installed if the maximum deviation
between the measured voltages is less than 1 V.
► Ensure that all battery modules are connected in parallel, i.e. all plus poles of
WARNING the battery modules are connected together (red to red). Likewise, ensure that all
minus poles of the battery modules are connected together (black to black).
CAUTION ► Ensure that all DC lines are
plugged into the sockets all the way.
Notice
6 kWh 8 kWh
456 ON
3
0 12
789A
EF
1 2 3 4
BCD
345 6 ON 345 6 ON
2 2
789A
789A
01
01
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
345 6 ON 345 6 ON
1 1
0 2
0 2
789A
789A
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
345 6 ON 345 6 ON
0 0
12
12
789A
789A
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
Figure 42: Connecting the BMS communication line on a sonnenBatterie with 6 and 8 kWh capacity
10 kWh 12 kWh
4 6 ON
5
0 12
789A
EF
1 2 3 4
BCD
4 4
456 ON 45 6 ON
3 3
0 12
0 12
78 A
789A
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
345 6 ON 345 6 ON
2 2
78 A
789A
01
01
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
345 6 ON 345 6 ON
1 1
0 2
0 2
78 A
789A
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
345 6 ON 345 6 ON
0 0
12
12
78 A
789A
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
Figure 43: Connecting the BMS communication line on a sonnenBatterie with 10 and 12 kWh capacity
14 kWh 16 kWh
7 45 6 ON
0 12
89A
EF
1 2 3 4
BCD
45 ON 45 ON
6 6
0 12
0 12
78 A
789A
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
4 6 ON 4 6 ON
5 5
0 12
0 12
78 A
789A
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
4 4
456 ON 45 6 ON
3 3
0 12
0 12
78 A
789A
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
345 6 ON 345 6 ON
2 2
78 A
789A
01
01
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
345 6 ON 345 6 ON
1 1
0 2
0 2
78 A
789A
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
345 6 ON 345 6 ON
0 0
12
12
78 A
789A
9
EF
EF
1 2 3 4 1 2 3 4
BCD BCD
Figure 44: Connecting the BMS communication line on a sonnenBatterie with 14 and 16 kWh capacity
1 Cover
2 Extension cabinet
Figure 46: Earthing wire between
3 Earth bolt
extension cabinet and cover
4 Contact disc
5 Cable lug
6 Locking nut
7 Earth conductor
DANGER ► Only connect PV systems whose unloaded voltage does not exceed the
WARNING maximum voltage for the PV inputs.
CAUTION
Notice Before plugging in/unplugging PV lines:
► Switch the PV disconnector (SPV) off.
Notice Prerequisite:
✔ The maximum input current of the PV inputs (see 3.1 – 11) must not be
exceeded.
✔ The unloaded voltage of the PV system must never exceed the maximum input
voltage (see 3.1 – 11) for the PV inputs. Please note that the unloaded voltage of
PV systems depends upon the ambient conditions (particularly the temperature).
► Remove the protective caps from
the PV connections XPVP and XPVM.
7 Commissioning
► Mark off the correct battery capacity and nominal power on the type plate of
the storage system.
The type plate is located on the outside of the storage system. The battery capacity
and nominal power can be determined from the technical data (see 3.1 - p. 13).
The photo upload is obligatory for both offline commissioning and online com-
missioning.
To fully document the installation, photos of the finished installation must be taken
and send to sonnen.
1. Take the described photos of the storage system (see appendix of the document).
► Make a copy of the filled in commissioning report, the original remains with the
operator.
► Send a scan of the commissioning report to the following e-mail address within
5 working days: service@sonnen.de and support@sonnen.com.au
The storage system can only be switched on if the public network voltage has been
switched on first.
WARNING
Figure 51: Switching SPV on
CAUTION
7.3.4 Switching on the fuse switch F1
The storage system is only ready for operation if the commissioning assistant is
fully completed.
The commissioning assistant does not support changes of the power factor mode.
Please contact the service, if this setting needs to be changed.
12345
123.456.78.99
► Log in as Installer. Use the password that you received throughout the
certification training.
CAUTION 8 Decommissioning
Deep-discharge of the battery modules
Notice
Destruction of the battery modules!
► Do not disconnect the storage system from the public grid for long periods of
time.
► Never continue to operate battery modules which have been deep-discharged.
I
SPV
F1
1. Switch off fuse switch F1 and PV disconnector SPV, as described in section 8.1
(p.61).
2. Switch off the grid voltage using the AC miniature circuit breaker.
The battery modules are the sole remaining sources of voltage in the storage
system.
9 Troubleshooting
Disturbance Reason Correction
No connection to the Web interface of No connection between the storage system and ► Make sure that the Ethernet line between
the storage system the server. the storage system and the Router of the home
(find-my.sonnen-batterie.com). network is correctly connected.
TCP-Port Service
22 ssh
80 http
8080 http
443 https
3333 debug
UDP-Port Dienst
1194 VPN
123 NTP
1196 VPN
The sonnen Eclipse of the storage The internet connection to the storage ► Check whether the home network router is
system pulses orange. system has been interrupted. able to establish an internet connection.
If so:
► Ensure that the network cable for the
storage system is connected to the home
network router.
The sonnen Eclipse of the storage The storage system has detected a problem that ► Please contact the sonnen service team to
system illuminates red. is preventing normal operation or may cause get help resolving the problem.
damage to the storage system.
The sonnen Eclipse of the storage The storage system is not connected to ► Check that the circuit breaker in the supply
system pulses green. the public electricity grid. line of the storage system is switched on.
If so: The public electricity grid does not provide
any electrical energy (grid outage).
► It can only be waited until the public
electrical grid supplies energy again. Thereafter,
the storage systems resumes normal operation.
Storage system with emergency power function No troubleshooting necessary.
only*: The storage system is not connected to
the public electricity network and is in
emergency operation.
*Optional accessories sonnenBackup-Box.
► Transport the battery modules in their original packaging only. If you no longer
Notice
have the original packaging, new packaging can be requested from sonnen GmbH.
WARNING ► Never transport damaged battery modules.
Telephone
Surname, first name
Email address
Street
Telephone
Name
Email address
Company
Certification number
Storage system location (only required if different from the address above) Details on network topology (mark off the applicable network)
kWh
Details on PV system
Electrician’s declaration
□ I confirm that my details are correct.
□ The storage system was installed and commissioned by me in the proper manner. I followed the installation instructions in doing
so.
Operator’s declaration
□ I confirm that my details are correct.
□ I received the warranty conditions.