Product Data: Airstream™ 42BHC, BVC System Fan Coils

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

Product AIRSTREAM™

42BHC,BVC
Data System Fan Coils

600 to 4000 Cfm

Carrier’s versatile belted fan coil units


satisfy design requirements:
• A selection of 8 sizes covers
capacities from 600 to 4000 cfm
• Choice of motors, from 1/4 to 5 hp,
eliminates oversizing
• Wide range of coil options for 2-pipe
or 4-pipe systems
• Optional DX coils with expansion
valve and distributor
• Single and three-phase electric
heat (1.0 to 40 kW)

Features/Benefits
42BHC UNIT The 42BHC, BVC belt drive
fan coil units provide year-
round comfort air
conditioning with central
station operating economy.
A variety of coil options
reduces first cost
Four, 6 or 8-row cooling coils combine
needed capacities with the most effi-
cient heat transfer surface. For
4-pipe systems, select either of two
split-coil options. Coils consist of alu-
minum fins securely bonded to 1/2-in.
OD seamless copper tubes. Each fin’s
aluminum collar ensures accurate con-
trol of the fin spacing, while complete-
ly covering the tubes to lengthen coil
life. All coils also feature manual air
vents, with automatic air vent available
as an option.

42BVC UNIT

Copyright 2005 Carrier Corporation Form 42B-1PD


Fan wheels are designed to provided on the top and bottom of each One-inch matte surface, fiberglass
provide low operating costs corner of the unit One-in. duct collars thermal/acoustical insulation lines the
The forward-curved, centrifugal, on discharge and on return are fur- fan coil cabinets to prevent sweating
double-inlet fans are statically and nished standard. These integral duct and to muffle sound transmission.
dynamically balanced at the factory to collars cut installation time and labor The stainless steel, double-sloped
minimize transmission of vibration expense. condensate drain pan extends under
to the building structure. Durable construction means full coil surface to cut maintenance
The belt-driven motor (single or easy-to-maintain units costs.
three phase) has a variable-pitch pulley The 42BHC,BVC fan coils casings are Slide-in return-duct collar filter
which adjusts at the jobsite to accom- fabricated from heavy-gage galvanized makes it possible to remove and
modate limited ranges of air quantities G90 steel, reinforced for maximum replace the filter without disturbing
and pressures. rigidity and structural strength. Remov- return air ductwork.
All motors (single and three phase) able side panels with tool-less camlock
are UL listed, factory wired, single fasteners allow easy access for servic-
speed with thermal overload protec- ing interior components.
tion and are continuous duty rated.
Motors are supplied with permanently
lubricated bearings, class-B insulation
and are open drip-proof. The motor Table of contents
mount has an adjustable platform for
Page
easy belt adjustment. The motor and
its mounting are independently isolated Features/Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
from the cabinet and the blower. An Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
adjustable pitch pulley allows cfm bal- Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ancing to meet system requirements. Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5
Motor drive packages are provided Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
with keyed pulleys. Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-18
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-21
Complete factory assembly Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
minimizes on-the-jobsite costs Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-33
and problems Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36
Compact, lightweight units are designed Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
for easy mounting. Knockouts designed Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
to accept 3/8-in. threaded rods are Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39,40

INTERNAL FEATURES OF A 42BHC FAN COIL UNIT

2
Model number nomenclature

42BH C 08 L

42BH — Vertical Belt Drive Fan Coil Unit Coil — Rows


42BV — Vertical Belt Drive Fan Coil Unit
B — 4, 2-Pipe
L — 6, 2-Pipe
H — 4/1, Same End Conn.
C — Design K — 4/2, Same End Conn.
N — 6/1, Same End Conn.
Q — 6/2, Same End Conn.
R — 8, 2-Pipe
1 — 4 With Electric Heat
2 — 6 With Electric Heat
Size — Nominal Cfm 3 — 8 With Electric Heat
06 — 600
08 — 800
10 — 1000
12 — 1200
16 — 1600
20 — 2000
30 — 3000
40 — 4000

NOTE: Refer to current 42 Series Master Prices for


complete model definition, including motor, cfm and
total static pressure.

Physical data
UNIT SIZE 42BHC, BVC 06 08 10 12 16 20 30 40
NOMINAL CFM 600 800 1000 1200 1600 2000 3000 4000
42BHC SHIPPING WT (lb)
203/234 205/236 253/287 256/290 312/346 344/380 437/474 553/590
(no heat/ with heat)
42BVC SHIPPING WT (lb)
200/231 202/233 243/277 247/281 289/323 351/387 436/473 522/559
(no heat/ with heat)
FILTERS (2 in. pleated)
Number...Size (in.) 1...161/2 x 24 1...161/2 x 24 1...181/4 x 33 1...181/4 x 33 2...181/4 x 211/2 2...203/4 x 22 2...29 x 22 2...29 x 29
Face Area (sq ft) 2.8 2.8 4.2 4.2 5.5 6.3 8.9 11.7
COILS
Size (in.) 15 x 20 15 x 20 15 x 29 15 x 29 15 x 39 18 x 40 27 x 40 27 x 54
Face Area (sq ft) 2.1 2.1 3.0 3.0 4.1 4.9 7.7 10.3
Fins per inch 10
Coil Water Weight (approx. lb per
0.240 0.240 0.324 0.324 0.420 0.492 0.768 1.020
row of coil)
FANS
Number...Size (in.) 1...9 x 4 1...9 x 6 1...10 x 4 1...10 x 7 1...11 x 10 1...12 x 9 1...12 x 12 1...15 x 12
COPPER COIL CONN. 8 ROW
1 OD 11/2 OD
(in.) (Cooling)
COPPER COIL CONN. 4 AND 6 ROW 3/4
(in.) (Cooling) OD 1 OD 11/2 OD

COPPER COIL CONN. 1 AND 2 ROW 1/


(in.) (Heating) 2 OD

DRAIN CONN. SIZES (in.) 3/ MPT


4

3
Options and accessories
42BHC, BVC OPTIONS AND ACCESSORIES electric heater data table for availability per unit) with
ITEM OPTION* ACCESSORY†
single-stage or multiple-stage, single power source.
Automatic Air Vents X Voltages:
Controls X • 115 v, 208 v, 230 v and 277 v single-phase 60 Hz
Electric Heat X
• 208 v, 230 v and 480 v three-phase 60 Hz
Filters X
Heating/Cooling Coils X Electric heat is available with the following staging options
Insulation X (3-phase staging is balanced).
Mixing Boxes X • 1 to 12 kW 1 stage only — single phase
Motors X
• 3 to 12 kW 1 or 2 stage only — single phase
Thermostats X
Valve Packages X
• 1 to 40 kW 1 stage only — 3 phase
• 4 to 40 kW 1 or 2 stage only — 3 phase
*Factory-installed option. • 12 to 40 kW 1, 2, or 3 stage — 3 phase
†Field-installed accessory.
Heater coils are constructed of high-grade resistance
wire that is supported by ceramic insulators on plated steel
The 42BHC and 42BVC fan coil units are designed to brackets. These heat elements are suspended directly in
offer maximum flexibility in an application, accessibility for front of the outlet after the blower and the coil. High limit
service, quiet operation and durability. thermal cutouts protect the heater in the event of air
Factory-installed options failure.
Automatic air vents — Automatic air vents have fiber- Filters — Two in. pleated filters are standard. One-in.
washers, which allow air in the pipes to pass through, pleated, two 1-in. throwaway, or 2-in. MERV (minimum
automatically bleeding the system. The fiber washers elimi- efficiency reporting value) 11 filters with 2-in. pleated
nate the need to manually remove air from the system. pre-filter are available. The 2-in. MERV 11 filters with 2-in.
When wet, washers swell and seal the system. pleated pre-filter include a filter rack.
Coils — Coils are available in a choice of two-pipe system Insulation — Tuf-Skin™ II (1-in. thick) insulation is
with 4-row cooling/heating or four-pipe system with 4, 6 standard. Units are available with ¾-in. closed cell, 1-in.
or 8-row cooling and 1 or 2 row heating. Tuf-Skin Rx™ edge sealed, or 1-in. foil-faced insulation.
Reheat operation is standard. Preheat is available as an Motors — A wide selection of standard motors provides
option. efficient operation in ducted applications with excellent
performance with up to 2 inches of total static pressure.
Controls
• Interlocking disconnect switch Available motor options:
• Heater power fusing • 115 v, 208 v, 230 v and 277 v single-phase 60 Hz
• 24 v Class 2 transformer (40 va) • 208 v, 230 v and 460 v three-phase 60 Hz
• 8-pole control terminal strip • Open drip-proof motors
• Auto reset temperature limit switch • External junction box
• Airflow safety switch
• Motor power fusing
Field-installed accessories
• Motor control contactor Mixing boxes — Mixing boxes can be used when outside
• 24 v condensate overflow switch air is required for ventilation. Preassembled at the factory
and shipped separately with base rails for field installation,
Electric heat — Total electric heat eliminates the require-
mixing boxes include a linkage kit consisting of two crank
ment for a boiler. Heating and/or cooling may be available arms, 2 swivels and either a 25 in. long (for sizes 06-16) or
on an individual basis throughout the year. Resistance
a 84 in. long (for sizes 20-40) rod for field installation of an
electric heat is available from 1.0 kW to 40.0 kW (refer to
actuator.

4
Thermostats — Three thermostats are available for field • programmable operating range, dead band, digital dis-
installation: play, temperature set-back
Honeywell T834C manual changeover, single-stage heat THERMOSTAT FUNCTIONS
thermostat features:
THERMOSTATS
• off-cool-heat system switch SYSTEM FUNCTION CHANGEOVER Honeywell Honeywell Sunne
• on-auto fan mode switch T834C T8500 T170
• single-stage electric heat 2 Pipe HW-Heat Only ACO — X X
• outside air signal 2 Pipe CW-Cool Only ACO — X X
CW/HW MCO — — X
Honeywell T8500 digital, automatic/manual changeover, 2 Pipe
Heat/Cool ACO — — X
2-stage heat thermostat features: CW/HW MCO — — X
2 Pipe Heat/Cool with
• digital display of temperatures and all functions Aux. Electric Heat ACO — — X
• off-cool-heat-auto system mode buttons CW-Cooling with MCO X X X
2 Pipe
• single speed fan operation Total Electric Heat ACO — X X
• on-auto fan mode button CW/HW MCO X X X
4 Pipe
• single or two stage electric heat signal Heat/Cool ACO — X X
• outside air signal LEGEND
• remote temperature sensor available ACO — Automatic Changeover
Aux — Auxiliary
Sunne T170 single-stage heat, 2-pipe heat/cool auto CW — Chilled Water
changeover thermostat features: HW — Hot Water
MCO — Manual Changeover
• digital display of ambient temperature and operating
mode
• single fan speed operation, power and operating mode Valve packages — Valve packages are factory assembled
buttons for field installation. Motorized valves (24 v) can be operat-
• continuous fan operation, cycling water control valve ed with power on with spring return or power off/power
• 4-pipe ACO/MCO (automatic changeover/manual on.
changeover) with “on-auto” fan mode button It is recommended that basic motor controls are ordered
• one or 2 stage electric heat signal available when valve packages are ordered.
• purge cycle and temperature sensor for 2-pipe cold
water/hot water systems

5
Base unit dimensions
42BHC FAN COIL BASE UNIT (NO CONTROLS)

DIMENSIONS (in.)
UNIT Supply Duct Return Duct Mounting Holes
42BHC Fan Size Depth Width Height
A B C D E F J K
06 9x 4 363/16 2811/16 181/2 71 / 8 109/16 137/8 11/8 241/16 167/16 273/16 351/4
08 9x 6 363/16 2811/16 181/2 89/16 109/16 137/8 11/8 241/16 167/16 273/16 351/4
10 10 x 4 373/4 371/16 201/4 71 / 2 1111/16 137/8 11/8 331/16 183/16 363/16 3613/16
12 10 x 7 373/4 371/16 201/4 915/16 1111/16 137/8 11/8 331/16 183/16 363/16 3613/16
16 11 x 10 3715/16 471/16 201/4 135/16 1211/16 1613/16 11/8 431/16 183/16 463/16 37
20 12 x 9 403/8 481/16 223/4 1
12 /2 3
13 /4 173/4 11/8 1
44 /16 2011/16 473/16 397/16
30 12 x 12 403/8 481/16 31 157/8 133/4 161/16 61/8 441/16 2815/16 473/16 397/16
40 15 x 12 439/16 621/16 31 167/16 161/16 2213/16 51/8 581/16 2815/16 613/16 425/8
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.

6
42BHC FAN COIL WITH MOTOR CONTROL OPTION

DIMENSIONS (in.)
UNIT Supply Duct Return Duct Mounting Holes
42BHC Fan Size Depth Width Height
A B C D E F J K
06 9x 4 363/16 2811/16 181/2 71/8 109/16 137/8 11/8 241/16 167/16 273/16 351/4
08 9x 6 363/16 2811/16 181/2 89/16 109/16 137/8 11/8 241/16 167/16 273/16 351/4
10 10 x 4 373/4 371/16 201/4 1
7 /2 11
11 /16 137/8 11/8 1
33 /16 183/16 3
36 /16 3613/16
12 10 x 7 373/4 371/16 201/4 915/16 1111/16 137/8 11/8 331/16 183/16 363/16 3613/16
16 11 x 10 3715/16 471/16 201/4 135/16 1211/16 1613/16 11/8 431/16 183/16 463/16 37
20 12 x 9 403/8 481/16 223/4 121/2 133/4 173/4 11/8 441/16 2011/16 473/16 397/16
30 12 x 12 403/8 481/16 31 7
15 /8 3
13 /4 161/16 61/8 1
44 /16 2815/16 3
47 /16 397/16
40 15 x 12 439/16 621/16 31 167/16 161/16 2213/16 51/8 581/16 2815/16 613/16 425/8
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.

7
Base unit dimensions (cont)
42BHC FAN COIL WITH ELECTRIC HEAT OPTION

DIMENSIONS (in.)
UNIT
Supply Duct Return Duct Mounting Holes
42BHC Fan Size Depth Width Height
A B C D E F J K
06 9x 4 363/16 2811/16 181/2 71 / 8 109/16 137/8 11 / 8 241/16 167/16 273/16 351/4
08 9x 6 363/16 2811/16 181/2 89/16 109/16 137/8 11 / 8 241/16 167/16 273/16 351/4
10 10 x 4 373/4 371/16 201/4 71 / 2 1111/16 137/8 11 / 8 331/16 183/16 363/16 3613/16
12 10 x 7 373/4 371/16 201/4 915/16 1111/16 137/8 11 / 8 331/16 183/16 363/16 3613/16
16 11 x 10 3715/16 471/16 201/4 5
13 /16 11
12 /16 1613/16 11 / 8 1
43 /16 183/16 3
46 /16 37
20 12 x 9 403/8 481/16 223/4 121/2 133/4 173/4 11 / 8 441/16 2011/16 473/16 397/16
30 12 x 12 403/8 481/16 31 157/8 133/4 161/16 61 / 8 441/16 2815/16 473/16 397/16
40 15 x 12 439/16 621/16 31 167/16 161/16 2213/16 51 / 8 581/16 2815/16 613/16 425/8
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.

8
42BVC FAN COIL BASE UNIT (NO CONTROLS)

DIMENSIONS (in.)
UNIT
Supply Duct Return Duct
42BVC Fan Size Depth Width Height
A B C E F
06 9x 4 20 281/16 361/2 71/8 109/16 33/4 241/16 167/16
08 9x 6 20 281/16 361/2 89/16 109/16 33/4 241/16 167/16
10 10 x 4 22 371/16 393/8 71/2 1111/16 51/2 1
33 /16 183/16
12 10 x 7 22 371/16 393/8 915/16 1111/16 51/2 331/16 183/16
16 11 x 10 22 471/16 393/8 135/16 1211/16 167/8 431/16 183/16
20 12 x 9 24 481/16 451/8 121/2 133/4 1713/16 441/16 2011/16
30 12 x 12 28 481/16 543/16 157/8 133/4 161/8 1
44 /16 2815/16
40 15 x 12 28 621/16 575/8 167/16 161/16 227/8 581/16 2815/16
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.

9
Base unit dimensions (cont)
42BVC FAN COIL WITH MOTOR CONTROL OPTION

DIMENSIONS (in.)
UNIT
Supply Duct Return Duct
42BVC Fan Size Depth Width Height
A B C E F
06 9x 4 20 281/16 361/2 71/8 109/16 33 / 4 241/16 167/16
08 9x 6 20 281/16 361/2 89/16 109/16 33 / 4 241/16 167/16
10 10 x 4 22 371/16 393/8 71/2 1111/16 51 / 2 331/16 183/16
12 10 x 7 22 371/16 393/8 915/16 1111/16 51 / 2 331/16 183/16
16 11 x 10 22 471/16 393/8 135/16 1211/16 167/8 1
43 /16 183/16
20 12 x 9 24 481/16 451/8 121/2 133/4 1713/16 441/16 2011/16
30 12 x 12 28 481/16 543/16 157/8 133/4 161/8 441/16 2815/16
40 15 x 12 28 621/16 575/8 167/16 161/16 227/8 581/16 2815/16
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
NOTES:change without notice.
1. 3.AllRight
dimensions are in left
hand shown, inches (±1opposite.
hand /4 in.).
2. 4.Any modifications
Hanger to product
rods, which specifications
are field-supplied, by any for
are shown person are only.
reference
subject to acceptance of the factory. Product specifications are
subject to change without notice.
3. RH shown, LH opposite.
4. Hanger rods, which are field-supplied, are shown for reference
only.

10
42BVC FAN COIL WITH ELECTRIC HEAT OPTION

DIMENSIONS (in.)
UNIT Supply Duct Return Duct
42BVC Fan Size Depth Width Height
A B C E F
06 9x 4 20 281/16 361/2 71/8 109/16 33/4 241/16 167/16
08 9x 6 20 281/16 361/2 89/16 109/16 33/4 241/16 167/16
10 10 x 4 22 371/16 393/8 71/2 1111/16 51/2 331/16 183/16
12 10 x 7 22 371/16 393/8 915/16 1111/16 51/2 1
33 /16 183/16
16 11 x 10 22 471/16 393/8 135/16 1211/16 167/8 431/16 183/16
20 12 x 9 24 481/16 451/8 121/2 133/4 1713/16 441/16 2011/16
30 12 x 12 28 481/16 543/16 157/8 133/4 161/8 441/16 2815/16
40 15 x 12 28 621/16 575/8 167/16 161/16 227/8 1
58 /16 2815/16
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to
change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.

11
Base unit dimensions (cont)
42BHC UNIT CORNER WEIGHTS (lb)

1
2

2 1 4
3

4 3

RIGHT HAND UNIT LEFT HAND UNIT

UNIT RIGHT-HAND UNITS LEFT-HAND UNITS TOTAL


CONFIGURATION
42BHC 1 2 3 4 1 2 3 4 WEIGHT
No Heat 50 55 47 51 55 50 51 47 203
06
With Heat 50 58 59 67 58 50 67 59 234
No Heat 51 55 47 52 55 51 52 47 205
08
With Heat 50 59 59 68 59 50 68 59 236
No Heat 63 71 55 63 71 63 63 55 253
10
With Heat 62 76 68 81 76 62 81 68 287
No Heat 64 72 56 64 72 64 64 56 256
12
With Heat 63 76 68 82 76 63 82 68 290
No Heat 80 87 69 76 87 80 76 69 312
16
With Heat 79 91 82 95 91 79 95 82 346
No Heat 90 98 74 82 98 90 82 74 344
20
With Heat 90 102 88 100 102 90 100 88 380
No Heat 118 127 92 100 127 118 100 92 437
30
With Heat 118 131 106 119 131 118 119 106 474
No Heat 155 162 114 122 162 155 122 114 553
40
With Heat 155 166 129 140 166 155 140 129 590
NOTE: Unit weights (shown in pounds) ±10%, are based on the 8-row coil and 1 Hp motor.

12
42BVC UNIT CORNER WEIGHTS (lb)

1 2

3 2 1 4
4 3

1 2

2 1
3 4

4 3
RIGHT HAND UNIT LEFT HAND UNIT

UNIT RIGHT-HAND UNITS LEFT-HAND UNITS TOTAL


CONFIGURATION
42BVC 1 2 3 4 1 2 3 4 WEIGHT
No Heat 52 54 51 43 54 52 43 51 200
06
With Heat 58 65 61 47 65 58 47 61 231
No Heat 53 55 51 43 55 53 43 51 202
08
With Heat 58 66 62 47 66 58 47 62 233
No Heat 63 69 61 50 69 63 50 31 243
10
With Heat 69 81 72 54 81 69 54 72 277
No Heat 64 70 62 51 70 64 51 62 247
12
With Heat 70 82 73 55 82 70 55 73 281
No Heat 74 85 72 58 85 74 58 72 289
16
With Heat 80 98 84 61 98 80 61 84 323
No Heat 90 108 86 68 108 90 68 86 351
20
With Heat 95 123 99 71 123 95 71 99 387
No Heat 110 139 106 81 139 110 81 106 436
30
With Heat 115 155 120 83 155 115 83 120 473
No Heat 131 172 125 94 172 131 94 125 522
40
With Heat 135 190 140 95 190 135 94 140 559
NOTE: Unit weights (shown in pounds) ±10% are based on the 8-row coil and 1 Hp motor.

TOTAL WEIGHT UNIT CORRECTION FACTOR (lb)


Corner weights on pages 12 and 13 are for 8-row water filled coils. For a different number of rows, total unit weight
can be determined by the following procedure:
• Identify the number of rows and the size of the unit.
• Determine the total weight of the unit from the Corner Weight tables.
• From the table below, identify the correction factor (for size of unit and number of rows) and subtract this from the
total weight.
UNITS 4 ROWS 5 ROWS 6 ROWS 7 ROWS
42BHC,BVC Correction Factors (lb)
06 21 16 11 5
08 21 16 11 5
10 28 21 14 7
12 28 21 14 7
16 39 29 20 10
20 46 35 23 12
30 74 55 37 18
40 98 74 49 25

13
Accessory dimensions
MIXING BOX

B W B W

2 2

TOP VIEWS

A 4
1

2.4
3

A
H 2.4

H
2.4
A

3
2.4

A 4 1

C C

BOTTOM/REAR INLET TOP/REAR INLET


RIGHT HAND SIDE VIEWS
NOTE: All dimensions in inches.

42BHC,BVC DIMENSIONS (in.)


UNIT SIZE H W A B C
06 18.5 28 6 24 11
08 18.5 28 6 24 11
10 20.25 37 8 33 13
12 20.25 37 8 33 13
16 20.25 47 8 43 13
20 22.75 48 8 44 13
30 31.0 48 10 44 15
40 31.0 48 10 44 15

14
MIXING BOX RAILS

1 A

3
1
W D

FRONT VIEW SIDE VIEW


NOTE: All dimensions in inches.

DIMENSIONS (in.) DIMENSIONS (in.)


UNIT UNIT
W D A W D A
42BHC06 28 51.6 16.1 42BVC06 28 35.5 16.1
42BHC08 28 51.6 16.1 42BVC08 28 35.5 16.1
42BHC10 37 55.2 18.1 42BVC10 37 39.5 18.1
42BHC12 37 55.2 18.1 42BVC12 37 39.5 18.1
42BHC16 47 55.4 18.1 42BVC16 47 39.5 18.1
42BHC20 48 57.8 18.1 42BVC20 48 41.5 18.1
42BHC30 48 59.8 20.1 42BVC30 48 47.5 20.1
42BHC40 62 63.0 20.1 42BVC40 62 47.5 20.1

15
Accessory dimensions (cont)
VALVE PACKAGES

Basic — Basic valve package includes 2 or 3-way Deluxe — Deluxe valve package includes a circuit
valves with balancing valves and 2 ball valvs. setter and a strainer in addition to the components
listed under basic valve package.

B F

A
E

D D

C C
A E
B F
NOTE: All dimensions in inches.

PIPING CLOSE
CONTROL VALVE PACKAGE SIZE A B C D E F Cv OFF
1/ 2in. 12.45 2.285 — — 15.25 7.41 3.5 25 psig
2-way 3/ in. 12.71 3.156 — — 17.71 7.936 5 20 psig
4

Normal Close Off 1 in. 14.88 3.38 — — 20.81 9.6 8 17 psig


Spring Return 1/2 in. 12.99 14.7 1.823 5.805 16.29 19.32 4 25 psig
3-way 3/4 in. 12.84 16.24 2.318 7.411 17.34 21.02 5 20 psig
1 in. 14.72 19.38 2.774 8.247 20.65 25.19 8 17 psig
1/2 in. 13.29 2.285 — — 16.09 7.41 3.5 60 psig
2-way 3/4 in. 13.59 3.156 — — 18.59 7.936 4.6 60 psig
High Close Off 1 in. 14.97 3.38 — — 20.90 9.6 6.6 60 psig
Power On/ 1/2 in.
Power Off 13.41 15.54 2.031 6.014 16.71 20.16 3.8 60 psig
3-way 3/ in. 13.03 16.62 2.219 7.313 17.53 21.4 5.9 60 psig
4
1 in. 14.77 19.47 2.731 8.248 20.70 25.28 9 60 psig

16
PIPING CONNECTION LOCATION DIAGRAM*

HWR CWR

C CWS

HWS

B
A Drain
2(51)
1-5/8(41)

H
G
8 -5 / 8 ( 219 )

6 -7/ 8 (175 )

0
10 -3 / 8 ( 264 )
E

RH Tell-Tale LH Tell-Tale

LEGEND Use the table on the next page to determine the location of the piping
CWR — Cold Water Return connections. For example, on a size 20 unit with 4 rows and a right
CWS — Cold Water Supply hand connection, the location of the chilled water supply line is deter-
HWR — Hot Water Return mined by G (6 in.) and B (74/5 in.).
HWS — Hot Water Supply
LH — Left Hand
RH — Right Hand
SO — Stub Out
*Right-hand unit with re-heat coil shown.

HEAD STUB OUT SIZES (in.)


42BHC,BVC
UNIT SIZE 8 Row Coil SO 6 Row Coil SO 4 Row Coil SO Heating 1 or 2 SO
Nominal Nominal Nominal Row Coil Nominal
06 1 0.75 0.75 0.5
08 1 0.75 0.75 0.5
10 1 0.75 0.75 0.5
12 1 0.75 0.75 0.5
16 1 1 1 0.5
20 1 1 1 0.5
30 1.5 1.5 1.5 0.5
40 1.5 1.5 1.5 0.5

17
Accessory dimensions (cont)
42BHC,BVC COIL ROWS DIMENSIONS (in.)
HEAT OPTIONS UNIT SIZE Cool Heat A B C D E F G H
0 — — — —
4 1 31/2 151/2 7 7 515/16
2 313/16 1513/16 79/16 79/16
06/08 0 — 61/8 123/4 — — —
6 1 31/2 151/2 93/16 93/16 81/8
2 313/16 1513/16 93/4 93/4
8 0 — — — — 101/4
0 — — — —
4 1 51/8 171/8 7 7 515/16
2 57/16 177/16 79/16 79/16
10/12 0 — 73/4 143/8 — — —
6 1 51/8 171/8 93/16 93/16 81/8
2 527/61 177/16 93/4 93/4
8 0 — — — — 101/4
0 — — — —
LH 105/8 95/8 7
4 1 12 515/16
RH 133/8 95/8 7
2 57/16 177/16 79/16 79/16
16 0 — 73/4 155/8 — — —
LH 105/8 1113/16 93/16
6 1 12 81/8
Re-heat RH 133/8 1113/16 93/16 211/16
2 57/16 177/16 93/4 93/4
8 0 — — — — 101/4
0 — — — —
LH 1115/16 95/8 7
4 1 135/16 515/16
RH 1411/16 95/8 7
2 51/2 201/16 79/16 79/16
20 0 — 713/16 183/16 — — —
LH 1115/16 1113/16 93/16
6 1 135/16 81/8
RH 1411/16 1113/16 93/16
2 51/2 201/16 93/4 93/4
8 0 — — — — 101/4
0 — — — —
LH 141/16 95/8 8
4 1 167/16 515/16
RH 1813/16 95/8 8
2 35/8 281/8 79/16 79/16
30/40 0 — 515/16 265/16 — — —
LH 141/16 1113/16 103/16
6 1 167/16 81/8
RH 1813/16 1113/16 103/16
2 35/8 281/8 93/4 93/4
8 0 — — — — 101/4
0 — 61/8 123/4 — — — 515/16 211/16
4 1 31/2 63/4 133/8 151/2 211/16 211/16 7 33/4
2 313/16 61/8 123/4 1513/16 31/4 31/4 81/8 47/8
06/08 0 — 61/8 123/4 — — — 81/8 211/16
6 1 31/2 63/4 133/8 151/2 211/16 211/16 93/16 33/4
2 313/16 61/8 123/4 1513/16 31/4 31/4 101/4 47/8
8 0 — 61/8 123/4 — — — 101/4 211/16
0 — 73/4 143/8 — — — 515/16 211/16
4 1 51/8 83/8 15 171/8 211/16 211/16 7 33/4
2 57/16 73/4 143/8 177/16 31/4 31/4 81/8 47/8
10/12 0 — 73/4 143/8 — — — 81/8 211/16
6 1 51/8 83/8 15 171/8 211/16 211/16 93/16 33/4
2 57/16 73/4 143/8 177/16 31/4 31/4 101/4 47/8
8 0 — 73/4 143/8 — — — 101/4 211/16
0 — 73/4 155/8 — — — 515/16 211/16
4 1 51/8 83/8 161/4 171/8 211/16 211/16 7 33/4
2 57/16 73/4 155/8 177/16 31/4 31/4 81/8 47/8
Pre-heat* 16 0 — 73/4 155/8 — — — 81/8 211/16
6 1 51/8 83/8 161/4 171/8 211/16 211/16 93/16 33/4
2 57/16 73/4 155/8 177/16 31/4 31/4 101/4 47/8
8 0 — 73/4 155/8 — — — 101/4 211/16
0 — 713/16 183/16 — — — 515/16 211/16
4 1 53/16 87/16 1813/16 193/4 211/16 211/16 7 33/4
2 51/2 713/16 183/16 201/16 31/4 31/4 81/8 47/8
20 0 — 713/16 183/16 — — — 81/8 211/16
6 1 53/16 87/16 1813/16 193/4 211/16 211/16 93/16 33/4
2 51/2 713/16 183/16 201/16 31/4 31/4 101/4 47/8
8 0 — 713/16 183/16 — — — 101/4 211/16
0 — 515/16 265/16 — — — 515/16 211/16
4 1 35/16 69/16 2615/16 2713/16 — — 7 33/4
2 35/8 515/16 265/16 281/8 211/16 211/16 81/8 47/8
30/40 0 — 515/16 265/16 — 31/4 31/4 81/8 211/16
6 1 35/16 69/16 2615/16 2713/16 — — 93/16 33/4
2 35/8 515/16 265/16 281/8 211/16 211/16 101/4 47/8
8 0 — 515/16 265/16 — 31/4 31/4 101/4 211/16

*Factory-installed option.

18
Application data
Basic definitions
UNIT HAND
Unit hand — When facing the supply air outlet from the
front of the unit (air blowing in your face), your right hand
will be the right hand side of the unit and your left hand the
left hand side of the unit.

PIPING COMPONENTS

CV FACTOR RATING*
SYMBOL/SKETCH DESCRIPTION 1/2 3/4 PSI F
MANUAL AIR VENT: Threaded brass needle valve
with screwdriver slot for adjustment.
Application — Body brazed into high point of heat-
ing and cooling coils for bleeding air from coil. Stan- N/A N/A 400 100
dard item on all hydronic coils (not used on steam
or DX coils). Should not be used in lieu of main sys-
tem air vents.
AUTOMATIC AIR VENT: Nickel plated brass valve,
fiber-disc type, with positive shut-off ballcheck and
quick vent feature via knurled vent screw.
Application — Optional replacement for manual air
vent. Automatically passes minute quantities of air
through the fiber discs which expand upon contact N/A N/A 125 240
with water, completely sealing the valve. As air
accumulates, the fiber discs dry and shrink, repeat-
ing the cycle. Not recommended for removing large
quantities of air encountered during initial start-up
or subsequent draining and refilling. Should not be
used in lieu of main system air vents.
SWAGE: Copper tube end expanded to accept a
copper tube of the same size for factory or field
brazing. N/A N/A 300 200
Application — Used where possible for all tubing
joints for best joint integrity.
CIRCUIT SETTER: Variable water flow balancing
valve with manual adjustment knob, pointer, per-
cent-open scale, memory stop and integral pres-
sure read-out ports. 2.12 3.9 300 250
Application — Used for close tolerance water flow
balancing. Positive shut-off ball valve feature allows
usage as combination balancing and shut-off valve.
LEGEND
Cv — Coefficient of Velocity
DX — Direct Expansion
*Check all system component pressure ratings (coils, values, pumps,
etc.) with manufacturer and any applicable local or national piping
codes prior to specifying system pressure rating.

19
Application data (cont)
PIPING COMPONENTS (cont)

CV FACTOR RATING*
SYMBOL/SKETCH DESCRIPTION 1/2 3/4 PSI F
BALANCE VALVE: Variable water flow manual bal-
ancing valve with screwdriver slot adjustment
screw.
Application — Often used in conjunction with test
port fittings for water flow balancing. Balance by 3.0 8.9 150 200
temperature differential or coil pressure drop
(check specifications for service fittings required if
balancing by pressure drop). May be used in 3-way
valve bypass line to permit equal flow balancing.
STRAINER: Y-type body with 50 mesh stainless
steel screen.
Application — Used for removal of small particles
from system water during normal system operation.
Should not be used in lieu of main system strain- 9.0 19.0 400 250
ers. Strainer screen may have to be removed dur- Clean Clean
ing initial high pressure system flushing during
start-up. Screen should be removed and cleaned
per normal maintenance schedule (provisions for
strainer blow-down not provided).
BALL VALVE: Manual balance and shut-off valve.
Application — Used for unit isolation and water flow
balancing. Without memory stop feature water bal- 4.0 7.5 400 200
ance point must be marked by installer (if neces-
sary). Check specifications for service fittings
required when used for water balancing.
LEGEND
Cv — Coefficient of Velocity
DX — Direct Expansion
*Check all system component pressure ratings (coils, values, pumps,
etc.) with manufacturer and any applicable local or national piping
codes prior to specifying system pressure rating.

20
PIPING COMPONENTS (cont)

CV FACTOR RATING
SYMBOL/SKETCH DESCRIPTION 1/ 3/4
2 1 PSI F
2-WAY MOTORIZED VALVE: Electric
2-position flow control valve (open/closed). 3.5 5.0 8.0
Normally closed body with manual override
lever. Installed in supply line to unit.
Application — All standard control and valve
packages are based upon normally closed SPRING RETURN
valves (valve electrically powered open and
closed by spring return when electric power 300 200
removed). Manual override lever allows valve
to be placed in the open position for second- 3.5 4.6 6.6
ary (unit) flushing, constant water flow prior to
start-up, etc. Manual override is automatically
disengaged when valve is electrically acti-
vated. Consult factory for normally open POWER ON/OFF
valve applications.
3-WAY MOTORIZED VALVE: Electric
2-position flow control valve (closed to coil/ 4.0 5.0 8.0
open to bypass or open to coil/closed to
bypass). Normally closed with manual over-
ride lever. Installed in supply line to unit.
Application — Same comments as 2-way SPRING RETURN
motorized valve except with manual override
lever engaged the valve is open to both ports 300 200
and water flow will take the path of least resis-
tance through the valve package (not neces- 3.8 5.9 9.0
sarily 100% through the coil).

POWER ON/OFF

LEGEND
Cv — Coefficient of Velocity
DX — Direct Expansion
NOTES:
1. Motorized spring return 2-way valves have a maximum close-off differential of 25 psi.
2. Motorized spring return 3-way valves have a maximum close-off differential of 25 psi.

21
Selection procedure
This selection procedure provides a guide to determine SC = SCb x Cs x Es
unit performance of the 42BHC, BVC units. Capacity = 34.2 x .96 x 1.00
tables (in Performance Data) are based on nominal cfm.
Correction factors are provided for other operating condi- = 32.83 MBtuh
tions as explained in the following selection example. a) Calculate water pressure drop (or refer to the Water
Pressure Drop for Cv Factor and Water Flow Rate
For applications outside the range provided in this
catalog, please consult the factory. table on page 33). From the Cv Factor by Coil and
Unit Size table on page 32, find the Cv value for
FORMULAS: unit size 16 with four rows.
TC = TCb x Ct x Et Cv = 7.2
SC = SCb x Cs x Es P = [GPM/(0.658 x Cv)]2
Where: = [7.0/(0.658 x 7.2)]2
Cs = Sensible Airflow Correction Factor = 2.18 feet of H2O
Ct = Total Airflow Correction Factor
b) For selections other than those listed here, please
Es = Sensible Elevation Correction Factor
contact the factory.
Et = Total Elevation Correction Factor
SC = Sensible Capacity IV Determine motor.
SCb = Base Sensible Capacity from Base Cooling Capaci- To determine motor and drive selection requirements
ties by gpm charts and obtain the cfm for a specific application, the
TC = Total Capacity total static pressure (TSP) for that application must be
TCb = Base Total Capacity from Base Cooling Capacities determined.
by gpm charts The TSP is the sum of the internal static pressure
(ISP) and the external static pressure (ESP) measured in
EXAMPLE: inches of water column. Internal static pressure is the
I Rate unit performance. sum of the static resistance of the unit’s components
— the cabinet, coil and filter. The ESP is the static
To rate the performance at sea level for a 42BHC16 resistance of the unit’s external components, including,
unit with a four-row coil at 80 F/67 F EAT, 45 F EWT,
but not limited to, ductwork, grilles and additional
7 gpm water flow, and 1500 cfm:
filtration. For non-ducted applications, the ESP is
a) Enter the Base Cooling Capacities by Gpm, 4-Row 0 in. wg.
Capacity Units table at 80 F/67 F EAT and
After the TSP has been calculated (see the following
45 F EWT.
example), use the motor horsepower table on pages 30
b) Locate the appropriate row for unit size 16 and and 31 to determine actual horsepower (hp) for the belt
7 gpm. drive unit. Horsepower offerings are limited to 1/4, 1/3,
Record the tabulated base performance. 1/2, 3/4, 1, 11/2, 2, 3 and 5.

TCb = 42.0 MBtuh The standard selection is the nearest offering above
SCb = 34.2 MBtuh the actual hp shown in the table.
∆T = 12.0 F Using the TSP of the table, match the unit size with
the cfm row to determine the correct motor for the
c) Divide CFM Actual by CFM Nominal to determine
specific application. Drive sheaves and the required
Cfm Ratio.
belt assembly will be provided to meet specific design
Cfm Ratio = 1500/1600 =.9375 requirements. Drive sheaves are set at the factory.
II Select CFM correction factors. Calculate the hp and drive selection required to deliv-
Select the Cfm correction factors, Ct and Cs, from the er 1500 cfm on a 42BHC16 unit equipped with a
Airflow Correction Factors table. (Interpolation may be 4-row hydronic cooling coil and a 2-in. pleated filter in
required.) a ducted application at .38 in. ESP, including duct and
Ct = .9625 grille losses.
Cs = .96 Using the Component Static Resistance table on
page 32, the ISP is calculated as follows:
Select the elevation correction factors, Et and Es, from
the Elevation Correction Factors table. (No correction Cabinet .09-in. wg
necessary in this example, unit is at sea level.) 4-row Wet Coil .30-in. wg
Et = 1.00 2-in. Pleated Filter .12-in. wg
Es = 1.00 ISP .51-in. wg
III Calculate actual performance. ESP .38-in. wg
TC = TCb x Ct x Et TSP .89-in. wg
= 42.0 x .9625 x 1.00
= 40.42 MBtuh

22
Performance data
42BHC,BVC AIRFLOW CORRECTION FACTORS DIRECT EXPANSION (DX) CORRECTION FACTORS
CFM RATIO % OF CORRECTION FACTOR
(Actual/Base) TOTAL (Ct) SENSIBLE (Cs)
NOMINAL CFM Total Sensible
1.40 1.25 1.26 80 0.95 0.93
1.35 1.22 1.23 90 0.97 0.96
1.30 1.19 1.20 100 1.00 1.00
1.25 1.16 1.17 110 1.02 1.04
1.20 1.13 1.14 120 1.05 1.08
1.15 1.10 1.11
Consult factory for values outside of table.
1.10 1.07 1.08 DX Total Capacity (MBtuh) = Base Et x Total Correction Factor
1.05 1.04 1.04 DX Sensible Capacity (MBtuh) = Base Es x Sensible Correction Factor
1.00 1.00 1.00 % of Nominal Cfm = Actual Cfm (from Fan Performance table)
÷ Nominal Cfm
0.95 0.97 0.97
0.90 0.94 0.93
0.85 0.90 0.89
0.80 0.86 0.85
0.75 0.82 0.81
0.70 0.78 0.77
0.65 0.74 0.72
0.60 0.70 0.67
0.55 0.66 0.62
ALTITUDE COOLING CORRECTION FACTORS
0.50 0.62 0.57 ELEVATION (ft) TOTAL HEAT (Et) SENSIBLE HEAT (Es)
0.45 0.58 0.52 1000 0.99 0.96
0.40 0.53 0.47 2000 0.98 0.93
3000 0.97 0.89
0.35 0.48 0.42
0.30 0.43 0.38 4000 0.96 0.86
5000 0.94 0.83
0.25 0.38 0.33 6000 0.93 0.80
NOTE: Use Sensible Heat correction factors when calculating heating 7000 0.92 0.77
capacity. 8000 0.91 0.75
9000 0.90 0.73

42BHC,BVC HOT WATER CAPACITY CORRECTION FACTORS

ENTERING AIR ENTERING WATER TEMPERATURE (F)


TEMPERATURE (F) 100 110 120 130 140 150 160 170 180 190 200
50 0.455 0.545 0.636 0.727 0.818 0.909 1.000 1.091 1.182 1.273 1.364
55 0.409 0.500 0.591 0.682 0.773 0.864 0.955 1.045 1.136 1.227 1.318
60 0.363 0.455 0.545 0.636 0.727 0.818 0.909 1.000 1.091 1.182 1.273
65 0.318 0.409 0.500 0.591 0.682 0.773 0.864 0.955 1.045 1.136 1.227
70 0.272 0.363 0.455 0.545 0.636 0.727 0.818 0.909 1.000 1.091 1.182
75 0.227 0.318 0.409 0.500 0.591 0.682 0.773 0.864 0.955 1.045 1.136
80 0.182 0.272 0.363 0.455 0.545 0.636 0.727 0.818 0.909 1.000 1.091
NOTES:
1. Leaving air temperature not to exceed 104 F with standard motor.
2. Base capacity ratings based on 180 F entering water temperature
and 70 F entering air temperature.
3. Hot Water Heating Capacity (MBtuh) = Rated Heating Capacity x
Hot Water Capacity Correction Factor x Sensible Airflow Correc-
tion Factor.

23
Performance data (cont)
42BHC, BVC NOMINAL COOLING CAPACITIES 42BHC,BVC NOMINAL HEATING CAPACITIES
COOLING* UNIT SIZE HEATING CAPACITY
NOMINAL CFM ROWS
UNIT SIZE NOMINAL COIL EWT Total Sensible 42BHC,BVC (MBtuh)
42BHC,BVC CFM ROWS (F) Capacity Capacity 1 27.0
06 600
(MBtuh) (MBtuh) 2 46.9
40 23.3 16.0 1 27.0
4 45 17.9 13.8 08 800
2 46.9
50 12.8 12.0
1 27.0
40 31.0 19.8 10 1000
06 600 6 45 24.5 17.0 2 46.9
50 18.0 14.5 1 38.5
12 1200
40 33.8 21.2 2 68.5
8 45 26.7 18.1 1 48.0
50 19.4 15.2 16 1600
2 87.7
40 28.4 20.0 1 58.7
4 45 21.9 17.5 20 2000
50 15.3 15.3 2 104.9
1 78.0
40 38.4 25.1 30 3000
08 800 6 45 30.3 21.7 2 149.2
50 22.5 18.6 1 92.3
40 4000
40 42.6 27.2 2 182.4
8 45 33.7 23.3
50 24.7 19.8
40 40.5 27.3 NOTES:
4 45 31.6 23.7 1. Ratings are based on 180 F Entering Water Temperature (EWT) and 70 F
50 23.4 20.6 Entering Air Temperature (EAT).
2. Leaving-air temperature is not to exceed 104 F with the standard motor.
40 52.2 33.3 Consult the factory for higher temperature motor applications.
10 1000 6 45 41.7 28.7 3. For information on four and six-row heating coil capacities and applications,
50 31.2 24.5 consult the factory.
40 57.7 36.0 4. For all application ratings, use the quick-selection ratings provided in this
8 45 46.4 31.0 catalog, or contact the factory.
50 34.6 26.2
40 45.4 31.2
4 45 35.5 27.2
50 26.5 23.8
40 59.6 38.4
12 1200 6 45 47.4 33.2
50 35.5 28.5
40 66.6 42.0
8 45 53.3 36.1
50 39.9 30.7
40 59.7 41.2
4 45 46.4 35.9
50 34.4 31.4
40 78.7 50.9
16 1600 6 45 62.6 44.1
50 46.8 37.8
40 89.0 56.0
8 45 71.3 48.3
50 53.3 41.0
40 75.2 51.6
4 45 59.0 45.1
50 44.1 39.5
40 99.0 63.8
20 2000 6 45 78.7 55.2
50 59.0 47.4
40 111.8 70.3
8 45 89.9 60.6
50 67.6 51.6
40 112.5 77.6
4 45 87.6 67.6
50 65.0 59.1
40 148.5 95.8
30 3000 6 45 117.8 82.8
50 88.1 71.1
40 168.0 105.5
8 45 135.0 91.0
50 101.2 77.4
40 157.7 106.7
4 45 123.6 92.9
50 92.6 81.1
40 204.0 130.5
40 4000 6 45 162.6 112.7
50 122.3 96.7
40 230.1 143.5
8 45 185.6 123.8
50 140.2 105.2
LEGEND
EWT — Entering Water Temperature
MBtuh — Capacity (Btuh in thousands)
*Based on entering air temperature of 67 F wb, 80 F db and temperature rise of 10
degrees F.
NOTE: All ratings at sea level. Ratings in accordance with ARI (Air Conditioning &
Refrigeration Institute).

24
42BHC,BVC 4-ROW COOLING CAPACITY (by Gpm)
75 F DB/ 63 F WB 80 F DB/67 F WB 85 F DB/71 F WB
UNIT
SIZE GPM 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT
42BHC,BVC ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb
3 10.9 16.3 13.2 9.0 13.5 12.1 7.2 10.7 10.7 13.0 19.5 14.5 11.1 16.6 13.4 9.1 13.7 12.3 15.3 22.9 15.7 13.3 19.9 14.6 11.2 16.9 13.5
06 4 9.1 18.3 14.0 7.5 15.0 12.7 5.7 11.5 11.5 11.0 22.0 15.5 9.3 18.6 14.1 7.6 15.2 12.8 13.1 26.2 16.9 11.3 22.6 15.5 9.5 18.9 14.2
5 7.9 19.7 14.6 6.4 16.1 13.1 5.0 12.5 11.6 9.6 23.9 16.3 8.0 20.1 14.7 6.5 16.2 13.2 11.4 28.5 17.8 9.8 24.5 16.3 8.2 20.4 14.8
3 12.2 18.3 16.0 10.0 15.0 15.0 8.4 12.7 12.7 14.5 21.7 17.4 12.4 18.7 16.3 10.2 15.2 15.2 16.9 25.4 18.8 14.8 22.2 17.7 12.6 19.0 16.6
08 4 10.4 20.8 17.0 8.6 17.2 15.6 6.9 13.8 13.8 12.4 24.9 18.6 10.6 21.1 17.2 8.7 17.4 15.8 14.6 29.2 20.2 12.7 25.4 18.8 10.7 21.4 17.4
5 9.0 22.6 17.7 7.4 18.6 16.1 5.8 14.5 14.5 10.8 27.1 19.5 9.2 22.9 17.9 7.5 18.7 16.3 12.9 32.1 21.3 11.1 27.7 19.6 9.3 23.2 18.0
6 8.0 23.9 18.3 6.5 19.5 16.5 5.0 14.9 14.9 9.6 28.9 20.3 8.1 24.3 18.4 6.6 19.7 16.7 11.5 34.4 22.1 9.8 29.5 20.3 8.2 24.6 18.5
3 15.4 23.1 20.2 12.7 19.0 19.0 10.6 16.0 16.0 18.2 27.2 22.0 15.6 23.4 20.6 12.8 19.2 19.2 21.1 31.7 23.7 18.5 27.8 22.3 15.8 23.8 21.0
10 4 13.2 26.4 21.6 11.0 21.9 19.8 8.8 17.5 17.5 15.7 31.5 23.6 13.4 26.8 21.8 11.1 22.1 20.1 18.4 36.9 25.5 16.0 32.0 23.8 13.6 27.1 22.1
5 11.5 28.8 22.6 9.5 23.7 20.5 7.4 18.5 18.5 13.8 34.6 24.9 11.7 29.2 22.8 9.6 23.9 20.8 16.3 40.7 27.0 14.1 35.2 24.9 11.8 29.6 22.9
6 10.2 30.6 23.4 8.4 25.1 21.1 6.4 19.1 19.1 12.3 36.9 25.8 10.4 31.1 23.5 8.4 25.3 21.3 14.6 43.8 28.2 12.6 37.7 25.8 10.5 31.5 23.6
3 16.4 24.6 22.8 13.8 20.7 20.7 11.6 17.4 17.4 19.3 28.9 24.7 16.7 25.0 23.3 14.0 20.9 20.9 22.3 33.5 26.5 19.6 29.5 25.1 16.9 25.4 23.8
12 4 14.2 28.4 24.3 11.9 23.7 22.4 9.7 19.3 19.3 16.8 33.6 26.5 14.4 28.8 24.6 11.6 23.2 23.2 19.6 39.2 28.5 17.1 34.2 26.7 14.5 29.1 25.0
5 12.4 31.1 25.4 10.3 25.8 23.2 8.2 20.5 20.5 14.8 37.1 27.8 12.6 31.5 25.7 10.4 26.0 23.6 17.4 43.6 30.1 15.1 37.8 28.0 12.7 31.9 25.9
6 11.1 33.2 26.3 9.1 27.3 23.9 7.1 21.4 21.4 13.3 39.8 28.9 11.2 33.7 26.5 9.2 27.5 24.2 15.6 46.9 31.4 13.5 40.5 29.0 11.3 34.0 26.7
5 14.2 35.4 31.4 11.7 29.3 29.3 9.9 24.7 24.7 16.8 41.9 34.2 14.4 36.1 32.0 11.9 29.7 29.7 19.5 48.8 36.8 17.1 42.8 34.7 14.7 36.6 32.6
16 7 11.8 41.3 33.8 9.8 34.3 31.0 7.8 27.4 27.4 14.1 49.4 37.1 12.0 42.0 34.2 9.9 34.6 31.5 16.6 58.0 40.1 14.4 50.3 37.3 12.1 42.5 34.6
9 10.1 45.3 35.5 8.3 37.2 32.2 6.4 28.9 28.9 12.1 54.4 39.1 10.2 46.0 35.8 8.3 37.5 32.6 14.3 64.4 42.5 12.3 55.5 39.2 10.3 46.5 36.0
11 8.7 48.1 36.7 7.1 39.3 33.0 5.4 29.9 29.9 10.6 58.3 40.7 8.9 48.8 36.9 7.2 39.5 33.3 12.6 69.3 44.4 10.8 59.4 40.6 9.0 49.5 37.0
5 16.5 41.3 37.9 13.8 34.6 34.6 11.6 29.1 29.1 19.4 48.6 41.2 16.8 42.0 38.7 14.0 35.0 35.0 22.5 56.3 44.2 19.8 49.5 41.8 17.0 42.6 39.5
20 7 13.9 48.5 40.8 11.6 40.5 37.6 9.3 32.7 32.7 16.5 57.6 44.6 14.0 49.2 41.4 11.7 40.8 38.3 19.2 67.4 48.1 16.7 58.6 45.0 14.2 49.7 41.9
9 11.9 53.5 42.9 9.8 44.1 39.1 7.7 34.8 34.8 14.2 64.0 47.1 12.0 54.1 43.3 9.9 44.4 39.6 16.7 75.2 51.0 14.5 65.0 47.3 12.2 54.7 43.6
11 10.4 57.1 44.4 8.5 46.8 40.1 6.6 36.1 36.1 12.5 68.6 48.9 10.5 57.8 44.7 8.5 47.0 40.6 14.8 81.3 53.3 12.7 69.9 49.0 10.6 58.4 44.9
7 15.9 55.6 55.6 13.9 48.5 48.5 11.7 41.0 41.0 19.0 66.5 59.7 16.2 56.8 56.8 14.1 49.4 49.4 22.0 77.0 64.0 19.5 68.2 61.0 16.5 57.9 57.9
9 14.6 65.5 58.6 12.1 54.4 54.4 10.2 45.8 45.8 17.2 77.4 63.7 14.8 66.8 59.8 12.2 55.1 55.1 20.0 90.1 68.5 17.6 79.0 64.7 15.1 67.8 60.9
30 11 13.1 72.3 61.3 11.0 60.5 56.6 8.9 49.1 49.1 15.6 85.9 67.0 13.4 73.5 62.2 11.1 61.1 57.7 18.3 100.5 72.2 15.9 87.6 67.6 13.5 74.5 63.1
14 11.4 79.9 64.5 9.4 66.1 58.8 7.5 52.3 52.3 13.7 95.6 70.7 11.6 81.1 65.1 9.5 66.6 59.7 16.1 112.5 76.6 13.9 97.4 71.1 11.7 82.1 65.7
17 11.4 85.5 66.8 8.3 70.2 60.5 6.4 54.5 54.5 12.1 102.8 73.6 10.2 86.8 67.3 8.3 70.7 61.2 14.3 121.8 80.1 12.3 104.9 73.8 10.3 87.9 67.7
11 16.4 90.5 79.5 13.5 74.4 74.4 11.4 62.5 62.5 19.4 106.8 86.4 16.7 91.8 80.8 13.7 75.1 75.1 22.6 124.1 92.8 19.7 108.5 87.4 16.9 92.8 82.1
14 14.4 100.9 83.7 12.0 84.0 76.8 9.6 67.4 67.4 17.1 119.9 91.4 14.6 102.1 84.6 12.1 84.6 78.2 20.0 140.2 98.6 17.4 121.8 92.0 14.7 103.2 85.6
40 17 12.8 108.7 87.0 10.6 89.7 79.2 8.3 70.6 70.6 15.3 129.9 95.4 12.9 110.0 87.6 10.6 90.2 80.2 18.0 152.6 103.2 15.5 132.0 95.7 13.1 111.1 88.3
21 11.1 116.5 90.2 9.1 95.5 81.5 7.0 73.6 73.6 13.3 140.0 99.4 11.2 118.0 90.7 9.1 95.9 82.3 15.8 165.5 108.1 13.6 142.4 99.4 11.3 119.2 91.1
25 9.8 122.3 92.7 8.0 99.8 83.2 6.0 75.6 75.6 11.8 147.9 102.7 9.9 124.0 93.0 8.0 100.3 84.0 14.1 175.8 112.1 12.0 150.4 102.4 10.0 125.5 93.3

LEGEND NOTE: All capacities are given in thousands of Btuh (MBtuh).


DB — Dry Bulb Temperature
EWT — Entering Water Temperature
MBtuh — Btuh in Thousands
SCb — Base Sensible Capacity at Nominal Cfm
TCb — Base Total Capacity at Nominal Cfm
WB — Wet Bulb Temperature
∆T — Change in Water Temperature (F)

42BHC,BVC 6-ROW COOLING CAPACITY (by Gpm)


75 F DB/63 F WB 80 F DB/67 F WB 85 F DB/71 F WB
UNIT
SIZE GPM 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT
42BHC,BVC ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb
3 13.5 20.2 15.4 11.1 16.7 13.9 8.8 13.2 12.5 16.1 24.2 16.9 13.7 20.6 15.5 11.2 16.8 14.0 19.0 28.4 18.3 16.5 24.7 16.9 13.9 20.8 15.5
06 4 11.3 22.6 16.4 9.2 18.5 14.6 7.2 14.4 12.9 13.6 27.2 18.2 11.5 23.0 16.4 9.3 18.6 14.7 16.1 32.2 19.8 13.9 27.9 18.1 11.7 23.4 16.4
5 9.7 24.2 17.1 7.9 19.7 15.1 6.1 15.1 13.3 11.7 29.2 19.1 9.9 24.6 17.1 7.9 19.9 15.2 13.9 34.8 20.9 12.0 30.0 19.0 10.0 25.1 17.1
3 15.3 22.9 18.7 12.8 19.2 17.2 10.2 15.3 15.3 18.1 27.2 20.4 15.5 23.3 18.9 12.9 19.3 17.4 21.2 31.8 22.0 18.5 27.7 20.5 15.7 23.6 19.1
08 4 13.0 26.0 20.0 10.7 21.4 18.1 8.3 16.5 16.5 15.5 31.1 22.0 13.2 26.4 20.1 10.8 21.6 18.3 18.3 36.5 23.8 15.8 31.7 22.0 13.4 26.7 20.2
5 11.3 28.1 20.9 9.2 23.1 18.7 7.2 18.0 16.7 13.5 33.8 23.1 11.4 28.6 21.0 9.3 23.2 18.9 16.0 40.0 25.2 13.8 34.6 23.1 11.6 29.0 21.0
6 9.9 29.7 21.6 8.1 24.3 19.2 6.3 18.8 17.0 12.0 35.9 24.0 10.1 30.2 21.6 8.2 24.5 19.3 14.2 42.6 26.2 12.2 36.7 23.9 10.2 30.7 21.6
4 16.2 32.3 25.0 13.4 26.8 22.7 10.4 20.8 20.8 19.2 38.5 27.4 16.4 32.7 25.1 13.5 26.9 22.9 22.5 45.0 29.6 19.5 39.1 27.4 16.5 33.1 25.2
10 5 14.1 35.3 26.3 11.6 29.0 23.6 9.1 22.8 21.1 16.9 42.3 29.0 14.3 35.8 26.3 11.7 29.2 23.8 19.9 49.8 31.5 17.2 43.0 28.9 14.5 36.2 26.3
6 12.5 37.5 27.2 10.2 30.6 24.3 7.9 23.8 21.5 15.0 45.1 30.2 12.7 38.1 27.2 10.3 30.8 24.4 17.8 53.3 32.9 15.4 46.1 30.0 12.9 38.6 27.2
8 10.1 40.5 28.6 8.2 32.9 25.3 6.3 25.3 22.1 12.3 49.1 31.9 10.3 41.3 28.5 8.3 33.2 25.3 14.6 58.5 35.0 12.6 50.3 31.7 10.5 41.9 28.4
6 13.7 41.0 30.8 11.2 33.6 27.7 8.8 26.5 24.8 16.4 49.1 33.9 13.8 41.5 30.9 11.3 33.8 27.9 19.3 57.8 36.8 16.6 49.9 33.8 14.0 41.9 30.9
12 8 11.2 44.7 32.4 9.1 36.4 28.9 7.1 28.2 25.5 13.5 53.9 35.9 11.3 45.4 32.4 9.2 36.7 29.0 16.0 63.9 39.3 13.8 55.0 35.8 11.5 46.0 32.4
10 9.4 47.1 33.5 7.7 38.3 29.7 5.9 29.4 26.0 11.5 57.3 37.4 9.6 48.0 33.5 7.7 38.6 29.7 13.6 68.2 41.1 11.7 58.6 37.2 9.8 48.8 33.4
7 14.6 51.2 39.6 12.1 42.3 35.9 9.4 32.8 32.8 17.5 61.1 43.5 14.8 51.9 39.8 12.2 42.6 36.3 20.5 71.7 47.0 17.8 62.1 43.5 15.0 52.4 40.0
16 9 12.5 56.1 41.7 10.2 46.0 37.4 8.0 36.0 33.3 15.0 67.4 46.0 12.6 56.9 41.8 10.3 46.2 37.6 17.7 79.5 50.1 15.3 68.7 45.9 12.8 57.6 41.8
11 10.8 59.5 43.2 8.8 48.5 38.5 6.8 37.6 34.0 13.1 71.8 47.9 11.0 60.5 43.2 8.9 48.9 38.6 15.5 85.2 52.4 13.3 73.4 47.7 11.1 61.3 43.2
13 9.5 62.0 44.4 7.8 50.5 39.3 6.0 38.8 34.5 11.6 75.3 49.4 9.7 63.2 44.3 7.8 50.9 39.4 13.8 89.6 54.2 11.8 76.9 49.1 9.9 64.2 44.2
7 17.0 59.6 47.6 14.2 49.5 43.4 11.2 39.2 39.2 20.2 70.7 52.0 17.2 60.3 47.9 14.2 49.8 44.0 23.6 82.5 56.0 20.5 71.7 52.1 17.4 60.8 48.2
9 14.6 65.9 50.2 12.0 54.2 45.3 9.2 41.5 41.5 17.5 78.7 55.2 14.8 66.6 50.4 12.1 54.5 45.7 20.5 92.4 59.8 17.8 79.9 55.1 14.9 67.3 50.5
20 11 12.8 70.4 52.2 10.5 57.6 46.7 8.2 45.0 41.6 15.4 84.6 57.6 13.0 71.3 52.2 10.5 57.9 47.0 18.1 99.8 62.7 15.6 86.1 57.4 13.1 72.1 52.2
13 11.4 73.8 53.7 9.3 60.2 47.8 7.2 46.6 42.3 13.7 89.0 59.5 11.5 74.9 53.6 9.3 60.5 48.0 16.2 105.3 64.9 14.0 90.8 59.2 11.7 75.9 53.6
15 10.2 76.5 54.9 8.3 62.2 48.7 6.4 47.9 42.8 12.3 92.6 61.0 10.4 77.8 54.8 8.4 62.6 48.8 14.7 110.2 67.0 12.6 94.6 60.7 10.5 78.9 54.7
11 16.3 89.4 71.5 13.5 74.4 65.3 10.7 59.0 59.0 19.3 106.2 78.1 16.5 90.6 72.1 13.6 75.0 66.2 22.5 124.0 84.3 19.6 107.9 78.4 16.7 91.6 72.7
30 14 14.1 98.9 75.5 11.6 81.5 68.2 8.9 62.5 62.5 16.9 118.2 83.0 14.3 100.2 75.8 11.7 82.0 68.8 19.8 138.9 90.0 17.2 120.3 82.9 14.5 101.3 76.0
17 12.4 105.8 78.5 10.2 86.7 70.3 8.0 67.8 62.7 15.0 127.2 86.7 12.6 107.3 78.6 10.3 87.2 70.8 17.6 150.0 94.3 15.2 129.6 86.4 12.8 108.6 78.7
21 10.7 112.5 81.5 8.7 91.7 72.4 6.8 71.0 63.9 12.9 135.8 90.4 10.9 114.3 81.4 8.8 92.3 72.7 15.4 161.2 98.8 13.2 138.8 89.9 11.0 115.9 81.3
17 15.6 132.8 101.1 12.9 109.4 91.3 10.2 86.6 82.1 18.7 158.6 111.1 15.8 134.3 101.4 12.9 109.9 92.0 21.9 185.9 120.3 18.9 160.8 110.8 15.9 135.4 101.6
40 21 13.6 142.7 105.4 11.1 116.8 94.3 8.7 91.3 83.9 16.3 171.3 116.4 13.8 144.5 105.4 11.2 117.3 94.8 19.2 201.8 126.5 16.6 174.2 115.8 13.9 145.9 105.3
25 12.0 150.0 108.6 9.8 122.3 96.6 7.6 94.8 85.3 14.5 180.8 120.4 12.2 152.2 108.5 9.8 123.0 97.0 17.1 213.8 131.4 14.7 184.4 119.7 12.3 154.1 108.3
LEGEND NOTE: All capacities are given in thousands of Btuh (MBtuh).
DB — Dry Bulb Temperature
EWT — Entering Water Temperature
MBtuh — Btuh in Thousands
SCb — Base Sensible Capacity at Nominal Cfm
TCb — Base Total Capacity at Nominal Cfm
WB — Wet Bulb Temperature
∆T — Change in Water Temperature (F)

25
Performance data (cont)
42BHC,BVC 8-ROW COOLING CAPACITY (by Gpm)
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
UNIT
SIZE GPM 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT
42BHC,BVC ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb ∆T TCb SCb
4 11.8 23.6 17.0 9.7 19.4 15.2 7.6 15.1 13.4 14.2 28.4 18.9 12.1 24.1 17.1 9.8 19.6 15.3 16.8 33.6 20.6 14.6 29.2 18.8 12.3 24.6 17.1
5 10.2 25.6 17.9 8.4 20.9 15.8 6.4 16.1 13.8 12.4 30.9 20.0 10.5 26.2 17.9 8.5 21.2 15.9 14.7 36.7 21.9 12.7 31.9 19.9 10.7 26.7 17.9
06 6 9.0 27.0 18.6 7.3 22.0 16.3 5.6 16.8 14.1 10.9 32.7 20.8 9.2 27.6 18.5 7.4 22.3 16.3 13.0 39.0 22.9 11.3 33.8 20.6 9.4 28.3 18.5
7 8.0 28.0 19.0 6.5 22.8 16.7 5.0 17.3 14.3 9.7 34.1 21.4 8.2 28.7 19.0 6.6 23.1 16.7 11.6 40.7 23.6 10.1 35.2 21.2 8.4 29.4 18.9
4 13.6 27.2 20.8 11.3 22.5 18.8 9.0 18.0 17.0 16.2 32.5 22.8 13.8 27.7 20.9 11.4 22.8 19.0 19.0 38.1 24.7 16.6 33.2 22.9 14.1 28.1 21.0
5 11.9 29.9 21.9 9.8 24.6 19.7 7.7 19.3 17.5 14.4 35.9 24.2 12.2 30.4 22.0 9.9 24.8 19.8 16.9 42.3 26.4 14.7 36.7 24.2 12.4 30.9 22.0
08 6 10.6 31.9 22.8 8.7 26.1 20.3 6.7 20.2 17.9 12.8 38.4 25.3 10.8 32.5 22.8 8.8 26.4 20.4 15.2 45.5 27.7 13.1 39.4 25.2 11.0 33.1 22.8
7 9.5 33.4 23.5 7.8 27.2 20.8 6.0 21.0 18.2 11.5 40.4 26.2 9.7 34.1 23.5 7.9 27.6 20.9 13.7 47.9 28.7 11.9 41.5 26.1 9.9 34.8 23.5
8 8.6 34.6 24.1 7.0 28.2 21.2 5.4 21.6 18.4 10.5 41.9 26.9 8.8 35.4 24.0 7.1 28.5 21.2 12.5 50.0 29.6 10.8 43.2 26.7 9.0 36.1 24.0
6 13.3 40.0 28.6 10.9 32.8 25.5 8.5 25.5 22.5 16.0 48.1 31.7 13.6 40.7 28.6 11.0 33.1 25.6 18.9 56.8 34.6 16.4 49.2 31.6 13.8 41.3 28.6
7 12.0 42.1 29.6 9.8 34.4 26.2 7.6 26.5 22.9 14.5 50.8 32.9 12.3 42.9 29.5 9.9 34.7 26.2 17.2 60.2 36.0 14.9 52.1 32.7 12.5 43.6 29.4
10 8 10.9 43.7 30.3 8.9 35.6 26.7 6.8 27.3 23.2 13.2 52.9 33.8 11.2 44.6 30.3 9.0 36.0 26.7 15.7 62.8 37.2 13.6 54.4 33.6 11.4 45.5 30.1
9 10.0 45.0 31.0 8.1 36.6 27.2 6.2 28.0 23.5 12.1 54.6 34.6 10.2 46.0 30.8 8.2 37.1 27.2 14.5 65.1 38.1 12.5 56.2 34.4 10.4 47.0 30.7
7 13.2 46.4 33.6 10.9 38.0 30.0 8.5 29.7 26.5 15.9 55.7 37.1 13.5 47.1 33.6 10.9 38.3 30.1 18.8 65.7 40.5 16.3 56.9 37.0 13.6 47.8 33.5
9 11.1 50.1 35.3 9.1 40.8 31.2 7.0 31.5 27.3 13.5 60.5 39.2 11.3 51.0 35.2 9.2 41.2 31.2 15.9 71.7 43.0 13.8 62.0 39.0 11.5 51.9 35.1
12 11 9.6 52.6 36.4 7.8 42.8 32.0 5.9 32.7 27.8 11.6 63.8 40.7 9.8 53.7 36.3 7.9 43.2 32.0 13.8 76.1 44.8 11.9 65.5 40.4 10.0 54.8 36.1
13 8.4 54.4 37.2 6.8 44.2 32.6 5.2 33.6 28.1 10.2 66.3 41.8 8.6 55.6 37.1 6.9 44.7 32.6 12.2 79.1 46.2 10.5 68.2 41.5 8.7 56.9 37.0
9 13.6 61.0 44.5 11.1 50.1 39.7 8.7 39.2 35.3 16.3 73.3 49.1 13.8 62.1 44.5 11.2 50.6 39.9 19.2 86.4 53.5 16.6 74.9 48.9 14.0 63.0 44.4
11 11.9 65.3 46.4 9.7 53.3 41.1 7.5 41.2 36.1 14.3 78.8 51.5 12.1 66.5 46.3 9.8 53.8 41.2 16.9 93.2 56.3 14.7 80.6 51.2 12.3 67.5 46.1
16 13 10.5 68.3 47.7 8.6 55.7 42.1 6.6 42.7 36.7 12.7 82.7 53.2 10.7 69.7 47.6 8.6 56.2 42.1 15.1 98.2 58.4 13.1 84.9 52.9 10.9 70.9 47.4
15 9.4 70.6 48.8 7.7 57.4 42.9 5.8 43.9 37.1 11.4 85.8 54.6 9.6 72.2 48.6 7.7 58.0 42.9 13.6 102.3 60.1 11.7 88.1 54.2 9.8 73.6 48.4
10 14.9 74.6 54.8 12.3 61.3 49.1 9.6 48.1 43.7 17.9 89.4 60.4 15.1 75.7 54.8 12.3 61.7 49.3 21.0 105.1 65.6 18.2 91.0 60.1 15.3 76.5 54.7
12 13.2 79.4 56.9 10.8 64.9 50.6 8.4 50.4 44.6 15.9 95.6 63.0 13.4 80.6 56.8 10.9 65.4 50.7 18.8 112.8 68.8 16.3 97.5 62.6 13.6 81.7 56.6
20 14 11.9 83.0 58.6 9.7 67.7 51.8 7.4 52.2 45.3 14.3 100.3 65.1 12.1 84.5 58.4 9.7 68.2 51.8 17.0 118.7 71.2 14.6 102.6 64.6 12.2 85.7 58.1
16 10.7 85.8 59.8 8.7 69.8 52.7 6.7 53.5 45.8 13.0 103.9 66.7 10.9 87.5 59.6 8.8 70.4 52.7 15.4 123.5 73.3 13.3 106.5 66.2 11.1 89.0 59.3
13 16.1 104.3 78.9 13.3 86.4 71.3 10.6 68.7 64.2 19.2 124.5 86.7 16.3 105.9 79.2 13.4 87.1 72.0 22.4 145.9 93.8 19.5 126.8 86.6 16.5 107.2 79.5
16 14.2 113.6 83.0 11.7 93.3 74.2 9.1 73.1 65.9 17.0 136.3 91.6 14.4 115.4 83.0 11.8 94.0 74.6 20.1 160.5 99.6 17.4 139.0 91.2 14.6 116.9 82.9
30 19 12.7 120.5 86.1 10.4 98.5 76.4 8.0 76.4 67.3 15.3 145.2 95.4 12.9 122.6 85.9 10.5 99.4 76.6 18.1 171.6 104.2 15.6 148.4 94.8 13.1 124.4 85.7
22 11.4 125.8 88.5 9.3 102.6 78.2 7.2 79.0 68.3 13.8 152.0 98.4 11.6 128.1 88.2 9.4 103.5 78.2 16.4 180.2 107.8 14.2 155.7 97.7 11.8 130.2 87.9
25 10.4 129.9 90.3 8.5 105.7 79.5 6.5 81.0 69.1 12.6 157.4 100.8 10.6 132.5 90.0 8.5 106.7 79.5 15.0 187.2 110.8 12.9 161.5 100.0 10.8 134.9 89.6
19 15.9 151.5 110.7 13.1 124.5 99.0 10.3 97.7 88.0 19.1 181.4 122.0 16.1 153.4 110.5 13.2 125.2 99.4 22.4 213.0 132.5 19.4 184.3 121.2 16.3 155.0 110.3
22 14.5 159.4 114.3 11.9 130.4 101.5 9.2 101.4 89.5 17.4 191.6 126.4 14.7 161.7 113.8 11.9 131.2 101.7 20.5 225.8 137.7 17.7 195.1 125.4 14.9 163.6 113.4
40 25 13.3 165.7 117.1 10.8 135.2 103.6 8.4 104.4 90.7 16.0 199.7 129.9 13.5 168.3 116.6 10.9 136.1 103.6 18.9 236.1 142.0 16.3 203.9 128.8 13.6 170.6 116.0
28 12.2 170.8 119.3 9.9 139.0 105.2 7.6 106.9 91.7 14.7 206.4 132.8 12.4 173.8 118.8 10.0 140.1 105.2 17.5 244.4 145.5 15.1 211.1 131.7 12.6 176.4 118.2
LEGEND NOTE: All capacities are given in thousands of Btuh (MBtuh).
DB — Dry Bulb Temperature
EWT — Entering Water Temperature
MBtuh — Btuh in Thousands
SCb — Base Sensible Capacity at Nominal Cfm
TCb — Base Total Capacity at Nominal Cfm
WB — Wet Bulb Temperature
∆T — Change in Water Temperature (F)

42BHC,BVC 4-ROW COOLING CAPACITY (by ∆T)


75 F DB/ 63 F WB 80 F DB/67 F WB 85 F DB/71 F WB
UNIT
SIZE ∆T 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT
42BHC,BVC GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb
10 3.5 17.3 13.6 2.5 12.5 11.7 3.5 17.3 13.6 4.7 23.3 16.0 3.6 17.9 13.8 2.6 12.8 12.0 6.0 30.0 18.5 4.8 24.2 16.2 3.7 18.3 14.0
12 2.5 14.9 12.6 — — — 2.5 14.9 12.6 3.5 20.8 15.0 2.6 15.5 12.9 — — — 4.6 27.7 17.5 3.6 21.7 15.2 2.7 16.0 13.2
06 14 — — — — — — — — — 2.6 18.1 13.9 — — — — — — 3.5 24.8 16.4 2.7 19.0 14.2 — — —
16 — — — — — — — — — — — — — — — — — — 2.7 21.8 15.3 — — — — — —
10 4.3 21.3 17.2 3.0 15.1 15.1 4.3 21.3 17.2 5.7 28.4 20.0 4.4 21.9 17.5 3.1 15.3 15.3 7.3 36.4 22.9 5.8 29.2 20.2 4.5 22.3 17.7
12 3.1 18.6 16.1 2.2 13.3 13.3 3.1 18.6 16.1 4.2 25.5 18.9 3.2 19.3 16.5 2.3 13.7 13.7 5.6 33.5 21.8 4.4 26.4 19.1 3.3 19.8 16.8
08 14 2.3 15.8 15.0 — — — 2.3 15.8 15.0 3.2 22.5 17.7 2.4 16.5 15.5 — — — 4.3 30.2 20.6 3.3 23.4 18.1 2.5 17.2 16.0
16 — — — — — — — — — 2.4 19.3 16.5 — — — — — — 3.4 27.0 19.3 2.5 20.3 17.0 — — —
18 — — — — — — — — — — — — — — — — — — 2.6 23.4 18.1 — — — — — —
10 6.2 30.9 23.5 4.6 23.1 20.3 6.2 30.9 23.5 8.1 40.5 27.3 6.3 31.6 23.7 4.7 23.4 20.6 10.2 51.2 31.1 8.4 41.8 27.4 6.4 32.2 23.9
12 4.7 28.1 22.3 3.4 20.7 19.3 4.7 28.1 22.3 6.2 37.3 26.0 4.8 28.8 22.6 3.5 21.0 19.7 8.0 47.9 29.8 6.4 38.5 26.1 4.9 29.4 22.9
10 14 3.6 25.2 21.1 2.5 17.6 17.6 3.6 25.2 21.1 4.9 34.3 24.8 3.7 25.9 21.5 2.6 18.1 18.1 6.4 44.7 28.5 5.0 35.4 25.0 3.8 26.5 21.9
16 2.8 22.0 19.8 — — — 2.8 22.0 19.8 3.9 31.0 23.5 2.9 22.9 20.4 — — — 5.2 41.2 27.2 4.0 32.1 23.8 2.9 23.5 20.9
18 — — — — — — — — — 3.1 27.5 22.1 — — — — — — 4.2 37.7 25.8 3.2 28.6 22.6 2.2 19.5 19.5
10 7.0 34.8 27.0 5.2 26.2 23.4 7.0 34.8 27.0 9.1 45.4 31.2 7.1 35.5 27.2 5.3 26.5 23.8 11.5 57.5 35.5 9.3 46.8 31.3 7.2 36.1 27.4
12 5.3 31.8 25.7 3.9 23.6 22.4 5.3 31.8 25.7 7.0 41.9 29.8 5.4 32.5 26.0 3.8 22.9 22.9 9.0 53.8 34.0 7.2 43.1 29.9 5.5 33.0 26.3
12 14 4.1 28.6 24.4 2.9 20.4 20.4 4.1 28.6 24.4 5.5 38.6 28.4 4.2 29.4 24.9 3.0 20.9 20.9 7.2 50.1 32.6 5.7 39.7 28.7 4.3 29.9 25.3
16 3.2 25.3 23.0 2.2 17.8 17.8 3.2 25.3 23.0 4.4 35.1 27.0 3.3 26.1 23.7 2.3 18.5 18.5 5.8 46.3 31.1 4.5 36.1 27.4 3.4 26.8 24.2
18 2.3 21.0 21.0 — — — 2.3 21.0 21.0 3.5 31.4 25.6 2.4 21.9 21.9 — — — 4.7 42.4 29.7 3.6 32.5 26.2 2.5 22.6 22.6
10 9.1 45.4 35.6 6.8 33.9 30.8 9.1 45.4 35.6 11.9 59.7 41.2 9.3 46.4 35.9 6.9 34.4 31.4 15.2 75.8 47.0 12.3 61.4 41.4 9.5 47.3 36.3
12 6.8 40.9 33.7 4.8 28.9 28.9 6.8 40.9 33.7 9.1 54.7 39.2 7.0 41.9 34.2 4.9 29.5 29.5 11.8 70.6 44.9 9.4 56.3 39.5 7.1 42.8 34.7
16 14 5.1 35.9 31.6 3.6 25.2 25.2 5.1 35.9 31.6 7.1 49.6 37.2 5.3 37.2 32.4 3.7 26.2 26.2 9.3 65.3 42.9 7.3 51.3 37.7 5.5 38.2 33.2
16 3.6 28.9 28.9 — — — 3.6 28.9 28.9 5.5 44.1 35.1 3.8 30.3 30.3 — — — 7.4 59.6 40.7 5.7 45.9 35.8 4.2 33.4 31.6
18 — — — — — — — — — 4.2 38.0 32.8 — — — — — — 6.0 53.7 38.5 4.5 40.1 33.8 — — —
10 11.6 57.9 44.8 8.7 43.7 38.9 11.6 57.9 44.8 15.0 75.2 51.6 11.8 59.0 45.1 8.8 44.1 39.5 19.1 95.4 58.8 15.5 77.6 51.9 12.0 60.0 45.5
12 8.9 53.2 42.8 6.6 39.5 37.2 8.9 53.2 42.8 11.6 69.9 49.4 9.0 54.2 43.3 6.7 40.1 38.0 14.9 89.6 56.5 12.0 71.7 49.7 9.2 55.1 43.8
20 14 6.9 48.1 40.7 4.9 34.2 34.2 6.9 48.1 40.7 9.2 64.6 47.3 7.0 49.3 41.4 5.0 35.0 35.0 11.9 83.4 54.1 9.5 66.3 47.7 7.2 50.2 42.1
16 5.3 42.8 38.5 3.8 30.0 30.0 5.3 42.8 38.5 7.4 59.0 45.1 5.5 44.1 39.5 3.9 31.2 31.2 9.7 77.4 51.8 7.6 60.7 45.7 5.6 45.2 40.4
18 3.9 35.4 35.4 — — — 3.9 35.4 35.4 5.9 53.1 42.8 4.1 36.9 36.9 — — — 7.9 71.3 49.5 6.1 54.8 43.7 4.2 38.0 38.0
10 17.2 85.8 66.9 12.8 64.1 58.0 17.2 85.8 66.9 22.5 112.5 77.6 17.5 87.6 67.6 13.0 65.0 59.1 28.6 142.8 88.4 23.1 115.8 77.8 17.8 89.2 68.2
12 12.9 77.4 63.4 9.1 54.7 54.7 12.9 77.4 63.4 17.2 103.3 73.8 13.2 79.4 64.5 9.3 55.8 55.8 22.1 132.7 84.4 17.7 106.4 74.4 13.5 81.0 65.3
30 14 9.8 68.3 59.7 6.8 47.9 47.9 9.8 68.3 59.7 13.4 94.0 70.1 10.1 70.6 61.2 7.1 49.8 49.8 17.6 123.3 80.7 13.9 97.0 71.0 10.4 72.5 62.5
16 6.9 55.2 55.2 — — — 6.9 55.2 55.2 10.5 84.0 66.2 7.6 61.1 57.7 — — — 14.1 112.9 76.8 10.9 87.2 67.5 7.9 63.5 59.5
18 — — — — — — — — — 8.1 72.8 62.0 — — — — — — 11.3 102.0 72.8 8.5 76.6 63.9 — — —
14 14.7 102.9 84.5 10.4 72.8 72.8 14.7 102.9 84.5 19.5 136.6 98.0 15.0 105.0 85.7 10.6 74.1 74.1 25.1 175.5 112.0 20.0 140.1 98.6 15.2 106.7 86.8
40 16 11.6 92.9 80.4 8.2 65.3 65.3 11.6 92.9 80.4 15.8 126.1 93.9 11.9 95.2 82.1 8.4 67.2 67.2 20.5 163.8 107.5 16.2 129.4 94.7 12.1 97.1 83.5
18 9.1 81.9 76.0 6.1 55.2 55.2 9.1 81.9 76.0 12.8 115.0 89.5 9.4 84.8 78.3 6.5 58.5 58.5 16.9 152.4 103.1 13.1 118.4 90.8 9.7 87.2 80.2
LEGEND NOTE: All capacities are given in thousands of Btuh (MBtuh).
DB — Dry Bulb Temperature
EWT — Entering Water Temperature
MBtuh — Btuh in Thousands
SCb — Base Sensible Capacity at Nominal Cfm
TCb — Base Total Capacity at Nominal Cfm
WB — Wet Bulb Temperature
∆T — Change in Water Temperature (F)

26
42BHC, BVC 6-ROW COOLING CAPACITY (by ∆T)
UNIT 75 F DB/63 F WB 80 F DB/67 F WB 85 F DB/71 F WB
SIZE ∆T 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT
42BHC,BVC GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb
10 4.8 23.8 17.0 3.5 17.7 14.3 2.4 12.0 12.0 6.2 31.0 19.8 4.9 24.5 17.0 3.6 18.0 14.5 7.8 38.8 22.7 6.4 32.2 19.9 5.0 25.1 17.1
12 3.6 21.8 16.1 2.6 15.8 13.5 — — — 4.8 28.9 18.9 3.7 22.4 16.2 2.7 16.1 13.8 6.2 37.0 21.9 5.0 30.0 19.0 3.8 23.0 16.3
06 14 2.8 19.6 15.1 — — — — — — 3.8 26.7 18.0 2.9 20.2 15.3 — — — 5.0 34.7 20.9 4.0 27.8 18.1 3.0 20.7 15.5
16 — — — — — — — — — 3.0 24.3 17.0 2.2 17.8 14.4 — — — 4.0 32.3 19.9 3.2 25.3 17.1 2.3 18.4 14.7
18 — — — — — — — — — 2.4 21.7 15.9 — — — — — — 3.3 29.8 18.9 2.5 22.7 16.2 — — —
10 5.9 29.6 21.6 4.4 22.2 18.4 3.1 15.5 15.5 7.7 38.4 25.1 6.1 30.3 21.7 4.5 22.5 18.6 9.7 48.3 28.6 8.0 39.8 25.1 6.2 31.0 21.7
12 4.5 27.2 20.5 3.3 20.0 17.5 2.3 14.0 14.0 6.0 35.8 23.9 4.6 27.9 20.7 3.4 20.3 17.8 7.6 45.6 27.5 6.2 37.1 24.0 4.7 28.5 20.8
08 14 3.5 24.7 19.4 2.5 17.7 16.6 — — — 4.7 33.2 22.8 3.6 25.3 19.7 2.6 18.1 17.0 6.1 42.9 26.3 4.9 34.3 23.0 3.7 25.8 19.9
16 2.7 21.9 18.3 — — — — — — 3.8 30.4 21.7 2.8 22.6 18.7 — — — 5.0 40.0 25.2 3.9 31.4 21.9 2.9 23.2 19.0
18 — — — — — — — — — 3.0 27.4 20.5 2.2 19.9 17.6 — — — 4.1 37.0 24.0 3.2 28.4 20.8 2.3 20.5 18.1
10 8.1 40.6 28.7 6.2 30.9 24.4 4.4 22.0 20.7 10.4 52.2 33.3 8.3 41.7 28.7 6.2 31.2 24.5 13.0 65.1 37.9 10.8 54.2 33.3 8.5 42.6 28.7
12 6.4 38.1 27.5 4.7 28.5 23.4 3.3 19.7 19.7 8.3 49.5 32.1 6.5 39.0 27.6 4.8 28.8 23.6 10.4 62.4 36.7 8.5 51.1 32.0 6.6 39.8 27.7
10 14 5.1 35.4 26.3 3.7 26.0 22.4 2.6 17.9 17.9 6.7 46.7 30.8 5.2 36.2 26.5 3.8 26.3 22.7 8.5 59.4 35.4 6.9 48.1 30.8 5.3 36.9 26.6
16 4.1 32.5 25.1 2.9 23.3 21.3 — — — 5.5 43.7 29.6 4.2 33.3 25.3 3.0 23.7 21.7 7.0 56.2 34.1 5.6 45.0 29.6 4.2 33.9 25.5
18 3.3 29.5 23.8 2.2 19.9 19.9 — — — 4.5 40.6 28.2 3.4 30.2 24.1 2.3 20.4 20.4 5.9 53.0 32.7 4.6 41.7 28.4 3.4 30.8 24.5
10 9.3 46.3 33.2 7.0 35.2 28.4 4.9 24.4 24.4 11.9 59.6 38.4 9.5 47.4 33.2 7.1 35.5 28.5 14.9 74.3 43.7 12.3 61.7 38.4 9.7 48.4 33.2
12 7.2 43.5 31.9 5.4 32.6 27.3 3.8 22.8 22.8 9.4 56.3 37.0 7.4 44.3 32.0 5.5 32.8 27.5 11.8 71.1 42.3 9.7 58.0 36.9 7.5 45.1 32.1
12 14 5.8 40.4 30.6 4.3 29.8 26.1 3.0 20.9 20.9 7.6 53.0 35.6 5.9 41.2 30.7 4.3 30.1 26.5 9.7 67.6 40.8 7.8 54.6 35.6 6.0 41.9 30.9
16 4.7 37.2 29.2 3.4 27.0 25.0 2.3 18.4 18.4 6.2 49.7 34.2 4.7 38.0 29.5 3.4 27.4 25.5 8.0 63.7 39.2 6.4 51.1 34.3 4.8 38.6 29.7
18 3.8 33.9 27.8 2.6 23.3 23.3 — — — 5.1 46.2 32.7 3.8 34.6 28.2 2.6 23.8 23.8 6.7 60.1 37.8 5.3 47.4 32.9 3.9 35.2 28.6
10 12.2 61.2 44.0 9.3 46.4 37.6 6.4 32.1 32.1 15.7 78.7 50.9 12.5 62.6 44.1 9.4 46.8 37.8 19.7 98.5 58.0 16.3 81.5 50.9 12.8 63.9 44.1
12 9.5 57.0 42.1 7.1 42.5 36.0 4.9 29.7 29.7 12.4 74.2 48.9 9.7 58.3 42.3 7.2 42.9 36.4 15.6 93.9 56.0 12.8 76.5 48.9 9.9 59.4 42.5
16 14 7.5 52.6 40.2 5.5 38.4 34.3 3.8 26.6 26.6 10.0 69.7 47.0 7.7 53.8 40.5 5.6 39.0 34.9 12.7 89.1 54.0 10.3 71.8 47.1 7.8 54.8 40.8
16 6.0 47.8 38.2 4.1 32.6 32.6 — — — 8.1 64.8 45.0 6.1 49.0 38.7 4.2 33.4 33.4 10.5 83.7 51.8 8.3 66.8 45.2 6.3 50.0 39.2
18 4.7 42.7 36.0 — — — — — — 6.6 59.6 42.9 4.9 44.0 36.8 3.3 29.8 29.8 8.7 78.6 49.7 6.8 61.5 43.2 5.0 45.1 37.5
10 15.4 76.9 55.1 11.7 58.6 47.1 8.1 40.6 40.6 19.8 99.0 63.8 15.7 78.7 55.2 11.8 59.0 47.4 24.7 123.3 72.5 20.4 102.1 63.6 16.1 80.3 55.2
12 12.0 72.3 53.0 9.1 54.3 45.4 6.3 38.1 38.1 15.6 93.6 61.5 12.3 73.7 53.2 9.1 54.7 45.8 19.7 117.9 70.2 16.0 96.3 61.3 12.5 75.0 53.3
20 14 9.6 67.4 50.9 7.1 49.9 43.6 5.0 35.0 35.0 12.6 88.2 59.2 9.8 68.7 51.2 7.2 50.4 44.2 16.0 112.0 67.7 13.0 90.7 59.2 10.0 69.7 51.4
16 7.8 62.3 48.7 5.7 45.3 41.7 3.9 31.0 31.0 10.4 82.9 56.9 7.9 63.5 49.1 5.7 45.9 42.6 13.3 106.1 65.3 10.6 85.1 57.0 8.1 64.4 49.5
18 6.3 56.9 46.4 4.3 39.1 39.1 — — — 8.6 77.3 54.6 6.5 58.1 47.1 4.4 40.0 40.0 11.1 100.2 62.9 8.8 79.2 54.8 6.6 59.1 47.6
10 23.0 115.1 82.6 17.5 87.3 70.6 12.1 60.5 60.5 29.7 148.5 95.8 23.6 117.8 82.8 17.6 88.1 71.1 37.0 185.2 109.0 30.6 153.2 95.6 24.1 120.3 82.9
12 17.9 107.5 79.3 13.4 80.2 67.6 9.3 56.0 56.0 23.3 139.8 92.1 18.3 109.9 79.6 13.5 81.0 68.4 29.3 176.0 105.0 24.0 144.1 92.0 18.6 111.9 79.8
30 14 14.2 99.3 75.7 10.4 72.6 64.6 7.2 50.3 50.3 18.8 131.3 88.4 14.5 101.5 76.3 10.5 73.7 65.7 23.9 167.6 101.5 19.3 135.3 88.6 14.8 103.3 76.8
16 11.3 90.6 72.0 7.7 61.8 61.8 — — — 15.3 122.4 84.7 11.6 92.8 72.9 7.9 63.2 63.2 19.7 157.8 97.5 15.7 126.0 85.0 11.8 94.5 73.7
18 9.0 81.1 68.0 6.1 54.6 54.6 — — — 12.5 112.9 80.8 9.3 83.5 69.4 6.3 56.7 56.7 16.5 148.3 93.6 12.9 116.2 81.4 9.5 85.5 70.6
10 31.8 158.9 112.7 24.3 121.4 96.3 17.4 87.2 82.3 40.8 204.0 130.5 32.5 162.6 112.7 24.5 122.3 96.7 — — — 42.2 210.9 130.2 33.2 166.2 112.7
12 25.0 150.0 108.6 18.9 113.1 92.8 13.1 78.8 78.8 32.3 193.6 125.9 25.5 153.0 108.8 19.0 113.9 93.5 40.6 243.4 143.8 33.3 199.6 125.7 26.0 155.7 108.9
40 14 20.1 140.7 104.6 14.9 104.6 89.3 10.4 73.1 73.1 26.2 183.1 121.4 20.5 143.3 104.9 15.1 105.4 90.4 33.2 232.4 139.1 26.9 188.5 121.3 20.8 145.4 105.1
16 16.4 131.0 100.3 12.0 95.7 85.7 8.2 66.0 66.0 21.6 172.9 117.0 16.7 133.2 100.9 12.1 96.8 87.2 27.6 220.5 134.1 22.2 177.4 117.0 16.9 135.1 101.5
18 13.4 120.7 96.0 9.6 86.3 82.0 6.3 56.3 56.3 18.0 162.2 112.6 13.7 122.9 96.9 9.3 84.1 84.1 23.2 208.8 129.3 18.5 166.1 112.7 13.8 124.6 97.8
LEGEND NOTE: All capacities are given in thousands of Btuh (MBtuh).
DB — Dry Bulb Temperature TCb — Base Total Capacity at Nominal Cfm
EWT — Entering Water Temperature WB — Wet Bulb Temperature
MBtuh — Btuh in Thousands ∆T — Change in Water Temperature (F)
SCb — Base Sensible Capacity at Nominal Cfm

42BHC, BVC 8-ROW COOLING CAPACITY (by ∆T)


UNIT 75 F DB/63 F WB 80 F DB/67 F WB 85 F DB/71 F WB
SIZE ∆T 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT
42BHC,BVC GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb
10 5.2 25.8 18.0 3.8 19.0 15.0 — — — 6.8 33.8 21.2 5.3 26.7 18.1 3.9 19.4 15.2 8.5 42.4 24.4 7.1 35.3 21.3 5.5 27.6 18.2
12 3.9 23.3 16.9 — — — — — — 5.2 31.4 20.2 4.0 24.2 17.1 — — — 6.7 40.2 23.4 5.5 32.8 20.3 4.2 25.0 17.2
06 14 — — — — — — — — — 4.1 28.7 19.0 — — — — — — 5.4 37.6 22.3 4.3 30.1 19.2 — — —
16 — — — — — — — — — — — — — — — — — — 4.4 34.8 21.1 3.4 26.9 17.9 — — —
18 — — — — — — — — — — — — — — — — — — 3.5 31.6 19.8 — — — — — —
10 6.5 32.7 23.2 4.9 24.3 19.6 3.3 16.5 16.5 8.5 42.6 27.2 6.7 33.7 23.3 4.9 24.7 19.8 10.7 53.4 31.1 8.9 44.3 27.2 6.9 34.7 23.4
12 5.0 29.8 21.9 3.6 21.4 18.4 — — — 6.6 39.7 25.9 5.1 30.7 22.1 3.3 19.9 19.9 8.4 50.7 29.9 6.9 41.3 26.0 5.3 31.5 22.3
08 14 3.8 26.4 20.5 — — — — — — 5.2 36.5 24.5 3.9 27.4 20.8 — — — 6.8 47.5 28.5 5.4 38.0 24.7 4.0 28.2 21.1
16 — — — — — — — — — 4.1 32.9 23.0 — — — — — — 5.5 44.0 27.1 4.3 34.3 23.3 — — —
18 — — — — — — — — — — — — — — — — — — 4.5 40.3 25.6 3.4 30.3 21.8 — — —
10 9.0 45.0 31.0 6.8 34.1 26.1 4.5 22.5 22.5 11.5 57.7 36.0 9.3 46.4 31.0 6.9 34.6 26.2 14.3 71.4 41.0 12.0 60.1 36.0 9.5 47.6 31.0
12 7.0 42.1 29.6 5.2 31.1 24.8 3.5 20.9 20.9 9.1 54.8 34.7 7.2 43.3 29.7 5.3 31.6 25.0 11.5 68.9 39.9 9.5 56.9 34.7 7.4 44.4 29.7
10 14 5.5 38.8 28.1 4.0 27.9 23.5 — — — 7.4 51.7 33.3 5.7 39.9 28.3 3.6 25.5 25.5 9.4 65.8 38.5 7.7 53.7 33.3 5.8 40.9 28.4
16 4.4 35.1 26.5 — — — — — — 6.0 48.2 31.8 4.5 36.2 26.8 — — — 7.8 62.3 36.9 6.2 50.0 31.9 4.6 37.2 27.1
18 3.4 31.0 24.7 — — — — — — 4.9 44.3 30.1 3.6 32.2 25.2 — — — 6.5 58.7 35.4 5.1 46.0 30.3 3.7 33.2 25.7
10 10.4 51.9 36.1 7.9 39.4 30.6 5.3 26.4 26.4 13.3 66.6 42.0 10.7 53.3 36.1 8.0 39.9 30.7 16.5 82.5 47.7 13.8 69.1 41.9 10.9 54.7 36.1
12 8.1 48.6 34.6 6.0 36.1 29.2 4.1 24.6 24.6 10.5 63.1 40.4 8.3 49.9 34.7 6.1 36.5 29.4 13.2 79.3 46.2 10.9 65.4 40.3 8.5 51.0 34.7
12 14 6.4 44.9 32.9 4.6 32.5 27.7 — — — 8.5 59.5 38.8 6.6 46.1 33.1 4.7 33.1 28.1 10.8 75.6 44.6 8.8 61.6 38.8 6.7 47.1 33.3
16 5.1 40.9 31.2 3.6 28.8 26.2 — — — 6.9 55.6 37.1 5.2 42.0 31.5 3.5 27.8 27.8 9.0 71.6 42.9 7.2 57.5 37.2 5.4 42.9 31.8
18 4.0 36.4 29.3 — — — — — — 5.7 51.2 35.2 4.2 37.6 29.8 — — — 7.5 67.5 41.2 5.9 53.0 35.5 4.3 38.6 30.3
10 13.9 69.4 48.2 10.5 52.6 40.8 7.0 35.2 35.2 17.8 89.0 56.0 14.3 71.3 48.3 10.7 53.3 41.0 22.1 110.6 63.9 18.5 92.5 56.0 14.6 73.1 48.3
12 10.8 64.9 46.2 8.0 48.1 38.9 5.4 32.6 32.6 14.1 84.4 54.0 11.1 66.7 46.3 8.1 48.8 39.3 17.7 106.0 61.8 14.6 87.5 53.9 11.4 68.2 46.4
16 14 8.6 59.9 43.9 6.2 43.2 36.9 — — — 11.4 79.6 51.8 8.8 61.5 44.2 6.3 44.0 37.5 14.5 101.2 59.7 11.8 82.4 51.9 9.0 62.9 44.4
16 6.8 54.2 41.5 4.7 37.7 34.6 — — — 9.3 74.2 49.5 7.0 55.9 42.0 4.6 36.7 36.7 12.0 95.8 57.4 9.6 76.8 49.7 7.2 57.2 42.4
18 5.3 47.8 38.8 — — — — — — 7.6 68.2 47.0 5.5 49.7 39.6 — — — 10.0 90.2 55.0 7.8 70.6 47.3 5.7 51.2 40.3
10 17.5 87.6 60.6 13.4 66.9 51.4 9.5 47.4 43.4 22.4 111.8 70.3 18.0 89.9 60.6 13.5 67.6 51.6 27.7 138.7 80.0 23.2 116.2 70.2 18.4 92.1 60.5
12 13.8 82.7 58.4 10.3 62.0 49.3 7.0 42.1 42.1 17.8 106.6 67.9 14.1 84.7 58.4 10.4 62.6 49.6 22.2 133.4 77.6 18.4 110.3 67.7 14.4 86.5 58.4
20 14 11.0 77.3 56.0 8.1 56.7 47.2 5.5 38.8 38.8 14.5 101.2 65.5 11.3 79.0 56.1 8.2 57.4 47.7 18.3 127.8 75.1 14.9 104.5 65.4 11.5 80.6 56.2
16 8.9 71.4 53.4 6.4 51.2 44.9 — — — 11.9 95.4 63.0 9.1 73.0 53.7 6.5 52.1 45.7 15.2 121.6 72.5 12.3 98.4 62.9 9.3 74.3 53.9
18 7.2 65.0 50.6 5.0 45.1 42.5 — — — 9.9 89.0 60.2 7.4 66.6 51.2 5.2 46.4 43.6 12.8 115.5 69.9 10.2 91.7 60.4 7.5 67.9 51.7
10 26.3 131.4 91.0 20.0 100.0 77.1 13.4 66.8 66.8 33.6 168.0 105.5 27.0 135.0 91.0 20.2 101.2 77.4 41.7 208.7 120.4 34.9 174.6 105.4 27.7 138.4 90.9
12 20.6 123.5 87.4 15.3 91.9 73.6 10.4 62.3 62.3 26.6 159.8 101.9 21.1 126.6 87.6 15.5 93.1 74.2 33.4 200.5 116.6 27.6 165.6 101.7 21.6 129.5 87.6
30 14 16.4 114.5 83.4 11.9 83.2 70.0 8.0 56.4 56.4 21.6 151.2 98.1 16.8 117.4 83.8 12.1 84.5 71.0 27.4 191.7 112.7 22.4 156.5 98.0 17.1 120.0 84.1
16 13.1 104.6 79.0 9.2 73.7 66.2 — — — 17.7 141.7 93.9 13.4 107.5 79.8 8.8 70.6 70.6 22.7 182.0 108.5 18.3 146.5 94.1 13.7 109.8 80.4
18 10.4 93.6 74.3 — — — — — — 14.6 131.1 89.4 10.7 96.7 75.6 — — — 19.1 171.9 104.3 15.1 135.5 89.9 11.0 99.1 76.6
10 36.1 180.6 123.9 27.7 138.7 105.1 19.7 98.7 88.4 46.0 230.1 143.5 37.1 185.6 123.8 28.0 140.2 105.2 56.9 284.6 163.3 47.8 238.9 143.1 38.1 190.4 123.5
12 28.6 171.7 119.8 21.6 129.7 101.2 14.6 87.5 87.5 36.7 220.3 139.2 29.3 175.8 119.7 21.8 130.8 101.6 45.7 274.2 158.6 38.0 228.2 138.7 29.9 179.6 119.4
40 14 23.1 161.9 115.4 17.1 120.1 97.2 11.7 81.8 81.8 30.0 210.2 134.5 23.6 165.5 115.4 17.3 121.1 97.9 37.7 264.2 154.1 31.0 217.1 134.1 24.1 168.5 115.3
16 18.9 151.2 110.5 13.7 109.8 92.9 9.3 74.3 74.3 24.9 199.6 129.9 19.3 154.3 110.8 13.9 111.1 94.1 31.6 253.0 149.2 25.7 205.7 129.6 19.6 156.9 111.0
18 15.5 139.5 105.4 11.0 98.8 88.5 — — — 20.9 188.0 124.9 15.8 142.4 106.1 11.2 100.6 90.2 26.8 241.3 144.2 21.5 193.4 124.7 16.1 144.8 106.6
LEGEND
DB — Dry Bulb Temperature TCb — Base Total Capacity at Nominal Cfm
EWT — Entering Water Temperature WB — Wet Bulb Temperature
MBtuh — Btuh in Thousands ∆T — Change in Water Temperature (F)
SCb — Base Sensible Capacity at Nominal Cfm

NOTE: All capacities are given in thousands of Btuh (MBtuh).

27
Performance data (cont)
DIRECT EXPANSION (DX) BASE COOLING CAPACITIES* (MBtuh) — 4-ROW COIL
UNIT CONNECTION R-22 ENTERING-AIR TEMPERATURE (F)—DRY BULB/WET BULB
SIZE SIZE(in.) CFM SUCTION 75/63 80/63 75/67 80/67 80/71 85/71
42BHC,BVC Liquid Suction TEMP(F) TH SH TH SH TH SH TH SH TH SH TH SH
40 8.6 7.8 9.9 9.9 13.5 7.8 13.5 9.8 18.7 9.8 18.8 11.7
400 45 5.4 5.4 7.8 7.8 7.2 5.5 8.4 7.9 13.5 7.8 13.6 9.8
50 2.3 2.3 5.4 5.4 2.3 2.3 5.4 5.4 6.6 5.5 7.8 7.8
40 13.3 12.0 15.4 15.4 19.5 11.5 19.5 14.5 26.9 14.2 26.6 17.1
06 3/8 5/8 600 45 9.0 9.0 12.3 12.3 11.5 8.5 13.2 12.1 19.4 11.4 19.7 14.5
50 5.0 5.0 8.9 8.9 5.0 5.0 8.9 8.9 11.0 8.6 13.0 12.2
40 15.3 13.8 17.7 17.7 21.9 13.1 22.0 16.5 30.1 16.1 29.8 19.4
700 45 10.4 10.4 14.2 14.2 13.3 9.9 15.1 13.9 21.9 13.0 22.2 16.6
50 6.1 6.1 10.4 10.4 6.1 6.1 10.4 10.4 12.7 9.9 15.0 14.1
40 13.3 12.0 15.4 15.4 19.5 11.5 19.5 14.5 26.9 14.2 26.6 17.1
600 45 9.0 9.0 12.3 12.3 11.5 8.5 13.2 12.1 19.4 11.4 19.7 14.5
50 5.0 5.0 8.9 8.9 5.0 5.0 8.9 8.9 11.0 8.6 13.0 12.2
40 17.0 15.4 19.8 19.8 24.3 14.6 24.2 18.4 33.0 17.7 32.4 21.4
08 3/8 5/8 800 45 11.8 11.8 15.9 15.9 14.9 11.1 16.8 15.6 24.1 14.5 24.4 18.4
50 7.1 7.1 11.7 11.7 7.1 7.1 11.7 11.7 14.2 11.2 16.7 15.8
40 18.4 16.9 21.5 21.5 26.3 15.9 26.2 20.1 35.5 19.2 35.3 23.4
900 45 12.9 12.9 17.3 17.3 16.2 12.1 18.3 17.1 26.4 15.9 26.3 20.1
50 7.9 7.9 12.9 12.9 7.9 7.9 12.9 12.9 15.6 12.3 17.3 17.3
40 24.7 18.9 23.9 23.9 33.2 18.3 32.9 22.2 42.0 21.5 41.4 25.2
800 45 17.2 15.8 20.0 20.0 24.9 14.9 24.9 18.9 33.9 18.2 33.6 22.1
50 11.9 11.9 16.0 16.0 15.1 11.3 17.0 15.9 24.6 14.8 24.9 18.9
40 29.1 22.7 29.1 29.1 38.8 21.7 38.6 26.5 48.8 25.3 48.4 30.0
10 1/2 7/8 1000 45 20.8 19.3 24.4 24.4 29.2 17.9 29.3 22.8 39.5 21.6 39.1 26.4
50 14.8 14.8 19.7 19.7 18.1 13.8 19.7 19.7 29.0 17.8 29.3 22.8
40 31.0 24.5 31.4 31.4 41.2 23.2 40.8 28.4 51.7 26.9 51.0 32.0
1100 45 22.3 20.9 26.4 26.4 31.1 19.2 31.2 24.6 41.9 23.1 41.6 28.4
50 16.0 16.0 21.2 21.2 19.4 14.9 21.2 21.2 30.8 19.2 31.2 24.6
40 29.1 22.7 29.1 29.1 38.8 21.7 38.6 26.5 48.8 25.3 48.4 30.0
1000 45 20.8 19.3 24.4 24.4 29.2 17.9 29.3 22.8 39.5 21.6 39.1 26.4
50 14.8 14.8 19.7 19.7 18.1 13.8 19.7 19.7 29.0 17.8 29.3 22.8
40 32.8 26.1 33.5 33.5 43.4 24.6 42.8 30.1 54.3 28.5 54.2 34.2
12 1/2 7/8 1200 45 23.7 22.4 28.1 28.1 32.7 20.4 32.9 26.2 44.0 24.5 43.5 30.1
50 17.1 17.1 22.7 22.7 20.6 16.0 22.7 22.7 32.5 20.4 32.9 26.3
40 34.4 27.6 35.3 35.3 45.4 25.9 45.1 31.9 56.7 29.9 56.6 36.0
1300 45 24.0 24.0 29.7 29.7 34.3 21.5 34.5 27.7 45.9 25.8 45.6 31.8
50 18.1 18.1 24.0 24.0 21.8 16.9 24.0 24.0 34.0 21.5 34.4 27.8
40 38.2 30.7 39.4 39.4 52.0 29.4 51.8 36.2 66.5 34.6 65.9 41.2
1400 45 26.0 26.0 32.8 32.8 37.9 23.8 38.3 30.8 53.0 29.4 52.6 36.1
50 18.9 18.9 25.9 25.9 21.8 18.0 25.9 25.9 37.2 23.7 38.3 31.0
40 41.9 34.1 43.7 43.7 56.7 32.3 56.0 39.7 72.3 37.9 71.8 45.4
16 5/8 7/8 1600 45 28.9 28.9 36.4 36.4 41.5 26.4 42.0 34.2 57.6 32.3 57.2 39.8
50 21.1 21.1 28.9 28.9 24.2 20.1 28.9 28.9 40.5 26.3 41.8 34.4
40 45.1 37.1 47.3 47.3 60.8 34.9 60.1 43.1 77.3 40.8 77.0 49.2
1800 45 31.4 31.4 39.5 39.5 44.6 28.6 45.1 37.3 61.6 34.9 61.2 43.2
50 23.0 23.0 31.4 31.4 26.3 22.0 31.4 31.4 44.0 28.7 44.9 37.5
40 48.8 39.2 50.3 50.3 65.9 37.3 65.4 45.8 83.7 43.7 83.2 52.2
1800 45 33.4 33.4 41.9 41.9 48.5 30.5 48.9 39.3 67.0 37.2 66.5 45.8
50 24.5 24.5 33.4 33.4 28.8 23.3 33.4 33.4 47.5 30.3 48.8 39.5
40 52.2 42.4 54.3 54.3 70.3 40.1 69.7 49.4 89.1 46.8 88.5 56.1
20 5/8 7/8 2000 45 36.2 36.2 45.3 45.3 51.9 32.9 52.4 42.6 71.3 40.0 70.6 49.3
50 26.6 26.6 36.1 36.1 31.0 25.3 36.1 36.1 51.2 32.9 52.2 42.8
40 55.3 45.3 57.8 57.8 74.2 42.6 73.6 52.6 93.9 49.6 93.2 59.6
2200 45 38.6 38.6 48.3 48.3 54.9 35.1 55.4 45.5 75.1 42.5 74.3 52.5
50 28.5 28.5 38.5 38.5 33.0 27.2 38.5 38.5 54.1 35.1 55.2 45.8
40 72.3 57.6 73.9 73.9 98.0 55.2 96.5 67.3 124.8 64.8 122.5 76.6
2600 45 49.0 49.0 61.6 61.6 72.0 44.9 72.6 57.8 99.7 55.1 98.6 67.3
50 35.9 35.9 49.0 49.0 42.3 34.1 49.0 49.0 71.0 44.8 72.5 58.0
40 76.1 61.1 78.4 78.4 102.8 58.2 102.0 71.5 130.8 68.2 129.8 81.4
2800 45 52.1 52.1 65.4 65.4 75.8 47.5 76.4 61.3 104.6 58.1 103.8 71.4
5/ 50 38.2 38.2 52.0 52.0 44.8 36.3 52.0 52.0 74.0 47.2 76.2 61.6
30 8 11/8
40 79.7 64.4 82.5 82.5 107.4 61.1 106.0 74.9 136.3 71.4 134.3 85.0
3000 45 54.9 54.9 68.9 68.9 79.2 50.0 79.9 64.7 109.0 60.9 107.7 74.9
50 40.4 40.4 54.9 54.9 47.2 38.4 54.9 54.9 77.7 49.8 79.7 64.9
40 83.0 67.5 86.3 86.3 111.6 63.7 110.9 78.7 141.5 74.4 141.0 89.4
3200 45 57.6 57.6 72.1 72.1 82.4 52.3 83.2 67.8 113.2 63.6 112.3 78.5
50 42.4 42.4 57.5 57.5 49.2 40.3 57.5 57.5 81.3 52.4 83.0 68.1
40 110.1 84.0 107.6 107.6 141.6 78.8 141.1 96.2 173.7 90.0 173.3 107.4
3600 45 82.1 72.3 91.7 91.7 111.1 66.5 110.8 84.0 143.8 78.3 143.3 95.7
50 58.8 58.8 75.4 75.4 76.7 53.6 81.4 72.8 110.8 66.3 111.1 84.0
40 113.6 87.3 112.1 112.1 145.9 81.6 144.1 99.3 178.8 93.0 178.3 111.3
3800 45 85.1 75.4 95.5 95.5 114.6 69.0 114.5 87.4 148.0 81.1 146.2 98.8
7/ 50 61.3 61.3 78.5 78.5 79.2 55.8 84.4 76.0 114.2 68.8 114.7 87.4
40 8 11/8
40 117.1 90.5 116.2 116.2 150.0 84.3 148.7 103.0 183.5 95.9 183.0 115.0
4000 45 87.9 78.4 99.0 99.0 117.8 71.4 117.8 90.6 151.9 83.7 150.5 102.4
50 63.7 63.7 81.5 81.5 81.7 57.9 87.1 79.1 117.3 71.2 118.0 90.7
40 120.4 93.6 120.1 120.1 153.8 86.8 153.0 106.5 187.9 98.6 187.4 118.5
4200 45 90.5 81.3 102.4 102.4 120.9 73.6 121.0 93.7 155.6 86.2 154.5 105.9
50 66.0 66.0 84.3 84.3 83.9 59.9 89.8 82.0 120.2 73.5 121.1 93.8
LEGEND *Capacity based on R-22 refrigerant at 105 F liquid temperature and 10 F
MBtuh — Capacity (Btuh in thousands) superheat.
SH — Sensible Heat
TH — Total Heat

28
DIRECT EXPANSION (DX) BASE COOLING CAPACITIES* (MBtuh) — 6-ROW COIL
UNIT CONNECTION R-22 ENTERING AIR TEMPERATURE (F) — DRY BULB/WET BULB
SIZE SIZE (in.) CFM SUCTION 75/63 80/63 75/67 80/67 80/71 85/71
42BHC,BVC Liquid Suction TEMP (F) TH SH TH SH TH SH TH SH TH SH TH SH
40 15.4 11.1 13.6 13.6 20.8 11.1 20.8 13.2 26.4 13.2 26.3 15.3
400 45 9.1 9.1 11.4 11.4 15.6 8.9 15.6 11.0 21.3 11.0 21.3 13.1
50 6.7 6.7 9.1 9.1 9.3 6.5 10.2 8.9 15.7 8.9 15.7 11.0
40 22.1 16.2 20.6 20.6 29.3 15.9 29.4 19.1 37.2 18.7 37.0 21.9
06 3/8 5/8 600 45 14.0 14.0 17.3 17.3 22.3 12.9 22.4 16.2 30.2 15.8 30.2 19.0
50 10.5 10.5 14.0 14.0 14.0 9.8 15.4 13.5 22.3 12.9 22.6 16.2
40 25.1 18.6 23.7 23.7 33.0 18.0 33.0 21.7 41.8 21.1 41.5 24.8
700 45 17.8 15.5 20.0 20.0 25.1 14.7 25.3 18.5 33.6 17.8 33.8 21.6
50 12.1 12.1 16.1 16.1 15.9 11.3 17.6 15.6 25.1 14.6 25.5 18.5
40 22.1 16.2 20.6 20.6 29.3 15.9 29.4 19.1 37.2 18.7 37.0 21.9
600 45 14.0 14.0 17.3 17.3 22.3 12.9 22.4 16.2 30.2 15.8 30.2 19.0
50 10.5 10.5 14.0 14.0 14.0 9.8 15.4 13.5 22.3 12.9 22.6 16.2
40 27.7 20.7 26.6 26.6 36.5 20.0 36.3 24.1 45.8 23.3 45.5 27.4
08 3/8 5/8 800 45 19.8 17.4 22.4 22.4 27.5 16.3 27.9 20.7 37.0 19.7 37.1 24.0
50 13.7 13.7 18.1 18.1 17.7 12.6 19.6 17.5 27.7 16.3 28.1 20.7
40 30.0 22.7 29.1 29.1 39.5 21.8 39.3 26.4 49.4 25.3 49.0 29.8
900 45 21.6 19.2 24.6 24.6 30.0 17.9 30.3 22.7 40.2 21.6 40.0 26.2
50 15.0 15.0 19.9 19.9 19.3 13.9 21.4 19.4 29.8 17.8 30.4 22.7
40 33.3 23.3 29.3 29.3 42.4 22.6 42.2 26.9 51.8 25.9 51.5 30.1
800 45 25.1 19.7 25.1 25.1 34.0 19.0 33.8 23.2 43.5 22.4 43.1 26.5
50 16.6 16.6 20.9 20.9 24.5 15.2 25.1 19.7 34.0 18.7 34.3 23.1
40 39.1 28.0 35.7 35.7 49.4 26.7 49.0 31.8 59.9 30.3 59.6 35.5
10 1/2 7/8 1000 45 29.8 23.9 30.7 30.7 39.6 22.5 39.6 27.9 50.3 26.3 49.9 31.5
50 20.3 20.3 25.5 25.5 28.7 18.2 29.7 24.0 39.5 22.2 39.9 27.7
40 41.6 30.1 38.7 38.7 52.3 28.4 52.0 34.2 63.3 32.2 62.6 37.8
1100 45 31.9 25.9 33.2 33.2 42.0 24.1 42.1 30.0 53.1 28.1 52.9 33.8
50 22.0 22.0 27.6 27.6 30.4 19.6 31.7 25.9 41.9 23.8 42.3 29.8
40 39.1 28.0 35.7 35.7 49.4 26.7 49.0 31.8 59.9 30.3 59.6 35.5
1000 45 29.8 23.9 30.7 30.7 39.6 22.5 39.6 27.9 50.3 26.3 49.9 31.5
50 20.3 20.3 25.5 25.5 28.7 18.2 29.7 24.0 39.5 22.2 39.9 27.7
40 43.9 32.1 41.4 41.4 54.9 30.1 54.7 36.3 66.3 33.9 65.8 40.1
12 1/2 7/8 1200 45 33.7 27.7 35.5 35.5 44.1 25.6 44.3 32.0 55.6 29.7 55.5 36.0
50 23.6 23.6 29.6 29.6 32.0 20.9 33.5 27.8 44.0 25.3 44.5 31.8
40 46.0 34.0 43.8 43.8 57.3 31.6 57.1 38.3 68.9 35.5 68.8 42.3
1300 45 35.4 29.5 37.7 37.7 46.0 26.9 46.3 33.9 57.9 31.2 57.8 37.9
50 25.1 25.1 31.4 31.4 33.5 22.1 35.2 29.6 45.8 26.7 46.4 33.7
40 53.9 38.8 49.4 49.4 69.0 37.3 68.6 44.6 84.6 42.7 83.7 49.8
1400 45 40.4 32.9 42.2 42.2 54.6 31.2 54.6 38.6 70.6 36.9 70.1 44.2
50 27.5 27.5 34.9 34.9 38.6 24.9 40.2 33.0 54.7 30.9 55.2 38.5
40 59.0 43.0 55.1 55.1 75.1 40.9 74.5 49.1 91.8 46.7 91.5 55.0
16 5/8 7/8 1600 45 44.4 36.8 47.1 47.1 59.6 34.4 59.7 42.9 76.5 40.5 76.1 48.8
50 30.7 30.7 39.0 39.0 42.1 27.7 44.2 36.9 59.4 34.0 60.1 42.7
40 63.5 46.9 60.2 60.2 80.4 44.1 80.0 53.3 97.9 50.2 97.5 59.4
1800 45 48.0 40.3 51.5 51.5 63.8 37.3 64.1 46.8 81.7 43.7 81.2 52.9
50 33.6 33.6 42.6 42.6 45.3 30.2 47.7 40.5 63.4 36.9 64.3 46.6
40 68.0 49.2 62.9 62.9 86.5 46.9 85.9 56.2 105.6 53.6 105.3 63.0
1800 45 51.3 42.0 53.8 53.8 68.8 39.5 68.8 49.0 88.2 46.4 87.9 55.9
50 35.3 35.3 44.6 44.6 48.8 31.7 51.1 42.1 68.7 39.0 69.4 48.8
40 72.7 53.2 68.3 68.3 92.1 50.3 91.8 60.7 112.2 57.2 111.5 67.5
20 5/8 7/8 2000 45 55.1 45.7 58.5 58.5 73.3 42.5 73.5 53.1 93.7 49.8 93.4 60.2
50 38.4 38.4 48.5 48.5 52.2 34.4 54.8 45.8 72.9 42.0 73.9 52.9
40 77.0 57.0 73.2 73.2 97.1 53.4 96.4 64.5 117.9 60.6 116.8 71.6
2200 45 58.5 49.1 62.7 62.7 77.4 45.3 77.7 56.9 98.5 52.8 98.1 64.1
50 41.2 41.2 52.0 52.0 55.2 36.8 58.1 49.3 77.2 45.0 77.9 56.7
40 100.8 72.3 92.2 92.2 128.7 69.5 127.6 82.8 157.6 79.5 156.4 92.9
2600 45 75.9 61.5 78.9 78.9 102.3 58.3 102.2 72.1 131.6 68.8 131.1 82.5
50 51.6 51.6 65.3 65.3 72.7 46.7 75.5 61.6 102.8 57.8 103.2 71.8
40 106.1 76.7 98.0 98.0 135.0 73.2 134.1 87.6 165.0 83.6 164.4 98.2
2800 45 80.1 65.5 83.9 83.9 107.4 61.6 107.4 76.4 137.7 72.4 137.3 87.1
5/ 50 54.9 54.9 69.5 69.5 76.4 49.5 79.7 65.6 107.2 60.9 108.3 76.1
30 8 11/8
40 111.0 80.8 103.6 103.6 140.9 76.7 140.2 92.2 171.8 87.4 170.2 102.6
3000 45 84.0 69.2 88.7 88.7 112.1 64.7 112.3 80.6 143.4 75.9 143.0 91.5
50 58.1 58.1 73.5 73.5 79.7 52.2 83.5 69.4 112.2 64.1 113.0 80.2
40 115.6 84.7 108.8 108.8 146.3 80.0 145.8 96.6 178.0 90.9 177.2 107.4
3200 45 87.6 72.8 93.1 93.1 116.5 67.6 116.8 84.5 148.6 79.1 148.1 95.7
50 61.1 61.1 77.2 77.2 82.9 54.7 87.1 73.0 115.8 66.9 117.4 84.2
40 137.6 99.2 128.3 128.3 168.6 92.0 168.3 111.0 200.7 102.8 200.3 121.7
3600 45 107.9 86.4 110.9 110.9 137.6 79.1 138.7 98.6 170.2 90.5 170.6 109.8
50 78.5 74.4 93.2 93.2 103.5 65.7 107.5 86.3 137.1 78.1 139.1 97.9
40 141.9 103.1 133.7 133.7 173.1 95.0 173.2 115.1 205.7 105.9 205.3 125.9
3800 45 111.6 90.0 115.6 115.6 141.4 81.8 142.9 102.5 174.4 93.4 175.2 113.9
7/ 50 78.8 78.8 97.2 97.2 106.5 68.3 111.0 90.1 140.6 80.8 143.2 101.9
40 8 11/8
40 145.9 106.9 138.9 138.9 177.3 97.8 177.7 119.1 210.2 108.8 210.2 129.9
4000 45 115.1 93.6 120.1 120.1 144.9 84.4 146.8 106.3 178.3 96.2 179.5 117.8
50 81.9 81.9 101.0 101.0 109.4 70.7 114.4 93.7 143.8 83.4 146.9 105.7
40 149.7 110.5 143.8 143.8 181.1 100.4 181.9 122.8 214.3 111.5 214.7 133.8
4200 45 118.3 97.1 124.4 124.4 148.1 86.9 150.4 110.0 181.8 98.9 183.5 121.6
50 84.9 84.9 104.7 104.7 112.1 73.1 117.5 97.2 146.6 85.9 150.4 109.3
LEGEND *Capacity based on R-22 refrigerant at 105 F liquid temperature and 10 F
MBtuh — Capacity (Btuh in thousands) superheat.
SH — Sensible Heat
TH — Total Heat

29
Performance data (cont)
UNIT HORSEPOWER DATA TABLE

UNIT TOTAL STATIC PRESSURE (in. wg)


SIZE BLOWER CFM 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
42BHC,BVC Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
400 677 0.05 770 0.07 857 0.09 937 0.11 1009 0.13 1077 0.14 1140 0.16 1200 0.18 1257 0.20
500 729 0.07 798 0.09 873 0.33 947 0.13 1019 0.16 1086 0.18 1150 0.20 1210 0.23 1267 0.25
06 9 in. x 4 in. 600 809 0.11 856 0.12 909 0.14 968 0.16 1031 0.18 1093 0.21 1154 0.24 1214 0.26 1271 0.29
700 906 0.15 939 0.17 977 0.18 1020 0.20 1067 0.22 1118 0.25 1171 0.28 1225 0.31 1278 0.34
800 1012 0.22 1038 0.23 1068 0.25 1100 0.27 1135 0.29 1174 0.31 1215 0.33 1259 0.36 1305 0.39
600 670 0.07 745 0.09 815 0.11 880 0.12 942 0.14 1000 0.16 1055 0.18 1108 0.20 1159 0.22
700 706 0.10 776 0.11 842 0.13 903 0.15 962 0.17 1018 0.19 1071 0.21 1123 0.24 1172 0.26
08 9 in. x 6 in. 800 748 0.12 812 0.14 874 0.17 932 0.19 988 0.21 1041 0.23 1092 0.25 1142 0.28 1190 0.30
900 794 0.16 853 0.18 910 0.20 965 0.23 1018 0.25 1069 0.28 1118 0.30 1165 0.33 1211 0.35
1000 — — — — — — — — — — 1103 0.34 1149 0.36 1193 0.39 1236 0.41
800 817 0.17 854 0.19 896 0.21 943 0.23 992 0.25 1042 0.28 1091 0.31 1139 0.34 1185 0.36
900 897 0.23 926 0.25 959 0.27 996 0.29 1036 0.31 1079 0.34 1123 0.37 1168 0.40 1212 0.43
10 10 in. x 4 in. 1000 982 0.31 1006 0.33 1033 0.35 1062 0.37 1095 0.39 1130 0.41 1167 0.44 1206 0.47 1246 0.50
1100 1068 0.41 1088 0.42 1111 0.44 1135 0.46 1161 0.48 1190 0.50 1221 0.53 1254 0.56 1288 0.59
1200 1143 0.51 1172 0.53 1192 0.55 1212 0.57 1234 0.59 1258 0.62 1284 0.64 1311 0.67 1340 0.70
1000 629 0.13 688 0.15 744 0.18 789 0.20 849 0.22 898 0.24 946 0.26 991 0.29 1035 0.31
1100 656 0.16 712 0.19 765 0.21 816 0.23 865 0.26 912 0.28 958 0.30 1002 0.33 1044 0.35
12 10 in. x 7 in. 1200 686 0.20 738 0.22 789 0.25 837 0.27 884 0.30 929 0.32 973 0.35 1015 0.38 1056 0.40
1300 717 0.24 767 0.27 814 0.29 861 0.32 905 0.35 948 0.37 990 0.40 1031 0.43 1071 0.46
1400 — — — — — — — — — — 968 0.43 1008 0.46 1048 0.49 1086 0.52
1400 — — 648 0.20 699 0.23 747 0.26 792 0.29 834 0.31 875 0.34 913 0.37 949 0.40
1500 611 0.20 664 0.23 714 0.26 761 0.29 805 0.32 847 0.35 887 0.38 925 0.41 961 0.44
16 11 in. x 10 in. 1600 631 0.24 682 0.27 730 0.30 776 0.33 819 0.36 860 0.39 899 0.42 937 0.45 973 0.48
1700 651 0.27 700 0.30 747 0.34 791 0.37 834 0.40 874 0.43 913 0.47 950 0.50 986 0.53
1800 — — — — — — — — — — 890 0.49 928 0.52 965 0.56 1000 0.60
1800 — — 629 0.32 672 0.36 712 0.39 751 0.43 788 0.46 824 0.50 860 0.54 894 0.57
1900 603 0.32 646 0.36 686 0.40 726 0.43 763 0.47 800 0.51 835 0.55 869 0.59 903 0.62
2000 621 0.36 662 0.40 702 0.44 740 0.48 777 0.52 812 0.56 846 0.60 880 0.64 913 0.68
20 12 in. x 9 in. 2100 639 0.41 679 0.45 718 0.49 755 0.53 790 0.57 825 0.61 859 0.66 891 0.70 923 0.74
2200 658 0.46 697 0.50 734 0.54 770 0.59 805 0.63 839 0.67 871 0.71 903 0.76 935 0.80
2300 — — — — — — — — — — — — 887 0.78 918 0.83 947 0.87
2400 — — — — — — — — — — — — — — 932 0.90 961 0.95
2400 604 0.43 647 0.47 688 0.52 728 0.57 766 0.62 803 0.66 840 0.71 875 0.76 909 0.82
2600 633 0.52 674 0.57 713 0.62 750 0.67 787 0.72 823 0.77 857 0.82 891 0.88 924 0.93
30 12 in. x 12 in. 2800 660 0.62 701 0.67 739 0.73 775 0.78 810 0.84 844 0.89 877 0.95 909 1.01 941 1.06
3000 694 0.74 730 0.79 766 0.85 800 0.91 834 0.97 866 1.03 898 1.09 929 1.15 960 1.21
3200 726 0.87 760 0.93 794 0.99 827 1.05 859 1.12 890 1.18 921 1.24 951 1.30 980 1.37
3400 — — — — — — — — — — — — 944 1.42 972 1.48 1000 1.55
3400 — — — — 609 0.79 639 0.85 668 0.91 697 0.97 724 1.04 752 1.10 778 1.16
3600 — — — — 627 0.90 656 0.96 684 1.03 712 1.09 738 1.16 765 1.22 791 1.29
40 15 in. x 12 in. 3800 — — 616 0.95 646 1.02 674 1.09 701 1.16 727 1.22 753 1.29 779 1.36 804 1.43
4000 607 1.01 637 1.08 665 1.15 692 1.22 718 1.29 744 1.37 769 1.44 794 1.51 818 1.58
4200 629 1.14 657 1.22 684 1.30 711 1.37 736 1.45 761 1.52 786 1.59 809 1.67 833 1.74
4400 — — — — — — — — — — — — 806 1.79 829 1.87 852 1.95
LEGEND NOTES:
— — Application not available 1. Contact factory if higher horsepower selection is required for a
Bhp — Horsepower given cfm and total static pressure.
2. The variable pitch motor sheave provided will allow + 15% rpm
adjustment. Unit sizes 06, 08, 10 and 12 have 3/4 in. bore fan
sheaves. Unit sizes 16, 20, 30 and 40 have 1-in. bore fan sheaves.
3. Consult factory for motor selections when outlet air temperature
exceeds 104 F on hot water coil applications.
4. Single-phase motors are only available to 2 hp. Three-phase
motors are available from 1/2 to 3 hp.

30
UNIT HORSEPOWER DATA TABLE (cont)

UNIT TOTAL STATIC PRESSURE (in. wg)


SIZE BLOWER CFM 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
42BHC,BVC Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
400 — — — — — — — — — — — — — — — — — —
500 1321 0.27 1374 0.30 — — — — — — — — — — — — — —
06 9 in. x 4 in. 600 1326 0.32 1378 0.35 1429 0.38 1478 0.40 — — — — — — — — — —
700 1331 0.37 1383 0.40 1433 0.43 1482 0.46 1529 0.50 1575 0.53 1619 0.56 1662 0.59 1705 0.63
800 1352 0.42 1399 0.46 1446 0.49 1492 0.52 1538 0.56 1583 0.60 1627 0.63 1670 0.67 1712 0.71
600 1208 0.24 — — — — — — — — — — — — — — — —
700 1220 0.28 1266 0.30 1310 0.33 1353 0.35 1395 0.37 — — — — — — — —
08 9 in. x 6 in. 800 1236 0.33 1280 0.35 1324 0.38 1366 0.40 1407 0.43 1447 0.45 1486 0.48 1524 0.51 1562 0.53
900 1256 0.38 1299 0.40 1341 0.43 1382 0.46 1423 0.49 1462 0.52 1500 0.54 1537 0.57 1574 0.60
1000 1278 0.44 1319 0.47 1359 0.49 1398 0.52 1436 0.55 1474 0.57 1510 0.60 1546 0.63 1582 0.65
800 1229 0.39 1271 0.42 1311 0.44 1350 0.47 1388 0.50 1425 0.52 1461 0.55 1496 0.58 1530 0.60
900 1254 0.46 1296 0.49 1336 0.52 1375 0.55 1413 0.58 1450 0.61 1486 0.64 1520 0.67 1554 0.70
10 10 in. x 4 in. 1000 1286 0.53 1326 0.57 1365 0.60 1403 0.64 1441 0.67 1477 0.70 1513 0.74 1547 0.77 1581 0.81
1100 1324 0.62 1360 0.66 1396 0.69 1433 0.73 1469 0.77 1504 0.80 1539 0.84 1573 0.88 1606 0.92
1200 1370 0.73 1402 0.76 1434 0.80 1467 0.84 1501 0.87 1534 0.91 1567 0.95 1600 0.99 1633 1.03
1000 1078 0.33 1120 0.36 1160 0.38 1200 0.40 1239 0.43 1276 0.45 1313 0.47 1349 0.50 1385 0.52
1100 1086 0.38 1126 0.40 1166 0.43 1222 0.48 1242 0.48 1279 0.51 1315 0.53 1350 0.56 1396 0.61
12 10 in. x 7 in. 1200 1097 0.43 1136 0.46 1174 0.48 1211 0.51 1248 0.54 1284 0.57 1319 0.59 1353 0.62 1387 0.65
1300 1110 0.49 1148 0.51 1185 0.54 1221 0.57 1257 0.60 1292 0.63 1326 0.66 1359 0.69 1392 0.72
1400 1124 0.55 1162 0.58 1198 0.61 1234 0.64 1269 0.67 1304 0.70 1338 0.73 1371 0.77 1404 0.80
1400 985 0.42 1018 0.45 1051 0.48 1083 0.51 1113 0.54 1143 0.57 1172 0.59 1200 0.62 1227 0.65
1500 996 0.47 1030 0.50 1062 0.53 1094 0.56 1124 0.59 1154 0.62 1182 0.65 1210 0.68 1238 0.71
16 11 in. x 10 in. 1600 1008 0.52 1041 0.55 1074 0.58 1105 0.61 1135 0.64 1165 0.67 1193 0.71 1221 0.74 1248 0.77
1700 1020 0.57 1053 0.60 1085 0.63 1116 0.67 1146 0.70 1176 0.73 1204 0.77 1232 0.80 1259 0.84
1800 1033 0.63 1065 0.66 1097 0.70 1128 0.73 1157 0.77 1186 0.80 1215 0.84 1242 0.87 1268 0.90
1800 927 0.61 959 0.65 991 0.69 1022 0.73 1052 0.77 — — — — — — — —
1900 935 0.66 967 0.70 998 0.74 1028 0.78 1058 0.83 1087 0.87 1115 0.91 — — — —
2000 944 0.72 975 0.76 1006 0.80 1035 0.85 1065 0.89 1093 0.93 1121 0.97 1149 1.02 1176 1.06
20 12 in. x 9 in. 2100 954 0.78 985 0.82 1014 0.87 1043 0.91 1072 0.96 1100 1.00 1128 1.04 1155 1.09 1181 1.14
2200 965 0.85 995 0.89 1024 0.94 1052 0.98 1080 1.03 1108 1.07 1135 1.12 1162 1.17 1188 1.21
2300 976 0.92 1004 0.96 1032 1.01 1060 1.05 1087 1.10 1114 1.14 1141 1.19 1167 1.24 1193 1.28
2400 989 0.99 1016 1.04 1044 1.09 1071 1.13 1097 1.18 1124 1.23 1150 1.28 1175 1.32 1200 1.37
2400 943 0.87 976 0.92 1008 0.97 1039 1.03 1070 1.08 1101 1.14 1130 1.20 1160 1.26 1189 1.32
2600 956 0.99 988 1.04 1019 1.10 1049 1.16 1079 1.21 1108 1.27 1137 1.33 1166 1.39 1194 1.45
30 12 in. x 12 in. 2800 972 1.12 1002 1.18 1032 1.24 1062 1.30 1090 1.36 1119 1.42 1147 1.48 1174 1.54 1201 1.61
3000 990 1.27 1019 1.33 1048 1.39 1076 1.45 1104 1.52 1131 1.58 1158 1.65 1185 1.71 1211 1.78
3200 1009 1.43 1037 1.50 1065 1.56 1093 1.63 1120 1.69 1146 1.76 1172 1.83 1198 1.90 1224 1.97
3400 1027 1.61 1055 1.68 1082 1.75 1108 1.82 1135 1.89 1161 1.96 1186 2.03 1212 2.10 1237 2.17
3400 805 1.23 830 1.30 856 1.36 881 1.43 905 1.51 930 1.58 954 1.65 978 1.73 1001 1.81
3600 816 1.36 841 1.43 865 1.50 889 1.57 913 1.64 937 1.72 960 1.79 983 1.87 1006 1.95
40 15 in. x 12 in. 3800 828 1.50 852 1.57 876 1.64 899 1.72 923 1.79 945 1.87 968 1.95 990 2.02 1012 2.10
4000 842 1.65 865 1.73 888 1.80 911 1.88 933 1.95 955 2.03 977 2.11 999 2.19 1020 2.27
4200 856 1.82 879 1.90 901 1.97 923 2.05 945 2.13 966 2.21 987 2.29 1008 2.37 1029 2.46
4400 874 2.03 896 2.11 917 2.19 938 2.27 959 2.35 980 2.43 1000 2.51 1020 2.60 1040 2.68
LEGEND NOTES:
— — Application not available 1. Contact factory if higher horsepower selection is required for a
Bhp — Horsepower given cfm and total static pressure.
2. The variable pitch motor sheave provided will allow + 15% rpm
adjustment. Unit sizes 06, 08, 10 and 12 have 3/4 in. bore fan
sheaves. Unit sizes 16, 20, 30 and 40 have 1-in. bore fan sheaves.
3. Consult factory for motor selections when outlet air temperature
exceeds 104 F on hot water coil applications.
4. Single-phase motors are only available to 2 hp. Three-phase
motors are available from 1/2 to 3 hp.

31
Performance data (cont)
42BHC,BVC COMPONENT STATIC RESISTANCE (in. wg)
WET COIL DRY COIL TWO-INCH
ONE-INCH TWO-INCH TWO-INCH PLEATED
UNIT NOMINAL
CABINET 4 6 8 1 2 4 6 8 PLEATED THROWAWAY PLEATED
SIZE 42BHC,BVC CFM MERV 11
Row Row Row Row Row Row Row Row FILTER FILTER FILTER FILTER
400 0.02 0.08 0.12 0.16 0.01 0.02 0.04 0.06 0.08 0.03 0.02 0.03 0.06
500 0.03 0.13 0.19 0.25 0.01 0.03 0.06 0.09 0.12 0.05 0.03 0.04 0.09
06 600 0.04 0.18 0.27 0.36 0.02 0.04 0.08 0.13 0.17 0.08 0.04 0.06 0.12
700 0.06 0.25 0.37 0.50 0.03 0.06 0.12 0.17 0.23 0.10 0.06 0.08 0.17
800 0.08 0.32 0.49 0.65 0.04 0.08 0.15 0.23 0.30 0.14 0.08 0.11 0.22
600 0.04 0.18 0.27 0.36 0.02 0.04 0.08 0.13 0.17 0.08 0.04 0.06 0.12
700 0.06 0.25 0.37 0.50 0.03 0.06 0.12 0.17 0.23 0.10 0.06 0.08 0.17
08 800 0.08 0.32 0.49 0.65 0.04 0.08 0.15 0.23 0.30 0.14 0.08 0.11 0.22
900 0.10 0.41 0.61 0.82 0.05 0.10 0.19 0.29 0.38 0.17 0.10 0.14 0.28
1000 0.12 0.51 0.76 1.01 0.06 0.12 0.24 0.35 0.47 0.21 0.12 0.17 0.34
800 0.04 0.15 0.23 0.31 0.02 0.04 0.07 0.11 0.14 0.07 0.04 0.06 0.12
900 0.05 0.19 0.29 0.39 0.02 0.05 0.09 0.14 0.18 0.09 0.05 0.07 0.15
10 1000 0.06 0.24 0.36 0.48 0.03 0.06 0.11 0.17 0.22 0.11 0.06 0.09 0.18
1100 0.08 0.29 0.44 0.58 0.03 0.07 0.14 0.20 0.27 0.14 0.08 0.11 0.22
1200 0.09 0.35 0.52 0.69 0.04 0.08 0.16 0.24 0.32 0.16 0.09 0.13 0.26
1000 0.06 0.24 0.36 0.48 0.03 0.06 0.11 0.17 0.22 0.11 0.06 0.09 0.18
1100 0.08 0.29 0.44 0.58 0.03 0.07 0.14 0.20 0.27 0.14 0.08 0.11 0.22
12 1200 0.09 0.35 0.52 0.69 0.04 0.08 0.16 0.24 0.32 0.16 0.09 0.13 0.26
1300 0.11 0.41 0.61 0.81 0.05 0.09 0.19 0.28 0.38 0.19 0.11 0.15 0.31
1400 0.13 0.47 0.71 0.94 0.05 0.11 0.22 0.33 0.44 0.22 0.13 0.17 0.36
1400 0.07 0.26 0.39 0.52 0.03 0.06 0.12 0.18 0.24 0.13 0.07 0.10 0.21
1500 0.09 0.30 0.45 0.60 0.03 0.07 0.14 0.21 0.28 0.15 0.09 0.12 0.24
16 1600 0.10 0.34 0.51 0.68 0.04 0.08 0.16 0.24 0.32 0.17 0.10 0.13 0.27
1700 0.11 0.38 0.58 0.77 0.04 0.09 0.18 0.27 0.36 0.19 0.11 0.15 0.31
1800 0.12 0.43 0.65 0.86 0.05 0.10 0.20 0.30 0.40 0.21 0.12 0.17 0.35
1800 0.12 0.30 0.45 0.60 0.03 0.07 0.14 0.21 0.28 0.13 0.08 0.10 0.21
1900 0.13 0.34 0.50 0.67 0.04 0.08 0.16 0.23 0.31 0.14 0.08 0.12 0.24
2000 0.14 0.37 0.56 0.74 0.04 0.09 0.17 0.26 0.35 0.16 0.09 0.13 0.26
20 2100 0.16 0.41 0.61 0.82 0.05 0.10 0.19 0.29 0.38 0.18 0.10 0.14 0.29
2200 0.17 0.45 0.67 0.90 0.05 0.10 0.21 0.31 0.42 0.19 0.11 0.16 0.32
2300 0.19 0.49 0.74 0.98 0.06 0.11 0.23 0.34 0.46 0.21 0.12 0.17 0.35
2400 0.21 0.54 0.80 1.07 0.06 0.12 0.25 0.37 0.50 0.23 0.13 0.19 0.38
2400 0.11 0.22 0.33 0.43 0.03 0.05 0.10 0.15 0.20 0.13 0.07 0.10 0.21
2600 0.13 0.25 0.38 0.51 0.03 0.06 0.12 0.18 0.24 0.15 0.09 0.12 0.24
30 2800 0.15 0.29 0.44 0.59 0.03 0.07 0.14 0.21 0.27 0.17 0.10 0.14 0.28
3000 0.18 0.34 0.51 0.68 0.04 0.08 0.16 0.24 0.31 0.20 0.12 0.16 0.32
3200 0.20 0.39 0.58 0.77 0.04 0.09 0.18 0.27 0.36 0.23 0.13 0.18 0.37
3400 0.23 0.43 0.65 0.87 0.05 0.10 0.20 0.30 0.40 0.25 0.15 0.20 0.42
3400 0.13 0.24 0.36 0.48 0.03 0.06 0.11 0.17 0.22 0.15 0.09 0.12 0.24
3600 0.15 0.27 0.40 0.54 0.03 0.06 0.12 0.19 0.25 0.16 0.10 0.13 0.27
40 3800 0.16 0.30 0.45 0.60 0.03 0.07 0.14 0.21 0.28 0.18 0.11 0.15 0.30
4000 0.18 0.33 0.50 0.66 0.04 0.08 0.15 0.23 0.31 0.20 0.12 0.16 0.33
4200 0.20 0.36 0.55 0.73 0.04 0.08 0.17 0.25 0.34 0.22 0.13 0.18 0.37
4400 0.22 0.40 0.60 0.80 0.05 0.09 0.19 0.28 0.37 0.25 0.14 0.20 0.40

Hydronic coil pressure drop — All of the factory’s hy- Coil pressure drop (ft wg):
dronic coils have a coefficient of velocity (Cv) resistance ∆P = (GPM2/Cv2 ) x 2.31
factor assigned to assist in a more accurate determination or
of water pressure drop (see Cv Factor by Coil and Unit Size ∆P = [GPM/(0.658 x Cv)]2
table below). or
Calculating pressure drop: Refer to the Water Pressure Drop for Cv Factor and
The Cv factor is equal to the flow rate of water in gpm Water Flow Rate table. See example on page 22.
through a piping component when the pressure drop
Cv FACTOR BY COIL AND UNIT SIZE
through the component is 1.0 pounds per square inch
(psi), or 2.31 ft wg. 42BHC,BVC UNIT SIZE
COIL TYPE
∆P (ft wg) = ∆P (psi) x 2.31 06 08 10 12 16 20 30 40
1 Row Heat Only 1.4 1.4 1.3 1.3 1.2 1.2 0.8 0.7
Use the Cv factor from the Cv Factor by Coil and Unit
2 Row Heat Only 2.4 2.4 2.2 2.2 2.0 1.9 1.6 1.4
Size table to determine the water coil pressure drop.
4 Row Heat/Cool 4.7 4.7 4.4 4.4 7.2 6.8 13.2 12.4
6 Row Heat/Cool 4.0 4.0 3.7 3.7 6.1 5.8 11.4 10.5
8 Row Heat/Cool 3.6 3.6 3.3 3.3 5.3 5.1 9.8 9.0

32
42BHC,BVC WATER PRESSURE DROP (ft. wg) FOR CV FACTOR AND WATER FLOW RATE (GPM)
Cv WATER FLOW RATE (GPM)
FACTORS 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10.0 10.5 11.0 11.5 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0
0.8 0.9 3.6 8.1 14.4 22.5 32.4 — — — — — — — — — — — — — — — — — — — — — — — — — —
0.9 0.7 2.8 6.4 11.4 17.8 25.6 34.9 — — — — — — — — — — — — — — — — — — — — — — — — —
1.0 0.5 2.3 5.2 9.2 14.4 20.7 28.2 36.9 — — — — — — — — — — — — — — — — — — — — — — — —
1.1 0.4 1.9 4.2 7.6 11.9 17.1 23.3 30.5 — — — — — — — — — — — — — — — — — — — — — — — —
1.2 — 1.6 3.6 6.4 10.0 14.4 19.6 25.6 32.4 — — — — — — — — — — — — — — — — — — — — — — —
1.3 — 1.3 3.0 5.4 8.5 12.3 16.7 21.8 27.6 34.1 — — — — — — — — — — — — — — — — — — — — — —
1.4 — 1.1 2.6 4.7 7.3 10.6 14.4 18.8 23.8 29.4 — — — — — — — — — — — — — — — — — — — — — —
1.5 — 1.0 2.3 4.1 6.4 9.2 12.5 16.4 20.7 25.6 31.0 — — — — — — — — — — — — — — — — — — — — —
1.6 — 0.9 2.0 3.6 5.6 8.1 11.0 14.4 18.2 22.5 27.2 32.4 — — — — — — — — — — — — — — — — — — — —
1.7 — 0.8 1.8 3.2 4.9 7.1 9.7 12.7 16.1 19.9 24.1 28.7 33.7 — — — — — — — — — — — — — — — — — — —
1.8 — 0.7 1.6 2.8 4.4 6.4 8.7 11.4 14.4 17.8 21.5 25.6 30.1 — — — — — — — — — — — — — — — — — — —
1.9 — 0.6 1.4 2.5 4.0 5.7 7.8 10.2 12.9 15.9 19.3 23.0 27.0 31.3 — — — — — — — — — — — — — — — — — —
2.0 — 0.5 1.3 2.3 3.6 5.2 7.0 9.2 11.6 14.4 17.4 20.7 24.4 28.2 32.4 — — — — — — — — — — — — — — — — —
2.1 — 0.5 1.1 2.0 3.2 4.7 6.4 8.3 10.6 13.0 15.8 18.8 22.1 25.6 29.4 33.5 — — — — — — — — — — — — — — — —
2.2 — 0.4 1.0 1.9 2.9 4.2 5.8 7.6 9.6 11.9 14.4 17.1 20.1 23.3 26.8 30.5 — — — — — — — — — — — — — — — —
2.3 — — 0.9 1.7 2.7 3.9 5.3 6.9 8.8 10.9 13.2 15.7 18.4 21.3 24.5 27.9 31.5 — — — — — — — — — — — — — — —
2.4 — — 0.9 1.6 2.5 3.6 4.9 6.4 8.1 10.0 12.1 14.4 16.9 19.6 22.5 25.6 28.9 32.4 — — — — — — — — — — — — — —
2.5 — — 0.8 1.4 2.3 3.3 4.5 5.9 7.4 9.2 11.1 13.3 15.6 18.1 20.7 23.6 26.7 29.9 33.3 — — — — — — — — — — — — —
2.6 — — 0.7 1.3 2.1 3.0 4.1 5.4 6.9 8.5 10.3 12.3 14.4 16.7 19.2 21.8 24.6 27.6 30.8 — — — — — — — — — — — — —
2.7 — — 0.7 1.2 1.9 2.8 3.8 5.0 6.4 7.9 9.5 11.4 13.3 15.5 17.8 20.2 22.8 25.6 28.5 31.6 — — — — — — — — — — — —
2.8 — — 0.6 1.1 1.8 2.6 3.6 4.7 5.9 7.3 8.9 10.6 12.4 14.4 16.5 18.8 21.2 23.8 26.5 29.4 32.4 — — — — — — — — — — —
2.9 — — 0.6 1.1 1.7 2.4 3.3 4.3 5.5 6.8 8.3 9.8 11.6 13.4 15.4 17.5 19.8 22.2 24.7 27.4 30.2 — — — — — — — — — — —
3.0 — — 0.5 1.0 1.6 2.3 3.1 4.1 5.2 6.4 7.7 9.2 10.8 12.5 14.4 16.4 18.5 20.7 23.1 25.6 28.2 31.0 — — — — — — — — — —
3.2 — — 0.5 0.9 1.4 2.0 2.7 3.6 4.5 5.6 6.8 8.1 9.5 11.0 12.6 14.4 16.3 18.2 20.3 22.5 24.8 27.2 29.8 — — — — — — — — —
3.4 — — — 0.8 1.2 1.8 2.4 3.2 4.0 4.9 6.0 7.1 8.4 9.7 11.2 12.7 14.4 16.1 18.0 19.9 22.0 24.1 26.4 28.7 — — — — — — — —
3.6 — — — 0.7 1.1 1.6 2.1 2.8 3.6 4.4 5.3 6.4 7.5 8.7 10.0 11.4 12.8 14.4 16.0 17.8 19.6 21.5 23.5 25.6 30.1 — — — — — — —
3.8 — — — 0.6 1.0 1.4 1.9 2.5 3.2 4.0 4.8 5.7 6.7 7.8 9.0 10.2 11.5 12.9 14.4 15.9 17.6 19.3 21.1 23.0 27.0 31.3 — — — — — —
4.0 — — — 0.5 0.9 1.3 1.7 2.3 2.9 3.6 4.3 5.2 6.1 7.0 8.1 9.2 10.4 11.6 13.0 14.4 15.9 17.4 19.0 20.7 24.4 28.2 — — — — — —
4.2 — — — 0.5 0.8 1.1 1.6 2.0 2.6 3.2 3.9 4.7 5.5 6.4 7.3 8.3 9.4 10.6 11.8 13.0 14.4 15.8 17.3 18.8 22.1 25.6 29.4 — — — — —
4.4 — — — 0.4 0.7 1.0 1.4 1.9 2.4 2.9 3.6 4.2 5.0 5.8 6.7 7.6 8.6 9.6 10.7 11.9 13.1 14.4 15.7 17.1 20.1 23.3 26.8 30.5 — — — —
4.6 — — — — 0.6 0.9 1.3 1.7 2.2 2.7 3.3 3.9 4.6 5.3 6.1 6.9 7.8 8.8 9.8 10.9 12.0 13.2 14.4 15.7 18.4 21.3 24.5 27.9 31.5 — — —
4.8 — — — — 0.6 0.9 1.2 1.6 2.0 2.5 3.0 3.6 4.2 4.9 5.6 6.4 7.2 8.1 9.0 10.0 11.0 12.1 13.2 14.4 16.9 19.6 22.5 25.6 28.9 — — —
5.0 — — — — 0.5 0.8 1.1 1.4 1.8 2.3 2.7 3.3 3.9 4.5 5.2 5.9 6.6 7.4 8.3 9.2 10.1 11.1 12.2 13.3 15.6 18.1 20.7 23.6 26.7 29.9 — —
5.3 — — — — 0.5 0.7 1.0 1.3 1.6 2.0 2.4 2.9 3.4 4.0 4.6 5.2 5.9 6.6 7.4 8.2 9.0 9.9 10.8 11.8 13.9 16.1 18.5 21.0 23.7 26.6 29.6 —
5.6 — — — — 0.4 0.6 0.9 1.1 1.4 1.8 2.2 2.6 3.1 3.6 4.1 4.7 5.3 5.9 6.6 7.3 8.1 8.9 9.7 10.6 12.4 14.4 16.5 18.8 21.2 23.8 26.5 29.4
5.9 — — — — — 0.6 0.8 1.0 1.3 1.6 2.0 2.3 2.8 3.2 3.7 4.2 4.7 5.3 5.9 6.6 7.3 8.0 8.7 9.5 11.2 13.0 14.9 16.9 19.1 21.5 23.9 26.5
6.2 — — — — — 0.5 0.7 0.9 1.2 1.5 1.8 2.1 2.5 2.9 3.3 3.8 4.3 4.8 5.4 6.0 6.6 7.2 7.9 8.6 10.1 11.7 13.5 15.3 17.3 19.4 21.6 24.0
6.5 — — — — — 0.4 0.6 0.8 1.1 1.3 1.6 1.9 2.3 2.6 3.0 3.5 3.9 4.4 4.9 5.4 6.0 6.6 7.2 7.8 9.2 10.7 12.3 13.9 15.8 17.7 19.7 21.8
6.8 — — — — — — 0.6 0.8 1.0 1.2 1.5 1.8 2.1 2.4 2.8 3.2 3.6 4.0 4.5 4.9 5.5 6.0 6.6 7.1 8.4 9.7 11.2 12.7 14.4 16.1 18.0 19.9
7.1 — — — — — — 0.5 0.7 0.9 1.1 1.3 1.6 1.9 2.2 2.5 2.9 3.3 3.7 4.1 4.5 5.0 5.5 6.0 6.6 7.7 8.9 10.3 11.7 13.2 14.8 16.5 18.3
7.5 — — — — — — 0.5 0.6 0.8 1.0 1.2 1.4 1.7 2.0 2.3 2.6 2.9 3.3 3.7 4.1 4.5 4.9 5.4 5.9 6.9 8.0 9.2 10.5 11.8 13.3 14.8 16.4
8.0 — — — — — — — 0.5 0.7 0.9 1.0 1.3 1.5 1.7 2.0 2.3 2.6 2.9 3.2 3.6 3.9 4.3 4.7 5.2 6.1 7.0 8.1 9.2 10.4 11.6 13.0 14.4
8.5 — — — — — — — 0.5 0.6 0.8 0.9 1.1 1.3 1.5 1.8 2.0 2.3 2.5 2.8 3.2 3.5 3.8 4.2 4.6 5.4 6.2 7.1 8.1 9.2 10.3 11.5 12.7
9.0 — — — — — — — 0.4 0.5 0.7 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.3 2.5 2.8 3.1 3.4 3.7 4.1 4.8 5.5 6.4 7.3 8.2 9.2 10.2 11.4
9.5 — — — — — — — — 0.5 0.6 0.7 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.3 2.5 2.8 3.1 3.3 3.6 4.3 5.0 5.7 6.5 7.4 8.2 9.2 10.2
10.0 — — — — — — — — 0.4 0.5 0.7 0.8 0.9 1.1 1.3 1.4 1.6 1.8 2.0 2.3 2.5 2.7 3.0 3.3 3.9 4.5 5.2 5.9 6.6 7.4 8.3 9.2
10.5 — — — — — — — — — 0.5 0.6 0.7 0.8 1.0 1.1 1.3 1.5 1.7 1.8 2.0 2.3 2.5 2.7 3.0 3.5 4.1 4.7 5.3 6.0 6.7 7.5 8.3
11.0 — — — — — — — — — 0.4 0.5 0.6 0.8 0.9 1.0 1.2 1.3 1.5 1.7 1.9 2.1 2.3 2.5 2.7 3.2 3.7 4.2 4.8 5.5 6.1 6.8 7.6
11.5 — — — — — — — — — — 0.5 0.6 0.7 0.8 0.9 1.1 1.2 1.4 1.5 1.7 1.9 2.1 2.3 2.5 2.9 3.4 3.9 4.4 5.0 5.6 6.3 6.9
12.0 — — — — — — — — — — 0.4 0.5 0.6 0.7 0.9 1.0 1.1 1.3 1.4 1.6 1.7 1.9 2.1 2.3 2.7 3.1 3.6 4.1 4.6 5.2 5.7 6.4
13.0 — — — — — — — — — — — 0.4 0.5 0.6 0.7 0.8 0.9 1.1 1.2 1.3 1.5 1.6 1.8 1.9 2.3 2.6 3.0 3.5 3.9 4.4 4.9 5.4
14.0 — — — — — — — — — — — — 0.5 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.3 1.4 1.5 1.7 1.9 2.3 2.6 3.0 3.4 3.8 4.2 4.7
15.0 — — — — — — — — — — — — — 0.5 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.7 2.0 2.3 2.6 2.9 3.3 3.7 4.1
16.0 — — — — — — — — — — — — — — 0.5 0.5 0.6 0.7 0.8 0.9 0.9 1.0 1.1 1.3 1.5 1.7 2.0 2.3 2.6 2.9 3.2 3.6
17.0 — — — — — — — — — — — — — — — 0.5 0.5 0.6 0.7 0.8 0.8 0.9 1.0 1.1 1.3 1.5 1.8 2.0 2.3 2.5 2.8 3.2
18.0 — — — — — — — — — — — — — — — 0.4 0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.3 2.5 2.8
19.0 — — — — — — — — — — — — — — — — 0.4 0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.3 2.5
20.0 — — — — — — — — — — — — — — — — — 0.4 0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.1 1.3 1.4 1.6 1.8 2.0 2.3

NOTE: Table interpolation is permissible, and extrapolation is not rec-


ommended.

SOUND POWER DATA


DISCHARGE SOUND RATINGS — A-WEIGHTED SOUND POWER LEVEL RATINGS* (dB)

CENTER FREQUENCY (Hz)


42BHC,BVC UNIT SIZE NOMINAL CFM
125 250 500 1000 2000 4000 8000
06 600 60 57 57 58 54 49 42
08 800 60 57 57 58 54 49 42
10 1000 68 65 65 66 62 57 50
12 1200 68 65 65 66 62 57 50
16 1600 69 66 66 67 63 58 51
20 2000 67 64 64 65 61 56 49
30 3000 70 67 67 68 64 59 52
40 4000 78 75 75 76 72 67 60
*These noise ratings are calculated values, not actual test values, and
apply only to the discharge of the unit, not the radiated sound levels.
Sound power is in decibels re 10e-12 w.

33
Typical wiring schematics
BASE UNIT, SINGLE-PHASE POWER

MOTOR CONTROL/DISCONNECT OPTION SINGLE-PHASE POWER

34
BASE UNIT, THREE-PHASE POWER

MOTOR CONTROL/DISCONNECT OPTION THREE-PHASE POWER

35
Typical wiring schematics (cont)
2-PIPE COOLING ONLY WITH SINGLE-SPEED FAN OPERATION AND HONEYWELL THERMOSTAT

NOTES:
1. Optional valves are field wired.
2. No HW valve with electric heat.

2-PIPE OR 4-PIPE HEATING/COOLING WITH SINGLE-SPEED


FAN OPERATION AND HONEYWELL DIGITAL THERMOSTAT

NOTES:
1. Optional valves are field wired.
2. No HW valve with electric heat.

36
Electrical data
42BHC,BVC ELECTRIC HEATER DATA AVAILABILITY 42BHC,BVC ELECTRIC HEATER DATA
42BHC UNIT SIZE FULL LOAD AMPS
kW
06 08 10 12 16 20 30 40 kW Single-Phase Three-Phase
1 ● ● ● — — — — — 120 V 208 V 240 V 277 V 208 V 240 V 480 V
1.5 ● ● ● ● — — — — 1 8.3 4.8 4.2 3.6 2.8 2.4 1.2
2 ● ● ● ● — — — — 1.5 12.5 7.2 6.3 5.4 4.2 2.4 1.2
2.5 ● ● ● ● ● — — — 2 16.7 9.6 8.3 7.2 5.6 4.8 2.4
3 ● ● ● ● ● — — — 2.5 20.8 12.0 10.4 9.0 6.9 6.0 3.0
3.5 ● ● ● ● ● ● — — 3 25.0 14.4 12.5 10.8 8.3 7.2 3.6
4 ● ● ● ● ● ● — — 3.5 29.2 16.8 14.6 12.6 9.7 8.4 4.2
4.5 ● ● ● ● ● ● — — 4 33.3 19.2 16.7 14.4 11.1 9.6 4.8
5 ● ● ● ● ● ● — — 4.5 37.5 21.6 18.8 16.2 12.5 10.8 5.4
6 ● ● ● ● ● ● ● ● 5 41.7 24.0 20.8 18.1 13.9 12.0 6.0
7 — ● ● ● ● ● ● ● 6 — 28.8 25.0 21.7 16.7 14.4 7.2
8 — ● ● ● ● ● ● ● 7 — 23.7 29.2 25.3 19.4 16.8 8.4
10 — — ● ● ● ● ● ● 8 — 38.5 33.3 28.9 22.2 19.2 9.6
12 — — — ● ● ● ● ● 10 — 47.6 41.3 35.7 27.5 23.8 11.9
15 — — — — ● ● ● ● 12 — — — 43.3 33.3 28.9 14.4
16 — — — — ● ● ● ● 15 — — — — 41.6 36.1 18.0
20 — — — — — ● ● ● 16 — — — — 44.4 38.5 19.2
25 — — — — — — ● ● 20 — — — — — 47.9 23.9
30 — — — — — — ● ● 25 — — — — — — 30.1
35 — — — — — — — ● 30 — — — — — — 36.1
40 — — — — — — — ● 35 — — — — — — 42.1
40 — — — — — — 48.0
LEGEND
● — Standard Offering
NOTES:
1. Stages available:
Single phase: 1-12 kW, 1 stage only
3-12 kW, 1 stage or 2 stage
Three phase: 1-40 kW, 1 stage only
4-40 kW, 1 or 2 stage
12-40 kW, 1, 2 or 3 stage
2. Electric Heating Capacities (Btuh) = Heater kW x 3413
3. Electric Heater Amperage for Single-phase Power
= (Heater kW x 1000)/Applied Voltage Electric Heater Amp. for 3-phase Power
= (Heater kW x 1000)/(Applied Voltage x 1.73).

MOTOR PERFORMANCE DATA (AMPS) Service Switches:


The service switch is an On/Off switch on incoming power
VOLTAGE Nominal HP
V-Ph-Hz 1/ 1/ 1/ 3/
supply to unit. Proper amperage load must be determined
4 3 2 4 1 11/2 2 3 5
before switch can be selected. The range of the fused or
115-1-60 5.2 6.0 8.6 13.3 14.4 — — — —
non-fused service switch is 0 to 40 amps.
208-1-60 3.0 3.6 4.8 6.5 7.4 9.4 11.0 — —
230-1-60 2.5 3.0 4.2 6.6 6.0 9.0 10.9 — — Amp Load = [Motor amps + Heater amps (if required)]*
277-1-60 2.1 2.5 3.6 5.1 5.4 8.5 8.0 — — 1.20.
208-3-60 — — 2.4 3.6 3.8 6.0 6.5 8.2 —
The UL listing signifies that Carrier’s fan coil units have been examined
230-3-60 — — 2.2 3.0 3.2 4.8 6.2 8.0 14.0 by UL and comply with the organization’s applicable standards of U.S.
460-3-60 — — 1.1 1.5 1.9 2.8 3.1 4.0 7.0 and Canadian national product safety standard, UL 1995/CSA C22.2
No. 236.
NOTES:
1. Motor Full Load Amps refer to National Electric Code (NEC)
Amps; actual motor nameplate amps may vary.
2. NEC data extrapolated for 277 v.
3. Motors are open drip proof, ball bearing, single speed, 1750 rpm
rated at continuous duty, 140 F ambient with reversible rotation.

37
Controls
Standard control features • 8-pole control terminal strip
• 4 in. x 4 in. junction box • Auto reset temperature limit switch
• Manual reset backup temperature limit switch
NOTE: Motor leads are wired to the 4 in. x 4 in. junction • 80/20 heater element wire
box, mounted on the external panel. Field verification of
• Motor power fusing*
the motor rotation is required on 3-phase applications.
• Motor control contactor**
Motor control options • Agency listed for 0-in. clearance
• Interlocking disconnect switch* Electric heat options:
• 24-v class 2 transformer (40 va)† • Single-phase, 1 or 2 stage heat
• 8-pole control terminal strip • Three-phase, 1, 2 or 3 stage heat
• Motor power fusing*
• Motor control contactor** *Complies with NEC’s requirement, Article 430 for dis-
Motor and electric heat control options connect, branch circuit protection motor controller and
motor overload protection.
NOTE: Electric heat option requires same voltage as motor
and must include the control option. These control features †No control fusing necessary.
are standard with electric heat options and control option. **Complies with NEC’s requirement for a motor starter
• Interlocking disconnect switch* with internal heating elements when used with the
• Heater power fusing* factory’s standard motors with integral thermal overload
• 24-v class 2 transformer (40 va)† protection.

38
Guide specifications
System Fan Coil Unit male MPT stainless secondary drain connection
(capped when not required). The outside surface of
HVAC Guide Specifications — 42B the drain pan shall be insulated with 1/8-in. closed
Size Range: 600 to 4000 Nominal Cfm cell insulation.
Carrier Model Number: C. Fans:
42BHC (Horizontal Fan Coil Unit) Belt-driven, double-width fan wheels shall have
42BVC (Vertical Fan Coil Unit) forward-curved blades and be statically and dynami-
Part 1 — General cally balanced. Fan drive shall consist of variable-
pitch motor pulley, fixed-pitch fan pulley and V-belt.
1.01 SYSTEM DESCRIPTION
Fans and scrolls shall be of galvanized steel.
Horizontal and vertical, 2-pipe or 4-pipe, belt-
D. Coils:
driven, galvanized casing model fan coil unit for
ducted installation above the ceiling or within Standard unit shall be equipped with a 4-row coil for
floor mounted cabinet, with full access to internal installation in a 2-pipe system and additional rows of
components. coil shall be provided for installation in a 4-pipe sys-
tem as described in the Options and Accessories
1.02 QUALITY ASSURANCE
section. Coils shall have 1/2-in. copper tubes, alumi-
A. Unit performance shall be rated in accordance with num fins bonded to the tubes by mechanical expan-
ARI Standard 440-2005. sion and have a working pressure of 250 psig at
B. Unit construction shall comply with ASHRAE (latest 200 F. Each coil shall have a manual air vent and
edition) Safety Code and NEC. sweat connections for copper tubes.
C. Unit shall be constructed in accordance with ETL E. Operating Characteristics:
and ETL, Canada standards. Factory-installed A single-circuit coil unit installed in a 2-pipe system
motors and electric heaters shall be UL approved. shall be capable of providing heating or cooling as
D. Each coil shall be factory tested for leakage determined by the operating mode of the central
at 350-psig air pressure with coil submerged water supply system. A double-circuit coil unit
in water. Insulation and adhesive shall meet installed in a 4-pipe system shall be capable of pro-
NFPA-90A requirements for flame spread and viding sequenced heating and cooling.
smoke generation. F. Motor(s):
E. Each coil shall be factory tested for leakage at Fan motors shall be open, drip-proof, single-speed,
350 psig air pressure with coil submerged in water. 60 Hz, 1750 rpm 1 or 3 phase, suitable for contin-
Insulation and adhesive shall meet NFPA-90A uous duty at 104 F (40 C). Single phase motors are
requirements for flame spread and smoke genera- capacitor start, include automatic reset thermal
tion. Factory-installed motors shall be UL approved. overload protection and are available in 115, 208,
1.03 DELIVERY, STORAGE AND HANDLING 230, or 277 volts (60 Hz). Three-phase motors are
Unit shall be handled and stored in accordance with available in 208, 230, or 460 volts (60 Hz). Motors
the manufacturer’s instructions. are resilient base mounted (except 3 and 5 hp
motors, which are rigid base mounted).
Part 2 — Products
G. Options and Accessories:
2.01 EQUIPMENT
1. Factory-Installed Options:
A. General:
a. Coils:
Factory-assembled, horizontal and vertical, draw-
thru type fan coil unit for ducted installation above 1) Unit coil(s) shall be equipped with auto-
the ceiling or floor mounting. Unit shall be complete matic air vent(s).
with water coils, fan(s), motor, belt drive, drain pan, 2) Unit shall be equipped with a high-
and filter. capacity 6-row or 8-row coil for installa-
tion in a 2-pipe system.
B. Casing:
3) For installation in a 4-pipe system, unit
Construction shall be heavy-gage galvanized steel, shall be equipped with either a 4-row
lined with one-in. thick fiberglass Tuf-Skin™ II cooling/1-row hot water heating split-
thermal/acoustical insulation. Knockouts shall be circuit coil, or a 4/2, 6/1, or 6/2 split-
provided for hanging the horizontal unit, that will circuit coil as required.
accept 3/8-in. threaded rod at the top, and bottom 4) Unit shall be equipped with either a 4-
of all unit corners. Supply and return duct connec- row DX (direct expansion) cooling coil
tion shall be 1 in. long. Removable side panels shall or a 6-row DX cooling coil as required.
be provided for access to the fan/motor assembly. A 5) Unit coil(s) shall be copper fin, copper
double-sloped drain pan shall be constructed of tube with stainless steel tube and sheets.
stainless steel, extending under the full length and b. Filters:
width of the coil(s) with a 3/4-in. male nominal pipe
thread stainless steel drain connection and 1/2-in. 1) A two-in. pleated filter shall be installed
in the unit (standard).

39
Guide specifications (cont)
2) One-in. pleated, (2) 1-in. throwaway or 2) Mixing boxes shall include
2-in pleated MERV 11 filters with 2-in. a linkage kit, which consists of two
pre-filter shall be installed as indicated crank arms, 2 swivels and a rod, 25 in.
on the equipment schedule. long (for unit sizes 06-16) or 84 in.
c. Insulation: long (for unit sizes 20-40), for the field
installation of the actuator.
1) Units shall be equipped with 1-in. thick
Tuf-Skin™ II insulation (standard). b. Thermostats:
2) Units are available with ¾-in. closed Three thermostats shall be available for
cell, 1-in. Tuf-Skin Rx™ edge sealed, field installation:
or 1-in. foil-faced insulation. 1) The single stage heat thermostat shall
d. Controls: feature manual changeover, off-cool-
1) Unit shall be equipped with 24-v trans- heat system switch, on-auto fan mode
former, motor contactor and terminal switch, single-stage electric heat, and
strip for connection to field or factory outside air signal.
provided controller. 2) The 2-stage heat thermostat shall fea-
2) Unit shall be equipped with interlock- ture automatic/manual changeover,
ing door-disconnect switch, touch-type digital display of temperatures and all
fusing, 24-v transformer, motor con- functions, off-cool-heat-auto system
tactor and terminal strip for connec- mode buttons, single speed fan opera-
tion to field provided controller. tion, on-auto fan mode button, single
3) Unit shall be equipped with interlock- or two stage electric heat signal, out-
ing door-disconnect switch, separate side air signal and optional remote
motor and electric heater touch-type temperature sensor.
fusing, 24-v transformer, motor con- 3) The single-stage heat, 2-pipe heat/
tactor and terminal strip for connec- cool thermostat shall feature digital
tion to field-provided or factory- display of ambient temperature and
provided controller. operating mode, single fan speed oper-
ation, power and operating mode but-
e. Motor(s): tons, continuous fan operation, cycling
Single-phase motors are capacitor start and water control valve, 4-pipe automatic
shall include automatic reset thermal over- changeover/manual changeover with
load protection and shall be available in “on-auto” fan mode button, optional
115, 208, 230, or 277 volts (60 Hz). one or 2-stage electric heat signal, and
Three-phase motors shall be available in purge cycle, temperature sensor for
208, 230, or 460 volts (60 Hz). 2-pipe cold water/hot water systems,
f. Electric Heat: and programmable operating range,
1) Electric heaters shall be constructed of dead band, digital display, tempera-
high-grade resistance wire supported ture set-back.
by ceramic insulators on plated steel c. Valve Packages:
brackets. The heat elements shall be 1) Valve packages shall be factory-
suspended in front of the outlet, after assembled for field installation.
the blower and coil. High-limit thermal 2) Basic valve packages shall include
cutouts shall protect the heat elements 2-way or 3-way valves with balancing
in the event of an air failure. valves and 2 ball valves.
2) Single-phase heaters shall be available 3) Deluxe valve packages shall include a
in 115, 208, 230, or 277 volts (60 circuit setting and a strainer in addition
Hz). Three-phase electric heat shall be to the features included in the basic
available in 208, 230, or 460 volts (60 valve package.
Hz).
2. Field-Installed Accessories:
a. Mixing Boxes:
1) Mixing boxes shall be preassembled at
the factory and shipped separately with
base rails.

Carrier Corporation • Syracuse, New York 13221 9-05A 9-05


Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3 New Book 4 Pg 40 Catalog No. 524-236 Printed in U.S.A. Form 42B-1PD