PERFORMANCE
CHECK POINT CARRIED NOT
OUT APPLICABLE
01) Complete installation as per the
approved drawing
02) Manifold leak test, at 7 Bar with
main valve closed for 02 minutes
03) Down stream pipe leak test at 7 Bar
with nozzle ends blanked (for 02
Minutes)
04) Time delay and cylinder actuator
operation test (operating all actuators
after 30 seconds) from Control
Station I
05) Pilot discharge line leak test at 7 bar
for 2 minutes from Control Station I
06) Distribution Main Valve function test
(Main Valve for Engine Room / Pump
Room & SCR Room) from Control
Station I
07) Function test for audible & visual
alarms, ventilation & blower shutdown
test from Control Station I
08) Time delay and cylinder actuator
operation test (operating all actuators
after 30 seconds) from Control
Station II
09) Pilot discharge line leak test at 7 bar
for 2 minutes from Control Station II
10) Distribution Main Valve function test
(Main Valve for Engine Room / Pump
Room & SCR Room) from Control
Station II
PERFORMANCE
CHECK POINT CARRIED NOT
OUT APPLICABLE
11) Function test for audible & visual
alarms, ventilation & blower shutdown test
from Control Station II
12) CO 2 Operating Instructions &
evacuation sign board checked
13) Reset the system
REMARKS: …………………………………………………………………………………….
……………………………………………………………………………………
RIG REPRESENTATIVE
NAME : _________________
TITLE : __________________
DATE : __________________