Woldia University: A Non Ideal Transformer
Woldia University: A Non Ideal Transformer
Woldia University: A Non Ideal Transformer
3. Iron losses
Since the iron core is subjected to alternating flux, there occurs eddy current and
hysteresis loss in it. These two losses together are known as iron losses or core
losses. The iron losses depend upon the supply frequency, maximum flux density
in the core, volume of the core etc. It may be noted that magnitude of iron losses is
quite small in a practical transformer.
From the above phasor diagram the no-load primary current I0 can be resolved into
two rectangular components:
1. The component IW in phase with the applied voltage V1. This is known as
active or working or iron loss component and supplies the iron loss and a
very small primary copper loss.
IW = I0 cos 0
Now: I02 =IW2+Im2 then Im= 𝐼𝑂2 − 𝐼𝑤2 = 0.62 − 0.1822 =0.572A
(b)
Im= 𝐼𝑂2 − 𝐼𝑤2 = 0.52 − 0.152 =0.476A
2. Practical Transformer on Load
We shall consider two cases (i) when such a transformer is assumed to have no
winding resistance and leakage flux (ii) when the transformer has winding
resistance and leakage flux.
1. No winding resistance and leakage flux
As shows a practical transformer with the assumption that resistances and leakage
reactances of the windings are negligible, with this assumption, V2 = E2 and V1 =
E1. Let us take the usual case of inductive load which causes the secondary current
I2 to lag the secondary voltage V2 by 2. The total primary current I1 must meet two
requirements viz.
(a) It must supply the no-load current I0 to meet the iron losses in the transformer
and to provide flux in the core.
(b) It must supply a current I'0 to counteract the demagnetizing effect of secondary
currently I2. The magnitude of I'2 will be such that:
N1I'2 N2I2
N2I2
I’= =KI2
N1
The total primary current I1 is the phasor sum of I'2 and I0 i.e.,
I1 I'2 I0, where:
I1 = I'2 + I0
Where: I'2 = KI2
V1=E1+I1 (R1+X1)
V2 = E2 I2 (R2 + jX2)
= E2 I2Z2
Po= Re (V2I2*) and pin =Re (V1I1*)
Example: A 23-kVA, 2300/230-V, 60 HZ step-down transformer has the following
resistance and leakage-reactance values: R1 = 4Ω, R2 = 0.04 Ω, X1 = 12 Ω, and
X2 = 0.12 Ω. The transformer is operating at 75% of its rated load. If the power
factor of the load is 0.866 leading, determine the efficiency of the transformer.
Solution: Since the transformer is operating at 75% of its rated load, the effective
value of the secondary winding current is:
Assuming the load voltage as a reference, the load current at a leading power factor
of 0.866, in phasor form, is:
2300
Since the transformation ratio is: K or a = = 10
230
We can determine the induced emf and the current on the primary side as:
N1 V1 I2
Since from the voltage transformation ratio = = =K
N2 V2 I1
V2 𝑉1
Z2= 𝑎𝑛𝑑 𝑍1 = 𝑡ℎ𝑒𝑛
𝐼2 𝐼1
𝑍1 𝑉1 𝐼2 𝑍1
= 𝐼1
= 𝐾2 : = 𝐾2
𝑍2 𝑉2 𝑍2
𝑅1 𝑋1
Similarly: = K2 𝑎𝑛𝑑 =K2
𝑅2 𝑋2
Note the importance of above relations. We can transfer the parameters from
one winding to the other. Thus:
A resistance R1 in the primary becomes R1/ K2 when transferred to the
secondary.
A resistance R2 in the secondary becomes K2 R2 when transferred to the
primary.
A reactance X1 in the primary becomes X1/ K2 when transferred to the
secondary.
A reactance X2 in the secondary becomes K2 X2 when transferred to the
primary.
It is important to remember that:
1. Referred to primary
When secondary resistance or reactance is transferred to the primary, it is
multiplied by K2. It is then called equivalent secondary resistance or reactance
referred to primary and is denoted by R'2 or X'2.
Equivalent resistance of transformer referred to primary
R01=R1+R’2=R1+K2R2
Equivalent reactance of transformer referred to primary
X02=X1+X’2=X1+K2X2
Equivalent impedance of transformer referred to primary
Z01= R201 + X012
Referred to secondary
When primary resistance or reactance is transferred to the secondary, it is
multiplied by K2. It is then called equivalent primary resistance or reactance
referred to the secondary and is denoted by R'1 or X'1.
Exact Equivalent Circuit of a Loaded Transformer
The following figure shows the exact equivalent circuit of a transformer on load.
Here R1 is the primary winding resistance and R2 is the secondary winding
resistance. Similarly, X1 is the leakage reactance of primary winding and X2 is the
leakage reactance of the secondary winding. The parallel circuit R0 X0 is the no-
load equivalent circuit of the transformer. The resistance R0 represents the core
losses (hysteresis and eddy current losses) so that current IW which supplies the
core losses is shown passing through R0. The inductive reactance X0 represents a
loss-free coil which passes the magnetizing current Im.
Similarly the figure below shows the approximate equivalent circuit as referred to
the secondary side of the transformer.
Thus open-circuit test enables us to determine iron losses and parameters R0 and
X0 of the transformer.
Where:
The power factor is always lagging for a real transformer, so the angle of the
current always lags the angle of the voltage by θ degrees. Therefore, the
admittance YE is:
Similarly shot circuit is used to determine the series impendence such as resistance
and inductance of the transformers. Thus:
and is lagging. The current angle is thus negative, and the overall impedance angle
θ is positive:
(a) Find the equivalent circuit of the transformer referred to the high-voltage side.
(b) Find the equivalent circuit of this transformer referred to the low-voltage side.
Solution:
(a) The turns ratio of this transformer is a = 2300/230 = 10. The excitation branch
values of the transformer equivalent circuit referred to the secondary (low voltage)
side can be calculated from the open-circuit test data, and the series elements
referred to the primary (high voltage) side can be calculated from the short-circuit
test data. From the open-circuit test data, the open-circuit impedance angle is:
The resulting simplified equivalent circuit referred to the primary side can be
found by convel1ing the excitation branch values to the primary side.
iii. The short-circuit test enables us to determine R01 and X01 (or R02 and X02).
We can thus find the total voltage drop in the transformer as referred to
primary or secondary. This permits us to calculate voltage regulation of the
transformer.
Performance of the Transformer
The performances of the transformer are determined by voltage regulation and
efficiency of the transformer.
Voltage regulation of the transformer
Voltage regulation is a quantity that compares the output voltage of the transformer
at no load with the output voltage at full load.
Where: V2NL and V2FL, are the effective values of no-load and full-load voltages at
the secondary terminal. The smaller the voltage regulation, the better the operation
of the transformer. The expressions for the percent voltage regulation for the
approximate equivalent circuits as viewed from the primary and the secondary
sides are:
Since at no load, Vs = VP/a, the voltage regulation can also be expressed as:
Depending on this formula the voltage regulation can be determine by the phasor
diagram. So, the phasor diagram for lagging, unity and leading power factor
respectively is:
Because the input power is the sum of output power and power losses.
The output power is given as:
The losses of the transformer are also core and copper losses:
power core loss: and power copper losses:
a) Find the equivalent circuit of the transformer referred to the high-voltage side.
(b) Find the equivalent circuit of this transformer referred to the low-voltage side.
(c) Calculate the full-load voltage regulation at 0.8 lagging power factor, 1.0
power factor, and at 0.8 leading power factor using the exact equation for V p.
(d) Plot the voltage regulation as load is increased from no load to full load at
power factors of 0.8 lagging, 1.0, and 0.8 leading.
(e) What is the efficiency of the transformer at full load with a power factor of 0.8
lagging?
Solution:
(a) The turns ratio of this transformer is a = 2300/230 = 10
To calculate Vp/a,:
The phasor diagram in the current and voltage with respect to lagging,
unity and leading power factor respectively is:
e) To find the efficiency of the transformer, first calculate its losses. The copper
(