Chapter 11 Summary of Parameter Settings: 00 Drive Parameters
Chapter 11 Summary of Parameter Settings: 00 Drive Parameters
Chapter 11 Summary of Parameter Settings: 00 Drive Parameters
com
Chapter 11 Summary of Parameter SettingsMS300
This chapter provides summary of parameter settings for user to gather the parameter setting ranges,
factory settings and set parameters. The parameters can be set, changed and reset by the digital keypad.
NOTE
00 Drive Parameters
Factory
Pr. Explanation Settings
Setting
102: 110 V, 1 Phase, 0.25 HP
103: 110 V, 1 Phase, 0.5 HP
104: 110 V, 1 Phase, 1 HP
302: 230 V, 1 Phase, 0.25 HP
303: 230 V, 1 Phase, 0.5 HP
304: 230 V, 1 Phase, 1 HP
305: 230 V, 1 Phase, 2 HP
306: 230 V, 1 Phase, 3 HP
202: 230 V, 3 Phase, 0.25 HP
203: 230 V, 3 Phase, 0.5 HP
204: 230 V, 3 Phase, 1 HP
205: 230 V, 3 Phase, 2 HP
206: 230 V, 3 Phase, 3 HP
207: 230 V, 3 Phase, 5 HP
Identity code of the AC motor Read
00-00 208: 230 V, 3 Phase, 7.5 HP
drive only
209: 230 V, 3 Phase, 10 HP
210: 230 V, 3 Phase, 15 HP
211: 230 V, 3 Phase, 20 HP
403: 460 V, 3 Phase, 0.5 HP
404: 460 V, 3 Phase, 1 HP
405: 460 V, 3 Phase, 2 HP
406: 460 V, 3 Phase, 3 HP
407: 460 V, 3 Phase, 5 HP
408: 460 V, 3 Phase, 7.5 HP
409: 460 V, 3 Phase, 10 HP
410: 460 V, 3 Phase, 15 HP
411: 460 V, 3 Phase, 20 HP
412: 460 V, 3 Phase, 25 HP
413: 460 V, 3 Phase, 30 HP
11-1
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
Display AC motor drive rated Read
00-01 Display by models
current only
0: No function
1: Parameter write protect
5: Reset KWH display to 0
6: Reset PLC
7: Reset CANopen index (Slave)
8: Keypad doesn't respond
9: All parameters are reset to factory settings
(base frequency is 50 Hz)
00-02 Parameter reset 0
10: All parameters are reset to factory settings
(base frequency is 60 Hz)
11: All parameters are reset to factory settings
(base frequency is 50 Hz) (saving the setting value of
user defined parameter 13-01~13-50)
12: All parameters are reset to factory settings
(base frequency is 60 Hz) (saving the setting value of
user defined parameter 13-01~13-50)
0: F (frequency command)
1: H (output frequency)
00-03 Start-up display selection 0
2: U (multi-function display, see Pr. 00-04)
3: A (output current)
0: Display output current (A) (Unit: Amps)
1: Display counter value (c) (Unit: CNT)
2: Display actual output frequency (H.) (Unit: Hz)
3: Display DC-BUS voltage (v) (Unit: Vdc)
4: Display output voltage (E) (Unit: Vac)
5: Display output power angle (n) (Unit: deg)
6: Display output power in kW (P) (Unit: Kw)
7: Display actual motor speed rpm (Unit: rpm)
Content of multi-function 10: Display PID feedback (b) (Unit: %)
00-04 3
display (user defined) 11: Display signal value of AVI analog input terminal (1.)
(Unit: %)
12: Display signal value of ACI analog input terminal (2.)
(Unit: %)
14: Display the temperature of IGBT (i.) (Unit: oC)
16: The status of digital input (ON / OFF) (i)
17: Display digital output status ON / OFF (o)
18: Display the multi-stage speed that is executing (S)
19: The corresponding CPU pin status of digital input (d)
11-2
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
20: The corresponding CPU pin status of digital output (0.)
22: Pulse input frequency (S.)
23: Pulse input position (q.)
25: Overload counting (0.00~100.00 %) (o.) (Unit: %)
26: GFF ground fault (G.) (Unit: %)
27: DC Bus voltage ripple (r.) (Unit: %)
28: Display PLC register D1043 data (C)
30: Display output of user defined (U)
31: H page x 00-05 display user gain (K)
35: Control mode display: 0 = speed control mode (SPD)
36: Present operating carrier frequency of drive (Hz) (J.)
38: Display drive status (6.)
41: KWH display (J) (Unit: kWh)
42: PID target value (h.) (Unit: %)
43: PID offset (o.) (Unit: %)
44: PID output frequency (b.) (Unit: Hz)
46: Display auxiliary frequency value (U.) (Unit: Hz)
47: Display master frequency value (A.) (Unit: Hz)
48: Display frequency value after addition and subtraction
of auxiliary and master frequency (L.) (Unit: Hz)
Coefficient gain in actual
00-05 0~160.00 1.00
output frequency
00-06 Software version Read only #.#
Parameter protection 0~65535
00-07 0
password input 0~3 (the times of password attempts)
0~65535
Parameter protection 0: No password protection / password is entered correctly
00-08 0
password setting (Pr. 00-07)
1: Password has been set
00-10 Control mode 0: Speed mode 0
0: VF (IM V/F control)
00-11 Control of speed mode 1: VFPG (IM V/F control + Encoder) 0
2: SVC (Pr. 05-33 set as IM or PM)
0: Normal load
00-16 Load selection 1
1: Heavy load
Normal load: 2~15 KHz 4
00-17 Carrier frequency
Heavy load: 2~15 KHz 4
bit 0: Control command forced by PLC control Read
00-19 PLC command mask
bit 1: Frequency command forced by PLC control Only
11-3
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Digital keypad
1: Communication RS-485 input
2: External analog input (Refer to Pr. 03-00)
3: External UP / DOWN terminal
4: Pulse input without direction command
Source of the master
00-20 (Refer to Pr. 10-16 without direction) 0
frequency command (AUTO)
6: CANopen communication card
7: Digital keypad dial
8: Communication card (not includes CANopen card)
[Note]:
Need to use with MO setting as 42, or use with KPC-CC01
0: Digital keypad
1: External terminals
2: Communication RS-485 input
Source of the operation
00-21 3: CANopen communication card 0
command (AUTO)
5: Communication card (not includes CANopen card)
[Note]:
Need to use with MO setting as 42, or use with KPC-CC01
0: Ramp to stop
00-22 Stop method 0
1: Coast to stop
0: Enable forward / reverse
00-23 Control of motor direction 1: Disable reverse 0
2: Disable forward
Memory of digital operator Read
00-24 Read only
(Keypad) frequency command only
11-4
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
bit 4~15: user defined unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
004xh: M/S
005xh: kW
006xh: HP
007xh: PPM
008xh: l /m
009xh: kg/s
00Axh: kg/m
00Bxh: kg/h
00Cxh: lb/s
00Dxh: lb/m
00Exh: lb/h
00Fxh: ft/s
010xh: ft/m
011xh: M
012xh: ft
013xh: degC
014xh: degF
015xh: mbar
016xh: bar
017xh: Pa
018xh: kPa
019xh: mWG
01Axh: inWG
01Bxh: ftWG
01Cxh: Psi
01Dxh: Atm
01Exh: L/s
01Fxh: L/m
020xh: L/h
021xh: m3/s
022xh: m3/h
023xh: GPM
024xh: CFM
11-5
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Disable
0~65535 (when Pr. 00-25 set to no decimal place)
00-26 Max. user defined value 0.0~6553.5 (when Pr. 00-25 set to 1 decimal place) 0
0.0~655.35 (when Pr. 00-25 set to 2 decimal place)
0.0~65.535 (when Pr. 00-25 set to 3 decimal place)
Read
00-27 User defined value Read only
only
0: Standard HOA function
1: Switching Local / Remote, the drive stops
2: Switching Local / Remote, the drive runs as the
REMOTE setting for frequency and operation status
3: Switching Local / Remote, the drive runs as the LOCAL
00-29 LOCAL / REMOTE selection 0
setting for frequency and operation status
4: Switching Local / Remote, the drive runs as LOCAL
setting when switch to Local and runs as REMOTE
setting when switch to Remote for frequency and
operation status.
0: Digital keypad
1: Communication RS-485 input
2: External analog input (Refer to Pr. 03-00)
3: External UP / DOWN terminal
4: Pulse input without direction command
Source of the master
00-30 (Refer to Pr. 10-16 without direction) 0
frequency command (HAND)
6: CANopen communication card
7: Digital keypad dial
8: Communication card (not includes CANopen card)
[Note]:
Need to use with MO setting as 41, or use with KPC-CC01
0: Digital keypad
1: External terminals
2: Communication RS-485 input
Source of the operation
00-31 3: CANopen communication card 0
command (HAND)
5: Communication card (not includes CANopen card)
[Note]:
Need to use with MO setting as 41, or use with KPC-CC01
0: STOP key disable
00-32 Digital keypad STOP function 0
1: STOP key enable
11-6
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Master and auxiliary frequency function disabled
1: By digital keypad
2: By communication RS-485 input
3: By analog input
00-35 Source of auxiliary frequency 0
4: By external Up / Down key input
5: Pulse input with steering command (refer to Pr. 10-16)
6: By CANopen
8: By communication card
0: Master + auxiliary frequency
Selection of master and
00-36 1: Master - auxiliary frequency 0
auxiliary frequency command
2: Auxiliary - master frequency
00-48 Display filter time (Current) 0.001~65.535 sec. 0.100
00-49 Display filter time (Keypad) 0.001~65.535 sec. 0.100
00-50 Software version (Date) Read only #####
11-7
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
01 Basic Parameters
Factory
Pr. Explanation Settings
Setting
60.00/
01-00 Max. operation frequency of motor 1 0.00~599.00 Hz
50.00
60.00/
01-01 Output frequency of motor 1 0.00~599.00 Hz
50.00
110 V / 230 V series: 0.0 V~255.0 V 220.0
01-02 Output voltage of motor 1
460 V series: 0.0~510.0 V 440.0
01-03 Mid-point frequency 1 of motor 1 0.00~599.00 Hz 3.00
110 V / 230 V series: 0.0 V~240.0 V 11.0
01-04 Mid-point voltage 1 of motor 1
460 V series: 0.0 V~480.0 V 22.0
01-05 Mid-point frequency 2 of motor 1 0.00~599.00 Hz 0.50
110 V / 230 V series: 0.0 V~240.0 V 2.0
01-06 Mid-point voltage 2 of motor 1
460 V series: 0.0 V~480.0 V 4.0
01-07 Min. output frequency of motor 1 0.00~599.00 Hz 0.00
110 V / 230 V series: 0.0 V~240.0 V 0.0
01-08 Min. output voltage of motor 1
460 V series: 0.0 V~480.0 V 0.0
01-09 Start-up frequency 0.00~599.00 Hz 0.50
01-10 Output frequency upper limit 0.00~599.00 Hz 599.00
01-11 Output frequency lower limit 0.00~599.00 Hz 0.00
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-12 Accel. time 1
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-13 Decel. time 1
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-14 Accel. time 2
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-15 Decel. time 2
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-16 Accel. time 3
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-17 Decel. time 3
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-18 Accel. time 4
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-19 Decel. time 4
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-20 JOG acceleration time
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
Pr. 01-45 = 0: 0.00~600.00 sec. 10.00
01-21 JOG deceleration time
Pr. 01-45 = 1: 0.00~6000.0 sec. 10.0
11-8
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
01-22 JOG frequency 0.00~599.00 Hz 6.00
st th
01-23 1 / 4 Accel. / decel. frequency 0.00~599.00 Hz 0.00
Pr. 01-45 = 0: 0.00~25.00 sec. 0.20
01-24 S-curve acceleration begin time 1
Pr. 01-45 = 1: 0.0~250.0 sec. 0.2
Pr. 01-45 = 0: 0.00~25.00 sec. 0.20
01-25 S-curve acceleration arrival time 2
Pr. 01-45 = 1: 0.0~250.0 sec. 0.2
Pr. 01-45 = 0: 0.00~25.00 sec. 0.20
01-26 S-curve deceleration begin time 1
Pr. 01-45 = 1: 0.0~250.0 sec. 0.2
Pr. 01-45 = 0: 0.00~25.00 sec. 0.20
01-27 S-curve deceleration arrival time 2
Pr. 01-45 = 1: 0.0~250.0 sec. 0.2
01-28 Skip frequency 1 (upper limit) 0.00~599.00 Hz 0.00
01-29 Skip frequency 1 (lower limit) 0.00~599.00 Hz 0.00
01-30 Skip frequency 2 (upper limit) 0.00~599.00 Hz 0.00
01-31 Skip frequency 2 (lower limit) 0.00~599.00 Hz 0.00
01-32 Skip frequency 3 (upper limit) 0.00~599.00 Hz 0.00
01-33 Skip frequency 3 (lower limit) 0.00~599.00 Hz 0.00
0: Output waiting
01-34 Zero-speed mode 1: Zero-speed operation 0
2: Fmin (Refer to Pr. 01-07, 01-41)
60.00/
01-35 Output frequency of motor 2 0.00~599.00 Hz
50.00
110 V / 230 V series: 0.0 V~255.0 V 220.0
01-36 Output voltage of motor 2
460 V series: 0.0~510.0 V 440.0
01-37 Mid-point frequency 1 of motor 2 0.00~599.00 Hz 3.00
110 V / 230 V series: 0.0 V~240.0 V 11.0
01-38 Mid-point voltage 1 of motor 2
460 V series: 0.0 V~480.0 V 22.0
01-39 Mid-point frequency 2 of motor 2 0.00~599.00 Hz 0.50
110 V / 230 V series: 0.0 V~240.0 V 2.0
01-40 Mid-point voltage 2 of motor 2
460 V series:0.0 V~480.0 V 4.0
01-41 Min. output frequency of motor 2 0.00~599.00 Hz 0.00
110 V / 230 V series: 0.0 V~240.0 V 0.0
01-42 Min. output voltage of motor 2
460 V series: 0.0 V~480.0 V 0.0
0: V/F curve determined by Pr. 01-00~01-08
01-43 V/F curve selection 1: 1.5th V/F curve 0
nd
2: 2 V/F curve
11-9
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Linear accel. / decel.
1: Auto accel., linear decel.
Auto acceleration / deceleration 2: Linear accel., auto decel.
01-44 0
setting 3: Auto accel. / decel.
4: Linear, stall prevention by auto accel. /
decel. (limited by Pr. 01-12 to 01-21)
Time unit for acceleration / 0: Unit 0.01 sec.
01-45 0
deceleration and S curve 1: Unit 0.1 sec.
Pr. 01-45 = 0: 0.00~600.00 sec.
01-46 Time for CANopen quick stop 1.00
Pr. 01-45 = 1: 0.0~6000.0 sec.
0: Normal decel.
01-49 Deceleration method 1: Overfluxing decel. 0
2: Traction energy control
60.00/
01-52 Max. operation frequency of motor 2 0.00~599.00 Hz
50.00
60.00/
01-53 Max. operation frequency of motor 3 0.00~599.00 Hz
50.00
60.00/
01-54 Output frequency of motor 3 0.00~599.00 Hz
50.00
110 V / 230V series: 0.0 V~255.0 V 220.0
01-55 Output voltage of motor 3
460 V series: 0.0 V~510.0 V 440.0
01-56 Mid-point frequency 1 of motor 3 0.00~599.00 Hz 3.00
110 V / 230 V series: 0.0 V~240.0 V 11.0
01-57 Mid-point voltage 1 of motor 3
460 V series: 0.0 V~480.0 V 22.0
01-58 Mid-point frequency 2 of motor 3 0.00~599.00 Hz 0.50
110 V / 230 V series: 0.0 V~240.0 V 2.0
01-59 Mid-point voltage 2 of motor 3
460 V series: 0.0 V~480.0 V 4.0
01-60 Min. output frequency of motor 3 0.00~599.00 Hz 0.00
110V / 230 V series: 0.0 V~240.0 V 0.0
01-61 Min. output voltage of motor 3
460 V series: 0.0 V~480.0 V 0.0
60.00/
01-62 Max. operation frequency of motor 4 0.00~599.00 Hz
50.00
60.00/
01-63 Output frequency of motor 4 0.00~599.00 Hz
50.00
110 V / 230 V series: 0.0 V~255.0 V 220.0
01-64 Output voltage of motor 4
460 V series: 0.0 V~510.0 V 440.0
01-65 Mid-point frequency 1 of motor 4 0.00~599.00 Hz 3.00
110V / 230 V series: 0.0 V~240.0 V 11.0
01-66 Mid-point voltage 1 of motor 4
460 V series: 0.0 V~480.0 V 22.0
01-67 Mid-point frequency 2 of motor 4 0.00~599.00 Hz 0.50
11-10
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
110 V / 230 V series: 0.0 V~240.0 V 2.0
01-68 Mid-point voltage 2 of motor 4
460 V series: 0.0 V~480.0 V 4.0
01-69 Min. output frequency of motor 4 0.00~599.00 Hz 0.00
110 V / 230V series: 0.0 V~240.0 V 0.0
01-70 Min. output voltage of motor 4
460 V series: 0.0 V~480.0 V 0.0
11-11
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
11-12
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
12: Output stop
13: Cancel the setting of auto accel. / decel. time
15: Rotating speed command from AVI
16: Rotating speed command from ACI
18: Forced to stop (Pr. 07-20)
19: Digital up command
20: Digital down command
21: PID function disabled
22: Clear counter command
23: Input the counter value (MI6)
24: FWD JOG command
11-13
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: UP / DOWN by the accel. / decel. time
1: UP / DOWN constant speed (Pr. 02-10)
02-09 UP / DOWN key mode 0
2: Pulse command (Pr. 02-10)
3: External terminals UP / DOWN mode
Constant speed. The accel. / decel.
02-10 0.001~1.000 Hz / ms 0.001
speed of the UP / DOWN Key
02-11 Digital input response time 0.000~30.000 sec. 0.005
02-12 Digital input mode selection 0000h~FFFFh (0: N.O.; 1: N.C.) 0000
02-13 Multi-function output 1 RY1 0: No function 11
02-16 Multi-function output 2 (MO1) 1: Indication during RUN 0
02-17 Multi-function output 3 (MO2) 2: Operation speed attained 0
3: Desired frequency attained 1 (Pr. 02-22)
4: Desired frequency attained 2 (Pr. 02-24)
5: Zero speed (Frequency command)
6: Zero speed, include STOP (Frequency
command)
7: Over torque 1 (Pr. 06-06~06-08)
8: Over torque 2 (Pr. 06-09~06-11)
9: Drive is ready
10: Low voltage warning (LV) (Pr. 06-00)
11: Malfunction indication
13: Overheat warning (Pr. 06-15)
14: Software brake signal indication (Pr. 07-00)
15: PID feedback error
16: Slip error (oSL)
17: Count value attained, does not return to 0
(Pr. 02-20)
18: Count value attained, returns to 0 (Pr. 02-19)
19: External interrupt B.B. input (Base Block)
20: Warning output
21: Over voltage warning
22: Over-current stall prevention warning
23: Over-voltage stall prevention warning
24: Operation source
25: Forward command
26: Reverse command
29: Output when frequency ≥ Pr. 02-34
30: Output when frequency < Pr. 02-34
31: Y-connection for the motor coil
11-14
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
32: △-connection for the motor coil
33: Zero speed (actual output frequency)
34: Zero speed include stop (actual output
frequency)
35: Error output selection 1 (Pr. 06-23)
36: Error output selection 2 (Pr. 06-24)
11-15
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
02-47 Zero-speed Level of Motor 0~65535 rpm 0
Status of multi-function input Read
02-50 Monitor the status of multi-function input terminals
terminal only
Status of multi-function output Monitor the status of multi-function output Read
02-51
terminal terminals only
Display external multi-function input Read
02-52 Monitor the status of PLC input terminals
terminals used by PLC only
Display external multi-function Read
02-53 Monitor the status of PLC output terminals
output terminals used by PLC only
Display memory of frequency Read
02-54 Read only
command used by external terminal only
Multi-function output terminal:
02-58 function 42: brake frequency 0.00~599.00 Hz 0.00
checking point
02-78 Gear ratio for simple index function 4.0~1000.0 200.0
02-79 Automatic positioning angle setting 0.0~6480.0 180.0
Automatic positioning deceleration 0.00 Function disable
02-80 0.00
time 0.01~100.00 s
EF active when terminal count value 0: Terminal count value attained, no EF display
02-81 0
attained 1: Terminal count value attained, EF active
0: By Current Freq. Command
Initial frequency command (F) mode
02-82 1: By Zero Freq. Command 0
after stop
2: Refer to Pr. 02-83 to set up
Initial frequency command (F)
02-83 0.00~599.0 Hz 60.00
setting after stop
11-16
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
11-17
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC Bus voltage
6: Power factor
7: Power
9: AVI
10: ACI
03-20 Multi-function output 1 (AFM) 12: Iq current command 0
13: Iq feedback value
14: Id current
15: Id feedback value
16: Vq-axis voltage command
17: Vd-axis voltage command
19: PG2 frequency command
20: CANopen analog output
21: RS-485 analog output
22: Communication card analog output
23: Constant voltage output
03-21 Gain of analog output (AFM) 0~500.0 % 100.0
0: Absolute value of output voltage
Analog output when in REV
03-22 1: Reverse output 0 V; Positive output 0-10 V 0
direction (AFM)
2: Reverse output 5-0 V; Positive output 5-10 V
03-27 AFM output bias -100.00~100.00 % 0.00
0: 0-10 V
03-28 AVI terminal input selection 0
3: -10 V ~ +10 V (Pr. 03-69 ~ 03-74 is valid)
0: 4-20 mA
03-29 ACI terminal input selection 1: 0-10 V 0
2: 0-20 mA
Monitor the status of PLC analog output terminals
bit 1: AFM
Status of PLC analog output Read
03-30 bit 2: AO10
terminal only
bit 3: AO11
.
0: 0-10 V output
03-31 AFM output selection 1: 0-20 mA output 0
2: 4-20 mA output
03-32 AFM DC output setting level 0.00~100.00 % 0.00
11-18
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
03-35 AFM filter output time 0.00 ~ 20.00 sec. 0.01
0:Disable
03-39 VR input selection 1
1:Frequency command
03-40 VR input bias -100.0~100.0 % 0.0
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
03-41 VR positive / negative bias 0
3: The absolute value of the bias voltage while
serving as the center
4: Serve bias as the center
03-42 VR gain -500.0~500.0 % 100.0
03-43 VR filter time 0~2.00 sec. 0.01
Multi-function MO output by source 0: AVI
03-44 0
of AI level 1: ACI
03-45 AI upper level 1 -100 % ~100.00 % 50
03-46 AI lower level 2 -100 % ~100.00 % 10
0: Regular Curve
1: 3 point curve of AVI (& AI10)
03-50 Analog input curve selection 2: 3 point curve of ACI (& AI11) 0
3: 3 point curve of AVI & ACI (& AI10 & AI11)
(AI10, AI11 is valid when extension card is installed)
03-29 = 1, 0.00~10.00 V
03-57 ACI lowest point 4.00
03-29 ≠ 1, 0.00~20.00 mA
03-58 ACI proportional lowest point 0.00~100.00 % 0.00
03-29 = 1, 0.00~10.00 V
03-59 ACI mid-point 12.00
03-29 ≠ 1, 0.00~20.00 mA
03-60 ACI proportional mid-point 0.00~100.00 % 50.00
03-29 = 1, 0.00~10.00 V
03-61 ACI highest point 20.00
03-29 ≠ 1, 0.00~20.00 mA
03-62 ACI proportional highest point 0.00~100.00 % 100.00
03-63 AVI voltage lowest point 0.00~10.00 V 0.00
AVI voltage proportional lowest
03-64 -100.00~100.00 % 0.00
point
03-65 AVI voltage mid-point 0.00~10.00 V 5.00
03-66 AVI voltage proportional mid-point -100.00~100.00 % 50.00
03-67 AVI voltage highest point 0.00~10.00 V 10.00
AVI voltage proportional highest
03-68 -100.00~100.00 % 100.00
point
11-19
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0.00~ -10.00 V
03-69 Negative AVI voltage lowest point 0.00
(valid when Pr. 03-28 set as -10 V ~ +10 V)
Negative AVI voltage proportional -100.00~100.00 %
03-70 0.00
lowest point (valid when Pr. 03-28 set as -10 V ~ +10 V)
0.00~ -10.00 V
03-71 Negative AVI voltage mid-point -5.00
(valid when Pr. 03-28 set as -10 V ~ +10 V)
Negative AVI voltage proportional -100.00~100.00 %
03-72 -50.00
mid-point (valid when Pr. 03-28 set as -10 V ~ +10 V)
0.00~ -10.00 V
03-73 Negative AVI voltage highest point -10.00
(valid when Pr. 03-28 set as -10 V ~ +10 V)
Negative AVI voltage proportional -100.00~100.00 %
03-74 -100.00
highest point (valid when Pr. 03-28 set as -10 V ~ +10 V)
11-20
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
11-21
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
05 Motor Parameters
Factory
Pr. Explanation Settings
Setting
0: No function
1: Dynamic test for induction motor (IM)
05-00 Motor parameter auto tuning 2: Static test for induction motor (IM) 0
13: High frequency stall test for PM synchronous
motor
Full-load current of induction
05-01 10~120 % of drive’s rated current #.##
motor 1 (A)
Rated power of induction motor 1
05-02 0~655.35 kW #.##
(kW)
Rated speed of induction motor 1 0~65535
05-03 1710
(rpm) 1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
05-04 Pole number of induction motor 1 2~20 4
No-load current of induction
05-05 0~ Pr. 05-01 factory setting #.##
motor 1 (A)
Stator resistance (Rs) of
05-06 0~65.535 #.###
induction motor 1
Rotor resistance (Rr) of induction
05-07 0~65.535 #.###
motor 1
Magnetizing inductance (Lm) of
05-08 0~6553.5 mH #.#
induction motor 1
Stator inductance (Lx) of
05-09 0~6553.5 mH #.#
induction motor 1
Full-load current of induction
05-13 10~120 % of drive’s rated current #.##
motor 2 (A)
Rated power of induction motor 2
05-14 0~655.35 kW #.##
(kW)
Rated speed of induction motor 2 0~65535
05-15 1710
(rpm) 1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
05-16 Pole number of induction motor 2 2~20 4
No-load current of induction
05-17 0~ Pr. 05-13 factory setting #.##
motor 2 (A)
Stator resistance (Rs) of
05-18 0~65.535 #.###
induction motor 2
Rotor resistance (Rr) of induction
05-19 0~65.535 #.###
motor 2
Magnetizing inductance (Lm) of
05-20 0~6553.5 mH #.#
induction motor 2
11-22
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
Stator inductance (Lx) of
05-21 0~6553.5 mH #.#
induction motor 2
1: Motor 1
2: Motor 2
05-22 Multi-motors (induction) selection 1
3: Motor 3 (VF or SVC control mode only)
4: Motor 4 (VF or SVC control mode only)
Frequency for Y-connection
05-23 /ᇞ-connection switch of induction 0.00~599.00 Hz 60.00
motor
Y-connection /ᇞ-connection 0: Disable
05-24 0
switch of induction motor 1: Enable
Delay time for Y-connection
05-25 /ᇞ-connection switch of induction 0.000~60.000 sec. 0.200
motor
Accumulative Watt-second of
05-26 Read only #.#
motor in low word (W-sec)
Accumulative Watt-second of
05-27 Read only #.#
motor in high word (W-sec)
Accumulative Watt-hour of motor
05-28 Read only #.#
(W-Hour)
Accumulative Watt-hour of motor
05-29 Read only #.#
in low word (KW-Hour)
Accumulative Watt-hour of motor
05-30 Read only #.#
in high word (KW-Hour)
Accumulative motor operation
05-31 00~1439 0
time (Min.)
Accumulative motor operation
05-32 00~65535 0
time (Day)
Induction motor or permanent 0: Induction Motor
05-33 magnet synchronous motors 1: SPM 0
selection 2: IPM
Full-load current of permanent
05-34 0~120 % of drive’s rated current #.#
magnet synchronous motor
Rated power of permanent
05-35 0.00~655.35 kW #.#
magnet synchronous motor
Rated speed of permanent
05-36 0~65535 rpm 2000
magnet synchronous motor
Pole number of permanent
05-37 0~65535 10
magnet synchronous motor
11-23
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
Stator resistance of permanent
05-39 0.000~65.535 0.000
magnet synchronous motor
Permanent magnet synchronous
05-40 0.00~655.35 mH 0.00
motor Ld
Permanent magnet synchronous
05-41 0.00~655.35 mH 0.00
motor Lq
Ke parameter of permanent
05-43 0.0~6553.5 (Unit: V / 1000 rpm) 0
magnet synchronous motor
Full-load current of induction
05-64 10~120 % of drive’s rated current #.##
motor 3 (A)
Rated power of induction motor 3
05-65 0~655.35 kW #.##
(kW)
Rated speed of induction motor 3 0~65535
05-66 1710
(rpm) 1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
05-67 Pole number of induction motor 3 2~20 4
No-load current of induction
05-68 0~ Pr. 05-64 factory setting #.##
motor 3 (A)
Stator resistance (Rs) of
05-69 0~65.535 #.###
induction motor 3
Full-load current of induction
05-70 10~120 % of drive’s rated current #.##
motor 4 (A)
Rated power of induction motor 4
05-71 0~655.35 kW #.##
(kW)
Rated speed of induction motor 4 0~65535
05-72 1710
(rpm) 1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
05-73 Pole number of induction motor 4 2~20 4
No-load current of induction
05-74 0~ Pr. 05-70 factory setting #.##
motor 4 (A)
Stator resistance (Rs) of
05-75 0~65.535 #.###
induction motor 4
11-24
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
11-25
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: No function
1: Continue operation after Over-torque detection
during constant speed operation
Over-torque detection selection 2: Stop after Over-torque detection during constant
06-09 0
(motor 2) speed operation
3: Continue operation after Over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
Over-torque detection level 10~250 % (100 % corresponds to the rated current
06-10 120
(motor 2) of the drive)
Over-torque detection time
06-11 0.0~60.0 sec. 0.1
(motor 2)
0: Inverter motor (with external forced cooling)
Electronic thermal relay selection 1
06-13 1: Standard motor (motor with fan on the shaft) 2
(motor 1)
2: Disabled
Electronic thermal relay action time
06-14 30.0~600.0 sec. 60.0
1 (motor 1)
Temperature level over-heat (OH)
06-15 0.0~110.0 oC 105.0
warning
06-16 Stall prevention limit level 0~100 % (Pr. 06-03, Pr. 06-04) 100
06-17 Fault record 1 0: No fault record 0
06-18 Fault record 2 1: Over-current during acceleration (ocA) 0
06-19 Fault record 3 2: Over-current during deceleration (ocd) 0
06-20 Fault record 4 3: Over-current during constant speed (ocn) 0
06-21 Fault record 5 4: Ground fault (GFF) 0
06-22 Fault record 6 6: Over-current at stop (ocS) 0
Fault record 7 (14-70) 7: Over-voltage during acceleration (ovA)
Fault record 8 (14-71) 8: Over-voltage during deceleration (ovd)
Fault record 9 (14-72) 9: Over-voltage during constant speed (ovn)
Fault record 10 (14-73) 10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Low-voltage at stop (LvS)
15: Phase loss protection (OrP)
16: IGBT over-heat (oH1)
18: TH1 open: IGBT over-heat protection error
( tH1o)
21: Drive over-load (oL)
22: Electronics thermal relay protection 1 (EoL1)
11-26
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
23: Electronics thermal relay protection 2 (EoL2)
24: Motor PTC overheat (oH3)
26: Over-torque 1 (ot1)
27: Over-torque 2 (ot2)
28: Low current (uC)
31: Memory read-out error (cF2)
33: U-phase current detection error (cd1)
34: V-phase current detection error (cd2)
35: W-phase current detection error (cd3)
36: Clamp current detection error (Hd0)
37: Over-current detection error (Hd1)
40: Auto tuning error (AUE)
41: PID feedback loss (AFE)
42: PG feedback error (PGF1)
43: PG feedback loss (PGF2)
44: PG feedback stall (PGF3)
45: PG slip error (PGF4)
48: Analog current input loss (ACE)
49: External fault input (EF)
50: Emergency stop (EF1)
51: External Base Block (bb)
52: Password error (Pcod)
54: Communication error (CE1)
55: Communication error (CE2)
56: Communication error (CE3)
57: Communication error (CE4)
58: Communication Time-out (CE10)
61: Y-connection / △-connection switch error (ydc)
62: Decel. Energy Backup Error (dEb)
63: Slip error (oSL)
72: Channel 1 (S1~DCM) safety loop error (STL1)
76: Safety torque off (STo)
77: Channel 2 (S2~DCM) safety loop error (STL2)
78: Internal loop error (STL3)
79: U phase Over current before run (Aoc)
80: V phase Over current before run (boc)
81: W phase Over current before run (coc)
82: U phase output phase loss (oPL1)
83: V phase output phase loss (oPL2)
84: W phase output phase loss (oPL3)
11-27
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
87: Drive over load in low frequency (oL3)
89: Initial rotor position detection error (roPd)
101: CANopen software disconnect 1 (CGdE)
102: CANopen software disconnect 2 (CHbE)
104: CANopen hardware disconnect (CbFE)
105: CANopen index setting error (CIdE)
106: CANopen station number setting error
(CAdE)
107: CANopen memory error (CFrE)
121: Internal communication error (CP20)
123: Internal communication error (CP22)
124: Internal communication error (CP30)
126: Internal communication error (CP32)
127: Software version error (CP33)
128: Over-torque 3 (ot3)
129: Over-torque 4 (ot4)
134: Electronics thermal relay 3 protection (EoL3)
135: Electronics thermal relay 4 protection (EoL4)
140: GFF detected when power on (Hd6)
141: GFF occurs before run (b4GFF)
142: Auto tuning error 1 (DC test stage) (AUE1)
143: Auto tuning error 2 (High frequency test stage)
(AUE2)
144: Auto tuning error 3 (Rotary test stage)
(AUE3)
06-23 Fault output option 1 0~65535 (refer to bit table for fault code) 0
06-24 Fault output option 2 0~65535 (refer to bit table for fault code) 0
06-25 Fault output option 3 0~65535 (refer to bit table for fault code) 0
06-26 Fault output option 4 0~65535 (refer to bit table for fault code) 0
11-28
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
Frequency command for Read
06-31 0.00~599.00 Hz
malfunction only
Read
06-32 Output frequency at malfunction 0.00~599.00 Hz
only
Read
06-33 Output voltage at malfunction 0.0~6553.5 V
only
Read
06-34 DC voltage at malfunction 0.0~6553.5 V
only
Read
06-35 Output current at malfunction 0.00~655.35 Amp
only
Read
06-36 IGBT temperature at malfunction 0.0~6553.5 oC
only
Capacitance temperature at Read
06-37 0.0~6553.5 oC
malfunction only
Read
06-38 Motor speed in rpm at malfunction 0~65535 rpm
only
Status of multi-function input Read
06-40 0000h~FFFFh
terminal at malfunction only
Status of multi-function output Read
06-41 0000h~FFFFh
terminal at malfunction only
Read
06-42 Drive’s status at malfunction 0000h~FFFFh
only
0: STO Latch
06-44 STO latch selection 0
1: STO No Latch
11-29
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Constant rated current and limit carrier wave by
load current and temperature
1: Constant carrier frequency and limit load current
06-55 Derating protection 0
by setting carrier wave
2: Constant rated current (same as setting 0), but
close current limit
06-56 PT100 voltage level 1 0.000~10.000 V 5.000
06-57 PT100 voltage level 2 0.000~10.000 V 7.000
06-58 PT100 level 1 frequency protect 0.00~599.00 Hz 0.00
Delay Time of Activating PT100
06-59 0~6000 sec. 60
Level 1 Frequency Protection
Software detection GFF current
06-60 0.0~6553.5 % 60.0
level
06-61 Software detection GFF filter time 0.00~655.35 sec. 0.10
Operation time of fault record 1 Read
06-63 0~65535 days
(Day) only
Operation time of fault record 1 Read
06-64 0~1439 min.
(Min.) only
Operation time of fault record 2 Read
06-65 0~65535 days
(Day) only
Operation time of fault record 2 Read
06-66 0~1439 min.
(Min.) only
Operation time of fault record 3 Read
06-67 0~65535 days
(Day) only
Operation time of fault record 3 Read
06-68 0~1439 min.
(Min.) only
Operation time of fault record 4 Read
06-69 0~65535 days
(Day) only
Operation time of fault record 4 Read
06-70 0~1439 min.
(Min.) only
06-71 Low current setting level 0.0 ~ 100.0 % 0.0
06-72 Low current detection time 0.00 ~ 360.00 sec. 0.00
0 : No function
1 : Warn and coast to stop
06-73 Treatment for low current 0
2 : Warn and ramp to stop by 2nd deceleration time
3 : Warn and operation continue
Operation time of fault record 5 Read
06-90 0~65535 days
(Day) only
Operation time of fault record 5 Read
06-91 0~1439 min.
(Min.) only
11-30
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
Operation time of fault record 6 Read
06-92 0~65535 days
(Day) only
Operation time of fault record 6 Read
06-93 0~1439 min.
(Min.) only
11-31
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
07 Special Parameters
Factory
Pr. Explanation Settings
Setting
110 V / 230 V: 350.0~450.0 Vdc 370.0
07-00 Software brake level
460 V: 700.0~900.0 Vdc 740.0
07-01 DC brake current level 0~100 % 0
07-02 DC brake time at startup 0.0~60.0 sec. 0.0
07-03 DC brake time at stop 0.0~60.0 sec. 0.0
07-04 DC brake start frequency 0.00~599.00 Hz 0.00
07-05 Voltage increasing gain 1~200 % 100
0: Stop operation
Restart after momentary power
07-06 1: Speed tracking by the speed before the power loss 0
loss
2: Speed tracking by minimum output frequency
07-07 Allowed power loss duration 0.0~20.0 sec. 2.0
07-08 Base block time 0.1~5.0 sec. 0.5
07-09 Current limit of speed tracking 20~200 % 100
0: Stop operation
07-10 Treatment of restart after fault 1: Speed tracking by current speed 0
2: Speed tracking by minimum output frequency
07-11 Restart times after fault 0~10 0
0: Disabled
1: Speed tracking by maximum output frequency
07-12 Speed tracking during start-up 0
2: Speed tracking by motor frequency at start
3: Speed tracking by minimum output frequency
0: Disabled
1: dEb with auto accel. / decal., the frequency will not
07-13 dEb function selection return after power recovery 0
2: dEb with auto accel. / decal., the frequency will
return after power recovery
07-15 Dwell time at accel. 0.00 ~ 600.00 sec. 0.00
07-16 Dwell frequency at accel. 0.00 ~ 599.00 Hz 0.00
07-17 Dwell time at decel. 0.00 ~ 600.00 sec. 0.00
07-18 Dwell frequency at decel. 0.00 ~ 599.00 Hz 0.00
0: Fan always ON
1: Fan will be OFF after the AC motor drive stops 1
minute
07-19 Fan cooling control 2: When the AC motor drive runs, the fan is ON. When 3
the AC motor drive stops, the fan is OFF
3: Fan turns ON when the temperature attain around
60 oC
11-32
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Coast to stop
1: Stop by 1st deceleration time
2: Stop by 2nd deceleration time
Deceleration of emergency or
07-20 3: Stop by 3rd deceleration time 0
forced stop th
4: Stop by 4 deceleration time
5: System Deceleration
6: Automatic Deceleration
0: Disabled
07-21 Auto energy-saving setting 0
1: Enabled
0: Enable AVR
Auto voltage regulation (AVR)
07-23 1: Disable AVR 0
function
2: Disable AVR during deceleration
0.0~100.0 %
07-29 Slip deviation level 0
0: No detection
11-33
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
Slip compensation gain 0.00~10.00
07-72 0.00
(motor 2) (Default value is 1 in SVC mode)
Torque compensation gain IM: 0~10 (when Pr. 05-33 = 0)
07-73 1
(motor 3) PM: 0~5000 (when Pr. 05-33 = 1 or 2)
Slip compensation gain
07-74 0.00~10.00 (Default value is 1 in SVC mode) 0.00
(motor 3)
Torque compensation gain IM: 0~10 (when Pr. 05-33 = 0)
07-75 1
(motor 4) PM: 0~5000 (when Pr. 05-33 = 1 or 2)
Slip compensation gain
07-76 0.00~10.00 (Default value is 1 in SVC mode) 0.00
(motor 4)
11-34
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
0: Parameter setting
08-16 PID compensation selection 0
1: Analog input
08-17 PID compensation -100.0 ~ +100.0 % 0
Setting of sleep mode 0: Refer to PID output command
08-18 0
function 1: Refer to PID feedback signal
08-19 Wakeup integral limit 0.0~200.0 % 50.0
11-35
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Serial connection
08-20 PID mode selection 0
1: Parallel connection
Enable PID to change 0: Operation direction can be changed
08-21 0
operation direction 1: Operation direction can not be changed
08-22 Wakeup delay time 0.00~600.00 sec. 0.00
bit 0 = 1, PID reverse running must follow the setting of
Pr. 00-23.
bit 0 = 0, PID reverse running refers to PID’s calculated
08-23 PID control flag 2
value.
bit 1 = 1, PID Kp gain is 2 decimal place
bit 1 = 0, PID Kp gain is 1 decimal place
PID output command limit
08-26 0.0~110.0 % 100.0
(reverse limit)
Acceleration / deceleration
08-27 0.00~655.35 sec. 0.00
time of PID command
0: PID control output 100.00 % corresponding to max.
Selection of frequency base
output frequency (Pr. 01-00)
08-29 corresponding to 100.00 % 0
1: PID control output 100.00 % corresponding to the
PID
input value of auxiliary frequency
11-36
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
09 Communication Parameters
Factory
Pr. Explanation Settings
Setting
09-00 Communication address 1~254 1
09-01 COM1 transmission speed 4.8~115.2 Kbps 9.6
11-37
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
09-21 Block transfer 11 0~65535 0
09-22 Block transfer 12 0~65535 0
09-23 Block transfer 13 0~65535 0
09-24 Block transfer 14 0~65535 0
09-25 Block transfer 15 0~65535 0
09-26 Block transfer 16 0~65535 0
0: Decoding Method 1
09-30 Communication decoding method 1
1: Decoding Method 2
09-33 PLC command force to 0 0~65535 0
09-35 PLC address 1~254 2
0: Disable
09-36 CANopen slave address 0
1~127
0: 1 Mbps
1: 500 Kbps
2: 250 Kbps
09-37 CANopen speed 0
3: 125 Kbps
4: 100 Kbps (Delta only)
5: 50 Kbps
bit 0: CANopen software disconnection 1 (CANopen
Guarding Time out)
bit 1: CANopen software disconnection 2 (CANopen
Heartbeat Time out)
09-39 CANopen warning record bit 3: CANopen SDO Time out 0
bit 4: CANopen SDO buffer overflow
bit 5: CANopen hardware disconnection warning
(Can Bus Off)
bit 6: Error protocol of CANopen
0: Delta defined decoding method
09-40 CANopen decoding method 1
1: CANopen Standard DS402 protocol
0: Node reset state
1: Com reset state
2: Boot up state Read
09-41 CANopen communication status
3: Pre operation state Only
4: Operation state
5: Stop state
11-38
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Not ready for use state
1: Inhibit start state
2: Ready to switch on state
3: Switched on state Read
09-42 CANopen control status
4: Enable operation state Only
7: Quick Stop Active state
13: Error reaction activation state
14: Error state
bit 0: CANopen reset, the internal address 20XX is 0
bit 1: CANopen reset, the internal address 264X is 0
09-43 CANopen reset index 65535
bit 2: CANopen reset, the internal address 26AX is 0
bit 3: CANopen reset, the internal address 60XX is 0
0: No communication card
1: DeviceNet slave
2: Profibus-DP slave
Identifications for communication
09-60 3: CANopen slave ##
card
4: Modbus-TCP slave
5: EtherNet/IP slave
10: Backup power supply
Firmware version of communication
09-61 Read only ##
card
09-62 Product code Read only ##
09-63 Error code Read only ##
DeviceNet: 0-63
09-70 Address of communication card 1
Profibus-DP: 1-125
Standard DeviceNet:
0: 125 Kbps
1: 250 Kbps
2: 500 Kbps
3: 1 Mbps (Delta Only)
Non-standard DeviceNet: (Delta Only)
0: 10 Kbps
09-71 Setting of DeviceNet speed 1: 20 Kbps 2
2: 50 Kbps
3: 100 Kbps
4: 125 Kbps
5: 250 Kbps
6: 500 Kbps
7: 800 Kbps
8: 1 Mbps
11-39
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
0: Disable
In this mode, baud rate can only be 125 Kbps,
250 Kbps, 500 Kbps, 1 Mbps in standard
09-72 Other setting of DeviceNet speed DeviceNet speed 0
1: Enable
In this mode, the baud rate of DeviceNet can be
same as CANopen (0-8).
IP Configuration of the 0: Static IP
09-75 0
communication card 1: Dynamic IP (DHCP)
IP address 1 of the communication
09-76 0~255 0
card
IP address 2 of the communication
09-77 0~255 0
card
IP address 3 of the communication
09-78 0~255 0
card
IP address 4 of the communication
09-79 0~255 0
card
Address mask 1 of the
09-80 0~255 0
communication card
Address mask 2 of the
09-81 0~255 0
communication card
Address mask 3 of the
09-82 0~255 0
communication card
Address mask 4 of the
09-83 0~255 0
communication card
Getway address 1 of the
09-84 0~255 0
communication card
Getway address 2 of the
09-85 0~255 0
communication card
Getway address 3 of the
09-86 0~255 0
communication card
Getway address 4 of the
09-87 0~255 0
communication card
Password for communication card
09-88 0~99 0
(low word)
Password for communication card
09-89 0~99 0
(high word)
0: No function
09-90 Reset communication card 0
1: Reset, return to factory setting
11-40
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
bit 0: Enable IP filter
bit 1: Internet parameters enable (1 bit)
When IP address is set up, this bit will be
enabled. After updating the parameters of
communication card, this bit will change to
Additional setting for
09-91 disable. 0
communication card
bit 2: Login password enable (1 bit)
When enter login password, this bit will be
enabled. After updating the parameters of
communication card, this bit will change to
disable.
bit 0: Password enable
When the communication card is set with
09-92 Status of communication card 0
password, this bit will be enabled. When the
password is clear, this bit will be disabled.
11-41
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
11-42
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
Frequency point when switch
10-39 from I/F mode to PM sensorless 0.00~599.00 Hz 20.00
mode.
Frequency when switch from
10-40 PM sensorless observer mode 0.00~599.00 Hz 20.00
to V/F mode.
Initial angle detection pulse
10-42 0.0~3.0 1.0
value
10-49 Zero voltage time while start up 00.000~60.000 sec. 00.000
10-51 Injection frequency 0~1200 Hz 500
15.0/
10-52 Injection magnitude 0.0~200.0 V
30.0
0: Disabled
1: Internal 1/4 rated current attracting the rotor to
10-53 Position detection method zero degrees 0
2: High frequency injection
3: Pulse injection
11-43
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
11 Advanced Parameters
Factory
Pr. Explanation Settings
Setting
bit 3: Dead Time compensation closed
11-00 System control 0
bit 7: Selection to save or not save the frequency
11-06 ASR 1 gain 0~40 Hz (IM) / 1~100 Hz (PM) 10
11-07 ASR 1 integral time 0.000~10.000 sec. 0.100
0: 2-phase
11-41 PWM mode selection 2
2: Space vector
11-42 System control flag 0000~FFFFh 0000
11-44
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
11-45
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
11-46
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com
CALL NOW 800-985-6929 http://www.deltaacdrives.com Email: info@deltaacdrives.com
Chapter 11 Summary of Parameter SettingsMS300
Factory
Pr. Explanation Settings
Setting
Read
14-69 IGBT temperature at malfunction 6 -3276.7~3276.7 oC
only
14-70 Fault record 7 Refer to fault record Pr. 6-17~06-22 0
14-71 Fault record 8 Refer to fault record Pr. 6-17~06-22 0
14-72 Fault record 9 Refer to fault record Pr. 6-17~06-22 0
14-73 Fault record 10 Refer to fault record Pr. 6-17~06-22 0
0: No function
1: Continue operation after Over-torque detection
during constant speed operation
Over-torque detection selection 2: Stop after Over-torque detection during constant
14-74 0
(motor 3) speed operation
3: Continue operation after Over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
10~250 % (100 % corresponds to the rated current
14-75 Over-torque detection level (motor 3) 120
of the drive)
14-76 Over-torque detection time (motor 3) 0.0~60.0 sec. 0.1
0: No function
1: Continue operation after Over-torque detection
during constant speed operation
Over-torque detection selection 2: Stop after Over-torque detection during constant
14-77 0
(motor) speed operation
3: Continue operation after Over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
10~250 % (100 % corresponds to the rated current
14-78 Over-torque detection level (motor 4) 120
of the drive)
14-79 Over-torque detection time (motor 4) 0.0~60.0 sec. 0.1
0: Inverter motor (with external forced cooling)
Electronic thermal relay selection 3
14-80 1: Standard motor (motor with fan on the shaft) 2
(motor 3)
2: Disabled
Electronic thermal relay action time 3
14-81 30.0~600.0 sec. 60.0
(motor 3)
0: Inverter motor (with external forced cooling)
Electronic thermal relay selection 4
14-82 1: Standard motor (motor with fan on the shaft) 2
(motor 4)
2: Disabled
Electronic thermal relay action time 4
14-83 30.0~600.0 sec. 60.0
(motor 4)
11-47
CALL
Downloaded from NOW 800-985-6929
www.Manualslib.com manuals search engine http://www.deltaacdrives.com Email: info@deltaacdrives.com