INGEDRIVE LV 400 Frequency converters

air or water-cooled, low-voltage

The LV400 series of the INGEDRIVE™ converter range is composed of low-voltage frequency
converters. They are designed to control induction, synchronous or permanent magnet motors in a
wide range of industrial and marine applications. Its modular design makes it possible to encompass
a wide range of powers and voltages while its intuitive structure facilitates its use and maintenance.
The whole Ingedrive converter range offers a powerful configuration tool enabling the user to view
and parameterise drives both locally using the touch screen and remotely via an Ethernet connection.

with IGBT Power Semiconductors

Control Unit + Communication Module

F.O. F.O. F.O.

TWO LEVEL AFE RECTIFIER TWO LEVEL INVERTER

D1 D3 D5 D1 D3 D5
Main Contactor
TR1 TR3 TR5 TR1 TR3 TR5

C V

D4 D6 D2 D4 D6 D2

TR4 TR6 TR2 TR4 TR6 TR2

Air or Water Cooling System

Applications:
Metals, water treatment, cement,
oil&gas, power generation, chemical and
marine

www.ingeteam.com
ingedrive.info@ingeteam.com
Technical characteristics
LV400
General data
Inverter Type Two-Level Voltage Source Inverter with LV-IGBT Power Semiconductors
Rectifier Type Diode Front End (DFE) 6P

The technical data in this catalogue is subject to change without prior notice. FY06IPTT01/0517
Diode Front End (DFE) 12P
Active Front End (AFE)
Main Supply Voltage Range 380 - 480 V AC 500 - 690 V AC
Output Power Range(1) 500 kVA - 2300 kVA (Water Cooled) 500 kVA - 6500 kVA (Water Cooled)
250 kVA - 1250 kVA (Air Cooled) 250 kVA - 1500 kVA (Air Cooled)
Supply Voltage Tolerance Typically ±10 %
Supply Frequency 50 / 60Hz (± 5%)
Input Power Factor 0.91 to 0.96 for DFE rectifiers
1 for AFE rectifiers
Output Voltage 0 to supply voltage
Output Frequency 0 to 120Hz (higher on request)
Efficiency at Rated Load Typically > 0.97 for DFE rectifiers
Typically > 0.96 for AFE rectifiers
Motor Types Induction, Synchronous or Permanent Magnet Motor
Converter Cooling Air Cooled
Water Cooled with Built-In Water to Water Heat Exchanger

Control properties
Control types Vector Control (VC), Voltage Frequency Control (VF)(2)
Static Speed Acc. (closed loop)(3) < 0.01% in field weakening / < 0.01% in constant flux
Static Torque Acc. (closed loop)(3) < 1% in field weakening / < 1% in constant flux
Static Torque Acc. (open loop)(3) < 2% in field weakening / < 2% in constant flux (for synchronous motors)
< 5% in field weakening / < 3% in constant flux (for induction motors)
Torque Response Time < 10ms
Shaft Torque Ripple(3) ± 1 % 
Drive Protection Functions Overcurrent, overvoltage and undervoltage monitoring; earth fault; short-circuit detection and protection;
semiconductor failure monitoring; cooling supervision; phase loss and others
Motor Protection Functions Overload(4), overspee

Enviromental cond.
Ambient Temp. for Storage -15 ºC to +75 ºC (for empty cooling system in water cooled version)
Ambient Temp. for Transport -15 ºC to +75 ºC (for empty cooling system in water cooled version)
Operation Altitude < 1000m above sea level (100% load capacity)
> 1000m above sea level (with derating)
Relative Air Humidity 5% to 95% (condensation not permitted)
Paint Colour RAL 7035 (others on request)
Compliance with Standards IEC 61800-2, IEC 60146-1-1, marine standards
Air cooled converter
Noise < 80dB (A) at a distance of 1m from the cubicle
Ambient Temp. for Operation +0 ºC to +40 ºC (higher with derating)
Degree of Protection IP23 (others on request)
Water cooled converter
Noise < 75dB (A) at a distance of 1m from the cubicle
Ambient Temp. for Operation +0 ºC to +45 ºC (higher with derating)
Degree of Protection IP44 (others on request)
Primary Circuit Coolants Allowed Seawater or freshwater
Primary Coolant Temp. Allowed +0 ºC to +38 ºC (higher with derating)
Primary Circuit Pressure Drop < 1bar
Max. Primary Service Pressure 6bar
Max. Primary ΔT 5 ºC
Secondary Circuit Coolant Controlled pre-mixed liquid (fresh water < 10μS/cm + anti-freezing)
Secondary Circuit Features Redundant pump

Options
Main Options Dynamic braking chopper, different communication modules, dv/dt filter, sinusoidal filter, input/output
isolation switch, marine customization and others

(1) Power rating are defined for 400V and 690V converters
(2) Only for induction motors and quadratic torque loads. No speed sensor needed
(3) Refers to maximum values of equipment
(4) Depends on electrical characteristics