Nothing Special   »   [go: up one dir, main page]

0% found this document useful (0 votes)
84 views64 pages

Instruction Bulletin: Communication Option

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 64

VD0C32S303A

October 1998
Instruction Bulletin Raleigh, NC, USA

®
ALTISTART 46
Communication Option
MODBUS® RTU, MODBUS ASCII,
UNI-TELWAY™
ASCII Protocol for PC
VW3G46301

User’s Manual
DANGER
HAZARDOUS VOLTAGE
• Read and understand this bulletin in its entirety before installing or
operating ALTISTART controllers. Installation, adjustment, repair and
maintenance of controllers must be performed by qualified
personnel.
• Disconnect all power before servicing the controller.
• Do not touch unshielded components or terminal strip screw
connections with voltage present.
• Install all covers before applying power or starting and stopping the
controller.
• User is responsible for conforming to all applicable code
requirements with respect to grounding all equipment.
• Many parts in the controller, including printed wiring boards, operate
at line voltage. Do not touch. Use only electrically insulated tools
while making adjustments.
Before installing the controller:
• Disconnect all power.
• Place a “Do not turn on” label on the controller disconnect.
• Lock the disconnect in the open position.
Electric shock will result in death or serious injury.
Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Table of Contents

CHAPTER 1: INSTALLATION AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . 1


INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
System Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLING THE COMMUNICATION OPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
CONNECTING TO A MULTI-DROP BUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SUB-D Connector Pin Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Connecting to a Standard RS-485 Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Connecting to a Standard RS-422 Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Connecting to a Standard RS-232C Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
WIRING RECOMMENDATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Connecting to a UNI-TELWAY Bus with Telemecanique PLC . . . . . . . . . . . . . . . . . 6
Connection Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Sample Network Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Connecting to a MODBUS Bus with MODICON™ PLC . . . . . . . . . . . . . . . . . . . . . 8
Connection Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
CONFIGURATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Configuring the Bus Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ASCII Message Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Reading the Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Modifying the Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Modifying the Configuration by Sending a File . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Configuration Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Information Requests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Additional Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

© 1998 Square D All Rights Reserved i


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Table of Contents October 1998

CHAPTER 2: CONNECTIONS AND REGISTER DEFINITIONS . . . . . . . . . . . . . . . . . . . 17


COMMUNICATION PRINCIPLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
ATS46 States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Data Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Accessing Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Power-Up Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
LINK/LOCAL Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
ATS46 CONTROLLER REGISTER DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 22

ii © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Table of Contents

CHAPTER 3: UNI-TELWAY PROTOCOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31


LIST OF REQUESTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Identification Request . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Status Request . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Read and Write Objects Requests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Example 1: Word Object Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Example 2: Byte Object Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Event Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
REGISTER UPDATE TIMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

© 1998 Square D All Rights Reserved iii


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Table of Contents October 1998

CHAPTER 4: MODBUS PROTOCOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37


PRINCIPLE OF COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Accessible Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Exchanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Checking and Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
MSTR BLOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Top Node Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Middle Node Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Bottom Node Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Read/Write Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Control Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Register Update Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
APPENDIX A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
APPENDIX B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
APPENDIX C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

iv © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 1: Installation & Configuration

CHAPTER 1: INSTALLATION AND CONFIGURATION


INTRODUCTION

The VW3G46301 Communication Option (also referred to as C1 in this


document) is designed for use with the ALTISTART 46 (ATS46) controller,
allowing it to be connected to multi-drop networks using MODBUS RTU,
MODBUS ASCII, or UNI-TELWAY protocols.
As a node on a network, the ATS46 controller can receive and respond to
data messages. The communication option provides access to the
following ATS46 functions:
• configuration of communication parameters
• configuration of controller parameters
• downloading of settings
• control and supervision
• monitoring and diagnostics

The VW3G46301 is supplied with a 118 in. (3 m) RS-485 connection


cable fitted with a 9-pin, male/female SUB-D connector.
During the process of commissioning the ATS46 controller for MODBUS
or UNI-TELWAY communications, four ATS46 parameters must be set via
a PC Terminal Emulation Program. The parameters are outlined in
Table 1 on page 12.
You must connect the PC’s serial COM port to the PLC communication
module (Figure 1 on page 2) with a cable. Order the PC cable, catalog no.
VY1G461510, from a Square D distributor or construct a PC cable using
the pin-out illustrated below.

1 1
2 3
3 2
5 5
1 1
6 6
9-Pin Male 2
4 4 2 9-Pin Female
7 7
SUB-D 3
8 8
3 SUB-D
Connector 4
9 6 6 9
4 Connector
5 5

7 7
ATS46 PLC
8 8 PC
Communication Module 9 9 Communication Port

© 1998 Square D All Rights Reserved 1


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 1: Installation & Configuration October 1998

System Safety

WARNING
LOSS OF CONTROL
• Control system designers must consider potential failure modes of control paths and, for
certain critical control functions, provide a means of achieving a safe state during and
after a path failure. An example of a critical control function is emergency stop. Separate
or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to
implications associated with unanticipated transmission delays or failures of the link.
Failure to follow this instruction can result in death, serious injury, or equipment
damage. [1]
[1]
For additional information, refer to NEMA ICS 1.1-1984 (latest revision), Safety Guidelines for the Application,
Installation, and Maintenance of Solid State Control.

INSTALLING THE COMMUNICATION OPTION


Before performing any work on the controller, disconnect the power
supply by using the safety switch disconnect or circuit breaker.
To install the communication option:
1. Ensure that the controller is connected to earth.
2. Mount the VW3G46301 communication option on the controller, as
shown in Figure 1.

PLC Communication Module


(VW3G46301)

Figure 1: Mounting the PLC Communication Module

2 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 1: Installation & Configuration

3. Connect the PC’s serial COM port to the ATS46 PLC Communication
Module. Use the optional PC cable, catalog no. VY1G461510
(ordered separately), or construct a cable using the pin-out illustrated
on page 1.
4. With power applied to the ATS46 controller, set up the controller
communication parameters (Table 1 on page 12) via the PC Terminal
Emulation Program. If you are using Microsoft® Windows® version
3.11 and earlier, see page 11 for instructions. If you are using
Windows 95 or a later version, refer to Appendix C for configuration
instructions.
5. When configuration is complete, remove power from the ATS46
controller, remove the PC cable, and connect the cable supplied with
this kit to the ATS46 Communications Module. Refer to “Wiring
Recommendations” on page 6 for more information about wiring.

CONNECTING TO A MULTI-DROP BUS

SUB-D Connector Pin Configuration

The transmission interface is electrically isolated from the controller in


accordance with the RS-485 and RS-422 (RS-232C compatible)
standard, and is available on a 9-pin female SUB-D connector.
When using the ASCII protocol for PC, leave the TER/ input unconnected.
When using a bus protocol, connect the TER/ input to the +5 V input.

1
TER/ 8
5V 0V 4
4.7 kΩ
D (B)
7
TX E
D (A)
3 5
9 SG=RD(B)
& 4.7 kΩ +5 V 4
8 0V
0V TER/ 3
5V 9 TX=D(A)
D(B) 7
2 RX=RD(A)
RD(B) 6
1 RS-232
5V
100 kΩ Side view of external contacts
RD (B) 5
RX & 6
2
RD (A)
100 kΩ
0V 0V

Figure 2: Electrical Interface

© 1998 Square D All Rights Reserved 3


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 1: Installation & Configuration October 1998

Connecting to a Standard RS-485 Bus


Cable with a 9- to 15-pin SUB-D connector is supplied with the option.

Pins to be used (side view of the 9-pin SUB-D connector)

0V 4

D(B) 7

D(A) 3

TER/ 8
5V 9

120 Ω
Zt line terminator recommended
1 nF at both ends of the line

Figure 3: RS-485 Interface

Connecting to a Standard RS-422 Bus

Pins to be used (side view of the 9-pin SUB-D connector)

0V 4

D(B) 7

D(A) 3

OR

RD(B) 6

RD(A) 2

TER/ 8
5V 9

Figure 4: RS-422 Interface

4 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 1: Installation & Configuration

Connecting to a Standard RS-232C Bus

Pins to be used (side view of the 9-pin SUB-D connector)

1
4

7
6
Data
TX 3 Transmission

SG 5 Common

Data
RX 2 Reception

TER/ 8 Jumper required for bus protocol;


5V 9 Do not use for ASCII protocol.

NOTE: Shield connected to ground at the other end.

Figure 5: RS-232C Interface

When connecting to a PC, use the interconnection cable with a 9-pin


SUB-D connector and the 9- to 25-pin adaptor.
Do not use the TER/ to 5 V jumper for ASCII protocol communication with
a PC. However, the jumper is necessary for communications using the
other protocols.

© 1998 Square D All Rights Reserved 5


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 1: Installation & Configuration October 1998

WIRING RECOMMENDATIONS
Follow the wiring practices required by national and local electrical codes
in addition to the following:
• Use metallic conduit for all controller wiring. Do not run multidrop cable
and power wiring in the same conduit.
• Metallic conduit carrying power wiring must be separated from metallic
conduit containing the multidrop cable by at least 8 cm (3 in).
• Non-metallic conduit or cable trays used to carry power wiring must be
separated from metallic conduit containing multidrop cable by at least
30.5 cm (12 in).
• Whenever power wiring and multidrop cable cross, the metallic conduit
and non-metallic conduit or trays must cross at right angles.
• For the multidrop cable, use shielded cable with two pairs of twisted
conductors. Use the cable recommended for each multidrop bus
system shown.
• To equalize the voltage potential, connect the multidrop cable shield as
shown in Figures 3, 4, or 5.

Connecting to a UNI-TELWAY Bus with Telemecanique PLC

Apply the following rules when constructing a UNI-TELWAY multidrop


network:
• Limit the number of nodes on the network to 28.
• Limit the stub cable length at each junction to 20 m (66 ft).
• Terminate each end of each twisted pair of the multidrop cable as
shown in Figure 6.

120 Ω

1 nF

Figure 6: Termination Device

6 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 1: Installation & Configuration

Connection Accessories

To facilitate connecting the controller to the multidrop bus, the following


cable (available in three lengths) is recommended:
• TSX-CSA 100: length 100 m (328 ft)
• TSX-CSA 200: length 200 m (656 ft)
• TSX-CSA 500: length 500 m (1,640 ft)

The TSX-SCA62 terminal block (Figure 7) is a passive unit that features


a printed circuit board fitted with screw terminals, enabling two pieces of
equipment to be connected to the bus. There is a jumper in the box which
can be used to connect the end-of-line terminator. Code the PLC address
by setting the microswitches on the printed circuit board inside the box.
These switch settings cannot be used to set the address of the
ALTISTART 46 controller. For more information, refer to the
documentation shipped with the TSX-SCA62.

1 2

Figure 7: TSX-SCA62 Connector

© 1998 Square D All Rights Reserved 7


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 1: Installation & Configuration October 1998

Sample Network Layout

Figure 8 illustrates one possible system configuration involving multiple


ALTISTART 46 controllers, connected to a UNI-TELWAY bus.

TSX-SCM 21.6 TSX-CSB015


TSX-SCA62
TSX-CSAXXX

VW3-G46301 VW3-G46301 VW3-G46301

ALTISTART 46 ALTISTART 46 ALTISTART 46


Controller Controller Controller

Figure 8: Example of Connection to UNI-TELWAY Bus


NOTE: The ground connections between the TSX-SCA62 box and the
ALTISTART 46 controller must be made for good system operation.
Connections should be as short as possible.

Connecting to a MODBUS Bus with MODICON™ PLC

Apply the following rules when constructing a MODBUS multidrop


network:
• Limit the number of nodes on the network to 32, including the master
node.
• Daisy-chain the multidrop cable as illustrated in Figure 9. Do not use
stub connections.

8 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 1: Installation & Configuration

Connection Accessories

Many MODICON PLCs cannot initiate messages from a MODBUS port


because they were intended to be used as slave devices only. Therefore,
when using a MODICON PLC, the MODICON BM85 bridge/multiplexer
(bridge mux) must be connected to the MODBUS Plus port. For multiple
controllers, a data-enabled, RS-232C to RS-485 converter must be used.
Figure 9 shows system configuration involving multiple ALTISTART 46
controllers connected to a MODBUS bus, using a MODICON PLC.
NOTE: Your MODBUS device or PLC may be capable of initiating a
message directly from a MODBUS port (it must be a master port). Consult
Schneider Automation for more information (1-800-468-5342).
If the bridge mux is configured as a slave port, only one ALTISTART
controller can be connected to each port. For the bridge mux, the
MODBUS address of the ATS46 controller is used as a slave device
address in configuration setup screen V1. Remember to go to setup
screen V4 to save changes before powering down the bridge mux.
If the bridge mux is configured as a master port, up to 31 ALTISTART
controllers or other devices can be connected to each port.

ATS46 ATS46
Controller A Controller B
Port 1 MODBUS 3 MODBUS 7
PLC Bridge Mux Port 2 Node Node
Port 3
Port 4
MSTR Block Address routing
talking to ATS46 Controller A:

Address first device 12


Address second device 1 (Port 1)
Address third device 3

MSTR Block Address routing


talking to ATS46 Controller B:

Address first device 12


Address second device 1 (Port 1)
Address third device 7

© 1998 Square D All Rights Reserved 9


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 1: Installation & Configuration October 1998

▲ Use Standard Modem Cable


DB 25 Male/DB 9 Female
GC BC00 301
and a Male-to-Male 9-Pin Adapter
or wire your own cable using
the following connections:
DB9 Male DB 25 Male Modicon PLC
RXD 2 2 TX
TXD 3 3 RX CPU I/O I/O I/O
DTR 4 4 RTS MB Slave Port
GND 5 5 CTS
DSR 6 6 DSR
RTS 7 GND MB Slave Port
CTS 20 DTR
MB+ Port

RS-485
ModBus+
MB+ Address 10
RS-485 Wiring
Modicon BM85 Interface *
bridge mux
1
1 2 3 4
2

3
RS-232C to RS-485 4
data enabled 5
converter
D(A) D(B) 0V
6
1 2 3 4 5 7 D (A)
WHT/ 8
WHT/ BLU/ BLU 9
BLU WHT 10 ATS46 Controller 5
BLU/ 11
WHT 12
13 ATS46 Controller
14 D (B) Slave Address 5
15 0 V Route Address 10:4:5

Wiring G
Interface * G
1
2
3 Wiring Interface *
4 1
5 2
6 3
7 D (A) 4
WHT/ 8 5
BLU 9 WHT/BLU
6
10 ATS46 Controller 4 7 D (A)
BLU/ 11 8
WHT 12 9
13 10 ATS46 Controller n
14 D (B) 11
15 0 V 12
G 13
BLU/WHT
G 14 D (B)
15 0 V
* 810-289-020 Female 15-Pin G
Wiring Interface: Telemecanique ABE-6SD15F or WAGO 810-289/W02 G
Cable: Belden 9841 or equivalent

Figure 9: MODBUS Network Diagram

10 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 1: Installation & Configuration

CONFIGURATION
To configure the Windows Terminal program:
1. Access the Terminal menu by selecting the Accessories and Terminal
icons.
2. As shown below, select «Settings», «Terminal Emulation», and TTY
(Generic) from the Terminal menu.

3. From the Terminal menu, select «Settings» and «Terminal


Preferences». Set the Terminal Preferences to the values shown
below.

© 1998 Square D All Rights Reserved 11


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 1: Installation & Configuration October 1998

4. From the Terminal menu, select «Parameters» and «Configuration».


Set Communications to the values shown below.

NOTE: When you select the parity bit, the number of data bits changes
to 7. In this case, change the number of stop bits to 2 to restore the
number of data bits to 8. Then set the number of stop bits back to 1.
Saving the terminal configuration to a *.trm file is recommended.

Configuring the Bus Communication

The configuration parameters for the communication option can be read


using any protocol, but can only be written in ASCII protocol. To select
ASCII protocol, install a cable with no jumper strap between TER/ and 5 V.
To use the configured protocol, install a jumper between TER/ and 5 V.

Table 1: Configuration Parameter Values


Selected Permitted
Address Parameter ASCII Default Comments
Protocol Values
Product Address
W2290 ADR 0
(ADR)
0 NO Address not configured
1-31 Value Station address
W2291 Protocol (PRO) PRO 2
UNI-TELWAY 2 UTW
3 Reserved
MODBUS
4 RTU
RTU
MODBUS
5 ASC
ASCII

12 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 1: Installation & Configuration

Table 1: Configuration Parameter Values (Continued)


Selected Permitted
Address Parameter ASCII Default Comments
Protocol Values
W2292 Speed (SPD) SPD 7
2 300 300 bits/s
3 600 600 bits/s
4 1200 1200 bits/s
5 2400 2400 bits/s
6 4800 4800 bits/s
7 9600 9600 bits/s
8 19200 19200 bits/s
W2293 Format (FOR) FOR 2
2 8O1 [1] 8 bits/odd parity/1 stop bit
3 8E1
4 8N1
5 8N2
6 7O1
7 7E1
8 7O2
9 7E2
Cannot be modified for
UTW 2 8O1
UNI-TELWAY
MODBUS
2-5
RTU
MODBUS
2-9
ASCII

[1] Read as number of bits, parity (O=odd, E= even, N= none), number of stop bits
Example: 8O1 = 8 odd bits, 1 stop bit.

ASCII Message Format


The format of ASCII messages using Terminal is shown below.
PC (Master) question: ?{Data}{End}
ATS46 (Slave) answer: >{Data}{CR LF}

where:
Data = question or response data in ASCII format
End = one or two end characters (CR or LF or CR LF or LF CR)
CR = carriage return (H‘OD’)
LF = line feed (H‘OA’)

© 1998 Square D All Rights Reserved 13


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 1: Installation & Configuration October 1998

NOTES:
• End characters are not shown in the remainder of this chapter.
• The Windows Terminal program does not use the backspace key
(deleting the last character entered). If the backspace key is used, the
echo of your message on the screen may seem correct, but it will be
refused.
• If the question or a requested value is not correct, the response is >N.

Reading the Configuration


question: ?CONF
response:
>CONF:PRO:UTW ADR:NO SPD:9600 FOR:8O1
(factory configuration)

The above sample configuration reads: UNI-TELWAY protocol, address


not configured, speed 9600 bits/s, 8-bit format, odd parity, one stop bit.
Response parameter descriptions are provided in the ASCII column of
Table 1 on page 12.

Modifying the Configuration


Changes made to the communication configuration are saved in ATS46
memory. The response format when modifying the configuration is
identical to that when entering the configuration. The parameters are
listed in Table 1 on page 12, and they can be modified one at a time
(Example 1) or several in one question (Example 2). The mnemonics are
provided in the ASCII column and the possible protocol values in the
Permitted Values column of Table 1.
Example 1
address 1 ?ADR=1
UNI-TELWAY protocol ?PRO=UTW
speed 19200 bits/s ?SPD=19200
8-bit format, odd parity,1 stop bit ?FOR=8O1

Example 2
MODBUS RTU protocol, address 1,
?CONF=PRO=RTU ADR=1 SPD=4800
speed 4800 bits/s, 8-bit format,
FOR=8N1
no parity, 1 stop bit
UNI-TELWAY protocol,
speed 19200 bits/s (format is fixed, ?CONF=PRO=UTW SPD=19200
address not modified)

Any parameters that are not modified retain their previous values (ensure
that these values are correct).

14 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 1: Installation & Configuration

Modifying the Configuration by Sending a File

It is possible to enter the configuration in a text file, prepared using a text


editor (Windows Notepad type), to avoid typing the same command line
repeatedly.
Enter the configuration you wish to send (e.g., ?CONF=PRO=UTW
ADR=1 SPD=9600) in the notepad and save the file. The file must end
with a CR or LF. Press Enter at the end of the configuration line.
In the Windows Terminal «Transfer» menu, select «Send a text file», then
select the file previously saved. The file is immediately transmitted via the
Serial Link. A message confirming the transfer is displayed.

Configuration Help

Help is provided for the mnemonics used. For example:


To access Help: ?HELP
Response: ?HELP PRO ADR SPD FOR

To access parameter Help: ?HELP PRO


Response: >HELP PRO: PRO=UTW or RTU, ASC

Information Requests

To identify the ATS46 controller type and option being used, send the
following request:
Information
?INFO
request:
Response: >INFO:C1:V:1.0 IE01H TYPE:01H CS9B5AH ATS46D32:V1.1

In the above example, the communication option C1 (=VWG46301) has


software version V1.0 IE01 (E= version index), a standard type with a
program that contains H’9B5A’ as checksum. The ATS46 controller type
is ATS46D32 with software version V1.1.
NOTE: The checksum listed above is not an exact value for V1.0 software,
but is provided to illustrate the Response format.

© 1998 Square D All Rights Reserved 15


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 1: Installation & Configuration October 1998

DIAGNOSTICS

Two indicator lamps are on the front panel of the option:

COM Red LED

OK Green LED

RS232/422/485

Figure 10: Communication Interface

Table 2: Communication Diagnostics


OK Lamp COM
Probable Cause Corrective Action
Green Lamp Red
1 0 Normal operation, bus and controller present OK
Check the interface or the communication
0 0 Switched off, powered off
option.
Check the communication bus and the
0 1 Bus communication fault connections. Check the switches on the
subscriber sockets.
Check the communication configuration or
1/10 [1]
0 Character error the TER/-5 V strap (absent in ASCII
(6x)
protocol/present in bus protocol).
1/10 0 Communication option not configured Configure the communication option.
Communication fault between the
Check the 6-pin connector between the
1/2 0 communication option and the ATS46
option and the ATS46 controller.
controller (bus cable connected to option)
Communication fault between the
Check the 6-pin connector between the
1/2 1 communication option and the ATS46
option and the ATS46 controller.
controller (PC cable connected to option)
Lamp status: 0 = off 1 = on 1/2 = slow flashing (500 ms) 1/10 = fast flashing (100 ms)
[1]
This display flashes for 600 ms (3x on and 3x off) if an incorrect character has been received. The short flashing
is repeated after a period of five seconds if an incorrect character is received. This only occurs when the
communication option is set for communication fault (no message received for 10 s in bus communication or 1 s
in ASCII protocol).
If the option never changes to normal operation, this display indicates that the wiring is correct (except, perhaps,
for the TER/–5 V strap), but that the configuration speed or format is not suitable.

Additional Diagnostics

For an explanation of fault code registers, refer to Table 9 on page 27.

16 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 2—Register Definitions

CHAPTER 2: CONNECTIONS AND REGISTER DEFINITIONS


COMMUNICATION PRINCIPLES

Power Connections

The power wiring to the ALTISTART 46 (ATS46) controller can be


connected in accordance with the diagrams shown in the ATS46 user
guide, part number VD0C32S301.

Control Connections

The connection from STOP to PL must be made at all times for the
controller to run. As shown in Figure 11 on page 18, the control
connection scheme depends on whether the start command is to be
issued via the terminal strip (LOCAL mode) or through the PLC (LINK
mode). The control scheme also depends on the setting of the DLI bit
(W4060,1), as shown in Table 3.

Table 3: Setting the DLI Bit


LOCAL Mode LINK Mode
(DLI = 0) (DLI = 1)
Start command only by PLC.
LI–PL connection = 0 Standard operation — can configure
LI ignored unless configured
(not connected) LI for all available options
for local control.
Cannot switch to LINK mode if LI is
LI–PL connection = 1 configured for local control. Other LI Start command only by
(connected) configurations can be used but will terminal input
not prevent switching to LINK mode.

WARNING
UNINTENDED EQUIPMENT OPERATION
If DLI = 1, the logic input (LI) is ignored unless configured for Force to
Local Control (W4022=4). All other functions of the logic input must be
actuated through the PLC command (W4060).
Failure to follow this instruction can result in death, serious injury,
or equipment damage.

© 1998 Square D All Rights Reserved 17


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 2—Register Definitions October 1998

S S
R R
T L P T L P
U U
O I L O I L
N N
P P
LINK LOCAL

STOP

RUN

Only connect from STOP to PL Use 3-wire control to start from


when starting solely from a PLC. the terminal or from a PLC.

Figure 11: Control Connections

ATS46 States

If automatic restart is not used, the controller state is either no fault


(ready/run) or fault. Figure 12 shows the four controller states which exist
if automatic restart is selected (W4035,1).

Automatically resettable fault

Automatic fault reset


Automatic reset

Fault resettable on request


No Fault
(normal operation) Fault resettable
Reset request on request

Non-resettable
fault
Non-resettable fault

Non-resettable fault
Controller re-initialization

Figure 12: ATS46 Controller States

WARNING
UNINTENDED EQUIPMENT ACTION
• Automatic restart can only be used for machines or installations that
present no danger to personnel or equipment in the event of automatic
restarting.
• Equipment operation must conform with national and local safety
regulations.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.

18 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 2—Register Definitions

Descriptions of each ATS46 state are provided below.


State Standard Mode (W4035,1 = 0) Auto Reset Mode (W4035,1 = 1)
1 No Fault Controller is ready or running Controller is ready or running with no fault
with no fault condition detected. condition detected.

2 Automatic Reset Not taken into account. This state follows a fault that can be reset
Fault without further intervention.
If R1 is configured as a fault relay, this type of
fault does not cause the R1 relay to change
state.
If R1 is configured for control of an isolation
contactor, this type of fault causes the R1
relay to change state.
3 Fault Reset on Causes the R1 relay to change When a fault is encountered, the drive will
Request state. Relay will re-energize check to see if (W4035,1=1) is set. If true, the
when a new run command is drive will reset once the fault is cleared. This
issued and the fault has cleared. will occur only if the fault is an auto restart
type. Refer to the Soft Start Controller User’s
Manual, part number VD0C32S301, for more
information on faults.
4 Non-resettable Requires cycling of control Requires cycling of control power to reset.
Fault power to reset.

Data Structure
The adjustment, control, supervision, and monitoring of ATS46 controllers
are performed using data (or objects) that are specific to this product.
The data consists of:
• Bits that execute logic commands and are designated Bi, where
i = Bit number. For example, B1 = Starter reset (request for online
reset).
• Words (of 16 bits) are designated Wx, where x is a word number.
Words are used to save either integer values (0 to 65535) or 16
independent logic states that are called registers.

Example: W4028 = Boost level (digital value)


W4061 = Controller status register (16 status bits)

NOTE: Bit numbers are displayed as 0 to 9, then A to F. For example,


W4061,1 designates Bit 1 of register 4061. W4061,F designates Bit F of
register 4061.

© 1998 Square D All Rights Reserved 19


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 2—Register Definitions October 1998

Accessing Data
The tables at the end of this chapter list the parameters that can be
accessed via the communication link. The exact function of each
parameter and its effect on the behavior of the controller are described in
the ATS46 user guide, part number VD0C32S301.
Data including fault and monitoring information can only be read. Any
attempt to write to this data will be refused. The bits and words
corresponding to the adjustment, configuration and command
parameters can be written to as well as read.

Units
Words are expressed as unsigned integer values (0 to 65535), using the
units defined in the tables at the end of this chapter. For values that are
listed as decimal units in the register definition tables, the decimal point is
implied.
Example: W4037 = Initial torque as a percentage of Tn (e.g., 50 = 50% of Tn)

Ranges
The range permitted by the controller is specified for each parameter.
Where noted, 0 in the range column indicates that when the parameter is
set to 0, the function is disabled.
Example: When W4036 = 0, no maximum torque limit is specified;
otherwise, the adjustment range is from 10 to 200 (as a percentage of Tn).

Power-Up Values
Each time the ATS46 controller is powered up, it is initialized with the
configuration and adjustments stored in EEPROM memory (in LINK
mode, store adjustments with W4060,E or return to factory settings with
W4060,D).
The controller is systematically set to LOCAL control mode (commands
are expected on the terminal block). To control the ATS46 controller from
a multi-drop bus, it is necessary to assign the commands to LINK mode
by setting W4060,1 to 1.

LINK/LOCAL Management

Two control modes are provided for ATS46 controller operation:


• LOCAL mode via 2- or 3-wire terminal block control
• LINK mode via a PC or a PLC

20 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 2—Register Definitions

ATS46 operating modes are only effective for accessing the command
parameters and have no effect on the configuration, adjustment, or
monitoring parameters.

Table 4: LINK/LOCAL Transition Parameters


Parameter Description
Command bit B2 (DLI) Assigns commands to LINK/LOCAL mode
Command word W4060,1 (DLI) Same as command bit B2 (DLI)
Command bit B4 (NTO) No time out
Command word W4060,4 (NTO) Same as command bit B4 (NTO)
Configuration word W4022 (LI) Assigns LI to LOCAL mode
Configuration word W4029 (STY) Selects stop type via LI_STOP
Monitoring word W4061,0 (LOC) LOCAL mode = 1, LINK mode = 0
Monitoring word W4061,5 (FLO) LOCAL mode = 1, not LOCAL mode = 0
Monitoring word W4066,0 (LIO) State of LI (0=low, 1=high)

Operation

In LOCAL mode, the terminal block is active and must be used to start
and stop the ATS46 controller.
In LINK mode, the serial link has write access to the commands. Only the
STOP terminal is active and will override all other commands.
If the controller is configured for LOCAL mode and LI is configured for
local control, activating LI will prevent the controller from switching to
LINK mode.
When the controller is switched out of LINK mode, the controller will run
if there is a RUN command present at the terminal strip.

In LINK mode, messages must be sent to the controller regularly (at least
one message every 10 seconds with UNI-TELWAY, MODBUS ASCII, and
MODBUS RTU protocol and every second in ASCII protocol). If a
message is not received, a controller serial link fault (SLF) occurs. The
communication check can be inhibited by setting bit NTO to 1, which
prevents the SLF fault from displaying. This is useful in setup and
troubleshooting; however, NTO should be set to 0 for normal serial link
command operation.

© 1998 Square D All Rights Reserved 21


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 2—Register Definitions October 1998

WARNING
LOSS OF CONTROL
Setting B4 or W4060,4 (NTO) to 1 disables serial link fault protection.
Provide alternate control paths when disabling serial link fault
protection.
Failure to follow this instruction can result in death, serious injury
or equipment damage.

ATS46 CONTROLLER REGISTER DESCRIPTIONS


NOTE: When using the MSTR block (refer to “MSTR Block” on page 40),
add 1 to the register number. Bit 0 is always the right-most or least-
significant bit. Bit F is always the left-most or most-significant bit.

Table 5: Command Bits (read and write)


Bit Name Description Function Address
Acknowledges a correctable fault
B0 RST Controller reset command W4060,0
and resets the fault relay.
LINK = 1, LOCAL = 0
Command assigned to The controller can only be
B1 DLI W4060,1
LINK/LOCAL mode controlled via the serial link (bus
or PC) or via its terminal block.
The controller triggers an EtF
B2 EXT External fault W4060,2
fault.
B3 — Reserved — —
The controller does not trigger
B4 NTO No Time Out an SLF fault if messages are not W4060,4
received within 10 s.
B5 RUN Start command 0=inactive; 1=active W4060,5
B6 CAF Braked stop command 0=inactive; 1=active W4060,6
B7 CAD Decelerated stop command 0=inactive; 1=active W4060,7
B8 CAL Freewheel stop command 0=inactive; 1=active W4060,8
B9 — Reserved — —

The bit designations in Table 5 follow UNI-TELWAY protocol. When using


MODBUS protocol, observe the following bit order designation.

UNI-TELWAY 0 1 2 3 4 5 6 7 8 9 A B C D E F
MODBUS 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

22 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 2—Register Definitions

WARNING
UNINTENDED EQUIPMENT OPERATION
There is a shift of 1 between the address in UNI-TELWAY and
MODBUS protocols. When using MODBUS protocol, add 1 to each
address listed in the following tables.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.

© 1998 Square D All Rights Reserved 23


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 2—Register Definitions October 1998

Table 6: Adjustment Words (read and write)

Address [1] Name Range Unit Description Possible Values


0 [2] Max torque during 0 = off (CLP must be on for
W4036 TLI % of Tn
10–200 acceleration value to be used)
Initial torque during
W4037 TQ0 0–100 % of Tn
acceleration
End of deceleration ramp
W4038 EDC 0–100 % of Tn
threshold
150–700
W4039 ILT % of In Current limit 0 = off
max 500% ICL
0 [2]
W4040 OIL % of In Current limit alarm 0 = off
50–300
W4041 BRC 0–100 — Braking current
W4042 EBA 20–100 % of braking time Adjustment of braking time
W4043 ACC 1–60 S Acceleration ramp time
W4044 DEC 1–60 S Deceleration ramp time
W4045 Reserved
W4046 Reserved
Adjustment of deceleration
W4047 RGC 0–100 —
gain
[1]
When using MODBUS protocol, add 1 to the address.
[2]
When the parameter is set to 0, the function is disabled.

Table 7: Configuration Words (read and write)

Address [1] Name Range Unit Description Possible Values


W4018–4019 Reserved Read at 8000 H
0=not assigned
1=force freewheel
2=external fault [2]
3=reserved
W4022 LI 0–8 Logic input LI assigned 4=local control
5=cascading motor control
6=reserved
7=motor overload reset
8=fault reset
0=not assigned
W4023 LO1 0–2 Logic output LO1 assigned 1=motor thermal alarm
2=motor powered
0=not assigned
1=motor current (A)
2=motor torque (% Tn)
W4024 AO 0–5 Analog output AO assigned
3=motor thermal state
4=power factor
5=active power
[1] When using MODBUS protocol, add 1 to the address.
[2]
In LINK mode, an external fault must be indicated by the PLC. Do not connect the external fault indication device
to the logic input on the ATS46 controller, as the signal will be ignored.
[3} When the parameter is set to 0, the function is disabled.

24 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 2—Register Definitions

Table 7: Configuration Words (read and write) (Continued)

Address [1] Name Range Unit Description Possible Values


W4025 ASC 50–500 % Analog output scale
W4026 IN 50–130% ICL 0.1 A Motor nominal current
W4027 LSC 20–90 % losses Stator loss compensation
W4028 BST 0 [3], 50–100 % of V Voltage boost level
0=freewheel
Stop type selection via logic
W4029 STY 0–2 1=deceleration ramp
input LI_STOP
2=braking
0=off
Default assigned to phase
W4030 PHR 0–2 1=direct rotation direction
rotation
2=reverse rotation direction
W4031 ULL 0 [3] or 20–100 % of Tn Underload trip threshold
Time adjustment before
W4032 TBS 0–999 seconds
starting
W4033 TLS 0 [3], 10–999 seconds Start time too long
0=protection inhibited
1=sub-class 2
2= class 10A
3=class 10
W4034 THP 0–7 Motor thermal protection
4=sub-class 15
5=class 20
6=sub-class 25
7=class 30
CNF Configuration register
4035,0 = 0 off
CLP 0–1 Torque control
4035,0 = 1 on
4035,1 = 0 manual reset
ARS 0–1 Automatic reset
4035,1 = 1 auto reset
4035,2 = 0 fault relay
4035,2 = 1 isolating relay
(Bit 4060,0 controller reset
R1 0–1 Relay R1 assignment
function clears fault when
this relay is used as a fault
W4035 relay.)
4035,3 = 0 not assigned
Logic output LO2
LO2 0–1 4035,3 = 1 current
assignment
threshold alarm
4035,4 = 0 0–20 mA
AO1 0–1 Analog output range
4035,4 = 1 4–20 mA
Select test operation on a 4035,5 = 0 not assigned
SST 0–1
low power motor 4035,5 = 1 test function
4035,6 = 0 not active
CSC 0–1 Cascading motor
4035,6 = 1 active
Reserved 4035,7–F
[1]
When using MODBUS protocol, add 1 to the address.
[2] In LINK mode, an external fault must be indicated by the PLC. Do not connect the external fault indication device
to the logic input on the ATS46 controller, as the signal will be ignored.
[3}
When the parameter is set to 0, the function is disabled.

© 1998 Square D All Rights Reserved 25


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 2—Register Definitions October 1998

Table 8: Command Word (read and write)

Address [1] Name Range Unit Description Possible Values


CMD Command register
Controller reset W4060,0 = 0 inactive
RST
command W4060,0 = 1 active
W4060,1 = 0 commands not
Commands assigned over link
DLI
assigned over link W4060,1 = 1 commands assigned
over link
W4060,2 = 0 inactive
External fault
EXT W4060,2 = 1 active on positive
command
edge [2]
Motor deceleration W4060,3 = inactive
DMC
control in cascade W4060,3 = 1 active
No time out W4060,4 = 0 enable
NTO
(no SLF fault) W4060,4 = 1 disable
W4060,5 = 0 inactive
RUN Start command
W4060,5 = 1 active
Braked stop W4060,6 = 0 inactive
CAF
command W4060,6 = 1 active
W4060
Decelerated stop W4060,7 = 0 inactive
CAD
command W4060,7 = 1 active
Freewheel stop W4060,8 = 0 inactive
CAL
command W4060,8 = 1 active
Reset motor thermal W4060,A = 0 no
RTH
state W4060,A = 1 yes/reset
W4060,C = 0 inactive
TRE Reset elapsed time W4060,C = 1 active on
positive edge
W4060,D = 0 inactive
Recall factory
INT W4060,D = 1 active on
setting
positive edge [2]
W4060,E = 0 inactive
Store adjustments in
MRE W4060,E = 1 active on
EEPROM
positive edge [2]
W4060,F = 0 inactive
Recall adjustments
RRE W4060,F = 1 active on
in EEPROM
positive edge [2]
[1]
When using MODBUS protocol, add 1 to the address.
[2] Bit returns to 0 after operation.

26 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 2—Register Definitions

Table 9: Monitoring Words (read only)

Address [1] Name Range Unit Description Possible Values


Controller status
ETA
register
W4061,0 = 0 local
LOC Local/Link mode
W4061,0 = 1 link
W4061,1 = 0 not ready
RDY Controller status
W4061,1 = 1 ready
W4061,2 = 0 normal operation
FAI Controller faulted
W4061,2 = 1 faulted
Stopped after request W4061,3 = 0 false
via terminal block W4061,3 = 1 true
W4061,5 = 0 false
FLO Local control
W4061,5 = 1 true
Communication check W4061,6 = 0 false
NTO
inhibited W4061,6 = 1 true
W4061,7 = 0 false
Current alarm threshold
W4061,7 = 1 true
W4061
W4061,8 = 0 false
SST Steady state
W4061,8 = 1 true
W4061,9 = 0 false
Short-circuit
W4061,9 = 1 true
W4061,A = 0 false
Stop phase
W4061,A = 1 true
W4061,B = 0 false
Acceleration phase
W4061,B = 1 true
W4061, C = 0 false
OVL Motor thermal alarm
W4061,C = 1 true
W4061,D = 0 false
LIM Current limited
W4061,D= 1 true
W4061,E = 0 false
NLP No mains supply
W4061,E = 1 true
W4061,F = 0 50 Hz
Mains supply frequency
W4061,F = 1 60 Hz
W4062 LCR 0–999 A/10 Motor current
W4063 LTR 0–255 % of Tn Motor load state
W4064 LTH 0–250 % Motor thermal state
[1]
When using MODBUS protocol, add 1 to the address.
[2] Bit returns to 0 after operation.

© 1998 Square D All Rights Reserved 27


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 2—Register Definitions October 1998

Table 9: Monitoring Words (read only) (Continued)

Address [1] Name Range Unit Description Possible Values


0=off
W4065 PHR 0–2 Phase rotation state 1=direct rotation direction
2=reverse rotation direction
LIO State of logic I/O
W4066,0 = 0 low
Logic input LI
W4066,0 = 1 high
W4066,1 = 0 low
Logic output LO1
W4066,1 = 1 high
W4066,2 = 0 low
Logic output LO2
W4066,2 = 1 high
W4066,3 = 0 open
Relay R1
W4066,3 = 1 closed
W4066,4 = 0 open
W4066 Relay R2
W4066,4 = 1 closed
W4066,5 = 0 thermal overshoot
Vigithem
W4066,5 = 1 closed
W4066,6 = 0 low
Logic input LI_RUN
W4066,6 = 1 high
W4066,7 = 0 low
Logic input LI_STOP
W4066,7 = 1 high
W4066,8 = 0 standard
Operating duty switch
W4066,8 = 1 severe
Reserved W4066,9–W4066,F
0.01 to 1 displayed as %;
W4067 COS 1–100 % Cos motor power factor
÷ by 100 for actual value
W4068 TFR 10–65535 Hours Elapsed time
[1] When using MODBUS protocol, add 1 to the address.
[2]
Bit returns to 0 after operation.

28 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 2—Register Definitions

Table 9: Monitoring Words (read only) (Continued)

Address [1] Name Range Unit Description Possible Values


DFT Fault register
Reserved W4069,0
INF Internal fault W4069,1
OCF Overcurrent fault W4069,2
PIF Phase inversion W4069,3
Reserved W4069,4
SLF Serial link W4069,5
ETF External fault W4069,6
STF Start too long W4069,7
W4069
Mains failure and start
USF W4069,8
request
PHF Phase failure W4069,9
OHF Controller thermal fault W4069,A
Rotor locked in steady
LRF W4069,B
state
OLF Motor thermal overload W4069,C
FRF W4069,D
Reserved W4069,E
ULF Underload W4069,F
Value of analog output
W4070 SAO
AO
Time before starting W4071,0 = 0 inactive
W4071 —
alarm W4071,0 = 1 active
0=inactive
W4072 LPR Active power
1=active
W4090 PTR Fault order
W4091 DFT Fault register repetition
Time counter repetition
W4092
(W4068)
[1] When using MODBUS protocol, add 1 to the address.
[2]
Bit returns to 0 after operation.

© 1998 Square D All Rights Reserved 29


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 2—Register Definitions October 1998

30 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 3—UNI-TELWAY Protocol

CHAPTER 3: UNI-TELWAY PROTOCOL


LIST OF REQUESTS

Table 10 describes the UNI-TELWAY requests accepted by the


ALTISTART 46 (ATS46) controller, and their limits. Detailed information
on coding the requests is given in the UNI-TELWAY reference manual,
TSX D24 004.

Table 10: List of Requests

Code Accepted by
Request
(Hexadecimal Format) ATS46 Controller
Identification H'0F’ Yes
Protocol version H'30' Yes
Status H'31' Yes
Mirror H'FA' Yes
Read error counter H'A2' Yes
Counter reset H'A4' Yes

Read one bit H'00' Yes


Write one bit H'10' Yes

Read one word H'04' Yes


Write one word H'14' Yes

Read objects H'36' 63 Words max. [1]


Write objects H'37' 60 Words max.

— Yes
Event data
— 2 Words

Specific H'F2' See Table 12


[1] The ATS46 controller uses only 27 words.

Identification Request

Table 11: Identification Request

Code
Request
(Hexadecimal Format)
Answer code H'3F'
Product type H'16' for ATS46 controller
Sub-type H'46' for ATS46 controller
Product version H'xx' [1]
ASCII string [2] Catalog number (e.g. ATS46D17N)
[1]
xx
= software version. For example, enter H'21' for V2.1.
[2]
The first byte of an ASCII string always corresponds to the length of the string.

© 1998 Square D All Rights Reserved 31


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 3—UNI-TELWAY Protocol October 1998

Status Request

Table 12: Status Request

Request Code (Hexadecimal Format)


Answer code H'61'
H'xx' [1]
Bit 0, internal fault
Bit 1, resettable fault
Bit 2, non-resettable fault
Current state Bit 3, not used
Bit 4, not used
Bit 5, not used
Bit 6, controller at a standstill (RDY, SLC, or fault)
Bit 7, controller in Local control mode

State mask H'C7' indicates the significant bits for the current state
[1] xx = software version. For example, enter H'21' for V2.1.

Read and Write Objects Requests

Read and write requests allow access to several words within the request
limits described in Table 10. They may be coded as shown in Table 13.

Table 13: Read and Write Objects Requests

Request Code (Hexadecimal Format)


H'36' (Read) or
Question code (TxTi,C)
H'37' (Write)

Category 0 to 7

Segment H'68' (internal word)

H'06' for reading a byte (8 bits) or


Object type
H'07' for reading or writing a word (16 bits)

Object address H'xxxx'

The answer to the “write objects” request is accepted if at least one word
is written. Reserved or unused words are read at 0 unless noted, and
writing them has no effect.
The following examples give typical read requests for the TSX7
programmable controller using a text block. The examples read words
W4022 to W4025 of the ATS46 controller, first using word object types
(Example 1), then using byte object types (Example 2).

32 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 3—UNI-TELWAY Protocol

Example 1: Word Object Type

The transmission text block in Figure 13 illustrates a read request using


the word object type (H'07'). In the example:
• TxTi,C=H'0736' (category + request)
• TxTi,L=6
• + Transmission Table

Internal Word Segment


Type of Word

H'07' H'68'

4023

Number of words to read


Number corresponding to first word

Figure 13: Reading Words W4023 to W4026:


Transmission Text Block

Figure 14 illustrates the reception text block associated with the read
request in Figure 13. In the example:
• TxTi,V=H'66' (report)
• TxTi,S=9 (9 bytes received)
• + Reception Table
The data received in the reception table is offset by one byte. The
application program must correct the data (by successive offsets, for
example) before it is used.

W4023 (least sig.) H'07'

W4024 (least sig.) W4023 (most sig.)

W4025 (least sig.) W4024 (most sig.)

W4026 (least sig.) W4025 (most sig.)

W4026 (most sig.)

Figure 14: Reading Words W4023 to W4026: Reception Text Block

© 1998 Square D All Rights Reserved 33


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 3—UNI-TELWAY Protocol October 1998

Example 2: Byte Object Type

The transmission text block in Figure 15 illustrates a read request using


the byte object type (H'06'). In the example:
• TxTi,C=H'0736' (category + request)
• TxTi,L=6
• + Transmission Table

Internal Word Segment


Type of Word

H'06' H'68'

8045

Number of bytes to read


(most significant bit of W4022 + 8 bytes comprising W4023 to W4026)
Number corresponding to the first byte
(most significant bit of W4022 has address 2 x 4022 + 1 = 8045)

Figure 15: Reading Words W4023 to W4026:


Transmission Text Block

Figure 16 illustrates the reception text block associated with the read
request in Figure 15. In the example:
• TxTi,V=H'66' (report)
• TxTi,S=10 (10 bytes received)
• + Reception Table
• The programming in Figure 15 enables the words to be correctly
registered in the reception table.

W4022 (most sig.) H'06'

W4023

W4024

W4025

W4026

Figure 16: Reading Words W4023 to W4026: Reception Text Block

34 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 3—UNI-TELWAY Protocol

Event Data

The ATS46 controller transmits event data on its own initiative to the
UNI-TELWAY link master, without having first received a question. This
data is sent via the “unrequested data” request and does not require an
answer from the receiver.
Event data is sent in the following two cases:
• When a fault appears or disappears (change of state of W4061, bit 2
of status register).
• When the controller is forced to local control by one of its logic inputs
(change of state of the input), if an input has been assigned to this
function via word W4022.
Event data consists of two 16-bit words, transmitted in the following order:
• ETA status register (W4061)
• DFT fault register (W4069)
Using event data with the TSX programmable controller requires the
following:
• Correct configuration of the master coupler for the UNI-TELWAY link
• Regular monitoring of the indicators which display changes in the
value of the data
• Assignment of the data via the read request of the event data

REGISTER UPDATE TIMES


Table 14 lists the maximum register update times for a single ATS46
controller using UNI-TELWAY protocol. These times assume a baud rate
of 9600 and no communication errors.

Table 14: Maximum Register Update Times

Number of Registers Read Time [1] Write Time [2]


Transferred (msec) (msec)
1 44.7 43.5
10 65.3 64.2
20 88.2 87.1
50 157.0 155.8
[1]
Read is by “read object” (36H) request. Values shown include query
time, master processing time, and acknowledge (ACK) time.
[2] Write is by “write object” (37H) request. Values shown include query
time, master processing time, and acknowledge (ACK) time.

© 1998 Square D All Rights Reserved 35


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 3—UNI-TELWAY Protocol October 1998

36 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 4—MODBUS Protocol

CHAPTER 4: MODBUS PROTOCOL


PRINCIPLE OF COMMUNICATION

MODBUS is a dialog protocol which creates a hierarchical structure


between a master device and one or several slave devices. The
ALTISTART 46 (ATS46) controller is always a slave device. MODBUS
protocol enables the master device to interrogate one or more intelligent
slaves. A multi-drop link connects the master device and slaves to one
another.
Two types of dialog are possible between master device and slave:
• The master device communicates to the slave and waits for a
response.
• The master device talks to a group of slaves without waiting for a
response (broadcast messages).

The slave number can be between 1 and 31. The number 0 is reserved
for a broadcast message.
In either type of dialog, the master device initiates and controls all
exchanges with the slaves. If an incorrect exchange occurs, the master
device reiterates the exchange and declares the slave absent if no answer
is received after a given time has elapsed. Only one device may transmit
on line at any time. A slave cannot initiate an exchange, nor is lateral
communication (i.e., slave to slave) possible. The master device's
programming must therefore be designed to interrogate a slave and send
the data received to another slave.

Master
Controller

Slave
Slave K Slave
J L

Figure 17: MODBUS Protocol

© 1998 Square D All Rights Reserved 37


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 4—MODBUS Protocol October 1998

NOTE: Register structures in the ALTISTART controller are of


UNI-TELWAY designation. When using MODBUS protocol, note the
following differences:
1. Reverse bit order—UNI-TELWAY protocol is hexadecimal, 0 to F,
where MODBUS protocol is from 16 to 1.
UNI-TELWAY 0 1 2 3 4 5 6 7 8 9 A B C D E F
MODBUS 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

2. Address offset by 1—Add 1 to the UNI-TELWAY address to get the


proper MODBUS address.

WARNING
UNINTENDED EQUIPMENT OPERATION
There is a shift of 1 between the address in UNI-TELWAY and
MODBUS protocols. When using MODBUS protocol, add 1 to each
address listed in the parameter tables throughout this manual.
Failure to follow this instruction can result in death, serious
injury or equipment damage.

Accessible Data

The MODBUS protocol enables data (bits and words) to be exchanged


between the master device and several slaves. In each slave unit, bit
areas are defined for the master device to use when reading or writing
data. Input objects may only be read, whereas output objects may be read
or written.

38 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 4—MODBUS Protocol

Slave J

Master Slave K
Controller MODBUS addressing

Transmission
Input
Bits

Table
User Program Output
Bits

Input
Words
Reception
Table

Output
Words

Slave L

Figure 18: Input and Output Data Objects

Exchanges
The master device always initiates data exchanges. The master device
waits for the slave's answer before transmitting the next message, thus
avoiding any conflict on the line. Operation in half-duplex is therefore
authorized.

Checking and Supervision

When two entities are communicating via asynchronous serial link,


control of exchanges between them must naturally include exception
messages, should exchange faults occur. A slave receiving an incoherent
message will report an exchange fault to the master device, which in turn
will determine whether to repeat the exchange.

© 1998 Square D All Rights Reserved 39


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 4—MODBUS Protocol October 1998

Master

ATS46
Controller

Figure 19: Communicating Exchange Faults

MSTR BLOCK

Overview
When using a bridge multiplexer as shown in Figure 9 on page 10, the
Master (MSTR) function block can be used. The BM85 bridge/multiplexer
(bridge mux) operates as a MODBUS Plus node and provides four serial
ports that can be configured separately for the serial devices in your
application. BM85 models are available for RS-232, RS-485 or
MODICON MODBUS serial devices.
If you are not using a bridge mux but would like to use MODBUS
commands, consult the MODICON MODBUS Protocol Reference Guide,
part number PI-MBUS-300. (This document is available by fax-on-
demand from Schneider Automation at 1-800-468-5342. Select option 3,
documents 3001 and 3002.)
PLCs that support MODBUS Plus communications have a special MSTR
instruction with which nodes on the network can initiate message
transactions. The MSTR function allows you to initiate one of nine
possible network communications operations over MODBUS Plus. Each
operation is designated by a code, as described in Table 15.

Table 15: MODBUS Operations Codes

Operation Code Operation Code


Write data 1 Read global database 6
Read data 2 Get remote statistics 7
Get local statistics 3 Clear remote statistics 8
Clear local statistics 4 Monitor peer cop status 9
Write global database 5

40 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 4—MODBUS Protocol

The read and write MSTR instruction blocks are discussed on page 42.
For more information, refer to the user guide, MODICON Ladder Logic
Block Library, part number 840 USE 101 00.

Inputs
The MSTR block has two control inputs (see Figure 20). When the input
to the top node is ON, it enables the instruction. When the input to the
middle node is ON, it terminates the active operation.

Outputs
The MSTR block can produce three possible outputs (see Figure 20). The
output from the top node echoes the state of the top input; i.e., it goes ON
while the instruction is active. The output from the middle node echoes the
state of the middle input; i.e., it goes ON if the MSTR operation is
terminated prior to completion. The output from the bottom node goes ON
when an MSTR operation has been completed successfully.

Enables selected Control Operation is active


MSTR operation Block

First register
Terminates active data Operation terminated to capture
MSTR operation unsuccessfully BCKM intermittent
area
errors

MSTR
length Operation successful

Figure 20: Block Structure

© 1998 Square D All Rights Reserved 41


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 4—MODBUS Protocol October 1998

Top Node Content

The 4x register entered in the top node is the first of nine contiguous
holding registers that comprise the control block.

Table 16: Control Block Registers


Register Content
Displayed Identifies one of the nine MSTR operations
First implied Displays error status
Second implied Displays length
Third implied Displays MSTR operation-dependent information
Routing 1 register (used to designate the address of the destination
Fourth implied
node for a network message transaction)
Fifth implied Routing 2 register
Sixth implied Routing 3 register
Seventh implied Routing 4 register
Eighth implied Routing 5 register

NOTE: Before programming an MSTR instruction, an understanding of


routing path structures is required. For information about routing path
structures, refer to the user guide, MODBUS Plus Network Planning and
Installation, part number 890 USE 100 00.

Middle Node Content

The 4x register entered in the middle node is the first in a group of


contiguous holding registers that comprise the data area. This data area
is the source of data in operations providing the communications
processor with data (e.g., a write operation). The data area is the
destination of the data in operations acquiring data from the
communications processor (e.g., a read operation).

Bottom Node Content

The integer value entered in the bottom node specifies length; i.e., the
maximum number of registers in the data area. The length must be in a
range between 1 and 100.

Read/Write Operations

An MSTR write operation transfers data from a controlling device to the


drive controller. An MSTR read operation transfers data from the drive
controller to a controlling device on the network.

42 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Chapter 4—MODBUS Protocol

Control Block

The registers in the MSTR control block (the top node) contain the
following information in a read or write operation.

Table 17: Control Block Registers


Register Function Content
Displayed Operation type 1=Write; 2=Read
Displays a hex value indicating an MSTR error,
First implied Error status
when relevant.
Write = number of registers to be sent to slave
Second implied Length
Read = number of registers to be read from slave
Specifies starting register in the ATS46 controller
to be read from or written to. Note that 1 must be
Third implied Slave device data area added to starting register. For example, to start
with W4062, current, 4063 would be placed in the
third implied register.
Designates the first through fifth routing path
Fourth–Eighth
Routing 1–5 addresses, respectively. The last nonzero byte in
implied
the routing path is the destination device.

Refer to the user guide, MODICON Ladder Logic Block Library, part
number 840 USE 101 00, for more information.

Register Update Times

Table 18 lists the maximum register update times for a single ALTISTART
controller using MODBUS protocol. These times assume a baud rate of
9600 and no communication errors.

Table 18: Maximum Register Update Times

Number of MODBUS ASCII MODBUS RTU


Registers Read Time [1] Write Time [1] Read Time [1] Write Time [1]
Transferred (msec) (msec) (msec) (msec)
1 68 59 61 52
10 106 97 82 73
20 148 138 105 96
50 273 263 174 165
[1]
Values include query time, master processing time, and acknowledge (ACK) time.

© 1998 Square D All Rights Reserved 43


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Chapter 4—MODBUS Protocol October 1998

44 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Appendix A—Function Index

APPENDIX A
Table 19: Function Index Table
Description Type Characteristics Code Address [1] Page
Return to factory settings C Active on positive edge CMD, INT W4060,D 26
Select closed loop (torque control)
Control loop F CLP W4035,0 25
open loop (voltage regulation)
C Run command CMD, RUN W4060,5 26
A Acceleration ramp time ACC W4043 24
A Initial torque during acceleration TQ0 W4037 24
A Maximum torque during acceleration TLI W4036 24
A Limit current ILT W4039 24
A Boost level BST W4028 25
Start A Start time too long TLS W4033 25
A Stator loss compensation LSC W4027 25
D Controller ready ETA, RDY W4061,1 27
D Steady state ETA, 8 W4061,8 27
D Short-circuited ETA, 9 W4061,9 27
D Current limited ETA, LIM W4061,D 27
D Acceleration phase ETA, B W4061,B 27
C Freewheel stop command CMD, CAL W4060,8 26
C Decelerated stop command CMD, CAD W4060,7 26
C Braked stop command CMD, CAF W4060,6 26
C Control motor deceleration in cascade DMC W4060,3 26
Stop A Decel: deceleration ramp slope DEC W4044 24
A final torque during deceleration EDC W4038 24
A Braking: braking current BRC W4041 24
A adjustment of braking time EBA W4042 24
D Stop phase ETA, A W4061,A 27
C Reset thermal state CMD, RTH W4060,A 26
A Trip threshold (underload) TLS W4031 25
Motor protection A Motor nominal current In W4026 25
F Motor thermal protection THP W4034 25
D Motor thermal state LTH W4064 27
Controller protection F, A Trip current threshold OIL W4040 24
F Default assignment of phase rotation PHR W4032 25
D Phase rotation state PHE W4065 28
Mains supply
D No mains supply ETA, E W4061,E 27
D Mains supply frequency ETA, F W4061,F 27
D Current LCR W4062 27
D Cos (ϕ) motor power factor COS W4067 28
Measurements D Torque LTR W4063 27
D Elapsed time meter TFR W4068 28
D Reset elapsed time meter TRE W4060,C 26
F Test on low power motors SST W4035,5 25
Special operation
C Cascade motor operation CSC W4035,6 25
Types: C = Command F = Configuration A = Adjustment D = Display
[1]
When using MODBUS protocol, add 1 to the address.

© 1998 Square D All Rights Reserved 45


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Appendix A—Function Index October 1998

Table 19: Function Index Table (Continued)


Description Type Characteristics Code Address [1] Page
F Assignment of logic input LI LI W4022 24
F Assignment of logic output LO1 LO1 W4023 24
F Assignment of logic output LO2 LO2 W4035,3 25
F Assignment of analog output AO AO W4024 24
A Analog output scale ASC W4025 25
F Analog output range AO1 W4035,4 25
F Assignment of relay R1 R1 W4035,2 25
D State of I/O: Logic input LI LIO W4066 28
I/O management D Logic output LO1 W4066,1 28
D Logic output LO2 W4066,2 28
D Relay R1 W4066,3 28
D Relay R2 W4066,4 28
D Vigithem W4066,5 28
D Logic input LI_RUN W4066,6 28
D Logic input LI_STOP W4066,7 28
D Operating duty switch W4066,8 28
D Value of analog output AO SAO W4070 29
C Assignment of online commands DLI W4060,1 26
C Store adjustments in EEPROM MRE W4060,E 26
C Recall adjustments from EEPROM RRE W4060,F 26
F Product address ADR W2290 12
Communication &
F Protocol PRO W2291 12
terminal block
F Transmission speed SPD W2292 13
management
F Character format FOR W2293 13
D In local/line mode LOC W4061,0 27
D Stopped after request via terminal block ETA, 3 W4061,3 27
D Local control FLO W4061,5 27
C External fault command EFL W4060,2 26
C Controller reset command RST W4060,0 26
C No time out SLF NTO W4060,4 26
F Automatic reset ARS W4035,1 25
D Controller faulted FAI W4061,2 27
D Communication check inhibited NTO W4061 27
D Current threshold alarm W4061,7 27
D Motor thermal alarm OVL W4061,C 27
D Internal fault INF W4069,1 29
D Short-circuit fault OCF W4069,2 29
Fault and alarm D Phase inversion fault PIF W4069,3 29
management D Serial link fault SLF W4069,5 29
D External fault ETF W4069,6 29
D Start too long fault STF W4069,7 29
D Mains failure and start request fault USF W4069,8 29
D Phase fault PHF W4069,9 29
D Controller thermal fault OHF W4069,A 29
D Locked rotor in steady state fault LRF W4069,B 29
D Motor thermal overload fault OLF W4069,C 29
D Mains frequency fault FRF W4069,D 29
D Underload fault ULF W4069,F 29
D Time before starting alarm TBS W4071,0 29
D Fault order PTR W4090 29
Fault history D Fault register repetition DFT W4091 29
D Time counter repetition W4092 29
Types: C = Command F = Configuration A = Adjustment D = Display
[1] When using MODBUS protocol, add 1 to the address.

46 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Appendix B—Function Index by Address

APPENDIX B
Table 20: Function Index Table by Address
Address [1] Description Type Characteristics Code Page
Communication & terminal
W2290 F Product address ADR 12
block management
Communication & terminal
W2291 F Protocol PRO 12
block management
Communication & terminal
W2292 F Transmission speed SPD 13
block management
Communication & terminal
W2293 F Character format FOR 13
block management
W4022 I/O management F Assignment of logic input LI LI 24
W4023 I/O management F Assignment of logic output LO1 LO1 24
W4024 I/O management F Assignment of analog output AO AO 24
W4025 I/O management A Analog output scale ASC 25
W4026 Motor protection A Motor nominal current In 25
W4027 Start A Stator loss compensation LSC 25
W4028 Start A Boost level BST 25
W4031 Motor protection A Trip threshold (underload) TLS 25
W4032 Mains supply F Default assignment of phase rotation PHR 25
W4033 Start A Start time too long TLS 25
W4034 Motor protection F Motor thermal protection THP 25
Select closed loop (torque control)
W4035,0 Control loop F CLP 25
open loop (voltage regulation)
W4035,1 Fault & alarm management F Automatic reset ARS 25
W4035,2 I/O management F Assignment of relay R1 R1 25
W4035,3 I/O management F Assignment of logic output LO2 LO2 25
W4035,4 I/O management F Analog output range AO1 25
W4035,5 Special operation F Test on low power motors SST 25
W4035,6 Special operation C Cascade motor operation CSC 25
W4036 Start A Maximum torque during acceleration TLI 24
W4037 Start A Initial torque during acceleration TQ0 24
W4038 Stop A Decel: final torque during deceleration EDC 24
W4039 Start A Limit current ILT 24
W4040 Controller protection F, A Trip current threshold OIL 24
W4041 Stop A Braking: braking current BRC 24
W4042 Stop A Braking: adjustment of braking time EBA 24
Types: C = Command F = Configuration A = Adjustment D = Display
[1] When using MODBUS protocol, add 1 to the address.

© 1998 Square D All Rights Reserved 47


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Appendix B—Function Index by Address October 1998

Table 20: Function Index Table by Address (Continued)


Address [1] Description Type Characteristics Code Page
W4043 Start A Acceleration ramp time ACC 24
W4044 Stop A Decel: deceleration ramp slope DEC 24
W4060,0 Fault & alarm management C Controller reset command RST 26
Communication & terminal
W4060,1 C Assignment of online commands DLI 26
block management
W4060,2 Fault & alarm management C External fault command EFL 26
W4060,3 Stop C Control motor deceleration in cascade DMC 26
W4060,4 Fault & alarm management C No time out SLF NTO 26
W4060,5 Start C Run command CMD, RUN 26
W4060,6 Stop C Braked stop command CMD, CAF 26
W4060,7 Stop C Decelerated stop command CMD, CAD 26
W4060,8 Stop C Freewheel stop command CMD, CAL 26
W4060,A Motor protection C Reset thermal state CMD, RTH 26
W4060,C Measurements D Reset elapsed time meter TRE 26
W4060,D Return to factory settings C Active on positive edge CMD, INT 26
Communication & terminal
W4060,E C Store adjustments in EEPROM MRE 26
block management
Communication & terminal
W4060,F C Recall adjustments from EEPROM RRE 26
block management
W4061 Fault & alarm management D Communication check inhibited NTO 27
Communication & terminal
W4061,0 D In local/line mode LOC 27
block management
W4061,1 Start D Controller ready ETA, RDY 27
W4061,2 Fault & alarm management D Controller faulted FAI 27
Communication & terminal
W4061,3 D Stopped after request via terminal block ETA, 3 27
block management
Communication & terminal
W4061,5 D Local control FLO 27
block management
W4061,7 Fault & alarm management D Current threshold alarm 27
W4061,8 Start D Steady state ETA, 8 27
W4061,9 Start D Short-circuited ETA, 9 27
W4061,A Stop D Stop phase ETA, A 27
W4061,B Start D Acceleration phase ETA, B 27
W4061,C Fault & alarm management D Motor thermal alarm OVL 27
W4061,D Start D Current limited ETA, LIM 27
W4061,E Mains supply D No mains supply ETA, E 27
Types: C = Command F = Configuration A = Adjustment D = Display
[1]
When using MODBUS protocol, add 1 to the address.

48 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Appendix B—Function Index by Address

Table 20: Function Index Table by Address (Continued)


Address [1] Description Type Characteristics Code Page
W4061,F Mains supply D Mains supply frequency ETA, F 27
W4062 Measurements D Current LCR 27
W4063 Measurements D Torque LTR 27
W4064 Motor protection D Motor thermal state LTH 27
W4065 Mains supply D Phase rotation state PHE 28
W4066 I/O management D State of I/O: Logic input LI LIO 28
W4066,1 I/O management D Logic output LO1 28
W4066,2 I/O management D Logic output LO2 28
W4066,3 I/O management D Relay R1 28
W4066,4 I/O management D Relay R2 28
W4066,5 I/O management D Vigithem 28
W4066,6 I/O management D Logic input LI_RUN 28
W4066,7 I/O management D Logic input LI_STOP 28
W4066,8 I/O management D Operating duty switch 28
W4067 Measurements D Cos (ϕ) motor power factor COS 28
W4068 Measurements D Elapsed time meter TFR 28
W4069,1 Fault & alarm management D Internal fault INF 29
W4069,2 Fault & alarm management D Short-circuit fault OCF 29
W4069,3 Fault & alarm management D Phase inversion fault PIF 29
W4069,5 Fault & alarm management D Serial link fault SLF 29
W4069,6 Fault & alarm management D External fault ETF 29
W4069,7 Fault & alarm management D Start too long fault STF 29
W4069,8 Fault & alarm management D Mains failure and start request fault USF 29
W4069,9 Fault & alarm management D Phase fault PHF 29
W4069,A Fault & alarm management D Controller thermal fault OHF 29
W4069,B Fault & alarm management D Locked rotor in steady state fault LRF 29
W4069,C Fault & alarm management D Motor thermal overload fault OLF 29
W4069,D Fault & alarm management D Mains frequency fault FRF 29
W4069,F Fault & alarm management D Underload fault ULF 29
W4070 I/O management D Value of analog output AO SAO 29
W4071,0 Fault & alarm management D Time before starting alarm TBS 29
W4090 Fault history D Fault order PTR 29
W4091 Fault history D Fault register repetition DFT 29
W4092 Fault history D Time counter repetition 29
Types: C = Command F = Configuration A = Adjustment D = Display
[1]
When using MODBUS protocol, add 1 to the address.

© 1998 Square D All Rights Reserved 49


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Appendix B—Function Index by Address October 1998

50 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Appendix C—Configuration with Windows 95 or Later Versions

APPENDIX C
If you have Windows 95, or a later version, to configure the ATS46
controller for MODBUS or UNI-TELWAY communications, first access the
HyperTerminal utility or a comparable Terminal Emulation Program.
Configure the COM port, terminal properties, and ASCII set-up as
illustrated in Figures 21 through 22.

Figure 21: Accessing HyperTerminal (Windows NT Example)

© 1998 Square D All Rights Reserved 51


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Appendix C—Configuration with Windows 95 or Later Versions October 1998

Figure 22: Creating a New Connection

Figure 23: Selecting a COM Port

52 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Appendix C—Configuration with Windows 95 or Later Versions

Figure 24: Setting COM Port Properties

Figure 25: Selecting Emulation Type

© 1998 Square D All Rights Reserved 53


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Appendix C—Configuration with Windows 95 or Later Versions October 1998

Figure 26: ASCII Set-Up

Figure 27: Sample Terminal Commands and ATS46 Responses

54 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Appendix C—Configuration with Windows 95 or Later Versions

© 1998 Square D All Rights Reserved 55


ALTISTART 46 Communication Option Bulletin No. VD0C32S303A
Appendix C—Configuration with Windows 95 or Later Versions October 1998

56 © 1998 Square D All Rights Reserved


Bulletin No. VD0C32S303A ALTISTART 46 Communication Option
October 1998 Appendix C—Configuration with Windows 95 or Later Versions

© 1998 Square D All Rights Reserved 57


Square D and are registered trademarks of Square D Company.
MICROSOFT and WINDOWS are registered trademarks of Microsoft
Corporation. MODBUS is a registered trademark and MODICON is a
trademark of Schneider Automation, Inc. ALTISTART is a registered
For MODICON/MODBUS support, trademark and UNI-TELWAY is a trademark of Telemecanique S.A. or
please contact Schneider its successor-in-interest, Schneider Electric S.A.
Automation at 1-800-468-5342.
Electrical equipment should be serviced only by qualified electrical
Square D Company maintenance personnel. No responsibility is assumed by Square D for
8001 Hwy 64 East any consequences arising out of the use of this material.
Knightdale, NC 27545
Bulletin No. VD0C32S303A October 1998 Replaces VD0C32S303
(919) 266-3671 dated September 1998 © 1998 Square D All Rights Reserved

You might also like