OIL PUMP TYPE TA

for Fuel oil #2 to #6 applications TA


TA - US - Ed.4 - June 2019
This is a general specification leaflet ; for specific applications not covered
herein, contact Suntec.
PUMP
The SUNTEC TA oil pump is specially designed for industrial heating applications IDENTIFICATION
using fuel oil #2 to #6. It is fitted with a preheater location to render cold starting (Not all model combinations are available
easier. Consult your Suntec representative)

APPLICATIONS

- Fuel oil #2 to #6 (for lighter oil and kerosene applications, contact SUNTEC), TA : Pressure regulation
B6-B20 (blends from 6% up to 20% biodiesel, per ASTM D396).
- One or two-pipe system.

PUMP OPERATING PRINCIPLE


Gear set capacity
The gear set draws oil from the tank and transfers it to the valve regulating the oil (see pump capacity curves)
pressure to the nozzle line. All oil which does not go through the nozzle line will
be dumped through the valve back to the return line in two pipe installation or, if it
is a one-pipe installation, back to the gear-set.
Shaft rotation
Bleed :
(seen from shaft end)
The plug of the pressure gauge port must be loosened until the air is evacuated A : clockwise rotation
from the system. C : anti clockwise rotation

Note :
All TA models are delivered for two-pipe system (by-pass plug fitted in vacuum
gauge port).
TA 2 A 40 10 7
For one-pipe system, the by-pass plug must be removed and the return port sealed
by steel plug and washer.

PREHEATING FACILITY
Model number
Care should be taken to avoid starting pump with high viscosity cold oil leading to
pump and coupling damage. For this reason, the TA pump body includes a cavity
to accept an electric preheater. This cavity has been located to give maximum heat
transfer from the heater to the oil in the pump without direct contact between the
heater cartridge and the oil. Revision number
Heaters should be connected for a period of time prior to starting the pump. When
the right temperature is reached, they can be switched off or left permanently
switched on to maintain fluid oil in the pump during the periodic burner shut-downs.
The oil supply, pipes and filters must be separately heated.

Oil under suction Vacuum or Vacuum or


inlet pressure Pressure inlet pressure Pressure
Oil under pressure gauge port gauge port gauge port gauge port
By-passed oil
returned to tank,
or to suction

Intake To Intake To
from Tank nozzle from Tank nozzle
By-pass By-pass
plug plug
inserted removed

Pressure Pressure
adjustment adjustment

TWO PIPE ONE PIPE Return


Return INSTALLATION INSTALLATION plugged

Suntec Industries Incorporated - 60 Aberdeen Drive - Glasgow, KY 42141 - USA


Tel : 270 651 7116 - Fax : 270 651 9276 - Mail : info@suntecpumps.com - www.suntecpumps.com
TECHNICAL DATA
General Hydraulic data
Mounting Flange mounting Nozzle pressure range* @ 2,4 cSt @75 cst

Connection threads Cylindrical according to Conical TAR 2/3/4: 100-350 psi 100-580 psi
ISO 228/1 TAR 5: 100-350 psi 100-435 psi
Inlet and return G 1/2 1/2 NPTF
Nozzle outlet G 1/2 1/2 NPTF * : optional pressure range = 30 - 100 psi,  contact SUNTEC
Pressure gauge port G 1/4 1/4 NPTF Delivery pressure setting 435 psi
Vacuum gauge port G 1/4 1/4 NPTF
Operating viscosity** 2,4 - 75 mm²/s (cSt)
Shaft Ø 12 mm

By-pass plug Inserted in vacuum gauge port for 2 pipe system; **: for viscosity lower than 2 cSt, the maximum pressure has to be reduced to
to be removed with a 3/16" Allen key for 1 pipe 290 psi for TAR2/3/4 and 245 psi for TAR5
system Oil temperature 32 - 302°F in the pump
Weight 11,9 lbs (TAR2) 12,6 lbs (TAR3) Inlet pressure 6,5 psi max. vacuum to prevent air separation
13,2 lbs (TAR4) 14,1 lbs (TAR5) from oil
Inlet feed pressure : 75 psi max.
Choice of heater Return pressure 75 psi max.
Cartridge Ø 12 mm
Rated speed 3600 rpm max.
Fitting according to EN 50262
Torque (@ 40 rpm) 0.3 N.m
Rating 80-100 W

Pump capacity Power consumption


Capacity (GpH) Power (W)

Rated speed :
1725 rpm
TA5

Viscosity :
TA4 75 cSt
2,4 cSt
TA5 TA3
TA4 TA2
TA3
TA2

Pressure (PSI) Pressure (PSI)


Capacity (GpH) Power (W)

Rated speed :
3450 rpm

Viscosity :
75 cSt
2,4 cSt

Pressure (PSI)
Pressure (PSI)
Data shown are for new pumps, with no allowance for wear.

PUMP DIMENSIONS Example shows pump with "C" rotation - Reverse all pump connections for "A" rotation - Dimensions in mm.
125
TA2 TA3 TA4 TA5
66 101
A
(mm) 50 54 58 64  22,5 22,5 
36

 
B
Ø54 Ø11
130
Ø19 min
B M16x1,5
85 
4
 Ø12
13,5
1,5 max
B-B  8 min
12 min Ø11
36 A 102 66 Ø12,1 min
71,5 min

 Nozzle outlet  Pressure


 Suction Return  gauge port
 Vacuum or inlet pressure gauge port
and internal by-pass plug
 Pressure
adjustment
 Preheater
cavity
We reserve the right to change specifications without prior notice. TA - US - Ed.4 - June. 2019