Technical Spesification of Distribution Transformer 33/0.416 KV
Technical Spesification of Distribution Transformer 33/0.416 KV
Technical Spesification of Distribution Transformer 33/0.416 KV
416 kV
Ministry of Electricity
Planning and Studies Office
Baghdad – Iraq
TECHNICAL SPESIFICATION OF
DISTRIBUTION TRANSFORMERS
Tenderer are invited for the design , manufacture , testing and supply of a
33000/416 volt, oil immersed copper winding outdoor type (Directly under the sun)
transformers to be supplied complete with all necessary fittings , accessories off-
load tap changer , insulating oil and spare parts . . . etc.
The transformer is to be bolted type hermetically sealed bushing insulators on both
H.T and L.T sides for the following rating: 100, 250, 400, for 630, 1000, 1600, and
2000 KVA to be box type a valid ISO 9001 certificate required.
2- GENERAL REQUIREMENTS :
The transformers shall be of first class quality and design for continuous
satisfactory operation as continuity of supply is of prime consideration. The design
shall be allow all necessary precaution for the safety of operation and maintenance
personnel. The transformers shall operate satisfactorily under variations of load,
voltage or short circuit or other conditions which may occur on the system provided
that these variations are within the assigned rating of the apparatus. All the
equipment shall be designed to obviate the risk of accidental short circuit.
(1)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
2-2 Altitudes
From sea level up to (1000m)
2-7 Guarantee:
The tenderer shall confirm than the transformer guaranteed against all
defects arising from faults design, materials and workmanship, for a period of
(12) months from commissioning or (18) months from delivery, whichever
period expires earlier.
(2)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
3- SYSTEM COPOSITION
The transformer shall operate in distribution systems where most of the network
is overhead lines and comprising partly underground cable.
4-TECHNICAL SPECIFICATION
The transformers shall be copper winding, hermetically sealed of the bolted
cover type and should have the following characteristics:-
•Rated outputs ONAN …. 100, 250, 400, 630, 1000, 1600, and 2000 KVA.
•Duty…….step-down, outdoor bushing type for rating power 100, 250,400, plug in
type for 630, 1000, 1600 and 2000 KVA
•Type: wound, 3-phase
•Rated voltage at no load …. H.V. 33kV L.V- 416 volt.
•System frequency ………50HZ
•Interphase Connection … H.V. Delta L.V- star with neutral brought out.
•Vector relationship …. . . . .. Dyn 11
•Type of Cooling …. ONAN
•Temperature rise ………(i) 45ْk in top oil by thermometer
(ii) 50ْk in winding by resistance
•The efficiency (at unity power factor and 100% of rated power) of the
transformer should be not less than the following:
1. 100 kVA ……. 98.1%
2. 250 kVA ……. 98.6%
3. 400 kVA ……. 98.7%
4. 630 kVA ……. 98.8%
5. 1000 kVA …... 98.9%
6. 1600, 2000 kVA ……99%
•The duration of the short circuit (for calculation) to rise the temp. of windings
from 1050 C to 2500 C should be not less than (5 Sec.) according to IEC 60076-part
5 –clause (4.1.5).
•The thickness of the radiator plates should be shock resistant and don’t affect
heat dissipation according to tender requirements.
•The low voltage winding must be of copper foil for 250, 400, 630, 1000, 1600,
and 2000 KVA transformers.
(3)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
•Off circuit tapings . . . . . . five tapping for + 2.5% + - 5% on the H.T winding for off
circuit operation externally. The mechanism must be of
the robust and definite position type with a click
indicating position arrived during tap changing.
•System Highest Voltage. H.V side 36 kV
•Terminal arrangement of transformers:-
-The 33 kV side terminal is to be a clamp type with eyebolt and nut suitable for
conductors up to 150 mm2 copper (for100, 250, 400 KVA). For 630, 1000, 1600,
and 2000 KVA the 33 kV side terminal is to be plug in type only.
-The low voltage terminals are to be flat bar type with holes suitable for compression
type terminal lug.
The sizes of L.V side single cable as follows:-
For 250 KVA transformer 8×1×95mm2 copper (not less than 2 holes per phase)
For 400KVA transformer 7×1×150 mm2 copper (not less than 3 holes per phase)
For 630 KVA transformer 11×1×240 mm2 copper (not less than 3 holes per phase)
For 1000 KVA transformer 14×1×240 mm2 copper (not less than 3 holes per phase)
For 1600 KVA transformer 21×1×240 mm2 copper (not less than 4 holes per phase)
For 2000 KVA transformer 28 × 1× 240 mm2 copper (not less than 5 holes per phase)
Terminal arrangement of outdoors transformers must be porcelain bushing
insulator (brown colored preferable) mounted on the top cover of transformer
for both H.T. and L.T, with arcing horn (double air gap is preferable) on H.T.
bushing for outdoor transformer only. Neutral bushing should be
distinguished from phase bushing.
- For 630, 1000, 1600, and 2000 kVA transformers should be plug-in type for H.V.
side (according to the tender requirements) with glands and cable holes suitable
for cable size of 1 x 50 mm2 , 18/30 kV.
Note: For 630, 1000, 1600, and 2000 kVA can use Bus-bar as
another alternative if needed
(4)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
6-painting
- The painting should be oil and weather (dust, humidity and heat …. etc.)
resistant type and the final coat is to be aluminum paint or equivalent.
Any alternative finishing which gives better heat radiation is accepted and
must be confirmed by calculations.
- Ministry of Electricity logo must be engraved on the cover of the transformer
at a suitable place.
7- insulating oil
The transformer is to be shipped with first filling of oil which shall be
(uninhibited insulation oil), according to the latest IEC 60296.
(5)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
9- Test
9-1 Inspection:
The material shall be subjected to inspection and test by our inspectors or
international inspector at any time during manufacture.
The manufacture shall provide all inspection facilities for the said
inspection and inspection shall be made at the place of manufacture or at
international testing facilities.
The inspector shall have the right of rejecting any portion of the material at
any time during manufacture if it does not meet with the requirements of this
specification in all particulars. He shall have the right of overseeing the packing
and shipping of all material to be supplied.
b- Routine tests
Each transformer shall be subjected to all the routine tests specified in
section twelve of IEC 76/1967.
(6)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
(7)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
10-3 Language:
The language to be used in the drawings and instruction book shall be English.
10-4 Dimension:
Due to the space requirement in our system, it is important for the
participants in this tender to make sure that the dimensions of each type of the
required transformers to be as small as possible, the following table is indicative
as a maximum for each single dimension:-
Table of Dimensions
Transformer Length Width Height
KVA mm mm mm
250 1580 930 1400
400 1710 1040 1500
11- Packing
The supplier will pack or protect the goods in the most appropriate manner. He
will be responsible for any loss or damage arising from careless packing or
protection up to the place of final destination after completion of the inspection
and tests at the factory, each item shall be packed for export shipment. All parts
provided for shipping purposes only and which are to be removed at the time of
erection shall be conspicuously tagged.
The method of packing shall be such as to protect all the items against excessive
corrosion of dampness, and shall afford adequate protection against breakage or
other injury, or loss due to breakage of cases or crates from the time the items
(8)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
leaves the factory until finally installed at the substation during which time, the
apparatus will travel by rail by a long sea voyage again by rail or truck to the site
of the substation. The equipment will also undoubtedly stand on wharves and in
the open during and in between periods of transportation and will thereby be
exposed to heavy rain, hot sun, humid climate and sudden changes of
temperature.
Owing to the numerous handlings, the containers should be very strong also extra
ordinary care should be given to the packing of the equipment and especially the
items having insulating material to prevent the injury due to moisture, from
sources external to the packing or from excessive condensation with the packing.
(9)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
SCHEDULE (A)
SCHEDULE OF GUARANTEED PERFORMANCE AND OTHER
TECHNICAL PARTICULARS
(TO BE COMPLETED BY THE TENDERER)
1- Name of manufacturer.
2- Country of origin.
3- Standard on which performance data is based.
4- Continuous maximum rating for the specified temperature rise and ambient
temperature ONAN rating (KVA)
5- Rated temperature rise ( K )
a- Oil by thermometer.
b- Winding by resistance.
6- Hottest spot temperature rise (K).
7- No-load voltage ratio at normal tap & vector relationship.
8- Exciting current referred to H.V. and 50 Hz at ..… – (Amps)
a- 90% rated voltage.
b- 100% rated voltage.
c- 110% rated voltage.
9- Power factor of exciting current at 100% rated voltage and 50 Hz…..
10- Iron losses at 50 HZ …… (kW).
a- 90% rated voltage.
b- 100% rated voltage.
c- 110% rated voltage.
11- Copper losses at full load (on rating) and at 750 C …..… (kW)
12- Total losses ….…... (kW).
13- Resistance voltage at full load and 750C ……. (%).
14- Reactance voltage at full load and 75 0C ……. (%)
15- Impedance voltage at full load and 75 0C ……. (%)
a- At normal tap.
b- At highest tap.
c- At lowest tap.
16- Resistance of H.V. winding per phase at 200C ……. (ohms).
17- Resistance of L.V. winding per phase at 20 0C……. (ohms).
18- Regulation at full load at 75 0C ……. (%)
a- 1.0 power factor.
b- 0.8 P.F lagging.
(10)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
23- Insulation of
a- Core bolts
b- Core bolts washer
c- Side plates
d- Core laminations
(11)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
(12)
TECHNICAL SPESIFICATION OF DISTRIBUTION TRANSFORMER 33/0.416 kV
SCHEDULE (B)
OIL CHARACTERISTICS TABLE (TO BE COMPLETED BY THE TENDERER)
NO. DESCRIPTION SPECIFICATIONS UNIT
1. MAKER’S NAME
2. REFERENCE NAME OF OIL
3. SLUDGE VALUE (Wt %)
4. FLASH POINT (CLOSED) C 0
5. POUR POINT C 0
6. VISCOSITY AT:
a. 400 C mm2 /s
b. -300 C mm2 /s
7. ELECTRIC STRENGTH (BREAKDOWN (KV)
8. ACIDITY(NEUTRALIZATION VALUE)
a. TOTAL mg KOH/g
b. INORGANIC mg KOH/g
9. COPPER DISCELERATION
10. CRACKLE
11. SPECIFIC GRAVITY
12. SULFER CONTENT
13. DIELECTRIC DISSIPATION FACTOR (tan δ)
(13)