PVI-6000-OUTD-US Manual PDF
PVI-6000-OUTD-US Manual PDF
PVI-6000-OUTD-US Manual PDF
AURORA
Photovoltaic Inverters
REVISION TABLE
This manual contains important safety and operational instructions that must be
accurately understood and followed during the installation and maintenance of the
equipment.
To reduce the risk of electrical shock hazards, and to make sure the equipment is
safely installed and commissioned, special safety symbols are used in this manual to
highlight potential safety risks and important safety information. The symbols are:
The equipment is provided with several labels, some of them with a yellow
background, which are related to safety issues.
Make sure to read the labels and fully understand them before installing the
equipment.
The labels utilize the following symbols:
Phase
Grounding (Earth)
Installation and Operator’s Manual Page 4 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
FOREWORD
¾ The installation of Aurora must be performed in full compliance with national and
local standards and regulations
¾ AURORA has no spare parts to replace.
For any maintenance or repair please contact the nearest authorized repair center.
Please contact your reseller if you need to know the nearest authorized repair
center.
¾ Read and understand all the instructions contained in this manual and become
familiar with the safety symbols in the relevant paragraphs before you install and
commission the equipment
¾ The connection to the distribution grid must be done only after receiving approval
from the distribution utility as required by national and state interconnection
regulations, and can be done only by qualified personnel.
¾ Cover the photovoltaic panels with dark opaque sheets before they are connected
to avoid any chance of high voltages to appear at the connecting cable
terminations.
GENERAL
During inverter operation, some parts can be powered, some not properly insulated
and, in some cases, some parts can move or rotate, or some surfaces be hot.
Unauthorized removal of the necessary protections, improper use, wrong installation
or wrong operation may lead to serious damage to people and objects.
Transport, handling, installation, commissioning and maintenance must be performed
by qualified and trained personnel (all accident prevention rules in force in the user's
country must be observed ! ! !).
According to these basic safety rules, qualified and trained people have skills for the
assembling, start-up and operation of the product, as well as the necessary
requirements and qualifications to perform such operations.
Installation and Operator’s Manual Page 5 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
ASSEMBLY
Devices shall be assembled and cooled according to the specifications mentioned in
the corresponding documents.
In particular, during transport and handling, parts shall not be bent and/or the
insulation distances shall not be changed. There should be no contact between
electronic parts and connection terminals.
Electrical parts must not be mechanically damaged or destroyed (potential health risk).
ELECTRICAL CONNECTION
With the inverter powered, comply with all prevailing national regulations on
accidents prevention.
Electrical connections shall be carried out in accordance with the applicable
regulations, such as conductor sections, fuses, PE connection.
OPERATION
Systems with inverters shall be provided with further control and protective devices in
compliance with the corresponding prevailing safety rules, such as those relating to the
compliance with technical equipment, accident-preventing regulations, etc. Any
calibration change shall be made using the operational software. Once the inverter has
been disconnected from the power grid, powered parts and electrical connections shall
not be touched as some capacitors could be charged. Comply with all corresponding
marks and symbols present on each device. During operation, make sure that all covers
and doors are closed.
MAINTENANCE AND SERVICE
Comply with manufacturer’s recommendations.
PVI-5000-OUTD-US
PVI-6000-OUTD-US
This document applies to the above-mentioned inverters, only.
The name plate affixed to the inverter provides the following information:
1) Manufacturing Part Number
2) Model Number
3) Serial Number
4) Week/Year of Manufacture
Installation and Operator’s Manual Page 7 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
CONTENTS
1 FOREWORD ...............................................................................10
1.1 PHOTOVOLTAIC ENERGY ...................................................................10
2 SYSTEM DESCRIPTION ..........................................................11
2.1 KEY ELEMENTS OF A PHOTOVOLTAIC SYSTEM: “STRINGS” AND
“ARRAYS” .............................................................................................................11
2.2 DATA TRANSMISSION AND CHECK .............................................................14
2.3 AURORA TECHNICAL DESCRIPTION.........................................................14
2.4 PROTECTIVE DEVICES ................................................................................16
2.4.1 Anti-Islanding ........................................................................................16
2.4.2 Panel Ground Fault ...............................................................................16
2.4.3 Further Protective Devices ....................................................................16
3 INSTALLATION.........................................................................17
3.1 PACKAGE INSPECTION................................................................................17
3.1.1 Inspecting package contents ..................................................................18
3.2 SELECTING THE INSTALLATION PLACE .......................................................19
3.3 BEFORE PERFORMING THE ELECTRICAL CONNECTIONS ..............................23
3.3.1 Switch Box ELECTRICAL CONNECTING and/or DISCONNECTING
procedure............................................................................................................24
3.3.2 Access to the internal terminal Blok removing the frontal cover...........26
3.3.3 AURORA Switch Box description ..........................................................27
3.3.4 AURORA typical electrical installations. ..............................................30
3.3.5 Possible AURORA D.C input configuration ..........................................31
3.3.5.1 AURORA Connection to one single Photovoltaic array
32
3.3.5.2 PARALLEL CONNECTION of the AURORA D.C
inputs 33
3.3.6 Connection to the AC GRID ..................................................................36
3.4 REMUVAL OF THE AURORA INVERTER FROM THE D.C SWITCH................39
3.4.1 ELECTRICAL DISCONNECTION E OF THE INVERTER FROM THE
SWITCH BOX PROCEDURE.............................................................................39
3.5 LITIUM BATTERY CR2032 SOBSTITUTION ..................................................40
4 START-UP ...................................................................................42
Installation and Operator’s Manual Page 8 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
8 TECHNICAL FEATURES.........................................................81
8.1 INPUT VALUES ...........................................................................................81
8.2 OUTPUT VALUES........................................................................................84
8.3 GRID PROTECTION CHARACTERISTICS ........................................................85
8.4 GENERAL CHARACTERISTICS .....................................................................86
8.5 POWER DERATING .....................................................................................87
Installation and Operator’s Manual Page 10 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
1 FOREWORD
2 SYSTEM DESCRIPTION
The AURORA inverter is capable of feeding a power grid using the power generated
by photovoltaic panels.
Photovoltaic panels transform the sun-radiated energy into electrical energy in the
form of direct (DC) current (through a photovoltaic field, also known as PV
generator). In order to utilize this energy and feed it back to the distribution grid, this
energy shall be turned into alternating (AC) current. Aurora does this conversion, also
known as DC to AC inversion, in a very efficient way, without using rotating parts but
just static power electronic devices.
When used in parallel with the grid, the alternate current generated by the inverter is
directly fed to the domestic distribution circuit, which is in its turn also connected to
the public power distribution grid.
The solar energy system can thus feed all the connected users, such as lighting
devices, household appliances, etc.
When the photovoltaic system is not generating sufficient energy, the power required
to ensure proper operation of connected users is taken from the public power grid.
While if the produced energy is too much, it is directly fed to the grid, thus becoming
available to other users.
According to national and local standards and regulations the produced energy can be
sold to the grid or credited to the user against future consumption, thus granting a great
saving of money.
2.1 Key elements of a photovoltaic system: “STRINGS” and “ARRAYS”
The so-called STRINGS technology has been developed in order to reduce the
installation costs of a photovoltaic system as much as possible. These costs are mainly
related to the wiring operations on inverter DC side and the consequent distribution on
the AC side.
A photovoltaic panel is composed of many photovoltaic cells assembled on the same
mount. A STRING is composed of a certain number of panels electrically connected in
series. An ARRAY is composed by one or more strings connected in parallel.
Larger photovoltaic systems may be implemented by using several arrays connected to
one or more AURORA inverters.
Installation and Operator’s Manual Page 12 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
The greater the number of panels in each string, the lower the cost and the less
complex the wiring connections of the system.
PV Cell
+ PV Panel
PV String
+
_ + PV Array
WARNING: String voltage shall not exceed 600 Vdc for any reason, so as
to avoid damage to the equipment.
NOTE: A minimum input voltage of 200 Vdc is required for Aurora to start
the grid connection sequence. Once connected, Aurora will transfer the
maximum power available for any input DC voltage value in a 90V to
580Vdc range to the grid.
Installation and Operator’s Manual Page 13 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
The total current of an array must also be within the capability limits of the inverter.
For AURORA, the limit is set at 18 Adc maximum for each input. The AURORA
model rated 6000W/5000W is capable of handling 2 separate arrays. The maximum
current limit for each input is 18Adc.
If the output of photovoltaic system exceeds the capacity of a single inverter,
additional AURORA inverters can be added to the system; each inverter will be
connected to an adequate section of the photovoltaic filed on the DC side and to the
grid on the AC side.
Each Aurora inverter will work independent of the others and will push to the grid the
maximum power available from its own section of the photovoltaic panels.
There are several factors and considerations to be taken into account when designing a
photovoltaic systems, such as the type of panels, available room, location, long-term
target output, etc. The system configurator available on Power-One's web site at
www.power-one.com may help in sizing a photovoltaic system.
2.4.1 Anti-Islanding
When the local power distribution grid fails due to a fault or when the equipment is
shut down for maintenance operations, Aurora shall be physically disconnected under
safety conditions, so as to protect the people working on the grid, in full compliance
with the applicable prevailing national standards and regulations. To avoid any
possible islanding operation, Aurora is provided with an automatic disconnection
protective system called Anti-Islanding.
The AURORA PVI-5000/6000-OUTD-US model is equipped with a state-of-the-art
anti-islanding protection system certified to the following standards and regulations:
¾ CSA-C22.2 N.107.1-01 UL Std N.1741
2.4.2 Panel Ground Fault
This version of AURORA has been designed for use with panels with a floating
connection (positive and negative terminals not connected to ground). A sophisticated
ground protection circuit continually monitors the ground connection; when it detects
a ground fault, this circuit shuts down AURORA and turns on a red LED on the front
panel to indicate a ground fault condition. The AURORA inverter is equipped with a
terminal for the system grounding conductor; see section 3.6 (step 3) for more details.
NOTE: For more details of AURORA shutdown or possible causes of
malfunction, please refer to sections 5.3 and 5.4.
Many control devices are fitted to Aurora, making its structure redundant, but at
the same time ensuring a perfect and fully safe operation.
Installation and Operator’s Manual Page 17 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
3 INSTALLATION
The following figure shows the recommended minimum clearances around the
inverter:
RECOMMENDED ARRANGEMENT
NOTE: Tilted mounting is allowed (see fig.7), but will worsen heat
dissipation and may result in self derating.
WARNING: Unit surface may become hot to the touch during operation.
DO NOT touch unit surface to avoid burns.
AURORA shall be mounted vertically as shown in fig.5, 6, 7, in fig MP01 and MP02
and always following the relative instructions.
In the box is provided a mounting kit with 4 screw and 4 wall plugs needed to mount
the metal bracket to a concrete wall. The screw can be mounted in any 4 of the 6 hole
presents in the bracket (pos B in fig.8 MP-01)
If needed to insure stability of the inverter is possible to use 2 additional screw in the 2
hole in pos "A" in the same figure.
WARNING: the bracket need to be mounted vertically to the wall and the
side with the hook (pos C in fig: MP-02- Wall Mounting) shall be mounted
up side as shown in the picture
If the installation is done on a concrete wall the provided wall plug shall be
used, the mounting hole in the wall shall be 10mm diameter and 75mm deep.
When the wall is made by different material the installation shall be done
using adequate mounting material, Power-One recommend to use always
stainless steal screw
Once the bracket is secured to the wall install the inverter as described in fig. 8 MP-02.
The inverter is hang to the bracket using the hook D and F that need to be well inserted
in the counterpart C and E (D connects to C and F connects to E)
The inverter need to be lifted up and then slide down making sure that the connecting
point in the bracket and in the back of the inverter engage properly.
Once the inverter is hang to the wall need to be secured using a M6x10 screw and the
relative washer that will pass through the opening on the lower side of the inverter
(pos H in Fig.8: MP-02 – Wall mounting) and tied to the pem in position G in the
bracket.
Installation and Operator’s Manual Page 22 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
When the ambient temperature rise above 50°C the inverter may self derate
the output power.
Always make sure that the airflow is not blocked in the installations.
Installation and Operator’s Manual Page 23 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
STEP 1 If the inverter is connected to the AC Grid (Fig 15-“terminal block for AC
connection”– pos. "1", "2" e "3") DISCONNECT the inverter from the AC Grid by
opening the switch indicated as Part “D” in Fig 9-“Connecting Diagram”
STEP 2 Cover carefully all the photovoltaic panel using appropriate cover or perform
the grid CONNECTION and/or DISCONNECTION operation during night ours.
Anyway make sure that the photovoltaic panels do not provide energy during this
operation.
Installation and Operator’s Manual Page 25 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
When selecting the wire for the installation the correct size needs to be
selected in order to avoid efficiency loses, refer to the Table “Tab CN01- SC
(section 3.3.7) grid connection to select the cable size.
The electrical power and signals wiring from the inverter to the A.C Grid and
to the photovoltaic panel are done trough the Switch Box as described in"
Fig.11 SB 01 – D.C. Switch Box Layout" –using the access window in pos
“A” for the power cable and the Windows in pos “D” for the signal cable.
Installation and Operator’s Manual Page 26 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
3.3.2 Access to the internal terminal Blok removing the frontal cover.
To remove the cover untightenn the 4 screw shown in fig 10 in pos “a” using the flat
screwdriver provided in the box with the inverter.
A A
A A
B B
B
B
When the connection operation are completed tighten the screws to the cover with at
least1.5Nm (13.2 in-lbs) torque to insure proper waterproof sealing
Installation and Operator’s Manual Page 27 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
WARNING: due to the high Voltage present in the power cable in the Switch
Box always PERFORM THE “ Switch Box CONNECTION and/or
DISCONNECTION PROCEDURE as explained on the section 3.3.2 of this
manual disconnect the Switch Box from the D.C power cable as described in
the “Switch Box connecting and/or Disconnecting procedure” prior to work
on those cables.
POS Details
A Terminal Block A.C OUT
B DIN bars for accessories
C GRID STANDARD TABLE
D MAIN GROUND - MAX WIRE SIZE = AWG# 4 (Refer to local code
for minimum wire size)
E Ground
F D.C. IN TERMINAL BL0OCK
G Cables Knockouts
WARNING: prior to perform any operation on the Swtch Box power input
ALWAYS PERFORM THE “ Switch Box CONNECTION and/or
DISCONNECTION PROCEDURE as explained on section 3.3.1 of this
manual.
WARNING: THE INPUT CURRENT shall not exceed 18A D.C for each
input channel:
All the screw on the electrical terminal block shall be tightenn using a 20
in/lbs troque
Step 1: Disconnect from the AC Grid by turning off the"AC Bipolar Switch" – Part
"D" in fig. 9 "Electrical connecxtion diagram"
Step 2: Remove the Switch Box cover and connect the DC cable to the terminal block
in pos"F" in. "Fig.11 SB-02 –Switch Box"; carefully check the correct polarity of the
DC cable.
Step 3: Connect the A.C cable following the instruction explained in chapter
“Electrical connection to the A.C Grid”, section 3.3.6. Refer to the table"CN01 A.C.
Grid connection"
Step 4: Open the inverter cover(4 screw in pos "b" in fig. 10 and connect the signals
cable (optional).Pass the cable inside the Switch Box trough the input knock outs pos
"D" fig.11 "SB 01 – D.C. Switch Box Layout")and then inside the inverter trough the
cable gland placed in the upper side of the switch Box; finally screw the cable in the
appropriate terminal block inside the inverter.
Step 5: Remove the cover from the photovoltaic panel or wait for the sun to irradiate
the panel
Installation and Operator’s Manual Page 31 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
VERIFY: that the D.C voltage in the Switch Box input (terminal block pos.
"F" Fg.11 "SB-02) has the right polarity and is within the operational range.
If the parameter are within the operating range defined in the specification close the
Inverter and the Switch Box cover and follow the instruction “START UP” on chapter
4.
3.3.5 Possible AURORA D.C input configuration
WARNING: prior to perform any operation on the Swtch Box power input
ALWAYS PERFORM THE “ Switch Box CONNECTION and/or
DISCONNECTION PROCEDURE as explained on section of this manual.
The AURORA inverter can be configured with an independent MPPT for each D.C
input channel or with the 2 input D.C channel connected in parallel with one MPPT. If
the inverter is configured with 2 independents MPPT the max current for each channel
shall not exceed 18 AMP.
Once the D.C connection is completed follow the instruction in the chapter
“ELECTRICAL CONNECTION TO THE A.C GRID”, section 3.3.6
Installation and Operator’s Manual Page 32 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
If the system has one single photovoltaic array and the current from it is less than 18 A
then the array can be connected to one single input channel (IN1).
The cover of the AURORA inverter need to be removed (Rif. Fig. 14 / screws pos.
"a”) in order to access to the board with the terminal block
Once the cover is removed short the pin marked as "- IN2" e "+ IN2"in the terminal
block "D.C. INPUTS". To connect the 2 pin use the cable provided with the unit as
shown in Fig. 12
Once the above operations are completed install the cover and tighten the screw with
a1.5Nm (13.2 in-lbs) torque and follow the procedure START UP (Chapter 4).
Installation and Operator’s Manual Page 33 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
WARNING: When the current from the photovoltaic array exceed 18 Amp
D.C, when the array power exceed 4KW or when there is a consistent
unbalance between the power from the 2 array is necessaries to parallel the 2
input
Installation and Operator’s Manual Page 34 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
To parallel the 2 input 2 AWG10 cable shall be used to connect the terminal block–
IN1 e –IN2 and +IN1 e +IN2 as shown in fig 13 (Black and red cable)
The switch “S1” shall be placed on position “PAR” as shown on Fig 14 in order to
configure the inverter in parallel mode.
Installation and Operator’s Manual Page 35 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Once this procedure is completed the front panel can be reinstalled in the unit (apply
13.2 in-lbs torque to the 4 screw) and is possible to start the “START UP “procedure.
(Chapter4)
Installation and Operator’s Manual Page 36 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Step 1: Remove the Switch Box front panel (remove the 4 screw in pos “b” in fig. 10)
Step 2: Lay down the cable between AURORA and the A.C. disconnect switch
Step 3: Pass the A.C cable inside AURORA through one of the cable gland present in
the lower side of the Switch Box (see Fig.11 "SB 01 – D.C. Switch Box Layout" –
pos. "A")
Steps 4: connect the 3 A.C wire to the relative terminal block present inside the
inverter. the connection shall be done based on the type of A.C Grid following the
table" Tab CN01 –A.C. Grid connection ". The ground cable shall be connected to the
terminal block pointed in pos. "D" on “Fig.11 SB-02 –Switch Box "
Installation and Operator’s Manual Page 37 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Based on the local GRID standard is possible to select different connection type. The
available configurations are shown in the table below (Tab CN01 –A.C Grid
connections)
Installation and Operator’s Manual Page 38 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Refer to the following in case become necessary to separate the Inverter Aurora form
the DC switch
STEP 1: Disconnect the High Voltage D.C power line coming from the photovoltaic
arrays using the appropriate switch in the Switch Box (pos. "C" – fig.11 "SB01"). Turn
the switch in the off position as indicated in the silk print (pos B in Fig.11 "SB01") and
LOCK as shown in Fig.11"SB 02 – D.C. Switch Box / Safety lock"
STEP 2: Disconnect the inverter from the A.C Grid using the A.C disconnect switch
shown as” Part "D" in Fig. 9 – " Connection diagram "
STEP 3: Wait about one minute to allow the internal capacitors to discharge (verify
that the LED in the front panel are off)
END PROC
.Disconnect the D.C cable from the inverter Board (remove the 4 screw from the
terminal block + and – IN1 and + and – IN2) (fig. 13/A "parallel connection")
Disconnect the 3 A.C cable (“1", "2" e "3") from the inverter pos "A", "B" e C in Fig.
13/A
Place the D.C cable inside the Switch Box; close the hole in the upper side of Switch
Box using the following water-tight cap
Inside AURARE there is a lithium battery type CR2032. When this battery is end of
life a message will be shown in the display informing that the battery need to be
replaced.
Installation and Operator’s Manual Page 41 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
To insert the new battery in the battery holder the component need to be slide in with a
30° angle as shown on fig 16. once pushed this way it will automatically found the
correct position inside the holder.
Once the battery is replaced put back the front panel in the inverter and perform the
START UP procedure.
Installation and Operator’s Manual Page 42 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
4 START-UP
WARNING: Do not touch the heat sink when the inverter is operating, as
some parts may be hot and cause burns.
3) Once both disconnects are closed, the inverter starts the grid connection
sequence, unless the grid voltage and frequency parameters are found to be
outside the operating range as per UL 1741 standard. The check routine is
indicated by the green LED labelled POWER over the display flashing.
The check routine may take 30 seconds up to several minutes, depending on grid
condition. Three screens are shown on the display during the check routing:
• “Measuring Riso…”, connection in progress with progress indication.
• Grid voltage value and status compared to specified values
(within/outside range).
• Grid frequency value and status compared to specified values
(within/outside range).
4) When the connection sequence is completed, AURORA starts operating; proper
operation is indicated by a warning sound and the green LED staying on. This
means that sun radiation is sufficient to feed the grid.
5) If the grid check routine gave a negative result, the unit will repeat the procedure
until all grid voltage and frequency parameters and grid configuration are found to
be in the specified range. During this process, the green LED will keep flashing.
Installation and Operator’s Manual Page 43 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
¾ Grid voltage
¾ Grid current
¾ Grid frequency
¾ Power transferred to the grid
¾ Voltage of photovoltaic array 1
¾ Current of photovoltaic array 1
¾ Voltage of photovoltaic array 2
¾ Current of photovoltaic array 2
¾ Heat sink temperature)
¾ Serial Number Part Number
¾ Manufacturing week
¾ Firmware revision code
¾ Daily energy
¾ Leakage current of the system
¾ Total energy
¾ Partial energy
¾ Mean grid voltage
¾ Insulation resistance
¾ Leakage current to ground
¾ Date, time
Installation and Operator’s Manual Page 46 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
1 2 3 ESC DOWN
UP ENTER
Possible LED combinations and their meanings are listed in the following table.
Installation and Operator’s Manual Page 48 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
KEY:
LED on
LED blinking
LED off
G 1) Nighttime mode
Y AURORA disconnected during night time; this occurs when input power
R is too low to feed the inverter.
G 5) Malfunction/Fault indication
Y Every time Aurora check system detects an operative malfunction or
R fault of the monitored system, the yellow LED comes on and a message
showing the type of problem found appears on the LCD.
G 6) RS-485 address setup indication
Y During installation, the yellow LED will keep flashing until the address
R is acknowledged. For further information about address entering, refer to
section 6.3.
G 7) Grid disconnection
Y If a grid failure event occurs while the system is regularly operating, the
R yellow LED turns on steady.
MESSAGES identify current AURORA status; so they do not relate to faults and
nothing has to be done; messages disappears as soon as the system is back to normal
operating conditions. See W strings in the table below.
ALARMS identify a possible fault of the equipment or of the connected parts. Alarm
signals will disappear as soon as the causes are removed, except for ground insulation
faults in the photovoltaic panels, which have to be corrected by qualified personnel.
Usually, when an error signal appears, an action is needed. This action will be
managed as much as possible by Aurora or, in case this is not possible, Aurora will
supply all the necessary helping information to the person who will have to carry out
the maintenance operations to fix the fault on the equipment or system. See E strings
in the table below.
Installation and Operator’s Manual Page 51 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Initialing…
Please waiting
2) The following screens may appear while waiting for the connection to be
established:
Missing Grid Waiting Sun
- While the system checks for grid connection to be established (“Missing Grid”), the
yellow LED next to the display turns on steady, while the green LED is flashing.
- When waiting for sun radiation (“Waiting Sun”), the green LED turns on steady.
- When the “Missing Grid” and “Waiting Sun” conditions are verified, the inverter is
connected.
Next connections:
2 secs
Vgrid 197.8 V
In range
Installation and Operator’s Manual Page 54 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Fgrid 50.17 Hz
In range
6) If measured instant values of voltage (step 4) and frequency (step 5) are outside the
allowed range, the following screens are shown alternately
- Next connections (screen 3)
- Vgrid (screen 4)
- Fgrid (screen 5)
Meas. Riso
………………………
ERROR
Code ……..
Type OUTD
Part No………
S/N ………..……..
Firmware…………
Once the error has been removed, the inverter resets all functions in progress and re-
starts the connection (Sect.5.5.2 Connection of system to the grid, item 2)
- Missing Grid
- Waiting Sun
Installation and Operator’s Manual Page 55 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Fig.20 Fig.21
Auto-scroll is indicated by 2 arrows in the top left corner of the display (Fig.20).
To stop auto-scroll, press the ENTER key (4th key from display). A padlock will
appear (Fig.21).
1A) If the measurements taken previously (see sect. 5.5.1) are found to be correct, the
system will proceed to the next checks. The 12 screens outlined below are shown
alternately as mentioned in section “A FEW POINTERS ON DISPLAY KEY
OPERATION”.
Type OUTD
PN------------
2A) shows inverter serial number and firmware revision level.
S/N--------- xxxxxx
FW rel. C.0.1.1
3A)
E-tod 0 Wh
$-tod 0.0 EUR
E-tod: Daily energy output.
$-tod: Daily energy savings. Value is expressed in the set currency.
Installation and Operator’s Manual Page 56 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
4A)
E-tot -------------
E-par 0 KWh
E-tot: Lifetime energy output (since first installation)
E-par: Partial energy output (during selected period)
5A)
P-out 0 W
T-inv - °C
P-out: Measured instant output power
The second line of the display shows the higher of two temperatures:
T-inv: inverter heat sink temperature
T-boost: Heat sink temperature
6A)
Ppk W
Ppk Day ………...W
Ppk: Maximum peak power achieved since partial counter was activated
Ppk Day: Maximum peak power achieved during the day. Counter will reset when unit
is powered off.
7A)
Vgrid 197 V
Vgrid Avg 0 V
Vgrid: Measured instant grid voltage
Vgrid Avg: Average grid voltage during the last 10 minutes of operation
8A)
Igrid 0.8 A
Fgrid 50.18 Hz
Igrid: Measured instant grid current
Fgrid: Measured instant grid frequency
9A)
Vin1 0V
I in1 0.0 A
Vin1: Instant input voltage measured at channel 1 input
Iin1: Instant input current measured at channel 1 input
Installation and Operator’s Manual Page 57 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
10A)
Vin2 0V
I in2 0.0 A
Vin2: Instant input voltage measured at channel 2 input
Iin2: Instant input current measured at channel 2 input
Or:
Vin 0V
I in 0.0 A
In a configuration with one input connected and a second input connected in parallel,
the following screen is shown instead of the 2 screens described above.
11A)
Pin 1 0W
Pin 2 0W
Pin1: Measured instant input power of channel 1
Pin2: Measured instant input power of channel 2
Pin 0W
In a configuration with one input connected and a second input connected in parallel,
the following screen is shown instead of the screen described above.
12A)
Riso 0.0 Mohm
Ileak 73 mA
Riso: Measured insulation resistance. Unlike the parameters discussed above, this is
not an instant value but a one-off measurement taken upon inverter start-up.
Installation and Operator’s Manual Page 58 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
13A)
Inverter OK
Wed 17 May 11 23
If all items described above tested are OK, the inverter shows a corresponding
message in the display top line along with date and time. Clock malfunctioning or
other non function-related faults (meaning such faults that do not affect the inverter's
ability to generate energy) are shown in the bottom line of the display in place of date
and time.
The following error messages are provided:
- CLOCK FAIL indicates clock malfunction, contact service
- BATTERY LOW
- SET TIME, appears the first time the unit is powered up or after the battery has been
replaced.
- FAN FAIL: contact service
- MEMORY FAIL: Data logging malfunction. Contact service.
5.5.5 Statistics
Select the STATISTICS menu to display the following submenu:
Lifetime
Partial
Today
Last 7 days
Last Month
Last 30 Days
Last 365 Days
User period
The display has 2 lines; use the keys at the side of the display to scroll through items
or open the corresponding submenus as described in section 5.5.3 A FEW POINTERS
ON DISPLAY KEY OPERATION.
An arrow on the left side of the display highlights your current selection as shown in
the following figure:
5.5.5.1 Lifetime
Select Lifetime to view the following information:
Time h
E-tot KWh
Val. EUR
CO2 Kg
5.5.5.2 Partial
Select Partial to view the following information:
Time h
E-par KWh
Ppeak W
Val. EUR
CO2 Kg
* Hold the ENTER key (4th key from display) depressed for over 3 seconds to reset all
counters in this submenu. After 3 seconds, a warning sound is repeated 3 times.
5.5.5.3 Today
Select Today to view the following information:
E-tod KWh
Ppeak W
Val. EUR
CO2 Kg
E-7d KWh
Val. EUR
CO2 Kg
E-mon KWh
Val. EUR
CO2 Kg
E-30d KWh
Val. EUR
CO2 Kg
E-365d KWh
Val. EUR
CO2 Kg
Installation and Operator’s Manual Page 62 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
This feature measures energy saving during a period selected by the user.
Press ENTER from the “User period” screen to access the following submenu:
Start 23 June
End 28 August
Use the display keys to set the start and end date of the period as follows:
¾ Use ENTER to move from one field to the next (from left to right)
¾ Use ESC to go back to the previous field (from right to left)
¾ Press ESC repeatedly to go back to the previous menus as described in sect.
5.5.3
To set days:
¾ Press DOWN to scroll numbers backwards (from 31 to 1)
¾ Press UP to scroll numbers from 1 to 31
If set dates are inconsistent, the display alerts the user to the problem:
Data err
Installation and Operator’s Manual Page 63 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
5.5.6 Setting
Select SETTING from the Main menu (sect. 5.5.4) to display the first screen, that
refers to the password:
Password
****
Default password is 0000. It can changed using the keys on display as usual:
¾ Use ENTER to move from one figure to the next (from left to right)
¾ Use ESC to go back to the previous figure (from right to left)
¾ Press ESC repeatedly to go back to the previous menus as described in sect.
5.5.3
¾ Press DOWN to scroll numbers backwards (from 9 to 0)
¾ Press UP to scroll numbers from 0 to 9
Type in the correct password and press ENTER to access all information of this
section:
Address
Display Set
Service
New Password
Cash
Time
Language
Vstart
Autotest
Alarm
Remote Control
UV Prot.time
MPPT scan EN/DIS
Scan Period
The display has 2 lines; use the keys at the side of the display to scroll through items
or open the corresponding submenus as described in section 5.5.4 A FEW
POINTERS ON DISPLAY DATA READING.
An arrow on left side of the display highlihghts your current selection. When chosen
item is selected, press ENTER to open the submenu.
Installation and Operator’s Manual Page 64 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
5.5.6.1 Address
This function is used to set addresses for communication of the single inverters
connected in the system on RS485 line. You can assign numbers from 2 to 250. Press
UP and DOWN to scroll numbers.
If you do not want to manually set the address of each inverter, select the AUTO
function and they will be distributed automatically.
AUTO
2
NEW ADDRESS NEW ADDRESS 3
248 Auto …..
…..
249
250
AUTO
Light
Contrast
Buzzer
5.5.6.3 Service
Only installing staff can gain access to this function, which is password-protected and
dedicated code is supplied by Power-One.
5.5.6.5 Cash
This function is about energy output savings.
Name EUR
Val/KWh 00.50
Name: set desired currency, using keys as usual. Default currency is Euro.
Val/KWh: it indicates the cost of 1 KWh expressed in set currency. Default setting is
0.50 Euro.
5.5.6.6 Time
This function allows time and date setting.
Time 14:21
Date 17 May 2006
Installation and Operator’s Manual Page 66 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
5.5.6.7 Language
It is possible to set the national language or English.
English
Italiano
VStart
200V
5.5.6.9 Autotest
Aurora internal test checking correct operation of the protection and the grid interface
device, as provided for by UL 1741 regulation.
Autotest
OV test
UV test
OF test
UF test
DC injection
OV = Max. voltage
UV = Min. voltage
OF = Max. Frequency
UF = Min. Frequency
DC injection = Output current direct component. This component shall not be >0.5%
with respect to inverter maximum rated current, or unit will switch off.
Installation and Operator’s Manual Page 67 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
The display has 2 lines; use the keys at the side of the display to scroll through items
or open the corresponding submenus.
An arrow on left side of the display highlihghts your current selection. When chosen
item is selected, press ENTER to open the submenu.
As soon as test is selected, the display shows
Test in progress
………………..
5.5.6.10 Alarm
The inverter features an alarm function that opens or closes a relay contact, access can
be gained through front door as indicated in Fig. 22. This contact can be used for
instance to activate a siren or a visual alarm in case inverter is disconnected from the
grid (no energy output) or for any alarm event generated by the system.
This function can activate two alarm modes. Press ENTER to open the relevant
submenu:
Production
Fault
An arrow on left side of the display highlihghts your current selection. When chosen
item is selected, press ENTER to confirm activation of chosen mode.
Installation and Operator’s Manual Page 68 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Manual ON and OFF input is read on inverter digital input. When set to OFF, the
display will cycle through the following screens:
5.5.6.12 UV Prot.time
This function is used to set inverter connection time after input voltage drops below
Under Voltage limit, set at 90V.
For example: if UV Prot.time is set at 60 seconds, and Vin voltage drops below 90V at
9.00, the inverter stays connected to the grid (at 0 power) up to 9.01.
Power-One sets this time at 60 seconds. The user can change this setting and set it
from 1 second to 3600 seconds.
MPPTscan En7Dis
Enable
5.5.6.14 Scan Interval
This function is used to set time interval for system max.multiple scan. Default setting
is 15 minutes.
Scan Interval
15 min
Installation and Operator’s Manual Page 70 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
5.5.7 Info
This menu is used to display all Aurora data:
¾ Part No. (part number)
¾ Serial No. – Wk – Yr (serial number, week, year)
¾ Fw rel (firmware release level)
Installation and Operator’s Manual Page 71 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Installation and Operator’s Manual Page 72 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
1st PLUG
2nd PLUG
Fig.23 - Holes for cables necessary for RS-485 port connection or wiring for RJ12
connectors connection.
For easier installation, the inverter features two holes so that input and output cables
can be separated in case more units are connected in a daisy chain as described below.
After passing through cable gland, cables are connected inside of the unit to RS-485
terminal blocks that can be reached by removing the front door. Refer to par. 3.7 for
details on front cover correct removal and reassembly procedure.
Wiring is again routed through the holes located at Inverter bottom which are blanked
with waterproof plugs (see Fig.23). Input wiring passes through one hole and is to be
assembled to one of the RJ12 connectors; ti does not matter whether it is no. 1 or no. 2
since signals are the same considering that they are connected in parallel.
Output wiring goes out from the other RJ12 connector through the other hole and
reaches the next unit.
RJ12 connectors
Signal
Pin # Description
Name
1 Not Used
+ Data Line
2 +TR
Required for RS485 communication.
Remote OFF
3 +R Required or Remote OFF control (see chapter
5.5.6.11 for details).
- Data Line
4 -TR
Required for RS485 communication.
5 Not Used
Signal Return
6 RTN
Common reference for logical signals.
Installation and Operator’s Manual Page 75 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
RS-485 terminal block or RJ12 connectors can be used to connect a single AURORA
inverter or many AURORA inverters connected in a daisy chain. Maximum number of
inverters that can be connected in daisy chain is 248. Recommended maximum length of this
chain is 1200 metres.
In case many inverters are connected in a daisy chain, it is necessary to assign an address to
each unit. Refer to paragraph 5.5.6.1 for instructions on how to set addresses.
Moreover, the last inverter of the chain must have line termination contact active (S2 switch -
120Ω TERM set to ON). See fig. 24.
Any AURORA device is supplied with default address two (2) and with the S1 dip switch in
the OFF position.
In order to ensure optimum communication on RS485 line, Power-One recommends to
connect PVI-RS232485 adapter in-between the first unit of the daisy chain and the computer.
See fig. 25 for further details.
To this purpose other equivalent devices available on the market can also be used but Power-
One does not assure correct connection operation since equipment has never been tested with
these equivalent devices.
Please note that these commercial devices could require an external termination impedance,
which is not necessary for Aurora PVI-232485.
The following diagram shows you how to connect many multiple units in daisy chain
configuration.
Installation and Operator’s Manual Page 76 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
NOTE: When using RS-485 link there can be up to 248 inverters connected on
the same link. Choose any address between 2 and 248
NOTE: When using RS-485 link, in case one or more inverters are added
later to the system, please remember to switch back to the OFF position the
dip-switch of the former last inverter of the system.
Installation and Operator’s Manual Page 77 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Output power PV
Pin1 W 1W 10 W 2%
N°1
Output power PV
Pin2 W 1W 10 W 2%
N°2
Partial
Partial time counter hh:mm:ss 1s 0.2
Time
Installation and Operator’s Manual Page 79 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
7 TROUBLESHOOTING
Aurora inverters comply with standards set for grid-tied operation, safety and
electromagnetic compatibility.
Before being delivered, the product has been successfully subjected to several tests to
check: operation, protective devices, performance and durability.
All these tests, together with the system ensuring Power-One quality, guarantee
Aurora optimal operation.
9 Work under safe conditions, as stated in chapter 3.5 and following, check that
connections between Aurora, photovoltaic field and power distribution grid have
been made correctly.
9 Carefully observe which LED is blinking and read the signal appearing on the
display; then, following the instructions given in chapters 5.3, 5.4 and 5.5, try to
identify the type of fault found.
Before contacting the service center, keep the following information handy:
INFO Aurora
9 Aurora model?
9 Serial number?
9 Week of production?
9 LED flashing?
9 Light blinking or steady?
9 Signal displayed?
8 TECHNICAL FEATURES
Max number of
Max number of
Panel voltage
Panel voltage
Panel voltage
Panel voltage
panels
panels
25 21.6 27 28.8 20 43.2 13
Table A
Installation and Operator’s Manual Page 83 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Value Value
Description
PVI – 5000-OUTD PVI – 6000-OUTD
Nominal input
360Vdc 360Vdc
voltage
Max. absolute
600Vdc 600Vdc
input voltage
Input voltage,
MPPT
90 Vdc to 580 Vdc 90 Vdc to 580 Vdc
operating
range
Input voltage,
MPPT
operating 150 Vdc to 530 Vdc 180 Vdc to 530 Vdc
range at full
power
Max. short
circuit current 22 Adc 22 Adc
(of each array)
Max. operating
input current 18 Adc 18 Adc
(of each array)
Max. input
power (of each 4000 W 4000 W
array)
PV Ground Ground fault detector and Ground fault detector and
fault protection interruption provided interruption provided
Two independent MPPT channel with shared negative poles
Input channels
or
configuration
Two channels in parallel
(array)
Value Value
Description
PVI – 5000-OUTD PVI – 6000-OUTD
Nominal 5000W
6000 W
output power
Grid voltage,
maximum 180 to 264 Vac 180 to 264 Vac
range
Default : 240V split phase Default : 240V split phase
Grid voltage,
Optional : 208 or 277 single Optional : 208 or 277 single
nominal
phase (setting required) phase (setting required)
Grid voltage,
82% to 115% of nominal 82% to 115% of nominal
operating
voltage voltage
range as per
(188.6 to 264Vac for (188.6 to 264Vac for
UL 1741
V=230Vac) V=230Vac)
regulation
Grid
frequency,
47 Hz to 63 Hz 47 Hz to 63 Hz
maximum
range
Grid
frequency, 60 Hz 60 Hz
nominal
Grid
frequency,
operating
59.72 Hz to 60.28 Hz 59.72 Hz to 60.28 Hz
range as per
UL 1741
regulation
Nominal
output 24 Arms; 20 Arms; 18 Arms 29 Arms; 25 Arms; 21.6 Arms
current
Max. output
30 Arms 30 Arms
current
Installation and Operator’s Manual Page 85 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Output over
current 40 Arms 40 Arms
protection
Complies with:
Anti islanding protection
- UL 1741 standard.
Installation and Operator’s Manual Page 86 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Value
Description
PVI – 5000-6000-OUTD
(*) Full power guaranteed up to T.amb = 40°C (as far as unit is not exposed to direct
sun radiation)
Installation and Operator’s Manual Page 87 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)
Power Derating
(max input current)
180
Installation and Operator’s Manual
(PVI-5000/6000-OUTD-US Rev: 1.1)
Fig. 27
Voltage Derating Range
180
Fig. 28
Necessary conditions for power derating due to environmental conditions and to input
voltage can occur at the same time, but in this instance power derating will always
consider the lowest value detected.
Installation and Operator’s Manual Page 90 of 94
(PVI-5000/6000-OUTD-US Rev: 1.1)