Service Manual: Warning
Service Manual: Warning
Service Manual: Warning
Service Manual
TABLE of CONTENTS These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
PAGE injury or death. WARNING signifies hazards which could result in
SAFETY CONSIDERATIONS ....................................................... 1 personal injury or death. CAUTION is used to identify unsafe
INTRODUCTION............................................................................ 1 practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which will
MODEL / SERIAL NUMBER NOMENCLATURES .................... 2 result in enhanced installation, reliability, or operation.
SPECIFICATIONS .......................................................................... 3
DIMENSIONS ................................................................................. 4
CLEARANCES................................................................................ 6
ELECTRICAL DATA ..................................................................... 7
WARNING
WIRING ........................................................................................... 7
ELECTRICAL SHOCK HAZARD
CONNECTION DIAGRAM............................................................ 7
Failure to follow this warning could result in personal injury or death.
WIRING DIAGRAMS..................................................................... 8 Before installing, modifying, or servicing system, main electrical
FAN AND MOTOR SPECIFICATIONS ........................................ 12 disconnect switch must be in the OFF position. There may be more than 1
disconnect switch.
REFRIGERATION CYCLE DIAGRAM........................................ 12
Lock out and tag switch with a suitable warning label.
REFRIGERANT LINES .................................................................. 13
SYSTEM EVACUATION AND CHARGING ............................... 14
SYSTEM VACUUM AND CHARGE ............................................ 14
ELECTRONIC FUNCTIONS ......................................................... 15
POINT CHECK FUNCTION .......................................................... 18
WARNING
TROUBLESHOOTING ................................................................... 20
DIAGNOSTIC GUIDES.................................................................. 21 EXPLOSION HAZARD
Failure to follow this warning could result in
DIAGNOSIS AND SOLUTION...................................................... 22 death, serious personal injury, and/or property
DISASSEMBLY INSTRUCTIONS SIZE 36.................................. 51 damage. Never use air or gases containing oxygen
DISASSEMBLY INSTRUCTIONS SIZE 48-58 ............................ 57 for leak testing or operating refrigerant
compressors. Pressurized mixtures of air or gases
containing oxygen can lead to an explosion.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can
be hazardous due to system pressures, electrical components, and
CAUTION
equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
start-up, and service this equipment.
operation.
Untrained personnel can perform basic maintenance functions such as Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground.
coil cleaning. All other operations should be performed by trained If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise
service personnel. to the valve connections on the outdoor units. If more than the
When working on the equipment, observe precautions in the literature recommended length is buried, refrigerant may migrate to the cooler
and on tags, stickers, and labels attached to the equipment. buried section during extended periods of system shutdown. This causes
Follow all safety codes. Wear safety glasses and work gloves. Keep a refrigerant slugging and could possibly damage the compressor at start-up.
quenching cloth and fire extinguisher nearby when brazing. Use care
in handling, rigging, and setting bulky equipment. INTRODUCTION
Read this manual thoroughly and follow all warnings or cautions
This service manual provides the necessary information to service,
included in the literature and attached to the unit. Consult local repair, and maintain the 38MBR family of heat pumps. Section 2 of
building codes and National Electrical Code (NEC) for special this manual has an appendix with data required to perform
requirements. Recognize safety information. This is the safety-alert troubleshooting. Use the “TABLE of CONTENTS” on page 1 to
symbol . When you see this symbol on the unit and in instructions locate a desired topic.
or manuals, be alert to the potential for personal injury. Understand
these signal words: DANGER, WARNING, and CAUTION.
MODEL / SERIAL NUMBER NOMENCLATURES
Table 1 —Unit Sizes
SYSTEM TONS kBTUh VOLTAGE-PHASE OUTDOOR MODEL
3.00 36,000 208/230-1 38MBRQ36A--3
4.00 48,000 208/230-1 38MBRQ48A--3
5.00 58,000 208/230-1 38MBRQ58A--3
OUTDOOR UNIT
38 MB R Q 36 A -- 3
38 = OUTDOOR UNIT
VOLTAGE
MB = MODEL 3 = 208/230-1-60
SYSTEM TYPE
Q = HEAT PUMP
NOMINAL CAPACITY
MAXIMUM NUMBER OF FAN COIL UNITS THAT
36 - 3 TONS
CAN BE CONNECTED TO THE OUTDOOR UNIT
48 - 4 TONS
A = 1:1
58 - 5 TONS
01 19 V 10001
L1
L2
Fig. 1 — Size 36K
Table 3 — Dimensions
OPERATING
UNIT SIZE WIDTH in (mm) DEPTH in (mm) HEIGHT in (mm) L1 in (mm) L2 in (mm) WEIGHT
36K 37.24 (946) 16.14 (410) 31.89 (810) 26.50 (673) 15.87 (403) 136.47 (61.9)
Table 4 — Dimensions
OPERATING
UNIT SIZE WIDTH in (mm) DEPTH in (mm) HEIGHT in (mm) L1 in (mm) L2 in (mm) WEIGHT
48K 37.22 (945) 15.58 (396) 52.48 (1333) 24.96 (634) 15.90 (404) 217.4 (98.6)
58K 37.22 (945) 15.58 (396) 52.48 (1333) 24.96 (634) 15.90 (404) 225.09 (102.1)
A
Air-inlet
D B C
Air-outlet
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. Use Electrical Data table
CAUTION
MCA (minimum circuit amps) and MOCP (maximum over current
protection) to correctly size the wires and the disconnect fuse or
breakers respectively. EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
Sizes 36-58 Recommended Connection Method for Power
and Communication Wiring or improper operation.
Wires should be sized based on NEC and local codes.
Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied
power wiring from the outdoor unit to the indoor unit consists of three
(3) wires and provides the power for the indoor unit. Two wires are
CAUTION
high voltage AC power and one is a ground wire. To minimize voltage
drop, the factory recommended wire size is 14/2 stranded with a
ground. EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
Communication Wiring: or improper operation.
Be sure to comply with local codes while running wire from
A separate shielded stranded copper conductor only, with a 600 volt
rating and double insulated copper wire, must be used as the the indoor unit to the outdoor unit.
communication wire from the outdoor unit to the indoor unit. Please Every wire must be connected firmly. Loose wiring may
use a separate shielded 16GA stranded control wire. cause the terminal to overheat or result in unit malfunction. A
fire hazard may also exist. Ensure all wiring is tightly
connected.
No wire should touch the refrigerant tubing, compressor or
any moving parts.
Disconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the
hole in the conduit panel.
CONNECTION DIAGRAM
L-PRO
H-PRO
Applicable to the units
W BLACK
T4
T3
TP
COMP V RED adopting DC motor only
U
BLUE 3
FM1
Y/G
Y/G
5
U
4-WAY1 SV CN20 M
BLUE CN3 CN42
BLUE
P-1
CN55
7 CN22
BLUE BLUE
V
BLACK CN40
MAIN BOARD
CN53
CN44 CN2
BLACK
HEAT_D
CN51
CN52
CN54
7 CN7
CN5 CN1
BLACK
CN6 CN34
RED
BLUE
BLUE
RED
BLACK
BLACK
OPTIONAL
RED
YELLOW
YELLOW
YELLOW
GRAY
L
XT2 S1 S2 (1)L1 (2)L2 L1 L2 XT1
OPTIONAL
POWER SUPPLY
Ferrite bead D
XT1
RED BLACK
~
1
Ferrite bead
L P6 P5 Y/G
3 2
~ ~
CH2
YELLOW
CN4 BLACK
L1 L2
RED
L N
CN3
MAIN
BLACK
5
YELLOW
TO INDOOR UNIT
CN2 CN1 BLUE
MAIN BOARD /BLACK
(1)L1 (2)L2
(1)N (2)N
CN3 P7
CH1 CN6 U W P8 RED
BLUE V P9
RED OPTIONAL
BLACK CN22
Ferrite bead
V
U W CN20 OPTIONAL
COMP IPM & PFC BOARD BLACK HEAT_D
CN19 RED
FAN1 10 ORANGE
Y/G CN9 CN6 CN25
HEAT_Y
Ferrite bead
CH2 CN24
2 ORANGE OPTIONAL
Ferrite bead BLUE
CH2 3 CN18
4-WAY
CN17
CN1 CON1 BLUE SV
T3 T4
CN12 CN8 CN9
DC MOTOR
CN28
AMBIENT SENSOR
DRIVER BOARD 2
YELLOW
PIPE TEMP.SENSOR
TH PAIQI
GRAY
3 CN31
CN36
Y/G DCFAN2 3
DCFAN1 FAN1 FAN2
CN32 XT2 S1 S2
Y/G
CN27
A
CN15 CN10 CN34
Ferrite
bead
ELECTRONIC RED YELLOW
EXPANSIVE
VALVE A
H-PRO
L-PRO
INDOOR OUTDOOR
Electronic
LIQUID SIDE CAPILIARY TUBE expansion valve
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
T2 Evaporator T1 Room temp. T4 Ambient EXCHANGE
temp. sensor sensor temp. sensor (CONDENSER)
middle
T2B Evaporator
temp. sensor
outlet
GAS SIDE
4-WAY VALVE
3-WAY VALVE
T5 Discharge
temp. sensor
COOLING
Compressor
HEATING
• The charge amount listed in Table 15 is for piping runs up to 25 ft. (7.6 m).
• For piping runs greater than 25 ft. (7.6 m), add refrigerant up to the allowable length as specified in Table 16.
CAUTION The deep vacuum method requires a vacuum pump capable of pulling a
vacuum of 500 microns and a vacuum gage capable of accurately mea-
suring this vacuum depth. The deep vacuum method is the most positive
UNIT DAMAGE HAZARD way of assuring a system is free of air and liquid water (see Fig. 11).
Failure to follow this caution may result in equipment damage
or improper operation.
5000
Never use the system compressor as a vacuum pump. 4500
4000
Refrigerant tubes and indoor coil should be evacuated using the 3500 LEAK IN
MICRONS
SYSTEM
recommended deep vacuum method of 500 microns. The alternate 3000
triple evacuation method may be used if the following procedure is
followed. Always break a vacuum with dry nitrogen. 2500
2000
VACUUM TIGHT
SYSTEM VACUUM AND CHARGE 1500
1000
TOO WET
TIGHT
Using Vacuum Pump 500 DRY SYSTEM
1. Completely tighten the flare nuts (A, B, C, D, E). Fully open all 0 1 2 3 4 5 6 7
circuits service valves. Connect the manifold gage charge hose to MINUTES
the charge port of the low side Master service valve to evacuate all
circuits at the same time (see Fig. 9). Fig. 11 — Deep Vacuum Graph
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage (see Fig. 10). Triple Evacuation Method
4. Start vacuum pump
5. Evacuate using the triple evacuation method. The triple evacuation method should be used. Refer to Fig. 12 and
proceed as follows:
6. After evacuation is complete, fully close the low side of manifold
gage and stop operation of vacuum pump. 1. Pump system down to 500 MICRONS of mercury and allow pump to
7. The factory charge contained in the outdoor unit is good for up continue operating for an additional 15 minutes. Unit must maintain
to 25ft. (8 m) of line length. For refrigerant lines longer than 500 microns or less for 30 minutes or more to ensure a dry system.
25ft. (8 m), add refrigerant as specified in “Additional Charge 2. Close service valves and shut off vacuum pump.
Table Per Zone” on page 13.
3. Connect a nitrogen cylinder and regulator to system and open until
8. Disconnect charge hose from charge connection of the low side system pressure is 2 psig.
service valve.
4. Close service valve and allow system to stand for 10 minutes.
9. Securely tighten caps of service valves. During this time, dry nitrogen will be able to diffuse throughout the
system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 12. System will then be
Outdoor Unit Refrigerant Indoor Unit free of any contaminants and water vapor.
A Low Side C
D EVACUATE
B High Side
BREAK VACUUM WITH DRY NITROGEN
Service Valve
WAIT
Fig. 9 — Service Valve EVACUATE
Low side valve High side valve CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
Charge hose Charge hose
RELEASE CHARGE INTO SYSTEM
Vacuum pump
Fig. 12 — Triple Evacuation Method
T4
A DC_FAN_HI_SPD_ADD
ADD
D
DD
28 (82.4°F) E DC_FAN_SSLOW_SPD_ADD
69.8°F(21°C)
26 (78.8°F)
66.2°F(19°C)
B DC_FAN_MID_SPD_ADD
_A
ADD
25 (77°F) D DC_FAN_SLOW_SPD_ADD
64.4°F(18°C)
23 (73.4°F) 60.8°F(16°C)
C DC_FAN_MIN_SPD_ADD
_ADD
DD
D C DC_FAN_MIN_SPD_ADD
22 (71.6°F) 59°F(15°C)
20 (69°F) 55.4°F(13°C)
D DC_FAN_SLOW_SPD_ADD
PD_A
ADD B DC_FAN_MID_SPD_ADD
19 (66.2°F) 53.6°F(12°C)
17 (62.6°F) 50°F(10°C)
E DC_FAN_SSLOW_SPD_ADD
SPD_A
ADD A DC_FAN_HI_SPD_ADD
Fig. 14 — Outdoor Fan Running Rules Fig. 17 — Outdoor Fan Running Rules
In the COOLING mode, the indoor fan runs all the time and the Indoor Fan Running Rules
speed can be selected as high, medium, low and auto. The indoor fan
is controlled as shown in Fig. 15. When the compressor is on, the indoor fan can be set to high/med/low/
auto. And the anti-cold wind function has the priority. The indoor fan
is controlled as shown in Fig. 18.
Setting Actual
T1-Td °F (°C)
Fan Speed Fan Speed
Setting Fan Actual Fan
4.5(40.1) H+(H+=H+G) Speed
T1-Td+34.7°F(1.5°C)
Speed
A H(=H)
H 3.0(37.4) -3°F(-1.5°C) H-(H-=H-G)
B
1.5(34.7) H-(H-=H-G) H -6°F(-3.0°C)
C -10°F(-4.5°C)
H(=H)
H+(H+=H+G)
M+(M+=M+Z)
4.5(40.1)
D M(M=M) -3°F(-1.5°C) M-(M-=M-Z)
M 3.0(37.4) M
E -6°F(-3.0°C)
M(M=M)
1.5(34.7) M-(M-=M-Z) -10°F(-4.5°C)
F M+(M+=M+Z)
L+(L+=L+D) -3°F(-1.5°C)
4.5(40.1) L-(L-=L-D)
G L(L=L) L -6°F(-3.0°C)
L 3.0(37.4) L(L=L)
H -10°F(-4.5°C)
1.5(34.7) L-(L-=L-D) L+(L+=L+D)
I
T1-Td
T1-Td+3°F(1.5°C)
6.0°C(13°F) H 0°F(0.0°C) L
5.0°C(11.0°F) a (H-L)*0.75+L -2°F(-1°C) (H+-L)*0.2+L
DRYING Mode
DRYING mode works the same as COOLING mode in BREEZE
speed. All protections are active and the same as that in the
COOLING mode.
Auto-Restart Function
The indoor unit is equipped with an auto-restart function, which is
carried out through an auto-restart module. In case of a sudden power
failure, the module memorizes the setting conditions before the power
failure. The unit resumes the previous operation setting (not including
sleep function) automatically after 3 minutes when power returns.
The display value is between 13~129 degree. If the temp. is lower than 13 degrees, the digital display tube displays “13”.
If the temp. is higher than 99 degrees, the digital display tube displays a single digit and a ten digit. (For example, if the
09 Compressor discharge temp.(T5) digital display tube displays “0.5”, it means the compressor discharge temp. is 105 degrees. If the digital display tube
displays “1.6”, it means the compressor discharge temp. is 116 degrees).
10 AD value of current
The display value is a hex number.
11 AD value of voltage
12 Indoor unit running mode code Off:0, Fan only 1,Cooling:2, Heating:3
13 Outdoor unit running mode code Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
Actual data/4.
14 EXV open angle If the value is higher than 99, the digital display tube displays a single digit and a ten digit.
For example, if the digital display tube displays “2.0”,it means the EXV open angle is 120×4=480p.).
Bit7 Frequency limit caused by IGBT radiator
Bit6 Frequency limit caused by PFC
Bit5 Frequency limit caused by T4
The display value is a hex number. For ex., the
Bit4 Frequency limit caused by T2 digital display tube displays 2A, then Bit5=1,
15 Frequency limit symbol Bit3=1, Bit1=1.
Bit3 Frequency limit caused by T3 It represents the frequency limit caused by T4,
T3 and current.
Bit2 Frequency limit caused by T5
Bit1 Frequency limit caused by current
Bit0 Frequency limit caused by voltage
16 DC fan motor speed
The display value is between 30~120 degrees. If the temp. is lower than 30 degrees, the digital display tube displays
“30”. If the temp. is higher than 99 degrees, the digital display tube displays a single digit and a ten digit. (For example, if
17 IGBT radiator temp. the digital display tube displays “0.5”, it means the IGBT radiator temp. is 105 degrees. If the digital display tube displays
“1.6”, it means the IGBT radiator temp. is 116 degrees).
18 Indoor unit number The indoor unit can communicate well with the outdoor unit. General:1, Twins:2
If the temp. is lower than 0 degree, the digital display tube displays “0”.If the temp. is higher than 70 degrees, the digital
19 Evaporator pipe temp. T2 of1# indoor unit display tube displays “70”. If the indoor unit is not connected, the digital display tube displays: “--”.
20 Evaporator pipe temp. T2 of 2# indoor unit
21 Evaporator pipe temp. T2 of 3# indoor unit
Actual data*HP*10
If the capacity demand code is higher than 99, the digital display tube displays a single digit and a tens digit. (For
22 1# Indoor unit capacity demand code example, the digital display tube displays “5.0”,it means the capacity demand is 15. If the digital display tube displays
“60”,it means the capacity demand is 6.0). If the indoor unit is not connected, the digital display tube displays: “--”.
23 2# Indoor unit capacity demand code
24 3# Indoor unit capacity demand code
25 Room temp. T1 of 1# indoor unit
If the temp. is lower than 0 degree, the digital display tube displays “0”.If the temp. is higher than 70 degrees, the digital
26 Room temp. T1 of 2# indoor unit display tube displays “70”. If the indoor unit is not connected, the digital display tube displays: “--”.
27 Average room temp. T1
28 Reason of stop
29 Evaporator pipe temp. T2B of 1# indoor unit If the temp. is lower than 0 degree, the digital display tube displays “0”.If the temp. is higher than 70 degrees, the digital
30 Evaporator pipe temp. T2B of 2# indoor unit display tube displays “70”. If the indoor unit is not connected, the digital display tube displays: “--”.
Troubleshooting
Power OFF.
Wait 2 minutes then power ON the unit.
Yes
EEPROM: A read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. For the location of the EEPROM
chip, refer to the Fig. 22.
Troubleshooting
Yes
Yes
Yes
Check the connecƟons and wires No Correct the connecƟons or replace the wires.
Yes
Troubleshooting
E1 displayed
ŽŵŵƵŶŝĐĂƟŽŶŵĂůĨƵŶĐƟŽŶďĞƚǁĞĞŶƚŚĞ
indoor and outdoor units
Power OFF.
Wait 2 minutes then restart the unit.
ŽĞƐƚŚĞƉƌŽďůĞŵƐƟůůĞdžŝƐƚ͍
Yes
No
/ƐƚŚĞƐŝŐŶĂůǁŝƌĞĂƐŚŝĞůĚĐĂďůĞ
ĂŶĚŝƐƚŚĞƐŚŝĞůĚĐĂďůĞĂĞĂƌƚŚŝŶŐ͍ No ĚŽƉƚĂƐŚŝĞůĚĐĂďůĞͬƐŚŝĞůĚĐĂďůĞĞĂƌƚŚŝŶŐ͘
Yes
No
Yes
No
Troubleshooting
YES
Does it turn easily? NO Find the cause of the problem and resolve.
YES
YES
It is within
normal parameters? NO Replace the indoor/outdoor PCB
YES
Troubleshooting
Yes
Yes
Fig. 26 — Test
Troubleshooting
Power OFF.
Wait 2 minutes then restart the unit.
ŽĞƐƚŚĞƉƌŽďůĞŵƐƟůůĞdžŝƐƚ͍
Yes
Check the T2
sensor.
Is cool air blowing from the indoor air outlet? Yes
Is it securely
ĂƩĂĐŚĞĚ͍
No Yes
No Yes
Repair the leak and recharge the refrigerant.
Check the system for blockages and
ŝĨĂŶLJĞdžŝƐƚ͕ĐůĞĂƌƚŚĞŵ͘
Troubleshooting
No
Yes
Yes
ŚĞĐŬƚŚĞĐŽŵƉƌĞƐƐŽƌƌĞƐŝƐƚĂŶĐĞǀĂůƵĞƐ͘ ZĞƉůĂĐĞƚŚĞĐŽŵƉƌĞƐƐŽƌ͘
No
ƌĞƚŚĞLJǁŝƚŚŝŶĂĐĐĞƉƚĂďůĞƉĂƌĂŵĞƚĞƌƐ͍
Yes
ZĞƉůĂĐĞƚŚĞŽƵƚĚŽŽƌŵĂŝŶW͘
Fig. 28 — P-V
Fig. 30 — P-N
Troubleshooting
ŚĞĐŬƚŚĞƉŽǁĞƌƐƵƉƉůLJ͘
/ƐŝƚŝŶǁŽƌŬŝŶŐŽƌĚĞƌ͍ EŽ dƵƌŶŽīƚŚĞƵŶŝƚ͘
zĞƐ
ŚĞĐŬƚŚĞĐŽŶŶĞĐƟŽŶƐĂŶĚǁŝƌĞƐ͘
ƌĞƚŚĞLJŝŶǁŽƌŬŝŶŐŽƌĚĞƌ͍ EŽ ŶƐƵƌĞƚŚĞƉƌŽƉĞƌĐŽŶŶĞĐƟŽŶƐ
ŽƌƌĞƉůĂĐĞƚŚĞǁŝƌĞƐ͘
YeƐ
dƵƌŶƉŽǁĞƌŽŶĂŶĚǁŚŝůĞƚŚĞ
ƵŶŝƚŝƐŝŶƐƚĂŶĚďLJ͕ĐŚĞĐŬŝĨƚŚĞǀŽůƚĂŐĞŝƐ
ďĞƚǁĞĞŶWĂŶĚEŝƐĂƚϯϭϬs͕ϯϰϬsŽƌϯϴϬs͍ ZĞƉůĂĐĞƚŚĞ/WDďŽĂƌĚ͘
EŽ
EĞdžƚ͕ƐƚĂƌƚƚŚĞƵŶŝƚĂŶĚŵĞĂƐƵƌĞƚŚĞ
ǀŽůƚĂŐĞďĞƚǁĞĞŶWĂŶĚE͘
/ƐŝƚďĞƚǁĞĞŶϮϮϬsΕϰϬϬs͍
zĞƐ
ŚĞĐŬƚŚĞƌĞĂĐƚŽƌ͘ ZĞƉůĂĐĞƚŚĞŽƵƚĚŽŽƌŵĂŝŶW͘
EŽ
/ƐŝƚŝŶǁŽƌŬŝŶŐŽƌĚĞƌ͍
zĞƐ
ZĞƉůĂĐĞƚŚĞƌĞĂĐƚŽƌ͘
Fig. 31 — Test
Troubleshooting
Check the indoor and outdoor unit’s Clear up the air inlet and outlet or the heat
Yes
ĂŝƌŇŽǁƐLJƐƚĞŵƐ͘ exchanger of the indoor and outdoor units.
Does a problem exist?
No
Power OFF.
Wait 10 minutes and re-start the unit.
Yes
Yes Yes
Yes
Troubleshooting
No
Yes
Yes
Yes
Replace the
outdoor main PCB.
Troubleshooting
ŚĞĐŬƚŚĞĐŽŶŶĞĐƟŽŶďĞƚǁĞĞŶƚŚĞ
temperature sensor and the PCB. No ŶƐƵƌĞĂƉƌŽƉĞƌĐŽŶŶĞĐƟŽŶ͘
/ƐŝƚƉƌŽƉĞƌůLJǁŝƌĞĚ͍
Yes
Yes
Troubleshooting
J0 displayed
Evaporator high
temperature protecƟon
Is the connecƟon
between T2 and the
Is the compressor PCB in working
No No Correct the connecƟon.
operaƟng? order?
Has T2 and T2B been
Yes
reversed?
Is the outdoor
Yes
ambient temp. higher Yes Stop the unit.
than 86°F (30°C)?
No
Is the resistance of
Replace the
T2 normal according No
Is the air outlet temp. sensor.
Yes Clean the air outlet. to Appendix 1?
blocked?
No
Refer to the Fan Speed
Out of Control
Is the indoor fan
No malfuncƟon soluƟon.
running normally?
Find the cause and
resolve the problem.
Yes
No
Replace the
Yes
indoor main PCB.
Troubleshooting
J1 displayed
High temperature
condenser protecƟon
Is the connecƟon
Is the compressor between the
temperature higher No temperature sensor No Correct the connecƟon.
than 149°F (65°C)? and the PCB in
working order?
Yes
Is the outdoor
Yes
ambient temp. higher Yes Stop the unit.
than 122°F (50°C)?
No Is the resistance of
the condenser temp.
Replace the
Is the outdoor unit Ensure the outdoor sensor normal No
temp. sensor.
venƟůaƟon funcƟoning No unit vent is according to
properly? funcƟoning properly? Appendix 1?
Yes
Refer to the Fan Speed
Out of Control
Is the outdoor fan
No malfuncƟon soluƟon.
running normally?
Find the cause and
resolve the problem.
Yes
No
Replace the
outdoor main board.
Yes
Has the problem
been solved?
No
No
Troubleshooting
J2 displayed
Temperature protecƟon
of condenser discharge
Is the compressor
Is the refrigerant Stop the leak and
temperature higher Yes Yes
leaking? add refrigerant.
than 239° F (115° C)?
No No
Yes
Measure the
compressor discharge
temp. sensor’s resistance value.
Replace the compressor
Is the value abnormal? No
discharge temp. sensor.
Refer to Appendix 2.
Does the problem
sƟůů exist?
Yes
Replace the
outdoor main PCB.
Does the problem sƟůů
exist?
No
Replace the
high pressure valve assembly.
Troubleshooting
J3 displayed
Yes No
Yes
No
Yes
Troubleshooting
J4 displayed
CommunicaƟon error
between the outdoor
main chip and the
compressor drive board.
No
No
Yes
Yes
No
Replace the
compressor drive board..
Yes
Is the system running
normally?
No
No
Troubleshooting
J5 displayed
Yes
Yes
No
Yes
Yes
Is the
Yes Clean the heat exchanger.
heat exchanger dirty?
No
Replace the
outdoor main
board.
Is the problem
resolved?
No
Troubleshooting
J6 displayed
Yes
Yes
No
Yes
Yes
Replace the
outdoor main
board.
Is the problem
resolved?
No
Troubleshooting
J8 displayed
Yes
Measure whether
Verify the wires are well Reconnect
the outdoor terminal No
connected. well.
voltage is normal.
Yes
Measure whether
Ensure L and N wiring is Reconnect
the voltage between L No
correct. well.
and N is normal.
Yes
Yes
Yes
No
Yes
Check the reactor Reconnect
or inductance wiring . No
the wiring.
Yes
Temperature sensors:
• Room temp. (T1) sensor,
• Indoor coil temp. (T2) sensor,
• Outdoor coil temp. (T3) sensor,
• Outdoor ambient temp. (T4) sensor,
• Compressor discharge temp. (T5) sensor.
Measure the resistance value of each winding by using the multi-meter.
Blue - Red
Blue - Black 0.65Ω 0.38Ω
Red - Blue
NORMAL
DIGITAL TESTER RESISTANCE DIGITAL TESTER NORMAL RESISTANCE VALUE
VALUE
(+)Red (-)Black (+)Red (-)Black
N U
∞ ∞
U V
P (Several MΩ) N (Several MΩ)
V W
W (+)Red
Pressure (bar)
12.0
10.0
8.0
6.0 70
75
4.0 80
2.0
0.0
Outdoor temp.
75 (23.89) 85 (29.44) 95 105 115
(35) (40.56) (46.11)
Pressure (bar)
40.0
35.0
30.0
25.0
55
20.0
65
15.0
75
10.0
5.0
Screws of big
handle
\ (3 screws)
4
3) Remove the front panel
screws (11 screws).
1) Use procedure 1 to
remove the panel plate.
compressor
6
7
Right-rear panel
screws
1) Complete steps 5 - 6 in
section 1 and section 2.
CN2(yellow)
CN1(red)
CN6(black)
CN3(yellow)
U V W(black)
CN9(10p,white)
Connectors:
CN8: Discharge temperature sensor
CN1/CN3
(2p,white)
CN12 Heatsink temperature
sensor(2p,red)
CN9:T3/T4 temperature sensor
(2p/2p,white)
CN15: Electronic expansive valve
(6p,red)
CN10: High and low pressure switch
(2p/2p, white)
CN17/CN18
Wires: CN19/CN20
CN17/CN18: 4-way valve (blue-blue) CN24/CN25
CN19/CN20: connected to crankcase
heating cable. (black-red)
CN24/CN25: Electric heater of
chassis (orange-orange)
CN1:L-IN (red or white)
CN3:N-IN (black)
1) Complete steps 5 - 6 in
section and section 2.
Coil
2) Extract the refrigerant gas.
Welded parts
3) Remove the electrical parts
in section 3.
Copyright 2019 CAC/BDP D 3300 Riverwood Parkway Atlanta GA, 30339 Edition Date: 07/19 Catalog No. 38MBR-03SM
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces: 38MBR-02SM